F
F
F
F
F F F
F
F
F
F
F
F
F
F
F
F
F
F
FF
F
F
OCCUPANT CALCULATION (Table 1004.1.2)
AIRCRAFT HANGAR (500 SF) 43,200 = 86 OCCUPANTS
INDUSTRIAL AREA (100SF) 12,675 = 126 OCCUPANTS
BUSINESS (100SF) 32,680 = 326 OCCUPANTS
TOTAL OCCUPANT LOAD = 538 OCCUPANTS
BUILDING INFORMATION & CODE REVIEW
APPLICABLE CODES:
UFC 4-211-01N, UFC 3-600-01, UFC 1-200-01
ENGINEERING TECHNICAL LETTER (ETL) 02-15
2012 NFPA 101 LIFE SAFETY CODE
2011 NFPA STANDARD ON AIR CRAFT HANGARS
2012 INTERNATIONAL BUILDING CODE (IBC)
OCCUPANCY TYPE: S-1 (IBC311.2)
CONSTRUCTION CLASSIFICATION: II-B
FULLY SPRINKLERED
HEIGHT AND AREA (TABLE 503 & SECTION 504):
NUMBER OF FLOORS ALLOWED 11 FLOORS
NUMBER OF FLOORS AS DESIGNED 1 FLOOR
HEIGHT ALLOWED Unlimited (503.1.1)
HEIGHT AS DESIGNED 86'-0"
AREA ALLOWED Unlimited (ETL 02-15)
AREA AS DESIGNED 90,342 SF
EXIT TRAVEL DISTANCE (NFPA 101: 40.6.1.2) 150' (Exterior Walls)
FIRE EXTINGUISHERS:
FIRE CLASS TYPE A
TRAVEL DISTANCE < 75 FT
CODE COMPLIANCE:
IBC 2009 - SECTION 412.4.6: FIRE SUPPRESSION
"AIRCRAFT HANGARS WITH A DOOR HEIGHT GREATER THAN 28 FEET SHALL BE PROVIDED
WITH
FIRE SUPPRESSION FOR A GROUP I HANGAR REGARDLESS OF MAXIMUM FIRE AREAS."
* HANGAR DOOR (AS DESIGNED) > 28 FEET = GROUP I HANGAR.
EXISTING DRAFT CURTAIN
EXISTING DOOR HEADER
PROVIDES REQUIREMENT
FOR DRAFT CURTAIN
NEW DRAFT CURTAIN
INDUSTRIAL
OCCUPANCY
BUSSINESS
OCCUPANCY
HANGAR (S-1)
OCCUPANCY
EX
IS
TI
NG
H
AN
GA
R
NE
W
T
AI
LD
OC
K
EX
TE
NS
IO
N
EXISTING HANGAR
NEW TAILDOCK
EXTENSION
1 HOUR PARTITION WALL
BETWEEN HANGAR AND
OFFICE AREA
1 HOUR PARTITION WALL
BETWEEN HANGAR AND
SHOP AREA
LIFE SAFETY LEGEND
DRAFT CURTAIN
1 HOUR WALL
FIRE EXTINGUISHER CABINET FEC
EXIT LIGHT
FE
C
FE
C
FE
C
FEC
FE
C
FE
C
FE
C
FE
C
FE
C
FEC FEC
FEC
FEC
FEC
FE
C
FEC
FE
C
FEC
FEC
FEC
FE
C
FE
C
FE
C FE
C
FEC
FE
C
FEC
MECHANICAL
OCCUPANCY
BUSINESS
OCCUPANCY
PEASE AIR BASE
NEW HAMPSHIRE
NATIONAL GUARD Project
Client
Drawing
NEW HAMPSHIRE AIR NATIONAL GUARD
REVISIONS
Description
Drawn by
Designed by
Scale
Date
Project No.
Approved by
Checked by No. Date
SheetAS SHOWN
Stamp
B-2 SUBMITTAL1 08/15/14
B-3 SUBMITTAL2 11/21/14
B-3 RESUBMITTAL3 12/31/14
ADDENDUM 24 02/25/15
LS-101
LIFE SAFETY PLAN
31 DECEMBER 2014
G UECKER
E MOREHOUSE
R WENTE
Q REMY
SZCQ139904
KC-46A ADAL MAINTENANCE HANGAR, BUILDING 254
PEASE AIR NATIONAL GUARD BASE, NEW HAMPSHIRE
SCALE: 1" = 20'-0"
LIFE SAFETY PLAN1
SCALE: 1" = 20'-0"
BOILER ROOM2
SCALE: 1" = 20'-0"
EXISTING NW MEZZANINE3
File details come from the government source that posted it. Updated .