Amendment 8 - ATT 2 - 518-22-700 Summary Log_ADD4_20260413.pdf

PDF 204 KB Posted

Attached to
Y1DA--518-22-700 EHRM Infrastructure Upgrades Construction Bedford VAMC
Solicitation number
36C77626R0003
Issued by

About this file

This is an Addendum to construction contract documents for Project 518-22-700 Bedford EHRM, issued by Triple C – The A&E Group on April 13, 2026. The addendum clarifies the electrical metering scope in response to six technical questions posed during the bidding process.

The key clarifications address metering requirements, specifications, and system integration. All Uninterruptible Power Supplies (UPS) and Power Distribution Units (PDU) provided under the contract must include monitoring and metering capabilities. The new Main Control Room (MCR) Main Distribution Panel (MDP) requires metering for four circuits: Control Room (CR), Load Shedding (LS), Equipment (EQ), and Network Protection (NP). Meter specifications are referenced in sections 23 09 23, 25 10 10 Part 2.6, 26 26 00, 26 33 53.10, and 27 11 26. The head-end server shall be located in the MCR with local LAN connections at each Transformer Room (TR) and the MCR. Data collection requirements are detailed in Specification 25 10 10 Part 2.6.D, 26 26 00, 26 33 53.10, and 27 11 26. The addendum also includes a complete revised specification book incorporating previous addenda (1, 2, 3) with numerous specification section changes, primarily updates to align with Technical Information Letter (TIL) 04-2026, plus removal of steam and water metering requirements from Section 25 10 10. No drawing changes were made.

View the file

Other files

File Type Posted
36C77626R0003 0011.pdf PDF
36C77626R0003 0010.pdf PDF
36C77626R0003 0009.pdf PDF
Amendment 9 - ATT 1 - RFI Responses updated 041426.pdf PDF
Amendment 8 - ATT 3 - 518-22-700.Bedford.MA.EHRM.Specs.IFC.20260413.pdf PDF
Amendment 8 - ATT 1 - RFI Responses updated 041326.pdf PDF
36C77626R0003 0008.pdf PDF
Amendment 7 -ATT 2 - 25 10 10 - Advanced Utility Metering System.Add3.20260408.pdf PDF
Amendment 7 - ATT 1 - 518-22-700.Summary Log_ADD3.20260408.pdf PDF
36C77626R0003 0007.pdf PDF
36C77626R0003 0006.pdf PDF
Amendment 6 - ATT 1 - RFI Responses updated 033126.pdf PDF
Amend 5 - ATT 9 -518-22-700.Bedford.EHRM.IFC.Add1.B04.20260225.pdf PDF
Amend 5 - ATT 26 -518-22-700.Bedford.EHRM.IFC.Add1.B61.2060225.pdf PDF
Amend 5 - ATT 6 -518-22-700.Bedford.EHRM.IFC.Add1.B01.20260225.pdf PDF
Amend 5 - ATT 24-518-22-700.Bedford.EHRM.IFC.Add1.B22.2060225.pdf PDF
Amend 5 - ATT 2 - Inspection and Lead Paint Screening Report Final.pdf PDF
Amend 5 - ATT 28-518-22-700.Bedford.EHRM.IFC.Add1.B70.2060225.pdf PDF
Amend 5 - ATT 14-518-22-700.Bedford.EHRM.IFC.Add1.B09.20260225.pdf PDF
Amend 5 - ATT 3 - 04 72 00 - Cast Stone Spec.pdf PDF
Amend 5 - ATT 16-518-22-700.Bedford.EHRM.IFC.Add1.B13.20260225.pdf PDF
Amend 5 - ATT 23-518-22-700.Bedf.EHRM.IFC.Add1.B21_19.2060225.pdf PDF
Amend 5 - ATT 22-518-22-700.Bedford.EHRM.IFC.Add1.B20.2060225.pdf PDF
Amend 5 - ATT 18-518-22-700.Bedford.EHRM.IFC.Add1.B15.20260225.pdf PDF
Amend 5 - ATT 29-518-22-700.Bedford.EHRM.IFC.Add1.B78.2060225.pdf PDF
Amend 5 - ATT 8 -518-22-700.Bedford.EHRM.IFC.Add1.B03.20260225.pdf PDF
36C77626R0003 0005.pdf PDF
Amend 5 - ATT 19-518-22-700.Bedford.EHRM.IFC.Add1.B16.2060225.pdf PDF
Amend 5 - ATT 20-518-22-700.Bedford.EHRM.IFC.Add1.B17.20260225.pdf PDF
Amend 5 - ATT 17-518-22-700.Bedford.EHRM.IFC.Add1.B14.20260225.pdf PDF
Amend 5 - ATT 11-518-22-700.Bedford.EHRM.IFC.Add1.B06.20260225.pdf PDF
Amend 5 - ATT 1 - 518-22-700.Summary Log_ADD1.20260225.pdf PDF
Amend 5 - ATT 31-518-22-700.Bedford.EHRM.IFC.Add1.B81.2060225.pdf PDF
Amend 5 - ATT 15-518-22-700.Bedford.EHRM.IFC.Add1.B10.20260225.pdf PDF
Amend 5 - ATT 27-518-22-700.Bedford.EHRM.IFC.Add1.B62.20260225.pdf PDF
Amend 5 - ATT 10-518-22-700.Bedford.EHRM.IFC.Add1.B05.20260225.pdf PDF
Amend 5 - ATT 21-518-22-700.Bedford.EHRM.IFC.Add1.B18.20260225.pdf PDF
Amend 5 - ATT 7 -518-22-700.Bedford.EHRM.IFC.Add1.B02.20260225.pdf PDF
Amend 5 - ATT 13-518-22-700.Bedford.EHRM.IFC.Add1.B08.20260225.pdf PDF
Amend 5 - ATT 4 - 08 87 33 - Decorative Film.pdf PDF
Amend 5 - ATT 25 -518-22-700.Bedford.EHRM.IFC.Add1.B33.2060225.pdf PDF
Amend 5 - ATT 35-518-22-700.Bedf.EHRM.IFC.Add1.SITE.20260225.pdf PDF
Amend 5 - ATT 32-518-22-700.Bedford.EHRM.IFC.Add1.B82.2060225.pdf PDF
Amend 5 - ATT 30-518-22-700.Bedford.EHRM.IFC.Add1.B80.2060225.pdf PDF
Amend 5 - ATT 12-518-22-700.Bedford.EHRM.IFC.Add1.B07.20260225.pdf PDF
Amend 5 - ATT 33-518-22-700.Bedford.EHRM.IFC.Add1.BCH.2060225.pdf PDF
Amend 5 - ATT 34-518-22-700.Bedford.EHRM.IFC.Add1.MCR.2060225.pdf PDF
Amend 5 - ATT 5 - 34 71 13 PASSIVE VEHICLE BARRIERS.pdf PDF
Amendment 4 - ATT 1 - RFI Responses updated 032626.pdf PDF
S06 - Amendment 0003 - ATT 1 - RFI Responses_Bedford.pdf PDF
Show 40 more

Latest 50 of 105 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

TRIPLE C – THE A&E GROUP

OUR REASONABLE SERVICE - TO PROVIDE YOU WITH EXEMPLARY SERVICE

410 Grand Avenue, Suite 201C � Laramie, Wyoming 82070 � Telephone: (307) 460-2054 � Fax: (307) 460-2053

ADDENDUM-04

Project: 518-22-700 Bedford EHRM

Date: 04/13/2026

Summary of Clarifications

Triple C has revised the final construction drawing documents for project 518-22-700, per request of the VA. See the following responses to Technical Questions regarding electrical metering scope:

1. “Where would we find the number of meters required for installation.”

1. All UPS and PDU provided on this contract shall be monitored/metered.

2. New MCR MDP shall be metered (CR, LS, EQ and NP)

2. “Please provide the specification on the selected meters.”

1. See Specifications 23 09 23, 25 10 10 - Part 2.6, 26 26 00, 26 33 53.10, and 27 11 26.

2. Added Specification 26 33 53.10 to Addendum 4

3. “Please provide the locations of said meters.”

1. See response to number 1, clarified in Addendum 4

4. “Please provide the location of the central equipment.”

1. Head-end server shall be located in MCR

5. “Please provide the connection location to the VA’s LAN.”

1. Connect locally at each TR and the MCR.

6. “Please provide the required data each meter is to collect.”

1. See Specification 25 10 10 – Part 2.6.D, 26 26 00, 26 33 53.10, and 27 11 26

CVE Verified Service-Disabled Veteran-Owned Small Business

TRIPLE C – THE A&E GROUP

OUR REASONABLE SERVICE - TO PROVIDE YOU WITH EXEMPLARY SERVICE

410 Grand Avenue, Suite 201C � Laramie, Wyoming 82070 � Telephone: (307) 460-2054 � Fax: (307) 460-2053

Specifications:

A new complete specification book has been printed combining previous revisions from Addenda 1, 2, 3 and the following changes:

SECTION DESCRIPTION OF/REASON FOR CHANGE

25 10 10 Removed steam and water metering requirements.

26 33 53.10 Added new specification.

27 05 00 Added new specification published on the TIL 04-2026.

27 05 26 Replaced specification with new version published on the TIL 04-2026.

27 05 33 Replaced specification with new version published on the TIL 04-2026.

27 05 36 Replaced specification with new version published on the TIL 04-2026.

27 05 53 Replaced specification with new version published on the TIL 04-2026.

27 10 00 Replaced specification with new version published on the TIL 04-2026.

27 10 00.1 Removed specification.

27 11 00 Removed specification.

27 11 16 Replaced specification with new version published on the TIL 04-2026.

27 11 19 Replaced specification with new version published on the TIL 04-2026.

27 11 26 Replaced specification with new version published on the TIL 04-2026.

27 13 13 Replaced specification with new version published on the TIL 04-2026.

27 13 13.13 Replaced specification with new version published on the TIL 04-2026.

27 13 23 Replaced specification with new version published on the TIL 04-2026.

27 15 13 Replaced specification with new version published on the TIL 04-2026.

27 16 19 Replaced specification with new version published on the TIL 04-2026.

Drawing Changes: NONE

End of ASI