Amend 5 - ATT 20-518-22-700.Bedford.EHRM.IFC.Add1.B17.20260225.pdf

PDF 5 MB Posted

Attached to
Y1DA--518-22-700 EHRM Infrastructure Upgrades Construction Bedford VAMC
Solicitation number
36C77626R0003
Issued by

About this file

This document is a set of architectural construction drawings for the EHRM Infrastructure Upgrades project at the Edith Nourse Memorial Veterans Hospital in Bedford, Massachusetts. The project involves the renovation of Building 17 (project number 518-22-700), with primary focus on converting Room 118 into a telecommunications room and implementing associated infrastructure improvements across multiple building levels.

The construction scope includes creating a new 157 square-foot telecommunications room with 1-hour fire and smoke-rated partitions compliant with VA Physical Security Standards and campus standards. Key architectural elements include new hollow metal door frames (3'-0" x 8'-0" with 45-minute fire rating), fire-treated plywood furring walls to enclose windows, and partition types ranging from non-rated to 4-hour fire barriers. Interior finishes specify sealed concrete with static dissipative coating (C-1/SDC) for flooring, Benjamin Moore paint colors (Manchester Tan HC-81 for walls, White Down OC-131 for doors/trim), and Johnsonite beige resilient base. The telecommunications infrastructure requires new Category 6A cabling, cable tray systems, network cameras with PoE+, patch panels, and vertical wire management. Additional work includes demolition of existing conditions, window treatments with 3M Fasara film, ADA-compliant signage with Braille, and comprehensive fire-stopping and sealing of all penetrations. The drawings were issued for construction on June 4, 2025, with Revision 1 dated February 25, 2026, prepared by architect TRIPLE C - The A/E Group under the direction of Mat Perkins and K. McDermott. The facility is fully sprinklered, and the contractor is responsible for all costs associated with moving, storing, and returning furnishings and equipment.

View the file

Other files

File Type Posted
36C77626R0003 0011.pdf PDF
36C77626R0003 0010.pdf PDF
36C77626R0003 0009.pdf PDF
Amendment 9 - ATT 1 - RFI Responses updated 041426.pdf PDF
Amendment 8 - ATT 2 - 518-22-700 Summary Log_ADD4_20260413.pdf PDF
Amendment 8 - ATT 3 - 518-22-700.Bedford.MA.EHRM.Specs.IFC.20260413.pdf PDF
Amendment 8 - ATT 1 - RFI Responses updated 041326.pdf PDF
36C77626R0003 0008.pdf PDF
Amendment 7 -ATT 2 - 25 10 10 - Advanced Utility Metering System.Add3.20260408.pdf PDF
Amendment 7 - ATT 1 - 518-22-700.Summary Log_ADD3.20260408.pdf PDF
36C77626R0003 0007.pdf PDF
36C77626R0003 0006.pdf PDF
Amendment 6 - ATT 1 - RFI Responses updated 033126.pdf PDF
Amend 5 - ATT 9 -518-22-700.Bedford.EHRM.IFC.Add1.B04.20260225.pdf PDF
Amend 5 - ATT 26 -518-22-700.Bedford.EHRM.IFC.Add1.B61.2060225.pdf PDF
Amend 5 - ATT 6 -518-22-700.Bedford.EHRM.IFC.Add1.B01.20260225.pdf PDF
Amend 5 - ATT 24-518-22-700.Bedford.EHRM.IFC.Add1.B22.2060225.pdf PDF
Amend 5 - ATT 2 - Inspection and Lead Paint Screening Report Final.pdf PDF
Amend 5 - ATT 28-518-22-700.Bedford.EHRM.IFC.Add1.B70.2060225.pdf PDF
Amend 5 - ATT 14-518-22-700.Bedford.EHRM.IFC.Add1.B09.20260225.pdf PDF
Amend 5 - ATT 3 - 04 72 00 - Cast Stone Spec.pdf PDF
Amend 5 - ATT 16-518-22-700.Bedford.EHRM.IFC.Add1.B13.20260225.pdf PDF
Amend 5 - ATT 23-518-22-700.Bedf.EHRM.IFC.Add1.B21_19.2060225.pdf PDF
Amend 5 - ATT 22-518-22-700.Bedford.EHRM.IFC.Add1.B20.2060225.pdf PDF
Amend 5 - ATT 18-518-22-700.Bedford.EHRM.IFC.Add1.B15.20260225.pdf PDF
Amend 5 - ATT 29-518-22-700.Bedford.EHRM.IFC.Add1.B78.2060225.pdf PDF
Amend 5 - ATT 8 -518-22-700.Bedford.EHRM.IFC.Add1.B03.20260225.pdf PDF
36C77626R0003 0005.pdf PDF
Amend 5 - ATT 19-518-22-700.Bedford.EHRM.IFC.Add1.B16.2060225.pdf PDF
Amend 5 - ATT 17-518-22-700.Bedford.EHRM.IFC.Add1.B14.20260225.pdf PDF
Amend 5 - ATT 11-518-22-700.Bedford.EHRM.IFC.Add1.B06.20260225.pdf PDF
Amend 5 - ATT 1 - 518-22-700.Summary Log_ADD1.20260225.pdf PDF
Amend 5 - ATT 31-518-22-700.Bedford.EHRM.IFC.Add1.B81.2060225.pdf PDF
Amend 5 - ATT 15-518-22-700.Bedford.EHRM.IFC.Add1.B10.20260225.pdf PDF
Amend 5 - ATT 27-518-22-700.Bedford.EHRM.IFC.Add1.B62.20260225.pdf PDF
Amend 5 - ATT 10-518-22-700.Bedford.EHRM.IFC.Add1.B05.20260225.pdf PDF
Amend 5 - ATT 21-518-22-700.Bedford.EHRM.IFC.Add1.B18.20260225.pdf PDF
Amend 5 - ATT 7 -518-22-700.Bedford.EHRM.IFC.Add1.B02.20260225.pdf PDF
Amend 5 - ATT 13-518-22-700.Bedford.EHRM.IFC.Add1.B08.20260225.pdf PDF
Amend 5 - ATT 4 - 08 87 33 - Decorative Film.pdf PDF
Amend 5 - ATT 25 -518-22-700.Bedford.EHRM.IFC.Add1.B33.2060225.pdf PDF
Amend 5 - ATT 35-518-22-700.Bedf.EHRM.IFC.Add1.SITE.20260225.pdf PDF
Amend 5 - ATT 32-518-22-700.Bedford.EHRM.IFC.Add1.B82.2060225.pdf PDF
Amend 5 - ATT 30-518-22-700.Bedford.EHRM.IFC.Add1.B80.2060225.pdf PDF
Amend 5 - ATT 12-518-22-700.Bedford.EHRM.IFC.Add1.B07.20260225.pdf PDF
Amend 5 - ATT 33-518-22-700.Bedford.EHRM.IFC.Add1.BCH.2060225.pdf PDF
Amend 5 - ATT 34-518-22-700.Bedford.EHRM.IFC.Add1.MCR.2060225.pdf PDF
Amend 5 - ATT 5 - 34 71 13 PASSIVE VEHICLE BARRIERS.pdf PDF
Amendment 4 - ATT 1 - RFI Responses updated 032626.pdf PDF
S06 - Amendment 0003 - ATT 1 - RFI Responses_Bedford.pdf PDF
Show 40 more

Latest 50 of 105 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

UP

DN

UP

DN

SHEET SYMBOL LEGEND

KEYNOTES

GENERAL NOTES

EXISTING CONSTRUCTION TO REMAIN

EXISTING CONSTRUCTION TO BE DEMOLISHED

NEW CONSTRUCTION, WITH PARTITION TYPE

A

A. SEE GENERAL NOTES AND PLANS FOR TYPICAL GENERAL PROJECT

REQUIREMENTS AND PROJECT LOCATION DRAWINGS.

B. SEE INTERIOR FINISH DRAWINGS FOR ADDITIONAL FINISHES

INFORMATION.

C. SEE MECHANICAL AND ELECTRICAL DRAWINGS FOR ADDITIONAL

SYSTEMS INFORMATION.

D. NEW TELECOM ROOMS SHALL BE 1 HOUR FIRE AND SMOKE RATED

AND COMPLY WITH THE LATEST VA PHYSICAL SECURITY STANDARDS,

AND CAMPUS STANDARDS.

E. SEE TYPICAL WALL FRAMING DETAILS ON SHEET A-511.

F. SEE TYPICAL HEAD OF WALL DETAIL ON SHEET A-512.

G. SEE TYPICAL CEILING DETAILS ON SHEET A-531

H. DATE OF THIS DRAWING SET. CONTRACTOR SHALL FIELD VERIFY ALL

DIMENSIONS, CONDITIONS, AND SITE-SPECIFIC INFORMATION AT THE

TIME OF BIDDING.

I. CONTRACTOR IS RESPONSIBLE FOR ALL COSTS ASSOCIATED

WITH MOVING, STORING AND RETURNING FURNISHINGS AND

EQUIPMENT TO THE PROPOSED WORK AREA(S). ANY

DISASSEMBLY AND REASSEMBLY OF SYSTEMS FURNITURE IN THE

PROPOSED WORK AREAS IS THE RESPONSIBILITY OF THE

CONTRACTOR AND MUST FOLLOW THE MANUFACTURER'S

WARRANTY.

PARTITION RATING GRAPHICS:

4 HR FIRE BARRIER

3 HR FIRE BARRIER

2 HR FIRE & SMOKE BARRIER

2 HR FIRE BARRIER

2 HR FIRE BARRIER/SHAFT

1 HR FIRE & SMOKE BARRIER

1 HR FIRE BARRIER

1 HR FIRE BARRIER/SHAFT

SMOKE PARTITION (NON RATED)

NON RATED

PARTITION RATING GRAPHIC DESIGNATION: PRIORITY

1 HIGHEST

5 LOWEST

PARTITIONS REQUIRED TO BE SMOKE RESISTANT, FIRE

RESISTANT, OR BOTH FIRE AND SMOKE RESISTANT ARE SHOWN

GRAPHICALLY ON PLANS WITH HATCH PATTERNS.

1/2" 1/2"

VARIES

SEE PLAN

WALL - SEE PLAN

FOR TYPE

SEALANT - EA. SIDE

& ALL AROUND,

TYP.

HOLLOW METAL

FRAME

/2

V

A R

IE

S

S E

E P

L A

N

/2

UNO

4" 2"

ADJACENT WALL

WHERE OCCURS

SEALANT - EA SIDE &

ALL AROUND, TYP.

HOLLOW METAL FRAME

WITH BITUMINOUS

COATING AND SOLID

GROUT FILLED*

WALL - SEE PLAN

FOR TYPE

*IN SNOW-PRONE AREAS

D1

TYPICAL FRAME

H E

IG

H

T

2" WIDTH 2"

E1

FRAME TYPE ELEVATIONS DOOR TYPE ELEVATIONS

F

FLUSH

B

5 6

CORRIDOR

130130

OFFICE

149 SF

B

5 6

CORRIDOR

130130

TELECOM

ROOM

157 SF

H W

-S H

-3 F

E X

IS

T

V

IF

'-6

EXIST (VIF)

11'-0"

B

B

B

B J2

17_29A-401

B8

TELECOM

ROOM

118118

ACOUSTICAL OR RATED

FLEXIBLE SEALANT

FLOOR LINE

ADD ONE LAYER OF 5/8" GWB,

ONE-SIDE WITH APPROVED UL

SETTING COMPOUND BETWEEN

LAYERS AND FASTENED TO

WALL AS REQUIRED, AT

EXISTING GWB WALL

ASSEMBLIES

STRUCTURAL DECK

EXISTING METAL STUDS AND

BATT INSULATION TO REMAIN

A/C GRADE, 3/4" FIRE-TREATED

PLYWOOD TO 8'-0" ABOVE FINISHED

FLOOR, ADHERED TO CONCRETE AT

EXISTING CONCRETE WALL

ASSEMBLIES

BOTTOM OF PLYWOOD

TO BE AT 12" AFF

UL DESIGN V497

1-HOUR PARTITION RATED FROM BOTH SIDES

EXISTING GWB OR

CONCRETE WALL

ASSEMBLY, WHERE OCCURS

SIDE OF

EXISTING

ROOM OR

CORRIDOR TO

REMAIN

17_29A-512

E5

17_29A-512

B4

B

5 6

TELECOM

ROOM

118118

OFFICE

118118

LINE OF

STRUCTURE

LINE OF

STRUCTURE

09 29 00

SOUND ATTENUATION BATTS

(SAB), WHERE OCCURS

NOTE:

IF PARTITION TYPE IS USED IN A

CHASE WALL CONDITION, PROVIDE

CROSS BRACING GUSSETS AT 48"

O.C. MAX VERTICALLY. FABRICATED

FROM 6" MTL STUDS.

6”

09 29 00

5/8" GWB

09 29 00

SAB RETAINER STRAP

WHERE SAB OCCURS

CEILING

07 92 00

SEALANT

09 22 16

METAL STUDS

17_29A-512

B4 17_29A-512

E5

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

TRIPLE C - The A/E Group

100 Pearl Street, 14th Floor

Hartford, CT 06103

MAT PERKINS

(860)270-0753

A u to d e s k D o c s /3

C

R

.P ro je c t.

-2

-7

.E H

R M

.I U

.B e d fo rd

.M A

.R

/5

-2 -7

.B e d fo rd .E

H R

M .A

R C

H .B

R

.r v t

/2

/2

:4

:5

A

M

17_29A-401

ARCHITECTURAL ENLARGED VIEWS - FIRST

LEVEL

518-22-700

06/04/2025 M. Perkins K. McDermott

ISSUED FOR

CONSTRUCTION

EHRM INFRASTRUCTURE

UPGRADES

200 Springs Rd, Bedford, MA 01730

3" = 1'-0" D1

HOLLOW METAL HEAD DETAIL

3" = 1'-0" E1

HOLLOW METAL JAMB DETAIL

1/4" = 1'-0" F1

DOOR AND FRAME TYPES ELEVATIONS

1 REMOVE EXISTING FLOORING, ADHESIVES, AND WALL BASE

2 REMOVE EXISTING DOOR AND FRAME

3 NEW 45 MIN. FIRE RATED DOOR AND FRAME. SEE DOOR SCHEDULE

AND SPECIFICATIONS FOR ADDITIONAL INFORMATION. MODIFY DOOR

AS REQUIRED FOR NEW ACCESS CONTROL HARDWARE.

4 PROVIDE TEMPORARY DUST TIGHT BARRIER AROUND WORK AREA

DURING ACTIVITIES WHICH PRODUCE DUST

5 NEW FURRING WALL AT EXTERIOR WALL TO ENCLOSE WINDOW.

MAINTAIN 1/2" GAP BETWEEN EXISTING WALL INTERIOR FACE AND

NEW STUDS. MODIFY/ REMOVE INTERIOR WINDOW TRIM AS

REQUIRED. INSTALL WINDOW FILM AT ALL FURRED WINDOWS. SEE

17IN101 FOR MORE INFORMATION.

6 EXISTING WALL TO BECOME 1 HOUR FIRE AND SMOKE-RATED. PATCH

AND SEAL ALL PENETRATIONS AS NECESSARY.

7 DEMO WALL AND FRAMING AS SHOWN ON PLAN

8 REMOVE EXISTING CEILING AND LIGHTS. MODIFY AND/OR PROVIDE

ADDITIONAL SUPPORTS AS REQUIRED FOR EXISTING CEILING ITEMS

TO REMAIN.

9 TELECOM ROOM TO BE OPEN TO DECK.

10 POTENTIAL ABATEMENT AT FLOOR FOR FLOOR PENETRATIONS.

REFER TO COVER SHEET FOR KNOWN ACM ITEMS WITHIN THIS

BUILDING.

11 REMOVE EXISTING TRANSOM AND FRAME ABOVE DOOR

1/16" = 1'-0" F6

FIRST LEVEL REFERENCE PLAN

1/4" = 1'-0" D8

ARCHITECTURAL FLOOR PLAN - FIRST LEVEL

- RM 118 - DEMO

1/4" = 1'-0" B8

ARCHITECTURAL FLOOR PLAN - FIRST LEVEL

- RM 118 - NEW

DOOR AND FRAME SCHEDULE

IDENTIFICATION DIMENSIONS PANEL FRAME DETAIL FIRE

RATING

HARDWARE

NOTESLEVEL ROOM NO. ROOM NAME DOOR NO. W1 H T TYPE MATERIAL FINISH GLAZING UNDERCUT TYPE MATERIAL FINISH HEAD JAMB SILL GROUP ELECTRICAL

LEVEL 1 118 TELECOM ROOM 118 3' - 0" 8' - 0" 1 3/4" F HM P-2 NONE 3/8" 1 HM P-2 D1/ 17A-401 E1/ 17A-401 F1/ 17A-401 45 MIN HW-SH-3F SEE SPEC 1.

NOTE: FIRE RESISTANCE TEST FOR TWO HOUR RATED WALLS: UL

V438, UL U411

(TYPE B) TYPICAL PARTITION

MARK STUD WIDTH PRTN WIDTH DESIGN STC

B 2 1/2" 3/4" 45

1/4" = 1'-0" D6

ARCHITECTURAL REFLECTED CEILING PLAN -

FIRST LEVEL - RM 118 - DEMO

1/4" = 1'-0" B6

ARCHITECTURAL REFLECTED CEILING PLAN -

FIRST LEVEL - RM 118 - NEW

1. SEE SPECIFICATIONS 08 71 00 FOR DOOR HARDWARE REQUIREMENTS. COORDINATE WITH ELECTRICAL.

NOT TO SCALE

B4

EXISTING CONDITOINS RM 118

(TYPE J) NON-RATED PARTITION

MARK STUD WIDTH PRTN WIDTH DESIGN STC

J2 2 1/2" 3 1/8" -

Number Revisions: Date:

1 Revision 1 Date 1

02/25/2026

"FIRE-RATED WALLS"- ADDITIONAL NOTES:

1. CONDITIONS INDICATED TO SHOW DESIGN INTENT. THEY ARE NOT INTENDED TO BE PROPRIETARY. CONTRACTOR MAY EMPLOY SIMILAR A UL-APPROVED TOP-OF-WALL DESIGNS THAT ARE APPROPRIATE FOR CONDITIONS.

2. REFER TO SECTION 07 84 00 / FIRESTOPPING FOR ADDITIONAL REQUIREMENTS REGARDING HEAD-OF-WALL CONDITION FOR FIRE-RATED WALLS.

SLOTTED TOP

TRACK

STUD

DESIGN BASIS: UL-HW-D-0082

CONCRETE SLAB

DESIGN BASIS: UL-HW-D-0042

METAL DECK

(PERPENDICULAR TO FLUTES)

/8

DESIGN BASIS: UL-HW-D-0264

METAL DECK

(PARALLEL TO FLUTES)

1" 1" 2"x20 GA

STRAPS @ 16"

O.C.

DESIGN BASIS: UL-HW-D-0259

STEEL BEAM

20 GA Z-BARS

TO

ACCOMMODATE

SFRM

SPRAY-APPLIED

FIRE-RESISTIVE

MATERIAL

(SFRM)

SAB

1 OR 2 LAYERS OF GWB;

SEE WALL TYPE

FIRE STOP SEALANT

FIRE STOP JOINT

SPRAY

MINERAL WOOL

FORMING MATERIAL

/8

/8

FIRE STOP JOINT

SPRAY

SLOTTED TOP

TRACK

STUD

SAB

1 OR 2 LAYERS OF GWB;

SEE WALL TYPE

/8

MINERAL WOOL

FORMING MATERIAL

SLOTTED TOP

TRACK

STUD

CONCRETE SLAB METAL DECK

(PERPENDICULAR TO FLUTES)

/8

/8

METAL DECK

(PARALLEL TO FLUTES)

1" 1"

/8

SLOTTED TOP

TRACK

2"x20 GA

STRAPS @ 16"

O.C.

STEEL BEAM

/8

20 GA Z-BARS

TO

ACCOMMODATE

SFRM

SPRAY-APPLIED

FIRE-RESISTIVE

MATERIAL

(SFRM)

SAB

GWB

ACOUSTICAL SEALANT

CUT ONE LAYER GWB TO

FOLLOW PROFILE OF DECKING.

SEAL CONTINUOUSLY WITH

ACOUSTICAL SEALANT.

FILL FLUTE VOID W/

SAB

GWB SOUND AND

SMOKE CLOSURE

STRIP SECURE TO

STRUCTURE AND SEAL

WITH ACOUSTICAL

SEALANT

ACOUSTICAL

SEALANT (BOTH

SIDES)

STUD

SAB

GWB

ACOUSTICAL SEALANT

(BOTH SIDES)

"SMOKE PARTITIONS AND SOUND-CONTROL WALLS"- ADDITIONAL NOTES:

1. UPGRADE TO DETAIL "B4" WHERE WALL IS DESIGNATED WITH A FIRE-RESISTANCE RATING.

2. FILL VOIDS WITH SOUND ATTENUATION BATTS (SAB).

3. SOUND WALLS AND SMOKE PARTITIONS REQUIRE THAT AT LEAST ONE LAYER OF GWB BE CUT TO FOLLOW UNDULATING SURFACES OF SUPERSTRUCTURES INCLUDING BUT NOT LIMITED TO FLUTES METAL DECKING. JOINT GWB TO SUPERSTRUCTURE WITH A CONTINUOUS BEAD OF ACOUSTICAL SEALANT.

4. BUILDING CODE REQUIRES THAT "SMOKE PARTITIONS" BE SEALED TO STRUCTURE AS INDICATED TO SUCCESSFULLY "….LIMIT THE PASSAGE OF SMOKE….".

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

TRIPLE C - The A/E Group

100 Pearl Street, 14th Floor

Hartford, CT 06103

MAT PERKINS

(860)270-0753

A u to d e s k D o c s /3

C

R

.P ro je c t.

-2

-7

.E H

R M

.I U

.B e d fo rd

.M A

.R

/5

-2 -7

.B e d fo rd .E

H R

M .A

R C

H .B

R

.r v t

/2

/2

:4

:5

A

M

17_29A-512

ARCHITECTURAL PARTITION HEAD DETAILS 518-22-700

06/04/2025 M. Perkins K. McDermott

ISSUED FOR

CONSTRUCTION

EHRM INFRASTRUCTURE

UPGRADES

200 Springs Rd, Bedford, MA 01730

3" = 1'-0" B4

HEAD-OF-WALL CONDITIONS - STUD WALLS - FIRE RATED WALLS

3" = 1'-0" E5

HEAD-OF-WALL CONDITIONS - STUD WALLS - SMOKE PARTITIONS AND SOUND CONTROL WALLS

NOTE:

STANDARD DETAILS APPLY TO TYPICAL CONSTRUCTION

TYPES AND ASSEMBLIES. NOT ALL DETAILS MAY BE

USED. CONTRACTOR SHALL VERIFY ACTUAL CONDITIONS

ON-SITE.

Number Revisions: Date:

1 Revision 1 Date 1

SHEET SYMBOL LEGEND

EXISTING CONSTRUCTION TO REMAIN

EXISTING CONSTRUCTION TO BE DEMOLISHED

NEW CONSTRUCTION, WITH PARTITION TYPE

GENERAL INTERIOR NOTES

KEYNOTES

GENERAL FINISH NOTES:

1. REFER TO SPECIFICATIONS FOR ADDITIONAL MATERIAL AND

INSTALLATION REQUIREMENTS.

2. REFER TO THIS SHEET FOR FINISH LEGEND AND ROOM FINISH

SCHEDULE.

3. IF POSSIBLE PROVIDE MATERIALS FROM SAME PRODUCTION RUN

FOR CONSISTENCY.

SUBSTITUTION NOTES:

1. COLOR IS AN IMPORTANT PART OF THIS PROJECT. ANY COLOR

SUBSTITUTION WILL REQUIRE APPROVAL BY THE COR.

TRANSITION NOTES:

1. INSTALL TRANSITIONS AT ALL DISSIMILAR FLOOR MATERIALS.

2. FOR ALL FLOOR FINISH AND PATTERN TRANSITIONS THAT OCCUR AT

DOORWAYS, TRANSITION MATERIALS AT CENTERLINE OF DOOR

WHEN DOOR PANEL IS IN THE CLOSED POSITION.

SIGNAGE NOTES:

1. REFER TO THIS SHEET SERIES SHEETS FOR SIGNAGE INFORMATION,

REFER TO SPECIFICATIONS FOR ADDITIONAL SIGNAGE,

IDENTIFICATION AND SYSTEMS/EQUIPMENT LABELING

REQUIREMENTS.

PAINTING NOTES:

1. ALL ADHESIVES AND PAINT TO BE LOW VOC/ODOR.

2. UNLESS OTHERWISE INDICATED, DO NOT PAINT FACTORY-FINISHED

ITEMS OR INSTALLER FINISHED ITEMS.

3. COORDINATE APPLICATIONS OF PAINTS AND ADHESIVES WITH COR.

PROVIDE SEALED ENVIRONMENT DURING HVAC FLUSH OUT PERIOD

TO ENSURE ODORS DO NOT TRANSMIT TO ADJACENT SPACES.

CODE NOTES:

1. ALL INTERIOR FINISHES SHALL HAVE FLAME SPREAD IN COMPLIANCE

WITH IBC 2024 803.13 INTERIOR WALL AND CEILING FINISH

REQUIREMENTS BY OCCUPANCY

INSTALLATION NOTES:

1. PROVIDE BACKING FOR ALL WALL MOUNTED EQUIPMENT.

MATERIAL FLOOR CHANGE (REFER TO THIS SHEET FOR DETAILS)

INTERIOR FINISH SYMBOLS

SEALED CONCRETE WITH STATIC DISSIPATIVE COATING (C-1/SDC)

INTERIOR FINISHES

PAINT

FIELD

CALIFORNIA PAINTS*

TO MATCH BENJAMIN MOORE

MANCHESTER TAN HC-81

ARCHITECT/ENGINEERS:

INTERIOR FINISHES

Drawing Title

Approved: Project Director

Project Title

Location

Date Checked Drawn

NB KLM

Project Number

Board Number

Office of Construction and Facilities Management

*BASIS OF DESIGN

**MATCH EXISTING CAMPUS PAINT COLORS

EHRM INFRASTRUCTURE

UPGRADES

518-22-700

200 Springs Road, Bedford, MA 01730

EDITH NOURSE MEMORIAL VETERANS HOSPITAL

P-1

DIGITAL IMAGES MAY HAVE COLOR INACCURACIES, REFER

TO ACTUAL SAMPLE FOR TRUEST COLOR DEPICTION

PAINT

METAL DOORS & TRIM

CALIFORNIA PAINTS*

TO MATCH BENJAMIN MOORE

WHITE DOWN OC-131

P-2

WALL BASE

JOHNSONITE*

BEIGE 49

RB-1

PAPER INSERT CARRIER, MAGNETIC

MOUNT, WITH NON-GLARE LENS

TEXT: 5/8"H LASER-PRINTED TEXT,

HELVETICA MEDIUM

COLOR: TO MATCH STATION

STANDARDS

1-1/2" x 1/32" ADA

TACTILE NUMERALS

AND GRADE II BRAILLE234

9"

Restricted Access5-3/16" X 9" CLEAR

ACETATE INSERT W/

COPY

9"X9" MAGNETICALLY

REMOVABLE SIGN

(ONE-PIECE)

RED SYMBOL AND

BLACK TEXT

1/2" 9" 1/2"

/2

/2

QUARTER-ROUND

SILVER FRAME

EXISTING FLOORING

TO BE REMOVED

TOP OF SLAB

EXISTING

FLOORING TO

REMAIN, EXISTING

ROOM SIDE EXISTING CONCRETE

FLOOR WITH STATIC

DISSIPATIVE (C-1/SDC)

RESILIENT BASE AS

SCHEDULED, EACH

SIDE OF NEW WALL

INSTALL 3/4"

PLYWOOD, MOUNT

BOTTOM OF

PLYWOOD 12" AFF

ADJACENT SPACE

TELECOM

ROOM SIDE

PARTITION AS SCHEDULED

EXISTING CONCRETE

FLOOR WITH STATIC

DISSIPATIVE (C-1/SDC)

LOCATION OF FLOOR

FINISH CHANGE;

SEAM OR ADAPTER

TRANSITION SHALL

OCCUR AT

CENTERLINE OF

DOOR IN CLOSED

POSITION

DOOR AS SCHEDULED

EXISTING FLOORING

TOP OF SLAB

CORRIDOR SIDE

DOOR FRAME BEYOND

C CENTER LINE OF DOORL

TRANSITION STRIP

(TR-1) OR EQUAL,

REFER TO SCHEDULE

FOR INFORMATION

TELECOM ROOM SIDE

SIGNAGE REFERENCES

VA SIGNAGE DESIGN MANUAL

SIGN VENDOR TO REFERENCE VA SIGNAGE DESIGN MANUAL FOR COMPLETE

SPECIFICATIONS

https://www.cfm.va.gov/til/spclRqmts.asp#SIGN

SIGN SYMBOL LEGEND

IN-08.02

IN-04.01A

IN-01.31

1 2 5 6

F1

17_29IN101

TYP.

F4

17_29IN101

TYP.

TELECOM ROOM FINISH DIAGRAM,

CONTRACTOR TO REFERENCE

ARCHITECTURE FOR ACTUAL WALL

CONSTRUCTION LOCATIONS

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

TRIPLE C - The A/E Group

100 Pearl Street, 14th Floor

Hartford, CT 06103

MAT PERKINS

(860)270-0753

A u to d e s k D o c s /3

C

R

.P ro je c t.

-2

-7

.E H

R M

.I U

.B e d fo rd

.M A

.R

/5

-2 -7

.B e d fo rd .E

H R

M .A

R C

H .B

R

.r v t

/2

/2

:4

:0

A

M

17_29IN101

INTERIOR FINISH PLAN, SIGNAGE & SCHEDULES 518-22-700

06/04/2025 M. Perkins K. McDermott

ISSUED FOR

CONSTRUCTION

EHRM INFRASTRUCTURE

UPGRADES

200 Springs Rd, Bedford, MA 01730

NTS

C1

COLOR BOARD

3" = 1'-0" D3

IN-04.03D SIGN DETAIL - PRIMARY ROOM

IDENTIFICATION

3" = 1'-0"

D1

IN-08.02C SIGN DETAIL - PROHIBIT

INSTRUCTIONAL AND CONTROL

NTS

D5

EXAMPLE OF EXISTING SIGNAGE

6" = 1'-0" F4

RESILIENT BASE (TOE BASE)

6" = 1'-0"

F1

THRESHOLD - CONCRETE TO EXISTING FLOORING

1 REMOVE EXISTING FLOORING, ADHESIVES, AND INSTALL NEW WALL

BASE

2 EXISTING WALLS ARE TO BE PATCHED AND PAINTED. SEE ROOM

FINISH SCHEDULE THIS SHEET FOR FINISHES.

3 ALL WALLS TO RECEIVE NEW PLYWOOD, COORDINATE WITH

ELECTRICAL DRAWINGS FOR FIXTURE LOCATIONS

4 30"x30" UNDER-FLOOR ACCESS PANEL

5 REFER TO ARCHITECTURAL PLANS FOR DETAILED ROOM

CONFIGURATION INFORMATION

6 TELECOM ROOM SPACE TO RECEIVE STATIC CONTROL CONCRETE

SEALER

REFER TO THIS SHEET FOR ROOM FINISH SCHEDULE & FINISH LEGEND

3" = 1'-0" D6

IN-01.31 SIGN DETAIL - FIRE EQUIPMENT

IDENTIFICATION SIGN

ROOM FINISH SCHEDULE

LEVEL NO. NAME

FLOOR WALLS CEILING

NOTESFINISH BASE

NORTH EAST SOUTH WEST

MATERIAL FINISHMATERIAL FINISH MATERIAL FINISH MATERIAL FINISH MATERIAL FINISH

LEVEL 1 118 TELECOM ROOM C-1/ SDC RB-1 GWB P-1/WD GWB P-1/WD GWB P-1/WD GWB P-1/WD OPEN

BUILDING SIGNAGE SCHEDULE

VERSIO

N TYPE COUNT DESCRIPTION DETAIL LOCATION REFERENCE

ADA

BRAILLE TEXT COLOR BACKGROUND COLOR

DIMENSIONS

CommentsSIGN_HEIGHT SIGN_WIDTH MOUNTING HEIGHT

IN-01.31 1 FIRE IDENTIFICATION SIGN D6 / IN101 FEC REFER TO PAGE 429 OF SIGNAGE DESIGN

MANUAL DATED 05/2023

NO WHITE RED 9" 9" 6' - 8" INSTALLED AT FIRE EXTINGUISHER CABINETS AT ALL

NEW TELECOM ROOMS

IN-04.01A 1 ROOM NUMBER IDENTIFICATION D3 / IN101 TELECOM ROOM REFER TO PAGE 261 OF SIGNAGE DESIGN

MANUAL DATED 05/2023

YES REFERENCE EXISTING

CAMPUS STANDARDS

REFERENCE EXISTING

CAMPUS STANDARDS

9" 9" 5' - 0" INSTALLED AT ALL NEW TELECOM ROOMS

IN-08.02 1 PROHIBIT INSTRUCTIONAL AND

CONTROL

D1 / IN101 TELECOM ROOM REFER TO PAGE 279 OF SIGNAGE DESIGN

MANUAL DATED 05/2023

NO REFERENCE EXISTING

CAMPUS STANDARDS

REFERENCE EXISTING

CAMPUS STANDARDS

9" 9" 5' - 9" INSTALLED AT ALL NEW TELECOM ROOMS MOUNTED

DIRECTLY ABOVE ROOM NAME SIGN

Grand total: 3

FINISH LEGEND

SYMBOL FINISH TYPE MANUFACTURER COLLECTION STYLE / TYPE COLOR SIZE SPEC SECTION NOTES

C-1/ SDC SEALED CONCRETE WITH STATIC DISSIPATIVE COATING SEALED CONCRETE* - - - - - TELECOM ROOM SPACE TO RECEIVE STATIC CONTROL CONCRETE

SEALER

F-1 FILM 3M* FASARA 7725SE-324 FROSTED CRYSTAL - 08 87 33 WINDOW FILM

P-1 PAINT CALIFORNIA PAINTS* - EGGSHELL TO MATCH BENJAMIN MOORE MANCHESTER TAN HC-81 - 09 91 00 FIELD

P-2 PAINT CALIFORNIA PAINTS* - SEMI-GLOSS TO MATCH BENJAMIN MOORE WHITE DOWN OC-131 - 09 91 00 METAL DOORS & TRIM

RB-1 RESILIENT BASE JOHNSONITE* TRADITIONAL TOE BASE BEIGE 49 4" 09 65 13

TR-1 TRIM SCHLUTER * - RENO-U SATIN ANODIZED ALUMINUM - 09 30 13 FLOOR TRANSITION

WD PLYWOOD FIRE TREATED PLYWOOD* - - HIGH GLOSS WHITE MPI (MASTER PAINTERS INSTITUTE)

67 OR SIM

4' X 8' - PLYWOOD TO BE PAINTED WITH 2 COATS OF FIRE RESISTANT PAINT. FIRE

RATING STAMPS SHALL NOT BE PAINTED OVER

*Materials are approved as basis of design, all material substitutions are subject to owner approval. Contractor to provide VA Interior Design Department with samples of all specified finish materials. VA COR/ Interior Design department shall approve all finishes prior to installation.

1/2" = 1'-0" F7

TYPICAL TELECOM ROOM FINISH DIAGRAM

Number Revisions: Date:

1 Revision 1 Date 1

WAP

WAP

WAP

WAP

WAP

WAP

WAP

WAP

WAP

WAP

WAP

WAP

WAP

WAP

DN

DN

UP

WAP

WAP

CTRK

WAP

WAP

WAP

WAP

CTRK

CTRK

WAP

WAP

WAP

DN

WAP

WAP

WAP

WAP

WAP

WAP

WAP

WAP

WAP

WAP

WAP

WAP

WAP

WAP

WALL SYMBOL LEGEND

EXISTING CONSTRUCTION TO REMAIN

SMOKE AND 1-HR RATED FIRE

BARRIER AND OPENINGS

SMOKE AND 2-HR RATED FIRE BARRIER

AND OPENINGS

SMOKE BARRIER AND OPENINGS

1 HR RATED FIRE BARRIER AND

OPENINGS

2 HR RATED FIRE BARRIER AND OPENINGS

CONTRACTOR SHALL CONFIRM ALL FIRE RATED WALL ASSEMBLIES

STORAGE

B17

RODENT

B16C

RODENT

B16A

RODENT

B16

LAB

B16B

ENTRANCE

B30

ROOM

B17A

QUARANTINE

B17B

OFFICE

B18

LOUNGE

B18A

RODENT RM

B18B

RODENT RM

B18C

CORRIDOR

B31

TOILET

B15A

MICE

B15

COLD RM

B13

ROOM

B14

CORRIDOR

B32

CAGE WASH

B19

SERVICE ROOM

B20

RADIOACTIVE STORAGE

B01

ROOM

RADIOACTIVE STORAGE

B02A

LAB GLASS WASHING

B03

ROOM

B04

DARK RM

B05

ENTRANCE

B06

OFFICE

B07

LAB

B08A

CORRIDOR

B34

LAB

B08

LAB

B10

LAB

B11LOBBY

B35

FOOD PREP

B12

CORRIDOR

B33

TOILET

B09

STEAM PIT

B30-AP-A

B18C-AP-A

B31-A

B31-A B32-A

B12-AP-A

B -B

B -C

B11-AP-A

B -A

B35-AP-A

B -A

B -A

B08-AP-A

B03-AP-A

B -A B05-A

B08A-C

B08A-B

B08A-A

B06-AP-A

B -A

B06-A

NO DATA

NO DATA

NO DATA

NO DATA

NO DATA

NO DATA

NO DATA

NO DATA

NO DATA

NO DATA

NO DATA

NO DATA NO DATA

NO DATA

NO DATA

NO DATA

NO DATA

NO DATA

SERVED FROM LEVEL 1

29 DATA PORTS FOR THIS AREA

6,052 GSF

TYP.

TYP.

TYP.

TYP.

FIBER PATH A

FIBER PATH B

17_29T-100

B1

B17-AP-A

B16-AP-A

B15-AP-A

B10-AP-A

B03-AP-B

B08-AP-A

TYP.

TYP.

TELE CLT

B35A

PATH TO B29 4" PVC

B18-C

B18-B

B18-A

NO DATA

NO DATA

PORCH

RESEARCH

ACOS ADMIN ASSISTANT

CLOS.

113A

CLOS.

113B

CLOS.

112A

RESEARCH

RESEARCH

ACOS OFFICE

CLOS.

116B

CLOS.

116A

CLOS.

117B

ACOS OFFICE

CLOS.

117A

TELECOM ROOM

FREEZER

101A

FILM LAB

ANTE ROOM

100A

COLD ROOM

RESEARCH

STAIR

LAB

PORCH

CORRIDOR

LAB

EXPLOSION ROOM

UTILITY

CENTRIFUGE

EXPLOSION PROOF ROOM

107A

LAB

CONFERENCE

CORRIDOR

TOILET

112A

TOILET

CLOS.

112B

17_29T-100

E1

130-A

113-AP-A

113-A

112-A

112-B

114-AP-A

114-A

115-CK-A

115-B

115-A

116-A

130-AP-A

110-A

117-A

-F

-G

-B

118-D1 -E

-A

118-C

-A

P -A

EXT-A

108-A 108-B

106-A

106-B

102-B

102-A

131-AP-A

103-A 103-B

103-AP-A

EXT-B

-A

104-B

NO DATA

NO DATA NO DATA NO DATA

NO DATA

NO DATA

NO DATA

NO DATA

NO DATA NO DATA

NO DATA

NO DATA

NO DATA

NO DATA

NO DATA

NO DATA

NO DATA

NO DATA

NO DATA

113-B

108-CK-A

104-CK-A

43 DATA PORTS FOR THIS AREA

5,973 GSF

TYP.

TYP.

TYP.

TYP.

TYP.

118-CAM-01

110-AP-A

107-AP-A

104-AP-A

LAB

ROOM

214B

ROOM

214A

GPM OFFICE

CORRIDOR

OFFICE

GPM OFFICE

STAIR

CLOS.

CLOS.

CLOS.

CLOS.

CORRIDOR

TOILET

OFFICE

TRAINING

CLOS.

213A CLOS.

CLOS.

CLOS.

CLOS.

CLOS.

OFFICE

PHOTOGRAPHER

OFFICE

LAB

LAB

CORRIDOR

CLOS.

CLOS.

CLOS.

CLOS.

CLOS.

LAB

OFFICE

LOUNGE

LAB

UTILITY

207A

214B-A

214-A

214-AP-A

-B

214A-A

230-AP-A

NO DATA

-A

219-A

219-B

212-A

211-A

211-AP-A

220-A

STAIR

240-AP-A

200-A

210-A

210-B

209-A

201-A

208-A

208-B 207-A

207-AP-A

205-A

205-B

-C

202-A 203-AP-A

203-A

-B

EXT-C

NO DATA

NO DATA

NO DATA NO DATA NO DATA

NO DATA

NO DATA

NO DATA NO DATA NO DATA NO DATA NO DATA NO DATA NO DATA

NO DATA

NO DATA

NO DATA

36 DATA PORTS FOR THIS AREA

5,581GSF

SERVED FROM LEVEL 1

TYP.

TYP.

TYP.

TYP.

TYP.

214-AP-B

219-AP-A

209-AP-A

201-AP-A

205-AP-A

17_29T-100

B3

TYP.

TELECOM ROOM

157 SF

STAIR

CLOS.

117A

118-G

118-B

118-D

118-F

TYP.

TYP.

10'-8"

118-AP-A

118-A

118-C

118-E

118-CAM-01

TYP.

TYP.

3'-0"

TYP.

5'-4"

TYP.

(NIC)

262' - 0"

TELECOM ROOM

157 SF

B29

FIBER PATH A

FIBER PATH B

CABLE LEGEND

(10) NEW CAT 6A

FIBER EXTENDING FROM

BUILDING 17 TO BUILDING 29

LOBBY

B35

LAB

B11

(E) WALL MOUNTED TE

(E)PATCH PANEL

(E)SECURITY CABINET

(E)PLYWOOD BACKBOARD

TELE CLT

B35A

12 SF

(E)INDOOR AC UNIT

5 11 12 18

ROOM

BATH

1A1-AP-A

1-AP-B

TYP.

PATH TO B17 4" PVC

CLOS.

213A

16 SF

TOILET

LAB

CORRIDOR

(E) PLYWOOD BACKBOARD

(E/REM) PATCH PANEL

(E) TELCO PATCH

(E) WALL MOUNTED TE

(E) WALL MOUNTED SWITCH

(E) INDOOR AC UNIT

TN

PN

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

CONSULTANT

321 4 5 6 7 8 9 10

GENERAL NOTES

KEYNOTES

TRIPLE C - The A/E Group

100 Pearl Street, 14th Floor

Hartford, CT 06103

MAT PERKINS

860-270-0753

STAMP

mat.perkins@triplecaeg.com

A u to d e s k D o c s /3

C

R

.P ro je c t.

-2

-7

.E H

R M

.I U

.B e d fo rd .M

A .R

/5

-2

-7

.B e d fo rd

.E H

R M

.M E

P .B

R

.r v t

/2

/2

:4

:4

A

M

17_29T-100

TELECOMMUNICATION PLAN - BASEMENT AND

FIRST LEVELS

518-22-700

17_29

06/04/2025 M. Perkins K.Mcdermott

ISSUED FOR

CONSTRUCTION

EHRM INFRASTRUCTURE

UPGRADES

200 Springs Rd, Bedford, MA 01730

SCALE: 1/8" = 1'-0"

F4

TELECOMMUNICATION PLAN -

BASEMENT LEVEL

SCALE: 1/8" = 1'-0"

E4

TELECOMMUNICATION PLAN - FIRST

LEVEL

SCALE: 1/8" = 1'-0"

B4

TELECOMMUNICATION PLAN -

SECOND LEVEL

SCALE: 1/2" = 1'-0"

E1

TELECOMMUNICATION ENLARGED

PLAN - FIRST LEVEL - RM 118 - NEW

SCALE: 1" = 100'-0"

F1

DIAMOND ANALYSIS -BUILDING 17_29

SCALE: 1/2" = 1'-0"

B1

TELECOMMUNICATION ENLARGED

PLAN - BASEMENT LEVEL - RM B35A -

EXISTING

SCALE: 1/8" = 1'-0"

F3

TELECOMMUNICATION PLAN - FIRST

LEVEL-BUILDING 29

A. PROPERLY FIRE STOP AND SEAL ALL PENETRATIONS THROUGH WALLS,

FLOORS, CEILINGS, AND ROOF AS PER OWNER, CODE, AND AHJ.

B. PRIOR TO INSTALLATION OF CABLE TRAY COORDINATE LOCATIONS WITH ALL

OTHER TRADES AND PROVIDE COORDINATION DRAWINGS FOR REVIEW. ALL

NEW CABLE, CABLE TRAY, J HOOKS SHALL BE INDEPENDENTLY SUPPORTED &

NOT CAUSE ADDITIONAL LOAD ON OTHER SYSTEMS.

C. NOT ALL PARTS AND PIECES ARE SHOWN FOR A COMPLETE SYSTEM.

CONTRACTOR IS RESPONSIBLE FOR PROVIDING A COMPLETE END-TO-END

WARRANTEED SOLUTION FOR THE CABLING.

D. ALL CABLING TO BE PLENUM RATED THROUGHOUT THE BUILDING.

E. ALL COMMUNICATIONS AND WIRELESS ACCESS POINT CABLING TO MEET OR

EXCEED CATEGORY 6A STANDARDS.

F. SEE E-501 FOR DEVICE STANDARD MOUNTING HEIGHTS.

G. ALL CONDUITS FOR TELECOMMUNICATIONS OUTLETS SHALL BE STEEL THIN

WALL ELECTRICAL METALLIC TUBING (TYPE EMT) UNLESS OTHERWISE NOTED.

UNDER NO CIRCUMSTANCES SHALL FLEXIBLE CONDUIT BE USED FOR

PATHWAYS INDICATED ON THIS DRAWING. ALL CONDUITS ARE TO BE, AT A

MINIMUM, 1-1/4" TRADE SIZE, UNLESS OTHERWISE NOTED. ALL CONDUITS FOR

TELECOMMUNICATIONS OUTLETS ARE TO BE STUBBED TO NEAREST CABLE

TRAY. CONTRACTOR IS TO ENSURE THAT NO CONDUIT EXCEEDS 40% FILL. IF

EXISTING CONDUIT IS NOT LARGE ENOUGH TO SUPPORT NEW CAT 6A CABLE

TO REPLACE ALL EXISTING CIRCUITS ONE-FOR-ONE, CONTRACTOR SHALL

PROVIDE THE MAXIMUM ALLOWABLE NEW CAT 6A CIRCUITS TO REPLACE

EXISTING. THE ADDITIONAL NEW CIRCUITS TO COMPLETE THE ONE-FOR-ONE

REPLACEMENT SHALL BE PROVIDED AT THE NEAREST AVAILABLE DROP WITH

EXISTING CONDUIT CAPACITY.

H. ALL CONDUIT PATHWAYS SHALL BE PROVIDED WITH NYLON BUSHINGS TO

PROTECT CABLES, REGARDLESS OF WHETHER THEY TERMINATE IN A DEVICE

OR JUNCTION BOX.

I. TERMINATE, TEST, LABEL AND DOCUMENT ALL TELECOMMUNICATION CABLES.

J. CONTRACTOR SHALL AVOID ALL SYSTEMS SHUTDOWNS, INSTALL NEW

EQUIPMENT PRIOR TO THE RENOVATION OF EXISTING EQUIPMENT; PROVIDE

TEMPORARY UTILITIES AS REQUIRED TO MEET THIS REQUIREMENT.

K. THE DEMOLITION OF DEVICES SHALL INCLUDE ALL ASSOCIATED CABLING

BACK TO THE RACK.

L. LABEL DEVICE PLATES WITH A PERMANENT ADHESIVE LABEL FOLLOWING ALL

STANDARDS AND REQUIREMENTS, SEE DETAIL SHEETS FOR ADDITIONAL

INFORMATION

M. CONTRACTOR SHALL PROVIDE TWO SETS OF LAMINATED FINAL

TELECOMMUNICATION ONE-LINE, RACK ELEVATION, AND CABLE SCHEDULE

DOCUMENTS. HANG ON THE WALL WITHIN THE TELECOM ROOM.

N. REFER TO R-900 SERIES SHEETS FOR PHOTO DOCUMENTATION OF EXISTING

CONDITIONS.

O. FOR EXISTING SECURITY CAMERAS BEING RE-CABLED, MAINTAIN EXISTING

CAMERA ANGLE AND PROTECT IN PLACE.

P. ALL EXISTING PENETRATIONS NO LONGER BEING USED WILL BE FILLED WITH

RATED ASSEMBLY.

Q. ABOVE CEILING SURVEY TO OCCUR FOR CABLE TRAY INSTALLATION. EXISTING

EQUIPMENT AND/ OR SYSTEMS TO BE SELECTED AS REQUIRED. ALL ACTIVE

SYSTEMS TO REMAIN OPERATIONAL.

1. PROVIDE NEW TELECOMMUNICATIONS OUTLET IN EXISTING LOCATION WITH

EXISTING EMT STUB UP TO NEAREST ACCESSIBLE CEILING SPACE. SEE DETAILS

ON SHEET T-501 FOR ADDITIONAL INFORMATION.

2. ALL EXISTING WAP'S TO REMAIN/PROTECT IN PLACE, AND NO NEW CABLING

REQUIRED FOR EXISTING WAP'S (WIRELESS ACCESS POINTS).

3. PROVIDE NEW 4-POST CHANNEL, PDU, UPS AND WIRE MANAGEMENT

COMPONENTS AS SHOWN ON T-500 SERIES AND T-600 SERIES SHEETS AND IN

THE SPECIFICATIONS.

4. PROVIDE NEW VERTICAL WIRE MANAGEMENT SYSTEM, SEE SPECIFICATIONS FOR

ADDITIONAL INFORMATION.

5. EXISTING CABLING CONDUIT AND WIREWAYS ARE TO REMAIN AND BE CAREFULLY

PROTECTED IN PLACE. ALL EXISTING DEVICES ON THE EXISTING RACK SHALL BE

TRANSFERRED TO THE NEW RACK. CONTRACTOR SHALL PROVIDE SHOP

DRAWINGS SHOWING THE PROPOSED NEW RACK ELEVATION AND PROVIDE A

PHASING PLAN FOR TRANSFERRING ALL EXISTING DEVICES TO REMAIN TO THE

NEW RACKS.

6. PROVIDE NEW CABLE TRAY PER REQUIREMENTS LISTED IN CABLE TRAY

SCHEDULE. COORDINATE WITH EXISTING CONDITIONS AND SUBMIT

COORDINATION DRAWINGS FOR REVIEW PRIOR TO COMMENCING WORK. SEE

T-500 SERIES SHEETS FOR ADDITIONAL REQUIREMENTS. COORDINATE LIGHT

FIXTURES WITH OVERHEAD CABLE TRAY AND SPEED SLEEVE FILL SHALL NOT

EXCEED 40%.

7. PROVIDE NEW IP ADDRESSABLE NETWORK CAMERA, POE+, PTZ, MOTION

SENSOR, AUTO-TRACKING, DOME WITH WALL MOUNT. MOUNT AT 8’ – 6” A.F.F. TO

TOP OF WALL BRACKET. INTEGRATE CAMERA INTO EXISTING VMS.

8. PROVIDE NEW DATA OUTLET, STUB-UP, AND BACK-BOX IN NEW LOCATION IN TR.

9. NEW 4” SPEED CONDUIT SLEEVE THROUGH WALL ABOVE CEILING GRID FOR

HORIZONTAL VOICE/DATA CABLING OR FIBER WITH PLASTIC BUSHINGS ON BOTH

ENDS TO PROTECT CABLES,CABLE TRAY AND SPEED SLEEVE FILL SHALL NOT

EXCEED 40%. FIRE CAULK PENETRATION PER SPECIFICATIONS.

10. EXISTING CONDUIT THROUGH WALL OR FLOOR WITH OPTICAL CABLE TO BE

PROTECTED IN PLACE UNTIL NEW SPEED CONDUIT SLEEVE AND FIBER IS

INSTALLED. DEMOLISH EXISTING CONDUIT ONCE NEW SPEED CONDUIT SLEEVE

AND FIBER ARE OPERATIONAL. CONTRACTOR SHALL PROVIDE A PHASING PLAN

FOR TRANSFERRING FIBER.

11. EXISTING EQUIPMENT TO REMAIN, PROTECT-IN-PLACE.

12. DEMOLISH EXISTING FIBER ONCE NEW FIBER IS OPERATIONAL. CONTRACTOR

SHALL PROVIDE A PHASING PLAN FOR TRANSFERRING FIBER.

13. ALL EXISTING ANALOG PHONE CABLE DEVICES AND TERMINATIONS ETC. SHALL

REMAIN OPERATIONAL AT ALL TIMES AND SHALL BE RETAINED AND REUSED.

PROTECT IN PLACE.

14. VERTICAL ROUTE WITH REDUNDANT SPARE CONDUIT TO DROP CEILING. SECURE

CONDUITS TO WALL. SEAL ALL FLOOR PENETRATIONS TO MAINTAIN FIRE RATING.

15. HORIZONTAL CABLE LENGTH LIMITATIONS PER STANDARD 3.1.

16. EXISTING PACS AND EQUIPMENT RACKS.

17. NEW INDOOR UNIT.

18. CONTRACTOR SHALL FIELD VERIFY EXISTING TELECOMMUNICATIONS EQUIPMENT

TO BE DEMOLISHED PRIOR TO COMMENCING WORK.

19. VERTICAL LADDER RACK.

20. EXISTING CAMERA TO BE RETAINED.

21. PROVIDE NEW TELECOMMUNICATIONS OUTLET IN EXISTING LOCATION WITH

SURFACE MOUNT CONDUIT/WIREMOULD UP TO NEAREST ACCESSIBLE CEILING

SPACE.

22. PROVIDE SPACE FOR FUTURE 4-POST RACK.

23. PROVIDE 10 NEW CAT 6A CABLES FROM EXISTING TR TO NEW TR LOCATION FOR

CROSS CONNECTION, EXISTING LOW VOLTAGE SYSTEMS.

24. EXISTING TELECOMMUNICATIONS OUTLET IN EXISTING LOCATION .PROVIDE

BLANK FACE PLATE.

25. REFER SHEET TS100 FOR DETAIL.

26. RELOCATE DATA PORT TO ADJACENT WALL, COORDINATE WITH COR.

NOTE: NOT ALL KEYNOTES

ARE USED ON EACH SHEET

SCALE: 1/2" = 1'-0"

B3

TELECOMMUNICATION ENLARGED

PLAN - SECOND LEVEL - RM 213 -

EXISTING

REFER TO COVER SHEET FOR KNOWN ACM ITEMS WITHIN

THIS BUILDING.

REFER TO COVER SHEET FOR KNOWN ACM ITEMS WITHIN

THIS BUILDING.

REFER TO COVER SHEET FOR KNOWN ACM ITEMS WITHIN

THIS BUILDING.

Revisions: Date:

Addendum 1 02/25/2026

Sheets
17_29A-401 - ARCHITECTURAL ENLARGED VIEWS -FIRST LEVEL
17_29A-512 - ARCHITECTURAL PARTITION HEAD DETAILS
17_29IN101 - INTERIOR FINISH PLAN, SIGNAGE & SCHEDULES
17_29T-100 - TELECOMMUNICATION PLAN -BASEMENT AND FIRST LEVELS

File details come from the government source that posted it. Updated .