- 36C77626R0003
About this file
This file consists of architectural construction drawings for EHRM Infrastructure Upgrades at the Edith Nourse Memorial Veterans Hospital in Bedford, MA, issued for construction on 06/04/2025 with an addendum dated 02/25/2026. The project, numbered 518-22-700, is prepared by TRIPLE C - The A/E Group and involves the conversion of existing spaces into two new telecom rooms (Room 178 on Level 1 and Room 233 on Level 2), each approximately 115-119 square feet.
The scope of work includes demolishing existing construction, installing 1-hour fire and smoke-rated walls, installing 45-minute fire-rated doors with hollow metal frames, applying fire-treated plywood to exterior walls with window film enclosures, sealing all penetrations, removing existing flooring and wall base, providing new fire extinguisher cabinets with Type 2A:10B:C clean agent extinguishers within 75 feet of each room, installing static dissipative concrete sealing, applying interior finishes including specific paint colors (Benjamin Moore Manchester Tan HC-81 and White Down OC-131), Johnsonite Beige 49 resilient base, signage per VA standards, and new ceiling systems. The contractor is responsible for all costs associated with moving, storing, and returning furnishings and equipment, including disassembly and reassembly of systems furniture per manufacturer warranty. Detailed partition specifications include Type A (4-inch studs, 45 STC rating), Type B (2.5-inch studs, 35 STC rating), and Type J (non-rated, 2.5-inch studs) with varying gypsum wallboard, sound attenuation batts, and sealant requirements. The drawings include floor plans, reflected ceiling plans, door and frame schedules, interior finish plans, signage schedules, and detailed head-of-wall conditions for fire-rated and smoke partitions. The contractor must field-verify all dimensions and conditions at time of bidding and coordinate with electrical and mechanical drawings for fixture and system locations.
View the file
Other files
Show 40 more
Latest 50 of 105 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SHEET SYMBOL LEGEND
KEYNOTES
GENERAL NOTES
EXISTING CONSTRUCTION TO REMAIN
EXISTING CONSTRUCTION TO BE DEMOLISHED
NEW CONSTRUCTION, WITH PARTITION TYPE
A
A. SEE GENERAL NOTES AND PLANS FOR TYPICAL GENERAL PROJECT
REQUIREMENTS AND PROJECT LOCATION DRAWINGS.
B. SEE INTERIOR FINISH DRAWINGS FOR ADDITIONAL FINISHES
INFORMATION.
C. SEE MECHANICAL AND ELECTRICAL DRAWINGS FOR ADDITIONAL
SYSTEMS INFORMATION.
D. NEW TELECOM ROOMS SHALL BE 1 HOUR FIRE AND SMOKE RATED
AND COMPLY WITH THE LATEST VA PHYSICAL SECURITY STANDARDS,
AND CAMPUS STANDARDS.
E. SEE TYPICAL WALL FRAMING DETAILS ON SHEET A-511.
F. SEE TYPICAL HEAD OF WALL DETAIL ON SHEET A-512.
G. SEE TYPICAL CEILING DETAILS ON SHEET A-531
H. ALL PHOTOS SHOWN REFLECT EXISTING CONDITIONS AS OF THE
DATE OF THIS DRAWING SET. CONTRACTOR SHALL FIELD VERIFY ALL
DIMENSIONS, CONDITIONS, AND SITE-SPECIFIC INFORMATION AT THE
TIME OF BIDDING.
I. CONTRACTOR IS RESPONSIBLE FOR ALL COSTS ASSOCIATED WITH
MOVING, STORING AND RETURNING FURNISHINGS AND EQUIPMENT
TO THE PROPOSED WORK AREA(S). ANY DISASSEMBLY AND
REASSEMBLY OF SYSTEMS FURNITURE IN THE PROPOSED WORK
AREAS IS THE RESPONSIBILITY OF THE CONTRACTOR AND MUST
FOLLOW THE MANUFACTURER'S WARRANTY.
TELECOM
ROOM
115 SF
ELECTRICAL
177177
6 7
5 6
F
G
10 11 12
06A-401
B8
TELECOM
ROOM
178178
TELECOM
ROOM
115 SF
ELECTRICAL
177177
(EXTING VIF)
9'-11 5/8"
B
B
H W
-S F
-3 F
5 6
F
G
(E X
T
IN
G V
IF
'-4
/8
B
B
J2 J2
5 6
F
G
TELECOM
ROOM
178178
TELECOM
ROOM
178178
ELECTRICAL
177177
ACOUSTICAL OR RATED
FLEXIBLE SEALANT
FLOOR LINE
ADD ONE LAYER OF 5/8" GWB,
ONE-SIDE WITH APPROVED UL
SETTING COMPOUND BETWEEN
LAYERS AND FASTENED TO
WALL AS REQUIRED, AT
EXISTING GWB WALL
ASSEMBLIES
STRUCTURAL DECK
EXISTING METAL STUDS AND
BATT INSULATION TO REMAIN
A/C GRADE, 3/4" FIRE-TREATED
PLYWOOD, ADHERED TO CONCRETE
AT EXISTING CONCRETE WALL
ASSEMBLIES
BOTTOM OF PLYWOOD
TO BE AT 12" AFF
UL DESIGN V497
1-HOUR PARTITION RATED FROM BOTH SIDES
EXISTING GWB OR
CONCRETE WALL
ASSEMBLY, WHERE OCCURS
SIDE OF
EXISTING
ROOM OR
CORRIDOR TO
REMAIN
06A-512
E5
06A-512
B4
C1
TYPICAL FRAME
H E
IG
H
T
2" WIDTH 2"
E1
FRAME TYPE ELEVATIONS DOOR TYPE ELEVATIONS
F
FLUSH
1/2" 1/2"
VARIES
SEE PLAN
WALL - SEE PLAN
FOR TYPE
SEALANT - EA. SIDE
& ALL AROUND,
TYP.
HOLLOW METAL
FRAME
/2
V
A R
IE
S
S E
E P
L A
N
/2
UNO
4" 2"
ADJACENT WALL
WHERE OCCURS
SEALANT - EA SIDE &
ALL AROUND, TYP.
HOLLOW METAL FRAME
WALL - SEE PLAN
FOR TYPE
ACOUSTICAL OR RATED
SEALANT BOTH SIDES
FLOOR LINE
5/8" GWB BOTH SIDES
SOUND ATTENUATION
BATTS (SAB) PER
SCHEDULE.
CEILING LINE
STRUCTURAL DECK
METAL STUDS, SIZE
PER SCHEDULE
06A-512
E5
A/C GRADE, 3/4" FIRE-
TREATED PLYWOOD
06A-512
B4
AT FIRE RATED
PARTITIONS
AT SMOKE RATED
PARTITIONS
BOTTOM OF PLYWOOD TO
BE AT 12" AFF
LINE OF
STRUCTURE
LINE OF
STRUCTURE
09 29 00
SOUND ATTENUATION BATTS
(SAB), WHERE OCCURS
NOTE:
IF PARTITION TYPE IS USED IN A
CHASE WALL CONDITION, PROVIDE
CROSS BRACING GUSSETS AT 48"
O.C. MAX VERTICALLY. FABRICATED
FROM 6" MTL STUDS.
6”
09 29 00
5/8" GWB
09 29 00
SAB RETAINER STRAP
WHERE SAB OCCURS
CEILING
07 92 00
SEALANT
09 22 16
METAL STUDS
06A-512
E5 06A-512
B4
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
TRIPLE C - The A/E Group
100 Pearl Street, 14th Floor
Hartford, CT 06103
MAT PERKINS
(860)-270-0753
A u to d e s k D o c s /3
C
R
.P ro je c t.
-2
-7
.E H
R M
.I U
.B e d fo rd
.M A
.R
/5
-2 -7
.B e d fo rd .E
H R
M .A
R C
H .B
R
.r v t
/2
/2
:3
:1
A
M
06A-401
ARCHITECTURAL ENLARGED VIEWS - FIRST
LEVEL
518-22-700
06/04/2025 M. Perkins K. McDermott
ISSUED FOR
CONSTRUCTION
EHRM INFRASTRUCTURE
UPGRADES
200 Springs Rd, Bedford, MA 01730
3" = 1'-0" C1
HOLLOW METAL HEAD DETAIL
3" = 1'-0" E1
HOLLOW METAL JAMB DETAIL
1/4" = 1'-0" F1
DOOR AND FRAME TYPES ELEVATIONS
1/4" = 1'-0" D8
ARCHITECTURAL FLOOR PLAN - FIRST LEVEL
- RM 178 - DEMO
1/32" = 1'-0" F8
FIRST FLOOR REFERENCE PLAN
1/4" = 1'-0" B8
ARCHITECTURAL FLOOR PLAN - FIRST LEVEL
- RM 178 - NEW
1 EXISTING WALLS TO BECOME 1 HR FIRE AND SMOKE-RATED.
PATCH AND SEAL ALL PENETRATIONS AS NECESSARY.
2 PROVIDE NEW FIRE EXTINGUISHER CABINET WITH A TYPE
2A:10B:C CLEAN AGENT FIRE EXTINGUISHER LOCATED NO
GREATER THAN 75 FEET AWAY FROM THE NEW TR. CONTRACTOR
TO COORDINATE THE NEW LOCATION WITH THE COR.
CONTRACTOR SHALL BID A NEW FEC FOR EACH TR IN THE SCOPE
OF WORK. SEE SPECIFICATION 10 44 13.
3 NEW 45 MIN. FIRE RATED DOOR. SEE DOOR SCHEDULE AND
SPECIFICATIONS FOR ADDITIONAL INFORMATION. COORDINATE
DOOR AND FRAME WITH ACCESS CONTROL HARDWARE.
4 REMOVE EXISTING DOOR AND FRAME
5 NEW FURRING WALL AT EXTERIOR WALL TO ENCLOSE WINDOW.
MAINTAIN 1/2" GAP BETWEEN EXISTING WALL INTERIOR FACE AND
NEW STUDS. MODIFY/REMOVE INTERIOR WINDOW TRIM AS
REQUIRED. INSTALL WINDOW FILM AT ALL FURRED WINDOWS. SEE
06IN101 FOR MORE INFORMATION.
6 REMOVE EXISTING FLOORING, ADHESIVE AND WALL BASE.
7 ALL ITEMS/EQUIPMENT TO BE REMOVED FROM SPACE PRIOR TO
DEMO.
8 TELECOM ROOM TO BE OPEN TO DECK
9 PROVIDE TEMPORARY DUST TIGHT BARRIER AROUND WORK
AREA DURING ANY ACTIVITIES WHICH PRODUCE DUST - TYPICAL.
10 POTENTIAL ABATEMENT AT FLOOR FOR FLOOR PENETRATIONS.
REFER TO COVER SHEET FOR KNOWN ACM ITEMS WITHIN THIS
BUILDING.
11 REFER TO COVER SHEET FOR KNOWN ACM ITEMS WITHIN THIS
BUILDING.
12 UNBOLT EXISTING RACK IN PLACE FOR FLOOR DEMOLITION
13 ALL WALLS TO RECEIVE NEW PLYWOOD WHERE FEASIBLE,
COORDINATE WITHELECTRICAL DRAWINGS FOR FIXTURE
LOCATIONS
DOOR AND FRAME SCHEDULE
IDENTIFICATION DIMENSIONS PANEL FRAME DETAIL
FIRE RATING
HARDWARE
NOTESLEVEL ROOM NO. ROOM NAME DOOR NO. W1 H T TYPE MATERIAL FINISH GLAZING TYPE MATERIAL FINISH HEAD JAMB SILL GROUP ELECTRICAL
LEVEL 1 178 TELECOM ROOM 178 3' - 6" 8' - 0" 0' - 2" F HM P-2 NONE 1 HM P-2 C1/06A-401 E1/06A-401 F1/06IN101 45 MIN HW-SF-3F SEE SPEC 1.
LEVEL 2 233 TELECOM ROOM 233 3' - 0" 8' - 0" 0' - 2" F HM P-2 NONE 1 HM P-2 C1/06A-401 E1/06A-401 F1/06IN101 45 MIN HW-SF-3F SEE SPEC 1.
1/4" = 1'-0" D6
ARCHITECTURAL REFLECTED CEILING PLAN -
FIRST LEVEL - RM 178 - DEMO
1/4" = 1'-0" B6
ARCHITECTURAL REFLECTED CEILING PLAN -
FIRST LEVEL RM 178 - NEW
NOTE: FIRE RESISTANCE TEST FOR TWO HOUR RATED WALLS: UL
V438, UL U411
(TYPE B) TYPICAL PARTITION
MARK STUD WIDTH PRTN WIDTH DESIGN STC
B 2 1/2" 3/4" 45
1. SEE SPECIFICATIONS 08 71 00 FOR DOOR HARDWARE REQUIREMENTS. COORDINATE WITH ELECTRICAL.
NOTE: FIRE RESISTANCE TEST FOR ONE HOUR RATED WALLS: UL
U465
(TYPE A) TYPICAL PARTITION
MARK STUD WIDTH PRTN WIDTH DESIGN STC
A4 4" 5 1/4" 35
NOT TO SCALE
F6
EXISTING CONDITOINS RM 178
Revisions: Date:
Addendum 1 02/25/2026
(TYPE J) NON-RATED PARTITION
MARK STUD WIDTH PRTN WIDTH DESIGN STC
J2 2 1/2" 3 1/8" -
02/25/2026
KEYNOTES
GENERAL NOTES
EXISTING CONSTRUCTION TO REMAIN
EXISTING CONSTRUCTION TO BE DEMOLISHED
NEW CONSTRUCTION, WITH PARTITION TYPE
A
A. SEE GENERAL NOTES AND PLANS FOR TYPICAL GENERAL PROJECT
REQUIREMENTS AND PROJECT LOCATION DRAWINGS.
B. SEE INTERIOR FINISH DRAWINGS FOR ADDITIONAL FINISHES
INFORMATION.
C. SEE MECHANICAL AND ELECTRICAL DRAWINGS FOR ADDITIONAL
SYSTEMS INFORMATION.
D. NEW TELECOM ROOMS SHALL BE 1 HOUR FIRE AND SMOKE RATED
AND COMPLY WITH THE LATEST VA PHYSICAL SECURITY STANDARDS,
AND CAMPUS STANDARDS.
E. SEE TYPICAL WALL FRAMING DETAILS ON SHEET A-511.
F. SEE TYPICAL HEAD OF WALL DETAIL ON SHEET A-512.
G. SEE TYPICAL CEILING DETAILS ON SHEET A-531
H. ALL PHOTOS SHOWN REFLECT EXISTING CONDITIONS AS OF THE
DATE OF THIS DRAWING SET. CONTRACTOR SHALL FIELD VERIFY ALL
DIMENSIONS, CONDITIONS, AND SITE-SPECIFIC INFORMATION AT THE
TIME OF BIDDING.
I. CONTRACTOR IS RESPONSIBLE FOR ALL COSTS ASSOCIATED WITH
MOVING, STORING AND RETURNING FURNISHINGS AND EQUIPMENT
TO THE PROPOSED WORK AREA(S). ANY DISASSEMBLY AND
REASSEMBLY OF SYSTEMS FURNITURE IN THE PROPOSED WORK
AREAS IS THE RESPONSIBILITY OF THE CONTRACTOR AND MUST
FOLLOW THE MANUFACTURER'S WARRANTY.
6 7
3 5
G
6 7
CORRIDOR
200B200B
9' -1
1/
4"
5'-2 1/2"
06A-402
C8
TELECOM
ROOM
233233
TELECOM
ROOM
119 SF
PRIVATE
BATH
229A229A1 1
2 9 3 5
G
A 4 B
B
B
B
B
B
B
H W
-S F
-3 F
3'-4"
(EXTG VIF)
12'-3 3/4"
(E X
T G
V
IF
9'
-9
/2
CORRIDOR
200B200B
1'-0"
1111 1616
TELECOM
ROOM
233233
3 5
G
CORRIDOR
200B200B
SHARED
BATHROOM
234A234A
PRIVATE
BATH
229A229A
DATA
CLOSET
50 SF
PATIENT
TOILET
65 SF
DATA
CLOSET
233233
PATIENT
TOILET
232232
Room B30F-34B30F-34
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
TRIPLE C - The A/E Group
100 Pearl Street, 14th Floor
Hartford, CT 06103
MAT PERKINS
(860)-270-0753
A u to d e s k D o c s /3
C
R
.P ro je c t.
-2
-7
.E H
R M
.I U
.B e d fo rd
.M A
.R
/5
-2 -7
.B e d fo rd .E
H R
M .A
R C
H .B
R
.r v t
/2
/2
:3
:1
A
M
06A-402
ARCHITECTURAL ENLARGED VIEWS - SECOND
LEVEL
518-22-700
06/04/2025 M. Perkins K. McDermott
ISSUED FOR
CONSTRUCTION
EHRM INFRASTRUCTURE
UPGRADES
200 Springs Rd, Bedford, MA 01730
1 EXISTING WALLS TO BECOME 1 HR FIRE AND SMOKE-RATED. PATCH
AND SEAL ALL PENETRATIONS AS NECESSARY.
2 PROVIDE NEW FIRE EXTINGUISHER CABINET WITH A TYPE 2A:10B:C
CLEAN AGENT FIRE EXTINGUISHER LOCATED NO GREATER THAN 75
FEET AWAY FROM THE NEW TR. CONTRACTOR TO COORDINATE
THE NEW LOCATION WITH THE COR. CONTRACTOR SHALL BID A
NEW FEC FOR EACH TR IN THE SCOPE OF WORK. SEE
SPECIFICATION 10 44 13.
3 NEW 45 MIN. FIRE RATED DOOR AND FRAME. SEE DOOR SCHEDULE
AND SPECIFICATIONS FOR ADDITIONAL INFORMATION.
COORDINATE DOOR AND FRAME WITH ACCESS CONTROL
HARDWARE.
4 REMOVE EXISTING WALL AND FRAMING.
5 REMOVE EXISTING DOOR AND FRAME
6 REMOVE EXISTING FLOORING, ADHESIVE AND WALL BASE.
7 ALL ITEMS/EQUIPMENT TO BE REMOVED FROM SPACE PRIOR TO
DEMO.
8 PROVIDE TEMPORARY DUST TIGHT BARRIER AROUND WORK AREA
DURING ANY ACTIVITIES WHICH PRODUCE DUST - TYPICAL
9 AT NEW WALL INSTALLATIONS, CONTRACTOR TO PAINT NEW WALL
IN ITS ENTIRETY. INSTALL NEW WALL BASE AT ENTIRE WALL SPACE
OR APPROPRIATE TRANSITION LOCATION AS APPROVED BY THE
COR.
10 EXISTING PLUMBING, FIXTURES, AND ACCESSORIES TO BE
DEMOLISHED. COORDINATE WITH VA COR FOR ANY ITEMS THAT
ARE TO BE SALVAGED. REFER TO PLUMBING DRAWINGS FOR ALL
ASSOCIATED PLUMBING, PIPING AND FIXTURES TO BE
DEMOLISHED. PIPING IS TO BE DEMOLISHED BACK TO THE SOURCE.
11 REMOVE EXISTING CEILING AND LIGHTS. MODIFY AND/OR PROVIDE
ADDITIONAL SUPPORTS AS REQUIRED FOR EXISTING CEILING
ITEMS TO REMAIN
12 TELECOM ROOM TO BE OPEN TO DECK
13 AT NEW WALL INSTALLATIONS, CONTRACTOR TO INSTALL NEW
HANDRAIL TO MATCH EXISTING. COORDINATE WITH COR.
14 REMOVE EXISTING TILE AND ADHESIVES FROM WALLS. REPAIR,
PATCH AND PAINT WALLS AS REQUIRED.
15 REMOVE ALL WALL MOUNTED ACCESSORIES. COORDINATE WITH
COR FOR ANY ITEMS TO BE SALVAGED.
16 POTENTIAL ABATEMENT AT FLOOR FOR FLOOR PENETRATIONS.
REFER TO COVER SHEET FOR KNOWN ACM ITEMS WITHIN THIS
BUILDING.
1/4" = 1'-0" D8
ARCHITECTURAL FLOOR PLAN - SECOND
LEVEL - RM 232/233 - DEMO
1/32" = 1'-0" F8
SECOND FLOOR REFERENCE PLAN
1/4" = 1'-0" C8
ARCHITECTURAL FLOOR PLAN - SECOND
LEVEL - RM 233 - NEW
1/4" = 1'-0" D6
ARCHITECTURAL REFLECTED CEILING PLAN -
SECOND LEVEL - RM 232/233 - DEMO
1/4" = 1'-0" C6
ARCHITECTURAL REFLECTED CEILING PLAN -
SECOND LEVEL - RM 233 - NEW
NOT TO SCALE
F6
EXISTING CONDITIONS RM 233
Revisions: Date:
"FIRE-RATED WALLS"- ADDITIONAL NOTES:
1. CONDITIONS INDICATED TO SHOW DESIGN INTENT. THEY ARE NOT INTENDED TO BE PROPRIETARY. CONTRACTOR MAY EMPLOY SIMILAR A UL-APPROVED TOP-OF-WALL DESIGNS THAT ARE APPROPRIATE FOR CONDITIONS.
2. REFER TO SECTION 07 84 00 / FIRESTOPPING FOR ADDITIONAL REQUIREMENTS REGARDING HEAD-OF-WALL CONDITION FOR FIRE-RATED WALLS.
SLOTTED TOP
TRACK
STUD
DESIGN BASIS: UL-HW-D-0082
CONCRETE SLAB
DESIGN BASIS: UL-HW-D-0042
METAL DECK
(PERPENDICULAR TO FLUTES)
/8
DESIGN BASIS: UL-HW-D-0264
METAL DECK
(PARALLEL TO FLUTES)
1" 1" 2"x20 GA
STRAPS @ 16"
O.C.
DESIGN BASIS: UL-HW-D-0259
STEEL BEAM
20 GA Z-BARS
TO
ACCOMMODATE
SFRM
SPRAY-APPLIED
FIRE-RESISTIVE
MATERIAL
(SFRM)
SAB
1 OR 2 LAYERS OF GWB;
SEE WALL TYPE
FIRE STOP SEALANT
FIRE STOP JOINT
SPRAY
MINERAL WOOL
FORMING MATERIAL
/8
/8
FIRE STOP JOINT
SPRAY
SLOTTED TOP
TRACK
STUD
SAB
1 OR 2 LAYERS OF GWB;
SEE WALL TYPE
/8
MINERAL WOOL
FORMING MATERIAL
SLOTTED TOP
TRACK
STUD
CONCRETE SLAB METAL DECK
(PERPENDICULAR TO FLUTES)
/8
/8
METAL DECK
(PARALLEL TO FLUTES)
1" 1"
/8
SLOTTED TOP
TRACK
2"x20 GA
STRAPS @ 16"
O.C.
STEEL BEAM
/8
20 GA Z-BARS
TO
ACCOMMODATE
SFRM
SPRAY-APPLIED
FIRE-RESISTIVE
MATERIAL
(SFRM)
SAB
GWB
ACOUSTICAL SEALANT
CUT ONE LAYER GWB TO
FOLLOW PROFILE OF DECKING.
SEAL CONTINUOUSLY WITH
ACOUSTICAL SEALANT.
FILL FLUTE VOID W/
SAB
GWB SOUND AND
SMOKE CLOSURE
STRIP SECURE TO
STRUCTURE AND SEAL
WITH ACOUSTICAL
SEALANT
ACOUSTICAL
SEALANT (BOTH
SIDES)
STUD
SAB
GWB
ACOUSTICAL SEALANT
(BOTH SIDES)
"SMOKE PARTITIONS AND SOUND-CONTROL WALLS"- ADDITIONAL NOTES:
1. UPGRADE TO DETAIL "B4" WHERE WALL IS DESIGNATED WITH A FIRE-RESISTANCE RATING.
2. FILL VOIDS WITH SOUND ATTENUATION BATTS (SAB).
3. SOUND WALLS AND SMOKE PARTITIONS REQUIRE THAT AT LEAST ONE LAYER OF GWB BE CUT TO FOLLOW UNDULATING SURFACES OF SUPERSTRUCTURES INCLUDING BUT NOT LIMITED TO FLUTES METAL DECKING. JOINT GWB TO SUPERSTRUCTURE WITH A CONTINUOUS BEAD OF ACOUSTICAL SEALANT.
4. BUILDING CODE REQUIRES THAT "SMOKE PARTITIONS" BE SEALED TO STRUCTURE AS INDICATED TO SUCCESSFULLY "….LIMIT THE PASSAGE OF SMOKE….".
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
TRIPLE C - The A/E Group
100 Pearl Street, 14th Floor
Hartford, CT 06103
MAT PERKINS
(860)-270-0753
A u to d e s k D o c s /3
C
R
.P ro je c t.
-2
-7
.E H
R M
.I U
.B e d fo rd
.M A
.R
/5
-2 -7
.B e d fo rd .E
H R
M .A
R C
H .B
R
.r v t
/2
/2
:3
:1
A
M
06A-512
ARCHITECTURAL PARTITION HEAD DETAILS 518-22-700
06/04/2025 M. Perkins K. McDermott
ISSUED FOR
CONSTRUCTION
EHRM INFRASTRUCTURE
UPGRADES
200 Springs Rd, Bedford, MA 01730
3" = 1'-0" B4
HEAD-OF-WALL CONDITIONS - STUD WALLS - FIRE RATED WALLS
3" = 1'-0" E5
HEAD-OF-WALL CONDITIONS - STUD WALLS - SMOKE PARTITIONS AND SOUND CONTROL WALLS
NOTE:
STANDARD DETAILS APPLY TO TYPICAL CONSTRUCTION
TYPES AND ASSEMBLIES. NOT ALL DETAILS MAY BE
USED. CONTRACTOR SHALL VERIFY ACTUAL CONDITIONS
ON-SITE.
Revisions: Date:
Addendum 1 02/25/2026
EXISTING CONSTRUCTION TO REMAIN
EXISTING CONSTRUCTION TO BE DEMOLISHED
NEW CONSTRUCTION, WITH PARTITION TYPE
GENERAL INTERIOR NOTES
KEYNOTES
GENERAL FINISH NOTES:
1. REFER TO SPECIFICATIONS FOR ADDITIONAL MATERIAL AND
INSTALLATION REQUIREMENTS.
2. REFER TO THIS SHEET FOR FINISH LEGEND AND ROOM FINISH
SCHEDULE.
3. IF POSSIBLE PROVIDE MATERIALS FROM SAME PRODUCTION RUN
FOR CONSISTENCY.
SUBSTITUTION NOTES:
1. COLOR IS AN IMPORTANT PART OF THIS PROJECT. ANY COLOR
SUBSTITUTION WILL REQUIRE APPROVAL BY THE COR.
TRANSITION NOTES:
1. INSTALL TRANSITIONS AT ALL DISSIMILAR FLOOR MATERIALS.
2. FOR ALL FLOOR FINISH AND PATTERN TRANSITIONS THAT OCCUR AT
DOORWAYS, TRANSITION MATERIALS AT CENTERLINE OF DOOR
WHEN DOOR PANEL IS IN THE CLOSED POSITION.
SIGNAGE NOTES:
1. REFER TO THIS SHEET SERIES SHEETS FOR SIGNAGE INFORMATION,
REFER TO SPECIFICATIONS FOR ADDITIONAL SIGNAGE,
IDENTIFICATION AND SYSTEMS/EQUIPMENT LABELING
REQUIREMENTS.
PAINTING NOTES:
1. ALL ADHESIVES AND PAINT TO BE LOW VOC/ODOR.
2. UNLESS OTHERWISE INDICATED, DO NOT PAINT FACTORY-FINISHED
ITEMS OR INSTALLER FINISHED ITEMS.
3. COORDINATE APPLICATIONS OF PAINTS AND ADHESIVES WITH COR.
PROVIDE SEALED ENVIRONMENT DURING HVAC FLUSH OUT PERIOD
TO ENSURE ODORS DO NOT TRANSMIT TO ADJACENT SPACES.
CODE NOTES:
1. ALL INTERIOR FINISHES SHALL HAVE FLAME SPREAD IN COMPLIANCE
WITH IBC 2024 803.13 INTERIOR WALL AND CEILING FINISH
REQUIREMENTS BY OCCUPANCY.
INSTALLATION NOTES:
1. PROVIDE BACKING FOR ALL WALL MOUNTED EQUIPMENT.
MATERIAL FLOOR CHANGE (REFER TO THIS SHEET FOR DETAILS)
INTERIOR FINISH SYMBOLS
SEALED CONCRETE WITH STATIC DISSIPATIVE COATING (C-1/SDC)
INTERIOR FINISHES
PAINT
FIELD
CALIFORNIA PAINTS*
TO MATCH BENJAMIN MOORE
MANCHESTER TAN HC-81
ARCHITECT/ENGINEERS:
INTERIOR FINISHES
Drawing Title
Approved: Project Director
Project Title
Location
Date Checked Drawn
NB KLM
Project Number
Board Number
Office of Construction and Facilities Management
*BASIS OF DESIGN
**MATCH EXISTING CAMPUS PAINT COLORS
EHRM INFRASTRUCTURE
UPGRADES
518-22-700
200 Springs Road, Bedford, MA 01730
EDITH NOURSE MEMORIAL VETERANS HOSPITAL
P-1
DIGITAL IMAGES MAY HAVE COLOR INACCURACIES, REFER
TO ACTUAL SAMPLE FOR TRUEST COLOR DEPICTION
PAINT
METAL DOORS & TRIM
CALIFORNIA PAINTS*
TO MATCH BENJAMIN MOORE
WHITE DOWN OC-131
P-2
WALL BASE
JOHNSONITE*
BEIGE 49
RB-1
PAPER INSERT CARRIER, MAGNETIC
MOUNT, WITH NON-GLARE LENS
TEXT: 5/8"H LASER-PRINTED TEXT,
HELVETICA MEDIUM
COLOR: TO MATCH STATION
STANDARDS
1-1/2" x 1/32" ADA
TACTILE NUMERALS
AND GRADE II BRAILLE234
9"
Restricted Access
5-3/16" X 9" CLEAR
ACETATE INSERT W/
COPY
9"X9" MAGNETICALLY
REMOVABLE SIGN
(ONE-PIECE)
RED SYMBOL AND
BLACK TEXT
1/2" 9" 1/2"
/2
/2
QUARTER-ROUND
SILVER FRAME
EXISTING FLOORING
TO BE REMOVED
TOP OF SLAB
EXISTING
FLOORING TO
REMAIN, EXISTING
ROOM SIDE CONCRETE FLOOR,
EXISTING
RESILIENT BASE AS
SCHEDULED, EACH
SIDE OF NEW WALL
INSTALL 3/4"
PLYWOOD TO 8'AFF,
MOUNT BOTTOM OF
PLYWOOD 12" AFF
ADJACENT SPACE
TELECOM
ROOM SIDE
PARTITION AS SCHEDULED
SEALED CONCRETE
LOCATION OF FLOOR
FINISH CHANGE;
SEAM OR ADAPTER
TRANSITION SHALL
OCCUR AT
CENTERLINE OF
DOOR IN CLOSED
POSITION
DOOR AS SCHEDULED
EXISTING FLOORING
TOP OF SLAB
CORRIDOR SIDE
DOOR FRAME BEYOND
C CENTER LINE OF DOORL
TRANSITION STRIP
(TR-1) OR EQUAL,
REFER TO SCHEDULE
FOR INFORMATION
TELECOM ROOM SIDE
SIGNAGE REFERENCES
VA SIGNAGE DESIGN MANUAL
SIGN VENDOR TO REFERENCE VA SIGNAGE DESIGN MANUAL FOR COMPLETE
SPECIFICATIONS
https://www.cfm.va.gov/til/spclRqmts.asp#SIGN
SIGN SYMBOL LEGEND
IN-08.02
IN-04.01A
2 5 6
IN-01.31
TELECOM ROOM FINISH DIAGRAM,
CONTRACTOR TO REFERENCE
ARCHITECTURE FOR ACTUAL WALL
CONSTRUCTION LOCATIONS
F1
06IN101
TYP.
F3
06IN101
TYP.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
TRIPLE C - The A/E Group
100 Pearl Street, 14th Floor
Hartford, CT 06103
MAT PERKINS
(860)-270-0753
A u to d e s k D o c s /3
C
R
.P ro je c t.
-2
-7
.E H
R M
.I U
.B e d fo rd
.M A
.R
/5
-2 -7
.B e d fo rd .E
H R
M .A
R C
H .B
R
.r v t
/2
/2
:3
:1
A
M
06IN101
INTERIOR FINISH PLAN, SIGNAGE & SCHEDULES 518-22-700
06/04/2025 M. Perkins K. McDermott
ISSUED FOR
CONSTRUCTION
EHRM INFRASTRUCTURE
UPGRADES
200 Springs Rd, Bedford, MA 01730
NTS
C1
COLOR BOARD
ROOM FINISH SCHEDULE
LEVEL NO. NAME
FLOOR WALLS CEILING
NOTESFINISH BASE
NORTH EAST SOUTH WEST
MATERIAL FINISHMATERIAL FINISH MATERIAL FINISH MATERIAL FINISH MATERIAL FINISH
LEVEL 1 178 TELECOM ROOM C-1/SDC RB-1 GWB P-1/WD GWB P-1/WD GWB P-1/WD GWB P-1/WD OPEN
LEVEL 2 233 TELECOM ROOM C-1/SDC RB-1 GWD P-1/WD GWD P-1/WD GWD P-1/WD GWD P-1/WD OPEN
BUILDING SIGNAGE SCHEDULE
VERSION
TYPE COUNT DESCRIPTION DETAIL LOCATION REFERENCE
ADA
BRAILLE TEXT COLOR BACKGROUND COLOR
DIMENSIONS
CommentsSIGN_HEIGHT SIGN_WIDTH MOUNTING HEIGHT
IN-01.31 2 FIRE IDENTIFICATION SIGN E5 /06IN101 FEC REFER TO PAGE 429 OF SIGNAGE DESIGN
MANUAL DATED 05/2023
NO WHITE RED 0' - 9" 0' - 9" 6' - 8" INSTALLED AT FIRE EXTINGUISHER CABINETS AT ALL
NEW TELECOM ROOMS
IN-04.01A 2 PRIMARY ROOM IDENTIFICATION
WITH INSERT
E3 /06IN101 PUBLIC SPACES REFER TO PAGE 261 OF SIGNAGE DESIGN
MANUAL DATED 05/2023
YES REFERENCE EXISTING
CAMPUS STANDARDS
REFERENCE EXISTING
CAMPUS STANDARDS
0' - 9" 0' - 9" 5' - 0" INSTALLED AT ALL NEW TELECOM ROOMS
IN-08.02 2 PROHIBIT INSTRUCTIONAL AND
CONTROL
E1/ 06IN101 TELECOM ROOM REFER TO PAGE 279 OF SIGNAGE DESIGN
MANUAL DATED 05/2023
NO REFERENCE EXISTING
CAMPUS STANDARDS
REFERENCE EXISTING
CAMPUS STANDARDS
0' - 9 1/2" 0' - 8 1/2" 5' - 9" INSTALLED AT ALL NEW TELECOM ROOMS MOUNTED
DIRECTLY ABOVE ROOM NAME SIGN
Grand total: 6
3" = 1'-0" E3
IN-04.01A SIGN DETAIL - PRIMARY ROOM
IDENTIFICATION
3" = 1'-0"
E1
IN-08.02 SIGN DETAIL - PROHIBIT
INSTRUCTIONAL AND CONTROL
3" = 1'-0"
E5
IN-01.31 SIGN DETAIL - FIRE EQUIPMENT IDENTIFICATION SIGN
6" = 1'-0" F3
RESILIENT BASE (TOE BASE)
6" = 1'-0"
F1
THRESHOLD - CONCRETE TO EXISTING FLOORING
FINISH LEGEND
SYMBOL FINISH TYPE MANUFACTURER COLLECTION STYLE / TYPE COLOR SIZE SPEC SECTION NOTES
C-1/SDC SEALED CONCRETE WITH STATIC DISSIPATIVE COATING SEALED CONCRETE* - - - - - TELECOM ROOM SPACE TO RECEIVE STATIC CONTROL CONCRETE SEALER
F-1 WINDOW FILM 3M* FASARA 7725SE-324 FROSTED CRYSTAL - 08 87 33
P-1 PAINT CALIFORNIA PAINTS* - EGGSHELL TO MATCH BENJAMIN MOORE MANCHESTER TAN HC-81 - 09 91 00 FIELD
P-2 PAINT CALIFORNIA PAINTS* - SEMI-GLOSS TO MATCH BENJAMIN MOORE WHITE DOWN OC-131 - 09 91 00 METAL DOORS & TRIM
RB-1 RESILIENT BASE JOHNSONITE* TRADITIONAL TOE BASE BEIGE 49 4" 09 65 13
TR-1 TRIM SCHLUTER * - RENO-U SATIN ANODIZED ALUMINUM - 09 30 13 FLOOR TRANSITION
WD PLYWOOD FIRE TREATED PLYWOOD* - - HIGH GLOSS WHITE MPI (MASTER PAINTERS INSTITUTE)
67 OR SIM
4' X 8' - PLYWOOD TO BE PAINTED WITH 2 COATS OF FIRE RESISTANT PAINT; FIRE
RATING STAMPS SHALL NOT BE PAINTED OVER
1 REMOVE EXISTING FLOORING, ADHESIVES, AND INSTALL NEW WALL
BASE
2 EXISTING WALLS ARE TO BE PATCHED AND PAINTED. SEE ROOM
FINISH SCHEDULE THIS SHEET FOR FINISHES.
3 ALL WALLS TO RECEIVE NEW PLYWOOD, COORDINATE WITH
ELECTRICAL DRAWINGS FOR FIXTURE LOCATIONS.
4 PROVIDE NEW ROOM SIGNAGE, SEE SIGNAGE SCHEDULE THIS
SHEET
5 REFER TO ARCHITECTURAL PLANS FOR DETAILED ROOM
CONFIGURATION INFORMATION
6 TELECOM ROOM SPACE TO RECEIVE STATIC CONTROL CONCRETE
SEALER
7 AT NEW WALL INSTALLATIONS, CONTRACTOR TO PAINT NEW WALL
IN ITS ENTIRETY. INSTALL NEW WALL BASE AT ENTIRE WALL SPACE
OR APPROPRIATE TRANSITION LOCATION AS APPROVED BY THE
COR.
REFER TO THIS SHEET FOR ROOM FINISH SCHEDULE & FINISH LEGEND
1/2" = 1'-0" F7
TELECOM ROOM FINISH DIAGRAM
*Materials are approved as basis of design, all material substitutions are subject to owner approval.
Contractor to provide VA Interior Design Department with samples of all specified finish materials.
VA COR/ Interior Design department shall approve all finishes prior to installation.
NTS
C5
EXAMPLE OF EXISTING SIGNAGE
Revisions: Date:
Addendum 1 02/25/2026
1 1
02/25/2026
EXISTING CONCRETE
FLOOR WITH STATIC
DISSIPATIVE (C-1/SDC)
LOCATION OF FLOOR
FINISH CHANGE;
SEAM OR ADAPTER
TRANSITION SHALL
OCCUR AT
CENTERLINE OF
DOOR IN CLOSED
POSITION
DOOR AS SCHEDULED
EXISTING FLOORING
TOP OF SLAB
CORRIDOR SIDE
DOOR FRAME BEYOND
C CENTER LINE OF DOORL
TRANSITION STRIP
(TR-1) OR EQUAL,
REFER TO SCHEDULE
FOR INFORMATION
TELECOM ROOM SIDE
6" = 1'-0" F1
THRESHOLD - CONCRETE TO EXISTING FLOORING
EXISTING FLOORING
TO BE REMOVED
TOP OF SLAB
EXISTING
FLOORING TO
REMAIN, EXISTING
ROOM SIDE EXISTING CONCRETE
FLOOR WITH STATIC
DISSIPATIVE (C-1/SDC)
RESILIENT BASE AS
SCHEDULED, EACH
SIDE OF NEW WALL
INSTALL 3/4"
PLYWOOD, MOUNT
BOTTOM OF
PLYWOOD 12" AFF
ADJACENT SPACE
TELECOM
ROOM SIDE
PARTITION AS SCHEDULED
6" = 1'-0" F4
RESILIENT BASE (TOE BASE)
| Sheets |
| 06A-401 - ARCHITECTURAL ENLARGED VIEWS - FIRST LEVEL |
| 06A-402 - ARCHITECTURAL ENLARGED VIEWS - SECOND LEVEL |
| 06A-512 - ARCHITECTURAL PARTITION HEAD DETAILS |
| 06IN101 - INTERIOR FINISH PLAN, SIGNAGE & SCHEDULES |