Amend 5 - ATT 9 -518-22-700.Bedford.EHRM.IFC.Add1.B04.20260225.pdf
PDF 4 MB Posted
- Solicitation number
- 36C77626R0003
About this file
This is an architectural drawing set for EHRM Infrastructure Upgrades at the Edith Nourse Rogers Memorial Veterans Hospital in Bedford, Massachusetts (Project 518-22-700). The drawings detail the construction of new telecom rooms across three building levels (Basement, Level 1, and Level 2) with associated modifications to existing spaces.
The project requires construction of three new telecom rooms (B05, 141, and 244) sized between 95-99 square feet each. Each room must be constructed with 1-hour fire and smoke-rated partition walls that comply with VA Physical Security Standards and campus standards. New 45-minute fire-rated doors and frames are required for each room, with hollow metal construction specified. All walls are to receive A/C grade, fire-treated 3/4" plywood adhered to existing wall assemblies, with plywood mounting at 12" above finished floor. Rooms shall include new fire extinguisher cabinets (Type 2A: 10B: C clean agent) positioned within 75 feet of each telecom room. Interior finishes include sealed concrete with static dissipative coating (C-1/SDC) for floors, Johnsonite Beige 49 wall base, drywall walls painted with California Paints to match Benjamin Moore Manchester Tan HC-81, and open ceilings. Room signage must comply with VA Signage Design Manual specifications, including ADA-compliant room identification signs and prohibit instructional/control signs. The contractor is responsible for all costs associated with moving, storing, and returning furnishings and equipment, including disassembly and reassembly of systems furniture per manufacturer warranty. All dimensions, conditions, and site-specific information must be field-verified at time of bidding. Known ACM items within the building are referenced on the cover sheet, with potential abatement required at floor penetrations.
View the file
Other files
Show 40 more
Latest 50 of 105 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SHEET SYMBOL LEGEND
KEYNOTES
GENERAL NOTES
EXISTING CONSTRUCTION TO REMAIN
EXISTING CONSTRUCTION TO BE DEMOLISHED
NEW CONSTRUCTION, WITH PARTITION TYPE
A
A. SEE GENERAL NOTES AND PLANS FOR TYPICAL GENERAL PROJECT
REQUIREMENTS AND PROJECT LOCATION DRAWINGS.
B. SEE INTERIOR FINISH DRAWINGS FOR ADDITIONAL FINISHES
INFORMATION.
C. SEE MECHANICAL AND ELECTRICAL DRAWINGS FOR ADDITIONAL
SYSTEMS INFORMATION.
D. NEW TELECOM ROOMS SHALL BE 1 HOUR FIRE AND SMOKE RATED
AND COMPLY WITH THE LATEST VA PHYSICAL SECURITY STANDARDS,
AND CAMPUS STANDARDS.
E. SEE TYPICAL WALL FRAMING DETAILS ON SHEET A-511.
F. SEE TYPICAL HEAD OF WALL DETAIL ON SHEET A-512.
G. SEE TYPICAL CEILING DETAILS ON SHEET A-531
H. ALL PHOTOS SHOWN REFLECT EXISTING CONDITIONS AS OF THE
DATE OF THIS DRAWING SET. CONTRACTOR SHALL FIELD VERIFY ALL
DIMENSIONS, CONDITIONS, AND SITE-SPECIFIC INFORMATION AT THE
TIME OF BIDDING.
I. CONTRACTOR IS RESPONSIBLE FOR ALL COSTS ASSOCIATED WITH
MOVING, STORING AND RETURNING FURNISHINGS AND EQUIPMENT
TO THE PROPOSED WORK AREA(S). ANY DISASSEMBLY AND
REASSEMBLY OF SYSTEMS FURNITURE IN THE PROPOSED WORK
AREAS IS THE RESPONSIBILITY OF THE CONTRACTOR AND MUST
FOLLOW THE MANUFACTURER'S WARRANTY.
PARTITION RATING GRAPHICS:
4 HR FIRE BARRIER
3 HR FIRE BARRIER
2 HR FIRE & SMOKE BARRIER
2 HR FIRE BARRIER
2 HR FIRE BARRIER/SHAFT
1 HR FIRE & SMOKE BARRIER
1 HR FIRE BARRIER
1 HR FIRE BARRIER/SHAFT
SMOKE PARTITION (NON RATED)
NON RATED
PARTITION RATING GRAPHIC DESIGNATION: PRIORITY
1 HIGHEST
5 LOWEST
PARTITIONS REQUIRED TO BE SMOKE RESISTANT, FIRE
RESISTANT, OR BOTH FIRE AND SMOKE RESISTANT ARE SHOWN
GRAPHICALLY ON PLANS WITH HATCH PATTERNS.
G
TELECOM
ROOM
B05
96 SF
TOILET
B07FB07F
G
TELECOM
ROOM
B05
96 SF
TOILET
B07FB07F
OPEN
WORKSTATIONS
B07B07
STAIR
2-B2-B
CORRIDOR
B43B43
B
B
B
B
B05
HW-SH-3F
04A-400
B8
TELECOM
ROOM
B05
96 SF
IT
B05B05
TELECOM
ROOM
B05B05
ACOUSTICAL OR RATED
FLEXIBLE SEALANT
FLOOR LINE
ADD ONE LAYER OF 5/8" GWB,
ONE-SIDE WITH APPROVED UL
SETTING COMPOUND BETWEEN
LAYERS AND FASTENED TO
WALL AS REQUIRED, AT
EXISTING GWB WALL
ASSEMBLIES
STRUCTURAL DECK
EXISTING METAL STUDS AND
BATT INSULATION TO REMAIN
A/C GRADE, 3/4" FIRE-TREATED
PLYWOOD, ADHERED TO CONCRETE
AT EXISTING CONCRETE WALL
ASSEMBLIES
BOTTOM OF PLYWOOD
TO BE AT 12" AFF
UL DESIGN V497
1-HOUR PARTITION RATED FROM BOTH SIDES
EXISTING GWB OR
CONCRETE WALL
ASSEMBLY, WHERE OCCURS
SIDE OF
EXISTING
ROOM OR
CORRIDOR TO
REMAIN
04A-512
D5
04A-512
B5
B1
TYPICAL FRAME
H E
IG
H
T
2" WIDTH 2"
B3
FRAME TYPE ELEVATIONS DOOR TYPE ELEVATIONS
F
FLUSH
1/2" 1/2"
VARIES
SEE PLAN
WALL - SEE PLAN
FOR TYPE
SEALANT - EA. SIDE
& ALL AROUND,
TYP.
HOLLOW METAL
FRAME
/2
V
A R
IE
S
S E
E P
L A
N
/2
UNO
4" 2"
ADJACENT WALL
WHERE OCCURS
SEALANT - EA SIDE &
ALL AROUND, TYP.
HOLLOW METAL FRAME
WALL - SEE PLAN
FOR TYPE
LINE OF
STRUCTURE
LINE OF
STRUCTURE
09 29 00
SOUND ATTENUATION BATTS
(SAB), WHERE OCCURS
NOTE:
IF PARTITION TYPE IS USED IN A
CHASE WALL CONDITION, PROVIDE
CROSS BRACING GUSSETS AT 48"
O.C. MAX VERTICALLY. FABRICATED
FROM 6" MTL STUDS.
6”
09 29 00
5/8" GWB
09 29 00
SAB RETAINER STRAP
WHERE SAB OCCURS
CEILING
07 92 00
SEALANT
09 22 16
METAL STUDS
04A-512
B5
04A-512
D5
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
TRIPLE C - The A/E Group
100 Pearl Street, 14th Floor
Hartford, CT 06103
MAT PERKINS
860-270-0753 mat.perkins@triplecaeg.com
A u to d e s k D o c s /3
C
R
.P ro je c t.
-2
-7
.E H
R M
.I U
.B e d fo rd
.M A
.R
/5
-2 -7
.B e d fo rd .E
H R
M .A
R C
H .B
R
.r v t
/2
/2
:4
:2
A
M
04A-400
ARCHITECTURAL ENLARGED VIEWS - BASEMENT
LEVEL
518-22-700
05/06/2025 M. Perkins K. McDermott
ISSUED FOR
CONSTRUCTION
EHRM INFRASTRUCTURE
UPGRADES
200 Springs Rd, Bedford, MA 01730
1 NEW 45 MIN. FIRE RATED DOOR AND FRAME. SEE DOOR SCHEDULE
AND SPECIFICATIONS FOR ADDITIONAL INFORMATION. MODIFY
DOOR AS REQUIRED FOR NEW ACCESS CONTROL HARDWARE.
2 PROVIDE NEW FIRE EXTINGUISHER CABINET WITH A TYPE 2A: 10B:
C CLEAN AGENT FIRE EXTINGUISHER LOCATED NO GREATER THAN
75 FEET AWAY FROM THE NEW TR. CONTRACTOR TO COORDINATE
THE NEW LOCATION WITH THE COR. CONTRACTOR SHALL BID A
NEW FEC FOR EACH TR IN THE SCOPE
3 TELECOM ROOM TO BE OPEN TO DECK ABOVE
4 EXISTING DOOR AND DOOR FRAME TO BE REMOVED
5 EXISTING CEILING AND LIGHTS TO REMAIN. MODIFY AND/OR
PROVIDE ADDITIONAL SUPPORTS AS REQUIRED FOR EXISTING
CEILING ITEMS TO REMAIN AT NEW WALL INSTALLATION.
6 PROVIDE TEMPORARY DUST TIGHT BARRIER AROUND WORK AREA
DURING ACTIVITIES WHICH PRODUCE DUST
7 EXISTING WALL TO BECOME 1 HOUR FIRE AND SMOKE-RATED.
PATCH AND SEAL ALL PENETRATIONS AS NECESSARY.
8 REFER TO COVER SHEET FOR KNOWN ACM ITEMS WITHIN THIS
BUILDING.POTENTIAL ABATEMENT AT FLOOR FOR FLOOR
PENETRATIONS. REFER TO COVER SHEET FOR KNOWN ACM ITEMS
WITHIN THIS BUILDING.
9 ALL WALLS TO RECEIVE NEW PLYWOOD WHERE FEASIBLE,
COORDINATE WITH
ELECTRICAL DRAWINGS FOR FIXTURE LOCATIONS
1/4" = 1'-0" D8
ARCHITECTURAL FLOOR PLAN - BASEMENT
LEVEL - RM B05 - DEMO
1/4" = 1'-0" B8
ARCHITECTURAL FLOOR PLAN - BASEMENT
LEVEL - RM B05 - NEW
1/32" = 1'-0" F5
BASEMENT REFERENCE PLAN
1/4" = 1'-0" B5
ARCHITECTURAL REFLECTED CEILING PLAN -
BASEMENT LEVEL - RM B05 - DEMO
1/4" = 1'-0" B6
ARCHITECTURAL REFLECTED CEILING PLAN -
BASEMENT LEVEL - RM B05 - NEW
NOTE: FIRE RESISTANCE TEST FOR TWO HOUR RATED WALLS: UL
V438, UL U411
(TYPE B) TYPICAL PARTITION
MARK STUD WIDTH PRTN WIDTH DESIGN STC
B 2 1/2" 3/4" 45
1/4" = 1'-0" C1
WRAPPED FRAME TYPES ELEVATIONS
3" = 1'-0" B1
HOLLOW METAL HEAD DETAIL
3" = 1'-0"
B3
HOLLOW METAL JAMB DETAIL
DOOR AND FRAME SCHEDULE
IDENTIFICATION DIMENSIONS PANEL FRAME DETAIL
FIRE RATING
HARDWARE
NOTESLEVEL ROOM NO. ROOM NAME DOOR NO. W1 H T TYPE MATERIAL FINISH GLAZING UNDERCUT TYPE MATERIAL FINISH HEAD JAMB SILL GROUP ELECTRICAL
BASEMENT B05 TELECOM ROOM B05 3' - 0" 7' - 0" 1 3/4" HM P-2 NONE 3/8" 1 HM P-2 F3/04A-402 F1/04A-402 F1/04IN101 45 MIN HW-SH-3F SEE SPEC 1
LEVEL 1 141 TELECOM ROOM 141 3' - 0" 7' - 0" 1 3/4" F HM P-2 NONE 3/8" 1 HM P-2 F3/04A-402 F1/04A-402 F1/04IN101 45 MIN HW-SH-3F SEE SPEC 1
LEVEL 2 244 TELECOM ROOM 244 3' - 0" 7' - 0" 1 3/4" F HM P-2 NONE 3/8" 1 HM P-2 F3/04A-402 F1/04A-402 F1/04IN101 45 MIN HW-SH-3F SEE SPEC 1
1. SEE SPECIFICATIONS 08 71 00 FOR DOOR HARDWARE REQUIREMENTS. COORDINATE WITH ELECTRICAL.
NOT TO SCALE
F3
EXISTING CONDITIONS FOR RM B05
Revisions: Date:
Addendum 1 02/25/2026
(TYPE J) NON-RATED PARTITION
MARK STUD WIDTH PRTN WIDTH DESIGN STC
J2 2 1/2" 3 1/8" -
02/25/2026
UP
KEYNOTES
GENERAL NOTES
EXISTING CONSTRUCTION TO REMAIN
EXISTING CONSTRUCTION TO BE DEMOLISHED
NEW CONSTRUCTION, WITH PARTITION TYPE
A
A. SEE GENERAL NOTES AND PLANS FOR TYPICAL GENERAL PROJECT
REQUIREMENTS AND PROJECT LOCATION DRAWINGS.
B. SEE INTERIOR FINISH DRAWINGS FOR ADDITIONAL FINISHES
INFORMATION.
C. SEE MECHANICAL AND ELECTRICAL DRAWINGS FOR ADDITIONAL
SYSTEMS INFORMATION.
D. NEW TELECOM ROOMS SHALL BE 1 HOUR FIRE AND SMOKE RATED
AND COMPLY WITH THE LATEST VA PHYSICAL SECURITY STANDARDS,
AND CAMPUS STANDARDS.
E. SEE TYPICAL WALL FRAMING DETAILS ON SHEET A-511.
F. SEE TYPICAL HEAD OF WALL DETAIL ON SHEET A-512.
G. SEE TYPICAL CEILING DETAILS ON SHEET A-531
H. ALL PHOTOS SHOWN REFLECT EXISTING CONDITIONS AS OF THE
DATE OF THIS DRAWING SET. CONTRACTOR SHALL FIELD VERIFY ALL
DIMENSIONS, CONDITIONS, AND SITE-SPECIFIC INFORMATION AT THE
TIME OF BIDDING.
I. CONTRACTOR IS RESPONSIBLE FOR ALL COSTS ASSOCIATED WITH
MOVING, STORING AND RETURNING FURNISHINGS AND EQUIPMENT
TO THE PROPOSED WORK AREA(S). ANY DISASSEMBLY AND
REASSEMBLY OF SYSTEMS FURNITURE IN THE PROPOSED WORK
AREAS IS THE RESPONSIBILITY OF THE CONTRACTOR AND MUST
FOLLOW THE MANUFACTURER'S WARRANTY.
PARTITION RATING GRAPHICS:
4 HR FIRE BARRIER
3 HR FIRE BARRIER
2 HR FIRE & SMOKE BARRIER
2 HR FIRE BARRIER
2 HR FIRE BARRIER/SHAFT
1 HR FIRE & SMOKE BARRIER
1 HR FIRE BARRIER
1 HR FIRE BARRIER/SHAFT
SMOKE PARTITION (NON RATED)
NON RATED
PARTITION RATING GRAPHIC DESIGNATION: PRIORITY
1 HIGHEST
5 LOWEST
PARTITIONS REQUIRED TO BE SMOKE RESISTANT, FIRE
RESISTANT, OR BOTH FIRE AND SMOKE RESISTANT ARE SHOWN
GRAPHICALLY ON PLANS WITH HATCH PATTERNS.
TELECOM
ROOM
99 SF
04A-401
B8
TELECOM
ROOM
99 SF
(EXTG VIF)
13'-1 1/2"
(E X
T G
V
IF
8'
-0
HW-SH-3F
TYP.
K
B
B
B
B
B
EXAM RM
B19EB19E
J2
K
EXAM RM
143143
SOCIAL
RM
101 SF
EXAM RM
143143
SOCIAL
RM
141141
TELECOM
ROOM
141141
EXAM RM
B19EB19E
TELECOM
ROOM
95 SF
04A-401
B4
K
NURSE
MANAGER
OFFICE
246246
CLINICAL
PSYCHOLOGIST
97 SF
TELECOM
ROOM
95 SF
HW-SH-3F
(E X
T G
V
IF
8'
-0
(EXIST VIF)
13'-0"
K
B
NURSE
MANAGER
OFFICE
246246
B
B
B B
B
J2
TELECOM
ROOM
244244
NURSE
MANAGER
OFFICE
246246
NURSE
MANAGER
OFFICE
246246
CLINICAL
PSYCHOLOGIST
244244
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
TRIPLE C - The A/E Group
100 Pearl Street, 14th Floor
Hartford, CT 06103
MAT PERKINS
860-270-0753 mat.perkins@triplecaeg.com
A u to d e s k D o c s /3
C
R
.P ro je c t.
-2
-7
.E H
R M
.I U
.B e d fo rd
.M A
.R
/5
-2 -7
.B e d fo rd .E
H R
M .A
R C
H .B
R
.r v t
/2
/2
:4
:2
A
M
04A-401
ARCHITECTURAL ENLARGED VIEWS - FIRST &
SECOND LEVEL
518-22-700
05/06/2025 M. Perkins K. McDermott
ISSUED FOR
CONSTRUCTION
EHRM INFRASTRUCTURE
UPGRADES
200 Springs Rd, Bedford, MA 01730
1/32" = 1'-0" F6
FIRST LEVEL REFERENCE PLAN
1/4" = 1'-0" B8
ARCHITECTURAL FLOOR PLAN - FIRST LEVEL
- RM 141 - NEW
1/4" = 1'-0" D8
ARCHITECTURAL FLOOR PLAN - FIRST LEVEL
- RM 141 - DEMO
1 NEW 45 MIN. FIRE RATED DOOR AND FRAME. SEE DOOR SCHEDULE
AND SPECIFICATIONS FOR ADDITIONAL INFORMATION. MODIFY
DOOR AS REQUIRED FOR NEW ACCESS CONTROL HARDWARE.
2 PROVIDE NEW FIRE EXTINGUISHER CABINET WITH A TYPE 2A: 10B: C
CLEAN AGENT FIRE EXTINGUISHER LOCATED NO GREATER THAN 75
FEET AWAY FROM THE NEW TR. CONTRACTOR TO COORDINATE THE
NEW LOCATION WITH THE COR. CONTRACTOR SHALL BID A NEW
FEC FOR EACH TR IN THE SCOPE
3 TELECOM ROOM TO BE OPEN TO DECK ABOVE
4 REMOVE EXISTING ACOUSTICAL CEILING AND LIGHTS. MODIFY
AND/OR PROVIDE ADDITIONAL SUPPORTS AS REQUIRED FOR
EXISTING CEILING ITEMS TO REMAIN.
5 PROVIDE TEMPORARY DUST TIGHT BARRIER AROUND WORK AREA
DURING ACTIVITIES WHICH PRODUCE DUST
6 EXISTING WALL TO BECOME 1 HOUR FIRE AND SMOKE-RATED.
PATCH AND SEAL ALL PENETRATIONS AS NECESSARY.
7 REMOVE EXISTING FLOORING, ADHESIVES, AND WALL BASE
8 REMOVE EXISTING DOOR AND FRAME
9 NEW FURRING WALL AT EXTERIOR WALL TO ENCLOSE WINDOW.
MAINTAIN 1/2" GAP BETWEEN EXISTING WALL INTERIOR FACE AND
NEW STUDS. MODIFY/ REMOVE INTERIOR WINDOW TRIM AS
REQUIRED. INSTALL WINDOW FILM AT ALL FURRED WINDOWS. SEE
04IN101 FOR MORE INFORMATION.
10 POTENTIAL ABATEMENT AT FLOOR FOR FLOOR PENETRATIONS.
REFER TO COVER SHEET FOR KNOWN ACM ITEMS WITHIN THIS
BUILDING.
1/4" = 1'-0" D6
ARCHITECTURAL REFLECTED CEILING PLAN -
FIRST LEVEL - RM 141 - DEMO
1/4" = 1'-0" B6
ARCHITECTURAL REFLECTED CEILING PLAN -
FIRST LEVEL - RM 141 - NEW
1/32" = 1'-0" F2
SECOND LEVEL REFERENCE PLAN
1/4" = 1'-0" D4
ARCHITECTURAL FLOOR PLAN - SECOND
LEVEL - RM 244 - DEMO
1/4" = 1'-0" B4
ARCHITECTURAL FLOOR PLAN - SECOND
LEVEL - RM 244 - NEW
1/4" = 1'-0" D2
ARCHITECTURAL REFLECTED CEILING PLAN -
SECOND LEVEL - RM 244 - DEMO
1/4" = 1'-0" B2
ARCHITECTURAL REFLECTED CEILING PLAN -
SECOND LEVEL - RM 244 - NEW
Revisions: Date:
Addendum 1 02/25/2026
"FIRE-RATED WALLS"- ADDITIONAL NOTES:
1. CONDITIONS INDICATED TO SHOW DESIGN INTENT. THEY ARE NOT INTENDED TO BE PROPRIETARY. CONTRACTOR MAY EMPLOY SIMILAR A UL-APPROVED TOP-OF-WALL DESIGNS THAT ARE APPROPRIATE FOR CONDITIONS.
2. REFER TO SECTION 07 84 00 / FIRESTOPPING FOR ADDITIONAL REQUIREMENTS REGARDING HEAD-OF-WALL CONDITION FOR FIRE-RATED WALLS.
SLOTTED TOP
TRACK
STUD
DESIGN BASIS: UL-HW-D-0082
CONCRETE SLAB
DESIGN BASIS: UL-HW-D-0042
METAL DECK
(PERPENDICULAR TO FLUTES)
/8
DESIGN BASIS: UL-HW-D-0264
METAL DECK
(PARALLEL TO FLUTES)
1" 1" 2"x20 GA
STRAPS @ 16"
O.C.
DESIGN BASIS: UL-HW-D-0259
STEEL BEAM
20 GA Z-BARS
TO
ACCOMMODATE
SFRM
SPRAY-APPLIED
FIRE-RESISTIVE
MATERIAL
(SFRM)
SAB
1 OR 2 LAYERS OF GWB;
SEE WALL TYPE
FIRE STOP SEALANT
FIRE STOP JOINT
SPRAY
MINERAL WOOL
FORMING MATERIAL
/8
/8
FIRE STOP JOINT
SPRAY
SLOTTED TOP
TRACK
STUD
SAB
1 OR 2 LAYERS OF GWB;
SEE WALL TYPE
/8
MINERAL WOOL
FORMING MATERIAL
SLOTTED TOP
TRACK
STUD
CONCRETE SLAB METAL DECK
(PERPENDICULAR TO FLUTES)
/8
/8
METAL DECK
(PARALLEL TO FLUTES)
1" 1"
/8
SLOTTED TOP
TRACK
2"x20 GA
STRAPS @ 16"
O.C.
STEEL BEAM
/8
20 GA Z-BARS
TO
ACCOMMODATE
SFRM
SPRAY-APPLIED
FIRE-RESISTIVE
MATERIAL
(SFRM)
SAB
GWB
ACOUSTICAL SEALANT
CUT ONE LAYER GWB TO
FOLLOW PROFILE OF DECKING.
SEAL CONTINUOUSLY WITH
ACOUSTICAL SEALANT.
FILL FLUTE VOID W/
SAB
GWB SOUND AND
SMOKE CLOSURE
STRIP SECURE TO
STRUCTURE AND SEAL
WITH ACOUSTICAL
SEALANT
ACOUSTICAL
SEALANT (BOTH
SIDES)
STUD
SAB
GWB
ACOUSTICAL SEALANT
(BOTH SIDES)
"SMOKE PARTITIONS AND SOUND-CONTROL WALLS"- ADDITIONAL NOTES:
1. UPGRADE TO DETAIL "B4" WHERE WALL IS DESIGNATED WITH A FIRE-RESISTANCE RATING.
2. FILL VOIDS WITH SOUND ATTENUATION BATTS (SAB).
3. SOUND WALLS AND SMOKE PARTITIONS REQUIRE THAT AT LEAST ONE LAYER OF GWB BE CUT TO FOLLOW UNDULATING SURFACES OF SUPERSTRUCTURES INCLUDING BUT NOT LIMITED TO FLUTES METAL DECKING. JOINT GWB TO SUPERSTRUCTURE WITH A CONTINUOUS BEAD OF ACOUSTICAL SEALANT.
4. BUILDING CODE REQUIRES THAT "SMOKE PARTITIONS" BE SEALED TO STRUCTURE AS INDICATED TO SUCCESSFULLY "….LIMIT THE PASSAGE OF SMOKE….".
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
TRIPLE C - The A/E Group
100 Pearl Street, 14th Floor
Hartford, CT 06103
MAT PERKINS
860-270-0753 mat.perkins@triplecaeg.com
A u to d e s k D o c s /3
C
R
.P ro je c t.
-2
-7
.E H
R M
.I U
.B e d fo rd
.M A
.R
/5
-2 -7
.B e d fo rd .E
H R
M .A
R C
H .B
R
.r v t
/2
/2
:4
:2
A
M
04A-512
ARCHITECTURAL PARTITION HEAD DETAILS 518-22-700
05/06/2025 M. Perkins K. McDermott
ISSUED FOR
CONSTRUCTION
EHRM INFRASTRUCTURE
UPGRADES
200 Springs Rd, Bedford, MA 01730
3" = 1'-0" B5
HEAD-OF-WALL CONDITIONS - STUD WALLS - FIRE RATED WALLS
3" = 1'-0" D5
HEAD-OF-WALL CONDITIONS - STUD WALLS - SMOKE PARTITIONS AND SOUND CONTROL WALLS
NOTE:
STANDARD DETAILS APPLY TO TYPICAL CONSTRUCTION
TYPES AND ASSEMBLIES. NOT ALL DETAILS MAY BE
USED. CONTRACTOR SHALL VERIFY ACTUAL CONDITIONS
ON-SITE.
Revisions: Date:
Addendum 1 02/25/2026
EXISTING CONSTRUCTION TO REMAIN
EXISTING CONSTRUCTION TO BE DEMOLISHED
NEW CONSTRUCTION, WITH PARTITION TYPE
GENERAL INTERIOR NOTES
KEYNOTES
GENERAL FINISH NOTES:
1. REFER TO SPECIFICATIONS FOR ADDITIONAL MATERIAL AND
INSTALLATION REQUIREMENTS.
2. REFER TO THIS SHEET FOR FINISH LEGEND AND ROOM FINISH
SCHEDULE.
3. IF POSSIBLE PROVIDE MATERIALS FROM SAME PRODUCTION RUN
FOR CONSISTENCY.
SUBSTITUTION NOTES:
1. COLOR IS AN IMPORTANT PART OF THIS PROJECT. ANY COLOR
SUBSTITUTION WILL REQUIRE APPROVAL BY THE COR.
TRANSITION NOTES:
1. INSTALL TRANSITIONS AT ALL DISSIMILAR FLOOR MATERIALS.
2. FOR ALL FLOOR FINISH AND PATTERN TRANSITIONS THAT OCCUR AT
DOORWAYS, TRANSITION MATERIALS AT CENTERLINE OF DOOR
WHEN DOOR PANEL IS IN THE CLOSED POSITION.
SIGNAGE NOTES:
1. REFER TO THIS SHEET SERIES SHEETS FOR SIGNAGE INFORMATION,
REFER TO SPECIFICATIONS FOR ADDITIONAL SIGNAGE,
IDENTIFICATION AND SYSTEMS/EQUIPMENT LABELING
REQUIREMENTS.
PAINTING NOTES:
1. ALL ADHESIVES AND PAINT TO BE LOW VOC/ODOR.
2. UNLESS OTHERWISE INDICATED, DO NOT PAINT FACTORY-FINISHED
ITEMS OR INSTALLER FINISHED ITEMS.
3. COORDINATE APPLICATIONS OF PAINTS AND ADHESIVES WITH COR.
PROVIDE SEALED ENVIRONMENT DURING HVAC FLUSH OUT PERIOD
TO ENSURE ODORS DO NOT TRANSMIT TO ADJACENT SPACES.
CODE NOTES:
1. ALL INTERIOR FINISHES SHALL HAVE FLAME SPREAD IN COMPLIANCE
WITH IBC 2024 803.13 INTERIOR WALL AND CEILING FINISH
REQUIREMENTS BY OCCUPANCY.
INSTALLATION NOTES:
1. PROVIDE BACKING FOR ALL WALL MOUNTED EQUIPMENT.
MATERIAL FLOOR CHANGE (REFER TO THIS SHEET FOR DETAILS)
INTERIOR FINISH SYMBOLS
SEALED CONCRETE WITH STATIC DISSIPATIVE COATING (C-1/SDC)
INTERIOR FINISHES
PAINT
FIELD
CALIFORNIA PAINTS*
TO MATCH BENJAMIN MOORE
MANCHESTER TAN HC-81
ARCHITECT/ENGINEERS:
INTERIOR FINISHES
Drawing Title
Approved: Project Director
Project Title
Location
Date Checked Drawn
NB KLM
Project Number
Board Number
Office of Construction and Facilities Management
*BASIS OF DESIGN
**MATCH EXISTING CAMPUS PAINT COLORS
EHRM INFRASTRUCTURE
UPGRADES
518-22-700
200 Springs Road, Bedford, MA 01730
EDITH NOURSE MEMORIAL VETERANS HOSPITAL
P-1
DIGITAL IMAGES MAY HAVE COLOR INACCURACIES, REFER
TO ACTUAL SAMPLE FOR TRUEST COLOR DEPICTION
PAINT
METAL DOORS & TRIM
CALIFORNIA PAINTS*
TO MATCH BENJAMIN MOORE
WHITE DOWN OC-131
P-2
WALL BASE
JOHNSONITE*
BEIGE 49
RB-1
PAPER INSERT CARRIER, MAGNETIC
MOUNT, WITH NON-GLARE LENS
TEXT: 5/8"H LASER-PRINTED TEXT,
HELVETICA MEDIUM
COLOR: TO MATCH STATION
STANDARDS
1-1/2" x 1/32" ADA
TACTILE NUMERALS
AND GRADE II BRAILLE234
9"
Restricted Access
5-3/16" X 9" CLEAR
ACETATE INSERT W/
COPY
9"X9" MAGNETICALLY
REMOVABLE SIGN
(ONE-PIECE)
RED SYMBOL AND
BLACK TEXT
1/2" 9" 1/2"
/2
/2
QUARTER-ROUND
SILVER FRAME
EXISTING FLOORING
TO BE REMOVED
TOP OF SLAB
EXISTING
FLOORING TO
REMAIN, EXISTING
ROOM SIDE EXISTING CONCRETE
FLOOR WITH STATIC
DISSIPATIVE (C-1/SDC)
RESILIENT BASE AS
SCHEDULED, EACH
SIDE OF NEW WALL
INSTALL 3/4"
PLYWOOD, MOUNT
BOTTOM OF
PLYWOOD 12" AFF
ADJACENT SPACE
TELECOM
ROOM SIDE
PARTITION AS SCHEDULED
EXISTING CONCRETE
FLOOR WITH STATIC
DISSIPATIVE (C-1/SDC)
LOCATION OF FLOOR
FINISH CHANGE;
SEAM OR ADAPTER
TRANSITION SHALL
OCCUR AT
CENTERLINE OF
DOOR IN CLOSED
POSITION
DOOR AS SCHEDULED
EXISTING FLOORING
TOP OF SLAB
CORRIDOR SIDE
DOOR FRAME BEYOND
C CENTER LINE OF DOORL
TRANSITION STRIP
(TR-1) OR EQUAL,
REFER TO SCHEDULE
FOR INFORMATION
TELECOM ROOM SIDE
SIGNAGE REFERENCES
VA SIGNAGE DESIGN MANUAL
SIGN VENDOR TO REFERENCE VA SIGNAGE DESIGN MANUAL FOR COMPLETE
SPECIFICATIONS
https://www.cfm.va.gov/til/spclRqmts.asp#SIGN
SIGN SYMBOL LEGEND
TELECOM ROOM FINISH DIAGRAM,
CONTRACTOR TO REFERENCE
ARCHITECTURE FOR ACTUAL WALL
CONSTRUCTION LOCATIONS
2 5 6
IN-08.02
IN-04.01A
IN-01.314
F4
04IN101
TYP.
F1
04IN101
TYP.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
TRIPLE C - The A/E Group
100 Pearl Street, 14th Floor
Hartford, CT 06103
MAT PERKINS
860-270-0753 mat.perkins@triplecaeg.com
A u to d e s k D o c s /3
C
R
.P ro je c t.
-2
-7
.E H
R M
.I U
.B e d fo rd
.M A
.R
/5
-2 -7
.B e d fo rd .E
H R
M .A
R C
H .B
R
.r v t
/2
/2
:4
:2
A
M
04IN101
INTERIOR FINISH PLAN, SIGNAGE & SCHEDULES 518-22-700
05/06/2025 M. Perkins K. McDermott
ISSUED FOR
CONSTRUCTION
EHRM INFRASTRUCTURE
UPGRADES
200 Springs Rd, Bedford, MA 01730
NTS
C1
COLOR BOARD
ROOM FINISH SCHEDULE
LEVEL NO. NAME
FLOOR WALLS CEILING
NOTESFINISH BASE
NORTH EAST SOUTH WEST
MATERIAL FINISHMATERIAL FINISH MATERIAL FINISH MATERIAL FINISH MATERIAL FINISH
BASEMENT B05 TELECOM ROOM C-1/ SDC RB-1 GWB P-1/ WD GWB P-1/ WD GWB P-1/ WD GWB P-1/ WD OPEN
LEVEL 1 141 TELECOM ROOM C-1/ SDC RB-1 GWB P-1/ WD GWB P-1/ WD GWB P-1/ WD GWB P-1/ WD OPEN
LEVEL 2 244 TELECOM ROOM C-1/ SDC RB-1 GWB P-1/ WD GWB P-1/ WD GWB P-1/ WD GWB P-1/ WD OPEN
BUILDING SIGNAGE SCHEDULE
VERSION
TYPE COUNT DESCRIPTION DETAIL LOCATION REFERENCE
ADA
BRAILLE TEXT COLOR BACKGROUND COLOR
DIMENSIONS
CommentsSIGN_HEIGHT SIGN_WIDTH MOUNTING HEIGHT
IN-01.31 3 FIRE IDENTIFICATION SIGN D6 / 04IN101 FEC REFER TO PAGE 429 OF SIGNAGE DESIGN
MANUAL DATED 05/2023
NO WHITE RED 9" 9" 6' - 8" INSTALLED AT FIRE EXTINGUISHER CABINETS AT ALL
NEW TELECOM ROOMS
IN-04.01A 3 ROOM NUMBER IDENTIFICATION D3 / 04IN101 TELECOM ROOM REFER TO PAGE 261 OF SIGNAGE DESIGN
MANUAL DATED 05/2023
YES REFERENCE EXISTING
CAMPUS STANDARDS
REFERENCE EXISTING
CAMPUS STANDARDS
9 1/2" 8 5/8" 5' - 0" INSTALLED AT ALL NEW TELECOM ROOMS
IN-08.02 3 PROHIBIT INSTRUCTIONAL AND
CONTROL
D1/ 04IN101 TELECOM ROOM REFER TO PAGE 279 OF SIGNAGE DESIGN
MANUAL DATED 05/2023
NO REFERENCE EXISTING
CAMPUS STANDARDS
REFERENCE EXISTING
CAMPUS STANDARDS
9 1/2" 8 5/8" 5' - 9" INSTALLED AT ALL NEW TELECOM ROOMS MOUNTED
DIRECTLY ABOVE ROOM NAME SIGN
Grand total: 9
3" = 1'-0" D3
IN-04.01A SIGN DETAIL - PRIMARY ROOM
IDENTIFICATION
3" = 1'-0"
D1
IN-08.02 SIGN DETAIL - PROHIBIT
INSTRUCTIONAL AND CONTROL
12" = 1'-0"
D5
EXAMPLE OF EXISTING SIGNAGE
6" = 1'-0" F4
RESILIENT BASE (TOE BASE)
6" = 1'-0"
F1
THRESHOLD - CONCRETE TO EXISTING FLOORING
FINISH LEGEND
SYMBOL FINISH TYPE MANUFACTURER COLLECTION STYLE / TYPE COLOR SIZE SPEC SECTION NOTES
C-1/ SDC SEALED CONCRETE WITH STATIC DISSIPATIVE COATING SEALED CONCRETE* - - - - - TELECOM ROOM SPACE TO RECEIVE STATIC CONTROL CONCRETE SEALER
F-1 WINDOW FILM 3M* FASARA 7725SE-324 FROSTED CRYSTAL - 08 87 33
P-1 PAINT CALIFORNIA PAINTS* - EGGSHELL TO MATCH BENJAMIN MOORE MANCHESTER TAN HC-81 - 09 91 00 FIELD
P-2 PAINT CALIFORNIA PAINTS* - SEMI-GLOSS TO MATCH BENJAMIN MOORE WHITE DOWN OC-131 - 09 91 00 METAL DOORS & TRIM
RB-1 RESILIENT BASE JOHNSONITE* TRADITIONAL TOE BASE BEIGE 49 4" 09 65 13
TR-1 TRIM SCHLUTER * - RENO-U SATIN ANODIZED ALUMINUM - 09 30 13 FLOOR TRANSITION
WD PLYWOOD FIRE TREATED PLYWOOD* - - HIGH GLOSS WHITE MPI (MASTER PAINTERS INSTITUTE)
67 OR SIM
4' X 8' - PLYWOOD TO BE PAINTED WITH 2 COATS OF FIRE RESISTANT PAINT; FIRE
RATING STAMPS SHALL NOT BE PAINTED OVER
1 REMOVE EXISTING FLOORING, ADHESIVES, AND INSTALL NEW WALL
BASE
2 EXISTING WALLS ARE TO BE PATCHED AND PAINTED. SEE ROOM
FINISH SCHEDULE THIS SHEET FOR FINISHES.
3 ALL WALLS TO RECEIVE NEW PLYWOOD, COORDINATE WITH
ELECTRICAL DRAWINGS FOR FIXTURE LOCATIONS
4 PROVIDE NEW ROOM SIGNAGE, SEE SIGNAGE SCHEDULE THIS
SHEET
5 REFER TO ARCHITECTURAL PLANS FOR DETAILED ROOM
CONFIGURATION INFORMATION
6 TELECOM ROOM SPACE TO RECEIVE STATIC CONTROL CONCRETE
SEALER
REFER TO THIS SHEET FOR ROOM FINISH SCHEDULE & FINISH LEGEND
3" = 1'-0" D6
IN-01.31 SIGN DETAIL - FIRE EQUIPMENT
IDENTIFICATION SIGN
*Materials are approved as basis of design, all material substitutions are subject to owner approval. Contractor to provide VA Interior Design Department with samples of all specified finish materials. VA COR/ Interior Design department shall approve all finishes prior to installation.
1/2" = 1'-0" F7
TYPICAL TELECOM ROOM FINISH DIAGRAM
Revisions: Date:
Addendum 1 02/25/2026
| Sheets |
| 04A-400 - ARCHITECTURAL ENLARGED VIEWS - BASEMENT LEVEL |
| 04A-401 - ARCHITECTURAL ENLARGED VIEWS - FIRST & SECOND LEVEL |
| 04A-512 - ARCHITECTURAL PARTITION HEAD DETAILS |
| 04IN101 - INTERIOR FINISH PLAN, SIGNAGE & SCHEDULES |