Amend 5 - ATT 7 -518-22-700.Bedford.EHRM.IFC.Add1.B02.20260225.pdf

PDF 3 MB Posted

Attached to
Y1DA--518-22-700 EHRM Infrastructure Upgrades Construction Bedford VAMC
Solicitation number
36C77626R0003
Issued by

About this file

This document is a set of architectural drawings and specifications for EHRM (Edith Nourse Memorial) Infrastructure Upgrades at a Department of Veterans Affairs facility located at 200 Springs Road, Bedford, Massachusetts. The project involves the renovation of three telecom rooms (Rooms 141, 236, and 342) across three building levels, with construction issued for bidding on June 4, 2025.

The scope of work includes converting existing spaces into 1-hour fire and smoke-rated telecom rooms that comply with VA Physical Security Standards and campus standards. Key construction requirements include demolition of existing walls, installation of new fire-rated partitions and doors (45-minute fire-rated hollow metal doors and frames), removal and replacement of flooring and wall base, provision of new fire extinguisher cabinets with Type 2A:10B:C clean agent extinguishers located no more than 75 feet from each telecom room, installation of window film on furred windows, painting with low-VOC materials matching Benjamin Moore Manchester Tan HC-81, and installation of static dissipative concrete flooring (C-1/SDC). Interior signage includes room identification signs and fire equipment identification signage per VA Signage Design Manual standards. The contractor is responsible for moving, storing, and returning existing furnishings and equipment, with all disassembly and reassembly of systems furniture following manufacturer warranties. Temporary dust barriers are required during demolition, and potential asbestos abatement may be necessary at floor penetrations. Construction details reference UL fire-resistance ratings (UL U465 for 1-hour walls, UL V438 and UL U411 for 2-hour walls) and specify firestopping requirements per Section 07 84 00.

View the file

Other files

File Type Posted
36C77626R0003 0011.pdf PDF
36C77626R0003 0010.pdf PDF
36C77626R0003 0009.pdf PDF
Amendment 9 - ATT 1 - RFI Responses updated 041426.pdf PDF
Amendment 8 - ATT 2 - 518-22-700 Summary Log_ADD4_20260413.pdf PDF
Amendment 8 - ATT 3 - 518-22-700.Bedford.MA.EHRM.Specs.IFC.20260413.pdf PDF
Amendment 8 - ATT 1 - RFI Responses updated 041326.pdf PDF
36C77626R0003 0008.pdf PDF
Amendment 7 -ATT 2 - 25 10 10 - Advanced Utility Metering System.Add3.20260408.pdf PDF
Amendment 7 - ATT 1 - 518-22-700.Summary Log_ADD3.20260408.pdf PDF
36C77626R0003 0007.pdf PDF
36C77626R0003 0006.pdf PDF
Amendment 6 - ATT 1 - RFI Responses updated 033126.pdf PDF
Amend 5 - ATT 9 -518-22-700.Bedford.EHRM.IFC.Add1.B04.20260225.pdf PDF
Amend 5 - ATT 26 -518-22-700.Bedford.EHRM.IFC.Add1.B61.2060225.pdf PDF
Amend 5 - ATT 6 -518-22-700.Bedford.EHRM.IFC.Add1.B01.20260225.pdf PDF
Amend 5 - ATT 24-518-22-700.Bedford.EHRM.IFC.Add1.B22.2060225.pdf PDF
Amend 5 - ATT 2 - Inspection and Lead Paint Screening Report Final.pdf PDF
Amend 5 - ATT 28-518-22-700.Bedford.EHRM.IFC.Add1.B70.2060225.pdf PDF
Amend 5 - ATT 14-518-22-700.Bedford.EHRM.IFC.Add1.B09.20260225.pdf PDF
Amend 5 - ATT 3 - 04 72 00 - Cast Stone Spec.pdf PDF
Amend 5 - ATT 16-518-22-700.Bedford.EHRM.IFC.Add1.B13.20260225.pdf PDF
Amend 5 - ATT 23-518-22-700.Bedf.EHRM.IFC.Add1.B21_19.2060225.pdf PDF
Amend 5 - ATT 22-518-22-700.Bedford.EHRM.IFC.Add1.B20.2060225.pdf PDF
Amend 5 - ATT 18-518-22-700.Bedford.EHRM.IFC.Add1.B15.20260225.pdf PDF
Amend 5 - ATT 29-518-22-700.Bedford.EHRM.IFC.Add1.B78.2060225.pdf PDF
Amend 5 - ATT 8 -518-22-700.Bedford.EHRM.IFC.Add1.B03.20260225.pdf PDF
36C77626R0003 0005.pdf PDF
Amend 5 - ATT 19-518-22-700.Bedford.EHRM.IFC.Add1.B16.2060225.pdf PDF
Amend 5 - ATT 20-518-22-700.Bedford.EHRM.IFC.Add1.B17.20260225.pdf PDF
Amend 5 - ATT 17-518-22-700.Bedford.EHRM.IFC.Add1.B14.20260225.pdf PDF
Amend 5 - ATT 11-518-22-700.Bedford.EHRM.IFC.Add1.B06.20260225.pdf PDF
Amend 5 - ATT 1 - 518-22-700.Summary Log_ADD1.20260225.pdf PDF
Amend 5 - ATT 31-518-22-700.Bedford.EHRM.IFC.Add1.B81.2060225.pdf PDF
Amend 5 - ATT 15-518-22-700.Bedford.EHRM.IFC.Add1.B10.20260225.pdf PDF
Amend 5 - ATT 27-518-22-700.Bedford.EHRM.IFC.Add1.B62.20260225.pdf PDF
Amend 5 - ATT 10-518-22-700.Bedford.EHRM.IFC.Add1.B05.20260225.pdf PDF
Amend 5 - ATT 21-518-22-700.Bedford.EHRM.IFC.Add1.B18.20260225.pdf PDF
Amend 5 - ATT 13-518-22-700.Bedford.EHRM.IFC.Add1.B08.20260225.pdf PDF
Amend 5 - ATT 4 - 08 87 33 - Decorative Film.pdf PDF
Amend 5 - ATT 25 -518-22-700.Bedford.EHRM.IFC.Add1.B33.2060225.pdf PDF
Amend 5 - ATT 35-518-22-700.Bedf.EHRM.IFC.Add1.SITE.20260225.pdf PDF
Amend 5 - ATT 32-518-22-700.Bedford.EHRM.IFC.Add1.B82.2060225.pdf PDF
Amend 5 - ATT 30-518-22-700.Bedford.EHRM.IFC.Add1.B80.2060225.pdf PDF
Amend 5 - ATT 12-518-22-700.Bedford.EHRM.IFC.Add1.B07.20260225.pdf PDF
Amend 5 - ATT 33-518-22-700.Bedford.EHRM.IFC.Add1.BCH.2060225.pdf PDF
Amend 5 - ATT 34-518-22-700.Bedford.EHRM.IFC.Add1.MCR.2060225.pdf PDF
Amend 5 - ATT 5 - 34 71 13 PASSIVE VEHICLE BARRIERS.pdf PDF
Amendment 4 - ATT 1 - RFI Responses updated 032626.pdf PDF
S06 - Amendment 0003 - ATT 1 - RFI Responses_Bedford.pdf PDF
Show 40 more

Latest 50 of 105 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

DN

UP

UP

UP

UP

UP

DN

UP

UP

DN

DN

DN

UP

SHEET SYMBOL LEGEND

KEYNOTES

GENERAL NOTES

EXISTING CONSTRUCTION TO REMAIN

EXISTING CONSTRUCTION TO BE DEMOLISHED

NEW CONSTRUCTION, WITH PARTITION TYPE

A

A. SEE GENERAL NOTES AND PLANS FOR TYPICAL GENERAL PROJECT

REQUIREMENTS AND PROJECT LOCATION DRAWINGS.

B. SEE INTERIOR FINISH DRAWINGS FOR ADDITIONAL FINISHES

INFORMATION.

C. SEE MECHANICAL AND ELECTRICAL DRAWINGS FOR ADDITIONAL

SYSTEMS INFORMATION.

D. NEW TELECOM ROOMS SHALL BE 1 HOUR FIRE AND SMOKE RATED

AND COMPLY WITH THE LATEST VA PHYSICAL SECURITY STANDARDS,

AND CAMPUS STANDARDS.

E. SEE TYPICAL WALL FRAMING DETAILS ON SHEET A-511.

F. SEE TYPICAL HEAD OF WALL DETAIL ON SHEET A-512.

G. SEE TYPICAL CEILING DETAILS ON SHEET A-531

H. ALL PHOTOS SHOWN REFLECT EXISTING CONDITIONS AS OF THE

DATE OF THIS DRAWING SET. CONTRACTOR SHALL FIELD VERIFY ALL

DIMENSIONS, CONDITIONS, AND SITE-SPECIFIC INFORMATION AT THE

TIME OF BIDDING.

I. CONTRACTOR IS RESPONSIBLE FOR ALL COSTS ASSOCIATED WITH

MOVING, STORING AND RETURNING FURNISHINGS AND EQUIPMENT

TO THE PROPOSED WORK AREA(S). ANY DISASSEMBLY AND

REASSEMBLY OF SYSTEMS FURNITURE IN THE PROPOSED WORK

AREAS IS THE RESPONSIBILITY OF THE CONTRACTOR AND MUST

FOLLOW THE MANUFACTURER'S WARRANTY.

PARTITION RATING GRAPHICS:

4 HR FIRE BARRIER

3 HR FIRE BARRIER

2 HR FIRE & SMOKE BARRIER

2 HR FIRE BARRIER

2 HR FIRE BARRIER/SHAFT

1 HR FIRE & SMOKE BARRIER

1 HR FIRE BARRIER

1 HR FIRE BARRIER/SHAFT

SMOKE PARTITION (NON RATED)

NON RATED

PARTITION RATING GRAPHIC DESIGNATION: PRIORITY

1 HIGHEST

5 LOWEST

PARTITIONS REQUIRED TO BE SMOKE RESISTANT, FIRE

RESISTANT, OR BOTH FIRE AND SMOKE RESISTANT ARE SHOWN

GRAPHICALLY ON PLANS WITH HATCH PATTERNS.

02A-401

B7

TELECOM

ROOM

141141

H

12 13

6 5

9' -3

3' -4

2'

-4 "18

H

12 13

TELECOM

ROOM

100 SF

ROOM

174174

ELEVATOR

EXISTING (VIF)

11'-5"

9' -3

HW-SH-3F

B

B

B

B

A

B

141A

HW-3G

PIV

OFFICE

141A

66 SF

2' -4

J21

A6

ELEVATOR

TELECOM

ROOM

100 SF

ROOM

174174

ELEVATOR

PIV

OFFICE

141A141A

PIV

OFFICE

173 SF

ROOM

174174

ELEVATOR

9' -2

/4

PIV

OFFICE

173 SF

ROOM

174174

ELEVATOR

02A-401

B3

TELECOM

ROOM

236236

G

F

TELECOM

ROOM

101 SF

H W

-S H

-3 F

B

B

B

B

E X

IS

T

IN

G

V

IF

'-7

/8

EXISTING (VIF)

8'-5 1/4"

OFFICE

138 SF

CORRIDOR

201A

493 SF

B

B

B

B

G

F

IRM

CLOSET

103 SF

CHIEF

OFFICE

237237

CORRIDOR

201A201A

15 17

TELECOM

ROOM

236236 OFFICE

237237

CORRIDOR

201A201A

IRM

CLOSET

236236

CHIEF

OFFICE

237237

CORRIDOR

201A201A

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

TRIPLE C - The A/E Group

100 Pearl Street, 14th Floor

Hartford, CT 06103

MAT PERKINS

860-270-0753 mat.perkins@triplecaeg.com

A u to d e s k D o c s /3

C

R

.P ro je c t.

-2

-7

.E H

R M

.I U

.B e d fo rd

.M A

.R

/5

-2 -7

.B e d fo rd .E

H R

M .A

R C

H .B

R

.r v t

/2

/2

:2

:0

A

M

02A-401

ARCHITECTURAL ENLARGED VIEWS - FIRST

LEVEL

518-22-700

06/04/2025 M. Perkins K. McDermott

ISSUED FOR CONSTRUCTION EHRM INFRASTRUCTURE

UPGRADES

200 Springs Rd, Bedford, MA 01730

1 EXISTING WALLS TO BECOME 1 HR FIRE AND SMOKE-RATED.

PATCH AND SEAL ALL PENETRATIONS AS NECESSARY.

2 PROVIDE NEW FIRE EXTINGUISHER CABINET WITH A TYPE 2A:10B:C

CLEAN AGENT FIRE EXTINGUISHER LOCATED NO GREATER THAN 75

FEET AWAY FROM THE NEW TR. CONTRACTOR TO COORDINATE

THE NEW LOCATION WITH THE COR. CONTRACTOR SHALL BID A

NEW FEC FOR EACH TR IN THE SCOPE OF WORK. SEE

SPECIFICATION 10 44 13.

3 NEW 45 MIN FIRE RATED DOOR AND FRAME. SEE DOOR SCHEDULE

AND SPECIFICATIONS FOR ADDITIONAL INFORMATION. COORDINATE

DOOR AND FRAME WITH ACCESS CONTROL HARDWARE

4 NEW FURRING WALL AT EXTERIOR WALL TO ENCLOSE WINDOW.

MAINTAIN 1/2" GAP BETWEEN EXISTING WALL INTERIOR FACE AND

NEW STUDS. MODIFY / REMOVE INTERIOR WINDOW TRIM AS

REQUIRED. INSTALL WINDOW FILM AT ALL FURRED WINDOWS, SEE

02IN101 FOR MORE INFORMATION

5 REMOVE EXISTING DOOR AND FRAME.

6 PROVIDE TEMPORARY DUST TIGHT BARRIER AROUND WORK AREA

DURING ANY ACTIVITIES WHICH PRODUCE DUST - TYPICAL.

7 REMOVE EXISTING FLOORING, ADHESIVE AND WALL BASE.

8 ALL ITEMS/ EQUIPMENT TO BE REMOVED FROM SPACE PRIOR TO

DEMO.

9 AT NEW WALL INSTALLATIONS, CONTRACTOR TO PAINT NEW WALL

IN ITS ENTIRETY. INSTALL NEW WALL BASE AT ENTIRE WALL SPACE

OR APPROPRIATE TRANSITION LOCATION AS APPROVED BY THE

COR

10 REMOVE EXISTING CEILING AND LIGHTS. MODIFY AND/OR PROVIDE

ADDITIONAL SUPPORTS AS REQUIRED FOR EXISTING CEILING ITEMS

TO REMAIN.

11 TELECOM ROOM TO BE OPEN TO DECK.

12 DEMO WALL AND FRAMING FOR NEW DOOR.

13 EXISTING CEILING AND LIGHTS TO REMAIN. MODIFY AND/OR

PROVIDE ADDITIONAL SUPPORTS AS REQUIRED FOR EXISTING

CEILING ITEMS TO REMAIN AT NEW WALL INSTALLATION.

14 LOCATION OF CONSTRUCTION

15 EXISTING OPEN TO DECK CEILING TO REMAIN.

16 INSTALL NEW DOOR, SEE DOOR SCHEDULE FOR INFORMATION

17 POTENTIAL ABATEMENT AT FLOOR FOR FLOOR PENETRATIONS.

REFER TO COVER SHEET FOR KNOWN ACM ITEMS WITHIN THIS

BUILDING.

18 REMOVE EXISTING WINDOW

1/32" = 1'-0" F7

FIRST LEVEL REFERENCE PLAN

1/4" = 1'-0" E7

ARCHITECTURAL FLOOR PLAN - FIRST LEVEL

- RM 141 - DEMO

1/4" = 1'-0" B7

ARCHITECTURAL FLOOR PLAN - FIRST LEVEL

- RM 141 - NEW

1/32" = 1'-0" F3

SECOND LEVEL REFERENCE PLAN

1/4" = 1'-0" B5

ARCHITECTURAL REFLECTED CEILING PLAN -

FIRST LEVEL - RM 141 - NEW

1/4" = 1'-0" E5

ARCHITECTURAL REFLECTED CEILING PLAN -

FIRST LEVEL - RM 141 - DEMO

1/4" = 1'-0" B3

ARCHITECTURAL FLOOR PLAN - SECOND

LEVEL - RM 236 - NEW

1/4" = 1'-0" E3

ARCHITECTURAL FLOOR PLAN - SECOND

LEVEL - RM 236 - DEMO

1/4" = 1'-0"

E1

ARCHITECTURAL REFLECTED CEILING PLAN -

SECOND LEVEL - RM 236 - DEMO

1/4" = 1'-0" B1

ARCHITECTURAL REFLECTED CEILING PLAN -

SECOND LEVEL - RM 236 - NEW

Revisions: Date:

Addendum 1 02/25/2026

NOT TO SCALE

F5

ROOM 141

NOT TO SCALE

F1

ROOM 236

02/25/2026

DN

DN

DN

SHEET SYMBOL LEGEND

KEYNOTES

GENERAL NOTES

EXISTING CONSTRUCTION TO REMAIN

EXISTING CONSTRUCTION TO BE DEMOLISHED

NEW CONSTRUCTION, WITH PARTITION TYPE

A

A. SEE GENERAL NOTES AND PLANS FOR TYPICAL GENERAL PROJECT

REQUIREMENTS AND PROJECT LOCATION DRAWINGS.

B. SEE INTERIOR FINISH DRAWINGS FOR ADDITIONAL FINISHES

INFORMATION.

C. SEE MECHANICAL AND ELECTRICAL DRAWINGS FOR ADDITIONAL

SYSTEMS INFORMATION.

D. NEW TELECOM ROOMS SHALL BE 1 HOUR FIRE AND SMOKE RATED

AND COMPLY WITH THE LATEST VA PHYSICAL SECURITY STANDARDS,

AND CAMPUS STANDARDS.

E. SEE TYPICAL WALL FRAMING DETAILS ON SHEET A-511.

F. SEE TYPICAL HEAD OF WALL DETAIL ON SHEET A-512.

G. SEE TYPICAL CEILING DETAILS ON SHEET A-531

H. ALL PHOTOS SHOWN REFLECT EXISTING CONDITIONS AS OF THE

DATE OF THIS DRAWING SET. CONTRACTOR SHALL FIELD VERIFY ALL

DIMENSIONS, CONDITIONS, AND SITE-SPECIFIC INFORMATION AT THE

TIME OF BIDDING.

I. CONTRACTOR IS RESPONSIBLE FOR ALL COSTS ASSOCIATED WITH

MOVING, STORING AND RETURNING FURNISHINGS AND EQUIPMENT

TO THE PROPOSED WORK AREA(S). ANY DISASSEMBLY AND

REASSEMBLY OF SYSTEMS FURNITURE IN THE PROPOSED WORK

AREAS IS THE RESPONSIBILITY OF THE CONTRACTOR AND MUST

FOLLOW THE MANUFACTURER'S WARRANTY.

PARTITION RATING GRAPHICS:

4 HR FIRE BARRIER

3 HR FIRE BARRIER

2 HR FIRE & SMOKE BARRIER

2 HR FIRE BARRIER

2 HR FIRE BARRIER/SHAFT

1 HR FIRE & SMOKE BARRIER

1 HR FIRE BARRIER

1 HR FIRE BARRIER/SHAFT

SMOKE PARTITION (NON RATED)

NON RATED

PARTITION RATING GRAPHIC DESIGNATION: PRIORITY

1 HIGHEST

5 LOWEST

PARTITIONS REQUIRED TO BE SMOKE RESISTANT, FIRE

RESISTANT, OR BOTH FIRE AND SMOKE RESISTANT ARE SHOWN

GRAPHICALLY ON PLANS WITH HATCH PATTERNS.

02A-402

B7

02A-402

D7

TELECOM

ROOM

342342

G

F

13 14

TELECOM

ROOM

136 SF

ELEVATOR

392392

PATIENT

RM

343343

CORRIDOR

391391

TEL

CLOSET

341A341A

STAIR-3

341341

B

B

B

B

B

B

(E X

T G

V

IF

'-2

/2

(EXTG VIF)

12'-3"

H W

-S H

-3 F

G

F

13 14

STORAGE

139 SFELEVATOR

392392

PATIENT

RM

343343

CORRIDOR

391391

TEL

CLOSET

341A341A

STAIR-3

341341

TELECOM

ROOM

342342

ELEVATOR

392392

PATIENT

RM

343343

CORRIDOR

391391

TEL

CLOSET

341A341A

STAIR-3

341341

STORAGE

342342

ELEVATOR

392392

PATIENT

RM

343343

CORRIDOR

391391

TEL

CLOSET

341A341A

STAIR-3

341341

TYPICAL FRAME

H E

IG

H

T

2" WIDTH 2"

FRAME TYPE ELEVATIONS DOOR TYPE ELEVATIONS

F

FLUSH

E1

D1

1/2" 1/2"

VARIES

SEE PLAN

WALL - SEE PLAN

FOR TYPE

SEALANT - EA. SIDE

& ALL AROUND,

TYP.

HOLLOW METAL

FRAME

/2

V

A R

IE

S

S E

E P

L A

N

/2

UNO

4" 2"

ADJACENT WALL

WHERE OCCURS

SEALANT - EA SIDE &

ALL AROUND, TYP.

HOLLOW METAL FRAME

WALL - SEE PLAN

FOR TYPE

ACOUSTICAL OR RATED

SEALANT BOTH SIDES

FLOOR LINE

5/8" GWB BOTH SIDES

SOUND ATTENUATION

BATTS (SAB) PER

SCHEDULE.

CEILING LINE

STRUCTURAL DECK

METAL STUDS, SIZE

PER SCHEDULE

02A-512

D5

A/C GRADE, 3/4" FIRE-

TREATED PLYWOOD

02A-512

B5

AT FIRE RATED

PARTITIONS

AT SMOKE RATED

PARTITIONS

BOTTOM OF PLYWOOD TO

BE AT 12" AFF

ACOUSTICAL OR RATED

FLEXIBLE SEALANT

FLOOR LINE

ADD ONE LAYER OF 5/8" GWB,

ONE-SIDE WITH APPROVED UL

SETTING COMPOUND BETWEEN

LAYERS AND FASTENED TO

WALL AS REQUIRED, AT

EXISTING GWB WALL

ASSEMBLIES

STRUCTURAL DECK

EXISTING METAL STUDS AND

BATT INSULATION TO REMAIN

A/C GRADE, 3/4" FIRE-TREATED

PLYWOOD, ADHERED TO CONCRETE

AT EXISTING CONCRETE WALL

ASSEMBLIES

BOTTOM OF PLYWOOD

TO BE AT 12" AFF

UL DESIGN V497

1-HOUR PARTITION RATED FROM BOTH SIDES

EXISTING GWB OR

CONCRETE WALL

ASSEMBLY, WHERE OCCURS

SIDE OF

EXISTING

ROOM OR

CORRIDOR TO

REMAIN

02A-512

D5

02A-512

B5

LINE OF

STRUCTURE

LINE OF

STRUCTURE

09 29 00

SOUND ATTENUATION BATTS

(SAB), WHERE OCCURS

NOTE:

IF PARTITION TYPE IS USED IN A

CHASE WALL CONDITION, PROVIDE

CROSS BRACING GUSSETS AT 48"

O.C. MAX VERTICALLY. FABRICATED

FROM 6" MTL STUDS.

6”

09 29 00

5/8" GWB

09 29 00

SAB RETAINER STRAP

WHERE SAB OCCURS

CEILING

07 92 00

SEALANT

09 22 16

METAL STUDS

02A-512

D5

02A-512

B5

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

TRIPLE C - The A/E Group

100 Pearl Street, 14th Floor

Hartford, CT 06103

MAT PERKINS

860-270-0753 mat.perkins@triplecaeg.com

A u to d e s k D o c s /3

C

R

.P ro je c t.

-2

-7

.E H

R M

.I U

.B e d fo rd

.M A

.R

/5

-2 -7

.B e d fo rd .E

H R

M .A

R C

H .B

R

.r v t

/2

/2

:2

:0

A

M

02A-402

ARCHITECTURAL ENLARGED VIEWS - THIRD

LEVEL

518-22-700

06/04/2025 M. Perkins K. McDermott

ISSUED FOR CONSTRUCTION EHRM INFRASTRUCTURE

UPGRADES

200 Springs Rd, Bedford, MA 01730

1/32" = 1'-0" F7

THIRD LEVEL REFERENCE PLAN

1/4" = 1'-0" B7

ARCHITECTURAL FLOOR PLAN - THIRD LEVEL

- RM 342 - NEW

1/4" = 1'-0" D7

ARCHITECTURAL FLOOR PLAN - THIRD LEVEL

- RM 342 - DEMO

1/4" = 1'-0" B5

REFLECTED CEILING PLAN - THIRD LEVEL -

RM 342 - NEW

1/4" = 1'-0" D5

REFLECTED CEILING PLAN - THIRD LEVEL -

RM 342 - DEMO

DOOR AND FRAME SCHEDULE

WT DIMENSIONS PANEL FRAME DETAIL

FIRE RATING

HARDWARE

NOTESLEVEL ROOM NO. ROOM NAME DOOR NO. W1 H T TYPE MATERIAL FINISH GLAZING UNDERCUT TYPE MATERIAL FINISH HEAD JAMB SILL GROUP ELECTRICAL

LEVEL 1 141 TELECOM ROOM 141 3' - 0" 7' - 0" 1 3/4" F HM P-2 NONE 3/8" 1 HM P-2 E1/02A-402 D1/02A-402 F1/02IN101 45 MIN HW-SH-3F SEE SPEC 1

LEVEL 1 141A PIV OFFICE 141A 3' - 0" 7' - 0" 1 3/4" F WD WD NONE 3/8" 1 HM P-2 E1/02A-402 D1/02A-402 F1/02IN101 - HW-3G SEE SPEC 1

LEVEL 2 236 TELECOM ROOM 236 3' - 0" 7' - 0" 1 3/4" F HM P-2 NONE 3/8" 1 HM P-2 E1/02A-402 D1/02A-402 F1/02IN101 45 MIN HW-SH-3F SEE SPEC 1

LEVEL 3 342 TELECOM ROOM 342 3' - 0" 7' - 0" 1 3/4" F HM P-2 NONE 3/8" 1 HM P-2 E1/02A-402 D1/02A-402 F1/02IN101 45 MIN HW-SH-3F SEE SPEC 1

1/4" = 1'-0" F1

WRAPPED FRAME TYPES ELEVATIONS

3" = 1'-0" E1

HOLLOW METAL HEAD DETAIL

3" = 1'-0" D1

HOLLOW METAL JAMB DETAIL

NOTE: FIRE RESISTANCE TEST FOR ONE HOUR RATED WALLS: UL

U465

(TYPE A) TYPICAL PARTITION

MARK STUD WIDTH PRTN WIDTH DESIGN STC

A4 4" 5 1/4" 35

A6 6" 7 1/4" 35

NOTE: FIRE RESISTANCE TEST FOR TWO HOUR RATED WALLS: UL V438,

UL U411

(TYPE B) TYPICAL PARTITION

MARK STUD WIDTH PRTN WIDTH DESIGN STC

B 2 1/2" 3/4" 45

1 EXISTING WALLS TO BECOME 1 HR FIRE AND SMOKE-RATED.

PATCH AND SEAL ALL PENETRATIONS AS NECESSARY.

2 PROVIDE NEW FIRE EXTINGUISHER CABINET WITH A TYPE 2A:10B:C

CLEAN AGENT FIRE EXTINGUISHER LOCATED NO GREATER THAN 75

FEET AWAY FROM THE NEW TR. CONTRACTOR TO COORDINATE

THE NEW LOCATION WITH THE COR. CONTRACTOR SHALL BID A

NEW FEC FOR EACH TR IN THE SCOPE OF WORK. SEE

SPECIFICATION 10 44 13.

3 NEW 45 MIN FIRE RATED DOOR AND FRAME. SEE DOOR SCHEDULE

AND SPECIFICATIONS FOR ADDITIONAL INFORMATION.

COORDINATE DOOR AND FRAME WITH ACCESS CONTROL

HARDWARE

4 TELECOM ROOM TO BE OPEN TO DECK.

5 REMOVE EXISTING DOOR AND FRAME.

6 PROVIDE TEMPORARY DUST TIGHT BARRIER AROUND WORK AREA

DURING ANY ACTIVITIES WHICH PRODUCE DUST - TYPICAL.

7 REMOVE EXISTING FLOORING, ADHESIVE AND WALL BASE.

8 ALL ITEMS/ EQUIPMENT TO BE REMOVED FROM SPACE PRIOR TO

DEMO.

9 REMOVE EXISTING CEILING AND LIGHTS. MODIFY AND/OR PROVIDE

ADDITIONAL SUPPORTS AS REQUIRED FOR EXISTING CEILING

ITEMS TO REMAIN.

10 POTENTIAL ABATEMENT AT FLOOR FOR FLOOR PENETRATIONS.

REFER TO COVER SHEET FOR KNOWN ACM ITEMS WITHIN THIS

BUILDING.

1. SEE SPECIFICATIONS 08 71 00 FOR DOOR HARDWARE REQUIREMENTS. COORDINATE WITH ELECTRICAL.

Revisions: Date:

Addendum 1 02/25/2026

NOT TO SCALE

F5

ROOM 342

(TYPE J) NON-RATED PARTITION

MARK STUD WIDTH PRTN WIDTH DESIGN STC

J2 2 1/2" 3 1/8" -

"FIRE-RATED WALLS"- ADDITIONAL NOTES:

1. CONDITIONS INDICATED TO SHOW DESIGN INTENT. THEY ARE NOT INTENDED TO BE PROPRIETARY. CONTRACTOR MAY EMPLOY SIMILAR A UL-APPROVED TOP-OF-WALL DESIGNS THAT ARE APPROPRIATE FOR CONDITIONS.

2. REFER TO SECTION 07 84 00 / FIRESTOPPING FOR ADDITIONAL REQUIREMENTS REGARDING HEAD-OF-WALL CONDITION FOR FIRE-RATED WALLS.

SLOTTED TOP

TRACK

STUD

DESIGN BASIS: UL-HW-D-0082

CONCRETE SLAB

DESIGN BASIS: UL-HW-D-0042

METAL DECK

(PERPENDICULAR TO FLUTES)

/8

DESIGN BASIS: UL-HW-D-0264

METAL DECK

(PARALLEL TO FLUTES)

1" 1" 2"x20 GA

STRAPS @ 16"

O.C.

DESIGN BASIS: UL-HW-D-0259

STEEL BEAM

20 GA Z-BARS

TO

ACCOMMODATE

SFRM

SPRAY-APPLIED

FIRE-RESISTIVE

MATERIAL

(SFRM)

SAB

1 OR 2 LAYERS OF GWB;

SEE WALL TYPE

FIRE STOP SEALANT

FIRE STOP JOINT

SPRAY

MINERAL WOOL

FORMING MATERIAL

/8

/8

FIRE STOP JOINT

SPRAY

SLOTTED TOP

TRACK

STUD

SAB

1 OR 2 LAYERS OF GWB;

SEE WALL TYPE

/8

MINERAL WOOL

FORMING MATERIAL

SLOTTED TOP

TRACK

STUD

CONCRETE SLAB METAL DECK

(PERPENDICULAR TO FLUTES)

/8

/8

METAL DECK

(PARALLEL TO FLUTES)

1" 1"

/8

SLOTTED TOP

TRACK

2"x20 GA

STRAPS @ 16"

O.C.

STEEL BEAM

/8

20 GA Z-BARS

TO

ACCOMMODATE

SFRM

SPRAY-APPLIED

FIRE-RESISTIVE

MATERIAL

(SFRM)

SAB

GWB

ACOUSTICAL SEALANT

CUT ONE LAYER GWB TO

FOLLOW PROFILE OF DECKING.

SEAL CONTINUOUSLY WITH

ACOUSTICAL SEALANT.

FILL FLUTE VOID W/

SAB

GWB SOUND AND

SMOKE CLOSURE

STRIP SECURE TO

STRUCTURE AND SEAL

WITH ACOUSTICAL

SEALANT

ACOUSTICAL

SEALANT (BOTH

SIDES)

STUD

SAB

GWB

ACOUSTICAL SEALANT

(BOTH SIDES)

"SMOKE PARTITIONS AND SOUND-CONTROL WALLS"- ADDITIONAL NOTES:

1. UPGRADE TO DETAIL "B4" WHERE WALL IS DESIGNATED WITH A FIRE-RESISTANCE RATING.

2. FILL VOIDS WITH SOUND ATTENUATION BATTS (SAB).

3. SOUND WALLS AND SMOKE PARTITIONS REQUIRE THAT AT LEAST ONE LAYER OF GWB BE CUT TO FOLLOW UNDULATING SURFACES OF SUPERSTRUCTURES INCLUDING BUT NOT LIMITED TO FLUTES METAL DECKING. JOINT GWB TO SUPERSTRUCTURE WITH A CONTINUOUS BEAD OF ACOUSTICAL SEALANT.

4. BUILDING CODE REQUIRES THAT "SMOKE PARTITIONS" BE SEALED TO STRUCTURE AS INDICATED TO SUCCESSFULLY "….LIMIT THE PASSAGE OF SMOKE….".

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

TRIPLE C - The A/E Group

100 Pearl Street, 14th Floor

Hartford, CT 06103

MAT PERKINS

860-270-0753 mat.perkins@triplecaeg.com

A u to d e s k D o c s /3

C

R

.P ro je c t.

-2

-7

.E H

R M

.I U

.B e d fo rd

.M A

.R

/5

-2 -7

.B e d fo rd .E

H R

M .A

R C

H .B

R

.r v t

/2

/2

:2

:0

A

M

02A-512

ARCHITECTURAL PARTITION HEAD DETAILS 518-22-700

06/04/2025 M. Perkins K. McDermott

ISSUED FOR CONSTRUCTION EHRM INFRASTRUCTURE

UPGRADES

200 Springs Rd, Bedford, MA 01730

3" = 1'-0" B5

HEAD-OF-WALL CONDITIONS - STUD WALLS - FIRE RATED WALLS

3" = 1'-0" D5

HEAD-OF-WALL CONDITIONS - STUD WALLS - SMOKE PARTITIONS AND SOUND CONTROL WALLS

NOTE:

STANDARD DETAILS APPLY TO TYPICAL CONSTRUCTION

TYPES AND ASSEMBLIES. NOT ALL DETAILS MAY BE

USED. CONTRACTOR SHALL VERIFY ACTUAL CONDITIONS

ON-SITE.

Revisions: Date:

Addendum 1 02/25/2026

SHEET SYMBOL LEGEND

EXISTING CONSTRUCTION TO REMAIN

EXISTING CONSTRUCTION TO BE DEMOLISHED

NEW CONSTRUCTION, WITH PARTITION TYPE

GENERAL INTERIOR NOTES

KEYNOTES

GENERAL FINISH NOTES:

1. REFER TO SPECIFICATIONS FOR ADDITIONAL MATERIAL AND

INSTALLATION REQUIREMENTS.

2. REFER TO THIS SHEET FOR FINISH LEGEND AND ROOM FINISH

SCHEDULE.

3. IF POSSIBLE PROVIDE MATERIALS FROM SAME PRODUCTION RUN

FOR CONSISTENCY.

SUBSTITUTION NOTES:

1. COLOR IS AN IMPORTANT PART OF THIS PROJECT. ANY COLOR

SUBSTITUTION WILL REQUIRE APPROVAL BY THE COR.

TRANSITION NOTES:

1. INSTALL TRANSITIONS AT ALL DISSIMILAR FLOOR MATERIALS.

2. FOR ALL FLOOR FINISH AND PATTERN TRANSITIONS THAT OCCUR AT

DOORWAYS, TRANSITION MATERIALS AT CENTERLINE OF DOOR

WHEN DOOR PANEL IS IN THE CLOSED POSITION.

SIGNAGE NOTES:

1. REFER TO THIS SHEET SERIES SHEETS FOR SIGNAGE INFORMATION,

REFER TO SPECIFICATIONS FOR ADDITIONAL SIGNAGE,

IDENTIFICATION AND SYSTEMS/EQUIPMENT LABELING

REQUIREMENTS.

PAINTING NOTES:

1. ALL ADHESIVES AND PAINT TO BE LOW VOC/ODOR.

2. UNLESS OTHERWISE INDICATED, DO NOT PAINT FACTORY-FINISHED

ITEMS OR INSTALLER FINISHED ITEMS.

3. COORDINATE APPLICATIONS OF PAINTS AND ADHESIVES WITH COR.

PROVIDE SEALED ENVIRONMENT DURING HVAC FLUSH OUT PERIOD

TO ENSURE ODORS DO NOT TRANSMIT TO ADJACENT SPACES.

CODE NOTES:

1. ALL INTERIOR FINISHES SHALL HAVE FLAME SPREAD IN COMPLIANCE

WITH IBC 2024 803.13 INTERIOR WALL AND CEILING FINISH

REQUIREMENTS BY OCCUPANCY.

INSTALLATION NOTES:

1. PROVIDE BACKING FOR ALL WALL MOUNTED EQUIPMENT.

INTERIOR FINISHES

PAINT

FIELD

CALIFORNIA PAINTS*

TO MATCH BENJAMIN MOORE

MANCHESTER TAN HC-81

ARCHITECT/ENGINEERS:

INTERIOR FINISHES

Drawing Title

Approved: Project Director

Project Title

Location

Date Checked Drawn

NB KLM

Project Number

Board Number

Office of Construction and Facilities Management

*BASIS OF DESIGN

**MATCH EXISTING CAMPUS PAINT COLORS

EHRM INFRASTRUCTURE

UPGRADES

518-22-700

200 Springs Road, Bedford, MA 01730

EDITH NOURSE MEMORIAL VETERANS HOSPITAL

P-1

DIGITAL IMAGES MAY HAVE COLOR INACCURACIES, REFER

TO ACTUAL SAMPLE FOR TRUEST COLOR DEPICTION

PAINT

METAL DOORS & TRIM

CALIFORNIA PAINTS*

TO MATCH BENJAMIN MOORE

WHITE DOWN OC-131

P-2

WALL BASE

JOHNSONITE*

BEIGE 49

RB-1

PAPER INSERT CARRIER, MAGNETIC

MOUNT, WITH NON-GLARE LENS

TEXT: 5/8"H LASER-PRINTED TEXT,

HELVETICA MEDIUM

COLOR: TO MATCH STATION

STANDARDS

1-1/2" x 1/32" ADA

TACTILE NUMERALS

AND GRADE II BRAILLE234

9"

Restricted Access

5-3/16" X 9" CLEAR

ACETATE INSERT W/

COPY

9"X9" MAGNETICALLY

REMOVABLE SIGN

(ONE-PIECE)

RED SYMBOL AND

BLACK TEXT

1/2" 9" 1/2"

/2

/2

QUARTER-ROUND

SILVER FRAME

EXISTING FLOORING

TO BE REMOVED

TOP OF SLAB

EXISTING

FLOORING TO

REMAIN, EXISTING

ROOM SIDE EXISTING CONCRETE

FLOOR WITH STATIC

DISSIPATIVE (C-1/SDC)

RESILIENT BASE AS

SCHEDULED, EACH

SIDE OF NEW WALL

INSTALL 3/4"

PLYWOOD, MOUNT

BOTTOM OF

PLYWOOD 12" AFF

ADJACENT SPACE

TELECOM

ROOM SIDE

PARTITION AS SCHEDULED

EXISTING CONCRETE

FLOOR WITH STATIC

DISSIPATIVE (C-1/SDC)

LOCATION OF FLOOR

FINISH CHANGE;

SEAM OR ADAPTER

TRANSITION SHALL

OCCUR AT

CENTERLINE OF

DOOR IN CLOSED

POSITION

DOOR AS SCHEDULED

EXISTING FLOORING

TOP OF SLAB

CORRIDOR SIDE

DOOR FRAME BEYOND

C CENTER LINE OF DOORL

TRANSITION STRIP

(TR-1) OR EQUAL,

REFER TO SCHEDULE

FOR INFORMATION

TELECOM ROOM SIDE

SIGNAGE REFERENCES

VA SIGNAGE DESIGN MANUAL

SIGN VENDOR TO REFERENCE VA SIGNAGE DESIGN MANUAL FOR COMPLETE

SPECIFICATIONS

https://www.cfm.va.gov/til/spclRqmts.asp#SIGN

SIGN SYMBOL LEGEND

IN-04.01A

IN-08.02

IN-01.31

TELECOM ROOM FINISH DIAGRAM,

CONTRACTOR TO REFERENCE

ARCHITECTURE FOR ACTUAL WALL

CONSTRUCTION LOCATIONS

2 5 61

TYP.

F4

02IN101

TYP.

F1

02IN101

TYP.

INTERIOR FINISH SYMBOLS

MATERIAL FLOOR CHANGE (REFER TO THIS SHEET FOR DETAILS)

SEALED CONCRETE WITH STATIC DISSIPATIVE COATING (C-1/SDC)

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

TRIPLE C - The A/E Group

100 Pearl Street, 14th Floor

Hartford, CT 06103

MAT PERKINS

860-270-0753 mat.perkins@triplecaeg.com

A u to d e s k D o c s /3

C

R

.P ro je c t.

-2

-7

.E H

R M

.I U

.B e d fo rd

.M A

.R

/5

-2 -7

.B e d fo rd .E

H R

M .A

R C

H .B

R

.r v t

/2

/2

:2

:1

A

M

02IN101

INTERIOR FINISH PLAN, SIGNAGE & SCHEDULES 518-22-700

06/04/2025 M. Perkins K. McDermott

ISSUED FOR CONSTRUCTION EHRM INFRASTRUCTURE

UPGRADES

200 Springs Rd, Bedford, MA 01730

NTS

C1

COLOR BOARD

ROOM FINISH SCHEDULE

LEVEL NO. NAME

FLOOR WALLS CEILING

NOTESFINISH BASE

NORTH EAST SOUTH WEST

MATERIAL FINISHMATERIAL FINISH MATERIAL FINISH MATERIAL FINISH MATERIAL FINISH

LEVEL 1 141 TELECOM ROOM C-1/SDC RB-1 GWB P-1/ WD GWB P-1/ WD GWB P-1/ WD GWB P-1/ WD OPEN

LEVEL 2 236 TELECOM ROOM C-1/SDC RB-1 GWB P-1/ WD GWB P-1/ WD GWB P-1/ WD GWB P-1/ WD OPEN

LEVEL 3 342 TELECOM ROOM C-1/SDC RB-1 GWB P-1/ WD GWB P-1/ WD GWB P-1/ WD GWB P-1/ WD OPEN

BUILDING SIGNAGE SCHEDULE

VERSION

TYPE COUNT DESCRIPTION DETAIL LOCATION REFERENCE

ADA

BRAILLE TEXT COLOR BACKGROUND COLOR

DIMENSIONS

CommentsSIGN_HEIGHT SIGN_WIDTH MOUNTING HEIGHT

IN-01.31 3 FIRE IDENTIFICATION SIGN D6 / 02IN101 FEC REFER TO PAGE 429 OF SIGNAGE DESIGN MANUAL DATED 05/2023 NO WHITE RED 9" 9" 6' - 8" INSTALLED AT FIRE EXTINGUISHER CABINETS AT ALL NEW

TELECOM ROOMS

IN-04.01A 3 ROOM NUMBER IDENTIFICATION D3 / 02IN101 TELECOM ROOM REFER TO PAGE 259 OF SIGNAGE DESIGN MANUAL DATED 05/2023 YES REFERENCE EXISTING

CAMPUS STANDARDS

REFERENCE EXISTING

CAMPUS STANDARDS

9 1/2" 8 5/8" 5' - 0" INSTALLED AT ALL NEW TELECOM ROOMS

IN-08.02 3 PROHIBIT INSTRUCTIONAL AND

CONTROL

D1/ 02IN101 TELECOM ROOM REFER TO PAGE 279 OF SIGNAGE DESIGN MANUAL DATED 05/2023 NO REFERENCE EXISTING

CAMPUS STANDARDS

REFERENCE EXISTING

CAMPUS STANDARDS

9 1/2" 8 5/8" 5' - 9" INSTALLED AT ALL NEW TELECOM ROOMS MOUNTED

DIRECTLY ABOVE ROOM NAME SIGN

Grand total: 9

3" = 1'-0" D3

IN-04.01A SIGN DETAIL - PRIMARY ROOM

IDENTIFICATION

3" = 1'-0"

D1

IN-08.02 SIGN DETAIL - PROHIBIT

INSTRUCTIONAL AND CONTROL

12" = 1'-0"

D5

EXAMPLE OF EXISTING SIGNAGE

6" = 1'-0" F4

RESILIENT BASE (TOE BASE)

6" = 1'-0"

F1

THRESHOLD - CONCRETE TO EXISTING FLOORING

FINISH LEGEND

SYMBOL FINISH TYPE MANUFACTURER COLLECTION STYLE / TYPE COLOR SIZE SPEC SECTION NOTES

C-1/SDC SEALED CONCRETE WITH STATIC DISSIPATIVE COATING SEALED CONCRETE* - - - - - TELECOM ROOM SPACE TO RECEIVE STATIC CONTROL CONCRETE SEALER

F-1 WINDOW FILM 3M* FASARA 7725SE-324 FROSTED CRYSTAL - 08 87 33

P-1 PAINT CALIFORNIA PAINTS* - EGGSHELL TO MATCH BENJAMIN MOORE MANCHESTER TAN HC-81 - 09 91 00 FIELD

P-2 PAINT CALIFORNIA PAINTS* - SEMI-GLOSS TO MATCH BENJAMIN MOORE WHITE DOWN OC-131 - 09 91 00 METAL DOORS & TRIM

RB-1 RESILIENT BASE JOHNSONITE* TRADITIONAL TOE BASE BEIGE 49 4" 09 65 13

TR-1 TRIM SCHLUTER * - RENO-U SATIN ANODIZED ALUMINUM - 09 30 13 FLOOR TRANSITION

WD PLYWOOD FIRE TREATED PLYWOOD* - - HIGH GLOSS WHITE MPI (MASTER PAINTERS INSTITUTE)

67 OR SIM

4' X 8' - PLYWOOD TO BE PAINTED WITH 2 COATS OF FIRE RESISTANT PAINT; FIRE

RATING STAMPS SHALL NOT BE PAINTED OVER

1 REMOVE EXISTING FLOORING, ADHESIVES, AND INSTALL NEW WALL

BASE

2 EXISTING WALLS ARE TO BE PATCHED AND PAINTED. SEE ROOM

FINISH SCHEDULE THIS SHEET FOR FINISHES.

3 ALL WALLS TO RECEIVE NEW PLYWOOD, COORDINATE WITH

ELECTRICAL DRAWINGS FOR FIXTURE LOCATIONS

4 PROVIDE NEW ROOM SIGNAGE, SEE SIGNAGE SCHEDULE THIS

SHEET

5 REFER TO ARCHITECTURAL PLANS FOR DETAILED ROOM

CONFIGURATION INFORMATION

6 TELECOM ROOM SPACE TO RECEIVE STATIC CONTROL CONCRETE

SEALER

REFER TO THIS SHEET FOR ROOM FINISH SCHEDULE & FINISH LEGEND

*Materials are approved as basis of design, all material substitutions are subject to owner approval. Contractor to provide VA Interior Design Department with samples of all specified finish materials. VA COR/ Interior Design department shall approve all finishes prior to installation.

1/2" = 1'-0" F7

TYPICAL TELECOM ROOM FINISH DIAGRAM

3" = 1'-0" D6

IN-01.31 SIGN DETAIL - FIRE EQUIPMENT

IDENTIFICATION SIGN

Revisions: Date:

Addendum 1 02/25/2026

1 1

Sheets
02A-401 - ARCHITECTURAL ENLARGED VIEWS - FIRST LEVEL
02A-402 - ARCHITECTURAL ENLARGED VIEWS - THIRD LEVEL
02A-512 - ARCHITECTURAL PARTITION HEAD DETAILS
02IN101 - INTERIOR FINISH PLAN, SIGNAGE & SCHEDULES