Amend 5 - ATT 27-518-22-700.Bedford.EHRM.IFC.Add1.B62.20260225.pdf
PDF 6 MB Posted
- Solicitation number
- 36C77626R0003
About this file
This document is a set of architectural and construction drawings for the Edith Nourse Rogers Memorial Veterans Hospital Infrastructure Upgrades project (Project 518-22-700, Building 62) located at 200 Springs Road, Bedford, MA. The drawings were issued for construction on 06/04/2025 with Addendum 1 dated 02/25/2026.
The project involves hazardous material abatement, renovation of telecom rooms, and infrastructure upgrades across basement, first, and second levels. Key scope items include: removal of asbestos-containing materials (ACM) identified in pipe insulation, fittings, and transite panels (60 linear feet); abatement of lead-based paint (20 square feet) and transite panels with mastic and caulking (100 square feet); construction of three new 1-hour fire and smoke-rated telecom rooms (B24A, 125, and 225) with approximately 121-162 square feet each; installation of new electrical systems including UPS units, emergency and normal power distribution, access control, and mechanical systems; telecommunications infrastructure including new CAT 6A cabling, cable tray, wireless access points, and security cameras; and interior finishes with static dissipative concrete flooring, painted walls, resilient base, and room signage. All work must comply with OSHA silica dust regulations, EPA and state environmental requirements, and maintain building operations in adjacent occupied spaces. The contractor must coordinate work phasing with the VA Contracting Officer's Representative, provide containment barriers, decontamination facilities, and daily debris removal, and submit waste shipment records within 35 days of material departure from the site.
View the file
Other files
Show 40 more
Latest 50 of 105 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DN
DN
DN
DN
DN
UP
UP
DN
UP
UP
UP
HAZARDOUS MATERIAL ABATEMENT GENERAL NOTES
1. ALL HAZARDOUS MATERIAL REMOVAL SHALL BE PERFORMED IN ACCORDANCE WITH THE PROJECT SPECIFICATIONS AND ALL APPLICABLE FEDERAL, STATE AND LOCAL LAWS, REGULATIONS, ORDERS AND
DIRECTIVES INCLUDING WITHOUT LIMITATIONS THOSE OF THE RESPONSIBLE STATE OF
MASSACHUSETTS AGENCIES, U.S. ENVIRONMENTAL PROTECTION AGENCY, U.S. DEPARTMENT OF
LABOR, OCCUPATIONAL SAFETY AND HEALTH ADMINISTRATION, NATIONAL INSTITUTE OF OCCUPATIONAL SAFETY AND HEALTH, STATE OF MASSACHUSETTS DEPARTMENT OF PUBLIC HEALTH, AND THE STATE OF
MASSACHUSETTS DEPARTMENT OF ENVIRONMENTAL CONSERVATION
2. CONTRACTOR SHALL COMPLY WITH OSHA REGULATIONS FOR SILICA DUST CONTROL 29 CFR 1926.1153, 29 CFR 1910.134
3. CONTRACTOR SHALL USE EXTREME CARE AND CAUTION DURING ALL ABATEMENT PROCEDURES.
CONTRACTOR SHALL CONDUCT REMOVAL OF ALL MATERIALS FROM THE SITE WITH A MINIMUM
DISTURBANCE AND PROVIDE REGULAR MAINTENANCE AND PROTECTION OF THE BUILDING PREMISES, STAGING AREA, TRANSPORTATION ROUTES, ETC, THROUGHOUT THE BUILDING. REFER TO THE ICRA PLANS FOR GUIDANCE ON PLANNED DEBRIS TRANSPORT PATHS. COORDINATE PHASING OF WORK AND HAZARDOUS MATERIAL CONTAINMENT PLANS WITH THE COR. COORDINATE USAGE OF STAIRS VS USAGE OF CHUTE FOR DISPOSAL OF REMOVED HAZARDOUS MATERIAL ON THE FIRST LEVEL. THE ABATEMENT
CONTRACTOR SHALL PREPARE THE WORK AREA FOR REMOVAL IN ACCORDANCE WITH APPLICABLE
REGULATIONS. WHERE OVERLAPS OCCUR, THE MOST STRINGENT REQUIREMENTS APPLY.
4. THE DISTURBANCE OF ANY ACM, OR SUSPECT ACM, SHALL BE PERFORMED BY A MAS LICENSED
ASBESTOS ABATEMENT CONTRACTOR.
5. THE DISTURBANCE OF ANY LEAD-BASED PAINT, OR SUSPECT LBP, SHALL BE PERFORMED BY A MAS LICENSED LEAD ABATEMENT CONTRACTOR. LEAD CONTAINING PAINT AND CONTAMINATED MATERIALS
SHALL BE REMOVED AND DISPOSED OF IN COMPLIANCE WITH EPA AND OSHA REGULATIONS.
6. CONTRACTOR TO MAINTAIN MEANS OF EGRESS PATHWAYS AT ALL TIMES. COORDINATE ALTERNATE PROVISIONS AND OBTAIN APPROVAL FROM OWNER AND AHJ IF EXISTING MEANS OF EGRESS MUST BE COMPROMISED OF MATERIAL EQUIPMENT, WASTE TRAILERS/DUMPSTERS, AS WELL AS CONTRACTOR PARKING SHALL BE COORDINATED WITH THE REST OF THE CONTRACT DOCUMENTS, THE GENERAL
CONTRACTOR, AND THE COR.
7. CONTRACTOR SHALL DEVELOP AND IMPLEMENT WRITTEN STANDARD OPERATING PROCEDURES FOR
ABATEMENT WORK TO ENSURE MAXIMUM PROTECTION AND SAFEGUARDS FOR LEAD AND/OR
ASBESTOS EXPOSURE TO WORKERS, PATIENTS, EMPLOYEES, GENERAL PUBLIC, AND THE
ENVIRONMENT.
8. THE LOCATIONS OF SITE STORAGE SHALL BE COORDINATED WITH THE VA COR.
9. CONTRACTOR SHALL PROVIDE ALL TOOLS, SCAFFOLDING, LADDERS, BARRIERS, AND ASSOCIATED
MATERIALS AND EQUIPMENT REQUIRED TO COMPLETE ALL WORK INDICATED IN THE CONTRACT
DOCUMENTS. THE OWNER OR THEIR REPRESENTATIVE SHALL NOT BE RESPONSIBLE FOR LOST,
DAMAGED OR STOLEN ITEMS.
10. CONTRACTOR SHALL PROVIDE ALL SIGNS, LABELS, WARNINGS, AND POSTED INSTRUCTIONS THAT ARE
NECESSARY TO PROTECT, INFORM, AND WARN OF THE HAZARD FROM ASBESTOS EXPOSURE.
11. CONTRACTOR SHALL POST IN A PROMINENT AND CONVENIENT PLACE FOR LABORERS, A COPY OF THE
LATEST APPLICABLE REGULATIONS FROM OSHA, EPA, NIOSH, MASDPH, AND THE MASDEC.
12. CONTRACTOR SHALL COMPLETELY PROTECT ALL CONTROLS, CONDUIT, TUBING, ELECTRICAL PANELS, EQUIPMENT, ETC, SCHEDULED TO REMAIN WITHIN THE WORK AREAS.
13. ALL BUILDING FINISHES, CONSTRUCTION EQUIPMENT, OR OTHER COMPONENTS OF THE BUILDING WHICH ARE SCHEDULED TO REMAIN, THAT ARE DAMAGED OR ARE IN ANY WAY DISRUPTED AS A RESULT OF THE EXECUTION OF THIS CONTRACT ARE TO BE REPLACED OR RESTORED TO ORIGINAL CONDITIONS
BY THE CONTRACTOR, WITHOUT ADDITIONAL COST TO THE OWNER.
14. THE VA AND THE HAZARDOUS MATERIAL ABATEMENT CONTRACTOR SHALL MUTUALLY AGREE ON THE NUMBER AND LOCATION OF ANY REMOTE DECONTAMINATION UNITS DURING THE PRE-CONSTRUCTION
MEETING. TWO RECOMMENDED LOCATIONS HAVE BEEN PROVIDED ON THE DRAWINGS.
15. SUBMIT DRAWINGS INDICATING THE LOCATION AND NUMBER OF HEPA FILTER EQUIPPED NEGATIVE
PRESSURE MACHINES, AIRLOCKS, AND DECONTAMINATION CHAMBERS. SUBMIT CALCULATIONS
SHOWING THE NUMBER OF AIR CHANGES FOR EACH CONTAINMENTS AREA.
16. PHASE WORK AS REQUIRED BY THE GENERAL CONTRACTOR AND VA. CONTRACTOR TO COORDINATE DEMOLITION ACTIVITIES WITH COR TO MAINTAIN FULL FUNCTIONALITY OF ADJACENT OCCUPIED SPACES.
THE GROUND LEVEL IS INTENDED TO REMAIN OPERATIONAL DURING THIS PROJECT. UTILIZE GLOVEBAG
METHODS ON THE GROUND LEVEL TO MINIMIZE IMPACT ON BUILDING OPERATIONS.
17. CONTRACTOR TO PROVIDE FIRE, SMOKE, DIRT, DUST AND NOISE CONTAINMENT BARRIERS BETWEEN WORK AREA AND ADJACENT OCCUPIED SPACES. COORDINATE WITH VA ICRA, ASBESTOS, AND LEAD
ABATEMENT REQUIREMENTS, AND THE COR.
18. CONTRACTOR TO COORDINATE ALL UTILITY SYSTEM SHUTDOWN ACTIVITIES IN ADVANCE WITH THE COR.
ALL OCCUPIED SPACES ADJACENT TO THE AREA OF WORK ARE TO REMAIN OPERATIONAL.
19. WORK OUTSIDE OF NORMAL HOURS MUST BE APPROVED BY THE COR.
20. THE ASBESTOS ABATEMENT CONTRACTOR AND THE MECHANICAL AND PLUMBING CONTRACTORS SHALL
BE RESPONSIBLE FOR DISMANTLING ANY HVAC EQUIPMENT AS NECESSARY TO GAIN ACCESS TO ACM
ON HVAC EQUIPMENT FOR PROPER REMOVAL AND DISPOSAL.
21. CONTRACTOR TO REMOVE ALL DEMOLITION AND CONSTRUCTION DEBRIS ON A DAILY BASIS.
COORDINATE MEANS, METHODS AND ROUTES WITH VA ASBESTOS AND ICRA REQUIREMENTS, AND THE COR. ALL REMOVED HAZARDOUS MATERIALS AND HAZARDOUS MATERIAL CONTAMINATED WASTE SHALL BE PROPERLY PACKAGED PRIOR TO REMOVAL FROM THE WORK AREAS. WARNING LABELS SHALL BE APPLIED TO ASBESTOS WASTE AS APPROPRIATE. ALL ACM OR LCP REMOVED SHALL BE ACCOMPANIED BY A WASTE SHIPMENT RECORDS. COMPLETED WASTE SHIPMENT RECORDS SHALL BE PROVIDED TO THE OWNER AS A PART OF THE CLOSEOUT DOCUMENTATION, ORIGINAL RECORDS SHALL BE PROVIDED
TO THE OWNER WITHIN 35 DAYS OF WASTE LEAVING THE SITE.
22. CONTRACTOR TO ASSUME THAT ALL UNTESTED ORIGINAL BUILDING MATERIALS TO CONTAIN ASBESTOS OR LEAD, UNLESS SAID MATERIAL IS TESTED AND CONFIRMED AS CONTAINING LESS THAN THE REGULATED PERCENTAGE OF ASBESTOS AND/OR LEAD. EXISTING ACM HAS BEEN CONFIRMED IN PIPE INSULATION AND FITTINGS, SPECIFIC ORIGINAL FLOORING MATERIALS, AND IN TRANSITE PANELS AT RADIATORS BELOW WINDOWS. NO ASBESTOS CONTENT HAS BEEN IDENTIFIED IN SAMPLING OF CEILING TILES, DRYWALL, JOINT COMPOUND, SKIM COAT, FIBERBOARD, FIRESTOP, COVE BASE, MASONRY WINDOW CAULK, BATHROOM CAULK, TILE GROUT, TILE GLUE, CERAMIC TILES, OR SPECIFIC FLOORING MATERIALS. LEAD CONTAINING PAINT HAS BEEN IDENTIFIED IN AT LEAST ONE AREA IN THE FACILITY.
SHOULD ANY PREVIOUSLY UNIDENTIFIED OR OTHERWISE UNANTICIPATED SUSPECT MATERIAL BE IDENTIFIED DURING CONSTRUCTION, STOP WORK AND NOTIFY OWNER FOR FURTHER DIRECTION.
UNDER NO CIRCUMSTANCES SHALL THE CONTRACTOR COLLECT OR ANALYZE BULK SAMPLES OF
SUSPECT MATERIALS WITHOUT THE APPROVAL OF THE OWNER.
23. ALL MATERIAL MEASUREMENTS, QUANTITIES, AND LOCATIONS ARE APPROXIMATE AND FOR GENERAL ORIENTATION ONLY. AS HIDDEN CONDITIONS ARE UNCOVERED, ADDITIONAL HAZARDOUS MATERIAL MAY
BE UNCOVERED THAT REQUIRE ABATEMENT. REFER TO SPECIFICATIONS FOR ADDITIONAL
INFORMATION.
24. COORDINATE WITH INDUSTRIAL HYGIENIST FOR REVIEW OF MONITORING, AND FINAL CONFIRMATION OF
ABATED AREAS, REFER TO SPEC SECTION 02 82 13.13
KEYNOTES#
QUANTITIES - ACM /LEAD MATERIALSLEGEND
REMOVAL PATH
SAMPLE
HA ## SAMPLE LOCATION
ASBESTOS /
LEAD PAINT
NOT ALL SAMPLE LOCATIONS SHOWN FOR CLARITY. ONLY
POSITIVE OR POSITIVE STOP SAMPLES ARE LOCATED.
SAMPLE NUMBER PER SURVEY REPORT FROM TERRACON.
REFER TO SURVEY REPORT FOR SPECIFIC SAMPLE
INFORMATION
PATH INDICATED IS PROVIDED FOR INTENT ONLY.
COORDINATE FINAL REMOVAL PATHWAYS, PHASING, AND
METHODS WITH GENERAL CONTRACTOR AND COR.
SAMPLE
PNT ##
20 SF LEAD CONTAINING PAINT TO BE ABATED
TP
TRANSITE PANELS 100 SF TRANSITE PANEL, MASTIC AND CAULKING (AT
WINDOWS) TO BE ABATED.
60 LF PIPE FITTTINGS, INSULATION AND MASTIC TO
BE COMPLETELY ABATED AND REMOVED.
STAIR-4
162162
1-BED
PATIENT
RM
118118
1-BED
PATIENT
ROOM
120120
DAY RM
119119
SHOWER
115B115B
LINEN
117117
HOUSE
KEEPING
CLOSET
116116
STORAGE
115A115A
TOILET
114114
LOBBY
115115
PIPE
CHASE
127127
1-BED
PATIENT
RM
113113
STORAGE
130130
ELECTRICAL
CLOSET
112A112A
2-BED
PATIENT
RM
109 A109 A
2-BED
PATIENT
RM
109 B109 B
1-BED
HOSPICE
RM
109 C109 C
CORRIDOR
132132
SHOWER
131131
STAIR-6
163163
LOUNGE
108108
TOILET
108A108ACLOSET
108B108B
1-BED
PATIENT
RM
107107
OFFICE
NURSE
MGR
106106
MED
SYRGICAL
SUPPLY
105105
STORAGE
104104
STAIR-5
121121
UTILITY
STORAGE
122122
2-BED
PATIENT
ROOM
123123
2-BED
PATIENT
RM
103103
2-BED
PATIENT
RM
102102
NURSE
STATION
124124
MEDICATION
RM
125125
3-BED
PATIENT
RM
126126
STAFF
REST
ROOM
127127
STAIR-2
128128
STORAGE
101101
ELECTRICAL
CLOSET
101 A101 A
ELEVATOR
100 B100 B
LOBBY
100100
TELECOM
100A100A
ELEVATOR
100C100C
MENS
RESTROOM
148148
WOMENS
RESTROOM
149149
STAIR-1
161161
DAY RM
140140
NURSE
STATION
141141
NOURISHMENT
ALCOVE
141 A141 A
TOILET
141 B141 B
QUIET
ROOM
142142
NURSE
MANAGER
143143
STORAGE
ROOM
144144
STORAGE
145145
REHAB
146146
2-BED
PATIENT
RM
147147
6-BED
PATIENT
RM
130130
1-BED
PATIENT
RM
129129
1-BED
PATIENT
RM
131131
LINEN
132132
SHOWER
134 A134 AHOUSE
KEEPING
CLOSET
133133
STORAGE
134B134B
CLOSET
134134
LOBBY
134134
PIPE
CHASE
136136
TOILET
135135
PIPE
CHASE
139139
1-BED
PATIENT
RM
136136
1-BED
PATIENT
RM
137137
ELECTRICAL
CLOSET
137 A137 A
STAIR-3
160160
TOILET
140 A140 A
CORRIDOR
138138
CORRIDOR
150150
CORRIDOR
151151CORRIDOR
152152
CORRIDOR
112112
CORRIDOR
111111
SAMPLE
PNT#166
TP
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
A/E:
TRIPLE C - The A/E Group
100 Pearl Street, 14th Floor
Hartford, CT 06103
MAT PERKINS
860-270-0753 mat.perkins@triplecaeg.com
A u to d e s k D o c s /3
C
R
.P ro je c t.
-2
-7
.E H
R M
.I U
.B e d fo rd
.M A
.R
/5
-2 -7
.B e d fo rd .E
H R
M .A
R C
H .B
R
.r v t
/2
/2
:1
:5
A
M
62H-101
HAZARDOUS MATERIAL ABATEMENT PLAN -
FIRST LEVEL
518-22-700
06/04/2025 M PERKINS J SONES
ISSUED FOR
CONSTRUCTION
EHRM INFRASTRUCTURE
UPGRADES
200 Springs Rd, Bedford, MA 01730
1/8" = 1'-0" F2
HAZARDOUS MATERIAL ABATEMENT PLAN - FIRST LEVEL
1 PRIOR TO DEMO PROVIDE CONTAINMENT BARRIER AND PERSONNEL DECONTAMINATION FACILITY PER 02 82 11 DURING ABATEMENT WORK. COORDINATE TIMING WITH COR (48 HR MAX) TO MINIMIZE
DISRUPTION TO OCCUPIED SPACES.
2 ABATE AND REMOVE LEAD BASED PAINT THROUGHOUT ENTIRE ROOM. ASSUMED DOOR FRAMES ALSO CONTAIN LEAD BASED PAINT. DISPOSE OF FRAME PROPERLY WHERE FRAME IS BEING REMOVED.
WHERE FRAME IS TO REMAIN, ABATE AND REMOVE PAINT ON DOOR FRAME.
Revisions: Date:
Addendum 1 2/25/2026
02/25/2026
SHEET SYMBOL LEGEND
KEYNOTES
GENERAL NOTES
EXISTING CONSTRUCTION TO REMAIN
EXISTING CONSTRUCTION TO BE DEMOLISHED
NEW CONSTRUCTION, WITH PARTITION TYPE
A
A. SEE GENERAL NOTES AND PLANS FOR TYPICAL GENERAL PROJECT
REQUIREMENTS AND PROJECT LOCATION DRAWINGS.
B. SEE INTERIOR FINISH DRAWINGS FOR ADDITIONAL FINISHES
INFORMATION.
C. SEE MECHANICAL AND ELECTRICAL DRAWINGS FOR ADDITIONAL
SYSTEMS INFORMATION.
D. NEW TELECOM ROOMS SHALL BE 1 HOUR FIRE AND SMOKE RATED
AND COMPLY WITH THE LATEST VA PHYSICAL SECURITY STANDARDS,
AND CAMPUS STANDARDS.
E. SEE TYPICAL WALL FRAMING DETAILS ON SHEET A-511.
F. SEE TYPICAL HEAD OF WALL DETAIL ON SHEET A-512.
G. SEE TYPICAL CEILING DETAILS ON SHEET A-531
H. DATE OF THIS DRAWING SET. CONTRACTOR SHALL FIELD VERIFY ALL
DIMENSIONS, CONDITIONS, AND SITE-SPECIFIC INFORMATION AT THE
TIME OF BIDDING.
I. CONTRACTOR IS RESPONSIBLE FOR ALL COSTS ASSOCIATED
WITH MOVING, STORING AND RETURNING FURNISHINGS AND
EQUIPMENT TO THE PROPOSED WORK AREA(S). ANY
DISASSEMBLY AND REASSEMBLY OF SYSTEMS FURNITURE IN THE
PROPOSED WORK AREAS IS THE RESPONSIBILITY OF THE
CONTRACTOR AND MUST FOLLOW THE MANUFACTURER'S
WARRANTY.
PARTITION RATING GRAPHICS:
4 HR FIRE BARRIER
3 HR FIRE BARRIER
2 HR FIRE & SMOKE BARRIER
2 HR FIRE BARRIER
2 HR FIRE BARRIER/SHAFT
1 HR FIRE & SMOKE BARRIER
1 HR FIRE BARRIER
1 HR FIRE BARRIER/SHAFT
SMOKE PARTITION (NON RATED)
NON RATED
PARTITION RATING GRAPHIC DESIGNATION: PRIORITY
1 HIGHEST
5 LOWEST
PARTITIONS REQUIRED TO BE SMOKE RESISTANT, FIRE
RESISTANT, OR BOTH FIRE AND SMOKE RESISTANT ARE SHOWN
GRAPHICALLY ON PLANS WITH HATCH PATTERNS.
62A-400
B7
TELECOM
RM
B24AB24A
H
I
10 11
MECHANICAL
ROOM
B23AB23A
ELECTRONIC
EQUIPMENT
B24B24
LOBBY
B41B41
4'-9" 3'-4"
5 15
RESTROOM
B25
121 SF
H
I
10 11
MECHANICAL
ROOM
B23AB23A
TELECOM
RM
B24AB24A ELECTRONIC
EQUIPMENT
B24B24
LOBBY
B41B41
B
A H
W -S
H -3
F
B
B
A6
B
B
(EXTG V.I.F.)
8'-1 1/2"
(E X
T G
V .I.
F
'-1
1/
2"
2'-4"
H
I
10 11
TELECOM
RM
B24AB24A
3 1/2"
H
I
10 11
3 1/2"
RESTROOM
B25B25
ACOUSTICAL OR RATED
SEALANT BOTH SIDES
FLOOR LINE
5/8" GWB BOTH SIDES
SOUND ATTENUATION
BATTS (SAB) PER
SCHEDULE.
CEILING LINE
STRUCTURAL DECK
METAL STUDS, SIZE
PER SCHEDULE
62A-512
E5
A/C GRADE, 3/4" FIRE-
TREATED PLYWOOD
62A-512
B4
AT FIRE RATED
PARTITIONS
AT SMOKE RATED
PARTITIONS
BOTTOM OF PLYWOOD TO
BE AT 12" AFF
ACOUSTICAL OR RATED
FLEXIBLE SEALANT
FLOOR LINE
ADD ONE LAYER OF 5/8" GWB,
ONE-SIDE WITH APPROVED UL
SETTING COMPOUND BETWEEN
LAYERS AND FASTENED TO
WALL AS REQUIRED, AT
EXISTING GWB WALL
ASSEMBLIES
STRUCTURAL DECK
EXISTING METAL STUDS AND
BATT INSULATION TO REMAIN
A/C GRADE, 3/4" FIRE-TREATED
PLYWOOD, ADHERED TO CONCRETE
AT EXISTING CONCRETE WALL
ASSEMBLIES
BOTTOM OF PLYWOOD
TO BE AT 12" AFF
UL DESIGN V497
1-HOUR PARTITION RATED FROM BOTH SIDES
EXISTING GWB OR
CONCRETE WALL
ASSEMBLY, WHERE OCCURS
SIDE OF
EXISTING
ROOM OR
CORRIDOR TO
REMAIN
62A-512
E5
62A-512
B4
/2
V
A R
IE
S
S E
E P
L A
N
/2
UNO
4" 2"
ADJACENT WALL
WHERE OCCURS
SEALANT - EA SIDE &
ALL AROUND, TYP.
HOLLOW METAL FRAME
WALL - SEE PLAN
FOR TYPE
1/2" 1/2"
VARIES
SEE PLAN
WALL - SEE PLAN
FOR TYPE
SEALANT - EA. SIDE
& ALL AROUND,
TYP.
HOLLOW METAL
FRAME
D1
TYPICAL FRAME
H E
IG
H
T
2" WIDTH 2"
C1
FRAME TYPE ELEVATIONS DOOR TYPE ELEVATIONS
F
FLUSH
LINE OF
STRUCTURE
LINE OF
STRUCTURE
09 29 00
SOUND ATTENUATION BATTS
(SAB), WHERE OCCURS
NOTE:
IF PARTITION TYPE IS USED IN A
CHASE WALL CONDITION, PROVIDE
CROSS BRACING GUSSETS AT 48"
O.C. MAX VERTICALLY. FABRICATED
FROM 6" MTL STUDS.
6”
09 29 00
5/8" GWB
09 29 00
SAB RETAINER STRAP
WHERE SAB OCCURS
CEILING
07 92 00
SEALANT
09 22 16
METAL STUDS
62A-512
B4
62A-512
E5
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
TRIPLE C - The A/E Group
100 Pearl Street, 14th Floor
Hartford, CT 06103
MAT PERKINS
(860)270-0753
A u to d e s k D o c s /3
C
R
.P ro je c t.
-2
-7
.E H
R M
.I U
.B e d fo rd
.M A
.R
/5
-2 -7
.B e d fo rd .E
H R
M .A
R C
H .B
R
.r v t
/2
/2
:1
:5
A
M
62A-400
ARCHITECTURAL ENLARGED VIEWS - BASEMENT
LEVEL
518-22-700
06/04/2025 M. Perkins K. McDermott
ISSUED FOR
CONSTRUCTION
EHRM INFRASTRUCTURE
UPGRADES
200 Springs Rd, Bedford, MA 01730
1 DEMO PORTION OF WALL/FRAMING FOR NEW DOOR
2 DEMO ALL WALL MOUNTED ITEMS. VA COR TO DETERMINE IF ANY
ITEMS ARE TO BE SALVAGED PRIOR TO START OF DEMO.
3 PROVIDE TEMPORARY DUST TIGHT BARRIER AROUND WORK AREA
DURING ACTIVITIES WHICH PRODUCE DUST
4 DEMO ALL TOILET PARTITION AND SHELVING. VA COR TO
DETERMINE IF ANY ITEMS ARE TO BE SALVAGED PRIOR TO START
OF DEMO.
5 REMOVE EXISTING TILE FLOORING, GROUT, ADHESIVES, AND WALL
BASE. PATCH AND REPAIR AS NEEDED FOR A SMOOTH FINISH.
6 REMOVE EXISTING DOOR AND FRAME
7 EXISTING PLUMBING, FIXTURES, AND ACCESSORIES TO BE
DEMOLISHED. COORDINATE WITH VA COR FOR ANY ITEMS THAT
ARE TO BE SALVAGED. ALL PIPING TO BE DEMOLISHED BACK TO
SOURCE. REFER TO PLUMBING DRAWINGS FOR ALL ASSOCIATED
PLUMBING, PIPING AND FIXTURES TO BE DEMOLISHED.
8 AT NEW WALL INSTALLATIONS, CONTRACTOR TO PAINT NEW WALL
IN ITS ENTIRETY. INSTALL NEW WALL BASE AT ENTIRE WALL SPAN
OR APPROPRIATE TRANSITION LOCATION AS APPROVED BY THE
COR.
9 REMOVE EXISTING CEILING AND LIGHTS. MODIFY AND/OR PROVIDE
ADDITIONAL SUPPORTS AS REQUIRED FOR EXISTING CEILING ITEMS
TO REMAIN.
10 EXISTING WALL TO BECOME 1 HOUR FIRE AND SMOKE-RATED.
PATCH AND SEAL ALL PENETRATIONS AS NECESSARY.
11 DEMO ALL TILE WALL FINISHES. ALL WALLS SHOULD BE PATCHED
AND REPAIRED TO RECEIVE NEW WALL ITEMS.
12 NEW 45 MIN. FIRE RATED DOOR AND DOOR. SEE DOOR SCHEDULE
AND SPECIFICATIONS FOR ADDITIONAL INFORMATION. MODIFY
DOOR AS REQUIRED FOR NEW ACCESS CONTROL HARDWARE.
13 PROVIDE NEW FIRE EXTINGUISHER CABINET WITH A TYPE 2A: 10B: C
CLEAN AGENT FIRE EXTINGUISHER LOCATED NO GREATER THAN 75
FEET AWAY FROM THE NEW TR. CONTRACTOR TO COORDINATE
THE NEW LOCATION WITH THE COR. CONTRACTOR SHALL BID A
NEW FEC FOR EACH TR IN THE SCOPE
14 OPEN TO DECK
15 POTENTIAL ABATEMENT AT FLOOR FOR FLOOR PENETRATIONS.
REFER TO COVER SHEET FOR KNOWN ACM ITEMS WITHIN THIS
BUILDING.
16 REMOVE EXISTING WALL MOUNTED MIRROR, STORE AND PROTECT
FOR RE-INSTALLATION. CONTRACTOR IS RESPONSIBLE FOR ALL
DAMAGES.
17 RE-INSTALL STORED WALL MOUNTED MIRROR. COR TO CONFIRM
PLACEMENT OF MIRROR PRIOR TO INSTALL
1/32" = 1'-0" F7
BASEMENT LEVEL REFERENCE PLAN
1/4" = 1'-0" D7
ARCHITECTURAL FLOOR PLAN - BASEMENT
LEVEL - RM B24A - DEMO
1/4" = 1'-0" B7
ARCHITECTURAL FLOOR PLAN - BASEMENT
LEVEL - RM B24A - NEW
1/4" = 1'-0"
B5
ARCHITECTURAL REFLECTED CEILING PLAN -
BASEMENT LEVEL - RM B24A - NEW
1/4" = 1'-0" D5
ARCHITECTURAL REFLECTED CEILING PLAN -
BASEMENT LEVEL - RM B24A - DEMO
DOOR AND FRAME SCHEDULE
IDENTIFICATION DIMENSIONS PANEL FRAME DETAIL
FIRE RATING
HARDWARE
NOTESLEVEL ROOM NO. ROOM NAME DOOR NO. W1 H T TYPE MATERIAL FINISH GLAZING UNDERCUT TYPE MATERIAL FINISH HEAD JAMB SILL GROUP ELECTRICAL
BASEMENT B24A TELECOM RM B24A 3' - 0" 7' - 0" 1 3/4" F HM P-2 NONE 3/8" 1 HM P-2 C1/62A-400 C3/62A-400 F1/62IN101 45 MIN. HW-SH-3F SEE SPEC 1
LEVEL 1 125 TELECOM RM 125 3' - 0" 7' - 0" 1 3/4" F HM P-2 NONE 3/8" 1 HM P-2 C1/62A-400 C3/62A-400 F1/62IN101 45 MIN. HW-SH-3F SEE SPEC 1,2
LEVEL 2 225 TELECOM ROOM 224E 3' - 0" 7' - 0" 1 3/4" F HM P-2 NONE 3/8" 1 HM P-2 C1/62A-400 C3/62A-400 F1/62IN101 45 MIN. HW-SH-3F SEE SPEC 1,2
1. SEE SPECIFICATIONS 08 71 00 FOR DOOR HARDWARE REQUIREMENTS. COORDINATE WITH ELECTRICAL.
2. DOOR HAS EXISTING CARD ACCESS
NOTE: FIRE RESISTANCE TEST FOR ONE HOUR RATED WALLS: UL
U465
(TYPE A) TYPICAL PARTITION
MARK STUD WIDTH PRTN WIDTH DESIGN STC
A4 4" 5 1/4" 35
A6 2 1/2" 6" 45
NOTE: FIRE RESISTANCE TEST FOR TWO HOUR RATED WALLS: UL
V438, UL U411
(TYPE B) TYPICAL PARTITION
MARK STUD WIDTH PRTN WIDTH DESIGN STC
B 2 1/2" 3/4" 45
3" = 1'-0" C1
HOLLOW METAL JAMB DETAIL
3" = 1'-0" D1
HOLLOW METAL HEAD DETAIL
1/4" = 1'-0"
D3
DOOR AND FRAME TYPES ELEVATIONS
Number Revisions: Date:
1 Addendum 1 2/25/2026
(TYPE J) NON-RATED PARTITION
MARK STUD WIDTH PRTN WIDTH DESIGN STC
J2 2 1/2" 3 1/8" -
DN
DN
DN
DN
UP
UP
DN
UP
UP
UP
DN
SHEET SYMBOL LEGEND
KEYNOTES
GENERAL NOTES
EXISTING CONSTRUCTION TO REMAIN
EXISTING CONSTRUCTION TO BE DEMOLISHED
NEW CONSTRUCTION, WITH PARTITION TYPE
A
A. SEE GENERAL NOTES AND PLANS FOR TYPICAL GENERAL PROJECT
REQUIREMENTS AND PROJECT LOCATION DRAWINGS.
B. SEE INTERIOR FINISH DRAWINGS FOR ADDITIONAL FINISHES
INFORMATION.
C. SEE MECHANICAL AND ELECTRICAL DRAWINGS FOR ADDITIONAL
SYSTEMS INFORMATION.
D. NEW TELECOM ROOMS SHALL BE 1 HOUR FIRE AND SMOKE RATED
AND COMPLY WITH THE LATEST VA PHYSICAL SECURITY STANDARDS,
AND CAMPUS STANDARDS.
E. SEE TYPICAL WALL FRAMING DETAILS ON SHEET A-511.
F. SEE TYPICAL HEAD OF WALL DETAIL ON SHEET A-512.
G. SEE TYPICAL CEILING DETAILS ON SHEET A-531
H. DATE OF THIS DRAWING SET. CONTRACTOR SHALL FIELD VERIFY ALL
DIMENSIONS, CONDITIONS, AND SITE-SPECIFIC INFORMATION AT THE
TIME OF BIDDING.
I. CONTRACTOR IS RESPONSIBLE FOR ALL COSTS ASSOCIATED
WITH MOVING, STORING AND RETURNING FURNISHINGS AND
EQUIPMENT TO THE PROPOSED WORK AREA(S). ANY
DISASSEMBLY AND REASSEMBLY OF SYSTEMS FURNITURE IN THE
PROPOSED WORK AREAS IS THE RESPONSIBILITY OF THE
CONTRACTOR AND MUST FOLLOW THE MANUFACTURER'S
WARRANTY.
PARTITION RATING GRAPHICS:
4 HR FIRE BARRIER
3 HR FIRE BARRIER
2 HR FIRE & SMOKE BARRIER
2 HR FIRE BARRIER
2 HR FIRE BARRIER/SHAFT
1 HR FIRE & SMOKE BARRIER
1 HR FIRE BARRIER
1 HR FIRE BARRIER/SHAFT
SMOKE PARTITION (NON RATED)
NON RATED
PARTITION RATING GRAPHIC DESIGNATION: PRIORITY
1 HIGHEST
5 LOWEST
PARTITIONS REQUIRED TO BE SMOKE RESISTANT, FIRE
RESISTANT, OR BOTH FIRE AND SMOKE RESISTANT ARE SHOWN
GRAPHICALLY ON PLANS WITH HATCH PATTERNS.
62A-401
B7
TELECOM
RM
125125
H
I
11 12
41 15
H
I
11 12
NURSE
STATION
124124
3-BED
PATIENT
RM
126126
CORRIDOR
151151
TELECOM
RM
162 SF
TYP.
H W
-S H
-3 F
B
B
A
B
B
J2
H
I
11 12
MEDICATION
RM
125125
H
I
11 12
TELECOM
RM
125125
62A-401
B3
TELECOM
ROOM
225225
H
I
41 15
H
I
NURSE
STATION
224224
TELECOM
ROOM
122 SF
3-BED
PATIENT
RM
226226
TYP.
4E
H W
-S H
-3 F
A
B B
B
B
B
(E X
IS
T
V
IF
'-5
/4
(EXIST VIF)
8'-2 1/2"
2'-5 1/4"
J2
H
I
H
I
TELECOM
ROOM
225225
MEDICATION
RM
162 SF
3-BED
PATIENT
RM
126126
NURSE
STATION
124124
OFFICE
121 SF 3-BED
PATIENT
RM
226226
NURSE
STATION
224224OFFICE
121 SF
3-BED
PATIENT
RM
226226
NURSE
STATION
224224
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
TRIPLE C - The A/E Group
100 Pearl Street, 14th Floor
Hartford, CT 06103
MAT PERKINS
(860)270-0753
A u to d e s k D o c s /3
C
R
.P ro je c t.
-2
-7
.E H
R M
.I U
.B e d fo rd
.M A
.R
/5
-2 -7
.B e d fo rd .E
H R
M .A
R C
H .B
R
.r v t
/2
/2
:1
:5
A
M
62A-401
ARCHITECTURAL ENLARGED VIEWS - FIRST
LEVEL
518-22-700
06/04/2025 M. Perkins K. McDermott
ISSUED FOR
CONSTRUCTION
EHRM INFRASTRUCTURE
UPGRADES
200 Springs Rd, Bedford, MA 01730
1/32" = 1'-0" F7
FIRST LEVEL REFERENCE PLAN
1/32" = 1'-0"
F3
SECOND FLOOR REFERENCE PLAN
1/4" = 1'-0" D7
ARCHITECTURAL FLOOR PLAN - FIRST LEVEL
- RM 125 - DEMO
1/4" = 1'-0" B7
ARCHITECTURAL FLOOR PLAN - FIRST LEVEL
- RM 125 - NEW
1/4" = 1'-0" D3
ARCHITECTURAL FLOOR PLAN - SECOND
LEVEL - RM 225 - DEMO
1/4" = 1'-0" B3
ARCHITECTURAL FLOOR PLAN - SECOND
LEVEL - RM 225 - NEW
1 REMOVE ALL EXISTING WALL MOUNTED ITEMS. REPAIR, PATCH
AND PAINT WALLS AS REQUIRED.
2 REMOVE EXISTING FLOORING, ADHESIVES, AND WALL BASE
3 PROVIDE TEMPORARY DUST TIGHT BARRIER AROUND WORK
AREA DURING ACTIVITIES WHICH PRODUCE DUST
4 ALL ITEMS ARE TO BE REMOVED FROM SPACE PRIOR TO DEMO.
5 EXISTING WALL TO BECOME 1 HOUR FIRE AND SMOKE-RATED.
PATCH AND SEAL ALL PENETRATIONS AS NECESSARY.
6 REMOVE EXISTING WINDOW AC UNIT
7 REMOVE EXISTING DOOR AND FRAME
8 AT NEW WALL INSTALLATIONS, CONTRACTOR TO PAINT NEW WALL
IN ITS ENTIRETY. INSTALL NEW WALL BASE AT ENTIRE WALL SPAN
OR APPROPRIATE TRANSITION LOCATION AS APPROVED BY THE
COR.
9 REMOVE EXISTING ACOUSTICAL CEILING AND LIGHTS. MODIFY
AND/OR PROVIDE ADDITIONAL SUPPORTS AS REQUIRED FOR
EXISTING CEILING ITEMS TO REMAIN.
10 EXISTING PLUMBING, FIXTURES, AND ACCESSORIES TO BE
DEMOLISHED. COORDINATE WITH VA COR FOR ANY ITEMS THAT
ARE TO BE SALVAGED. ALL PIPING TO BE DEMOLISHED BACK TO
SOURCE. REFER TO PLUMBING DRAWINGS FOR ALL ASSOCIATED
PLUMBING, PIPING AND FIXTURES TO BE
DEMOLISHED.
11 NEW FURRING WALL AT EXTERIOR WALL TO ENCLOSE WINDOW.
MAINTAIN 1/2" GAP BETWEEN EXISTING WALL INTERIOR FACE AND
NEW STUDS. MODIFY/ REMOVE INTERIOR WINDOW TRIM AS
REQUIRED. INSTALL WINDOW FILM AT ALL FURRED WINDOWS. SEE
62IN101 FOR MORE INFORMATION.
12 OPEN TO DECK
13 NEW 45 MIN. FIRE RATED DOOR AND FRAME. SEE DOOR
SCHEDULE AND SPECIFICATIONS FOR ADDITIONAL INFORMATION.
MODIFY DOOR AS REQUIRED FOR NEW ACCESS CONTROL
HARDWARE.
14 PROVIDE NEW FIRE EXTINGUISHER CABINET WITH A TYPE 2A:
10B: C CLEAN AGENT FIRE EXTINGUISHER LOCATED NO GREATER
THAN 75 FEET AWAY FROM THE NEW TR. CONTRACTOR TO
COORDINATE THE NEW LOCATION WITH THE COR. CONTRACTOR
SHALL BID A NEW FEC FOR EACH TR IN THE SCOPE
15 POTENTIAL ABATEMENT AT FLOOR TO FLOOR PENETRATIONS
1/4" = 1'-0" D5
ARCHITECTURAL REFLECTED CEILING PLAN -
FIRST LEVEL - RM 125 - DEMO
1/4" = 1'-0" B5
ARCHITECTURAL REFLECTED PLAN - FIRST
LEVEL - RM 125 - NEW
1/4" = 1'-0" D1
ARCHITECTURAL REFLECTED CEILING PLAN -
SECOND LEVEL - RM 225 - DEMO
1/4" = 1'-0" B1
ARCHITECTURAL REFLECTED CEILING PLAN -
SECOND LEVEL - RM 225 - NEW
Number Revisions: Date:
1 Addendum 1 2/25/2026
"FIRE-RATED WALLS"- ADDITIONAL NOTES:
1. CONDITIONS INDICATED TO SHOW DESIGN INTENT. THEY ARE NOT INTENDED TO BE PROPRIETARY. CONTRACTOR MAY EMPLOY SIMILAR A UL-APPROVED TOP-OF-WALL DESIGNS THAT ARE APPROPRIATE FOR CONDITIONS.
2. REFER TO SECTION 07 84 00 / FIRESTOPPING FOR ADDITIONAL REQUIREMENTS REGARDING HEAD-OF-WALL CONDITION FOR FIRE-RATED WALLS.
SLOTTED TOP
TRACK
STUD
DESIGN BASIS: UL-HW-D-0082
CONCRETE SLAB
DESIGN BASIS: UL-HW-D-0042
METAL DECK
(PERPENDICULAR TO FLUTES)
/8
DESIGN BASIS: UL-HW-D-0264
METAL DECK
(PARALLEL TO FLUTES)
1" 1" 2"x20 GA
STRAPS @ 16"
O.C.
DESIGN BASIS: UL-HW-D-0259
STEEL BEAM
20 GA Z-BARS
TO
ACCOMMODATE
SFRM
SPRAY-APPLIED
FIRE-RESISTIVE
MATERIAL
(SFRM)
SAB
1 OR 2 LAYERS OF GWB;
SEE WALL TYPE
FIRE STOP SEALANT
FIRE STOP JOINT
SPRAY
MINERAL WOOL
FORMING MATERIAL
/8
/8
FIRE STOP JOINT
SPRAY
SLOTTED TOP
TRACK
STUD
SAB
1 OR 2 LAYERS OF GWB;
SEE WALL TYPE
/8
MINERAL WOOL
FORMING MATERIAL
SLOTTED TOP
TRACK
STUD
CONCRETE SLAB METAL DECK
(PERPENDICULAR TO FLUTES)
/8
/8
METAL DECK
(PARALLEL TO FLUTES)
1" 1"
/8
SLOTTED TOP
TRACK
2"x20 GA
STRAPS @ 16"
O.C.
STEEL BEAM
/8
20 GA Z-BARS
TO
ACCOMMODATE
SFRM
SPRAY-APPLIED
FIRE-RESISTIVE
MATERIAL
(SFRM)
SAB
GWB
ACOUSTICAL SEALANT
CUT ONE LAYER GWB TO
FOLLOW PROFILE OF DECKING.
SEAL CONTINUOUSLY WITH
ACOUSTICAL SEALANT.
FILL FLUTE VOID W/
SAB
GWB SOUND AND
SMOKE CLOSURE
STRIP SECURE TO
STRUCTURE AND SEAL
WITH ACOUSTICAL
SEALANT
ACOUSTICAL
SEALANT (BOTH
SIDES)
STUD
SAB
GWB
ACOUSTICAL SEALANT
(BOTH SIDES)
"SMOKE PARTITIONS AND SOUND-CONTROL WALLS"- ADDITIONAL NOTES:
1. UPGRADE TO DETAIL "B4" WHERE WALL IS DESIGNATED WITH A FIRE-RESISTANCE RATING.
2. FILL VOIDS WITH SOUND ATTENUATION BATTS (SAB).
3. SOUND WALLS AND SMOKE PARTITIONS REQUIRE THAT AT LEAST ONE LAYER OF GWB BE CUT TO FOLLOW UNDULATING SURFACES OF SUPERSTRUCTURES INCLUDING BUT NOT LIMITED TO FLUTES METAL DECKING. JOINT GWB TO SUPERSTRUCTURE WITH A CONTINUOUS BEAD OF ACOUSTICAL SEALANT.
4. BUILDING CODE REQUIRES THAT "SMOKE PARTITIONS" BE SEALED TO STRUCTURE AS INDICATED TO SUCCESSFULLY "….LIMIT THE PASSAGE OF SMOKE….".
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
TRIPLE C - The A/E Group
100 Pearl Street, 14th Floor
Hartford, CT 06103
MAT PERKINS
(860)270-0753
A u to d e s k D o c s /3
C
R
.P ro je c t.
-2
-7
.E H
R M
.I U
.B e d fo rd
.M A
.R
/5
-2 -7
.B e d fo rd .E
H R
M .A
R C
H .B
R
.r v t
/2
/2
:1
:5
A
M
62A-512
ARCHITECTURAL PARTITION HEAD DETAILS 518-22-700
06/04/2025 M. Perkins K. McDermott
ISSUED FOR
CONSTRUCTION
EHRM INFRASTRUCTURE
UPGRADES
200 Springs Rd, Bedford, MA 01730
3" = 1'-0" B4
HEAD-OF-WALL CONDITIONS - STUD WALLS - FIRE RATED WALLS
3" = 1'-0" E5
HEAD-OF-WALL CONDITIONS - STUD WALLS - SMOKE PARTITIONS AND SOUND CONTROL WALLS
NOTE:
STANDARD DETAILS APPLY TO TYPICAL CONSTRUCTION
TYPES AND ASSEMBLIES. NOT ALL DETAILS MAY BE
USED. CONTRACTOR SHALL VERIFY ACTUAL CONDITIONS
ON-SITE.
Number Revisions: Date:
1 Addendum 1 2/25/2026
SHEET SYMBOL LEGEND
EXISTING CONSTRUCTION TO REMAIN
EXISTING CONSTRUCTION TO BE DEMOLISHED
NEW CONSTRUCTION, WITH PARTITION TYPE
GENERAL INTERIOR NOTES
KEYNOTES
GENERAL FINISH NOTES:
1. REFER TO SPECIFICATIONS FOR ADDITIONAL MATERIAL AND
INSTALLATION REQUIREMENTS.
2. REFER TO THIS SHEET FOR FINISH LEGEND AND ROOM FINISH
SCHEDULE.
3. IF POSSIBLE PROVIDE MATERIALS FROM SAME PRODUCTION RUN
FOR CONSISTENCY.
SUBSTITUTION NOTES:
1. COLOR IS AN IMPORTANT PART OF THIS PROJECT. ANY COLOR
SUBSTITUTION WILL REQUIRE APPROVAL BY THE COR.
TRANSITION NOTES:
1. INSTALL TRANSITIONS AT ALL DISSIMILAR FLOOR MATERIALS.
2. FOR ALL FLOOR FINISH AND PATTERN TRANSITIONS THAT OCCUR AT
DOORWAYS, TRANSITION MATERIALS AT CENTERLINE OF DOOR
WHEN DOOR PANEL IS IN THE CLOSED POSITION.
SIGNAGE NOTES:
1. REFER TO THIS SHEET SERIES SHEETS FOR SIGNAGE INFORMATION,
REFER TO SPECIFICATIONS FOR ADDITIONAL SIGNAGE,
IDENTIFICATION AND SYSTEMS/EQUIPMENT LABELING
REQUIREMENTS.
PAINTING NOTES:
1. ALL ADHESIVES AND PAINT TO BE LOW VOC/ODOR.
2. UNLESS OTHERWISE INDICATED, DO NOT PAINT FACTORY-FINISHED
ITEMS OR INSTALLER FINISHED ITEMS.
3. COORDINATE APPLICATIONS OF PAINTS AND ADHESIVES WITH COR.
PROVIDE SEALED ENVIRONMENT DURING HVAC FLUSH OUT PERIOD
TO ENSURE ODORS DO NOT TRANSMIT TO ADJACENT SPACES.
CODE NOTES:
1. ALL INTERIOR FINISHES SHALL HAVE FLAME SPREAD IN COMPLIANCE
WITH IBC 2024 803.13 INTERIOR WALL AND CEILING FINISH
REQUIREMENTS BY OCCUPANCY
INSTALLATION NOTES:
1. PROVIDE BACKING FOR ALL WALL MOUNTED EQUIPMENT.
MATERIAL FLOOR CHANGE (REFER TO THIS SHEET FOR DETAILS)
INTERIOR FINISH SYMBOLS
CONCRETE WITH STATIC DISSIPATIVE COATING (C-1/ SDC)
INTERIOR FINISHES
PAINT
FIELD
CALIFORNIA PAINTS*
TO MATCH BENJAMIN MOORE
MANCHESTER TAN HC-81
ARCHITECT/ENGINEERS:
INTERIOR FINISHES
Drawing Title
Approved: Project Director
Project Title
Location
Date Checked Drawn
NB KLM
Project Number
Board Number
Office of Construction and Facilities Management
*BASIS OF DESIGN
**MATCH EXISTING CAMPUS PAINT COLORS
EHRM INFRASTRUCTURE
UPGRADES
518-22-700
200 Springs Road, Bedford, MA 01730
EDITH NOURSE MEMORIAL VETERANS HOSPITAL
P-1
DIGITAL IMAGES MAY HAVE COLOR INACCURACIES, REFER
TO ACTUAL SAMPLE FOR TRUEST COLOR DEPICTION
PAINT
METAL DOORS & TRIM
CALIFORNIA PAINTS*
TO MATCH BENJAMIN MOORE
WHITE DOWN OC-131
P-2
WALL BASE
JOHNSONITE*
BEIGE 49
RB-1
PAPER INSERT CARRIER, MAGNETIC
MOUNT, WITH NON-GLARE LENS
TEXT: 5/8"H LASER-PRINTED TEXT,
HELVETICA MEDIUM
COLOR: TO MATCH STATION
STANDARDS
1-1/2" x 1/32" ADA
TACTILE NUMERALS
AND GRADE II BRAILLE234
9"
Restricted Access
5-3/16" X 9" CLEAR
ACETATE INSERT W/
COPY
9"X9" MAGNETICALLY
REMOVABLE SIGN
(ONE-PIECE)
RED SYMBOL AND
BLACK TEXT
1/2" 9" 1/2"
/2
/2
QUARTER-ROUND
SILVER FRAME
EXISTING FLOORING
TO BE REMOVED
TOP OF SLAB
EXISTING
FLOORING TO
REMAIN, EXISTING
ROOM SIDE EXISTING CONCRETE
FLOOR WITH STATIC
DISSIPATIVE (C-1/SDC)
RESILIENT BASE AS
SCHEDULED, EACH
SIDE OF NEW WALL
INSTALL 3/4"
PLYWOOD, MOUNT
BOTTOM OF
PLYWOOD 12" AFF
ADJACENT SPACE
TELECOM
ROOM SIDE
PARTITION AS SCHEDULED
EXISTING CONCRETE
FLOOR WITH STATIC
DISSIPATIVE
(C-1/SDC)
LOCATION OF FLOOR
FINISH CHANGE;
SEAM OR ADAPTER
TRANSITION SHALL
OCCUR AT
CENTERLINE OF
DOOR IN CLOSED
POSITION
DOOR AS SCHEDULED
EXISTING FLOORING
TOP OF SLAB
CORRIDOR SIDE
DOOR FRAME BEYOND
C CENTER LINE OF DOORL
TRANSITION STRIP
(TR-1) OR EQUAL,
REFER TO SCHEDULE
FOR INFORMATION
TELECOM ROOM SIDE
SIGNAGE REFERENCES
VA SIGNAGE DESIGN MANUAL
SIGN VENDOR TO REFERENCE VA SIGNAGE DESIGN MANUAL FOR COMPLETE
SPECIFICATIONS
https://www.cfm.va.gov/til/spclRqmts.asp#SIGN
SIGN SYMBOL LEGEND
IN-08.02
IN-04.01A
IN-01.31
TELECOM ROOM FINISH DIAGRAM,
CONTRACTOR TO REFERENCE
ARCHITECTURE FOR ACTUAL WALL
CONSTRUCTION LOCATIONS
F1
62IN101
TYP.
F3
62IN101
TYP.
1 2 5 6
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
TRIPLE C - The A/E Group
100 Pearl Street, 14th Floor
Hartford, CT 06103
MAT PERKINS
(860)270-0753
A u to d e s k D o c s /3
C
R
.P ro je c t.
-2
-7
.E H
R M
.I U
.B e d fo rd
.M A
.R
/5
-2 -7
.B e d fo rd .E
H R
M .A
R C
H .B
R
.r v t
/2
/2
:1
:5
A
M
62IN101
INTERIOR FINISH PLAN, SIGNAGE & SCHEDULES 518-22-700
06/04/2025 M. Perkins K. McDermott
ISSUED FOR
CONSTRUCTION
EHRM INFRASTRUCTURE
UPGRADES
200 Springs Rd, Bedford, MA 01730
NTS
C1
COLOR BOARD
3" = 1'-0" D3
IN-04.01A SIGN DETAIL - PRIMARY ROOM
IDENTIFICATION
3" = 1'-0"
D1
IN-08.02 SIGN DETAIL - PROHIBIT
INSTRUCTIONAL AND CONTROL
NTS
D5
EXAMPLE OF EXISTING SIGNAGE
6" = 1'-0" F3
RESILIENT BASE (TOE BASE)
6" = 1'-0"
F1
THRESHOLD - CONCRETE TO EXISTING FLOORING
1 REMOVE EXISTING FLOORING, ADHESIVES, AND INSTALL NEW WALL
BASE
2 EXISTING WALLS ARE TO BE PATCHED AND PAINTED. SEE ROOM
FINISH SCHEDULE THIS SHEET FOR FINISHES.
3 ALL WALLS TO RECEIVE NEW PLYWOOD, COORDINATE WITH
ELECTRICAL DRAWINGS FOR FIXTURE LOCATIONS
4 PROVIDE NEW ROOM SIGNAGE, SEE SIGNAGE SCHEDULE THIS
SHEET
5 REFER TO ARCHITECTURAL PLANS FOR DETAILED ROOM
CONFIGURATION INFORMATION
6 TELECOM ROOM SPACE TO RECEIVE STATIC CONTROL CONCRETE
SEALER
REFER TO THIS SHEET FOR ROOM FINISH SCHEDULE & FINISH LEGEND
ROOM FINISH SCHEDULE
LEVEL NO. NAME
FLOOR WALLS CEILING
NOTESFINISH BASE
NORTH EAST SOUTH WEST
MATERIAL FINISHMATERIAL FINISH MATERIAL FINISH MATERIAL FINISH MATERIAL FINISH
BASEMENT B24A TELECOM RM C-1/SDC RB-1 GWB P-1/WD GWB P-1/WD GWB P-1/WD GWB P-1/WD OPEN
LEVEL 1 125 TELECOM RM C-1/SDC RB-1 GWB P-1/WD GWB P-1/WD GWB P-1/WD GWB P-1/WD OPEN
LEVEL 2 225 TELECOM ROOM C-1/SDC RB-1 GWB P-1/WD GWB P-1/WD GWB P-1/WD GWB P-1/WD OPEN
BUILDING SIGNAGE SCHEDULE
VERSIO
N TYPE COUNT DESCRIPTION DETAIL LOCATION REFERENCE
ADA
BRAILLE TEXT COLOR BACKGROUND COLOR
DIMENSIONS
CommentsSIGN_HEIGHT SIGN_WIDTH MOUNTING HEIGHT
IN-01.31 3 FIRE IDENTIFICATION SIGN D6 / IN101 FEC REFER TO PAGE 429 OF SIGNAGE DESIGN
MANUAL DATED 05/2023
NO WHITE RED 9" 9" 6' - 8" INSTALLED AT FIRE EXTINGUISHER CABINETS AT ALL
NEW TELECOM ROOMS
IN-04.01A 3 ROOM NUMBER IDENTIFICATION D3/ IN101 TELECOM ROOM REFER TO PAGE 259 OF SIGNAGE DESIGN
MANUAL DATED 05/2023
YES REFERENCE EXISTING
CAMPUS STANDARDS
REFERENCE EXISTING
CAMPUS STANDARDS
9" 9" 5' - 0" INSTALLED AT ALL NEW TELECOM ROOMS
IN-08.02 3 PROHIBIT INSTRUCTIONAL AND
CONTROL
D1/ IN101 TELECOM ROOM REFER TO PAGE 279 OF SIGNAGE DESIGN
MANUAL DATED 05/2023
NO REFERENCE EXISTING
CAMPUS STANDARDS
REFERENCE EXISTING
CAMPUS STANDARDS
9" 9" 5' - 9" INSTALLED AT ALL NEW TELECOM ROOMS MOUNTED
DIRECTLY ABOVE ROOM NAME SIGN
Grand total: 9
FINISH LEGEND
SYMBOL FINISH TYPE MANUFACTURER COLLECTION STYLE / TYPE COLOR SIZE SPEC SECTION NOTES
C-1/SDC SEALED CONCRETE WITH STATIC DISSIPATIVE COATING SEALED CONCRETE* - - - - - TELECOM ROOM SPACE TO RECEIVE STATIC CONTROL CONCRETE SEALER
F-1 FILM 3M* FASARA 7725SE-324 FROSTED CRYSTAL - 08 87 33 WINDOW FILM
P-1 PAINT CALIFIRNIA PAINTS* - EGGSHELL TO MATCH BENJAMIN MOORE MANCHESTER TAN HC-81 - 09 91 00 FIELD
P-2 PAINT CALIFORNIA PAINTS* - SEMI-GLOSS TO MATCH BENJAMIN MOORE WHITE DOWN OC-131 - 09 91 00 METAL DOORS & TRIM
RB-1 RESILIENT BASE JOHNSONITE* TRADITIONAL TOE BASE BEIGE 49 4" 09 65 13
TR-1 TRIM SCHLUTER * - RENO-U SATIN ANODIZED ALUMINUM - 09 30 13 FLOOR TRANSITION
WD PLYWOOD FIRE TREATED PLYWOOD* - - HIGH GLOSS WHITE MPI (MASTER PAINTERS INSTITUTE)
67 OR SIM
4' X 8' - PLYWOOD TO BE PAINTED WITH 2 COATS OF FIRE RESISTANT PAINT; FIRE
RATING STAMPS SHALL NOT BE PAINTED OVER
*Materials are approved as basis of design, all material substitutions are subject to owner approval. Contractor to provide VA Interior Design Department with samples of all specified finish materials. VA COR/ Interior Design department shall approve all finishes prior to installation.
1/2" = 1'-0" F8
TYPICAL TELECOM ROOM FINISH DIAGRAM
3" = 1'-0" D6
IN-01.31 SIGN DETAIL - FIRE EQUIPMENT
IDENTIFICATION SIGN
Number Revisions: Date:
1 Addendum 1 2/25/2026
E S
CR
MD
RX DC
MD
CR
E S
DC RX
CR
E S
MD
DC RX
TELECOM RM
B24A
121 SF
LOBBY
B41
ELECTRONIC
EQUIPMENT
B24
B
-T R
B
A A
B
-T R
B
A B
B62-TRB24AB- 2,4,6
B62-TRB24AA- 2,4,6
B
-T R
B
A A
B
-T R
B
A A
B
-T R
B
A A
B
-T R
B
A B
B62-TRB24AB- 5
B62-TRB24AB- 1
B
-T R
B
A A
B
-T R
B
A A
B
-T R
B
A B
B62-TRB24AA- 1
B62-TRB24AB- 1
B62-TRB24AA- 1
B62-TRB24AB- 1
L1BL1
L1 L1
TYP.
IU-0-01
TYP.
TYP.
TYP.
TYP.
2 8
TYP.
TYP.
NURSE STATION
CORRIDOR
3-BED PATIENT
RM
B
-T R
A B
-T
R
B
B62-TR125B- 2,4,6
B62-TR125A- 2,4,6
L1
L1BL1
L1
B
-T R
5A
B
-T R
5A
B
-T R
5A
B
-T R
5B
B
-T R
5A
B62-TR125B- 1
B62-TR125A- 1
B
-T R
5B
B62-TR125A- 1
B62-TR125B- 1
B62-TR125A- 1
B62-TR125B- 1
TYP.
TYP.
TYP.
IU-1-01
TYP.
CU-1-01
CU-0-01 CU-2-01
B
-N P
A -T
R B
-N
P B
-T R
B
-T R
5B
5, B62-TR125B- 8,10
B
-T R
5B
,1
B
-T R
B
C U
-1 -0
CU-2-01
C U
-0 -0
13 19
TYP.
2 8
7 7
TYP.
TYP.
TELECOM RM
162 SF
TELECOM ROOM
122 SF
NURSE STATION
3-BED PATIENT
RM
B
-T R
A B
-T
R
B
B62-TR225A- 1 B62-TR225B- 1
B62-TR225A- 1B62-TR225B- 1
B62-TR225A- 1
B62-TR225B- 1
B
-T R
5A
B62-TR225B- 1
IU-2-01
TYP.
TYP.
TYP.
B
-T R
5A
B
-T R
5A
B
-T R
5B
B
-T R
5A
L1
L1
L1BL1
TYP.
B62-TR225A- 2,4,6
B62-TR225B- 2,4,6
TYP.
TYP.
TYP.
TYP.
MEDICATION RM
NURSE STATION
CORRIDOR
3-BED PATIENT
RM
TYP.
TYP.
OFFICE
NURSE STATION
3-BED PATIENT
RM
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
CONSULTANT
321 4 5 6 7 8 9 10
GENERAL NOTES
KEYNOTES
TRIPLE C - The A/E Group
100 Pearl Street, 14th Floor
Hartford, CT 06103
MAT PERKINS
860-270-0753
STAMP
mat.perkins@triplecaeg.com
A u to d e s k D o c s /3
C
R
.P ro je c t.
-2
-7
.E H
R M
.I U
.B e d fo rd .M
A .R
/5
-2
-7
.B e d fo rd
.E H
R M
.M E
P .B
R
.r v t
/2
/2
:0
:2
P
M
62E-401
ELECTRICAL ENLARGED PLANS 518-22-700
06/04/2025 M. Perkins J. Castenir
ISSUED FOR
CONSTRUCTION
EHRM INFRASTRUCTURE
UPGRADES
200 Springs Rd, Bedford, MA 01730
A. CONTRACTOR SHALL COORDINATE ALL EQUIPMENT, DUCTWORK AND PIPING
WITH STRUCTURAL, MECHANICAL, AND ELECTRICAL SYSTEMS AND SHALL
PROVIDE NECESSARY OFFSETS TO AVOID CONFLICTS AND TO MAINTAIN
REQUIRED EQUIPMENT ACCESS AND SERVICEABILITY.
B. EXISTING CONDITIONS ARE BASED ON EXISTING PLANS AND FIELD VERIFICATION
WHERE FEASIBLE. CONSTRUCTION AREA CONDITIONS MAY DIFFER FROM
THOSE INDICATED.
C. MINIMUM BRANCH CIRCUIT SIZE SHALL BE 2#12, 1#12G., 3/4"C.
D. CONTRACTOR SHALL COORDINATE FINAL POINT OF CONNECTIONS
WITH VA COR PRIOR TO ROUGH-IN.
E. PROVIDE NEMA 3R ENCLOSURES FOR EQUIPMENT INSTALLED
OUTDOORS
F. SIZE BRANCH CIRCUITS AND FEEDERS TO EQUIPMENT PER PANEL
SCHEDULE AND FEEDER AND BRANCH CIRCUIT SIZING TABLE ON E-701.
G. COORDINATE FINAL EQUIPMENT CONNECTIONS AT EQUIPMENT WITH
EQUIPMENT SUPPLIER, PRIOR TO ROUGH-IN.
H. LABEL DEVICE PLATES WITH A PERMANENT ADHESIVE LABEL LISTING
PANEL AND CIRCUIT FEEDING THE WIRING DEVICE.
I. UPDATE PANEL SCHEDULES AFFECTED BY RENOVATION.
J. NEW CIRCUIT BREAKERS PROVIDED SHALL MATCH THE EXISTING TYPE
AND AIC RATING OF CIRCUIT BREAKERS IN PANEL BEING RENOVATED.
K. CONTRACTOR SHALL FIELD COORDINATE CABLE TRAY LAYOUT WITH
EXISTING UTILITIES ROUTED THROUGH THE RENOVATED SPACE.
L. CONTRACTOR SHALL COMPLY WITH NEC 300.22 FOR CONDUIT ROUTED IN
PLENUM SPACES.
M. REFER TO E-901 FOR CUTSHEETS.
N. COMPLY WITH NEC 220.87 FOR ALL 30-DAY LOAD MEASUREMENTS OF
PANELBOARDS.
O. LOCATE DISCONNECT SWITCHES TO MAINTAIN WORKING CLEARANCES
PER NEC 110.26.
P. CONTRACTOR SHALL LABEL ALL JUNCTION BOX COVERS WITH THE CIRCUITS
CONTAINED AND SOURCE PANEL IDENTIFIED.
NOTE: NOT ALL KEYNOTES
ARE USED ON EACH SHEET
1. PROVIDE NEW 20" x 4" BONDING BAR, SET OF INSULATORS STAND-OFF
BRACKETS, AND STAINLESS STEEL SCREWS. PROVIDE ALL GROUNDING CABLE
AND CONNECTORS AND INSTALL PER TYPICAL DETAIL ON T-500 SERIES SHEETS.
2. NEW 5KW RACK-MOUNTED 208 V UNINTERRUPTIBLE POWER SUPPLY (UPS) WITH
NEMA 20A L21-20P INPUT AND L21-20R OUTPUT. PROVIDE NEW 208V 3-PHASE
CIRCUIT AND RECEPTACLE ON EMERGENCY POWER CIRCUIT. SEE T-500 SERIES
SHEETS FOR MORE DETAILS. ADDITIONALLY PROVIDE ADEQUATE RACK RAIL KIT
AND NIC FOR THE ASSOCIATED UPS.
3. PROVIDE ONE NEW EMERGENCY AND ONE NEW NORMAL POWER BRANCH
120/208 TPST CIRCUIT BREAKER FED FROM ABOVE FOR EACH RACK UPS
CIRCUIT. PROVIDE NEW CONDUIT, CONDUCTORS, AND DEVICES TO SUPPLY
EACH NEW RECEPTACLE. SEE T-500 SERIES SHEETS FOR MORE DETAILS.
4. NEW NORMAL POWER RECEPTACLE, SEE PANEL SCHEDULE FOR ADDITIONAL
INFORMATION.
5. NEW EMERGENCY POWER RECEPTACLE, SEE PANEL SCHEDULE FOR
ADDITIONAL INFORMATION.
6. NEW GFCI WET LOCATION RATED SERVICE RECEPTACLE. PROVIDE WITH A
WEATHERPROOF, EXTRA-DUTY, IN-USE COVER PER NEC 406.9.
7. NEW MECHANICAL INDOOR AND OUTDOOR UNITS, SEE MECHANICAL SHEETS
FOR ADDITIONAL INFORMATION.
8. PROVIDE (2) REDUNDANT VERTICAL PDUS AT EACH RACK.
9. SPACE FOR FUTURE RACK.
10. NEW POWER SUPPLY AND BATTERY BACKUP FOR NEW PACS EQUIPMENT.
PROVIDE A 20 AMP CIRCUIT PER NEC AND MANUFACTURERS
RECOMMENDATIONS.
11. PROVIDE NEW ACCESS CONTROL PER SPECIFICATIONS. HDP12 AND FIPS
COMPLIANT, CARD READER WITH PINPAD CARD, PIV READY.
12. LIGHTS SHALL BE WIRED TO THE NEW WALL MOUNTED SINGLE POLE SWITCH AT
THE CLOSET ENTRANCE. THE CONTROL SCHEME FOR THE LIGHTING CONTROL
SHALL BE MANUAL ON/ MANUAL OFF. COORDINATE FIXTURES WITH OVERHEAD
CABLE TRAY.
13. PROVIDE HEAVY DUTY NEMA 3R RATED 600V NON-FUSED DISCONNECT SWITCH
FOR MECHANICAL UNIT. SEE ELECTRICAL SCHEDULES ON E-700 SERIES SHEETS
FOR ADDITIONAL INFORMATION. COORDINATE LOCATION WITH NEW AND
EXISTING CONDITIONS.
14. NEW NORMAL POWER ELECTRICAL PANEL, FIELD COORDINATE LOCATION WITH
EXISTING AND NEW CONDITIONS. SEE E-600 AND E-700 SERIES SHEETS FOR
ADDITIONAL INFORMATION.
15. NEW EMERGENCY POWER ELECTRICAL PANEL, FIELD COORDINATE LOCATION
WITH EXISTING AND NEW CONDITIONS. SEE E-600 AND E-700 SERIES SHEETS
FOR ADDITIONAL INFORMATION.
16. NEW 4” SPEED CONDUIT SLEEVE THROUGH WALL ABOVE CEILING GRID FOR
HORIZONTAL VOICE/DATA CABLING OR FIBER WITH PLASTIC BUSHINGS ON BOTH
ENDS TO PROTECT CABLES,CABLE TRAY AND SPEED SLEEVE FILL SHALL NOT
EXCEED 40%. FIRE CAULK PENETRATION PER SPECIFICATIONS.
17. INDOOR UNIT IS POWERED BY THE OUTDOOR UNIT.
18. PROVIDE TRI-TECH (PIR, MICROWAVE, DOPLER) MOTION SENSOR.
19. 2#10, #10 GND - 3/4"C. 30A DISCONNECT.
20. NOT USED.
21. VERTICAL ROUTE FOR TELECOM RISER. SEAL ALL FLOOR PENETRATIONS TO
MAINTAIN FIRE RATING.
22. PROVIDE A 30 DAY LOAD MEASUREMENT OF PANELBOARD INDICATED. PROVIDE
THE REPORT TO THE COR AND AE PRIOR TO COMMENCEMENT OF PANELBOARD
RENOVATION.
23. PROVIDE NEW CIRCUIT BREAKERS AND FEEDERS SERVICING NEW TELECOM
EQUIPMENT. REFER TO SHEETS E-601 & E-701 FOR SIZING.
24. EXISTING ATS TO REMAIN. PROTECT IN PLACE.
25. EXISTING EQUIPMENT TO REMAIN. PROTECT IN PLACE.
26. EXISTING PANELBOARD TO REMAIN. PROTECT IN PLACE.
27. PROVIDE NEW 16" x 4" BONDING BAR, SET OF INSULATORS STAND-OFF
BRACKETS, AND STAINLESS STEEL SCREWS. PROVIDE ALL GROUNDING CABLE
AND CONNECTORS AND INSTALL PER TYPICAL DETAIL ON T-500 SERIES SHEETS.
28. EXISTING ACCESS CONTROL PANEL TO REMAIN. PROTECT IN PLACE.
29. EXISTING DOOR SECURITY TO REMAIN. PROTECT IN PLACE.
30. REMOVE EXISTING LIGHTING FIXTURE.
31. REMOVE EXISTING LIGHTING SWITCH.
32. REMOVE EXISTING RECEPTACLE.
33. EXISTING DISCONNECT TO REMAIN. PROTECT IN PLACE.
SCALE: 1/2" = 1'-0"
F8
ELECTRICAL ENLARGED PLAN -
BASEMENT LEVEL - RM B24A - NEW
SCALE: 1/2" = 1'-0"
F3
ELECTRICAL ENLARGED PLAN - FIRST
LEVEL - RM 125 - NEW
SCALE: 1/2" = 1'-0"
F1
ELECTRICAL ENLARGED PLAN -
SECOND LEVEL - RM 225 - NEW
SCALE: 1/2" = 1'-0"
C3
ELECTRICAL ENLARGED PLAN - FIRST
LEVEL - RM 125 - DEMO
SCALE: 1/2" = 1'-0"
C1
ELECTRICAL ENLARGED PLAN -
SECOND LEVEL - RM 225 - DEMO
REFER TO COVER SHEET FOR KNOWN ACM ITEMS
WITHIN THIS BUILDING.
Revisions: Date:
Addendum 1 02/25/2026
UP
UP
UP UP
UP
WAP
WAP
WAP
WAP
CTRK CTRK
WAP
WAP
WAP
CTRK
WAP
CTRK
CTRK
CTRK
CTRK
WAP
WAP
WAP
CTRK
CTRK
WAP
WAP
WAP
CTRK
CTRK
CTRK
WAP
WAP
WAP
CTRK
CTRK
CTRK
WAP
WAP
CTRK
CTRK
CTRK
CTRKWAP
WAP
WAP
WAP
CTRK
WAP
WAP
WAP
WAP
WAP
WAP
WAP
WAP
WAP
WAP
WALL SYMBOL LEGEND
EXISTING CONSTRUCTION TO REMAIN
SMOKE AND 1-HR RATED FIRE
BARRIER AND OPENINGS
SMOKE AND 2-HR RATED FIRE BARRIER
AND OPENINGS
SMOKE BARRIER AND OPENINGS
1 HR RATED FIRE BARRIER AND
OPENINGS
2 HR RATED FIRE BARRIER AND OPENINGS
CONTRACTOR SHALL CONFIRM ALL FIRE RATED WALL ASSEMBLIES
STORAGE
ROOM
B19
STORAGE
ROOM
B18
OFFICE
RECREATION
B20
LAUNDRY
B21
OFFICE
DOCTOR
B17
GRECC
FAMILY
ROOM
B16
SERVICE
ROOM
B16A
MEN'S
ROOM
B15
OFFICE
THERAPY
ASSISTANTS
B14
OFFICE
B12
OFFICE
OCCUPATIONAL
THERAPIST
B11
ELEC
CLOS
B13A
STAIR 6
B53
DAY ROOM
T.A.C.
B10
KITCHEN
B09
OFFICE
B07
UNISEX
RESTROOM
B05
WOMENS
ROOM
B04
POD ROOM
B03B
STORAGE
ROOM
B03
STORAGE
B02
ELECTRIC
ROOM
B02A
ELEV.
B03A
CLOSET
B03A
ROOM
B01
ROOM
B33D
MECHANICAL
ROOM
B23
MECHANICAL
ROOM
B23A
STAIR 5
B22
STAIR 4
B52
TELECOM
RM
B24A
121 SF
ELECTRONIC
EQUIPMENT
B24
STORAGE
ROOM
B25A
OFFICE
B25
CLOS
B26
BREAK
ROOM
B33B
STAIR 2
B27
STOR.
ROOM
B29A
TLT
B28
ELECTRONIC
TECHNICIANS
B29
STAIR 1
B51
STORAGE
ROOM
B33A
STAIR 3
B50
STORAGE
ROOM
B33
ELECTRONIC
SHOP
BREAK
ROOM
B30
STORAGE
ROOM
B30A
OFFICE HR
B31A
ELECTRONIC
RADIO
ROOM
B31
OFFICE
PROGRAM
SPECIALIST
B32
CORRIDOR
B13
LOBBY
B41
CORRIDOR
B40
LOBBY
B42
62T-401
F1
B13-AP-A
B13-AP-B
B13-AP-C
B17-C
NO DATA
B19-A
B20-AP-A
B13-CK-B B19-CK-A
B20-A
B17-A
B17-B
B16-A
B16-AP-A
B21-A
B22-AP-A
B42-A
B42-AAP-A
B14-B
B07-B
B07-A
B07-CK-A
B07-AP-B
CORRIDOR
B43
B -A
B43-CK-C
B43-CK-B
B43-CK-A
B09-CK-A
B09-A
B53-AP-A
B12-A
B11-B
B11-A
B09-AP-B
B10-B
B -A
B10-AP-A
B03B-CK-A
B13-CK-E
B03B-A
B13-AP-F
B03-AP-A
B41-A
B01-AP-A
B33D-A
B33D-B
B40-CK-A
B33B-CK-A
B40-CK-B
B33B-AP-A
B33B-A
ROOM
B24B
B24A-AP-A
B25-A
B25-AP-A
B -A
B33-CK-A
B33-CK-B
B -A
B33-CK-C
B33-B
B33-AP-C
B33-AP-B
B33-CK-E
B33-CK-F
B33-CK-G
EXT-A
EXT-B
B33A-A
B32-B
B32-A
B32-CK-A
B31-A
B27-AP-A
B31A-A
B29-C
B29-B
B29-A
B29-AP-A
B30-A
B30-B
B30-AP-A
B51-AP-A
NO DATA
NO DATA
NO DATA
NO DATA
NO DATA NO DATA
NO DATA
NO DATA
NO DATA
NO DATA
NO DATA
NO DATA
B13-CK-D
NO DATA
NO
DATA
TYP.
TYP.
TYP.
TYP.
TYP.
B A
-A
B24A-B
B A
-D
B24A-C
B24A-CAM-01
FIBER PATH A
FIBER PATH B
B11-AP-A
B14-AP-A
B03B-AP-A
B19-AP-A
B21-AP-A
B24-AP-A
B33-AP-A
B33-AP-D
B32-AP-A
B31A-AP-A
TYP.
TYP.
62T-401
C1
TO BUILDING 61
NO DATA
NO DATA
262' - 0"
TELECOM
RM
B24A
121 SF
FIBER PATH A
FIBER PATH B
CABLE LEGEND
(10) NEW CAT 6A
TNPN
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
CONSULTANT
321 4 5 6 7 8 9 10
GENERAL NOTES
KEYNOTES
TRIPLE C - The A/E Group
100 Pearl Street, 14th Floor
Hartford, CT 06103
MAT PERKINS
860-270-0753
STAMP
mat.perkins@triplecaeg.com
A u to d e s k D o c s /3
C
R
.P ro je c t.
-2
-7
.E H
R M
.I U
.B e d fo rd .M
A .R
/5
-2
-7
.B e d fo rd
.E H
R M
.M E
P .B
R
.r v t
/2
/2
:1
:2
P
M
62T-100
TELECOMMUNICATION PLAN - BASEMENT LEVEL 518-22-700
06/04/2025 M. Perkins K.Mcdermott
ISSUED FOR
CONSTRUCTION
EHRM INFRASTRUCTURE
UPGRADES
200 Springs Rd, Bedford, MA 01730
SCALE: 1/8" = 1'-0"
F2
TELECOMMUNICATION PLAN -
BASEMENT LEVEL
97 DATA PORTS THIS AREA
15,764 GSF
SCALE: 1" = 100'-0"
F1
DIAMOND ANALYSIS - BASEMENT
LEVEL
A. PROPERLY FIRE STOP AND SEAL ALL PENETRATIONS THROUGH WALLS,
FLOORS, CEILINGS, AND ROOF AS PER OWNER, CODE, AND AHJ.
B. PRIOR TO INSTALLATION OF CABLE TRAY COORDINATE LOCATIONS WITH ALL
OTHER TRADES AND PROVIDE COORDINATION DRAWINGS FOR REVIEW. ALL
NEW CABLE, CABLE TRAY, J HOOKS SHALL BE INDEPENDENTLY SUPPORTED &
NOT CAUSE ADDITIONAL LOAD ON OTHER SYSTEMS.
C. NOT ALL PARTS AND PIECES ARE SHOWN FOR A COMPLETE SYSTEM.
CONTRACTOR IS RESPONSIBLE FOR PROVIDING A COMPLETE END-TO-END
WARRANTEED SOLUTION FOR THE CABLING.
D. ALL CABLING TO BE PLENUM RATED THROUGHOUT THE BUILDING.
E. ALL COMMUNICATIONS AND WIRELESS ACCESS POINT CABLING TO MEET OR
EXCEED CATEGORY 6A STANDARDS.
F. SEE E-501 FOR DEVICE STANDARD MOUNTING HEIGHTS.
G. ALL CONDUITS FOR TELECOMMUNICATIONS OUTLETS SHALL BE STEEL THIN
WALL ELECTRICAL METALLIC TUBING (TYPE EMT) UNLESS OTHERWISE NOTED.
UNDER NO CIRCUMSTANCES SHALL FLEXIBLE CONDUIT BE USED FOR
PATHWAYS INDICATED ON THIS DRAWING. ALL CONDUITS ARE TO BE, AT A
MINIMUM, 1-1/4" TRADE SIZE, UNLESS OTHERWISE NOTED. ALL CONDUITS FOR
TELECOMMUNICATIONS OUTLETS ARE TO BE STUBBED TO NEAREST CABLE
TRAY. CONTRACTOR IS TO ENSURE THAT NO CONDUIT EXCEEDS 40% FILL. IF
EXISTING CONDUIT IS NOT LARGE ENOUGH TO SUPPORT NEW CAT 6A CABLE
TO REPLACE ALL EXISTING CIRCUITS ONE-FOR-ONE, CONTRACTOR SHALL
PROVIDE THE MAXIMUM ALLOWABLE NEW CAT 6A CIRCUITS TO REPLACE
EXISTING. THE ADDITIONAL NEW CIRCUITS TO COMPLETE THE ONE-FOR-ONE
REPLACEMENT SHALL BE PROVIDED AT THE NEAREST AVAILABLE DROP WITH
EXISTING CONDUIT CAPACITY.
H. ALL CONDUIT PATHWAYS SHALL BE PROVIDED WITH NYLON BUSHINGS TO
PROTECT CABLES, REGARDLESS OF WHETHER THEY TERMINATE IN A DEVICE
OR JUNCTION BOX.
I. TERMINATE, TEST, LABEL AND DOCUMENT ALL TELECOMMUNICATION CABLES.
J. CONTRACTOR SHALL AVOID ALL SYSTEMS SHUTDOWNS, INSTALL NEW
EQUIPMENT PRIOR TO THE RENOVATION OF EXISTING EQUIPMENT; PROVIDE
TEMPORARY UTILITIES AS REQUIRED TO MEET THIS REQUIREMENT.
K. THE DEMOLITION OF DEVICES SHALL INCLUDE ALL ASSOCIATED CABLING
BACK TO THE RACK.
L. LABEL DEVICE PLATES WITH A PERMANENT ADHESIVE LABEL FOLLOWING ALL
STANDARDS AND REQUIREMENTS, SEE DETAIL SHEETS FOR ADDITIONAL
INFORMATION
M. CONTRACTOR SHALL PROVIDE TWO SETS OF LAMINATED FINAL
TELECOMMUNICATION ONE-LINE, RACK ELEVATION, AND CABLE SCHEDULE
DOCUMENTS. HANG ON THE WALL WITHIN THE TELECOM ROOM.
N. REFER TO R-900 SERIES SHEETS FOR PHOTO DOCUMENTATION OF EXISTING
CONDITIONS.
O. FOR EXISTING SECURITY CAMERAS BEING RE-CABLED, MAINTAIN EXISTING
CAMERA ANGLE AND PROTECT IN PLACE.
P. ALL EXISTING PENETRATIONS NO LONGER BEING USED WILL BE FILLED WITH
RATED ASSEMBLY.
Q. ABOVE CEILING SURVEY TO OCCUR FOR CABLE TRAY INSTALLATION. EXISTING
EQUIPMENT AND/ OR SYSTEMS TO BE SELECTED AS REQUIRED. ALL ACTIVE
SYSTEMS TO REMAIN OPERATIONAL.
1. PROVIDE NEW TELECOMMUNICATIONS OUTLET IN EXISTING LOCATION WITH
EXISTING EMT STUB UP TO NEAREST ACCESSIBLE CEILING SPACE. SEE DETAILS
ON SHEET T-501 FOR ADDITIONAL INFORMATION.
2. ALL EXISTING WAP'S TO REMAIN/PROTECT IN PLACE, AND NO NEW CABLING
REQUIRED FOR EXISTING WAP'S (WIRELESS ACCESS POINTS).
3. PROVIDE NEW 4-POST CHANNEL, PDU, UPS AND WIRE MANAGEMENT
COMPONENTS AS SHOWN ON T-500 SERIES AND T-600 SERIES SHEETS AND IN
THE SPECIFICATIONS.
4. PROVIDE NEW VERTICAL WIRE MANAGEMENT SYSTEM, SEE SPECIFICATIONS FOR
ADDITIONAL INFORMATION.
5. EXISTING CABLING CONDUIT AND WIREWAYS ARE TO REMAIN AND BE CAREFULLY
PROTECTED IN PLACE. ALL EXISTING DEVICES ON THE EXISTING RACK SHALL BE
TRANSFERRED TO THE NEW RACK. CONTRACTOR SHALL PROVIDE SHOP
DRAWINGS SHOWING THE PROPOSED NEW RACK ELEVATION AND PROVIDE A
PHASING PLAN FOR TRANSFERRING ALL EXISTING DEVICES TO REMAIN TO THE
NEW RACKS.
6. PROVIDE NEW CABLE TRAY PER REQUIREMENTS LISTED IN CABLE TRAY
SCHEDULE. COORDINATE WITH EXISTING CONDITIONS AND SUBMIT
COORDINATION DRAWINGS FOR REVIEW PRIOR TO COMMENCING WORK. SEE
T-500 SERIES SHEETS FOR ADDITIONAL REQUIREMENTS. COORDINATE LIGHT
FIXTURES WITH OVERHEAD CABLE TRAY AND SPEED SLEEVE FILL SHALL NOT
EXCEED 40%.
7. PROVIDE NEW IP ADDRESSABLE NETWORK CAMERA, POE+, PTZ, MOTION
SENSOR, AUTO-TRACKING, DOME WITH WALL MOUNT. MOUNT AT 8’ – 6” A.F.F. TO
TOP OF WALL BRACKET. INTEGRATE CAMERA INTO EXISTING VMS.
8. PROVIDE NEW DATA OUTLET, STUB-UP, AND BACK-BOX IN NEW LOCATION IN TR.
9. NEW 4” SPEED CONDUIT SLEEVE THROUGH WALL ABOVE CEILING GRID FOR
HORIZONTAL VOICE/DATA CABLING OR FIBER WITH PLASTIC BUSHINGS ON BOTH
ENDS TO PROTECT CABLES,CABLE TRAY AND SPEED SLEEVE FILL SHALL NOT
EXCEED 40%. FIRE CAULK PENETRATION PER SPECIFICATIONS.
10. EXISTING CONDUIT THROUGH WALL OR FLOOR WITH OPTICAL CABLE TO BE
PROTECTED IN PLACE UNTIL NEW SPEED CONDUIT SLEEVE AND FIBER IS
INSTALLED. DEMOLISH EXISTING CONDUIT ONCE NEW SPEED CONDUIT SLEEVE
AND FIBER ARE OPERATIONAL. CONTRACTOR SHALL PROVIDE A PHASING PLAN
FOR TRANSFERRING FIBER.
11. EXISTING EQUIPMENT TO REMAIN, PROTECT-IN-PLACE.
12. DEMOLISH EXISTING FIBER ONCE NEW FIBER IS OPERATIONAL. CONTRACTOR
SHALL PROVIDE A PHASING PLAN FOR TRANSFERRING FIBER.
13. ALL EXISTING ANALOG PHONE CABLE DEVICES AND TERMINATIONS ETC. SHALL
REMAIN OPERATIONAL AT ALL TIMES AND SHALL BE RETAINED AND REUSED.
PROTECT IN PLACE.
14. VERTICAL ROUTE WITH REDUNDANT SPARE CONDUIT FOR TELECOM RISER. SEAL
ALL FLOOR PENETRATIONS TO MAINTAIN FIRE RATING.
15. HORIZONTAL CABLE LENGTH LIMITATIONS PER STANDARD 3.1.
16. EXISTING PACS AND EQUIPMENT RACKS.
17. NEW INDOOR UNIT.
18. CONTRACTOR SHALL FIELD VERIFY EXISTING TELECOMMUNICATIONS…