This is a set of structural construction drawing sheets for the EHRM Infrastructure Upgrades project at Edith Nourse Memorial Veterans Hospital, 200 Springs Road, Bedford, MA 01730. The project number is 518-22-700, prepared by TRIPLE C - The A/E Group (Hartford, CT), issued for construction on 06/04/2025 with Addendum 1 dated 02/25/2026.
The drawing set comprises structural details, foundation plans, masonry schedules, steel framing details, and interior finish specifications for a fully sprinklered facility. Key structural elements include: reinforced concrete masonry (12" CMU) walls with vertical reinforcement (1-#7 at 8" OC for MW1 walls and 1-#5 at 48" OC for MW2 walls), cast-in-place concrete footings at -4'-0" elevation with 4,000 psi compressive strength, steel roof deck systems, prefabricated cold-formed steel (CFS) roof trusses designed for blast loads of 18 KSF balanced snow and 21.6-36.2 PSF wind uplift, and steel beam-to-masonry connections. Interior finishes specified include luxury vinyl tile (Armstrong), porcelain tile (Dal Tile), sealed concrete flooring, acoustical ceiling tile (Armstrong Ultima Health Zone), gypsum wallboard with paint finishes, resilient base, and corner guards. Design loads include 86 PSF ground snow load with 59.8 PSF flat-roof snow load, 127 mph ultimate wind speed (Exposure C), and seismic design Category C per ASCE 7-22. Special inspections are required per IBC for steel construction, concrete work, masonry, and soils verification. Delegated design submittals required include cold-formed steel framing, roof trusses, and cribbing designs.
View the file
Other files
Show 40 more
Latest 50 of 105 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
STRUCTURAL ABBREVIATIONS:
A
ADDL ADDITIONAL
ADJ ADJACENT
ALT ALTERNATE
ALUM ALUMINUM
AR ANCHOR ROD
ARCH ARCHITECT
O
OC ON CENTER
OD OUTSIDE DIAMETER
OSF OUTSIDE FACE
OPNG OPENING
OPP OPPOSITE
O/O OUT TO OUT
U
UNO UNLESS NOTED OTHERWISE
URM UNREINFORCED MASONRY
E
EA EACH
EF EACH FACE
EL ELEVATION
ELEC ELECTRICAL
ELEV ELEVATOR
EJ EXPANSION JOINT
EMBED EMBEDMENT
EQ EQUAL
EQUIP EQUIPMENT
ES EACH SIDE
EW EACH WAY
E-W EAST - WEST DIRECTION
(E) EXISTING
EXP EXPANSION
S
SB SOIL BORING
SC SLIP CRITICAL
SCHED SCHEDULE
SER STRUCTURAL ENGINEER OF RECORD
SF SQUARE FOOT
SIM SIMILAR
SL SNOW LOAD
SOG SLAB ON GRADE
SPA SPACES
SPEC SPECIFICATION
SPF SPRUCE PINE FIR
SS STAINLESS STEEL
SSLT SHORT-SLOT LOAD TRANSVERSE
STD STANDARD
STIFF STIFFENER
STL STEEL
STRUCT STRUCTURE / STRUCTURAL
SYM SYMMETRICAL
SYP SOUTHERN YELLOW PINE
Q
QTY QUANTITY
F
FDN FOUNDATION
FD FLOOR DRAIN
FFE FINISHED FLOOR ELEVATION
FLR FLOOR
FS FOOTING STEP
FT FEET
FTG FOOTING
FV FIELD VERIFY
N
NIC NOT IN CONTRACT
N-S NORTH - SOUTH DIRECTION
NLT NAIL LAMINATED TIMBER
NTS NOT TO SCALE
NWT NORMAL WEIGHT
G
GA GAGE/GAUGE
GALV GALVANIZED
GB GRADE BEAM
GC GENERAL CONTRACTOR
GLB GLUE LAMINATED BEAM
GLC GLUE LAMINATED COLUMN
GLT GLUE LAMINATED TIMBER
GR GRADE
GSN GENERAL STRUCTURAL NOTES
GWB GYPSUM WALL BOARD
L
LB(S) POUND(S)
LL LIVE LOAD
LLH LONG LEG HORIZONTAL
LLV LONG LEG VERTICAL
LONG LONGITUDINAL
LSL LAMINATED STRAND LUMBER
LSH LONG SIDE HORIZONTAL
LSV LONG SIDE VERTICAL
LWT LIGHT WEIGHT
LVL LAMINATED VENEER LUMBER
M
MAX MAXIMUM
MCJ MASONRY CONTROL JOINT
MECH MECHANICAL
MEP MECHANICAL, ELECTRICAL & PLUMBING
MEZZ MEZZANINE
MFR MANUFACTURER
MIN MINIMUM
MISC MISCELLANEOUS
MSR MACHINE STRESS RATED
MTL METAL
H
HK HOOK
HORIZ HORIZONTAL
HSA HEADED STUD ANCHOR
HSS HOLLOW STRUCTURAL SHAPE
HT HEIGHT
B
BDE BOTTOM OF DECK ELEVATION
BFE BOTTOM OF FOOTING ELEVATION
BM BEAM
BOL BOTTOM OF LINTEL
BOT BOTTOM
BP BEARING PLATE / BASE PLATE
BR BOTTOM REINFORCING
BTWN BETWEEN
C
CA COLUMN ABOVE
CANTL CANTILEVER
CB COLUMN BELOW
CFS COLD-FORMED STEEL
CGS CENTER OF GRAVITY STRAND
CIP CAST IN PLACE
CJ CONTROL JOINT
CJP COMPLETE JOINT PENETRATION
CL CENTER LINE
CLR CLEAR
CLT CROSS LAMINATED TIMBER
CMU CONCRETE MASONRY UNIT
COL COLUMN
CONC CONCRETE
CONN(S) CONNECTION(S)
CONST CONSTRUCTION
CONT CONTINUOUS
COSP CODE OF STANDARD PRACTICE
D d NAIL DIAMETER db BAR DIAMETER
DBA DEFORMED BAR ANCHOR
DBL DOUBLE
DEG DEGREE
DEMO DEMOLITION
DF DOUGLAS FIR-LARCH
DIA DIAMETER
DIAG DIAGONAL
DIM DIMENSION
DL DEAD LOAD
DLT DOWEL LAMINATED TIMBER
I
ID INSIDE DIAMETER
INCL INCLUDE
ISF INSIDE FACE
J
JT JOINT
JBE JOIST BEARING ELEVATION
K
K KIPS
KLF KIPS PER LINEAL FOOT
KSF KIPS PER SQUARE FOOT
KSI KIPS PER SQUARE INCH
KO KNOCK OUT
R
R RADIUS
RD ROOF DRAIN
REF REFERENCE
REINF REINFORCEMENT/REINFORCING
REQD REQUIRED
REV REVISION
RO ROUGH OPENING
RSS RUGGED STRUCTURAL SCREW
RTU ROOF TOP UNIT
P
PAF POWER ACTUATED FASTENER
PC PRECAST CONCRETE
PL PLATE
PLF POUNDS PER LINEAL FOOT
PLYWD PLYWOOD
PRE FAB PREFABRICATED
PROJ PROJECTION
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
PSL PARALLEL STRAND LUMBER
PT POST TENSIONED
V
VERT VERTICAL
W
W/ WITH
W/O WITHOUT
WD WOOD
WF WIDE FLANGE
WL WIND LOAD
WP WORK POINT
WT WEIGHT
WWR WELDED WIRE REINFORCING
T
T/G TONGUE AND GROOVED
TBE TOP OF BEAM ELEVATION
TDE TOP OF DECK ELEVATION
TEMP TEMPORARY
TFE TOP OF FOOTING ELEVATION
TGBE TOP OF GRADE BEAM ELEVATION
TPCE TOP OF PILE CAP ELEVATION
TPCPE TOP OF PRECAST PLANK ELEVATION
TPE TOP OF PIER ELEVATION
TR TOP REINFORCING
TRANS TRANSVERSE
TSE TOP OF SHEATHING ELEVATION
TSE TOP OF SLAB ELEVATION
TSE TOP OF SUBFLOOR ELEVATION
TWE TOP OF WALL ELEVATION
TYP TYPICAL
GENERAL SYMBOLS:
B1001 CONCRETE BEAM MARK NUMBER
B1001-PT POST TENSIONED CONCRETE BEAM MARK NUMBER
BP1 BEARING / BASE PLATE MARK NUMBER
BRF1 BRACE FRAME MARK NUMBER
BR1 MILD STEEL BOTTOM REINFORCING MARK NUMBER
C1 COLUMN MARK NUMBER
CC1 CONCRETE COLUMN MARK NUMBER
CW1 CONCRETE WALL NUMBER
D1 STEEL DECK MARK NUMBER
DC1 DROP CAPITAL MARK NUMBER
DP1 DRILLED PIER MARK NUMBER
DPC1 DRILLED PIER CAP NUMBER
EP1 EMBEDDED PLATE MARK NUMBER
F1 SPREAD FOOTING MARK NUMBER
GB1 GRADE BEAM MARK NUMBER
H1 HEADER MARK NUMBER
HCP HOLLOW CORE PLANK
HD1 HOLD DOWN MARK NUMBER
J10 JOIST MARK NUMBER
L1 LINTEL MARK NUMBER
MC1 MASONRY COLUMN MARK NUMBER
MF1 MOMENT FRAME MARK NUMBER
MW1 MASONRY WALL NUMBER
P1 PIER MARK NUMBER
PC1 PILE CAP MARK NUMBER
RD1 ROOF DECK MARK NUMBER
S1 SLAB MARK NUMBER
SC1 STEEL COLUMN MARK NUMBER
SR1 STUD RAIL REINFORCING MARK NUMBER
SW1 SHEAR WALL MARK NUMBER
T1 TRUSS MARK NUMBER
TR1 MILD STEEL TOP REINFORCING MARK NUMBER
W1 WALL MARK NUMBER
WC1 WOOD COLUMN MARK NUMBER
WF1 WALL FOOTING MARK NUMBER
WO1 WEB OPENING
MARKS AND SYMBOLS LEGEND:
KEYNOTE MARK NUMBER
FS
W1
FOOTING STEP LOCATION
APPROXIMATE LOCATION OF DRAIN TILE
CONTINUOUS EXTENT OF ELEMENT
SLAB STEP LOCATION WITH ELEVATIONS
MATCH LINE
EXISTING BUILDING GRID LINE
SHADED AREA INDICATES PROJECTION OF
EXISTING CONSTRUCTION
ELEVATION MARKER
NEW BUILDING GRID LINE
LINE OF DEMOLITION
APPROXIMATE LOCATION OF UTILITY PIPE
PENETRATION THROUGH FOUNDATION WALL
MARKS:
WALL MARK NUMBER OR WALL TYPE
APPROXIMATE LOCATION OF SOIL BORING
TENSION / COMPRESSION PILE
TEST PILE
COMPRESSION PILE
PLAN SYMBOLS LEGEND:
F1 (xx'-xx")
P1
C1
COLUMN MARK
PIER MARK
FOOTING MARK
TOP OF FOOTING
ELEVATION
W F
FOUNDATION SYSTEM:
EXTENT OF ELEMENT
SLAB STEP LOCATION
CHANGE IN SLAB SLOPE
CHANGE IN SLAB THICKNESS
SPAN DIRECTION OF ELEMENT
SPREAD FOOTING WALL FOOTING
(x x'
-x x"
TOP OF FOOTING
ELEVATION
STEEL FRAMING SYSTEM:
Vxx = V SHEAR REACTION (KIPS) Axx = AXIAL REACTION / THROUGH FORCE (KIPS) Mxx = MOMENT REACTION (KIP/FT) Txx = TORSIONAL REACTION (KIP/FT) Vhxx = HORIZONTAL SHEAR REACTIONS (KIPS)
V41 [12]
UPWARD CAMBER REQUIRED AT MID SPAN
OF STEEL BEAM IN INCHES
NUMBER OF HEADED STUDS
MOMENT FRAME CONNECTION
STEEL BEAM
(E)
EXISTING FRAMING MEMBER
W__ x __ C=3/4
(xx'-x")
WO1WEB OPENING
ELEVATION OF MEMBER
CANTILEVER BEAM
SIZE - SAME AS
BACKSPAN, UNO
SHADED AREA INDICATES CUT THROUGH
EXISTING CONSTRUCTION
SB1
Sxxx
Sxxx
DETAIL CALLOUT
ELEVATION CALLOUT
TYPICAL STEEL CONNECTION SYMBOLS:
CA or CB
CB TYP BEAM BEARING ON COLUMN
CA TYP TRANSFER BEAM COLUMN ABOVE
CA or CB
CB TYP BEAM BEARING ON COLUMN
CA TYP TRANSFER BEAM COLUMN ABOVE
CA or CB
CB TYP BEAM BEARING ON COLUMN
CA TYP TRANSFER BEAM COLUMN ABOVE
TYP CANTILEVERED BEAM MOMENT CONNECTION
(S,D) STIFFENER AND/OR DOUBLER WHERE INDICATED
TYP CANTILEVERED BEAM MOMENT CONNECTION
TYP CANTILEVERED BEAM MOMENT CONNECTION
(S,D)
(S,D)
TYP STUB CANTILEVERED CONNECTION
(S,D) STIFFENER AND/OR DOUBLER WHERE INDICATED
TYP CANTILEVERED BEAM MOMENT CONNECTION.
TYP MOMENT FRAME CONNECTION
(S,D) STIFFENER AND/OR DOUBLER WHERE INDICATED
TYP MOMENT FRAME CONNECTION
TYP MOMENT FRAME CONNECTION
(S,D)
TYP BEAM SHEAR SPLICE CONNECTION
TYP DRAG STRUT OR COLLECTOR BEAM. DESIGN
CONNECTION FOR AXIAL LOAD INDICATED ON PLAN IN
ADDITION TO REQUIRED SHEAR LOAD. SEE TYPICAL
SHEAR & AXIAL CONNECTION DETAILS
TYP BRACING BEAM OR ROLL BEAM
CONNECTION DESIGN FORCE
CONNECTION DESIGN FORCE (REVERSIBLE)
CONNECTION DESIGN MOMENT
CONNECTION DESIGN MOMENT (REVERSIBLE)
SHEET LIST
SHEET # SHEET NAME
MCRS-001 LEGEND SHEET
MCRS-002 GENERAL STRUCTURAL NOTES
MCRS-201 FOUNDATION PLAN
MCRS-202 ROOF FRAMING PLAN
MCRS-401 FOUNDATION SCHEDULES AND TYPICAL DETAILS
MCRS-402 MASONRY SCHEDULES AND TYPICAL DETAILS
MCRS-403 STEEL SCHEDULES AND TYPICAL DETAILS
MCRS-501 FOUNDATION DETAILS
MCRS-701 FRAMING DETAILS
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
TRIPLE C - The A/E Group
100 Pearl Street, 14th Floor
Hartford, CT 06103
MAT PERKINS
860-270-0753
MBJ PROJECT # 24.513
A u to d e s k D o c s /3
C
R
.P ro je c t.
-2
-7
.E
H R
M .I U
.B e d fo rd .M
A .R
/5
-2
-7
.B e d fo rd .E
H R
M .M
C R
.M B
J S
T R
U C
R
.r v t
/2
/2
:4
:2
A
M
MCRS-001
LEGEND SHEET 518-22-700
MCR
06/04/2025 CRO JJH
ISSUED FOR CONSTRUCTION EHRM INFRASTRUCTURE
UPGRADES
200 Springs Rd, Bedford MA 01730
BUILDING PERSPECTIVE - FOR REFERENCE ONLY
# Revisions: Date:
1 Addendum 1 02/25/2026
TYPICAL NOTES:
These notes specify the requirements for the design represented in these documents. The construction and materials shall comply with all the pertinent codes and references, plans, and details, including (but not limited to) those shown in architectural, civil, mechanical and electrical drawings.
The Contractor shall verify all dimensions and existing conditions in the field that affect construction prior to commencing work on the affected element or shop drawing submittals. Resolve any discrepancies with the Architect prior to construction.
The contract structural drawings and specifications represent the completed structure. The Contractor is responsible for bracing and shoring (without overstressing) all structural elements as necessary at any stage of construction until completion of the project. The Structural Engineer of Record is not responsible for the Contractor’s means, methods, sequences or procedures of construction. Contractor shall recognize and consider effects of thermal movements of structural elements during construction period.
The Contractor is solely responsible for site safety including all temporary precautionary measures and safety programs. Site observation visits by the Structural Engineer of Record do not include review of the contractor’s safety precautions.
Refer to architectural, mechanical and electrical drawings for locations, elevations, dimensions, and details of sleeves, inserts, openings, recesses, curbs, housekeeping pads, etc. that are not shown on the structural drawings and do not damage structural members.
Information shown in the structural drawings regarding existing conditions represents the current and general field conditions related to the new work, to the best of our knowledge. Report all discrepancies (unforeseen conditions) to the Architect for resolution prior to performing related new work.
Requests for information shall be submitted in writing and shall reference the part of the construction documents that is in question.
SPECIAL INSPECTIONS:
Special inspections required by the building code and these documents shall be provided in addition to inspections to be performed by the city in which the project is located.
Contractor shall read and understand their duties in the specification and under the building code for special inspections and coordinate as necessary the Owner's responsibilities.
The Special Inspectors shall be provided by the Owner and shall use current structural drawings incorporating all revisions and approved shop drawings.
Special inspection reports are to be submitted promptly and within 24 hours to the Structural Engineer of Record and Contractor from the time when inspections are performed.
The General Contractor shall provide timely notice (minimum 24 hours) to the Special Inspector and sufficient time for the Inspector to perform their inspection.
For a schedule of Special Structural Inspections required by the building code for this project, see the Special Inspection Schedule.
DELEGATED DESIGN AND DEFERRED SUBMITTALS:
The following items are a delegated design and shall be issued as deferred submittals per IBC. The delegated design submittal shall include shop drawings and an engineering analysis signed and sealed by the licensed design professional responsible for their preparation:
Cold-Formed Steel Framing Cold-Formed Steel Roof Trusses Cribbing for Underpinning (as needed for the Project)
The contractor shall retain a professional engineer licensed in the state where this project is located to design and detail delegated design items to meet the performance and design criteria indicated in the contract documents.
All items issued as deferred submittals shall be issued a minimum of 30 days prior to installation and shall not be installed until their design and submittal documents have been reviewed for general conformance to the drawings by the General Contractor, the Structural Engineer of Record and the Building Official. A copy of the deferred submittal shall be forwarded to the Building Official after the Structural Engineer of Record has reviewed the documents and prior to the erection of the deferred submittal items.
DESIGN CODES AND STANDARDS:
2024 International Building Code, as amended and adopted by the U.S. Department of Veterans Affairs Structural Design Manual, PG-18-10.
U.S. Department of Veterans Affairs Seismic Design Requirements, H-18-8.
Physical Security and Resiliency Design Manual (PSRDM).
MATERIAL PROPERTIES:
Reinforcing Steel (Fy):
Typical 60,000 psi ASTM A615 Grade 60 Weldable 60,000 psi ASTM A706 Grade 60
Cast-in-Place Concrete (f'c) at 28 days, u.n.o.:
Controlled Low 1,200 psi Maximum Strength Material (CLSM) 50 psi Minimum Footings 4,000 psi Concrete for Underpinning 3,000 psi Piers and Walls (non-shear) 4,000 psi Slabs on Grade 4,000 psi Exterior Concrete 4,500 psi w/ air entrainment All Concrete not otherwise noted 4,000 psi
Concrete Masonry- Unit Strength (f'm):
F’m 2,000 psi Typical Units: 2,800 psi per ASTM C90 Masonry Grout 2,000 psi Masonry Mortar ASTM C270, Type S
Structural Steel (Fy):
Wide Flanges: 50,000 psi ASTM A992 Angles, Channels, Plates, and Bars 36,000 psi ASTM A36 Rectangular HSS 46,000 psi ASTM A500, Grade B Round HSS 42,000 psi ASTM A500, Grade B Steel Pipe 35,000 psi ASTM A53, Grade B
Structural Fasteners:
Typical High-Strength Bolts 120,000 psi ASTM F3125 Grade A325 Twist-off Tension Control Bolts 120,000 psi ASTM F3125 Grade1852, Type 1 High-Strength Bolts where noted 150,000 psi ASTM F3125 Grade A490 Carbon Steel, Threaded Rods 36,000 psi ASTM A36 Threaded Rods Grade B7 where noted 125,000 psi ASTM A193 Stainless Steel, Threaded Rods 85,000 psi ASTM F593 Anchor Rods, Grade 36 U.N.O. 36,000 psi ASTM F1554 Anchor Rods, Grade 55 where noted 55,000 psi ASTM F1554 Anchor Rods Grade 105 where noted 105,000 psi ASTM F1554 Direct Tension Indicator Washers where noted ASTM F959
Cold-Formed Steel Framing (Fy):
Studs, Joists, Braces-16 ga. and heavier 50,000 psi ASTM A653 Studs, Joists, Braces-18 ga. and lighter 33,000 psi ASTM A653 Track, Channels and Accessories 33,000 psi ASTM A653
DESIGN LOADS:
LATERAL LOADS:
Risk Category: IV Wind Loads:
Primary Frame Wind Data:
Basic Wind Speed: V ult = 127 mph
Exposure Category: C Internal Pressure Coefficient (Gcpi): +0.18 or –0.18
Components and Cladding Wind Loads:
Exterior Component/Cladding: Supplier to develop based on code criteria and indicate on shop drawings.
Seismic Loads:
Primary Seismic Data:
Mapped Spectral Response Accelerations: Ss: 0.3 S1: 0.059
Site Class: BC
Design Spectral Acceleration Parameters: Sds: 0.18 Sd1: 0.039
Importance Factor: 1.5 Seismic Design Category: C
Basic Seismic-Force- Resisting System: Intermediate Reinforced Masonry Shear Walls
Response Modification Factor: R = 3.5 Overstrength Factor: ΩO = 2.5 Seismic Response Coefficient: Cs = 0.077
Ultimate Design Base Shear: V = 0.077(W)
Analysis Procedure: Equivalent Lateral Force Procedure
GRAVITY LOADS:
Dead Load:
Roof: 25 psf (10 psf load on bottom chord of trusses)
Snow Load:
Ground Snow Load, Pg: 86 psf Flat-Roof Snow Load, Pf: 59.8 psf Snow Exposure Factor, Ce: 1.00 Thermal Factor, Ct: 1.00 Slope Factor, Cs: 0.99 Unbalanced/Drift Snow Load: Refer to plan, U.N.O.
Tornado Load:
Tornado Speed, VT: 50 mph Design Tornado Pressure pT: Design for Tornado Loads is not required.
See ASCE 7-22 Section 32.5.2
Roof Live Load:
Live Load, (reducible): 20 psf
CONVENTIONAL FOOTINGS:
Footings are designed for a maximum allowable soil bearing pressure of 4000 pounds per square foot on undisturbed natural soil or compacted engineered fill. It shall be the Contractor’s/Owner’s responsibility to retain a Geotechnical Engineer to verify that this value may be achieved at the bottom of footing elevation with out damaging, differential settlement.
The quality of the bedrock shall be explored by the Owner's Geotechnical Engineer for the presence of soil filled seams at each column location. This shall be accomplished by drilling a 1 1/2" diameter test hole into the bedrock at each footing location prior to the placing of concrete. The depth of test hole will depend of the quality of the exposed rock,but shall not be less than 6'-0" below the bottom of the footing.
All topsoil, fill, organic, and/or other unsuitable bearing material shall be removed below the footings and/or within the building area to the depths indicated in the geotechnical engineering report and extent of removal shall be field verified by the Geotechnical Engineer.
All excavations shall be observed by a qualified Geotechnical Engineer to verify removal of all unsuitable material,and confirm the proper preparation of bearing conditions. Rock excavation for individual footings is not expected to exceed five foot depth, U.N.O. No mass excavation is anticipated. Blasting is not permitted.
For footings that do not bear on natural undisturbed soil, extend engineered fill laterally beyond bottom edge of footing per recommendations in the geotechnical report.
Foundation and retaining walls shall be back filled with free draining fill approved by the Geotechnical Engineer. Provide drainage board and perforated pipe as required by the contract documents and verify with the Architect and Civil Engineer.
Engineered fill shall not be placed on frozen material and frozen material shall not be used as engineered fill. Contractor shall provide any means necessary to prevent frost penetration under footings during construction.
Backfill equally on both sides of foundation walls to prevent overturning or lateral wall movement, or brace as necessary.
For stepping of wall footings reference drawings for detail.
FOUNDATIONS:
Refer to geotechnical report number J4245018 by Terracon, dated February 10, 2025.
The Contractor shall verify the location of all existing and new underground utilities and tanks prior to beginning excavation.
For underground utilities adjacent to foundations and through foundations reference drawings for typical detail showing step footings below utilities as required to avoid undermining of structure by utilities.
REINFORCED CONCRETE:
The detailing, fabrication and erection of all reinforcing shall be done in accordance with the latest edition of ACI-315, “Manual of Standard Practice for Detailing Reinforced Concrete Structures and ACI-318, “Building Code Requirements for Structural Concrete.”
All reinforcing bars are deformed and continuous, unless noted otherwise. Refer to drawings for reinforcing lap length schedule.
Provide suitable wire spacers, chairs, etc. for support of reinforcing steel in proper position while placing concrete. All bars shall be tied to prevent displacement while placing concrete. All chairs and slab bolsters shall be plastic or steel with plastic tips. When reinforcing steel is epoxy coated or p/t tendons are fully encapsulated, all chairs and slab bolsters shall be epoxy coated or plastic and all support bars shall be epoxy coated. Chairs are to be stable and resist tipping.
The fabricator shall submit a complete list of accessories and placing details with the shop drawings.
No horizontal construction joints shall be placed in beams, joists, or slabs, unless shown on drawings.
Locate vertical construction joints in beams and slabs at central one third of span. Refer to drawings for details. Submit proposed construction joint locations to the Structural Engineer of Record for review prior to placement of concrete. Where new concrete is placed against existing concrete, the existing concrete shall be roughened to a minimum 1/4" amplitude.
Refer to drawings for placement guidelines of embedded pipes, sleeves, and conduits. Conduits are not permitted in slabs 3 inches or less in thickness.
Conduit and piping shall be fabricated and installed so that cutting, bending, or displacement of reinforcement from its specified location is not required.
Concrete cover for pipe embedments with their fittings shall be at least 1-1/2 in. For concrete exposed to earth or weather, and at least 3/4 in. For concrete not exposed to weather, or not in contact with ground
Aluminum conduit, aluminum sleeves and aluminum embeds are not permitted in concrete.
All conduits shall be placed within the middle one-third of the slab thickness.
The maximum size of conduits shall be 1 1/4” diameter and shall be spaced no closer (to each other or reinforcing steel) than 4 inches unless prior approval is obtained from the structural engineer.
Sleeves and conduits shall pass perpendicularly through beams in the center third of the beam's depth. Embedded boxes shall not be located on the bottom face of beams and shall meet clearance requirements for beam reinforcing tendons and reinforcing steel.
Embedded boxes, sleeves and conduits shall not be placed within a distance of 2’-6” from the face of any column and shall not be placed within 1’-6” of any anchor without prior approval from the structural engineer.
In areas of high conduit concentration where it is not possible to meet the above requirements, consult the structural engineer prior to placement.
Provide a 3/4 inch chamfer for all exposed concrete corners. See architectural drawings for details and additional requirements.
Formwork and all shoring for flatwork shall be left in place until the concrete reaches at least 75 percent of the 28-day compressive strength. Design of shoring and reshoring is the responsibility of the Contractor and shall conform to ACI 347R and ACI 347.2R.
Concrete compressive strength testing used to determine flatwork stripping times shall be performed using one of the following methods:
CIPPOC and standard cylinders cured and stored in the same conditions as the flatwork.
Maturity testing properly calibrated and conducted by an approved testing agency.
Calcium chloride is not permitted as a concrete additive.
Concrete Cover on Reinforcing:
Topping Slab: 3/4" clear top Slab on Grade: upper third of slab Concrete covers are intended to meet 2 hour rating requirements of IBC Section 721.1 prescriptive fire protection.
Footings and Caissons: 3” clear bottom and sides 2” clear top Walls: #5 and smaller 1 1/2” clear earth or weather face #6 and greater 2" clear earth or weather face 3/4” interior face
SHOP DRAWINGS:
Submit shop drawing schedule with construction schedule that includes consideration for review period. See specification for additional information.
General contractor shall submit shop drawings in digital format for structural review. Digital drawings shall meet the following requirements.
1. All pages are native .pdf files, rotated, printed to scale with searchable text.
2. All transmittals shall be located as the first page of the submittal or as a separate file within one digital package.
3. Contractor digital review comments and their digital stamp shall be attached. Our review will not occur until the contractor has reviewed, coordinated with other trades and provided shop stamp.
4. MBJ will mark-up the digital set in red and return a digital file via email, ftp site or other means.
5. Under no circumstances will MBJ review shop drawings that are considered to be scanned/copied construction document submittals. The Detailer shall produce and submit original documents for review.
LOOSE ANGLE BRICK LINTELS:
Fit lintel such that vertical leg is tight to back of brick, locate brick ties to backup at first bed joint above angle’s vertical leg and provide minimum 8” support each end.
Refer to architectural drawings for locations and to structural drawings for lintel schedule.
STEEL ROOF DECK:
Manufacturer shall be a current member of the Steel Deck Institute (SDI).
Detail, manufacture and install steel roof deck and accessories in accordance with the SDI specifications and codes and OSHA requirements.
Steel roof deck shall be as noted on plan.
Welding shall be in accordance with AWS D1.3. Welders shall be qualified in accordance with AWS D1.3.
Where spray-on fireproofing of the deck is required, the Contractor shall verify that the deck finish is compatible with the proposed fireproofing material to ensure proper bonding of the fireproofing. Coordinate fireproofing locations and requirements with the architect.
All steel deck shall span a minimum of three spans, unless otherwise approved by the engineer. Deck ends are to be lapped over supports.
Contractor shall verify the location and extent of acoustical steel deck with the architectural drawings.
Reference drawings for detail on steel roof deck fastening requirements unless noted otherwise.
Provide reinforcement or frames for deck openings as indicated on the drawings.
POST-INSTALLED ANCHORS:
Post installed anchors to be installed in concrete base material shall have current ICC approval for use in both cracked and un-cracked concrete in accordance with ACI 355.2, ACI 355.4, ICC ES AC193 and ICC ES AC308.
Post-installed anchors to be installed in masonry base material shall have a current ICC approval for use in uncracked, fully grouted concrete masonry unit construction in accordance with ICC-ES AC01, ICC-ES AC58 and ICC-ES AC106. Contact Engineer of Record for anchorage to hollow masonry or unreinforced clay masonry not covered by this section.
Post-installed anchors shall only be used where specified on the construction documents. The Contractor shall obtain approval from the Engineer of Record prior to installing post-installed anchors in place of missing or misplaced cast-in-place anchors.
Submit a work plan including proposed products for approval prior to commencing corrective work.
Post-installed adhesive anchors shall not be used for fire rated components supporting gravity loads.
Verify that supporting substrate and environmental conditions are consistent with the manufacturer’s installation instructions and the ICC-ES report.
Post-installed anchors shall be installed in accordance with the manufacturer’s installation instructions and the ICC-ES report, including hole drilling and cleaning.
The general contractor shall engage a testing company to locate existing reinforcing and other embedded items by non-destructive means (GPR, pacometer or other approved means) as necessary to accurately locate existing elements prior to beginning drilling operations. Do not cut or damage existing reinforcing or other embedded items unless explicitly approved by the Engineer of Record. Notify the EOR if there is a conflict between the anchor location and an embedded item.
Pre-approved products for post-installed anchors are listed below. See specifications for additional pre-approved products and substitution request requirements.
The following wedge anchor products are pre-approved:
Base Material Product ICC-ES Report Concrete Hilti Kwik Bolt TZ2 ESR-4266 Concrete Simpson Strong Bolt ESR-3037 Concrete Dewalt Power Stud+ SD2 ESR-2502 Masonry (*) Hilti Kwik Bolt 1 IAPMO ER-677 Masonry (*) Simpson Wedge-All ESR-1396 Masonry (*) Dewalt Power Stud+ SD1 ESR-2966
The following sleeve anchor products are pre-approved:
Base Material Product ICC-ES Report Concrete Hilti HSL-3 ESR-1545 Concrete Dewalt Power Bolt + ESR-3260
The following screw anchor products are pre-approved:
Base Material Product ICC-ES Report Concrete Hilti HUS-EZ ESR-3027 Concrete Simpson DEWAL HD ESR-2713 Concrete Dewalt Screw Bolt+ ESR-3889 Masonry (*) Hilti HUS-EZ ESR-3056 Masonry (**) Simpson Titen HD ESR-1056 Masonry (*) Dewalt Screw Bolt+ ESR-4042
The following adhesive anchor products are pre-approved:
Base Material Product ICC-ES Report Concrete Hilti HIT HY 200-V3 ESR-4868 Concrete Hilti HIT HY 100 ESR-3574 Concrete Hilti HIT RE 500-V3 ESR-3814 Concrete Simpson AT XP IAPMO ER-0263 Concrete Dewalt AC200+ ESR-4027 Concrete Dewalt Pure110+ ESR-3298 Masonry (**) Hilti HIT HY 270 ESR-4143/4144 Masonry (**) Simpson AT XP IAPMO ER-0281
The following power-actuated fastener products are pre-approved:
Base Material Product ICC-ES Report Steel/Concrete/Masonry/Wood Hilti Low Velocity ESR-1663 Steel/Concrete/Masonry/Wood Hilti X-U ESR-2269 Steel/Concrete/Masonry/Wood Simpson Powder-Actuated ESR-2138 Steel/Concrete/Masonry/Wood Dewalt Power-Driven ESR-2024 Steel/Concrete/Masonry/Wood Dewalt Trak-It ESR-3275
(*) Indicates products listed are for anchorage to solid grouted concrete masonry units only.
(**) Indicated products listed are for anchorage to solid grouted or ungrouted concrete masonry units. Do not use anchors in ungrouted cells unless shown explicitly directed by Engineer of Record.
STRUCTURAL STEEL:
Structural steel shall be detailed, fabricated and erected in compliance with AISC Specification for the design, fabrication, erection of structural steel for building, and Code of Standard Practice, and OSHA steel erection standards.
All beams and girders shall be cambered at mid-span as indicated on the structural drawings. The cambers indicated shall be measured in the fabricators shop. Cambering tolerances shall be (-0”, +1/2”). No center point cambering allowed.
Splicing structural members where not detailed on the drawings is prohibited without prior approval of the Structural Engineer of Record.
Modification of structural steel members in the field is not allowed without written approval by the Structural Engineer of Record.
All composite beams using the concrete slab as a compression flange are designed for unshored construction unless noted otherwise.
Anchor rods shall be minimum 3/4” diameter or as detailed in drawings.
Where weld sizes are not indicated provide minimum weld size as indicated in AISC table J2.4.
STRUCTURAL STEEL CONNECTIONS:
All steel connections are as indicated on the drawings.
Unless detailed otherwise, beam shop connections may be welded or bolted and field connections are to be bolted. Bolts shall be a minimum 3/4" diameter for connections specified or detailed in the drawings. The fabricator may submit an alternate connection with the calculations that is certified by a professional engineer who is licensed in the state where the project is located.
All re-entrant corners must be shaped notch free per AWS D1.1 to a minimum radius of 1” except corners in connection material and beam copes.
Provide stiffeners and doublers where shown. Member reinforcements shall be the minimum of the size as indicated or as required by engineering analysis of the connection.
For beam to spandrel beam connections provide full depth stiffeners and fill maximum bolt rows.
Welded connections shall be made in accordance with AWS D1.1 Structural Welding Code using E70XX electrodes unless noted otherwise. Weld sizes not shown or controlled by the required forces shall be AWS code minimum size. Welds shall be visually inspected for compliance with the AWS code visual inspection criteria. Welders shall be qualified in accordance with AWS D1.1 and shall be experienced in welding structural steel.
Full penetration welds shall be tested using NDT methods such as ultrasonic, magnetic particle or other methods referenced in the AWS code. Welds subject to NDT methods shall also have been found compliant with the AWS visual inspection criteria.
CONCRETE SLABS ON GRADE:
Slabs on grade shall be place in lane fashion.
The control or construction joints shall be placed as shown on the drawings. The joints shall align with the column grids and be spaced as noted below:
Exterior slabs 24 times slab thickness, maximum;
Interior slabs 36 times slab thickness, maximum;
Interior slabs 48 times slab thickness, maximum.
with carpeting
The panels formed by control or construction joints shall not be “L” shaped, and a rectangular panel’s aspect ratio shall not exceed 1.5.
Refer to the drawings for the typical slab on grade construction and saw cut control joint detail. Control and construction joints must be continuous and not offset.
Refer to drawings for detail of isolation diamonds or circles at columns.
Refer to drawings for reinforcing at re-entrant corners. Bend bars as necessary at obstructions.
Refer to the specification for the existence, type, and thickness of interior ground vapor retarder. Locate a vapor retarder directly beneath the slab on grade on top of a 6 inch compactable granular base. Refer to the specification for requirements for the compactable granular base.
Mechanically vibrate concrete around trench drains, floor ducts, construction joint dowels, loading docks, architectural features and other embedded items.
Refer to flooring manufacturer’s specification for levelness, flatness and curing of concrete slabs on grade to receive special architectural floor finishes.
Where slab demolition occurs in slabs on grade, curbs and sidewalk areas, typically saw cut slabs for new work to the widths indicated on plan. Where such saw cuts would occur within 3 feet or less of an existing control or construction joint, remove slabs to the nearest existing control or construction joint. Dowel edges as indicated for typical slabs in other areas. Provide slab control joints in new slabs at locations to match existing slab control joints, and also a spacing to keep slab panel aspect ratios as square as possible, but at a spacing not to exceed 10’-0”. Slab finishes shall match original existing finishes of surrounding slabs, subject to review of Architect.
REINFORCED MASONRY:
Masonry work shall conform to all requirements of TMS 402/602, “Building Code Requirements and Specification for Masonry Structures.”
All masonry units are placed in running bond fashion. Corners shall have a standard bond by overlapping units.
Special shapes shall be provided for jambs, columns, pilasters, control joints, corners, and lintels.
All masonry walls shall have horizontal joint reinforcing spaced at 16” oc. Horizontal joint reinforcing shall be ladder style and fabricated with galvanized nine-gauge wire and shall include corner and intersecting wall pieces. Provide minimum 6” laps at all splices.
Vertical reinforcing shall be held in place by rebar positioners, crossties, chairs, or tying to every other layer of horizontal reinforcing steel. Refer to the detail in the drawings for vertical reinforcing bar location in a core.
Provide concrete cover of minimum 1/2" to face shell.
Refer to detail in the drawings for reinforcing bar lap lengths.
Extend vertical reinforcing from footings to 2" clear top of wall or to beam bearing. Extend vertical reinforcing into the next level of construction and lap in accordance with the lap schedule.
When typical vertical wall reinforcing is interrupted by long wall openings, provide typical vertical wall reinforcing above and below opening, and extend into horizontal bond beams. Refer to the schedule on the drawings, for masonry wall opening lintels and jamb reinforcing.
Provide vertical reinforcing at the ends of walls and at wall intersections to match specified reinforcing. Run reinforcing full height of walls.
All masonry units shall be placed with full face shell mortar coverage on horizontal and vertical face shells. Webs shall also have full mortar coverage around all grouted cells.
Fill block core at vertical reinforcing (8" minimum length along wall) with concrete grout. Filling cores with mortar is not allowed.
Vibrate in place. Rodding and puddling are not allowed.
Maximum grout lift height is 5'-4". Maximum grout pour height is 8'-0", provide cleanouts if pour heights exceed 5'-4".
Masonry cement mortar is not allowed.
Calcium chloride or admixtures containing chloride shall not be used in mortar or grout.
For reinforced masonry bond beams, provide bent corner bars at corners and intersections that match reinforcing. Step bond beams as necessary to match roof slopes. Lap reinforcing bars per schedule.
For construction of masonry control joints refer to detail in drawings.
Unless noted otherwise on the drawings place control joints in masonry walls such that no straight run of wall exceeds 24’-0” and within 4’-0” of corners. Do not place control joints within 48 inches of a masonry opening jamb or a steel bearing plate.
Bond beams shall be constructed with flow through knock out bond beam blocks and reinforced with 2 - #5 continuous unless noted otherwise.
Place bond beam reinforcing continuously through control joints. Do not splice bond beam reinforcing within 6’-0” of a control joint.
Provide bond beam with reinforcing at all floor lines, roof lines, and top of walls. Refer to details in the drawings.
Grout below steel bearing plate and refer to the drawings for additional information.
Refer to drawings for reinforcing schedule, top of wall bracing, thickened bearing slab and lintel schedule for non-bearing masonry walls. Refer to Architectural drawings for location and extent.
1.3 High-Strength Bolting-Slip-Critical and Material
1.4 Steel Material, Seismic - Section 1705.12.1
1.2 High Strength Bolting-Bearing Material
1.1 Fabricator Documentation - Note (1)
1. STEEL CONSTRUCTION: Section 1705.2.1 and Table 1705.2.3
Continuous Periodic None
1.5 Welds: Full and Part Pen and Multi-Pass Fillet
1.6 Welds: Single Pass Fillet for All Sections
1.7 Frame Joint Detail Compliance
2.1 Member Shape and Size Compliance in Formwork
2. CONCRETE CONSTRUCTION: Section 1705.3 and Table 1705.3
2.2 Reinf Steel and PT Tendons Size, Quantity and Placement
2.3 Weldability of Reinforcing and Welds
2.4 Anchors in Concrete
2.5 Use of Required Mix Design
2.6 Sample for Specimens and Tests
2.7 Placement of CIP Concrete and Shotcrete
2.8 Curing Compliance
2.9 Strength for Stressing PT Tendons
2.10 Prestressing Force Application
2.11 Grouting Bonded Tendons - Seismic
2.12 Strength for Formwork Removal
2.13 Erection of Precast Members
3. MASONRY CONSTRUCTION: Section 1705.4
4.1 Bearing Material, Capacity and Depth
4. SOILS: Section 1705.6 and Table 1705.6
4.2 Compacted Fill Compliance With Soils Report
Notes:
1. When the fabricator does not meet the requirements of 1704.2.5.1.
2. Empirically designed masonry is excluded.
STRUCTURAL TEST AND SPECIAL INSPECTION SCHEDULE:
3.1 Level 3: TMS 602 Table 4
3.1.1 Proportions of Site-Prepared Mortar
3.1.2 Sample Panel Construction
3.1.3 Grout Space
3.1.4 Placement of Reinforcement, Connectors and Anchors
3.1.5 Proportions of Site Prepared Grout
3.1.6 Placement of Masonry Units and Mortar
Joint Construction
3.1.7 Size and Location of Structural Members
3.1.8 Welding of Reinforcement
3.1.9 Grout Placement
3.1.10 Preparation of Grout Specimens, Mortar Specimens
and/or Prisms
COLD-FORMED STEEL (METAL) FRAMING:
The cold-formed steel supplier shall submit certified shop drawings and design calculations prepared by a qualified Professional Engineer registered in the state where the project is located. See project specification manual for additional submittal requirements.
CFS supplier or installer shall provide all connectors, fasteners, bridging and bracing as required to provide a complete stable installation.
Attachment of studs to the building structure shall be designed by the supplier and shall be in locations shown on the structural drawings. Do not attach exterior studs to the bottom flange of beams unless specifically shown on the structural drawings.
The design and connection detailing of all cold-formed steel material including, but not limited to exterior studs, bearing studs, headers, jambs, joists, rafters and anchorage shall be by the Cold-Formed Steel Supplier. The minimum design criteria for all systems other than bearing framing shall meet the following criteria:
Stud in exterior walls shall be minimum 600S162-43 (6”-18 gauge) studs at 16” oc.
Studs shall be cold rolled steel, galvanized, C shape, with minimum 1 5/8” flange and minimum 1/2” return. They are to be punched for utility access and galvanized to G60 coating per ASTM 525.
At all openings in exterior and bearing walls provide a minimum two studs full wall height each side of opening and a minimum one additional stud each side for lintel bearing.
Anchor bottom track to concrete or masonry with minimum 0.145" diameter power driven fasteners with minimum 3/4" embed at 16” oc.
Top and bottom tracks shall be cold formed steel,galvanized U shaped and minimum 18 gauge.
Cold-Formed steel framing fasteners shall be minimum #10 self-drilling screws, with low profile head when beneath sheathing. Provide a minimum of two screws per connection unless noted otherwise. Screws are to extend through last connected layer with at least 3 threads exposed on backside.
Fasten cold-formed framing to wood with minimum #10 x 1 7/8” bugle head woodscrews. Pre-drill holes in metal studs.
Provide a minimum of two screws per connection unless noted otherwise.
All framing components shall be squarely cut for attachment to perpendicular members. Stud ends must seat tightly into tracks for all bearing applications.
Wall stud deflection criteria:
For wall studs providing lateral support to masonry veneer and cementitious stucco, limit deflection to L/600.
For wall studs providing lateral support to other materials, limit deflection to L/360.
Joist and rafter deflection criteria:
Live Load Deflection limit to L/360.
Total Load Deflection limit to L/240.
All cold-formed designations are in accordance with the Steel Stud Manufacturers Association (SSMA).
Refer to architectural drawings and specification for size, minimum gage, extent, and location of interior non-bearing cold-formed steel framing not shown on the structural drawings. Interior cold-formed steel framing is to be designed for 5 psf lateral pressure by the cold-formed steel supplier.
Temporary bracing shall be furnished by the cold-formed steel supplier and framing installer and maintained until permanent systems providing lateral stability are in place.
Welding shall conform to the American Welding Society (AWS) “Structural Welding Code – Sheet Steel, D1.3 – Current Edition.” Welders shall be qualified in accordance with AWS D1.3 and shall be experienced in cold-formed welding.
All cold-formed steel material to be welded must be nominal 16 gauge or thicker.
Touch up all cold-formed material at welds with zinc-rich paint.
Align load bearing wall studs with floor or roof joists.
Splices in studs, joists, and headers, are not permitted, unless approved in writing by the structural engineer.
Framing components may be pre-assembled into panels prior to erecting. Prefabricated panels shall be square, with components attached in a manner that prevents racking.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
TRIPLE C - The A/E Group
100 Pearl Street, 14th Floor
Hartford, CT 06103
MAT PERKINS
860-270-0753
MBJ PROJECT # 24.513
A u to d e s k D o c s /3
C
R
.P ro je c t.
-2
-7
.E
H R
M .I U
.B e d fo rd .M
A .R
/5
-2
-7
.B e d fo rd .E
H R
M .M
C R
.M B
J S
T R
U C
R
.r v t
/2
/2
:4
:2
A
M
MCRS-002
GENERAL STRUCTURAL NOTES 518-22-700
MCR
06/04/2025 CRO JJH
ISSUED FOR CONSTRUCTION EHRM INFRASTRUCTURE
UPGRADES
200 Springs Rd, Bedford MA 01730
# Revisions: Date:
F S
F S
F S
1. SEE SHEET MCRS-001 FOR SHEET INDEX, TYPICAL ABBREVIATIONS AND LEGENDS.
2. SEE SHEET MCRS-002 FOR GENERAL STRUCTURAL NOTES.
3. SEE SHEET MCRS-401 FOR FOUNDATION SCHEDULES AND TYPICAL DETAILS.
4. SEE SHEET MCRS-402 FOR MASONRY SCHEDULES AND TYPICAL DETAILS.
5. SEE SHEET MCRS-403 FOR STEEL SCHEDULES AND TYPICAL DETAILS.
6. SEE SHEET MCRS-501 FOR FOUNDATION DETAILS.
7. SEE SHEET MCRS-701 FOR FRAMING DETAILS.
REFERENCE NOTES:
PLAN NOTES (UNLESS NOTED OTHERWISE):
1. PROJECT DATUM ELEVATION 0'- 0" = 181.0'. SEE CIVIL AND ARCHITECTURAL DRAWINGS.
2. TOP OF FOOTING ELEVATION (TFE) = -4'- 0", UNLESS NOTED OTHERWISE ON PLAN AS (XX'-XX").
3. ALL FOOTINGS ARE CENTERED UNDER WALLS AND COLUMNS.
4. SEE TYPICAL FOUNDATION DETAILS FOR UTILITY PENETRATIONS THROUGH FOUNDATIONS. SEE PLAN
FOR APPROXIMATE LOCATIONS. VERIFY LOCATIONS AND ELEVATIONS WITH MECHANICAL DRAWINGS.
5. TOP OF PIER ELEVATION (TPE) = -1'- 0", UNLESS NOTED OTHERWISE ON PLAN AS (XX'-XX").
6. CIP FOUNDATION TOP OF WALL ELEVATION (TWE) = -1'- 0" , UNLESS NOTED OTHERWISE ON PLAN.
7. FOR SLAB JOINT LAYOUTS, SEE PLANS AND GENERAL STRUCTURAL NOTES FOR CRITERIA. FOR
TYPICAL CONTROL AND CONSTRUCTION JOINTS SEE TYPICAL SLAB JOINTING DETAILS.
8. SEE ARCHITECTURAL DRAWINGS FOR ADDITIONAL INFORMATION, INCLUDING LOCATIONS AND
DIMENSIONS OF RAMPS, SLAB SLOPES, SLAB STEPS AND SLAB DEPRESSIONS.
9. VERIFY SIZE, LOCATION AND INVERT ELEVATIONS FOR ALL UTILITIES, SITE STRUCTURES, SUMPS AND
DRAINS WITH CIVIL, MECHANICAL, ELECTRICAL AND ARCHITECTURAL DRAWINGS.
10. SEE CIVIL / LANDSCAPE DRAWINGS FOR PAVING AND SITE DETAILS AT THE BUILDING EXTERIOR.
11. REFER TO THE GEOTECHNICAL REPORT FOR EXISTING SUBSURFACE CONDITIONS AND OTHER
INFORMATION. REMOVAL OF EXISTING BEDROCK MAY BE NEEDED IN SOME AREAS. CONTRACTOR
SHALL VERIFY THE EXISTING CONDITIONS AND COORDINATE REMOVALS WITH THE GEOTECHNICAL
AND STRUCTURAL ENGINEERS.
C
B
A
6" CONC SOG W/ #5
AT 18" OC EACH WAY
7' - 9" 13' - 6 3/8" 15' - 9" 6' - 4 5/8" 16' - 8 1/2" 26' - 8"
MCRS-501
MCRS-401
MCRS-401
CJ
C J
C J
C J
C J
MCRS-501
CJ
MCRS-401
CW2
MCRS-501
D
E
F
/8
/4
/4
CJ CJ
MCJ
MCJ
M C
J
MCJ
MCRS-501
MCRS-401
MCRS-501
MCRS-501
MCRS-401
MCRS-501
MCRS-401
-4
-6
-6
-4
MCRS-401
CW1
CW1
CW1
CW1
CW1
CW1 CW2
CW2
CW2
CW2
MW2
MW2
MW1
MW1
MW1
MW2
MW2
MW1
MW1MW1
MCRS-501
W
WF1 (-4' - 0")
W
WF1 (-4' - 0")
W
WF1 (-4' - 0")
WF1 (-4' - 0")
W
WF1 (-4' - 0")
W
WF1
C J
C J
CJ
V E
R
IF
Y
VERIFY W/ ARCH
8' - 2"
VERIFY W/ ARCH
9' - 4"
VERIFY W/ ARCH
9' - 4"
V E
R
IF
Y W
A
R C
H
V E
R
IF
Y W
A
R C
H
V E
R
IF
Y W
A
R C
H
/8
1' - 2"
VERIFY W/ ARCH
6' - 4"
8"
/8
SC1
F1 (-4' - 0")
P1
TSE = 0' - 0"
TWE = 0' - 0" TWE = 0' - 0"
TWE = 0' - 0"
TWE = 0' - 0"
TWE = 0' - 0"
TWE = 0' - 0"
TWE = 0' - 0"
WF1
-6
-4
(E) 4'-2" x 4'-2" x 1'-4"(E) 4'-2" x 4'-2" x 1'-4"
(E) 6'-0" x 6'-6" x 1'-9"
(E) 4'-10" x 5'-2" x 1'-8"
(E) 4'-10" x 5'-2" x 1'-8"
(E) 4'-2" x 4'-2" x 1'-4"(E) 4'-2" x 4'-2" x 1'-4"
(E
1' -8 x
1' -0 x
C O
N T
(E) 6'-0" x 6'-6" x 1'-9"
(E
1' -8 x
1' -0 x
C O
N T
(E ) 1 x 1
(E) 14 x 14
(E ) 1 x 1
(E ) 1 x 1
(E ) 1 x 1
(E) 18 x 24
(E) 1'-8" x 1'-0" x CONT
(E
1' -8 x
1' -0 x
C O
N T
( -6' - 1" )
( -6' - 5" ) ( -6' - 5" )
-6
( -6' - 11" )
( -6' - 5" )( -6' - 5" )
( -6' - 0" )
-6
(E
1' -8 x
1' -0 x
C O
N T
(E) 1'-8" x 1'-0" x CONT
( -6' - 1" )
(E) 6" CONC SOG
(E) TSE = 0' - 0"
MCRS-501
MCJ
M C
J
M C
J
M C
J
M C
J
MCJ
M C
J
M C
J
M C
J
MCJ
M C
J
MCJ
M C
J
MCJ
FLOOR DRAIN - SEE ARCHITECTURAL AND PLUMBING FOR MORE INFORMATION. PROVIDE 1 - #5 x
24" LONG ON EACH SIDE.
KEYNOTES:
HOUSEKEEPING PAD - SEE . SEE ARCHITECTURAL AND MECHANICAL DRAWINGS FOR
EXACT SIZE AND LOCATION.
2 6/ MCRS-501
EXISTING STORM DRAIN TO BE REMOVED AND REPLACED. STEP FOOTINGS AS NEEDED - SEE
DETAIL .
7/ MCRS-401
EXISTING BEDROCK REMOVAL LIKELY IN THIS AREA - SEE PLAN NOTE 11.4
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
TRIPLE C - The A/E Group
100 Pearl Street, 14th Floor
Hartford, CT 06103
MAT PERKINS
860-270-0753
MBJ PROJECT # 24.513
A u to d e s k D o c s /3
C
R
.P ro je c t.
-2
-7
.E
H R
M .I U
.B e d fo rd .M
A .R
/5
-2
-7
.B e d fo rd .E
H R
M .M
C R
.M B
J S
T R
U C
R
.r v t
/2
/2
:4
:2
A
M
MCRS-201
FOUNDATION PLAN 518-22-700
MCR
06/04/2025 CRO JJH
ISSUED FOR CONSTRUCTION EHRM INFRASTRUCTURE
UPGRADES
200 Springs Rd, Bedford MA 01730
1/4" = 1'-0"1
FOUNDATION PLAN
# Revisions: Date:
1 Addendum 1 02/25/2026
CASE 1
ONE BAR PER CELL
LOCATED IN THE
CENTER OF THE CELL
CASE 2
ALL OTHER CONDITIONS INCLUDING TWO
BARS PER CELL AND SINGLE BARS NOT
LOCATED IN THE CENTER OF THE CELL
CMU REINFORCING BAR LAP SPLICE SCHEDULE: f'm = 2000 PSI
#3
#4
#5
#6
#7
#8
CASE 1 CASE 1 CASE 2 CASE 1 CASE 2 CASE 1 CASE 2
6" CMU 8" CMU 10" CMU 12" CMUBAR
SIZE
14" 14" 14" 14" 14" 14"
21" 18" 18" 24" 18" 22"
15"
25"
32" 22" 22" 37" 22" 35"39"
- 38" 35" 54" 35" 54"54"
- 52" 40" 63" 40" 63"-
- - 61" - 53" 72"-
NOTES:
1. REINFORCING BAR LAP SPLICE SCHEDULE APPLIES TO UNCOATED, GRADE 60 REINFORCING BARS IN
ASTM C 90 HOLLOW UNITS.
2. CASE 1: ONE BAR PER CELL LOCATED IN THE CENTER OF THE CELL.
CASE 2: ALL OTHER CONDITIONS, INCLUDING TWO BARS PER CELL AND SINGLE BARS NOT LOCATED IN
THE CENTER OF THE CELL.
3. FOR EPOXY COATED BAR, MULTIPLY THE ABOVE LENGTHS BY 1.5.
4. MAXIMUM SPACING OF BARS BEING LAPPED IS ONE FIFTH THE LAP SPLICE LENGTH, NOT TO EXCEED 8".
5. REINFORCING BARS SHALL BE LAPPED IN THE SAME CMU CELL.
6. ALL BARS MUST BE PLACED IN FULLY GROUTED CELLS OR BOND BEAMS.
NOTES:
1. SEE TYPICAL WALL DETAILS FOR ADDITIONAL INFORMATION.
2. PROVIDE DOWELS AT FOUNDATION TO MATCH SIZE AND SPACING OF VERTICAL REINFORCING.
3. PROVIDE HORIZONTAL JOINT REINFORCEMENT PER GENERAL STRUCTURAL NOTES.
LINTEL - SEE LINTEL
SCHEDULE
LINTEL REINFORCING -
SEE LINTEL SCHEDULE
TYPICAL VERTICAL
WALL REINF - SEE CMU
WALL SCHEDULE
DOWELS TO STRUCTURE BELOW
TO MATCH VERT REINF SIZE AND
LOCATION - SEE WALL DETAILS
JAMB REINFORCING
- SEE JAMB SCHEDULE
BOND BEAM REINFORCING -
SEE TOP OF WALL DETAILS
NOTES:
1. JAMB AND END OF WALL REINFORCING SHALL BE FULL HEIGHT OF WALL AND SHALL BE IN ADDITION TO TYPICAL VERTICAL WALL REINFORCING.
2. PROVIDE CONTROL JOINTS TO MEET SPACING REQUIREMENTS SHOWN AND AT LOCATIONS WHERE CHANGES IN WALL HEIGHT OCCUR, WHERE CHANGES IN WALL THICKNESS OCCUR, AND WHERE
MOVEMENT JOINTS IN THE FLOOR ABOVE AND/OR BELOW OCCUR.
3. SEE ARCHITECTURAL DRAWINGS FOR CONTROL JOINT LOCATIONS AT NON-LOAD BEARING WALLS NOT SHOWN ON STRUCTURAL DRAWINGS.
4. SEE ARCHITECTURAL DRAWINGS FOR WALL OPENINGS NOT SHOWN ON STRUCTURAL DRAWINGS.
5. PROVIDE CLEANOUT AT BOTTOM COURSE FOR GROUT POURS GREATER THAN 5'-0" HIGH.
6. SILL REINFORCING SHALL BE LADDER JOINT REINFORCING IN THE FIRST OR SECOND MORTAR JOINT BELOW THE SILL OR A REINFORCED BOND BEAM. SILL REINFORCING SHALL EXTEND BETWEEN CONTROL
JOINTS.
7. SEE NON-LOAD BEARING INTERIOR CMU WALL REINFORCING SCHEDULE FOR LINTEL AND JAMB REINFORCING REQUIRED AT NON-LOAD BEARING INTERIOR WALLS.
END OF WALL OR
CORNER
CONTROL JOINT - SEE
TYPICAL DETAIL
END OF WALL OR
CORNER
REINFORCING - SEE
TYPICAL DETAIL
OR CORNER
4'-0" MAX TO
END OF WALL
CONTROL JOINT - SEE TYPICAL DETAIL
24'-0" MAX
CONTROL JOINT SPACING
TO WALL OPENING
4'-0" MIN
H E
IG
H
T
'-0
T
Y P
L
IF
T
L A
P S
P L
IC
E
JAMB REINFORCING
- SEE JAMB SCHEDULE
SILL REINFORCING
SEE TYPICAL CMU
WALL CONTROL JOINT
THROUGH BOND BEAM
PLAN DETAILS FOR
REINFORCING
REQUIREMENTS
TYP
12" MIN
WALL CORNER
JAMB OR WALL END
WALL INTERSECTION
L A
P S
P L
IC
E
T Y
P
ADDITIONAL BAR TO
MATCH SCHEDULED
VERT WALL REINF
ADDITIONAL
BAR TO MATCH
SCHEDULED
VERT WALL
REINF
90 DEG
HOOK
POUR THRU BOND
BEAM…