Amend 5 - ATT 30-518-22-700.Bedford.EHRM.IFC.Add1.B80.2060225.pdf
PDF 4 MB Posted
- Solicitation number
- 36C77626R0003
About this file
This file contains architectural drawings and specifications for the EHRM Infrastructure Upgrades project at the Edith Nourse Memorial Veterans Hospital in Bedford, Massachusetts (Project Number 518-22-700, Building 80). The drawings were issued for construction on June 4, 2025, with Addendum 1 issued on February 25, 2026, and are prepared by TRIPLE C - The A/E Group.
The project scope includes renovation of basement and first-level spaces, specifically Room 4 in the basement (760 SF office space with cubicles, kitchen/break room, and corridor) and Room 102 on the first level (a new 140 SF telecom room). Key construction requirements include: installation of 45-minute fire-rated doors and frames with access control hardware modifications; creation of fire and smoke-rated partitions with specific UL design ratings (1-hour fire and smoke-rated for the telecom room); provision of temporary dust-tight barriers during dusty work; potential asbestos abatement at floor penetrations; new fire extinguisher cabinets (Type 2A:10B:C clean agent) located no more than 75 feet from each telecom room; removal and reinstallation of existing furnishings and systems furniture by the contractor; new interior finishes including painted gypsum wallboard (Benjamin Moore Manchester Tan HC-81 and White Down OC-131), resilient base (Johnsonite Beige 49), and sealed concrete with static dissipative coating for the telecom room; and installation of ADA-compliant signage per the VA Signage Design Manual. The contractor is responsible for all costs associated with moving, storing, and returning furnishings and equipment, and must verify all dimensions and site-specific conditions at the time of bidding. The project is fully sprinklered and must comply with the latest VA Physical Security Standards and Campus Standards.
View the file
Other files
Show 40 more
Latest 50 of 105 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
UP
UP
UP
UP
UP
SHEET SYMBOL LEGEND
KEYNOTES
GENERAL NOTES
EXISTING CONSTRUCTION TO REMAIN
EXISTING CONSTRUCTION TO BE DEMOLISHED
NEW CONSTRUCTION, WITH PARTITION TYPE
A
A. SEE GENERAL NOTES AND PLANS FOR TYPICAL GENERAL PROJECT
REQUIREMENTS AND PROJECT LOCATION DRAWINGS.
B. SEE INTERIOR FINISH DRAWINGS FOR ADDITIONAL FINISHES
INFORMATION.
C. SEE MECHANICAL AND ELECTRICAL DRAWINGS FOR ADDITIONAL
SYSTEMS INFORMATION.
D. NEW TELECOM ROOMS SHALL BE 1 HOUR FIRE AND SMOKE RATED
AND COMPLY WITH THE LATEST VA PHYSICAL SECURITY STANDARDS,
AND CAMPUS STANDARDS.
E. SEE TYPICAL WALL FRAMING DETAILS ON SHEET A-511.
F. SEE TYPICAL HEAD OF WALL DETAIL ON SHEET A-512.
G. SEE TYPICAL CEILING DETAILS ON SHEET A-531
H. DATE OF THIS DRAWING SET. CONTRACTOR SHALL FIELD VERIFY ALL
DIMENSIONS, CONDITIONS, AND SITE-SPECIFIC INFORMATION AT THE
TIME OF BIDDING.
I. CONTRACTOR IS RESPONSIBLE FOR ALL COSTS ASSOCIATED
WITH MOVING, STORING AND RETURNING FURNISHINGS AND
EQUIPMENT TO THE PROPOSED WORK AREA(S). ANY
DISASSEMBLY AND REASSEMBLY OF SYSTEMS FURNITURE IN THE
PROPOSED WORK AREAS IS THE RESPONSIBILITY OF THE
CONTRACTOR AND MUST FOLLOW THE MANUFACTURER'S
WARRANTY.
PARTITION RATING GRAPHICS:
4 HR FIRE BARRIER
3 HR FIRE BARRIER
2 HR FIRE & SMOKE BARRIER
2 HR FIRE BARRIER
2 HR FIRE BARRIER/SHAFT
1 HR FIRE & SMOKE BARRIER
1 HR FIRE BARRIER
1 HR FIRE BARRIER/SHAFT
SMOKE PARTITION (NON RATED)
NON RATED
PARTITION RATING GRAPHIC DESIGNATION: PRIORITY
1 HIGHEST
5 LOWEST
PARTITIONS REQUIRED TO BE SMOKE RESISTANT, FIRE
RESISTANT, OR BOTH FIRE AND SMOKE RESISTANT ARE SHOWN
GRAPHICALLY ON PLANS WITH HATCH PATTERNS.
CRAWL
SPACE
OFFICE
SPACE
CUBICLES
B04B04
80A-400
C6
9 10 11
D
E
F
OFFICE
SPACE
CUBICLES
B04
760 SF
KITCHEN
BREAK
ROOM
B04AB04A
CORRIDOR
B20B20
CRAWL
SPACE
STAIR
B11B11
9 10 11
D
E
F
OFFICE
SPACE
CUBICLES
B04
760 SF
KITCHEN
BREAK
ROOM
B04AB04A
CORRIDOR
B20B20
CRAWL
SPACE
STAIR
B11B11
04 H W
-S H
-3 F
9 10 11
D
E
F
OFFICE
SPACE
CUBICLES
B04
760 SF
KITCHEN
BREAK
ROOM
B04AB04A
CORRIDOR
B20B20
CRAWL
SPACE
STAIR
B11B11
OFFICE
SPACE
CUBICLES
B04
760 SF
KITCHEN
BREAK
ROOM
B04AB04A
CORRIDOR
B20B20
CRAWL
SPACE
STAIR
B11B11
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
TRIPLE C - The A/E Group
100 Pearl Street, 14th Floor
Hartford, CT 06103
MAT PERKINS
860-270-0753
A u to d e s k D o c s /3
C
R
.P ro je c t.
-2
-7
.E H
R M
.I U
.B e d fo rd
.M A
.R
/5
-2 -7
.B e d fo rd .E
H R
M .A
R C
H .B
R
.r v t
/2
/2
:5
:5
P
M
80A-400
ARCHITECTURAL ENLARGED VIEWS -
BASEMENT LEVEL
518-22-700
06/04/2025 M. Perkins K. McDermott
ISSUED FOR
CONSTRUCTION
EHRM INFRASTRUCTURE
UPGRADES
200 Springs Rd, Bedford, MA 01730
1/32" = 1'-0" F6
BASEMENT LEVEL REFERENCE PLAN
1/4" = 1'-0" E6
ARCHITECTURAL FLOOR PLAN - BASEMENT LEVEL - ROOM 4 - DEMO
1/4" = 1'-0" C6
ARCHITECTURAL FLOOR PLAN - BASEMENT LEVEL - ROOM 4 - NEW
1/4" = 1'-0"
C4
ARCHITECTURAL REFLECTED CEILING PLAN - BASEMENT LEVEL - ROOM 4 - NEW
1/4" = 1'-0" E4
ARCHITECTURAL REFLECTED CEILING PLAN - BASEMENT LEVEL - ROOM 4 - DEMO
1 REMOVE EXISTING DOOR AND FRAME
2 PROVIDE TEMPORARY DUST TIGHT BARRIER AROUND WORK AREA
DURING ACTIVITIES WHICH PRODUCE DUST
3 NEW 45 MIN. FIRE RATED DOOR AND FRAME. SEE DOOR SCHEDULE
AND SPECIFICATIONS FOR ADDITIONAL INFORMATION. MODIFY
DOOR AS REQUIRED FOR NEW ACCESS CONTROL HARDWARE.
4 EXISTING CEILING TO REMAIN
5 POTENTIAL ABATEMENT AT FLOOR FOR FLOOR PENETRATIONS.
REFER TO COVER SHEET FOR KNOWN ACM ITEMS WITHIN THIS
BUILDING.
Number Revisions: Date:
1 Addendum 1 2/25/2026
02/25/2026
DN
DN
DN
DN
SHEET SYMBOL LEGEND
KEYNOTES
GENERAL NOTES
EXISTING CONSTRUCTION TO REMAIN
EXISTING CONSTRUCTION TO BE DEMOLISHED
NEW CONSTRUCTION, WITH PARTITION TYPE
A
A. SEE GENERAL NOTES AND PLANS FOR TYPICAL GENERAL PROJECT
REQUIREMENTS AND PROJECT LOCATION DRAWINGS.
B. SEE INTERIOR FINISH DRAWINGS FOR ADDITIONAL FINISHES
INFORMATION.
C. SEE MECHANICAL AND ELECTRICAL DRAWINGS FOR ADDITIONAL
SYSTEMS INFORMATION.
D. NEW TELECOM ROOMS SHALL BE 1 HOUR FIRE AND SMOKE RATED
AND COMPLY WITH THE LATEST VA PHYSICAL SECURITY STANDARDS,
AND CAMPUS STANDARDS.
E. SEE TYPICAL WALL FRAMING DETAILS ON SHEET A-511.
F. SEE TYPICAL HEAD OF WALL DETAIL ON SHEET A-512.
G. SEE TYPICAL CEILING DETAILS ON SHEET A-531
H. DATE OF THIS DRAWING SET. CONTRACTOR SHALL FIELD VERIFY ALL
DIMENSIONS, CONDITIONS, AND SITE-SPECIFIC INFORMATION AT THE
TIME OF BIDDING.
I. CONTRACTOR IS RESPONSIBLE FOR ALL COSTS ASSOCIATED
WITH MOVING, STORING AND RETURNING FURNISHINGS AND
EQUIPMENT TO THE PROPOSED WORK AREA(S). ANY
DISASSEMBLY AND REASSEMBLY OF SYSTEMS FURNITURE IN THE
PROPOSED WORK AREAS IS THE RESPONSIBILITY OF THE
CONTRACTOR AND MUST FOLLOW THE MANUFACTURER'S
WARRANTY.
PARTITION RATING GRAPHICS:
4 HR FIRE BARRIER
3 HR FIRE BARRIER
2 HR FIRE & SMOKE BARRIER
2 HR FIRE BARRIER
2 HR FIRE BARRIER/SHAFT
1 HR FIRE & SMOKE BARRIER
1 HR FIRE BARRIER
1 HR FIRE BARRIER/SHAFT
SMOKE PARTITION (NON RATED)
NON RATED
PARTITION RATING GRAPHIC DESIGNATION: PRIORITY
1 HIGHEST
5 LOWEST
PARTITIONS REQUIRED TO BE SMOKE RESISTANT, FIRE
RESISTANT, OR BOTH FIRE AND SMOKE RESISTANT ARE SHOWN
GRAPHICALLY ON PLANS WITH HATCH PATTERNS.
80A-401
B8
TELECOM
ROOM
102102
C
TELECOM
ROOM
140 SF
HW-SH-3F
(E X
IS
T
V
IF
'-0
(EXIST VIF)
11'-0"
B
A4
A4
B
B
B
7' -0
/8
4' -1
/8
C
9 5 5 9
RECEPTION
AREA
102A102A
CORRIDOR
130130
7' -0
OFFICE
PEER
SUPPORT
143 SF
ACOUSTICAL OR RATED
SEALANT BOTH SIDES
FLOOR LINE
5/8" GWB BOTH SIDES
SOUND ATTENUATION
BATTS (SAB) PER
SCHEDULE.
CEILING LINE
STRUCTURAL DECK
METAL STUDS, SIZE
PER SCHEDULE
80A-512
E5
A/C GRADE, 3/4" FIRE-
TREATED PLYWOOD
80A-512
B4
AT FIRE RATED
PARTITIONS
AT SMOKE RATED
PARTITIONS
BOTTOM OF PLYWOOD TO
BE AT 12" AFF
ACOUSTICAL OR RATED
FLEXIBLE SEALANT
FLOOR LINE
ADD ONE LAYER OF 5/8" GWB,
ONE-SIDE WITH APPROVED UL
SETTING COMPOUND BETWEEN
LAYERS AND FASTENED TO
WALL AS REQUIRED, AT
EXISTING GWB WALL
ASSEMBLIES
STRUCTURAL DECK
EXISTING METAL STUDS AND
BATT INSULATION TO REMAIN
A/C GRADE, 3/4" FIRE-TREATED
PLYWOOD, ADHERED TO CONCRETE
AT EXISTING CONCRETE WALL
ASSEMBLIES
BOTTOM OF PLYWOOD
TO BE AT 12" AFF
UL DESIGN V497
1-HOUR PARTITION RATED FROM BOTH SIDES
EXISTING GWB OR
CONCRETE WALL
ASSEMBLY, WHERE OCCURS
SIDE OF
EXISTING
ROOM OR
CORRIDOR TO
REMAIN
80A-512
E5
80A-512
B4
1/2" 1/2"
VARIES
SEE PLAN
WALL - SEE PLAN
FOR TYPE
SEALANT - EA. SIDE
& ALL AROUND,
TYP.
HOLLOW METAL
FRAME
/2
V
A R
IE
S
S E
E P
L A
N
/2
UNO
4" 2"
ADJACENT WALL
WHERE OCCURS
SEALANT - EA SIDE &
ALL AROUND, TYP.
HOLLOW METAL FRAME
WALL - SEE PLAN
FOR TYPE
E1
TYPICAL FRAME
H E
IG
H
T
2" WIDTH 2"
E2
FRAME TYPE ELEVATIONS DOOR TYPE ELEVATIONS
F
FLUSH
C
C
TELECOM
ROOM
140 SF
OFFICE
PEER
SUPPORT
102102
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
TRIPLE C - The A/E Group
100 Pearl Street, 14th Floor
Hartford, CT 06103
MAT PERKINS
860-270-0753
A u to d e s k D o c s /3
C
R
.P ro je c t.
-2
-7
.E H
R M
.I U
.B e d fo rd
.M A
.R
/5
-2 -7
.B e d fo rd .E
H R
M .A
R C
H .B
R
.r v t
/2
/2
:5
:5
P
M
80A-401
ARCHITECTURAL ENLARGED VIEWS - FIRST
LEVEL
518-22-700
06/04/2025 M. Perkins K. McDermott
ISSUED FOR
CONSTRUCTION
EHRM INFRASTRUCTURE
UPGRADES
200 Springs Rd, Bedford, MA 01730
1/32" = 1'-0" F6
FIRST LEVEL REFERENCE PLAN
1/4" = 1'-0" B8
ARCHITECTURAL FLOOR PLAN - FIRST LEVEL
- RM 102 - NEW
1/4" = 1'-0" D8
ARCHITECTURAL FLOOR PLAN - FIRST LEVEL
- RM 102 - DEMO
1 OPEN TO DECK
2 NEW 45 MIN. FIRE RATED DOOR AND FRAME. SEE DOOR SCHEDULE
AND SPECIFICATIONS FOR ADDITIONAL INFORMATION. MODIFY
DOOR AS REQUIRED FOR NEW ACCESS CONTROL HARDWARE.
3 REMOVE EXISTING WINDOW AND FRAME
4 PROVIDE NEW FIRE EXTINGUISHER CABINET WITH A TYPE 2A: 10B: C
CLEAN AGENT FIRE EXTINGUISHER LOCATED NO GREATER THAN 75
FEET AWAY FROM THE NEW TR. CONTRACTOR TO COORDINATE THE
NEW LOCATION WITH THE COR. CONTRACTOR SHALL BID A NEW FEC
FOR EACH TR IN THE SCOPE
5 REMOVE EXISTING DOOR AND FRAME
6 REMOVE EXISTING FLOORING, ADHESIVES, AND WALL BASE
7 AT NEW WALL INSTALLATIONS, CONTRACTOR TO PAINT NEW WALL IN
ITS ENTIRETY. INSTALL NEW WALL BASE AT ENTIRE WALL SPAN OR
APPROPRIATE TRANSITION LOCATION AS APPROVED BY THE COR.
8 EXISTING WALL TO BECOME 1 HOUR FIRE AND SMOKE-RATED.
PATCH AND SEAL ALL PENETRATIONS AS NECESSARY.
9 PROVIDE TEMPORARY DUST TIGHT BARRIER AROUND WORK AREA
DURING ACTIVITIES WHICH PRODUCE DUST
10 REMOVE EXISTING ACOUSTICAL CEILING AND LIGHTS. MODIFY
AND/OR PROVIDE ADDITIONAL SUPPORTS AS REQUIRED FOR
EXISTING CEILING ITEMS TO REMAIN.
11 POTENTIAL ABATEMENT AT FLOOR FOR FLOOR PENETRATIONS.
REFER TO COVER SHEET FOR KNOWN ACM ITEMS WITHIN THIS
BUILDING.
NOT TO SCALE
B3
FIRST LEVEL EXISTING RM 102
NOT TO SCALE
B1
FIRST LEVEL EXISTING RM 102
NOTE: FIRE RESISTANCE TEST FOR ONE HOUR RATED WALLS: UL
U465
(TYPE A) TYPICAL PARTITION
MARK STUD WIDTH PRTN WIDTH DESIGN STC
A4 6" 6" <varies>
NOTE: FIRE RESISTANCE TEST FOR TWO HOUR RATED WALLS: UL
V438, UL U411
(TYPE B) TYPICAL PARTITION
MARK STUD WIDTH PRTN WIDTH DESIGN STC
B 2 1/2" 3/4" 45
DOOR AND FRAME SCHEDULE
IDENTIFICATION DIMENSIONS PANEL FRAME DETAIL
FIRE RATING
HARDWARE
NOTESLEVEL ROOM NO. ROOM NAME DOOR NO. W1 H T TYPE MATERIAL FINISH GLAZING UNDERCUT TYPE MATERIAL FINISH HEAD JAMB SILL GROUP ELECTRICAL
BASEMENT B04 OFFICE SPACE CUBICLES 04 3' - 0" 7' - 0" 1 3/4" 1 HM P-2 NONE 3/8" 1 HM P-2 E1/80A-401 E2/80A-401 F1/80IN101 45 MIN. HW-SH-3F SEE SPEC 1
LEVEL 1 102 TELECOM ROOM 102 3' - 0" 7' - 0" 1 3/4" 1 HM P-2 NONE 3/8" 1 HM P-2 E1/80A-401 E2/80A-401 F1/80IN101 45 MIN. HW-SH-3F SEE SPEC 1
3" = 1'-0" E1
HOLLOW METAL HEAD DETAIL
3" = 1'-0"
E2
HOLLOW METAL JAMB DETAIL
1/4" = 1'-0" E4
DOOR AND FRAME TYPES ELEVATIONS
1/4" = 1'-0" D6
ARCHITECTURAL REFLECTED CEILING PLAN -
FIRST LEVEL - RM 102 - DEMO
1/4" = 1'-0" B6
ARCHITECTURAL REFLECTED CEILING PLAN -
FIRST LEVEL - RM 102 - NEW
1. SEE SPECIFICATIONS 08 71 00 FOR DOOR HARDWARE REQUIREMENTS. COORDINATE WITH ELECTRICAL.
Number Revisions: Date:
1 Addendum 1 2/25/2026
"FIRE-RATED WALLS"- ADDITIONAL NOTES:
1. CONDITIONS INDICATED TO SHOW DESIGN INTENT. THEY ARE NOT INTENDED TO BE PROPRIETARY. CONTRACTOR MAY EMPLOY SIMILAR A UL-APPROVED TOP-OF-WALL DESIGNS THAT ARE APPROPRIATE FOR CONDITIONS.
2. REFER TO SECTION 07 84 00 / FIRESTOPPING FOR ADDITIONAL REQUIREMENTS REGARDING HEAD-OF-WALL CONDITION FOR FIRE-RATED WALLS.
SLOTTED TOP
TRACK
STUD
DESIGN BASIS: UL-HW-D-0082
CONCRETE SLAB
DESIGN BASIS: UL-HW-D-0042
METAL DECK
(PERPENDICULAR TO FLUTES)
/8
DESIGN BASIS: UL-HW-D-0264
METAL DECK
(PARALLEL TO FLUTES)
1" 1" 2"x20 GA
STRAPS @ 16"
O.C.
DESIGN BASIS: UL-HW-D-0259
STEEL BEAM
20 GA Z-BARS
TO
ACCOMMODATE
SFRM
SPRAY-APPLIED
FIRE-RESISTIVE
MATERIAL
(SFRM)
SAB
1 OR 2 LAYERS OF GWB;
SEE WALL TYPE
FIRE STOP SEALANT
FIRE STOP JOINT
SPRAY
MINERAL WOOL
FORMING MATERIAL
/8
/8
FIRE STOP JOINT
SPRAY
SLOTTED TOP
TRACK
STUD
SAB
1 OR 2 LAYERS OF GWB;
SEE WALL TYPE
/8
MINERAL WOOL
FORMING MATERIAL
SLOTTED TOP
TRACK
STUD
CONCRETE SLAB METAL DECK
(PERPENDICULAR TO FLUTES)
/8
/8
METAL DECK
(PARALLEL TO FLUTES)
1" 1"
/8
SLOTTED TOP
TRACK
2"x20 GA
STRAPS @ 16"
O.C.
STEEL BEAM
/8
20 GA Z-BARS
TO
ACCOMMODATE
SFRM
SPRAY-APPLIED
FIRE-RESISTIVE
MATERIAL
(SFRM)
SAB
GWB
ACOUSTICAL SEALANT
CUT ONE LAYER GWB TO
FOLLOW PROFILE OF DECKING.
SEAL CONTINUOUSLY WITH
ACOUSTICAL SEALANT.
FILL FLUTE VOID W/
SAB
GWB SOUND AND
SMOKE CLOSURE
STRIP SECURE TO
STRUCTURE AND SEAL
WITH ACOUSTICAL
SEALANT
ACOUSTICAL
SEALANT (BOTH
SIDES)
STUD
SAB
GWB
ACOUSTICAL SEALANT
(BOTH SIDES)
"SMOKE PARTITIONS AND SOUND-CONTROL WALLS"- ADDITIONAL NOTES:
1. UPGRADE TO DETAIL "B4" WHERE WALL IS DESIGNATED WITH A FIRE-RESISTANCE RATING.
2. FILL VOIDS WITH SOUND ATTENUATION BATTS (SAB).
3. SOUND WALLS AND SMOKE PARTITIONS REQUIRE THAT AT LEAST ONE LAYER OF GWB BE CUT TO FOLLOW UNDULATING SURFACES OF SUPERSTRUCTURES INCLUDING BUT NOT LIMITED TO FLUTES METAL DECKING. JOINT GWB TO SUPERSTRUCTURE WITH A CONTINUOUS BEAD OF ACOUSTICAL SEALANT.
4. BUILDING CODE REQUIRES THAT "SMOKE PARTITIONS" BE SEALED TO STRUCTURE AS INDICATED TO SUCCESSFULLY "….LIMIT THE PASSAGE OF SMOKE….".
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
TRIPLE C - The A/E Group
100 Pearl Street, 14th Floor
Hartford, CT 06103
MAT PERKINS
860-270-0753
A u to d e s k D o c s /3
C
R
.P ro je c t.
-2
-7
.E H
R M
.I U
.B e d fo rd
.M A
.R
/5
-2 -7
.B e d fo rd .E
H R
M .A
R C
H .B
R
.r v t
/2
/2
:5
:5
P
M
80A-512
ARCHITECTURAL PARTITION HEAD DETAILS 518-22-700
06/04/2025 M. Perkins K. McDermott
ISSUED FOR
CONSTRUCTION
EHRM INFRASTRUCTURE
UPGRADES
200 Springs Rd, Bedford, MA 01730
3" = 1'-0" B4
HEAD-OF-WALL CONDITIONS - STUD WALLS - FIRE RATED WALLS
3" = 1'-0" E5
HEAD-OF-WALL CONDITIONS - STUD WALLS - SMOKE PARTITIONS AND SOUND CONTROL WALLS
NOTE:
STANDARD DETAILS APPLY TO TYPICAL CONSTRUCTION
TYPES AND ASSEMBLIES. NOT ALL DETAILS MAY BE
USED. CONTRACTOR SHALL VERIFY ACTUAL CONDITIONS
ON-SITE.
Number Revisions: Date:
1 Addendum 1 2/25/2026
SHEET SYMBOL LEGEND
EXISTING CONSTRUCTION TO REMAIN
EXISTING CONSTRUCTION TO BE DEMOLISHED
NEW CONSTRUCTION, WITH PARTITION TYPE
GENERAL INTERIOR NOTES
KEYNOTES
GENERAL FINISH NOTES:
1. REFER TO SPECIFICATIONS FOR ADDITIONAL MATERIAL AND
INSTALLATION REQUIREMENTS.
2. REFER TO THIS SHEET FOR FINISH LEGEND AND ROOM FINISH
SCHEDULE.
3. IF POSSIBLE PROVIDE MATERIALS FROM SAME PRODUCTION RUN
FOR CONSISTENCY.
SUBSTITUTION NOTES:
1. COLOR IS AN IMPORTANT PART OF THIS PROJECT. ANY COLOR
SUBSTITUTION WILL REQUIRE APPROVAL BY THE COR.
TRANSITION NOTES:
1. INSTALL TRANSITIONS AT ALL DISSIMILAR FLOOR MATERIALS.
2. FOR ALL FLOOR FINISH AND PATTERN TRANSITIONS THAT OCCUR AT
DOORWAYS, TRANSITION MATERIALS AT CENTERLINE OF DOOR
WHEN DOOR PANEL IS IN THE CLOSED POSITION.
SIGNAGE NOTES:
1. REFER TO THIS SHEET SERIES SHEETS FOR SIGNAGE INFORMATION,
REFER TO SPECIFICATIONS FOR ADDITIONAL SIGNAGE,
IDENTIFICATION AND SYSTEMS/EQUIPMENT LABELING
REQUIREMENTS.
PAINTING NOTES:
1. ALL ADHESIVES AND PAINT TO BE LOW VOC/ODOR.
2. UNLESS OTHERWISE INDICATED, DO NOT PAINT FACTORY-FINISHED
ITEMS OR INSTALLER FINISHED ITEMS.
3. COORDINATE APPLICATIONS OF PAINTS AND ADHESIVES WITH COR.
PROVIDE SEALED ENVIRONMENT DURING HVAC FLUSH OUT PERIOD
TO ENSURE ODORS DO NOT TRANSMIT TO ADJACENT SPACES.
CODE NOTES:
1. ALL INTERIOR FINISHES SHALL HAVE FLAME SPREAD IN COMPLIANCE
WITH IBC 2024 803.13 INTERIOR WALL AND CEILING FINISH
REQUIREMENTS BY OCCUPANCY
INSTALLATION NOTES:
1. PROVIDE BACKING FOR ALL WALL MOUNTED EQUIPMENT.
MATERIAL FLOOR CHANGE (REFER TO THIS SHEET FOR DETAILS)
INTERIOR FINISH SYMBOLS
CONCRETE WITH STATIC DISSIPATIVE COATING (C-1/ SDC)
INTERIOR FINISHES
PAINT
FIELD
CALIFORNIA PAINTS*
TO MATCH BENJAMIN MOORE
MANCHESTER TAN HC-81
ARCHITECT/ENGINEERS:
INTERIOR FINISHES
Drawing Title
Approved: Project Director
Project Title
Location
Date Checked Drawn
NB KLM
Project Number
Board Number
Office of Construction and Facilities Management
*BASIS OF DESIGN
**MATCH EXISTING CAMPUS PAINT COLORS
EHRM INFRASTRUCTURE
UPGRADES
518-22-700
200 Springs Road, Bedford, MA 01730
EDITH NOURSE MEMORIAL VETERANS HOSPITAL
P-1
DIGITAL IMAGES MAY HAVE COLOR INACCURACIES, REFER
TO ACTUAL SAMPLE FOR TRUEST COLOR DEPICTION
PAINT
METAL DOORS & TRIM
CALIFORNIA PAINTS*
TO MATCH BENJAMIN MOORE
WHITE DOWN OC-131
P-2
WALL BASE
JOHNSONITE*
BEIGE 49
RB-1
PAPER INSERT CARRIER, MAGNETIC
MOUNT, WITH NON-GLARE LENS
TEXT: 5/8"H LASER-PRINTED TEXT,
HELVETICA MEDIUM
COLOR: TO MATCH STATION
STANDARDS
1-1/2" x 1/32" ADA
TACTILE NUMERALS
AND GRADE II BRAILLE234
9"
Restricted Access
5-3/16" X 9" CLEAR
ACETATE INSERT W/
COPY
9"X9" MAGNETICALLY
REMOVABLE SIGN
(ONE-PIECE)
RED SYMBOL AND
BLACK TEXT
1/2" 9" 1/2"
/2
/2
QUARTER-ROUND
SILVER FRAME
EXISTING FLOORING
TO BE REMOVED
TOP OF SLAB
EXISTING
FLOORING TO
REMAIN, EXISTING
ROOM SIDE EXISTING CONCRETE
FLOOR WITH STATIC
DISSIPATIVE (C-1/SDC)
RESILIENT BASE AS
SCHEDULED, EACH
SIDE OF NEW WALL
INSTALL 3/4"
PLYWOOD, MOUNT
BOTTOM OF
PLYWOOD 12" AFF
ADJACENT SPACE
TELECOM
ROOM SIDE
PARTITION AS SCHEDULED
EXISTING CONCRETE
FLOOR WITH STATIC
DISSIPATIVE (C-1/SDC)
LOCATION OF FLOOR
FINISH CHANGE;
SEAM OR ADAPTER
TRANSITION SHALL
OCCUR AT
CENTERLINE OF
DOOR IN CLOSED
POSITION
DOOR AS SCHEDULED
EXISTING FLOORING
TOP OF SLAB
CORRIDOR SIDE
DOOR FRAME BEYOND
C CENTER LINE OF DOORL
TRANSITION STRIP
(TR-1) OR EQUAL,
REFER TO SCHEDULE
FOR INFORMATION
TELECOM ROOM SIDE
SIGNAGE REFERENCES
VA SIGNAGE DESIGN MANUAL
SIGN VENDOR TO REFERENCE VA SIGNAGE DESIGN MANUAL FOR COMPLETE
SPECIFICATIONS
https://www.cfm.va.gov/til/spclRqmts.asp#SIGN
SIGN SYMBOL LEGEND
TELECOM ROOM FINISH DIAGRAM,
CONTRACTOR TO REFERENCE
ARCHITECTURE FOR ACTUAL WALL
CONSTRUCTION LOCATIONS
IN-08.02
IN-04.01A
IN-01.31
1 2 5 6
F1
80IN101
TYP.
F3
80IN101
TYP.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
TRIPLE C - The A/E Group
100 Pearl Street, 14th Floor
Hartford, CT 06103
MAT PERKINS
860-270-0753
A u to d e s k D o c s /3
C
R
.P ro je c t.
-2
-7
.E H
R M
.I U
.B e d fo rd
.M A
.R
/5
-2 -7
.B e d fo rd .E
H R
M .A
R C
H .B
R
.r v t
/2
/2
:5
:5
P
M
80IN101
INTERIOR FINISH PLAN, SIGNAGE & SCHEDULES 518-22-700
06/04/2025 M. Perkins K. McDermott
ISSUED FOR
CONSTRUCTION
EHRM INFRASTRUCTURE
UPGRADES
200 Springs Rd, Bedford, MA 01730
NTS
C1
COLOR BOARD
3" = 1'-0" D3
IN-04.01A SIGN DETAIL - PRIMARY ROOM
IDENTIFICATION
3" = 1'-0"
D1
IN-08.02 SIGN DETAIL - PROHIBIT
INSTRUCTIONAL AND CONTROL
NTS
D5
EXAMPLE OF EXISTING SIGNAGE
6" = 1'-0" F3
RESILIENT BASE (TOE BASE)
6" = 1'-0"
F1
THRESHOLD - CONCRETE TO EXISTING FLOORING
1 REMOVE EXISTING FLOORING, ADHESIVES, AND INSTALL NEW WALL
BASE
2 EXISTING WALLS ARE TO BE PATCHED AND PAINTED. SEE ROOM
FINISH SCHEDULE THIS SHEET FOR FINISHES.
3 ALL WALLS TO RECEIVE NEW PLYWOOD, COORDINATE WITH
ELECTRICAL DRAWINGS FOR FIXTURE LOCATIONS
4 PROVIDE NEW ROOM SIGNAGE, SEE SIGNAGE SCHEDULE THIS
SHEET
5 REFER TO ARCHITECTURAL PLANS FOR DETAILED ROOM
CONFIGURATION INFORMATION
6 TELECOM ROOM SPACE TO RECEIVE STATIC CONTROL CONCRETE
SEALER
REFER TO THIS SHEET FOR ROOM FINISH SCHEDULE & FINISH LEGEND
1/2" = 1'-0" F7
TYPICAL TELECOM ROOM FINISH DIAGRAM
3" = 1'-0" D6
IN-01.31 SIGN DETAIL - FIRE EQUIPMENT
IDENTIFICATION SIGN
ROOM FINISH SCHEDULE
LEVEL NO. NAME
FLOOR WALLS CEILING
NOTESFINISH BASE
NORTH EAST SOUTH WEST
MATERIAL FINISHMATERIAL FINISH MATERIAL FINISH MATERIAL FINISH MATERIAL FINISH
BASEMENT B04 OFFICE SPACE CUBICLES EXIST EXIST EXIST EXIST EXIST EXIST EXIST EXIST EXIST EXIST EXIST PATCH AND REPAIR AS NEEDED FOR DOOR
INSTALLATION, MATCH EXISTING FINISHES.
LEVEL 1 102 TELECOM ROOM C-1/SDC RB-1 GWB P-1/WD GWB P-1/WD GWB P-1/WD GWB P-1/WD OPEN
BUILDING SIGNAGE SCHEDULE
VERSIO
N TYPE COUNT DESCRIPTION DETAIL LOCATION REFERENCE
ADA
BRAILLE TEXT COLOR BACKGROUND COLOR
DIMENSIONS
CommentsSIGN_HEIGHT SIGN_WIDTH MOUNTING HEIGHT
IN-01.31 1 FIRE IDENTIFICATION SIGN D6 / 80IN101 FEC REFER TO PAGE 429 OF SIGNAGE DESIGN
MANUAL DATED 05/2023
NO WHITE RED 9" 9" 6' - 8" INSTALLED AT FIRE EXTINGUISHER CABINETS AT ALL NEW
TELECOM ROOMS
IN-04.01A 1 ROOM NUMBER IDENTIFICATION D3 / 80IN101 TELECOM ROOM REFER TO PAGE 259 OF SIGNAGE DESIGN
MANUAL DATED 05/2023
YES REFERENCE EXISTING
CAMPUS STANDARDS
REFERENCE EXISTING
CAMPUS STANDARDS
9" 9" 5' - 0" INSTALLED AT ALL NEW TELECOM ROOMS
IN-08.02 1 PROHIBIT INSTRUCTIONAL AND
CONTROL
D1/ 80IN101 TELECOM ROOM REFER TO PAGE 279 OF SIGNAGE DESIGN
MANUAL DATED 05/2023
NO REFERENCE EXISTING
CAMPUS STANDARDS
REFERENCE EXISTING
CAMPUS STANDARDS
9" 9" 5' - 9" INSTALLED AT ALL NEW TELECOM ROOMS MOUNTED DIRECTLY
ABOVE ROOM NAME SIGN
Grand total: 3
FINISH LEGEND
SYMBOL FINISH TYPE MANUFACTURER COLLECTION STYLE / TYPE COLOR SIZE SPEC SECTION NOTES
C-1/SDC SEALED CONCRETE WITH STATIC DISSIPATIVE COATING SEALED CONCRETE* - - - - - TELECOM ROOM SPACE TO RECEIVE STATIC CONTROL CONCRETE SEALER
P-1 PAINT CALIFORNIA PAINTS* - EGGSHELL TO MATCH BENJAMIN MOORE MANCHESTER TAN HC-81 - 09 91 00 FIELD
P-2 PAINT CALIFORNIA PAINTS* - SEMI-GLOSS TO MATCH BENJAMIN MOORE WHITE DOWN OC-131 - 09 91 00 METAL DOORS & TRIM
RB-1 RESILIENT BASE JOHNSONITE* TRADITIONAL TOE BASE BEIGE 49 4" 09 65 13
TR-1 TRIM SCHLUTER * - RENO-U SATIN ANODIZED ALUMINUM - 09 30 13 FLOOR TRANSITION
WD PLYWOOD FIRE TREATED PLYWOOD* - - HIGH GLOSS WHITE MPI (MASTER PAINTERS
INSTITUTE) 67 OR SIM
4' X 8' - PLYWOOD TO BE PAINTED WITH 2 COATS OF FIRE RESISTANT PAINT; ;FIRE RATING
STAMPS SHALL NOT BE PAINTED OVER
*Materials are approved as basis of design, all material substitutions are subject to owner approval. Contractor to provide VA Interior Design Department with samples of all specified finish materials. VA COR/ Interior Design department shall approve all finishes prior to installation.
Number Revisions: Date:
1 Addendum 1 2/25/2026
| Sheets |
| 80A-400 - ARCHITECTURAL ENLARGED VIEWS - BASEMENT LEVEL |
| 80A-401 - ARCHITECTURAL ENLARGED VIEWS - FIRST LEVEL |
| 80A-512 - ARCHITECTURAL PARTITION HEAD DETAILS |
| 80IN101 - INTERIOR FINISH PLAN, SIGNAGE & SCHEDULES |