This document is a Hazardous Material Abatement Plan (set of architectural and MEP drawings) for infrastructure upgrades at Edith Nourse Memorial Veterans Hospital in Bedford, Massachusetts. The project involves removal and abatement of asbestos-containing materials (ACM), lead-based paint (LBP), and associated contaminated materials from the first level of Building 18, with 160 square feet of lead-containing paint identified for abatement. The U.S. Department of Veterans Affairs (VA) is the federal agency overseeing the project under Project Number 518-22-700. TRIPLE C - The A/E Group serves as the Architect/Engineer of Record (100 Pearl Street, 14th Floor, Hartford, CT 06103).
The contract requires contractors to comply with all applicable federal, state, and local regulations including OSHA standards for silica dust control (29 CFR 1926.1153 and 29 CFR 1910.134), EPA requirements, and Massachusetts Department of Public Health and Environmental Conservation directives. All asbestos disturbance must be performed by a Massachusetts-licensed asbestos abatement contractor, and all lead-based paint disturbance by a Massachusetts-licensed lead abatement contractor. Key deliverables include: written standard operating procedures for worker and environmental protection; drawings indicating negative pressure equipment, airlocks, and decontamination chambers with air change calculations; daily debris removal with proper packaging and warning labels; waste shipment records provided within 35 days; and coordination with an industrial hygienist for final confirmation of abated areas. The contractor must maintain means of egress, provide containment barriers, coordinate phasing with the Contracting Officer Representative (COR), and restore any damaged building components to original condition at no additional cost to the VA.
View the file
Other files
Show 40 more
Latest 50 of 105 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
HAZARDOUS MATERIAL ABATEMENT GENERAL NOTES
1. ALL HAZARDOUS MATERIAL REMOVAL SHALL BE PERFORMED IN ACCORDANCE WITH THE PROJECT SPECIFICATIONS AND ALL APPLICABLE FEDERAL, STATE AND LOCAL LAWS, REGULATIONS, ORDERS AND
DIRECTIVES INCLUDING WITHOUT LIMITATIONS THOSE OF THE RESPONSIBLE STATE OF
MASSACHUSETTS AGENCIES, U.S. ENVIRONMENTAL PROTECTION AGENCY, U.S. DEPARTMENT OF
LABOR, OCCUPATIONAL SAFETY AND HEALTH ADMINISTRATION, NATIONAL INSTITUTE OF OCCUPATIONAL SAFETY AND HEALTH, STATE OF MASSACHUSETTS DEPARTMENT OF PUBLIC HEALTH, AND THE STATE OF
MASSACHUSETTS DEPARTMENT OF ENVIRONMENTAL CONSERVATION
2. CONTRACTOR SHALL COMPLY WITH OSHA REGULATIONS FOR SILICA DUST CONTROL 29 CFR 1926.1153, 29 CFR 1910.134
3. CONTRACTOR SHALL USE EXTREME CARE AND CAUTION DURING ALL ABATEMENT PROCEDURES.
CONTRACTOR SHALL CONDUCT REMOVAL OF ALL MATERIALS FROM THE SITE WITH A MINIMUM
DISTURBANCE AND PROVIDE REGULAR MAINTENANCE AND PROTECTION OF THE BUILDING PREMISES, STAGING AREA, TRANSPORTATION ROUTES, ETC, THROUGHOUT THE BUILDING. REFER TO THE ICRA PLANS FOR GUIDANCE ON PLANNED DEBRIS TRANSPORT PATHS. COORDINATE PHASING OF WORK AND HAZARDOUS MATERIAL CONTAINMENT PLANS WITH THE COR. COORDINATE USAGE OF STAIRS VS USAGE OF CHUTE FOR DISPOSAL OF REMOVED HAZARDOUS MATERIAL ON THE FIRST LEVEL. THE ABATEMENT
CONTRACTOR SHALL PREPARE THE WORK AREA FOR REMOVAL IN ACCORDANCE WITH APPLICABLE
REGULATIONS. WHERE OVERLAPS OCCUR, THE MOST STRINGENT REQUIREMENTS APPLY.
4. THE DISTURBANCE OF ANY ACM, OR SUSPECT ACM, SHALL BE PERFORMED BY A MAS LICENSED
ASBESTOS ABATEMENT CONTRACTOR.
5. THE DISTURBANCE OF ANY LEAD-BASED PAINT, OR SUSPECT LBP, SHALL BE PERFORMED BY A MAS LICENSED LEAD ABATEMENT CONTRACTOR. LEAD CONTAINING PAINT AND CONTAMINATED MATERIALS
SHALL BE REMOVED AND DISPOSED OF IN COMPLIANCE WITH EPA AND OSHA REGULATIONS.
6. CONTRACTOR TO MAINTAIN MEANS OF EGRESS PATHWAYS AT ALL TIMES. COORDINATE ALTERNATE PROVISIONS AND OBTAIN APPROVAL FROM OWNER AND AHJ IF EXISTING MEANS OF EGRESS MUST BE COMPROMISED OF MATERIAL EQUIPMENT, WASTE TRAILERS/DUMPSTERS, AS WELL AS CONTRACTOR PARKING SHALL BE COORDINATED WITH THE REST OF THE CONTRACT DOCUMENTS, THE GENERAL
CONTRACTOR, AND THE COR.
7. CONTRACTOR SHALL DEVELOP AND IMPLEMENT WRITTEN STANDARD OPERATING PROCEDURES FOR
ABATEMENT WORK TO ENSURE MAXIMUM PROTECTION AND SAFEGUARDS FOR LEAD AND/OR
ASBESTOS EXPOSURE TO WORKERS, PATIENTS, EMPLOYEES, GENERAL PUBLIC, AND THE
ENVIRONMENT.
8. THE LOCATIONS OF SITE STORAGE SHALL BE COORDINATED WITH THE VA COR.
9. CONTRACTOR SHALL PROVIDE ALL TOOLS, SCAFFOLDING, LADDERS, BARRIERS, AND ASSOCIATED
MATERIALS AND EQUIPMENT REQUIRED TO COMPLETE ALL WORK INDICATED IN THE CONTRACT
DOCUMENTS. THE OWNER OR THEIR REPRESENTATIVE SHALL NOT BE RESPONSIBLE FOR LOST,
DAMAGED OR STOLEN ITEMS.
10. CONTRACTOR SHALL PROVIDE ALL SIGNS, LABELS, WARNINGS, AND POSTED INSTRUCTIONS THAT ARE
NECESSARY TO PROTECT, INFORM, AND WARN OF THE HAZARD FROM ASBESTOS EXPOSURE.
11. CONTRACTOR SHALL POST IN A PROMINENT AND CONVENIENT PLACE FOR LABORERS, A COPY OF THE
LATEST APPLICABLE REGULATIONS FROM OSHA, EPA, NIOSH, MASDPH, AND THE MASDEC.
12. CONTRACTOR SHALL COMPLETELY PROTECT ALL CONTROLS, CONDUIT, TUBING, ELECTRICAL PANELS, EQUIPMENT, ETC, SCHEDULED TO REMAIN WITHIN THE WORK AREAS.
13. ALL BUILDING FINISHES, CONSTRUCTION EQUIPMENT, OR OTHER COMPONENTS OF THE BUILDING WHICH ARE SCHEDULED TO REMAIN, THAT ARE DAMAGED OR ARE IN ANY WAY DISRUPTED AS A RESULT OF THE EXECUTION OF THIS CONTRACT ARE TO BE REPLACED OR RESTORED TO ORIGINAL CONDITIONS
BY THE CONTRACTOR, WITHOUT ADDITIONAL COST TO THE OWNER.
14. THE VA AND THE HAZARDOUS MATERIAL ABATEMENT CONTRACTOR SHALL MUTUALLY AGREE ON THE NUMBER AND LOCATION OF ANY REMOTE DECONTAMINATION UNITS DURING THE PRE-CONSTRUCTION
MEETING. TWO RECOMMENDED LOCATIONS HAVE BEEN PROVIDED ON THE DRAWINGS.
15. SUBMIT DRAWINGS INDICATING THE LOCATION AND NUMBER OF HEPA FILTER EQUIPPED NEGATIVE
PRESSURE MACHINES, AIRLOCKS, AND DECONTAMINATION CHAMBERS. SUBMIT CALCULATIONS
SHOWING THE NUMBER OF AIR CHANGES FOR EACH CONTAINMENTS AREA.
16. PHASE WORK AS REQUIRED BY THE GENERAL CONTRACTOR AND VA. CONTRACTOR TO COORDINATE DEMOLITION ACTIVITIES WITH COR TO MAINTAIN FULL FUNCTIONALITY OF ADJACENT OCCUPIED SPACES.
THE GROUND LEVEL IS INTENDED TO REMAIN OPERATIONAL DURING THIS PROJECT. UTILIZE GLOVEBAG
METHODS ON THE GROUND LEVEL TO MINIMIZE IMPACT ON BUILDING OPERATIONS.
17. CONTRACTOR TO PROVIDE FIRE, SMOKE, DIRT, DUST AND NOISE CONTAINMENT BARRIERS BETWEEN WORK AREA AND ADJACENT OCCUPIED SPACES. COORDINATE WITH VA ICRA, ASBESTOS, AND LEAD
ABATEMENT REQUIREMENTS, AND THE COR.
18. CONTRACTOR TO COORDINATE ALL UTILITY SYSTEM SHUTDOWN ACTIVITIES IN ADVANCE WITH THE COR.
ALL OCCUPIED SPACES ADJACENT TO THE AREA OF WORK ARE TO REMAIN OPERATIONAL.
19. WORK OUTSIDE OF NORMAL HOURS MUST BE APPROVED BY THE COR.
20. THE ASBESTOS ABATEMENT CONTRACTOR AND THE MECHANICAL AND PLUMBING CONTRACTORS SHALL
BE RESPONSIBLE FOR DISMANTLING ANY HVAC EQUIPMENT AS NECESSARY TO GAIN ACCESS TO ACM
ON HVAC EQUIPMENT FOR PROPER REMOVAL AND DISPOSAL.
21. CONTRACTOR TO REMOVE ALL DEMOLITION AND CONSTRUCTION DEBRIS ON A DAILY BASIS.
COORDINATE MEANS, METHODS AND ROUTES WITH VA ASBESTOS AND ICRA REQUIREMENTS, AND THE COR. ALL REMOVED HAZARDOUS MATERIALS AND HAZARDOUS MATERIAL CONTAMINATED WASTE SHALL BE PROPERLY PACKAGED PRIOR TO REMOVAL FROM THE WORK AREAS. WARNING LABELS SHALL BE APPLIED TO ASBESTOS WASTE AS APPROPRIATE. ALL ACM OR LCP REMOVED SHALL BE ACCOMPANIED BY A WASTE SHIPMENT RECORDS. COMPLETED WASTE SHIPMENT RECORDS SHALL BE PROVIDED TO THE OWNER AS A PART OF THE CLOSEOUT DOCUMENTATION, ORIGINAL RECORDS SHALL BE PROVIDED
TO THE OWNER WITHIN 35 DAYS OF WASTE LEAVING THE SITE.
22. CONTRACTOR TO ASSUME THAT ALL UNTESTED ORIGINAL BUILDING MATERIALS TO CONTAIN ASBESTOS OR LEAD, UNLESS SAID MATERIAL IS TESTED AND CONFIRMED AS CONTAINING LESS THAN THE REGULATED PERCENTAGE OF ASBESTOS AND/OR LEAD. EXISTING ACM HAS BEEN CONFIRMED IN PIPE INSULATION AND FITTINGS, SPECIFIC ORIGINAL FLOORING MATERIALS, AND IN TRANSITE PANELS AT RADIATORS BELOW WINDOWS. NO ASBESTOS CONTENT HAS BEEN IDENTIFIED IN SAMPLING OF CEILING TILES, DRYWALL, JOINT COMPOUND, SKIM COAT, FIBERBOARD, FIRESTOP, COVE BASE, MASONRY WINDOW CAULK, BATHROOM CAULK, TILE GROUT, TILE GLUE, CERAMIC TILES, OR SPECIFIC FLOORING MATERIALS. LEAD CONTAINING PAINT HAS BEEN IDENTIFIED IN AT LEAST ONE AREA IN THE FACILITY.
SHOULD ANY PREVIOUSLY UNIDENTIFIED OR OTHERWISE UNANTICIPATED SUSPECT MATERIAL BE IDENTIFIED DURING CONSTRUCTION, STOP WORK AND NOTIFY OWNER FOR FURTHER DIRECTION.
UNDER NO CIRCUMSTANCES SHALL THE CONTRACTOR COLLECT OR ANALYZE BULK SAMPLES OF
SUSPECT MATERIALS WITHOUT THE APPROVAL OF THE OWNER.
23. ALL MATERIAL MEASUREMENTS, QUANTITIES, AND LOCATIONS ARE APPROXIMATE AND FOR GENERAL ORIENTATION ONLY. AS HIDDEN CONDITIONS ARE UNCOVERED, ADDITIONAL HAZARDOUS MATERIAL MAY
BE UNCOVERED THAT REQUIRE ABATEMENT. REFER TO SPECIFICATIONS FOR ADDITIONAL
INFORMATION.
24. COORDINATE WITH INDUSTRIAL HYGIENIST FOR REVIEW OF MONITORING, AND FINAL CONFIRMATION OF
ABATED AREAS, REFER TO SPEC SECTION 02 82 13.13
KEYNOTES#
QUANTITIES - ACM /LEAD MATERIALSLEGEND
REMOVAL PATH
SAMPLE
HA ## SAMPLE LOCATION
ASBESTOS /
LEAD PAINT
NOT ALL SAMPLE LOCATIONS SHOWN FOR CLARITY. ONLY
POSITIVE OR POSITIVE STOP SAMPLES ARE LOCATED.
SAMPLE NUMBER PER SURVEY REPORT FROM TERRACON.
REFER TO SURVEY REPORT FOR SPECIFIC SAMPLE
INFORMATION
PATH INDICATED IS PROVIDED FOR INTENT ONLY.
COORDINATE FINAL REMOVAL PATHWAYS, PHASING, AND
METHODS WITH GENERAL CONTRACTOR AND COR.
160 SF LEAD CONTAINING PAINT TO BE ABATED
SAMPLE
PNT ##
OFFICE
101101
LAB
102102
OFFICE
103103
TOILET
104104
OFFICE
105105
HAC
106106
Room 107107
CONFERENCE
RM
108108
OFFICE
109109
STORAGE
110110
TOILET
111111
OFFICE
112112
Room 113113
OFFICE
114114
LAB
115115
OFFICE
116116
Room
OFFICE
118118
Room
CORRIDOR
120120
CORRIDOR
121121
STAIR
122122
HAC
121B121B
STAIR
111B111B
TELECOM
111A111A
UTILITY
CLOSET
121A121A
CLOSET
108A108A
CORRIDOR
123123CLOSET
CLOSET
CLOSET
CLOSET
CLOSET
CLOSET
CLOSET
CLOSET
CLOSET
CLOSET
CLOSET
CLOSET
CLOSET
CLOSET
CLOSET
CLOSET
CLOSET
SAMPLE
PNT#219
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
TRIPLE C - The A/E Group
100 Pearl Street, 14th Floor
Hartford, CT 06103
MAT PERKINS
(860)270-0753
A u to d e s k D o c s /3
C
R
.P ro je c t.
-2
-7
.E H
R M
.I U
.B e d fo rd
.M A
.R
/5
-2 -7
.B e d fo rd .E
H R
M .A
R C
H .B
R
.r v t
/2
/2
:3
:0
P
M
18H-101
HAZARDOUS MATERIAL ABATEMENT PLAN -
FIRST LEVEL
518-22-700
06/04/2025 M PERKINS J SONES
ISSUED FOR
CONSTRUCTION
EHRM INFRASTRUCTURE
UPGRADES
200 Springs Rd, Bedford, MA 01730
1/8" = 1'-0" F3
HAZARDOUS MATERIAL ABATEMENT PLAN - FIRST LEVEL
1 PRIOR TO DEMO PROVIDE CONTAINMENT BARRIER AND PERSONNEL DECONTAMINATION FACILITY PER 02 82 11 DURING ABATEMENT WORK. COORDINATE TIMING WITH COR (48 HR MAX) TO MINIMIZE
DISRUPTION TO OCCUPIED SPACES.
2 ABATE AND REMOVE LEAD BASED PAINT THROUGHOUT ENTIRE ROOM. ASSUMED DOOR FRAMES ALSO CONTAIN LEAD BASED PAINT. DISPOSE OF FRAME PROPERLY WHERE FRAME IS BEING REMOVED.
WHERE FRAME IS TO REMAIN, ABATE AND REMOVE PAINT ON DOOR FRAME.
Number Revisions: Date:
1 Addendum 1 02/25/2026
02/25/2026
SHEET SYMBOL LEGEND
KEYNOTES
GENERAL NOTES
EXISTING CONSTRUCTION TO REMAIN
EXISTING CONSTRUCTION TO BE DEMOLISHED
NEW CONSTRUCTION, WITH PARTITION TYPE
A
A. SEE GENERAL NOTES AND PLANS FOR TYPICAL GENERAL PROJECT
REQUIREMENTS AND PROJECT LOCATION DRAWINGS.
B. SEE INTERIOR FINISH DRAWINGS FOR ADDITIONAL FINISHES
INFORMATION.
C. SEE MECHANICAL AND ELECTRICAL DRAWINGS FOR ADDITIONAL
SYSTEMS INFORMATION.
D. NEW TELECOM ROOMS SHALL BE 1 HOUR FIRE AND SMOKE RATED
AND COMPLY WITH THE LATEST VA PHYSICAL SECURITY STANDARDS,
AND CAMPUS STANDARDS.
E. SEE TYPICAL WALL FRAMING DETAILS ON SHEET A-511.
F. SEE TYPICAL HEAD OF WALL DETAIL ON SHEET A-512.
G. SEE TYPICAL CEILING DETAILS ON SHEET A-531
H. DATE OF THIS DRAWING SET. CONTRACTOR SHALL FIELD VERIFY ALL
DIMENSIONS, CONDITIONS, AND SITE-SPECIFIC INFORMATION AT THE
TIME OF BIDDING.
I. CONTRACTOR IS RESPONSIBLE FOR ALL COSTS ASSOCIATED
WITH MOVING, STORING AND RETURNING FURNISHINGS AND
EQUIPMENT TO THE PROPOSED WORK AREA(S). ANY
DISASSEMBLY AND REASSEMBLY OF SYSTEMS FURNITURE IN THE
PROPOSED WORK AREAS IS THE RESPONSIBILITY OF THE
CONTRACTOR AND MUST FOLLOW THE MANUFACTURER'S
WARRANTY.
PARTITION RATING GRAPHICS:
4 HR FIRE BARRIER
3 HR FIRE BARRIER
2 HR FIRE & SMOKE BARRIER
2 HR FIRE BARRIER
2 HR FIRE BARRIER/SHAFT
1 HR FIRE & SMOKE BARRIER
1 HR FIRE BARRIER
1 HR FIRE BARRIER/SHAFT
SMOKE PARTITION (NON RATED)
NON RATED
PARTITION RATING GRAPHIC DESIGNATION: PRIORITY
1 HIGHEST
5 LOWEST
PARTITIONS REQUIRED TO BE SMOKE RESISTANT, FIRE
RESISTANT, OR BOTH FIRE AND SMOKE RESISTANT ARE SHOWN
GRAPHICALLY ON PLANS WITH HATCH PATTERNS.
B
C
7 8
CORRIDOR
121121
3'-7 1/2"
3' -0
/2
3' -0
/2
3'-6"
10 10
B
C
7 8
E X
IS
T
V
IF
'-1
1/
2"
EXIST (VIF)
11'-8 1/2"
TELECOM
ROOM
168 SF
H W
-S H
-3 F
CORRIDOR
121121
B B
B
B
B
B
B
B B
B
B
BJ2
18A-401
B8
TELECOM
ROOM
110110
STORAGE
151 SF
ACOUSTICAL OR RATED
FLEXIBLE SEALANT
FLOOR LINE
ADD ONE LAYER OF 5/8" GWB,
ONE-SIDE WITH APPROVED UL
SETTING COMPOUND BETWEEN
LAYERS AND FASTENED TO
WALL AS REQUIRED, AT
EXISTING GWB WALL
ASSEMBLIES
STRUCTURAL DECK
EXISTING METAL STUDS AND
BATT INSULATION TO REMAIN
A/C GRADE, 3/4" FIRE-TREATED
PLYWOOD, ADHERED TO CONCRETE
AT EXISTING CONCRETE WALL
ASSEMBLIES
BOTTOM OF PLYWOOD
TO BE AT 12" AFF
UL DESIGN V497
1-HOUR PARTITION RATED FROM BOTH SIDES
EXISTING GWB OR
CONCRETE WALL
ASSEMBLY, WHERE OCCURS
SIDE OF
EXISTING
ROOM OR
CORRIDOR TO
REMAIN
18A-512
E5
18A-512
B4
1/2" 1/2"
VARIES
SEE PLAN
WALL - SEE PLAN
FOR TYPE
SEALANT - EA. SIDE
& ALL AROUND,
TYP.
HOLLOW METAL
FRAME
/2
V
A R
IE
S
S E
E P
L A
N
/2
UNO
4" 2"
ADJACENT WALL
WHERE OCCURS
SEALANT - EA SIDE &
ALL AROUND, TYP.
HOLLOW METAL FRAME
WALL - SEE PLAN
FOR TYPE
B4
TYPICAL FRAME
H E
IG
H
T
2" WIDTH 2"
C4
FRAME TYPE ELEVATIONS DOOR TYPE ELEVATIONS
F
FLUSH
B
C
7 8
TELECOM
ROOM
168 SF
STORAGE
110110
LINE OF
STRUCTURE
LINE OF
STRUCTURE
09 29 00
SOUND ATTENUATION BATTS
(SAB), WHERE OCCURS
NOTE:
IF PARTITION TYPE IS USED IN A
CHASE WALL CONDITION, PROVIDE
CROSS BRACING GUSSETS AT 48"
O.C. MAX VERTICALLY. FABRICATED
FROM 6" MTL STUDS.
6”
09 29 00
5/8" GWB
09 29 00
SAB RETAINER STRAP
WHERE SAB OCCURS
CEILING
07 92 00
SEALANT
09 22 16
METAL STUDS
18A-512
B4 18A-512
E5
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
TRIPLE C - The A/E Group
100 Pearl Street, 14th Floor
Hartford, CT 06103
MAT PERKINS
(860)270-0753
A u to d e s k D o c s /3
C
R
.P ro je c t.
-2
-7
.E H
R M
.I U
.B e d fo rd
.M A
.R
/5
-2 -7
.B e d fo rd .E
H R
M .A
R C
H .B
R
.r v t
/2
/2
:5
:1
A
M
18A-401
ARCHITECTURAL ENLARGED VIEWS - FIRST
LEVEL
518-22-700
06/04/2025 M. Perkins K. McDermott
ISSUED FOR
CONSTRUCTION
EHRM INFRASTRUCTURE
UPGRADES
200 Springs Rd, Bedford, MA 01730
1 REMOVE EXISTING FLOORING, ADHESIVES, AND WALL BASE
2 REMOVE EXISTING DOOR AND FRAME
3 NEW 45 MIN. FIRE RATED DOOR AND FRAME. SEE DOOR SCHEDULE
AND SPECIFICATIONS FOR ADDITIONAL INFORMATION. MODIFY DOOR
AS REQUIRED FOR NEW ACCESS CONTROL HARDWARE.
4 PROVIDE NEW FIRE EXTINGUISHER CABINET WITH A TYPE 2A: 10B: C
CLEAN AGENT FIRE EXTINGUISHER LOCATED NO GREATER THAN 75
FEET AWAY FROM THE NEW TR. CONTRACTOR TO COORDINATE THE
NEW LOCATION WITH THE COR. CONTRACTOR SHALL BID A NEW FEC
FOR EACH TR IN THE SCOPE
5 PROVIDE TEMPORARY DUST TIGHT BARRIER AROUND WORK AREA
DURING ACTIVITIES WHICH PRODUCE DUST
6 REMOVE EXISTING CEILING AND LIGHTS. MODIFY AND/OR PROVIDE
ADDITIONAL SUPPORTS AS REQUIRED FOR EXISTING CEILING ITEMS
TO REMAIN.
7 NEW FURRING WALL AT EXTERIOR WALL TO ENCLOSE WINDOW.
MAINTAIN 1/2" GAP BETWEEN EXISTING WALL INTERIOR FACE AND
NEW STUDS. MODIFY/ REMOVE INTERIOR WINDOW TRIM AS
REQUIRED. INSTALL WINDOW FILM AT ALL FURRED WINDOWS. SEE
18IN101 FOR MORE INFORMATION.
8 EXISTING WALL TO BECOME 1 HOUR FIRE AND SMOKE-RATED. PATCH
AND SEAL ALL PENETRATIONS AS NECESSARY.
9 OPEN TO DECK
10 DEMO EXISTING WALL AND FRAMING AS SHOWN ON PLAN
11 POTENTIAL ABATEMENT AT FLOOR FOR FLOOR PENETRATIONS.
REFER TO COVER SHEET FOR KNOWN ACM ITEMS WITHIN THIS
BUILDING.
1/4" = 1'-0" D8
ARCHITECTURAL FLOOR PLAN - FIRST LEVEL
- RM 110 - DEMO
1/4" = 1'-0" B8
ARCHITECTURAL FLOOR PLAN - FIRST LEVEL
- RM 110 - NEW
1/16" = 1'-0" F6
FIRST LEVEL REFERENCE PLAN
NOTE: FIRE RESISTANCE TEST FOR TWO HOUR RATED WALLS: UL
V438, UL U411
(TYPE B) TYPICAL PARTITION
MARK STUD WIDTH PRTN WIDTH DESIGN STC
B 2 1/2" 3/4" 45
DOOR AND FRAME SCHEDULE
IDENTIFICATION DIMENSIONS PANEL FRAME DETAIL
FIRE RATING
HARDWARE
NOTESLEVEL ROOM NO. ROOM NAME DOOR NO. W1 H T TYPE MATERIAL FINISH GLAZING UNDERCUT TYPE MATERIAL FINISH HEAD JAMB SILL GROUP ELECTRICAL
LEVEL 1 110 TELECOM ROOM 110 3' - 0" 7' - 0" 1 3/4" F HM P-2 NONE 3/8" 1 HM P-2 B4/18A-401 C4/18A-401 F1/18IN101 45 MIN. HW-SH-3F SEE SPEC 1
1. SEE SPECIFICATIONS 08 71 00 FOR DOOR HARDWARE REQUIREMENTS. COORDINATE WITH ELECTRICAL.
3" = 1'-0" B4
HOLLOW METAL HEAD DETAIL
3" = 1'-0" C4
HOLLOW METAL JAMB DETAIL
1/4" = 1'-0" D4
DOOR AND FRAME TYPES ELEVATIONS
1/4" = 1'-0" B6
ARCHITECTURAL REFLECTED CEILING PLAN -
FIRST LEVEL - RM 110 - NEW
1/4" = 1'-0" D6
ARCHITECTURAL REFLECTED CEILING PLAN -
FIRST LEVEL - RM 110 - DEMO
NOT TO SCALE
F5
EXISTING CONDITIONS 110
Number Revisions: Date:
1 Addendum 1 02/25/2026
(TYPE J) NON-RATED PARTITION
MARK STUD WIDTH PRTN WIDTH DESIGN STC
J2 2 1/2" 3 1/8" -
SHEET SYMBOL LEGEND
EXISTING CONSTRUCTION TO REMAIN
EXISTING CONSTRUCTION TO BE DEMOLISHED
NEW CONSTRUCTION, WITH PARTITION TYPE
GENERAL INTERIOR NOTES
KEYNOTES
GENERAL FINISH NOTES:
1. REFER TO SPECIFICATIONS FOR ADDITIONAL MATERIAL AND
INSTALLATION REQUIREMENTS.
2. REFER TO THIS SHEET FOR FINISH LEGEND AND ROOM FINISH
SCHEDULE.
3. IF POSSIBLE PROVIDE MATERIALS FROM SAME PRODUCTION RUN
FOR CONSISTENCY.
SUBSTITUTION NOTES:
1. COLOR IS AN IMPORTANT PART OF THIS PROJECT. ANY COLOR
SUBSTITUTION WILL REQUIRE APPROVAL BY THE COR.
TRANSITION NOTES:
1. INSTALL TRANSITIONS AT ALL DISSIMILAR FLOOR MATERIALS.
2. FOR ALL FLOOR FINISH AND PATTERN TRANSITIONS THAT OCCUR AT
DOORWAYS, TRANSITION MATERIALS AT CENTERLINE OF DOOR
WHEN DOOR PANEL IS IN THE CLOSED POSITION.
SIGNAGE NOTES:
1. REFER TO THIS SHEET SERIES SHEETS FOR SIGNAGE INFORMATION,
REFER TO SPECIFICATIONS FOR ADDITIONAL SIGNAGE,
IDENTIFICATION AND SYSTEMS/EQUIPMENT LABELING
REQUIREMENTS.
PAINTING NOTES:
1. ALL ADHESIVES AND PAINT TO BE LOW VOC/ODOR.
2. UNLESS OTHERWISE INDICATED, DO NOT PAINT FACTORY-FINISHED
ITEMS OR INSTALLER FINISHED ITEMS.
3. COORDINATE APPLICATIONS OF PAINTS AND ADHESIVES WITH COR.
PROVIDE SEALED ENVIRONMENT DURING HVAC FLUSH OUT PERIOD
TO ENSURE ODORS DO NOT TRANSMIT TO ADJACENT SPACES.
CODE NOTES:
1. ALL INTERIOR FINISHES SHALL HAVE FLAME SPREAD IN COMPLIANCE
WITH IBC 2024 803.13 INTERIOR WALL AND CEILING FINISH
REQUIREMENTS BY OCCUPANCY
INSTALLATION NOTES:
1. PROVIDE BACKING FOR ALL WALL MOUNTED EQUIPMENT.
MATERIAL FLOOR CHANGE (REFER TO THIS SHEET FOR DETAILS)
INTERIOR FINISH SYMBOLS
SEALED CONCRETE WITH STATIC DISSIPATIVE COATING (C-1/SDC)
INTERIOR FINISHES
PAINT
FIELD
CALIFORNIA PAINTS*
TO MATCH BENJAMIN MOORE
MANCHESTER TAN HC-81
ARCHITECT/ENGINEERS:
INTERIOR FINISHES
Drawing Title
Approved: Project Director
Project Title
Location
Date Checked Drawn
NB KLM
Project Number
Board Number
Office of Construction and Facilities Management
*BASIS OF DESIGN
**MATCH EXISTING CAMPUS PAINT COLORS
EHRM INFRASTRUCTURE
UPGRADES
518-22-700
200 Springs Road, Bedford, MA 01730
EDITH NOURSE MEMORIAL VETERANS HOSPITAL
P-1
DIGITAL IMAGES MAY HAVE COLOR INACCURACIES, REFER
TO ACTUAL SAMPLE FOR TRUEST COLOR DEPICTION
PAINT
METAL DOORS & TRIM
CALIFORNIA PAINTS*
TO MATCH BENJAMIN MOORE
WHITE DOWN OC-131
P-2
WALL BASE
JOHNSONITE*
BEIGE 49
RB-1
PAPER INSERT CARRIER, MAGNETIC
MOUNT, WITH NON-GLARE LENS
TEXT: 5/8"H LASER-PRINTED TEXT,
HELVETICA MEDIUM
COLOR: TO MATCH STATION
STANDARDS
1-1/2" x 1/32" ADA
TACTILE NUMERALS
AND GRADE II BRAILLE234
9"
Restricted Access
5-3/16" X 9" CLEAR
ACETATE INSERT W/
COPY
9"X9" MAGNETICALLY
REMOVABLE SIGN
(ONE-PIECE)
RED SYMBOL AND
BLACK TEXT
1/2" 9" 1/2"
/2
/2
QUARTER-ROUND
SILVER FRAME
EXISTING FLOORING
TO BE REMOVED
TOP OF SLAB
EXISTING
FLOORING TO
REMAIN, EXISTING
ROOM SIDE EXISTING CONCRETE
FLOOR WITH STATIC
DISSIPATIVE (C-1/SDC)
RESILIENT BASE AS
SCHEDULED, EACH
SIDE OF NEW WALL
INSTALL 3/4"
PLYWOOD, MOUNT
BOTTOM OF
PLYWOOD 12" AFF
ADJACENT SPACE
TELECOM
ROOM SIDE
PARTITION AS SCHEDULED
EXISTING CONCRETE
FLOOR WITH STATIC
DISSIPATIVE
(C-1/SDC)
LOCATION OF FLOOR
FINISH CHANGE;
SEAM OR ADAPTER
TRANSITION SHALL
OCCUR AT
CENTERLINE OF
DOOR IN CLOSED
POSITION
DOOR AS SCHEDULED
EXISTING FLOORING
TOP OF SLAB
CORRIDOR SIDE
DOOR FRAME BEYOND
C CENTER LINE OF DOORL
TRANSITION STRIP
(TR-1) OR EQUAL,
REFER TO SCHEDULE
FOR INFORMATION
TELECOM ROOM SIDE
SIGNAGE REFERENCES
VA SIGNAGE DESIGN MANUAL
SIGN VENDOR TO REFERENCE VA SIGNAGE DESIGN MANUAL FOR COMPLETE
SPECIFICATIONS
https://www.cfm.va.gov/til/spclRqmts.asp#SIGN
SIGN SYMBOL LEGEND
IN-08.02
IN-01.31
1 2 5 6
TELECOM ROOM FINISH DIAGRAM,
CONTRACTOR TO REFERENCE
ARCHITECTURE FOR ACTUAL WALL
CONSTRUCTION LOCATIONS
F1
18IN101
TYP.
F4
18IN101
TYP.
IN-04.01A
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
TRIPLE C - The A/E Group
100 Pearl Street, 14th Floor
Hartford, CT 06103
MAT PERKINS
(860)270-0753
A u to d e s k D o c s /3
C
R
.P ro je c t.
-2
-7
.E H
R M
.I U
.B e d fo rd
.M A
.R
/5
-2 -7
.B e d fo rd .E
H R
M .A
R C
H .B
R
.r v t
/2
/2
:5
:1
A
M
18IN101
INTERIOR FINISH PLAN, SIGNAGE & SCHEDULES 518-22-700
06/04/2025 M. Perkins K. McDermott
ISSUED FOR
CONSTRUCTION
EHRM INFRASTRUCTURE
UPGRADES
200 Springs Rd, Bedford, MA 01730
NTS
C1
COLOR BOARD
3" = 1'-0" D3
IN-04.03D SIGN DETAIL - PRIMARY ROOM
IDENTIFICATION
3" = 1'-0"
D1
IN-08.02 SIGN DETAIL - PROHIBIT
INSTRUCTIONAL AND CONTROL
NTS
C4
EXAMPLE OF EXISTING SIGNAGE
6" = 1'-0" F4
RESILIENT BASE (TOE BASE)
6" = 1'-0"
F1
THRESHOLD - CONCRETE TO EXISTING FLOORING
1 REMOVE EXISTING FLOORING, ADHESIVES, AND INSTALL NEW WALL
BASE
2 EXISTING WALLS ARE TO BE PATCHED AND PAINTED. SEE ROOM
FINISH SCHEDULE THIS SHEET FOR FINISHES.
3 ALL WALLS TO RECEIVE NEW PLYWOOD, COORDINATE WITH
ELECTRICAL DRAWINGS FOR FIXTURE LOCATIONS
4 PROVIDE NEW ROOM SIGNAGE, SEE SIGNAGE SCHEDULE THIS
SHEET
5 REFER TO ARCHITECTURAL PLANS FOR DETAILED ROOM
CONFIGURATION INFORMATION
6 TELECOM ROOM SPACE TO RECEIVE STATIC CONTROL CONCRETE
SEALER
REFER TO THIS SHEET FOR ROOM FINISH SCHEDULE & FINISH LEGEND
3" = 1'-0" D5
IN-01.31 SIGN DETAIL - FIRE EQUIPMENT
IDENTIFICATION SIGN
ROOM FINISH SCHEDULE
LEVEL NO. NAME
FLOOR WALLS CEILING
NOTESFINISH BASE
NORTH EAST SOUTH WEST
MATERIAL FINISHMATERIAL FINISH MATERIAL FINISH MATERIAL FINISH MATERIAL FINISH
LEVEL 1 110 TELECOM ROOM C-1/ SDC RB-1 GWB P-1/WD GWB P-1/WD GWB P-1/WD GWB P-1/WD GWB
BUILDING SIGNAGE SCHEDULE
VERSIO
N TYPE COUNT DESCRIPTION DETAIL LOCATION REFERENCE
ADA
BRAILLE TEXT COLOR BACKGROUND COLOR
DIMENSIONS
CommentsSIGN_HEIGHT SIGN_WIDTH MOUNTING HEIGHT
IN-01.31 1 FIRE IDENTIFICATION SIGN D5 / IN101 FEC REFER TO PAGE 429 OF SIGNAGE DESIGN
MANUAL DATED 05/2023
NO WHITE RED 9" 9" 6' - 8" INSTALLED AT FIRE EXTINGUISHER CABINETS AT ALL
NEW TELECOM ROOMS
IN-04.01A 1 ROOM NUMBER IDENTIFICATION D3 / IN101 TELECOM ROOM REFER TO PAGE 261 OF SIGNAGE DESIGN
MANUAL DATED 05/2023
NO REFERENCE EXISTING
CAMPUS STANDARDS
REFERENCE EXISTING
CAMPUS STANDARDS
9" 9" 5' - 0" INSTALLED AT ALL NEW TELECOM ROOMS MOUNTED
DIRECTLY ABOVE ROOM NAME SIGN
IN-08.02 1 PROHIBIT INSTRUCTIONAL AND
CONTROL
D1 / IN101 TELECOM ROOM REFER TO PAGE 279 OF SIGNAGE DESIGN
MANUAL DATED 05/2023
NO REFERENCE EXISTING
CAMPUS STANDARDS
REFERENCE EXISTING
CAMPUS STANDARDS
9" 9" 5' - 9" INSTALLED AT ALL NEW TELECOM ROOMS MOUNTED
DIRECTLY ABOVE ROOM NAME SIGN
Grand total: 3
FINISH LEGEND
SYMBOL FINISH TYPE MANUFACTURER COLLECTION STYLE / TYPE COLOR SIZE SPEC SECTION NOTES
C-1/ SDC SEALED CONCRETE WITH STATIC DISSIPATIVE COATING SEALED CONCRETE* - - - - - TELECOM ROOM SPACE TO RECEIVE STATIC CONTROL CONCRETE SEALER
F-1 FILM 3M* FASARA 7725SE-324 FROSTED CRYSTAL - 08 87 33 WINDOW FILM
P-1 PAINT CALIFIRNIA PAINTS* - EGGSHELL TO MATCH BENJAMIN MOORE MANCHESTER TAN HC-81 - 09 91 00 FIELD
P-2 PAINT CALIFORNIA PAINTS* - SEMI-GLOSS TO MATCH BENJAMIN MOORE WHITE DOWN OC-131 - 09 91 00 METAL DOORS & TRIM
RB-1 RESILIENT BASE JOHNSONITE* TRADITIONAL TOE BASE BEIGE 49 4" 09 65 13
TR-1 TRIM SCHLUTER * - RENO-U SATIN ANODIZED ALUMINUM - 09 30 13 FLOOR TRANSITION
WD PLYWOOD FIRE TREATED PLYWOOD* - - HIGH GLOSS WHITE MPI (MASTER PAINTERS INSTITUTE) 67
OR SIM
4' X 8' - PLYWOOD TO BE PAINTED WITH 2 COATS OF FIRE RESISTANT PAINT; FIRE
RATING STAMPS SHALL NOT BE PAINTED OVER
*Materials are approved as basis of design, all material substitutions are subject to owner approval. Contractor to provide VA Interior Design Department with samples of all specified finish materials. VA COR/ Interior Design department shall approve all finishes prior to installation.
1/2" = 1'-0" F7
TYPICAL TELECOM ROOM FINISH DIAGRAM
Number Revisions: Date:
1 Addendum 1 02/25/2026
DN DN
DN
DN
UP
WALL SYMBOL LEGEND
EXISTING CONSTRUCTION TO REMAIN
SMOKE AND 1-HR RATED FIRE
BARRIER AND OPENINGS
SMOKE AND 2-HR RATED FIRE BARRIER
AND OPENINGS
SMOKE BARRIER AND OPENINGS
1 HR RATED FIRE BARRIER AND
OPENINGS
2 HR RATED FIRE BARRIER AND OPENINGS
CONTRACTOR SHALL CONFIRM ALL FIRE RATED WALL ASSEMBLIES
OFFICE
LAB
OFFICE
TOILET
OFFICE
HAC
Room
CONFERENCE RM
OFFICE
TELECOM ROOM
TOILET
OFFICE
Room
OFFICE
LAB
OFFICE
CLOSET
113A
OFFICE
CLOSET
113B
CORRIDOR
CORRIDOR
STAIR
HAC
121B
STAIR
111B
EXISTING TE
111B
UTILITY CLOSET
121A
CLOSET
108A
CORRIDOR
CLOSET
107A
CLOSET
105B
CLOSET
105A
CLOSET
103B
CLOSET
103A
CLOSET
101B
CLOSET
101A
CLOSET
112B
CLOSET
112A
CLOSET
114B
CLOSET
114A
CLOSET
116B
CLOSET
116A
CLOSET
118B
CLOSET
118A
18FX101
C7
18FX101
C4
CORRIDOR
STAIR
STAIR
STAIR
OFFICE
CLOSET
112B
TELECOM ROOM
168 SF
5' - 5"
2 8
2 7
STORAGE
151 SF
CORRIDOR
OFFICE
CLOSET
CLOSET
CLOSET
STAIR
STAIR
STAIR
TN
PN
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
CONSULTANT
321 4 5 6 7 8 9 10
GENERAL NOTES
KEYNOTES
TRIPLE C - The A/E Group
100 Pearl Street, 14th Floor
Hartford, CT 06103
MAT PERKINS
860-270-0753
STAMP
mat.perkins@triplecaeg.com
A u to d e s k D o c s /3
C
R
.P ro je c t.
-2
-7
.E H
R M
.I U
.B e d fo rd .M
A .R
/5
-2
-7
.B e d fo rd
.E H
R M
.M E
P .B
R
.r v t
/2
/2
:5
:3
A
M
18FX101
FIRE PROTECTION PLAN - FIRST LEVEL 518-22-700
06/04/2025 M. Perkins N.Harper
ISSUED FOR
CONSTRUCTION
EHRM INFRASTRUCTURE
UPGRADES
200 Springs Rd, Bedford, MA 01730
SCALE: 1/8" = 1'-0"
F4
FIRE PROTECTION PLAN - FIRST
LEVEL
SPRINKLER HEAD LEGEND
SYM.
DEMO
TYPE
QUICK
RESPONSE
TEMP "K"
DEMO
QUANTITY
PENDENT
YES 170F 5.6UPRIGHT
YES 155F 5.6
NOTE: LEGEND INFORMATION IS SPECIFIC TO THIS SHEET ONLY
NEW
QUANTITY
SYM.
NEW
+1
SCALE: 1/2" = 1'-0"
C7
FIRE PROTECTION ENLARGED PLAN
FIRST LEVEL - 111A NEW
SCALE: 1/2" = 1'-0"
C4
FIRE PROTECTION ENLARGED PLAN
FIRST LEVEL - 110 DEMO
CONTRACTOR SHALL PROVIDE THE FOLLOWING PRIOR TO
COMMENCEMENT OF WORK FOR REVIEW AND APPROVAL:
A. SHOP DRAWING IDENTIFYING MAIN PIPE SIZES AND LOCATIONS,
LOCATION OF PIPE BRACING, HANGERS AND SPRINKLER HEADS
AND DETAILS
B. CUT SHEETS AND SUBMITTAL FOR ALL PIPING, FITTINGS,
SPRINKLER HEADS, HANGERS AND SUPPORT ATTACHMENTS
A. EXISTING CONDITIONS ARE BASED ON EXISTING PLANS AND FIELD VERIFICATION
WHERE FEASIBLE. ACTUAL CONDITIONS MAY DIFFER FROM THOSE INDICATED.
CONTRACTOR SHALL FIELD VERIFY IN ADVANCE THE LOCATION AND CONDITION
OF THE EXISTING SYSTEMS SHOWN TO BE MODIFIED OR REMOVED. CONTRACTOR
TO NOTIFY ARCHITECT SHOULD CONDITIONS BE FOUND TO DIFFER SIGNIFICANTLY
FROM THE CONSTRUCTION DOCUMENTS.
B. A DETAILED SCHEDULE, INCLUDING PROJECTED SERVICE INTERRUPTION DATES
WITH DURATIONS, AND DETAILED PHASING PLAN IS TO BE PROVIDED TO THE COR
PRIOR TO THE START OF WORK. THIS SUBMITTAL MUST BE ACCEPTED BY THE
COR PRIOR TO THE START OF WORK.
C. REFER TO ARCHITECTURAL DRAWINGS FOR EXACT DIMENSIONAL DATA, CEILING
HEIGHTS, AND SQUARE FOOTAGE.
D. CONTRACTOR SHALL COORDINATE ALL WORK WITH BUILDING OWNER AND
OTHER TRADES PRIOR TO CONSTRUCTION.
E. ALL PIPING TO BE ROUTED WITHIN CEILING SPACE OR CONCEALED IN FURRED
CHASES UNLESS NOTED OTHERWISE.
F. ALL AREAS ARE DESIGNED AS ORDINARY HAZARD GROUP 1 OCCUPANCY UNLESS
NOTED OTHERWISE ON PLAN.
G. ALL SPRINKLER SYSTEMS SHALL BE INSTALLED IN ACCORDANCE WITH THE 2025
NFPA 13.
H. ALL MATERIALS, DEVICES, HANGERS AND SUPPORTS SHALL BE NEW AND UL
LISTED FOR USE IN FIRE PROTECTION SYSTEMS.
I. ALL NEW SPRINKLERS SHALL BE PROVIDED WITH NEW ESCUTCHEONS TO MATCH
EXISTING BUILDING STANDARDS.
J. INSTALL QUICK RESPONSE SPRINKLERS (QRS) IN ALL AREAS, EXCEPT WHERE
SPECIFICALLY PROHIBITED AS DEFINED BY 2025 NFPA 13.
K. PIPING TO BE SCHEDULE 40 BLACK STEEL WITH CAST IRON FITTINGS.
L. ANY FLOOR, WALL, OR CEILING CUTTING OR FILLING THAT IS REQUIRED TO
COMPLETE THIS PROJECT, THE CONTRACTOR SHALL PATCH AND PAINT AND
RETURN TO MATCH EXISTING CONDITIONS AND FINISHES.
M. CONTRACTOR TO PROVIDE GALVANIC PROTECTION AS REQUIRED AT
CONNECTIONS BETWEEN ALL DISSIMILAR METALS.
N. CONTRACTOR TO VALIDATE AND VERIFY ALL FIRE RATED AND/OR SMOKE RATED
WALLS AND ASSEMBLIES INDICATED ON PLANS IN WORK AREA. PROVIDE ALL
PIPING PENETRATIONS OF FIRE, SMOKE AND FULL HEIGHT WALLS SHALL BE
CAULKED AIRTIGHT TO THE ADJACENT STRUCTURE BY MEANS OF U.L. APPROVED
FIREPROOF CAULKING MATERIAL.
O. ALL NEW PIPES TO BE CLEANED AND TESTED PRIOR TO COMMISSIONING.
P. THE SPRINKLER CONTRACTOR SHALL COORDINATE AND PERFORM ALL FIRE
PROTECTION WORK IN ACCORDANCE WITH VA REQUIREMENTS TO ENSURE THAT
CONTINUOUS SPRINKLER COVERAGE IS PROVIDED THROUGHOUT THE PROJECT.
THE SPRINKLER CONTRACTOR SHALL COORDINATE ALL FIRE PROTECTION
SYSTEM SHUTDOWNS, INCLUDING POINTS OF TIE IN, ETC. WITH THE VA PRIOR TO
PERFORMING WORK.
Q. CONTRACTOR SHALL REPLACE EXISTING SPRINKLERS WITH NEW UPRIGHT
SPRINKLERS AT THE TIME OF CEILING REMOVAL TO MAINTAIN SPRINKLER
PROTECTION WITHIN THE CONSTRUCTION AREA.
R. CONTRACTOR SHALL REPAIR ANY DAMAGE TO THE EXISTING IRRIGATION SYSTEM.
S. ALL NEWLY EXPOSED SPRINKLER PIPING TO BE PAINTED.
1. EXISTING SPRINKLER HEAD IN THIS LOCATION TO REMAIN, PROTECT IN PLACE.
2. CONTRACTOR IS RESPONSIBLE FOR MAINTAINING COMPLIANCE WITH THE 2025
NFPA 13 FOR SURROUNDING SPACING DURING AND AFTER RENOVATION.
CONTRACTOR IS RESPONSIBLE FOR FIELD VERIFYING SPRINKLER HEAD
LOCATIONS AND PIPING TO BE MODIFIED BY THE RENOVATION PRIOR TO
COMMENCING WORK.
3. EXISTING PENDENT SPRINKLER HEAD IN THIS LOCATION TO BE REMOVED AND
REPLACED WITH NEW UPRIGHT SPRINKLER HEAD WITH PROTECTIVE HEAD
CAGE. INSTALL SPRINKLER HEAD AND HANGERS IN ACCORDANCE WITH THE
2025 NFPA 13. SEE SHEET FX001 FOR ADDITIONAL INFORMATION.
4. EXISTING UPRIGHT SPRINKLER HEAD IN THIS LOCATION TO BE REMOVED AND
REPLACED WITH NEW UPRIGHT SPRINKLER HEAD WITH PROTECTIVE HEAD
CAGE. INSTALL SPRINKLER HEAD AND HANGERS IN ACCORDANCE WITH THE
2025 NFPA 13. SEE SHEET FX001 FOR ADDITIONAL INFORMATION.
5. NEW UPRIGHT SPRINKLER HEAD WITH PROTECTIVE HEAD CAGE. CONNECT
PIPING TO NEAREST BRANCH LINE. INSTALL SPRINKLER HEAD AND HANGERS IN
ACCORDANCE WITH THE 2025 NFPA 13. SEE SHEET FX001 FOR ADDITIONAL
INFORMATION.
6. NEW HEAT/SMOKE DETECTOR AND FIRE ALARM STROBE/HORN, MOUNT AND
SUPPORT FROM DECK ABOVE. COORDINATE LOCATION WITH ALL OTHER
TRADES, EXISTING CONDITIONS, AND COR. SEE ARCHITECTURAL PLANS FOR
ADDITIONAL INFORMATION.
7. CONTRACTOR TO V.I.F. IF THERE ARE ADDITIONAL SPRINKLER HEADS WITHIN
THE NEW TR SPACE. IF AN ADDITIONAL HEAD IS FOUND, USE EXISTING
LOCATION AND REPLACE WITH A NEW UPRIGHT SPRINKLER HEAD IF THE
DIMENSIONS COMPLY WITH NFPA 13.
8. TR SPACES ARE DESIGNATED AS LIGHT HAZARD .
9. REMOVE EXISTING SIDEWALL FIRE SPRINKLER.
NOTE: NOT ALL KEYNOTES
ARE USED ON EACH SHEET
REFER TO COVER SHEET FOR KNOWN ACM ITEMS
WITHIN THIS BUILDING.
Revisions: Date:
Addendum 1 02/25/2026
Ariah
Ariah
UP
UP
DN DN
DN
DN
UP
WAP
CTRK
WAP
WAP
WAP
WAP
WAP
WAP
WAP
WAP
WAP
WAP
DN
WAP
CTRK
WAP
WAP
WAP
WAP
CTRK
WAP
WAP
CTRK
WAP
WAP
WAP
WALL SYMBOL LEGEND
EXISTING CONSTRUCTION TO REMAIN
SMOKE AND 1-HR RATED FIRE
BARRIER AND OPENINGS
SMOKE AND 2-HR RATED FIRE BARRIER
AND OPENINGS
SMOKE BARRIER AND OPENINGS
1 HR RATED FIRE BARRIER AND
OPENINGS
2 HR RATED FIRE BARRIER AND OPENINGS
CONTRACTOR SHALL CONFIRM ALL FIRE RATED WALL ASSEMBLIES
ROOM
B01
ROOM
B02
ROOM
B03
ROOM
B04
CORRIDOR
B05
ROOM
B06
ROOM
B07
ROOM
B08
STAIR
B09
CORRIDOR
B10
CORRIDOR
B11
STAIR
CRAWL SPACE
CS-1
CRAWL SPACE
CS-2
ROOM
NO DATA
NO DATA
NO DATA
NO DATA
NO DATA
NO DATA NO DATA
NO DATA NO DATA
NO DATA
FIBER PATH A
FIBER PATH B
TYP.
NO DATA
OFFICE
LAB
OFFICE
TOILET
OFFICE
HAC
Room
CONFERENCE RM
OFFICE
TELECOM ROOM
TOILET
OFFICE
Room
OFFICE
LAB
OFFICE
CLOSET
113A
OFFICE
CLOSET
113B
CORRIDOR
CORRIDOR
STAIR
HAC
121B
STAIR
111B
EXISTING TE
111B
UTILITY CLOSET
121A
CLOSET
108A
CORRIDOR
CLOSET
107A
CLOSET
105B
CLOSET
105A
CLOSET
103B
CLOSET
103A
CLOSET
101B
CLOSET
101A
CLOSET
112B
CLOSET
112A
CLOSET
114B
CLOSET
114A
CLOSET
116B
CLOSET
116A
CLOSET
118B
CLOSET
118A
18T-401
F7
118-A 118-B
118-C 116-A
116-B
NO DATA NO DATA
114-AP-A
114-A
114-B
NO DATA
112-B 112-A
122-AP-A
122-A
NO DATA NO DATA
101-A
101-B
101-AP-A
NO DATA
103-B 103-A
105-B 105-A
107-B
107-A
109-A
123-AP-A
123-A
NO DATA
108-A
NO DATA
NO DATANO DATA
NO DATA
NO DATA
113-A
113-AP-A
115-A
115-B
120-AP-A
TYP.
TYP.
TYP.
TYP.
TYP.
110-D
110-A
110-B
110-C
18T-401
C7
EXT-A
EXT-B
114-CK-A
111A-CAM-01
118-AP-A
121-AP-A
101-AP-B
102-AP-A
107-AP-A
108-B
TYP.
NO DATA
LAB
OFFICE
LAB
LAB
LAB
OFFICE
LAB
DARK ROOM
FREEZER
OFFICE
CLOSET
LAB
LAB
LAB
OFFICE
Room
OFFICE
OFFICE
CORRIDOR
STAIR
OFFICE
HAC
Room
218A
ROOF BELOW
ROOF BELOW
220-B 220-A
220-AP-A
218A-A
218-A
NO DATA
216-A
216-B
212-A
212-AP-A
222-A
201-A 203-A
203-B
205-A
207-A
207-B 209-AP-A
209-A
208-AP-A
206-D
206-A206-B
206-C
221-AP-A
202-A
202-B
202-C
202-D
200-AP-A
200-A
NO DATA
NO DATA
221-A221-AP-A
217-A
219-A
219-AP-A
215-A
TYP.
TYP.
217-CR-A
18T-401
C5
218A-CK-A
202-CK-A
TYP.
215-AP-A
201-AP-A
207-C
TYP.
CAT6a RISER TO
NEW TR
TELECOM ROOM
168 SF
262' - 0"
FIBER PATH A
FIBER PATH B
CABLE LEGEND
(10) NEW CAT 6A
TN
PN
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
CONSULTANT
321 4 5 6 7 8 9 10
GENERAL NOTES
KEYNOTES
TRIPLE C - The A/E Group
100 Pearl Street, 14th Floor
Hartford, CT 06103
MAT PERKINS
860-270-0753
STAMP
mat.perkins@triplecaeg.com
A u to d e s k D o c s /3
C
R
.P ro je c t.
-2
-7
.E H
R M
.I U
.B e d fo rd .M
A .R
/5
-2
-7
.B e d fo rd
.E H
R M
.M E
P .B
R
.r v t
/2
/2
:0
:1
P
M
18T-100
TELECOMMUNICATION PLAN - BASEMENT, FIRST
AND SECOND LEVEL
518-22-700
06/04/2025 M. Perkins K.Mcdermott
ISSUED FOR
CONSTRUCTION
EHRM INFRASTRUCTURE
UPGRADES
200 Springs Rd, Bedford, MA 01730
SCALE: 1/8" = 1'-0"
F4
TELECOMMUNICATION PLAN -
BASEMENT LEVEL
SCALE: 1/8" = 1'-0"
E4
TELECOMMUNICATION PLAN - FIRST
LEVEL
SCALE: 1/8" = 1'-0"
C4
TELECOMMUNICATION PLAN -
SECOND LEVEL
0 DATA PORTS FOR THIS AREA
5,932 GSF
48 DATA PORTS FOR THIS AREA
6,018 GSF
41 DATA PORTS FOR THIS AREA
5,851 GSF
SERVED FROM LEVEL 1
SERVED FROM LEVEL 1
SCALE: 1" = 100'-0"
F1
DIAMOND ANALYSIS - BUILDING 18
A. PROPERLY FIRE STOP AND SEAL ALL PENETRATIONS THROUGH WALLS,
FLOORS, CEILINGS, AND ROOF AS PER OWNER, CODE, AND AHJ.
B. PRIOR TO INSTALLATION OF CABLE TRAY COORDINATE LOCATIONS WITH ALL
OTHER TRADES AND PROVIDE COORDINATION DRAWINGS FOR REVIEW. ALL
NEW CABLE, CABLE TRAY, J HOOKS SHALL BE INDEPENDENTLY SUPPORTED &
NOT CAUSE ADDITIONAL LOAD ON OTHER SYSTEMS.
C. NOT ALL PARTS AND PIECES ARE SHOWN FOR A COMPLETE SYSTEM.
CONTRACTOR IS RESPONSIBLE FOR PROVIDING A COMPLETE END-TO-END
WARRANTEED SOLUTION FOR THE CABLING.
D. ALL CABLING TO BE PLENUM RATED THROUGHOUT THE BUILDING.
E. ALL COMMUNICATIONS AND WIRELESS ACCESS POINT CABLING TO MEET OR
EXCEED CATEGORY 6A STANDARDS.
F. SEE E-501 FOR DEVICE STANDARD MOUNTING HEIGHTS.
G. ALL CONDUITS FOR TELECOMMUNICATIONS OUTLETS SHALL BE STEEL THIN
WALL ELECTRICAL METALLIC TUBING (TYPE EMT) UNLESS OTHERWISE NOTED.
UNDER NO CIRCUMSTANCES SHALL FLEXIBLE CONDUIT BE USED FOR
PATHWAYS INDICATED ON THIS DRAWING. ALL CONDUITS ARE TO BE, AT A
MINIMUM, 1-1/4" TRADE SIZE, UNLESS OTHERWISE NOTED. ALL CONDUITS FOR
TELECOMMUNICATIONS OUTLETS ARE TO BE STUBBED TO NEAREST CABLE
TRAY. CONTRACTOR IS TO ENSURE THAT NO CONDUIT EXCEEDS 40% FILL. IF
EXISTING CONDUIT IS NOT LARGE ENOUGH TO SUPPORT NEW CAT 6A CABLE
TO REPLACE ALL EXISTING CIRCUITS ONE-FOR-ONE, CONTRACTOR SHALL
PROVIDE THE MAXIMUM ALLOWABLE NEW CAT 6A CIRCUITS TO REPLACE
EXISTING. THE ADDITIONAL NEW CIRCUITS TO COMPLETE THE ONE-FOR-ONE
REPLACEMENT SHALL BE PROVIDED AT THE NEAREST AVAILABLE DROP WITH
EXISTING CONDUIT CAPACITY.
H. ALL CONDUIT PATHWAYS SHALL BE PROVIDED WITH NYLON BUSHINGS TO
PROTECT CABLES, REGARDLESS OF WHETHER THEY TERMINATE IN A DEVICE
OR JUNCTION BOX.
I. TERMINATE, TEST, LABEL AND DOCUMENT ALL TELECOMMUNICATION CABLES.
J. CONTRACTOR SHALL AVOID ALL SYSTEMS SHUTDOWNS, INSTALL NEW
EQUIPMENT PRIOR TO THE RENOVATION OF EXISTING EQUIPMENT; PROVIDE
TEMPORARY UTILITIES AS REQUIRED TO MEET THIS REQUIREMENT.
K. THE DEMOLITION OF DEVICES SHALL INCLUDE ALL ASSOCIATED CABLING
BACK TO THE RACK.
L. LABEL DEVICE PLATES WITH A PERMANENT ADHESIVE LABEL FOLLOWING ALL
STANDARDS AND REQUIREMENTS, SEE DETAIL SHEETS FOR ADDITIONAL
INFORMATION
M. CONTRACTOR SHALL PROVIDE TWO SETS OF LAMINATED FINAL
TELECOMMUNICATION ONE-LINE, RACK ELEVATION, AND CABLE SCHEDULE
DOCUMENTS. HANG ON THE WALL WITHIN THE TELECOM ROOM.
N. REFER TO R-900 SERIES SHEETS FOR PHOTO DOCUMENTATION OF EXISTING
CONDITIONS.
O. FOR EXISTING SECURITY CAMERAS BEING RE-CABLED, MAINTAIN EXISTING
CAMERA ANGLE AND PROTECT IN PLACE.
P. ALL EXISTING PENETRATIONS NO LONGER BEING USED WILL BE FILLED WITH
RATED ASSEMBLY.
Q. ABOVE CEILING SURVEY TO OCCUR FOR CABLE TRAY INSTALLATION. EXISTING
EQUIPMENT AND/ OR SYSTEMS TO BE SELECTED AS REQUIRED. ALL ACTIVE
SYSTEMS TO REMAIN OPERATIONAL.
1. PROVIDE NEW TELECOMMUNICATIONS OUTLET IN EXISTING LOCATION WITH
EXISTING EMT STUB UP TO NEAREST ACCESSIBLE CEILING SPACE. SEE DETAILS
ON SHEET T-501 FOR ADDITIONAL INFORMATION.
2. ALL EXISTING WAP'S TO REMAIN/PROTECT IN PLACE, AND NO NEW CABLING
REQUIRED FOR EXISTING WAP'S (WIRELESS ACCESS POINTS).
3. PROVIDE NEW 4-POST CHANNEL, PDU, UPS AND WIRE MANAGEMENT
COMPONENTS AS SHOWN ON T-500 SERIES AND T-600 SERIES SHEETS AND IN
THE SPECIFICATIONS.
4. PROVIDE NEW VERTICAL WIRE MANAGEMENT SYSTEM, SEE SPECIFICATIONS FOR
ADDITIONAL INFORMATION.
5. EXISTING CABLING CONDUIT AND WIREWAYS ARE TO REMAIN AND BE CAREFULLY
PROTECTED IN PLACE. ALL EXISTING DEVICES ON THE EXISTING RACK SHALL BE
TRANSFERRED TO THE NEW RACK. CONTRACTOR SHALL PROVIDE SHOP
DRAWINGS SHOWING THE PROPOSED NEW RACK ELEVATION AND PROVIDE A
PHASING PLAN FOR TRANSFERRING ALL EXISTING DEVICES TO REMAIN TO THE
NEW RACKS.
6. PROVIDE NEW CABLE TRAY PER REQUIREMENTS LISTED IN CABLE TRAY
SCHEDULE. COORDINATE WITH EXISTING CONDITIONS AND SUBMIT
COORDINATION DRAWINGS FOR REVIEW PRIOR TO COMMENCING WORK. SEE
T-500 SERIES SHEETS FOR ADDITIONAL REQUIREMENTS. COORDINATE LIGHT
FIXTURES WITH OVERHEAD CABLE TRAY AND SPEED SLEEVE FILL SHALL NOT
EXCEED 40%.
7. PROVIDE NEW IP ADDRESSABLE NETWORK CAMERA, POE+, PTZ, MOTION
SENSOR, AUTO-TRACKING, DOME WITH WALL MOUNT. MOUNT AT 8’ – 6” A.F.F. TO
TOP OF WALL BRACKET. INTEGRATE CAMERA INTO EXISTING VMS.
8. PROVIDE NEW DATA OUTLET, STUB-UP, AND BACK-BOX IN NEW LOCATION IN TR.
9. NEW 4” SPEED CONDUIT SLEEVE THROUGH WALL ABOVE CEILING GRID FOR
HORIZONTAL VOICE/DATA CABLING OR FIBER WITH PLASTIC BUSHINGS ON BOTH
ENDS TO PROTECT CABLES,CABLE TRAY AND SPEED SLEEVE FILL SHALL NOT
EXCEED 40%. FIRE CAULK PENETRATION PER SPECIFICATIONS.
10. EXISTING CONDUIT THROUGH WALL OR FLOOR WITH OPTICAL CABLE TO BE
PROTECTED IN PLACE UNTIL NEW SPEED CONDUIT SLEEVE AND FIBER IS
INSTALLED. DEMOLISH EXISTING CONDUIT ONCE NEW SPEED CONDUIT SLEEVE
AND FIBER ARE OPERATIONAL. CONTRACTOR SHALL PROVIDE A PHASING PLAN
FOR TRANSFERRING FIBER.
11. EXISTING EQUIPMENT TO REMAIN, PROTECT-IN-PLACE.
12. DEMOLISH EXISTING FIBER ONCE NEW FIBER IS OPERATIONAL. CONTRACTOR
SHALL PROVIDE A PHASING PLAN FOR TRANSFERRING FIBER.
13. ALL EXISTING ANALOG PHONE CABLE DEVICES AND TERMINATIONS ETC. SHALL
REMAIN OPERATIONAL AT ALL TIMES AND SHALL BE RETAINED AND REUSED.
PROTECT IN PLACE.
14. VERTICAL ROUTE WITH REDUNDANT SPARE CONDUIT FOR TELECOM RISER. SEAL
ALL FLOOR PENETRATIONS TO MAINTAIN FIRE RATING.
15. HORIZONTAL CABLE LENGTH LIMITATIONS PER STANDARD 3.1.
16. EXISTING PACS AND EQUIPMENT RACKS.
17. NEW INDOOR UNIT.
18. CONTRACTOR SHALL FIELD VERIFY EXISTING TELECOMMUNICATIONS EQUIPMENT
TO BE DEMOLISHED PRIOR TO COMMENCING WORK.
19. VERTICAL LADDER RACK.
20. EXISTING CAMERA TO BE RETAINED.
21. PROVIDE NEW TELECOMMUNICATIONS OUTLET IN EXISTING LOCATION WITH
SURFACE MOUNT CONDUIT/WIREMOULD UP TO NEAREST ACCESSIBLE CEILING
SPACE.
22. PROVIDE SPACE FOR FUTURE 4-POST RACK.
23. PROVIDE 10 NEW CAT 6A CABLES FROM EXISTING TR TO NEW TR LOCATION FOR
CROSS CONNECTION, EXISTING LOW VOLTAGE SYSTEMS.
NOTE: NOT ALL KEYNOTES
ARE USED ON EACH SHEET
REFER TO COVER SHEET FOR KNOWN ACM ITEMS
WITHIN THIS BUILDING.
REFER TO COVER SHEET FOR KNOWN ACM ITEMS
WITHIN THIS BUILDING.
REFER TO COVER SHEET FOR KNOWN ACM ITEMS
WITHIN THIS BUILDING.
Revisions: Date:
Addendum 1 02/25/2026
Ariah
| Sheets |
| 18H-101 - HAZARDOUS MATERIAL ABATEMENT PLAN -FIRST LEVEL |
| 18A-401 - ARCHITECTURAL ENLARGED VIEWS -FIRST LEVEL |
| 18IN101 - INTERIOR FINISH PLAN, SIGNAGE & SCHEDULES |
| 18FX101 - FIRE PROTECTION PLAN - FIRST LEVEL |
| 18T-100 - TELECOMMUNICATION PLAN -BASEMENT, FIRST AND SECOND LEVEL |