S06 Att Amend 0002 AE601 - DOOR_WINDOW SCHEDULE.pdf

PDF 372 KB Posted

Attached to
Z2DA--Project # 695-19-131 Renovate and Expand Dialysis Clinic Clement J. Zablocki VA Medical Center Milwaukee, WI
Solicitation number
36C25220B0021
Issued by

About this file

This pre-solicitation notice is for a construction project to renovate and expand an existing dialysis clinic located at the Clement J. Zablocki VA Medical Center in Milwaukee, Wisconsin. The contractor will be responsible for demolishing an existing vacant ward and reconstructing the space to house the hospital's relocated dialysis clinic. Scope of work includes trades such as demolition, concrete, electrical, plumbing, HVAC, architectural, and specialty furnishings. The total square footage of the renovated space will be approximately 11,000 square feet. Hazardous materials abatement is also required. The project number is 695-19-131 and has an anticipated price range between $2-5 million. The period of performance is 540 calendar days from notice to proceed. The solicitation for this 100% SDVOSB set-aside construction project is scheduled to post on FedBizOpps on May 13, 2020 with a bid opening on June 16, 2020. A pre-bid conference will be held at the site.

View the file

Other files

File Type Posted
Amend 0005 00 01 10 TABLE OF CONTENTS.pdf PDF
Amend 0005 22 67 19.16 REVERSE-OSMOSIS WATER EQUIPMENT.pdf PDF
Amend 0005 08 71 13.11 LOW ENERGY DOOR OPERATORS.pdf PDF
S06 36C25220B0021 0005.pdf PDF
Amend 0005 01 91 00 COMMISSIONING REQUIREMENTS.pdf PDF
Amend 0005 01 01 10 SN SPECIAL NOTES.pdf PDF
Amend 0005 11 73 00 CEILING MOUNT PATIENT LIFT.pdf PDF
Amend 0005 14 92 00 PNEUMATIC TUBE SYSTEM.pdf PDF
Amend 0003 Photos Revised.pdf PDF
S06 36C25220B0021 0004.pdf PDF
AI601 - FINISH SCHEDULES.pdf PDF
Wage Determination 6.19.20.pdf PDF
Amend 0003 Photos.pdf PDF
SECTION 10 21 23 - CUBICLE CURTAIN TRACKS.pdf PDF
36C25220B0021 0003.pdf PDF
S06 Att Amend 0002 00 01 10 - TABLE OF CONTENTS.pdf PDF
S06 Att Amend 0002 EP100 - BASEMENT FLOOR OVERALL PLAN.pdf PDF
S06 Att Amend 0002 AI201 - INTERIOR FINISHES ELEVATIONS.pdf PDF
S06 36C25220B0021 0002.pdf PDF
S06 Att Amend 0002 28 05 13 - CONDUCTORS AND CABLES FOR ELECTRONIC SAFETY AND SECURITY.pdf PDF
S06 Att Amend 0002 10 21 23 - CUBICLE CURTAIN TRACKS.pdf PDF
S06 Att Amend 0002 01 74 19 - CONSTRUCTION WASTE MANAGEMENT.pdf PDF
S06 Att Amend 0002 GC101 - INFECTION CONTROL_PHASING PLAN.pdf PDF
S06 Att Amend 0002 09 05 16 - FLOOR PREP1.pdf PDF
S06 Att Amend 0002 ET102 - SEVENTH FLOOR SYSTEMS PLAN - DIVISION 28.pdf PDF
S06 Att Amend 0002 AD101 - SEVENTH FLOOR DEMOLITION PLAN.pdf PDF
S06 Att Amend 0002 MD101 - MECHANICAL DEMOLITION FLOOR PLAN - 7TH FLOOR.pdf PDF
S06 Att Amend 0002 10 14 00 - SIGNAGE.pdf PDF
S06 Att Amend 0002 12 24 00 - WINDOW SHADES.pdf PDF
S06 Att Site Visit Sign In 5.28.20.pdf PDF
S06 Att Amend 0002 03 30 53 - CAST-IN-PLACE CONCRETE.pdf PDF
S06 Att Amend 0002 QH101 - SEVENTH FLOOR EQUIPMENT PLAN.pdf PDF
S06 Att Amend 0002 01 91 00 - COMMISSIONING REQUIREMENTS.pdf PDF
S06 Att Amend 0002 22 07 11 - PLUMBING INSULATION.pdf PDF
S06 Att Amend 0002 ET101D - SEVENTH FLOOR DEMOLITION PLAN.pdf PDF
S06 Att Amend 0002 22 11 00 - FACILITY WATER DISTRIBUTION.pdf PDF
S06 Att Amend 0002 AE501 - BUILDING DETAILS.pdf PDF
S06 Att Amend 0002 AI901 - SIGNAGE PLAN.pdf PDF
S06 Att Amend 0002 AI101 - FINISH WALL TREATMENT PLAN.pdf PDF
S06 Att Amend 0002 EP401 - ONE LINE DIAGRAM.pdf PDF
S06 Att Wage Determination 6.5.20.pdf PDF
Site Visit Sign In 5.20.20.pdf PDF
36C25220B0021 0001.docx DOCX document
Amend 0001 Specification 22 63 00.pdf PDF
Amend 0001 Specification 00 01 10.pdf PDF
Amend 0001 Specification 08 14 00.pdf PDF
Amend 0001 Specification 09 06 00.pdf PDF
Amend 0001 J_A Patient Ceiling Lift.pdf PDF
36C25220B0021-011.pdf PDF
36C25220B0021-012.pdf PDF
Show 40 more

Latest 50 of 72 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

F1 F2

AS SCHEDULED 2" TYP

A S

S C

H E

D U

LE

D

D1 D2

A S

S C

H E

D U

LE

D

AS SCHEDULED

D3

AS SCHEDULED

A S

S C

H E

D U

LE

D

A S

S C

H E

D U

LE

D

AS SCHEDULED

2"

AS SCHEDULED

2"

2" A

S S

C H

E D

U

LE

D

DOUBLE EGRESS

AE601

TYP

AE601

TYP

AE601

TYP

AE601

TYP

DOOR AND FRAME TYPE LEGEND WINDOW TYPE LEGEND

A S

S C

H E

D U

LE

D

AS SCHEDULED

SLIDING

TRANSACTION

FIXED

A S

S C

H E

D U

LE

D

AS SCHEDULED

2" 2"

2" 2"

D4

A S

S C

H E

D U

LE

D

AS SCHEDULED AS SCHEDULED

A S

S C

H E

D U

LE

D

4" 8"

A F

F

3'

2'

D5

F3

AS SCHEDULED 2" TYP

RESCUE FRAME

A S

S C

H E

D U

LE

D

AS SCHEDULED

A S

S C

H E

D U

LE

D

4" 8" 8" 4"

A F

F

3'

2'

D6 D7

AS SCHEDULED

A S

S C

H E

D U

LE

D

AE601

TYP

AE601

TYP

HOLLOW METAL FRAME,

RE: DOOR SCHEDULE

WALL TYPE,

RE: PLANS

DOUBLE STUD FRAMING

SEALANT BOTH SIDES

HOLLOW METAL FRAME,

RE: DOOR SCHEDULE

WALL TYPE,

RE: PLANS

FRAMING STUD HEADER

SEALANT BOTH SIDES

FRAMING STUD HEADER

DOUBLE EGRESS DOOR

HOLLOW METAL DOOR FRAME

SEALANT - BOTH SIDES

WALL TYPE,

RE: PLANS

2"

1/

4"

DOUBLE EGRESS DOOR HOLLOW

METAL DOOR FRAME

JAMB ANCHORS

SEALANT - BOTH SIDES

DOUBLE STUD FRAMING

2"

WALL TYPE,

RE: PLANS

3 1/4" 2"

DOUBLE STUD FRAMING

RESCUE DOOR HOLLOW METAL

DOOR FRAME

SEALANT - BOTH SIDES

WALL TYPE,

RE: PLANS

RESCUE STOP/ STRIKE

TOILET SIDE

CORRIDOR SIDE

2"

FRAMING STUD HEADER

RESCUE DOOR HOLLOW METAL

DOOR FRAME

SEALANT - BOTH SIDES

WALL TYPE,

RE: PLANS

RESCUE STOP/ STRIKE

CORRIDOR

SIDE

TOILET

SIDE

1. DOOR TO RECEIVE A CARD READER, REFER TO ELECTRICAL DRAWINGS.

2. PROVIDE AUTO OPERATOR BUZZER AT RECEPTION DESK FOR DOOR

ACCESS CONTROL.

3. OPERATION INTENT OF DOORS IS TO ENTER BY CARD READER THAT

ACTIVATES THE AUTOMATIC OPENERS. EGRESS WILL BE BY WAVE PADDLE

LOCATED WITHIN THE DIALYSIS SUITE. COORDINATION WITH VENDOR AND

ET DRAWINGS FOR MORE INFORMATIN.

A. CONTRACTOR IS RESPONSIBLE TO COORDINATE ALL HARDWARE

REQUIREMENTS BETWEEN HARDWARE SUPPLIES, ACCESS CONTROL

VENDOR, AND ANY OTHER TRADES THAT ARE INVOLVED. POWER SUPPLIES

AND AUXILIARY COMPONENTS REQUIRED TO MAKE A HARDWARE SET WORK

BETWEEN ACCESS CONTROL AND HARDWARE SHALL BE PROVIDED.

B. ALL HOLLOW METAL DOORS AND FRAMES SHALL BE FACTORY PRIMED AND

RECEIVE PAINT FINISH ON SITE. REFER TO FINISH SCHEDULE FOR HOLLOW

METAL PAINT COLOR.

C. PROVIDE SEALANT AROUND PERIMETER OF DOOR/ WINDOW FRAME

ADJACENT TO WALL AND FLOOR CONSTRUCTION, BOTH SIDES.

D. LOCATE HINGE SIDE OF DOOR 6" OFF OF ADJACENT WALL UNLESS

OTHERWISE INDICATED ON FLOOR PLAN AE102.

E. MAINTAIN ADA CLEARANCE AROUND DOORS AND REFER ANY

DISCREPANCIES DUE TO COR AND ARCHITECT FOR CLARIFICATION.

F. RATED FRAMES, DOORS AND GLAZING SHALL BE UL LABELED IN A VISIBLE

LOCATION.

G. REFER TO DOOR/ WINDOW AND FRAME LEGEND FOR REFERENCE TO

TYPICAL HEAD, JAMB AND SILL DETAILS.

H. ALL HOLLOW METAL JAMBS TO BE PREPARED FOR ACCESS CONTROL AND

SECURITY HARDWARE. REFER TO ENGINEERING DRAWINGS FOR

ADDITIONAL INFORMATION.

I. REFER TO SPECIFICATIONS AND ENGINEERING DRAWINGS FOR ADDITIONAL

HARDWARE INFORMATION.

J. COORDINATE POWER AND DATA REQUIREMENTS AT DESIGNATED DOOR

OPENINGS WITH ENGINEERING DRAWINGS.

DOOR AND FRAME GENERAL NOTES

DOOR SCHEDULE COMMENTS

MG-1 CLEAR FULLY TEMPERED FLOAT GLASS

FR-1 FIRE PROTECTION RATED LAMINATED CERAMIC GLASS

GLAZING LEGEND

LOUVER SCHEDULE GENERAL NOTES

1. REFER TO MECHANICAL ENGINEERING DRAWINGS FOR ADDITIONAL

INFORMATION AND COORDINATION.

2. INSTALLATION SHALL BE COORDINATED WITH COR AND VA SAFETY.

CONTRACTOR TO PROVIDE FALL PROTECTION DURING WINDOW DEMO

AND LOUVER INSTALLATION.

3. INSTALLATION SHALL BE A LINE ITEM ON THE CONTRACTOR SCHEDULE.

4. PROVIDE WITH BIRD SCREEN.

5. COLOR AND FINISH TO MATCH PREVIOUS WINDOW SYSTEM PROJECT,

COORDINATE WITH VA.

6. FIELD VERIFY EXACT DIMENSIONS IN FIELD PRIOR TO ORDERING.

LOUVERS SHALL BE INSTALLED IN EXISTING WINDOW OPENINGS.

4 7/8"

SOLID SURFACE SILL

CAULK, BOTH SIDES

TREATED WOOD SHIM

AS REQUIRED

WALL PARTITION

AS SCHEDULED

SLIDING TRANSACTION

WINDOW

5/8" TYPE 'X' GYP BD

WALL PARTITION

AS SCHEDULED

CORNER BEAD,

BOTH SIDES

1/2" 4 7/8" 1/2"

1/ 2"

1/

2"

5 7/8"

EQ EQ

3'

A F

F

SILL

FASTENER

STEEL ANGLE

EXISTING

MASONRY WALL

EXTERIORINTERIOR

LOUVER. REFER TO LOUVER

SCHEDULE AND

SPECIFICATION 08 90 00

BIRD SCREEN.

STEEL ANGLE

FASTENER, TYP.

EXISTING

MASONRY WALL

BREAK METAL

FLASHING BELOW SILL

1/

2"

ANCHOR FASTENER IN EXISTING

EXTERIOR CONCRETE WALL

PROVIDE NEOPRENE GASKET

BETWEEN LOUVER AND STEEL

ANGLE

PROVIDE SEALANT AT

EXTERIOR LOUVER FLANGE

NOTE:

MATCH LOUVERS INSTALLED

IN MECHANICAL ROOM ON 8A.

INSTALLATION METHOD

SHOULD MATCH CURRENTLY

INSTALLED LOUVERS.

ALUMINUM SLIDING DOOR

SEALANT BOTH SIDES

SEE PLAN FOR WALL TYPE

STEEL STUD

ACOUSTICAL SOUND BATT

INSULATION

6"

MTL STUD KICKER AT 4'-0" O.C.

ALUMINUM SLIDING

DOOR

CONTINUOUS FLOOR FINISH

OVER EXISTING SLAB

SEE PLAN FOR WALL TYPE

SEALANT BOTH SIDES

ALUMINUM SLIDING DOOR

SLIDING PANEL1/4" 1 3/4"

AC1.0

QTY DESCRIPTION MFG FIN

3 EA HINGE BB1168 (NRP) HA US26D

1 EA STOREROOM LOCK 70 8204 LE1L SA US26D

1 EA INTERCHANGEABLE CORE 33700006N MC 26

1 EA ELEC STRIKE 1500C-LM HS 630

1 EA CLOSER 4040XP REG LC AL

1 EA KICK PLATE K1050 10" 4BE CSK RO US32D

1 EA WALL STOP 402/405 (AS REQ'D) RO US26D

1 EA GASKET S88BL PE

1 EA E-LYNX HARNESS (JAMB) QC-C1500P MK

1 EA WIRING DIAGRAM ELEVATION & PTP OT

1 EA CARD READER BY SECURITY CONTRACTOR HD BLK

1 EA POWER SUPPLY BPS (SIZE & TYPE AS REQ'D) SU

NOTES:

USE STANDARD WEIGHT HINGES AT DOORS 36" WIDE OR LESS. DOOR NORMALLY CLOSED AND LOCKED.

VALID CARD READ UNLOCKS ELECTRIC STRIKE FOR ENTRY. KEY OVERRIDE AVAILABLE. STRIKE IS LOCKED

WITHOUT POWER (FAIL SECURE). FREE EGRESS AT ALL TIMES.

AC2.0

QTY DESCRIPTION MFG FIN

3 EA HINGE (HEAVYWEIGHT) BB1168 (NRP) HA US26D

1 EA STOREROOM LOCK 70 8204 LE1L SA US26D

1 EA FORMAT INTER. CORE 33700006N MC 26

1 EA ELEC STRIKE 1500C-LM HS 630

1 EA CLOSER 4040XP REG LC AL

1 EA KICK PLATE K1050 10" 4BE CSK RO US32D

1 EA WALL STOP 402/405 (AS REQ'D) RO US26D

1 EA GASKET S88BL PE

1 EA E-LYNX HARNESS (JAMB) QC-C1500P MK

1 EA REMOTE RELEASE BY SECURITY CONTRACTOR OT

1 EA WIRING DIAGRAM ELEVATION & PTP OT

1 EA CARD READER BY SECURITY CONTRACTOR HD BLK

1 EA POWER SUPPLY BPS (SIZE & TYPE AS REQ'D) SU

NOTES:

DOORS NORMALLY CLOSED AND LOCKED. VALID CARD READ UNLOCKS ELECTRIC STRIKE FOR ENTRY.

REMOTE RELEASE BUTTON AT RECEPTION DESK UNLOCKS ELECTRIC STRIKE. KEY OVERRIDE AVAILABLE.

STRIKE IS LOCKED WITHOUT POWER (FAIL SECURE). FREE EGRESS AT ALL TIMES.

AC4.0

QTY DESCRIPTION MFG FIN

3 EA HINGE BB1279 (NRP) HA US26D

1 EA STOREROOM LOCK 70 8204 LE1L SA US26D

1 EA FORMAT INTER. CORE 33700006N MC 26

1 EA ELEC STRIKE 1500C-LM HS 630

1 EA DOOR CLOSER 4040XP REG LC AL

1 EA KICK PLATE K1050 10" 4BE CSK RO US32D

1 EA ELECTROMAG. HOLDER 998M RF 689

1 EA GASKET S88BL PE

1 EA E-LYNX HARNESS (JAMB) QC-C1500P MK

1 EA WIRING DIAGRAM ELEVATION & P.T.P. OT

1 EA CARD READER BY SECURITY CONTRACTOR HD BLK

1 EA POWER SUPPLY BPS (SIZE & TYPE AS REQ'D) SU

NOTES:

DOOR NORMALLY CLOSED AND LOCKED. VALID CARD READ UNLOCKS ELECTRIC STRIKE FOR ENTRY. KEY OVERRIDE AVAILABLE. STRIKE IS LOCKED WITHOUT POWER (FAIL SECURE). DOOR CAN BE HELD OPEN ON MAGNETIC HOLDER TIED TO FIRE ALARM SYSTEM. DOOR RELEASES, CLOSES, AND IS LATCHED UPON

LOSS OF POWER OR SIGNAL FROM THE FIRE COMMAND CENTER. FREE EGRESS AT ALL TIMES.

AC5.0

QTY DESCRIPTION MFG FIN

1 EA CONTINUOUS HINGE FM300 7'0 MR 630

1 EA CONTINUOUS HINGE x EPT FM300 7'0 EL-CEPT MR 630

1 EA SVR EXIT (EO, DEL EGRESS) 12 59 NB8710 EO SA US32D

1 EA SVR EXIT (EO, RATED) 12 NB8710 EO SA US32D

1 EA FORMAT INTER. CORE 33700006N MC 26

2 EA DOOR CLOSER 4040XP EDA LC AL

2 EA KICK PLATE K1050 10" 4BE CSK RO US32D

2 EA WALL STOP 402/405 (AS REQ'D) RO US26D

1 EA GASKET S88BL PE

1 EA DOOR EDGE SEAL S772BL PE

1 EA E-LYNX HARNESS (JAMB) QC-C1500P MK

1 EA E-LYNX HARNESS (DOOR) QC-C***(LENGTH/TYPE AS REQ'D) MK

1 EA WIRING DIAGRAM ELEVATION & P.T.P. OT

1 EA CARD READER BY SECURITY CONTRACTOR HD BLK

1 EA POWER SUPPLY BPS (SIZE & TYPE AS REQ'D) SU

NOTES:

DOORS NORMALLY CLOSED AND LATCHED. EXIT DEVICE FOR TRAVEL FROM PLAN LEFT TO RIGHT IS FREE EGRESS AT ALL TIMES. PUSHING EXIT DEVICE, TO TRAVEL FROM PLAN RIGHT TO LEFT, INITIATES DELAYED EGRESS SEQUENCE: DOOR REMAINS LOCKED AND LOCAL ALARM SOUNDS. AFTER A 15-SECOND DELAY, DOOR RELEASES FOR EGRESS. DELAYED EGRESS IS RESET MANALLY BY KEY IN PUSH RAIL OF EXIT DEVICE. VAILD CARD READ AT PUSH SIDE OF DOOR LEAF BYPASSES DELAYED EGRESS FOR IMMEDIATE PASSAGE THROUGH DOOR. DELAYED EGRESS EXIT DEVICE IS CONNECTED TO FIRE ALARM, SO THAT

DOOR ALLOWS IMMEDIATE EGRESS UPON FIRE ALARM OR LOSS OF POWER.

AC5.1

QTY DESCRIPTION MFG FIN

1 EA CONTINUOUS HINGE FM300 7'0 MR 630

1 EA CONTINUOUS HINGE x EPT FM300 7'0 EL-CEPT MR 630

1 EA SVR EXIT (EO, DEL EGRESS) 12 59 NB8710 EO SA US32D

1 EA SVR EXIT (EO, RATED) 12 NB8710 EO SA US32D

1 EA FORMAT INTER. CORE 33700006N MC 26

2 EA DOOR CLOSER 4040XP EDA LC AL

2 EA KICK PLATE K1050 10" 4BE CSK RO US32D

2 EA WALL STOP 402/405 (AS REQ'D) RO US26D

1 EA GASKET S88BL PE

1 EA DOOR EDGE SEAL S772BL PE

1 EA E-LYNX HARNESS (JAMB) QC-C1500P MK

1 EA E-LYNX HARNESS (DOOR) QC-C***(LENGTH/TYPE AS REQ'D) MK

1 EA WIRING DIAGRAM ELEVATION & P.T.P. OT

1 EA CARD READER BY SECURITY CONTRACTOR HD BLK

1 EA POWER SUPPLY BPS (SIZE & TYPE AS REQ'D) SU

NOTES:

DOORS NORMALLY CLOSED AND LATCHED. EXIT DEVICE FOR TRAVEL FROM PLAN RIGHT TO LEFT (INTO DIALYSIS) IS FREE EGRESS AT ALL TIMES. PUSHING EXIT DEVICE, TO TRAVEL FROM PLAN LEFT (DIALYSIS) TO RIGHT, INITIATES DELAYED EGRESS SEQUENCE: DOOR REMAINS LOCKED AND LOCAL ALARM SOUNDS.

AFTER A 15-SECOND DELAY, DOOR RELEASES FOR EGRESS. DELAYED EGRESS IS RESET MANUALLY BY KEY IN PUSH RAIL OF EXIT DEVICE. VALID CARD READ AT PUSH SIDE OF DOOR LEAF BYPASSES DELAYED EGRESS FOR IMMEDIATE PASSAGE THROUGH DOOR. DELAYED EGRESS EXIT DEVIDE IS CONNECTED TO FIRE ALARM, SO THAT DOOR ALLOWS IMMEDIATE EGRESS UPON FIRE ALARM OR LOSS OF POWER.

AC6.0

QTY DESCRIPTION MFG FIN

2 EA CONTINUOUS HINGE x EPT FM300 7'0 EL-CEPT MR 630

1 EA SVR EXIT (EO, ELR) 12 56 NB8710 EO SA US32D

1 EA SVR EXIT (STO LVR, ELR) 12 56 70 NB8706 ETL SA US32D

1 EA FORMAT INTER. CORE 33700006N MC 26

2 EA AUTO OPERATOR BY SECTION __________ OT

2 EA ARMOR PLATE K1050 F 34" HVBEV CSK OT US32D

1 EA GASKET S88BL PE

1 EA DOOR EDGE SEAL S772BL PE

2 EA E-LYNX HARNESS (JAMB) QC-C1500P MK

2 EA E-LYNX HARNESS (DOOR) QC-C***(LENGTH/TYPE AS REQ'D) MK

1 EA REMOTE RELEASE BY SECURITY CONTRACTOR OT

1 EA WIRING DIAGRAM ELEVATION & P.T.P. OT

1 EA CARD READER BY SECURITY CONTRACTOR HD BLK

1 EA POWER SUPPLY BPS (SIZE & TYPE AS REQ'D) SU

NOTES:

DOORS NORMALLY CLOSED AND LOCKED. VALID CARD READ FROOM PULL SIDE RETRACTS LATCH OF BOTH EXIT DEVICES AND OPENS BOTH DOORS AUTOMATICALLY, SIMULTANEOUSLY. REMOTE RELEASE BUTTON AT RECEPTION DESK RETRACTS LATCH OF BOTH EXIT DEVICES AND OPENS BOTH DOORS AUTOMATICALLY, SIMULTANEOUSLY. PUSH BUTTON FROM PUSH SIDE RETRACTS LATCH OF BOTH EXIT DEVICES AND OPENS BOTH DOORS AUTOMATICALLY, SIMULTANEOUSLY. KEY OVERRIDE FROM PULL SIDE

AVAILABLE. FREE MANUAL EGRESS AT ALL TIMES.

1.0

QTY DESCRIPTION MFG FIN

3 EA HINGE BB1279 (NRP) MK US32D

1 EA OFFICE/ENTRY LOCK 70 8205 LE1L SA US26D

1 EA FORMAT INTER. CORE 33700006N MC 26

1 EA WALL STOP 402/405 (AS REQ'D) RO US26D

1.1

QTY DESCRIPTION MFG FIN

3 EA HINGE BB1279 (NRP) MK US32D

1 EA OFFICE/ENTRY LOCK 70 8205 LE1L SA US26D

1 EA FORMAT INTER. CORE 33700006N MC 26

1 EA SURF OVERHEAD STOP 9-X36 (5458) RF 630

2.0

QTY DESCRIPTION MFG FIN

2 EA CONTINUOUS HINGE FM300 7'0 MR 630

2 EA SVR EXIT (EO) NB8710 EO SA US32D

2 EA CLOSER x HOLD OPEN 4040XP H LC AL

2 EA KICK PLATE K1050 10" 4BE CSK RO US32D

2 EA WALL STOP 402/405 (AS REQ'D) RO US26D

1 EA GASKET S88BL PE

1 EA DOOR EDGE SEAL S772BL PE

2.1

QTY DESCRIPTION MFG FIN

2 EA CONTINUOUS HINGE FM300 7'0 MR 630

2 EA SVR EXI, PASSAGE LEVER NB8715 ETL SA US32D

2 EA CLOSER 4040XP HCUSH LC AL

2 EA KICK PLATE K1050 10" 4BE CSK RO US32D

1 EA GASKET S88BL PE

1 EA DOOR EDGE SEAL S772BL PE

3.0

QTY DESCRIPTION MFG FIN

3 EA HINGE BB1191 (NRP) HA US32D

1 EA PRI. x DEADBOLT (OCC/VAC) V21 70 8205 VN1L SA US26D

1 EA WALL STOP 402/405 (AS REQ'D) RO US26D

3.1

QTY DESCRIPTION MFG FIN

3 EA HINGE (HEAVYWEIGHT) BB1168 (NRP) HA US26D

1 EA PRI. x DEADBOLT (OCC/VAC) V21 70 8205 VN1L SA US26D

1 EA WALL STOP 402/405 (AS REQ'D) RO US26D

3.2

QTY DESCRIPTION MFG FIN

3 EA HINGE BB1191 (NRP) HA US32D

1 EA PRI. x DEADBOLT (OCC/VAC) V21 8265 VN1L SA US26D

1 EA WALL STOP 402/405 (AS REQ'D) RO US26D

3.3

QTY DESCRIPTION MFG FIN

1 EA PIVOT EP-5J MK US26D

1 EA PRIVACY (OCC/VAC) V21 8265 VN1L SA US26D

1 EA CONC OVERHEAD STOP 2-X36 RF 630

2 EA ASTRAGAL 300CP 84" PE

1 EA DOUBLE LIP STRIKE DLS-8 CH MK US26D

1 EA EMERGENCY STOP DS-6 MK US26D

NOTES:

ASTRAGAL SEAL ROUTED INTO BOTH DOOR EDGES. MODIFY STRIKE FOR MORTISE LOCK.

3.4

QTY DESCRIPTION MFG FIN

1 EA PIVOT SET 117-3/4 RF 626

1 EA PRIVACY (OCC/VAC) V21 8265 VN1L SA US26D

1 EA CONC OVERHEAD STOP 2-X36 RF 630

2 EA ASTRAGAL 300CP 84" PE

1 EA DOUBLE LIP STRIKE DLS-8 CH MK US26D

1 EA EMERGENCY STOP DS-6 MK US26D

NOTES:

ASTRAGAL SEAL ROUTED INTO BOTH DOOR EDGES. MODIFY STRIKE FOR MORTISE LOCK.

4.0

QTY DESCRIPTION MFG FIN

3 EA HINGE BB1279 (NRP) HA US26D

1 EA STOREROOM LOCK 72 8204 LE1L SA US26D

1 EA FORMAT INTER. CORE 33700006N MC 26

1 EA DOOR CLOSER 4040XP EDA LC AL

1 EA KICK PLATE K1050 10" 4BE CSK RO US32D

1 EA WALL STOP 402/405 (AS REQ'D) RO US26D

4.1

QTY DESCRIPTION MFG FIN

6 EA HINGE (HEAVYWEIGHT) BB1199 (NRP) HA US32D

1 EA SELF-LATCHING FB (TOP ONLY) 2905 RO US26D

1 EA STOREROOM LOCK 72 8204 LE1L SA US26D

2 EA SURF OVERHEAD STOP 9-X36 (5458) RF 630

5.0

QTY DESCRIPTION MFG FIN

1 EA BALANCE OF HARDWARE BY DOOR MANUFACTURER MA

6.0

QTY DESCRIPTION MFG FIN

6 HINGE BB1279 (NRP) HA US26D

1 AUTO FB SET 2962 RO US26D

1 EA CLASSROOM LOCK 70 8237 LE1L SA US26D

1 EA FORMAT INTER. CORE 33700006N MC 26

1 EA COORDINATOR 2672 RO US28

2 EA MOUNTING BRACKET 2601AB RO US28

2 EA DOOR CLOSER 4040XP EDA ` LC AL

2 EA KICK PLATE K1050 10" 4BE CSK RO US32D

2 EA ELECTROMAG. HOLDER 998M RF 689

1 EA GASKET S88BL PE

1 EA DOOR EDGE SEAL S772BL PE

NOTES:

DOOR CAN BE LOCKED OR UNLOCKED FROM CORRIDOR SIDE WITH A KEY AND LEFT IN THAT STATE. WHEN DOOR IS UNLOCKED, FREE ENTRY BY LEVER AT ALL TIMES. DOORS CAN BE HELD OPEN AT 180-DEGREES ON MAGNETIC HOLDERS TIED TO FIRE ALARM SYSTEM. DOORS RELEASE, CLOSE, AND LATCH UPON LOSS

OF POWER OR SIGNAL FROM THE FIRE COMMAND CENTER. FREE EGRESS AT ALL TIMES.

7.0

QTY DESCRIPTION MFG FIN

1 RIM EXIT (STOREROOM, RATED) 12 70 8804 ETL US32D SA

1 SMALL FORMAT INTER CORE 33700006N 26 MC

NOTES:

FIELD VERIFY COMPATIBILITY OF NEW HARDWARE WITH EXISTING DOOR/FRAME/HARDWARE

COMPONENTS. ADD OR INCLUDE ALL NECESSARY FILLER PLATES, PATCHES, ETC TO MEET REQUIREMENTS

FOR FIRE RATED DOOR OPENING. KEY ENTRY ONLY. FREE EGRESS AT ALL TIMES.

DOOR HARDWARE SCHEDULE

2" R

E : F

R A

M E

T Y

P E

2"

1/4" CLEAR TGL

P-TYPE;

RE: PLAN

1. HEAD & SILL SIMILAR

2. PROVIDE (3) ANCHORS MIN. PER

JAMB: 4 AT RATED PARTITIONS.

3. HM JAMB THROAT 1/8" LARGER

THAN PARTITION, CAULK AND

PAINT (TYPICAL)

NOTES:

WELDED H.M. FRAME

H.M. STOP

DOUBLE STUD @ JAMB

X

VARIES

125/256"125/256"

125/256" 125/256"

EQ VARIES EQ

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Consultant:

C U s e rs

\d v a lla n d in g h a m \D o c u m e n ts

\1

.1

.1

A v d v a lla n d in g h a m g u id o n d e s ig n .c o m

.r v t

/5

/2

:2

:1

P M

AE601

DOOR & WINDOW SCHEDULE

GUIDON

1221 N. PENNSYLVANIA STREET

INDIANAPOLIS, IN 46202

317.800.6388

RING & DUCHATEAU, LLP.

17400 W. CAPITOL DRIVE

BROOKFIELD, WI 53045

414.778.1700

RENOVATE AND EXPAND

DIALYSIS CLINIC

5000 W National Ave, Milwaukee, WI 53295

695-19-131

03/26/2020 JDJ

100% CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

DOOR SCHEDULE

DOOR

DIMENSIONS DOOR FRAME DETAIL

GLAZING

FIRE

RATING

HARDWARE

SET COMMENTSWIDTH HEIGHT THICKNESS TYPE MATERIAL FINISH TYPE

MATERI

AL FINISH HEAD JAMB SILL

7A01 2' - 6" 7' - 0" 1 3/4" D1 WD ST-CLR F1 HM PT-2 2/AE601 1/AE601 4.0

7100A 5' - 0" 7' - 0" 1 3/4" D4 WD ST-CLR F1 HM PT-2 2/AE601 1/AE601 FR-1 45 MIN 6.0

7100B 4' - 0" 7' - 0" 1 3/4" D3 WD ST-CLR F1 HM PT-2 2/AE601 1/AE601 MG-1 AC2.0 1, 2, 3

7101 3' - 0" 7' - 0" 1 3/4" D1 WD ST-CLR F3 HM PT-2 4/AE601 3/AE601 3.1

7102 4' - 0" 7' - 0" 1 3/4" D1 WD ST-CLR F1 HM PT-2 2/AE601 1/AE601 3.1

7103 4' - 0" 7' - 0" 1 3/4" D1 WD ST-CLR F1 HM PT-2 2/AE601 1/AE601 3.1

7104 3' - 0" 7' - 0" 1 3/4" D5 WD ST-CLR F1 HM PT-2 2/AE601 1/AE601 MG-1 1.1

7116 3' - 0" 7' - 0" 1 3/4" D5 WD ST-CLR F1 HM PT-2 2/AE601 1/AE601 MG-1 AC1.0 1

7117 4' - 0" 7' - 0" 1 3/4" D1 WD ST-CLR F1 HM PT-2 2/AE601 1/AE601 FR-1 45 MIN AC1.0 1

7119 4' - 0" 7' - 0" 1 3/4" D1 WD ST-CLR F1 HM PT-2 2/AE601 1/AE601 FR-1 45 MIN AC1.0 1

7121 3' - 0" 7' - 0" 1 3/4" D1 WD ST-CLR F1 HM PT-2 2/AE601 1/AE601 FR-1 45 MIN AC1.0 1

7123 5' - 0" 7' - 0" 1 3/4" D2 WD ST-CLR F1 HM PT-2 2/AE601 1/AE601 4.1

7124 3' - 0" 7' - 0" 1 3/4" D1 WD ST-CLR F1 HM PT-2 2/AE601 1/AE601 45 MIN AC1.0 1

7125 3' - 0" 7' - 0" 1 3/4" D5 WD ST-CLR F1 HM PT-2 2/AE601 1/AE601 MG-1 AC1.0 1

7126 2' - 0" 7' - 0" 1 3/4" D1 WD ST-CLR F1 HM PT-2 2/AE601 1/AE601 4.0

7128 2' - 0" 7' - 0" 1 3/4" D1 WD ST-CLR F1 HM PT-2 2/AE601 1/AE601 AC1.0 1

7129 3' - 0" 7' - 0" 1 3/4" D1 WD ST-CLR F1 HM PT-2 2/AE601 1/AE601 3.0

7130 3' - 0" 7' - 0" 1 3/4" D1 WD ST-CLR F1 HM PT-2 2/AE601 1/AE601 1.0

7131 3' - 0" 7' - 0" 1 3/4" D1 WD ST-CLR F1 HM PT-2 2/AE601 1/AE601 1.0

7132 2' - 6" 7' - 0" 1 3/4" D1 WD ST-CLR F1 HM PT-2 2/AE601 1/AE601 4.0

7133 4' - 0" 7' - 0" 1 3/4" D1 WD ST-CLR F3 HM PT-2 4/AE601 3/AE601 3.2

7134 7' - 8 1/2" 7' - 0" 1 3/4" D7 ALUM CLR ANODIZED BY MANUF. ALUM CLR ANODIZED 8/AS601 10/AS601 7/AS601 MG-1 None 5.0

7134A 3' - 0" 7' - 0" 1 3/4" D1 WD ST-CLR F1 HM PT-2 2/AE601 1/AE601 3.2

7135 7' - 8 1/2" 7' - 0" 1 3/4" D7 ALUM CLR ANODIZED BY MANUF. ALUM CLR ANODIZED 8/AS601 10/AS601 7/AS601 MG-1 None 5.0

7135A 3' - 0" 7' - 0" 1 3/4" D1 WD ST-CLR F3 HM PT-2 4/AE601 3/AE601 3.1

7136 7' - 8 1/2" 7' - 0" 1 3/4" D7 ALUM CLR ANODIZED BY MANUF. ALUM CLR ANODIZED 8/AS601 10/AS601 7/AS601 MG-1 None 5.0

7136A 4' - 0" 7' - 0" 1 3/4" D1 WD ST-CLR F3 HM PT-2 4/AE601 3/AE601 3.2

7139 4' - 0" 7' - 0" 1 3/4" D1 HM P- F1 HM PT-2 2/AE601 1/AE601 AC1.0 1

7140 4' - 0" 7' - 0" 1 3/4" D1 HM P- F1 HM PT-2 2/AE601 1/AE601 AC1.0

7150 3' - 0" 7' - 0" 1 3/4" D5 WD ST-CLR F1 HM PT-2 2/AE601 1/AE601 FR-1 45 MIN AC4.0 1

7151 3' - 0" 7' - 0" 1 3/4" D1 WD ST-CLR F1 HM PT-2 2/AE601 1/AE601 4.0

7152 3' - 0" 7' - 0" 1 3/4" D1 WD ST-CLR F1 HM PT-2 2/AE601 1/AE601 1.0

7153 3' - 0" 7' - 0" 1 3/4" D5 WD ST-CLR F1 HM PT-2 2/AE601 1/AE601 MG-1 1.0

7154 3' - 0" 7' - 0" 1 3/4" D5 WD ST-CLR F1 HM PT-2 2/AE601 1/AE601 MG-1 1.0

7155 3' - 0" 7' - 0" 1 3/4" D5 WD ST-CLR F1 HM PT-2 2/AE601 1/AE601 MG-1 1.0

7156 3' - 0" 7' - 0" 1 3/4" D5 WD ST-CLR F1 HM PT-2 2/AE601 1/AE601 MG-1 1.0

7157 3' - 0" 7' - 0" 1 3/4" D5 WD ST-CLR F1 HM PT-2 2/AE601 1/AE601 MG-1 1.0

7158 3' - 0" 7' - 0" 1 3/4" D5 WD ST-CLR F1 HM PT-2 2/AE601 1/AE601 MG-1 1.0

7159 3' - 0" 7' - 0" 1 3/4" D1 WD ST-CLR F1 HM PT-2 2/AE601 1/AE601 4.1

C7A08 7' - 0" 7' - 0" 1 3/4" D6 WD ST-CLR F2 HM PT-2 6/AE601 5/AE601 FR-1 45 MIN AC5.0 1 (X2)

C7A10 7' - 0" 7' - 0" 1 3/4" D6 WD ST-CLR F2 HM PT-2 2/AE601 1/AE601 MG-1 AC5.1

C7A10A 4' - 0" 7' - 0" 1 3/4" D1 WD ST-CLR F1 HM PT-2 6/AE601 5/AE601 AC4.0 1

C7A11 7' - 0" 7' - 0" 1 3/4" D6 WD ST-CLR F2 HM PT-2 6/AE601 5/AE601 MG-1 2.0 1

C7A12 6' - 0" 7' - 0" 1 3/4" D6 WD ST-CLR F1 HM PT-2 2/AE601 1/AE601 MG-1 2.1

C7A13 6' - 0" 7' - 0" 1 3/4" D6 WD ST-CLR F1 HM PT-2 2/AE601 1/AE601 FR-1 45 MIN AC6.0 1, 2, 3

ST7-4 3' - 10" 7' - 0" 1 3/4" EXISTING EXISTING EXISTING EXISTING EXIST. EXISTING EXISTING EXISTING EXISTING EXISTING EXISTING 7.0

SCALE: 3" = 1'-0"AE601

1 DOOR JAMB DETAIL, HM

SCALE: 3" = 1'-0"AE601

2 DOOR HEAD DETAIL, HM

SCALE: 3" = 1'-0"AE601

6 DOOR HEAD DETAIL, HM DOUBLE EGRESS

SCALE: 3" = 1'-0"AE601

5 DOOR JAMB DETAIL, HM DOUBLE EGRESS

SCALE: 3" = 1'-0"AE601

3 DOOR HAMB DETAIL, ANTI-BARRICADE

SCALE: 3" = 1'-0"AE601

4 DOOR HEAD DETAIL, ANTI-BARRICADE

WINDOW SCHEDULE

TYPE MARK TYPE MATERIAL FINISH WIDTH HEIGHT

DETAIL

GLAZING COMMENTSHEAD JAMB SILL

A SLIDING TRANSACTION ALUM SATIN ANOD 4' - 0" 4' - 0" 9/AE601 9/AE601 MG-1 PROVIDE SFIC LOCK

B FIXED HM SATIN ANOD 4' - 0" 4' - 0" 111/AE601 11/AE601 11/AE601 MG-1

C FIXED HM SATIN ANOD 2' - 0" 4' - 0" 11/AE601 11/AE601 11/AE601 FR-1 45 MINUTE RATED

LOUVER SCHEDULE

MARK TAG

AIR

FLOW SIZE WxH FREE AREA PRESS. DROP (IN.

WG) BPWP (FT/MIN) MODEL MATERIAL FINISH(CFM) (IN x IN) (SF) (FT/MIN)

LV-1 44 x 66 10.09 1,077 *GREENHECK ESD-635" ALUM PAINT

LV-2 44 x 66 10.09 1,077 *GREENHECK ESD-635" ALUM PAINT

SCALE: 3" = 1'-0"AE601

9 SLIDING TRANSACTION WINDOW HEAD & SILL

SCALE: 3" = 1'-0"AE601

13 EXTERIOR LOUVER SECTION

SCALE: 3" = 1'-0"AE601

8 SLIDING DOOR HEADER DETAIL

SCALE: 3" = 1'-0"AE601

7 SLIDING DOOR SILL DETAIL

SCALE: 3" = 1'-0"AE601

10 SLIDING DOOR JAMB DETAIL

NO SCALEAE601

15 BOX HEADER DETAIL

Revisions: Date:

ADDENDUM 02 06/05/2020

SCALE: 3" = 1'-0"AE601

11 DETAIL - HM WINDOW JAMB

2 2