This document contains panelboard schedules and drawings for the modernization of Building 22 at the Ann Arbor VA Medical Center. The project includes work such as lighting, power, receptacles, equipment, and emergency systems. Specific panelboards are scheduled with circuit information, loads, locations and notes. Drawings show panel types, ratings, locations and branch circuiting. The federal opportunity pre-solicitation is to inform potential offerors of an upcoming IFB for the modernization project requiring construction services. Services include labor, materials, equipment and supervision to complete the project per drawings and specifications. Work must comply with codes, standards and manufacturer recommendations and be performed during normal business hours excluding federal holidays. The projected cost is between $5-10 million. The government intends to award a firm fixed price contract within 120 days of bid opening. The acquisition is 100% set aside for verified SDVOSBs. The solicitation will be issued on November 30, 2022 via SAM.gov and include bid documents, specifications, forms and drawings. Further solicitation details and dates will be provided then. Offerors should monitor SAM.gov and register in SAM and VIP databases to receive solicitation amendments. Questions may be sent to the listed contracting specialist by email only.
View the file
Other files for this federal contract opportunity
Show all 49
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
A u to d e s k D o c s /A n n A rb o r
V A
M o d e rn iz e B ld g
/F
F E
A n n A rb o r
M o d e rn iz e
B
M E
P rv t
/1
/2
:2
:0
P
M
E602
PANELBOARD SCHEDULES
09/02/2022 JB CLG
MODERNIZE BUILDING 22 506-21-102
ANN ARBOR, MICHIGAN
100% BID DOCUMENTS
ANN ARBOR
VAMC
Approved: Veteran's Affairs Medical Center
Notes:
Total Est. Demand: 7 A
Lighting 58 VA 100.00% 58 VA Total Conn.: 6 A
Power 180 VA 100.00% 180 VA Total Est. Demand: 2354 VA
Receptacle 720 VA 100.00% 720 VA Total Conn. Load: 2075 VA
Motor 1117 VA 125.00% 1396 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:
Total Amps: 5 A 4 A 9 A
Total Load: 552 VA 430 VA 1092 VA
41 Space -- 1 -- -- 1 -- Space 42
39 Space -- 1 -- -- 1 -- Space 40
37 Space -- 1 -- -- 1 -- Space 38
35 Space -- 1 -- -- 1 -- Space 36
33 Space -- 1 -- -- 1 -- Space 34
31 Space -- 1 -- -- 1 -- Space 32
29 Space -- 1 -- -- 1 -- Space 30
27 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 28
25 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 26
23 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 24
21 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 22
19 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 20
17 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 18
15 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 16
13 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 14
11 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 12
9 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 10
7 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 8
5 Receptacle 20 A 1 720 VA 372 VA -- -- -- 6
3 Lighting Room 04, 05 20 A 1 58 VA 372 VA -- -- -- 4
1 CONTROLS CIRCUIT 20 A 1 180 VA 372 VA 3 20 A 22-CP-1 2
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Notes:
Enclosure: Type 1
Mounting: Surface Wires: 4 Mains Rating: 225 A
Supply From: Phases: 3 Mains Type: MLO
Location: ELECTRIC SERVICE ROOM 04 Volts: 120/208 Wye A.I.C. Rating: 22,000 A
Branch Panel: 22-RB-1
Notes:
Total Est. Demand: 45 A
Total Conn.: 47 A
Lighting 3149 VA 100.00% 3149 VA Total Est. Demand: 16339 VA
Power 2520 VA 100.00% 2520 VA Total Conn. Load: 17009 VA
Receptacle 11340 VA 94.09% 10670 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:
Total Amps: 51 A 44 A 47 A
Total Load: 6091 VA 5338 VA 5580 VA
41 Space -- 1 -- -- 1 -- Space 42
39 Space -- 1 -- -- 1 -- Space 40
37 Space -- 1 -- -- 1 -- Space 38
35 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 36
33 Receptacle 20 A 1 180 VA 0 VA 1 20 A Spare 34
31 Power OPEN OFFICE G11 20 A 1 180 VA 180 VA 1 20 A Power OPEN OFFICE G11 32
29 Power OPEN OFFICE G11 20 A 1 180 VA 180 VA 1 20 A Power OPEN OFFICE G11 30
27 Power OPEN OFFICE G11 20 A 1 180 VA 180 VA 1 20 A Power OPEN OFFICE G11 28
25 Power OPEN OFFICE G11 20 A 1 180 VA 180 VA 1 20 A Power OPEN OFFICE G11 26
23 Power OPEN OFFICE G11 20 A 1 180 VA 180 VA 1 20 A Power OPEN OFFICE G11 24
21 Power OPEN OFFICE G11 20 A 1 180 VA 180 VA 1 20 A Power OPEN OFFICE G11 22
19 Power OPEN OFFICE G11 20 A 1 180 VA 0 VA 1 20 A Spare 20
17 Receptacle Room C1 20 A 1 1080... 180 VA 1 20 A Receptacle 18
15 Receptacle Room C5, C6 20 A 1 900 VA 180 VA 1 20 A CONTROLLED TEMPERATURE ROOM LTG 16
13 Receptacle OPEN OFFICE G11 20 A 1 180 VA 1080... 1 20 A Receptacle TELECOMM. G13 14
11 Receptacle VERAM OPEN OFFICE G06 20 A 1 1080... 720 VA 1 20 A Receptacle VERAM OPEN OFFICE G06 12
9 Receptacle Room G07 20 A 1 1260... 1080... 1 20 A Receptacle VERAM OFFICE/FUTURE EXAM G08 10
7 Receptacle EXAM G03 20 A 1 900 VA 900 VA 1 20 A Receptacle EXAM G04 8
5 Receptacle Room G01 20 A 1 900 VA 900 VA 1 20 A Receptacle EXAM G02 6
3 Lighting OPEN OFFICE A4 20 A 1 673 VA 345 VA 1 20 A Lighting Room C4, C5, C6, C2 4
1 Lighting Room G01, G02 20 A 1 1347... 784 VA 1 20 A Lighting Room G22, G16 2
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Notes:
Enclosure: Type 1
Mounting: Surface Wires: 4 Mains Rating: 225 A
Supply From: Phases: 3 Mains Type: MLO
Location: ELECTRIC ROOM G18B Volts: 120/208 Wye A.I.C. Rating: 22,000 A
Branch Panel: 22-R1-1
Notes:
Total Est. Demand: 16 A
Total Conn.: 16 A
Total Est. Demand: 5940 VA
Power 3240 VA 100.00% 3240 VA Total Conn. Load: 5940 VA
Receptacle 2700 VA 100.00% 2700 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:
Total Amps: 25 A 18 A 9 A
Total Load: 2880 VA 1980 VA 1080 VA
41 Space -- 1 -- -- 1 -- Space 42
39 Space -- 1 -- -- 1 -- Space 40
37 Space -- 1 -- -- 1 -- Space 38
35 Space -- 1 -- -- 1 -- Space 36
33 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 34
31 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 32
29 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 30
27 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 28
25 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 26
23 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 24
21 Power OPEN OFFICE A4 20 A 1 180 VA 0 VA 1 20 A Spare 22
19 Power OPEN OFFICE A4 20 A 1 180 VA 180 VA 1 20 A Power OPEN OFFICE A4 20
17 Power 20 A 1 180 VA 180 VA 1 20 A Power OPEN OFFICE A4 18
15 Power 20 A 1 180 VA 180 VA 1 20 A Power 16
13 Power OPEN OFFICE A4 20 A 1 180 VA 180 VA 1 20 A Power 14
11 Power 20 A 1 180 VA 180 VA 1 20 A Power 12
9 Power OPEN OFFICE A4 20 A 1 180 VA 180 VA 1 20 A Power OPEN OFFICE A4 10
7 Power OPEN OFFICE A4 20 A 1 180 VA 180 VA 1 20 A Power OPEN OFFICE A4 8
5 Power SHARED OFFICE A7 20 A 1 180 VA 180 VA 1 20 A Power SHARED OFFICE A7 6
3 Receptacle OPEN OFFICE A4 20 A 1 720 VA 360 VA 1 20 A SHARED OFFICE A7 4
1 Receptacle OFFICE A5 20 A 1 900 VA 900 VA 1 20 A Receptacle OFFICE A6 2
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Notes:
Enclosure: Type 1
Mounting: Surface Wires: 4 Mains Rating: 225 A
Supply From: Phases: 3 Mains Type: MLO
Location: ELECTRIC ROOM G18B Volts: 120/208 Wye A.I.C. Rating: 22,000 A
Branch Panel: 22-R1-2
Notes:
Total Est. Demand: 30 A
Total Conn.: 30 A
Power 2340 VA 100.00% 2340 VA Total Est. Demand: 10845 VA
Receptacle 8280 VA 100.00% 8280 VA Total Conn. Load: 10800 VA
Motor 180 VA 125.00% 225 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:
Total Amps: 38 A 29 A 24 A
Total Load: 4500 VA 3420 VA 2880 VA
41 Space -- 1 -- -- 1 -- Space 42
39 Space -- 1 -- -- 1 -- Space 40
37 Space -- 1 -- -- 1 -- Space 38
35 Space -- 1 -- -- 1 -- Space 36
33 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 34
31 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 32
29 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 30
27 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 28
25 Power LAB G36 20 A 1 180 VA 180 VA 1 20 A Motor CYLINDER STORAGE G34 26
23 Power LAB G36 20 A 1 180 VA 180 VA 1 20 A Power LAB G36 24
21 Drinking Fountain 20 A 1 180 VA 180 VA 1 20 A Lektriever 22
19 Fume Hood 20 A 1 180 VA 180 VA 1 20 A Fume Hood 20
17 Receptacle 20 A 1 720 VA 360 VA 1 20 A Receptacle Room G09, G05 18
15 Receptacle Room G12 20 A 1 720 VA 540 VA 1 20 A Receptacle MICROSCOPE G10 16
13 Power PRIVATE LAB G22 20 A 1 360 VA 540 VA 1 20 A Receptacle VMU BEHAVIOR ROOM G16 14
11 Power LAB G21 20 A 1 180 VA 180 VA 1 20 A Power LAB G21 12
9 Power LAB G21 20 A 1 180 VA 360 VA 1 20 A Power CONTROLLED TEMPERATURE ROOM... 10
7 Power LAB G21 20 A 1 180 VA 900 VA 1 20 A Receptacle Room G21 8
5 Receptacle 20 A 1 360 VA 720 VA 1 20 A Receptacle 6
3 Receptacle OFFICE G24 20 A 1 900 VA 360 VA 1 20 A Receptacle 4
1 Receptacle OFFICE G23 20 A 1 900 VA 900 VA 1 20 A Receptacle OFFICE G26 2
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Notes:
Enclosure: Type 1
Mounting: Surface Wires: 4 Mains Rating: 225 A
Supply From: Phases: 3 Mains Type: MLO
Location: ELECTRIC ROOM G18A Volts: 120/208 Wye A.I.C. Rating: 22,000 A
Branch Panel: 22-R1-3
Notes:
Total Est. Demand: 4 A
Total Conn.: 4 A
Lighting 1047 VA 100.00% 1047 VA Total Est. Demand: 1407 VA
Receptacle 360 VA 100.00% 360 VA Total Conn. Load: 1407 VA
Other 0 VA 0.00% 0 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:
Total Amps: 8 A 2 A 1 A
Total Load: 997 VA 232 VA 178 VA
41 Space -- 1 -- -- 1 -- Space 42
39 Space -- 1 -- -- 1 -- Space 40
37 Space -- 1 -- -- 1 -- Space 38
35 Space -- 1 -- -- 1 -- Space 36
33 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 34
31 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 32
29 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 30
27 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 28
25 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 26
23 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 24
21 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 22
19 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 20
17 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 18
15 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 16
13 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 14
11 Lighting TELECOMM. G13 20 A 1 58 VA 0 VA 1 20 A Spare 12
9 FACP 20 A 1 0 VA 112 VA 1 20 A Lighting Room S1-1, S1-2, 01 10
7 -- -- -- 60 VA 60 VA -- -- -- 8
5 -- -- -- 60 VA 60 VA -- -- -- 6
3 DATA RACK RECEPT. 30 A 3 60 VA 60 VA 3 30 A DATA RACK RECEPT. 4
1 EGRESS LIGHTING 20 A 1 526 VA 351 VA 1 20 A EGRESS LIGHTING 2
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Notes:
Enclosure: Type 1
Mounting: Surface Wires: 4 Mains Rating: 100 A
Supply From: Phases: 3 Mains Type: MCB
Location: ELECTRIC ROOM G18A Volts: 120/208 Wye A.I.C. Rating:
Branch Panel: 22-EM1
EMERGENCY
09/02/2022 No. Revisions: Date:
100% BID DOCUMENTS 09/02/2022
1 ADDENDUM 01 02/14/2023
Notes:
Lighting 261 VA 100.00% 261 VA Total Est. Demand: 79 A
Power 360 VA 100.00% 360 VA Total Conn.: 74 A
Receptacle 720 VA 100.00% 720 VA Total Est. Demand: 28532 VA
Motor 25390 VA 107.09% 27191 VA Total Conn. Load: 26731 VA
Equipment 0 VA 0.00% 0 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:
Total Amps: 71 A 71 A 81 A
Total Load: 8522 VA 8529 VA 9681 VA
53 Space -- 1 -- -- 1 -- Space 54
51 Space -- 1 -- -- 1 -- Space 52
49 Space -- 1 -- -- 1 -- Space 50
47 Space -- 1 -- -- 1 -- Space 48
45 Space -- 1 -- -- 1 -- Space 46
43 Space -- 1 -- 0 VA 1 20 A Spare 44
41 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 42
39 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 40
37 38
35 36
33 Motor MECHANICAL PENTHOUSE R01 20 A 1 168 VA 34
31 Power MECHANICAL PENTHOUSE R01 20 A 1 360 VA 672 VA -- -- -- 32
29 Perchloric Acid Fan Motor 20 A 1 1920... 672 VA -- -- -- 30
27 GWH-1 20 A 1 600 VA 672 VA 3 20 A 22-AHU-3-RF 28
25 -- -- -- 2402... 261 VA 1 20 A Lighting MECHANICAL PENTHOUSE R01 26
23 -- -- -- 2402... 728 VA -- -- -- 24
21 22-AHU-3-SF 30 A 3 2402... 728 VA 2 15 A ACCU-2 22
19 -- -- -- 480 VA 480 VA -- -- -- 20
17 -- -- -- 480 VA 480 VA -- -- -- 18
15 22-P-1A 20 A 3 480 VA 480 VA 3 20 A 22-P-1B 16
13 Receptacle 20 A 1 720 VA 180 VA 1 20 A 22-EF-4 14
11 -- -- -- 728 VA 685 VA -- -- -- 12
9 ACCU-1 15 A 2 728 VA 685 VA -- -- -- 10
7 22-EF-2 20 A 1 696 VA 685 VA 3 20 A 22-EF-5 8
5 -- -- -- 1585... 0 VA -- -- -- 6
3 -- -- -- 1585... 0 VA -- -- -- 4
1 VP-1 20 A 3 1585... 0 VA 3 20 A Existing Air Compressor 2
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Notes:
Enclosure: Type 1 MCB Rating: 1 A
Mounting: Surface Wires: 4 Mains Rating: 400 A
Supply From: Phases: 3 Mains Type: MLO
Location: MECHANICAL PENTHOUSE... Volts: 120/208 Wye A.I.C. Rating: 22,000 A
Branch Panel: 22-R3-1