This document contains a pre-solicitation notice and mechanical drawings for a federal construction project. The Department of Veterans Affairs intends to solicit bids for the modernization of Building 22 at the LTC Charles S. Kettles Veterans Medical Center in Ann Arbor, Michigan, with construction services required between approximately $5-10 million. The project involves mechanical system upgrades and compliance with manufacturer and code standards. The solicitation is planned for release on November 30th, 2022 via SAM.gov and is a 100% set-aside for qualified Service-Disabled Veteran-Owned Small Businesses. Bids are due by a date to be specified in the forthcoming solicitation. The work must be completed during normal daytime business hours excluding federal holidays.
View the file
Other files for this federal contract opportunity
Show all 49
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
NOTE:
1. SIZE WATER FILTER FOR 5%
OF TOTAL SYSTEM FLOW
1/2" [15mm]
WATER
FILTER
PRESSURE
GAUGE
LOW POINT
DRAIN
AUTOMATIC FLOWCONTROL
DEVICE SEE NOTE 2
DRAIN
CONNECTION
T O
P U
M P
S U
C T
IO
N
F R
O M
P U
M P
D
IS
C H
A R
G E
NOTE:
TOP OF CHEMICAL POT FEEDER
TANK SHALL NOT BEMORE THAN
4'-0" [1200mm]ABOVE FINISHED
FLOOR.
1" [25mm]
CHEMICAL POT
FEEDER- MINIMUM
CAPACITY 5 GALLONS
[19L]
1" [25mm]
FUNNEL
3/4" [20mm]
TO
DRAIN
F R
O M
P U
M P
D
IS
C H
A R
G E
T O
P U
M P
S U
C T
IO
N
AUTOMATIC FLOW
CONTROL AND
BALANCE DEVICE
DESIGNER'S NOTE:
1. USE THIS DETAIL FOR UNIT MOUNTED PREHEAT COIL.
2. EDIT DETAIL FOR LOW PRESSURE STEAM, IF NECESSARY.
MPS
MPR
INTEGRAL FACE AND
BYPASS DAMPER
FLOAT AND THERMOSTATIC
TRAP ASSEMBLY
SPRING LOADED VACUUM BREAKER
VENTED TO ATMOSPHERE TYPICAL
ON BOTH THE STEAM SUPPLY AND
THE CONDENSATE LINES.
FLEXIBLE CONNECTOR INSTALLED PARALLEL
TO COIL HEADER AND AS CLOSE AS POSSIBLE
TO COIL CONDENSATE CONNECTION.
ON/OFF
CONTROL VALVE
VB
207kPA
(30 PSIG)
VB
SINGLE COIL
WATER COIL
AIR VENT WHEN
COIL IS NOT
SELF-VENTING
DRAIN WHEN COIL IS NOT
SELF-DRAINING
TEST PLUG
(TYP.)
PIPE HANGER SHALL SUPPORT
PIPING INDEPENDENT OF COIL
REDUCER, IF REQUIRED
DRAIN
WATER COIL
AIR VENT WHEN
COIL IS NOT
SELF-VENTING
TEST PLUG
(TYP.)
PIPE HANGER SHALL SUPPORT
PIPING INDEPENDENT OF COIL
WATER COIL
REDUCER, IF REQUIRED
DRAIN WHEN COIL IS
NOT SELF-DRAINING
DRAIN
DOUBLE COIL
NOTES:
1. PIPING SHALL BE INSTALLED IN SUCH MANNER THAT IT WILL NOT BLOCK THE SWING OR USE OF ACCESS DOORS OR
PANELS; NEITHER SHALL IT BLOCK THE SERVICING OF FILTERS, VALVES, OR EQUIPMENT.
MV
MV
MV
MV
MV
MV
MV
CALIBRATED BALANCING
VALVE (TYP.)
MV
OR
AV
TYPICAL MANUAL AIR VENT
TYPICAL CHILLED AND HOT WATER
PIPING DRAIN VALVE CONNECTIONS
THREADED PIPING
ELEVATION
WELDED PIPING
ELEVATION
TYPICAL WATER PIPING
REDUCER, IF
REQUIRED
3/4" [20mm] BALL VALVE
ADAPTER TO 3/4" [20mm] HOSE
THREAD-PROVIDE HOSE CAP NUT
NOTES:
1. DRAIN ALL LOW POINTS AS INDICATED ABOVE.
2. WHERE SCALE POCKETS ARE SHOWN ON PIPE RISER DIAGRAMS AND/OR
PLANS LOCATE DRAIN AT BOTTOM OF SCALE POCKET.
AIR VENT
1/2" [15mm]
BALL VALVE
1/4" [8mm]
COPPER TUBING
1/2" [15mm] x 4" [100mm]
NIPPLE
CIRCULATING
WATER PIPING
ELEVATION
NOTES:
1. VENT ALL HIGH POINTS INDICATED ABOVE.
2. IF AUTOMATIC AIR VENTS ARE USED, PIPE DISCHARGE TO DRAIN.
DRAW THRU
BLOW THRU
2" [50mm]
PLUS X
1" [25mm]
MINIMUM
X
2X
UNIT TYPE A B
WHERE X = STATIC PRESSURE IN PAN
DRAIN LINE SHALL BE AT LEAST THE SAME SIZE
AS THE NIPPLE ON THE DRAIN PAN PIPING SHALL
BE RIGID COPPER TYPE L OR TYPE M UNLESS
NOTE BELOW IS MET
PITCH DOWN
TOWARD DRAIN
CLEAN OUT
FLOOR SINK
DRAIN
PAN
DIELECTRIC
FITTING
NOTE:
1. CPVC PIPE MAY BE USED ONLY IF APPROVED BYLOCAL VA AND IS
INDOORS AND DOES NOT PASS THROUGHRATED BARRIERS.
2. DIELECTRIC FITTING TO BE USED WHEN TWO DISSIMILARMETALS ARE
TO BE CONNECTED.
B A
1" [2
5m m
MV
COIL
TEST PLUG (TYP.)
REDUCER, IF REQUIRED
WATER RETURN
MANUAL AIR VENT
UNION CONNECTIONS (TYP.)
WATER SUPPLY
SHUT OFF VALVE
DRAIN WITH HOSE CONNECTION
MODULATION CONTROL VALVE
BALANCING VALVE
NOTES:
1. PIPING ARRANGEMENT ALSO APPLIES TO SMALL COILS FOUND IN FAN COIL
UNITS.
PIPE HANGERS - PROVIDE DOUBLE DEFLECTION
NEOPRENE (TYPE HN) FOR FIRST TWO ON EACH
SIDE OF PUMP (SEE NOTE NO. 1)
PRESSURE GAGE
1/2" [15mm]
STRAINERFLEXIBLE
CONNECTIONBALL OR
BUTTERFLY TYP.
NOTES:
1. SUPPORT PUMP FROM PIPING ONLY. DO NOT SUPPORT PUMP FROM MOTOR.
INSULATION
BOLT (TYPICAL)
FLOOR
SLAB
FIRE-STOPPING
MATERIAL
BOLT
PIPE
PIPE SLEEVE
WHERE SPECIFIED
RISER
CLAMP
PIPE
PIPE SLEEVE WHERE
SPECIFIED RISER CLAMP. BOTTOM
CLAMP REQUIRED AT
ANCHOR POINTS ONLY.
ELEVATION
PLAN
RISER CLAMP
NOTES:
1. PROVIDE ANCHORS ONLY WHERE SHOWN ON
DRAWINGS.
2. EXTEND SLEEVE ABOVE FLOOR WHERE SPECIFIED.
STEEL EXPANSION SHIELD FOR EXISTING CONSTRUCTION
AND INSERTS FOR NEW CONSTRICTION THIS TYPE SHALL
BE USED ONLY IN SLABS OR BEAMS OF 4" [100mm] MIN
DEPTH
3/8" [10mm] MIN DIA EXPANSION BOLTS FOR
EXISTING CONSTRUCTION AND INSERTS FOR NEW
CONSTRUCTION
CONCRETE
FLOOR SLAB
CLIP
ANGLE
NUTS & WASHERS
3/8" [10mm] MIN DIA
HANGER RODS
FOR PIPES UNDER 2" [50mm] IN SIZE USE 1-1/2"x1-1/2"x1/4" [40x40x6.4mm] ANGLE. ALL PIPES 2" [50mm] & LARGER USE 3"x3"x1/4" [75x75x6.4mm] ANGLE
TURNBUCKLE
3/8" [10mm] MIN DIA
HANGER RODS
3/8" [10mm] MIN DIA INSERTS
NEW CONSTRUCTION ONLY.
DUCT RISER - SEE FLOOR
PLANS FOR SIZES
WALL
ANCHOR
Y
X
Y
FASTENER, TYP.
FIGURE A
FIGURE A - SUGGESTED SIZING
DUCT SIZE BAND SIZE
BAND
18"x12" 1 1/2"x16 GA.
24"x20" 1"x1/8"
DUCT GAGE
28, 26
24, 22, 20
18, 16
ALLOWABLE LOAD
PER FASTENER (1,2)
25 lb
35 lb
50 lb
1. WELD, BOLT OR NO.8 SCREW (MIN.)
DEVIATION PERMITTED BY OTHER
ANALYSIS. X=1", Y=2"; ADD OTHERS TO
ACCOMODATE LOAD. MINIMUM OF 3 ON
24" WIDTH AND UP. ADD ALONG SIDES
NEAREST ANCHORS.
2. FASTENING METHOD FOR WELDED
STAINLESS STEEL DUCTWORK SHALL BE
WELD.
DUCT RISER - SEE FLOOR
PLANS FOR SIZES
WALL
ANCHOR
Y
X
Y
FASTENER, TYP.
FIGURE B
ANCHOR, TYP.
SEE SMACNA KNEE BRACKET TABLES IN THE
ROUND INDUSTRIAL STANDARDS.
FASTENER, TYP.
FIGURE B - SUGGESTED SIZING
DUCT SIZE ANGLE SIZE
30"x12" 1"x1"x1/8"
36"x18"
42"x24"
48"x30"
1"x1"x1/8"
1 1/4"x1 1/4"x1/8"
1 1/4"x1 1/4"x1/8"
NOTES:
1. NOTES APPLY TO FIGURE A AND B.
2. BRACKETS ARE SIZED FOR 12 FEET OF DUCT, MAXIMUM.
3. LOCATE DUCTS AGAINST WALL OR MAXIMUM OF 2" AWAY FROM
WALL.
4. EACH WALL ANCHOR SHALL SATISFY THE FOLLOWING CRITERIA
UNLESS OTHER ANALYSIS IS MADE:
A. TENSILE LOAD = 3/8 x DUCT WEIGHT; SAFETY FACTOR 4.
B. SHEAR LOAD x 1/2 x DUCT WEIGHT; SAFETY FACTOR 4.
WALL
STEAM
CONDENSATE
RETURN
TEMPERATURE
SENSOR
SCALE POCKET. 6" DEEP TYP.
STEAM SEPARATOR
STEAM SUPPLY
CONTROL VALVE
DUCT CROSS SECTION
INVERTED BUCKET
TRAP ASSEMBLY
NOTE:
SEE MANUFACTURER'S PIPING RECOMMENDATIONS FOR FINAL LAYOUT
STEAM DISTRIBUTION
PANEL
TERMINATE ABOVE
FLOOR DRAIN
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
A u to d e s k D o c s /A n n A rb o r
V A
M o d e rn iz e B ld g
/F
F E
A n n A rb o r
M o d e rn iz e
B
M E
P rv t
/1
/2
:2
:5
P
M
M503
MECHANICAL DETAILS
09/02/2022 KF JG
MODERNIZE BUILDING 22 506-21-102
ANN ARBOR, MICHIGAN
100% BID DOCUMENTS
ANN ARBOR
VAMC
Approved: Veteran's Affairs Medical Center
NTS
WATER FILTERS - CLOSED LOOP HYDRONIC SYSTEMS
NTS
WATER TREATMENT - CLOSED SYSTEMS
NTS
INTEGRAL FACE AND BYPASS STEAM COIL DETAIL
NTS
WATER COILS - PIPING CONNECTIONS
NTS
DRAIN VALVE AND AIR VENT CONNECTIONS (HYDRONIC SYSTEMS)
NTS
AIR HANDLING UNIT DRAIN TRAP DETAIL
NTS
TERMINAL UNIT WATER COILS - PIPING CONNECTIONSNTS
IN-LINE PUMPS - CONNECTIONS
NTS
SUPPORT/ANCHOR FOR PIPE RISERS
NTS
SECURING HANGER RODS IN CONCRETE
NTS
DUCT RISER SUPPORTS - WALL
NTS
STEAM HUMIDIFIER - PIPING CONNECTIONS
No. Revisions: Date:
100% BID DOCUMENTS 09/02/2022
1 ADDENDUM 01 02/14/2023
09/02/2022
| Sheets |
| M503 - MECHANICAL DETAILS |