Drawing 11.17_PL501 - PLUMBING DETAILS.pdf
PDF 829 KB Posted
- Attached to
- Z1DA--Modernize Building 22 506-21-102 Federal contract opportunity
- Solicitation number
- 36C25023B0005
About this file
This document contains a pre-solicitation announcement and construction drawings for a federal contract opportunity. The Department of Veterans Affairs intends to solicit bids for a project to modernize Building 22 at the LTC Charles S. Kettles Veterans Administration Medical Center in Ann Arbor, Michigan. The project scope includes all necessary labor, tools, materials and equipment to complete construction in accordance with manufacturer recommendations, codes and standards. Work is to be performed during normal business hours excluding federal holidays. The NAICS code is 236220 for commercial and institutional building construction, with a small business size standard of $16.5 million. The estimated value is between $5-10 million. The government intends to award a firm fixed price contract within 120 days of bid opening. This is a 100% set-aside for qualified Service-Disabled Veteran Owned Small Businesses. The pre-solicitation notice provides details on registration requirements, with the full solicitation to be posted on November 30, 2022 on SAM.gov. The construction drawings include plumbing details for the project.
View the file
Other files for this federal contract opportunity
Show all 49
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
[2100]
NOM. SIZE
PIPE
TUBING
IN.
[mm]
FT.
[mm]
FT.
[mm]
SIDE VIEW TRAPEZE HANGER FOR UP
TO 1000 LB. [453KG] UNIFORM LOAD
ADJUSTABLE CLEVIS
HANGER TYPE 1 - SEE
SPECIFICATIONS
PROVIDE INSULATION SHIELD &
INSERT FOR ALL PIPING (8"
[200mm] MIN.)
BAND
1-5/8" [43mm] 12 GAUGE CHANNEL OR 2"x2"x1/4" [50x50x6.4mm] ANGLE
1/2" [15mm] DIA. HANGER RODS WITH 36" [900mm] MAX. SPACING ON EACH
CHANNEL
WELD
SADDLE
INSULATION SHIELD AT
HANGER
PROVIDE HIGH COMPRESSIVE
STRENGTH INSULATION (9 PSF MIN.
DENSITY) UNDER INSULATION
SHIELD
INSULATION (VAPOR BARRIER TYPE
IS REQUIRED FOR LOW
TEMPERATURE PIPE)
HANGER ROD
MAXIMUM PIPE/TUBING SUPPORT SPACING
NOTE: FOR TRAPEZE HANGER TAKE SPACING OF SMALLEST SIZE ON TRAPEZE.
[2 5m m
1" M
A X
NOTES:
SEE SPECIFER FOR DETAILED
HANGER REQUIREMENTS
ADJUSTABLE CLEVIS
HANGER TYPE 43 - SEE
SPECIFICATIONS
THRU 3/4
THRU [20]
5 FT
[1500]
[25]
[2100]
[1800]
1 1/4 [32]
[2100]
[2100]
1 1/2 [40]
[2700]
[2400]
[50]
[3000]
[2400]
2 1/2 [65]
[3400]
[2700]
[75]
[3700]
[3000]
[100]
[4100]
[3700]
[125]
[4900]
[4000]
[150]
[200]
[250]
[300]
[350]
[400]
[450]
[500]
[600]
[5200]
[5800]
[4100]
[4900]
[6700]
[7000]
[7600]
[8200]
[8500]
[9100]
[9600]
STEEL EXPANSION SHIELD FOR EXISTING CONSTRUCTION
AND INSERTS FOR NEW CONSTRICTION THIS TYPE SHALL
BE USED ONLY IN SLABS OR BEAMS OF 4" [100mm] MIN
DEPTH
3/8" [10mm] MIN DIA EXPANSION BOLTS FOR
EXISTING CONSTRUCTION AND INSERTS FOR NEW
CONSTRUCTION
CONCRETE
FLOOR SLAB
CLIP
ANGLE
NUTS & WASHERS
3/8" [10mm] MIN DIA
HANGER RODS
FOR PIPES UNDER 2" [50mm] IN SIZE USE 1-1/2"x1-1/2"x1/4" [40x40x6.4mm] ANGLE. ALL PIPES 2" [50mm] & LARGER USE 3"x3"x1/4" [75x75x6.4mm] ANGLE
TURNBUCKLE
3/8" [10mm] MIN DIA
HANGER RODS
3/8" [10mm] MIN DIA INSERTS
NEW CONSTRUCTION ONLY.
FLOOR
GWH-1
DRAIN PAN, DRAIN TO
NEAREST FLOOR DRAIN
TEMPERATURE & PRESSURE RELIEF VALVE
BY MANUFACTURER OF DOMESTIC WATER
HEATER, ROUTE TO DRAIN PAN
THERMOMETER
NOTES:
1. SEE PLUMBING DRAWINGS FOR PIPING & DUCT CONTINUATIONS.
2. REFER TO SHEET PL-601 FOR GWH-1, DWHRP-1, ET-1, AND GPR-17 SCHEDULES.
3. REFER TO NATURAL GAS SCHEMATIC DIAGRAM ON SHEET PL602 FOR NATURAL GAS CONNECTION TO WATER HEATER.
CONCRETE EQUIPMENT PAD
DRAIN
TO EXTERIOR
ET-1
1-1/2" DCW
1-1/2" DHW
3/4" DHWR
DHWRP-1
GPR-17
3/4" G
4" DIAMETER EXHAUST AIR
DUCT
4" DIAMETER INTAKE AIR
DUCT
MINIMUM 16 GAGE GALVANIZED STEEL
PLATE 12"x48" [300x1200mm] MIN.
SECURED TO A MIN. 4 STUDS PER
LAVATORY
1/4" [6mm]∅ MOLLY BOLT HOLLOW WALL
ANCHOR (1 EA. SIDE OF LAV)
MIN. (3) 1/4" [6mm]
MACHINE BOLTS
W/DOUBLE LOCK NUTS
ON BACK SIDE
MIN. 5 1/4" [131mm]∅
GALV. MACHINE BOLTS
WELDED TO PLATE
1/4" [6mm]
TYP. 1/8"
TYP. [3mm]
A A
PLAN
SECTION A
NOTES:
1.
2.
AT LAVS WITH FOOT PEDAL CONTROLS PROVIDE
AN ADDITIONAL 16 GAGE GALVANIZED STEEL
PLATE 12"x16" [300x600mm] SECURED TO A
MINIMUM OF 2 STUDS PER FOOT PEDAL.
PROVIDE 20 GAGE STUDS WHEN HEIGHT
EXCEEDS 12'-0" [3600mm]
STEEL HANGER BY LAV MFGR
STEEL WALL PLATE
WALL ANCHOR
STUDS
FOR FIXTURE
HEIGHT SEE
ARCHITECTURAL
DRAWINGS
V A
R
IE
S
3' -3
[9 m m
T
O F
LO
O
R
EXTERIOR SIDE OF CONCRETE WALL
1/4" [6mm] STEEL PLATE WATER STOP & ANCHOR
COLLAR
[5 0m m
FLEXIBLE EXPANSION JOINT
MIN. DEFLECTION 15" [375mm] MIN. EXPANSION 4" [100mm]
RESILIENT
WATERPROOF
CAULKING
5/8" [16mm] ROD
WELD
PIPE CENTERED
IN SLEEVE
1/4"x1/4" [6x6mm]
IRON PIPE CLAMP
STANDARD
WEIGHT GAL.
STEEL PIPE SLEEVE
1/4"x1/4" [6x6mm]
IRON PIPE STRAP
MODULAR TYPE WALL
PENETRATION SEAL
FLANGED
CONNECTION
[1 m m
INTERIOR SIDE OF
WALL
STAINLESS STEEL BOLTS,
NUTS & WASHERS
INSULATION
BOLT (TYPICAL)
FLOOR
SLAB
FIRE-STOPPING
MATERIAL
BOLT
PIPE
PIPE SLEEVE
WHERE SPECIFIED
RISER CLAMP
PIPE
PIPE SLEEVE WHERE
SPECIFIED RISER CLAMP. BOTTOM
CLAMP REQUIRED AT
ANCHOR POINTS ONLY.
ELEVATION
PLAN
RISER CLAMP
NOTES:
1. PROVIDE ANCHORS ONLY WHERE SHOWN ON
DRAWINGS.
2. EXTEND SLEEVE ABOVE FLOOR WHERE SPECIFIED.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
A u to d e s k D o c s /A n n A rb o r
V A
M o d e rn iz e B ld g
/F
F E
A n n A rb o r
M o d e rn iz e
B
M E
P rv t
/2
/2
:4
:3
A M
PL501
PLUMBING DETAILS
09/02/2022 PP GP
MODERNIZE BUILDING 22 506-21-102
ANN ARBOR, MICHIGAN
100% BID DOCUMENTS
ANN ARBOR
VAMC
Approved: Veteran's Affairs Medical Center
NTS
PIPE HANGERS
NTS
SECURING HANGER RODS IN CONCRETE
NTS
NATURAL GAS WATER HEATER (GWH-1) DETAIL
NTS
LAVATORY MOUNTING
NTS
PIPE PENETRATION THROUGH WALLS BELOW GRADE
NTS
SUPPORT/ANCHOR FOR PIPE RISERS
No. Revisions: Date:
100% BID DOCUMENTS 09/02/2022
2 ADDENDUM 02 03/02/2023
09/02/2022
| Sheets |
| PL501 - PLUMBING DETAILS |
File details come from the government source that posted it. Updated .