B09_Attachment_49_-_E15_REV_0007.pdf
PDF 89 KB Posted
- Solicitation number
- 140P2024R0114
About this file
This document appears to be an enlarged electrical plan and section for the Kilauea Visitor Center (KVC) project at Hawaii Volcanoes National Park. The key details are:
The project involves replacing the existing single-phase warehouse building PV panel, inverters, and wireway with a new three-phase system. This includes replacing the existing generator building panel, adding a new PV rapid shut down, expanding the generator building, installing a new standby automatic transfer switch, diesel generator, and main service switchboard. The existing single-phase switchboard will be removed and replaced with a new three-phase switchboard. New PV inverters and wireway will also be installed. Additionally, the project calls for modifying the existing shop building electrical system to connect to the new main distribution panel. The document provides detailed electrical plans and specifications for these upgrades and replacements.
View the file
Other files
Show 40 more
Latest 50 of 72 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
A T
S
JJJ
J
J J
J
J
J
F
REMOVE EXISTING SINGLE PHASE
WAREHOUSE BUILDING PV PANEL,
INVERTERS AND WIREWAY,
REPLACE WITH NEW THREE PHASE
EXISTING
SHOPS
BUILDING
EXISTING
GENERATOR
BUILDING
PANEL 'PVS'
F
NEW PV RAPID SHUT DOWN
13' GENERATOR
BLDG. EXPANSION NEW STANDBY AUTOMATIC
TRANSFER SWITCH
NEW DIESEL
GENERATOR
NEW MAIN SERVICE
SWITCHBOARD 'MDP'.
REMOVE EXISTING
SWITCHBOARD
NEW PV INVERTERS
AND WIREWAY
BATTERY CHARGER
WATER JACKET HEATER
FUEL COOLER
MOTORIZED
LOUVERS
PANEL 'GEN'
GEN-6.
GEN-8.
GEN-5.
G E
N -7
G E
N -2
,4
G E
N -1
GEN-3. GEN-11.
GEN-13.
G E
N -1
GEN-10.
G E
N -1
(E) LG UNIT
NEW EF-3
NEW UNDERGROUND
SERVICE, SEE SITE
ELECTRICAL PLAN
F
NEW PV RAPID SHUT-
DOWN SWITCH
G G
GEN-10.
G E
N -1
.W
GENERATOR
EMERGENCY
SHUT-DOWN
PUSH-BUTTON
(E)
(E)
GEN-10.
G G
GEN-10.
EXISTING AM RADIO, RECONNECT
TO NEW PANEL 'GEN'
GEN-14.
'ZL1''ZL1''ZL1'
'ZL1' 'ZL1' 'ZL1' 'ZL1'
'ZL1'
EM
EM
EM
EM
EM
EM
'ZL_', INTEGRAL
OCCUPANCY
SENSOR
EMLV$
L V
L V
'ZL_'
INTEGRAL
OCCUPANCY
SENSOR
7 7
OF
PMIS/PKG NO.
DRAWING NO.SUB SHEET NO.
HAWAII VOLCANOES NATIONAL PARK
KILAUEA VISITOR CENTER
DESIGNED:
CADD:
TECH REVIEW:
DATE:
187007
SHEET
HAVO 305150B
SCALE IN FEET
/1 /2
:4 :2 P M
C R e v it P r o je c t s \M
E P H A V O K V C R r a y m o n d c 1.
r v t
E15E15E15E15
ENLARGED PLANS ANDENLARGED PLANS ANDENLARGED PLANS ANDENLARGED PLANS AND
SECTIONS SECTIONS SECTIONS SECTIONS −−−− ELECTRICALELECTRICALELECTRICALELECTRICAL
MJ,DO
HN, DO
MO
05/24/2024
SCALE: 1/4" = 1'-0"E15
1 EXISTING GENERATOR & WAREHOUSE BLDG MODIFICATIONS - POWER
0 2' 4' 8'
SHEET KEYNOTES
1. REPLACEMENT PANELBOARD. REMOVE
EXISTING PANELBOARD AND INSTALL
NEW PANELBOARD IN ITS PLACE.
NOTE - NEW PANELBOARD IS LARGER
THAN THE EXISTING PANELBOARD, SO
MODIFICATIONS FOR THE NEW
PANELBOARD TO FIT WILL BE
REQUIRED.
2. REPLACEMENT PV INVERTER. REMOVE
EXISTING INVERTER AND INSTALL NEW
INVERTER IN ITS PLACE. NOTE - NEW
INVERTER IS LARGER THAN THE
EXISTING INVERTER, SO
MODIFICATIONS FIR THE NEW
INVERTER TO FIT WILL BE REQUIRED.
3. ADJUST LOCATION OF EXISTING
RECEPTACLE IF NEEDED, RECONNECT
TO EXISTING SHOP PANEL. REPLACE
EXISTING SURGE SUPPRESSOR WITH
NEW THREE PHASE SURGE
SUPPRESSOR.
4. REMOVE EXISTING SINGLE PHASE
MAIN SWITCHBOARD AND REPLACE
WITH NEW 3 PHASE SWITCHBOARD
'MDP'.
5. REMOVE EXISTING SINGLE PHASE
GENERATOR LOAD CENTER AND
AUTOMATIC TRANSFER SWITCH
REPLACE IN PLACE WITH NEW 3
PHASE PANEL 'GEN' (LOCATE TO
MAINTAIN CODE CLEARANCE IN FRONT
OF NEW PANEL).
6. EXISTING SHOP BUILDING TO REMAIN.
SEE ONE-LINE DIAGRAM FOR
CONNECTION TO NEW MAIN
DISTRIBUTION PANEL.
7. PROVIDE INTEGRAL EMERGENCY
BATTERY BALLAST. IOTA ILB CP10
SERIES OR EQUAL.
8. PROVIDE ENGRAVED LABEL FOR SHUT
DOWN SWITCH.
9. GFCI PROTECTION PROVIDED BY
BREAKER. SEE SPECIFICATIONS FOR
RECEPTACLE TYPE.
SCALE: 1/4" = 1'-0"E15
2 GENERATOR BLDG - LIGHTING
markj Cloud markj Cloud
| Sheets |
| E15 - ENLARGED PLANS AND SECTIONS - ELECTRICAL |