USAID/EHIP
New Health Center Construction Task Order 8, Combined RFI Log
Durame Site 202 Batu Site 251 Gimbichu Site 208 Arsi Negele Site 277 Waka Site 213 Meki Site 290
RFI No. Date Rec'd Item No. Question TT Response Response Date Follow-up
Durame 00011
16-May-14 1 On the Site Utilities Plan (SN - OO 1), water supply lines and sewer lines pass behind Delivery, Admin and OPD blocks. However, the space behind these blocks (between the blocks and existing retaining wall) is narrow and impossible to maintain the minimum 3 m horizontal distance between the water lines and sewer lines as stated in SN - 000 (please refer to attached pictures). Please note that the existing manholes are to remain and to be repaired as required as stated in Note 5 (SN - OO 1).
Please clarify.
PROPOSED SOLUTION:
Proposed solution is to use surface mounted GS pipes where it is impossible to maintain the 3 m horizontal spacing.
Solution is acceptable. Water supply lines can be galvanized steel, surface mounted attached with galvanized steel brackets every 1M.
19-May-14
P:\01298\127-01298-11002\Construction\RFIs\TO#8 - Combined RFI's\RFI Log TO#8 COMBINED
Inkntluional Rdilo'f & D(;vdnpmr!lf
TK International Bulding NO.2 5th floor Addis Ababa, TRANSMITTAL
No. 00033
PROJECT: TO-14-00003(TO#8)Durame Renovation DATE: Friday, May 16,2014
TO: USAID/ET REF: Request for Information US Embassy Addis Ababa, ATTN: Roger Sydney
WE ARE SENDING: SUBMITTED FOR: ACTION TAKEN:
D Shop Drawings D Approval D Approved as Submitted
D Letter D YourUse D Approved as Noted
D Prints D As Requested D Retumed After Loan
D Change Order li'J Review and Comment D Resubmit
D Plans liit Submit
D Samnles SENTVIA: D Retumed
D Specifications IIi'J Attached D Retumed for Corrections
~. Other: ReQuest for lnforrnation D Senarate Cover Via: Mail D Due Date:
ITEM PACKAGE REV. COPIES DATE DESCRIPTION STATUS
RFI 5/1612014 Water Supply Lines OPN
Remarks:
CC: IRD Document Control
P.O. Box 6005 www.ird.org Tel.: +251·016·630023
International Relicf & Development
TK International Building No.2
5th floor
Addis Ababa
TITLE: Water Supply Lines
PROJECT: TO-14-00003(TO#8) Durame Renovation
TO: USAID/ET
Addis Ababa
ATTN: Roger Sydney
QUESTION:
REQUEST FOR INFORMATION
No. 00011
DATE: Friday, May 16,2014
Contraet No.: TO#8
US Embassy
On the Site Utilities Plan (SN - OO 1), water supply lines and sewer lines pass behind Delivery, Admin and OPD blocks. However, the space behind these blocks (between the blocks and existing retaining wall) is narrow and impossible to maintain the minimum 3 m horizontal distance between the water lines and sewer lines as stated in SN - 000 (please refer to attached pictures). Please note that the existing manholes are to remain and to be repaired as required as stated in Note 5 (SN - OO 1). Please clarify.
Note: IRD has not assessed the full impaet of this issue in terms of additional eost and extension of time. IRD reserve s the right to submit a c1aim as provided in Contraet Seetion I.
PROPOSED SOLUTION:
Proposed solution is to use surface mounted GS pipes where it is impossible to maintain the 3 m horizontal spacmg.
Requested By: International Reliefand Development