Gimbichu
| Engineer's QA Punch List - Electrical Work Items | |||||
| Location: | GIMBICHU HEALTH CENTER | Date of Visit: | 20-Apr-15 | ||
| Must be completed immediately for substantial completion | |||||
| Already completed | |||||
| white | Must be completed within warranty period | ||||
| NOTE: | Uninstalled parts may need connections in ceilings and must be finished before start of waranty period due to safety reason. Any new installation and new material supplies need 1 year waranty after handing over. | ||||
| Detailed Punch List Items: | Clean-Up | ||||
| Location/Room | Punch List Comments | Rating | Comments | ||
| I) OPD | |||||
| 1 | Verandah | 1.1 | Label the neutral line, neutral bus and the ground bus in LPP-A | ||
| 2 | Sample Room | 2.1 | 1 socket outlet is not installed | ||
| 3 | Ceiling | 3.1 | Conduits are unfinished to light fixtures and junction boxes. | ||
| 3.2 | Different size RNC conduits are used, only 16mm diam should be used | ||||
| 3.3 | Additional conduit supports are required | ||||
| 3.4 | Junction boxes are over filled, cable glands of junction boxes are not used | ||||
| II) Delivery Block: | |||||
| 1 | Delivery | 1.1 | Type 4.1 Emergency light fixtures are not installed | Install UPS for these 4.1 lights + (3x1.5) mm sq electric power cable from UPS to light points, multi-core copper conductor, PVC/PVC, colorcoded, in PVC conduit diameter 32 mm with conduit supports. Include new 100A battery. Install new, 11 watt CFL light bulbs instead of the fluorescent tubes. | |
| 2 | Outdoor, front and back side | 2.1 | Light switch is not weather proof | ||
| 3 | Postnatal | 3.1 | Type 4.1 Emergency light fixtures are not installed | Install UPS for these 4.1 lights + (3x1.5) mm sq electric power cable from UPS to light points, multi-core copper conductor, PVC/PVC, colorcoded, in PVC conduit diameter 32 mm with conduit supports. Include new 100A battery. Install new, 11 watt CFL light bulbs instead of the fluorescent tubes. | |
| 4 | Toilet | 4.1 | Light switches is not water proof type | ||
| 4.2 | Water heater socket needs switch | ||||
| 5 | Labor | 5.1 | Type 4.1 Emergency light fixtures are not installed, | Install UPS for these 4.1 lights + (3x1.5) mm sq electric power cable from UPS to light points, multi-core copper conductor, PVC/PVC, colorcoded, in PVC conduit diameter 32 mm with conduit supports. Include new 100A battery. Install new, 11 watt CFL light bulbs instead of the fluorescent tubes. | |
| 6 | Toilet | 6.1 | Light switches is not water proof type | ||
| 6.2 | Water heater socket needs switch | ||||
| 6.3 | Lamp holder has loose connection | ||||
| 7 | Ceiling | 7.1 | Conduits are unfinished to light fixtures | ||
| 7.2 | Two types of RNC conduits are being used, 32 and 16mm diams, only 16mm should be used | ||||
| 7.3 | Conduits are not well organized to the building structure | ||||
| 7.4 | Junction boxes should be sealed by bushings | ||||
| 7.5 | Additional conduit supports are required-/30cm from fixture and junction boxes and at max spacing of 2 meters/ | ||||
| III) Registration Block: | |||||
| 1 | Verandah | 1.1 | Tele terminal box is not installed, connection to each room outlet is not done in the terminal box. | ||
| 2 | Finance | 2.1 | One socket outlet is not installed. | ||
| 3 | TB clinic | 3.1 | Install water proof wiring device for the mirror socket outlet | ||
| 3.2 | Verandah light switch is not weather proof | ||||
| 4 | Passage/Verandah | 4.1 | Conduits are unfinished to light fixtures | ||
| 5 | Dispensary | 5.1 | Water heater socket needs switch | ||
| 6 | Ceiling | 6.1 | Junction boxes are over filled | ||
| 6.2 | Cable glands are missed from junction boxes | ||||
| 6.3 | Additional junction boxes are required | ||||
| 6.4 | Conduiting is not organized to the building structure | ||||
| 6.5 | Conduits are unfinished to lighting fixtures | ||||
| 6.6 | Additional supports are required | ||||
| IV) ART Block: | |||||
| 1 | LPP-B | 1.1 | Make jumping wires 6mm2 | ||
| 1.2 | Label main neutral line, neutral bus and ground bus | ||||
| 2 | Ceiling | 4.1 | Cable glands are missed from junction boxes | ||
| 4.2 | Conduiting is not organized to the building structure | ||||
| 4.3 | Conduits are unfinished to lighting fixtures | ||||
| 4.4 | Additional supports are required | ||||
| V) Pit Latrine Block: | |||||
| 1 | Verandah | 1.1 | 1 Light switch and 1 light fixture are not installed, conduits and wires are done | ||
| 1.2 | 4-Type 5 light fixtures are not installed, conduits and wires are done |
| VI) General Site Work | ||||
| 1 | Site Work | 1.1 | New 3 phase power supply from EEPCO is connected and measured to be 180 V during daylight hours. The old electric meter has been relocated to the new meter location. | |
| 1.2 | New electrical manhole is not installed | |||
| 1.3 | Tele supply cable is pulled but is not connected. | |||
| 1.4 | Testing should be done to all blocks' electrical works | MDB failed megger testing to EEPCO power source. Short was also detected on breaker #2 on LPP-C. Many light fixtures in ART, OPD, Delivery, Registration Blocks do not work when Block panel powered on. Sources of electrical errors must beidentified and corrected. | ||
| 1.5 | Load distributions in boards should be per schedules | |||
| 1.6 | Label the neutral and ground cables in all distribution boards | |||
| 1.8 | Solar powered compound light fixtures are not installed | |||
| Attachments: |
| Comments and observations are provided in this report for the use of the Client. Nothing in this report should be taken by the Contractor as a directive to modify the plans, specifications or completed work unless appropriate documentation is provided by the Client. | |
| Bizuayehu Tessema | |
| ---End of Report--- |