CX-575
WASHED AND SCREENED STONE
AGGREGATE. EFFECTIVE SIZE
RANGE 20 TO 50 MM
Ø110 MM PVC INLET PIPE, FOR
PIPE INVERT, REF SITE DWGS
Ø110 MM PERFORATED
PVC INLET PIPE
450 450
PIPE PERFORATION
END CAP
R
CX-575
WASHED AND SCREENED STONE
AGGREGATE. EFFECTIVE SIZE
RANGE 20 TO 50 MM
Ø110 MM PVC INLET PIPE, FOR
PIPE INVERT, REF SITE DWGS
Ø110 MM PERFORATED
PVC INLET PIPE
450 450
PIPE PERFORATION
END CAP
M
I N
M
I N
Ø110 MM PVC INLET PIPE, FOR
PIPE INVERT, REF SITE DWGS
NATURAL SOIL
SELECTED FILL, PROVIDE SEEDING
ASSUMED EXST LEVEL OF BEDROCK/
GROUND WATER/ IMPERMEABLE SOIL
WASHED AND SCREENED STONE
AGGREGATE. EFFECTIVE SIZE
RANGE 20 TO 50 MM
REF SITE GRADING PLAN F/ SLOPE
Ø110 MM PERFORATED PVC INLET
PIPE 2% SLOPED, REF 9/CX-575
BEDDING DETAIL PER 12/CX-575
FRICTION KEY, 50MM DEEP
0.5MM POLY SHEET MEMBRANE, 400 MM
OFFSET F/ SEEPAGE BED ALL AROUND (SUBMITTAL REQUIRED)
M
I N
M
I N
NATURAL SOIL
SELECTED FILL, PROVIDE SEEDING
ASSUMED EXST LEVEL OF BEDROCK/
GROUND WATER/ IMPERMEABLE SOIL
WASHED AND SCREENED STONE AGGREGATE.
EFFECTIVE SIZE RANGE 20 TO 50 MM
REF SITE GRADING PLAN F/ SLOPE
Ø110 MM PVC INLET PIPE, FOR
PIPE INVERT, REF SITE DWGS
Ø110 MM PERFORATED PVC INLET
PIPE 2% SLOPED, REF 9/CX-575
BEDDING DETAIL PER 12/CX-575
FRICTION KEY, 50MM DEEP
0.5MM POLY SHEET MEMBRANE, 400 MM
OFFSET F/ SEEPAGE BED ALL AROUND (SUBMITTAL REQ)
Ø110 MM PERFORATED
PVC INLET PIPE
WASHED AND SCREENED STONE
AGGREGATE. EFFECTIVE SIZE
RANGE 20 TO 50 MM
STONE LINTEL, TYP
C X
ROUGHLY SHAPED STONE
LINTEL FOR PIPE PROTECTION
WASHED AND SCREENED
STONE AGRREGATE
EFFECTIVE RANGE 20 TO 50MM
Ø110 PVC PIPE
ALTERNATING 3MM
PERFORATION
LOCATIONS @100 O.C.
110 SCHD
40 PVC
SELECTED FILL PROVIDE SEEDLING
FINISHED GRADE
BACKFILL
PLACE SAND (RED ASH) AGAINST
UNDISTURBED SIDES & BOTTOM
OF TRENCH TO 300 ABOVE TOP (MIN)
M
I N
300 MIN BELOW PIPE
NATURAL SOIL
WARNING TAPE AS PER SPEC SEC 2316,2.2
STANDARD
DETAIL BOOK
w w w t e t r a t e c h c o m
O n e
G r a n t
S t r e e t
F r a m i n g h a m
M
A
P
M
P
D
O C
S S
I T
E S
R
E N
O V
A T
I O
N S
R
E N
O V
A T
I O
N
S
T A
N D
A R
D
D
E T
A
L
B
O O
K S
H E
E T
F I L
E S
E
H I P
C
X
S
O A
K A
W A
Y P
I T
D T
L S
D
W G
E L
E S
E
M
I S
I K
I R
S O
A K
A W
A Y
P
T
D
E T
A I L
S
CX-575
SOAKAWAY PIT TYPE 1 PLAN 1
SCALE: 1:50
SOAKAWAY PIT TYPE 2 PLAN 3
SCALE: 1:50
SOAKAWAY PIT TYPE 1 SECTION 5
SCALE: 1:50
SOAKAWAY PIT TYPE 2 SECTION 7
SCALE: 1:50
PIPE PROTECTION DTL9
SCALE: 1:20
PIPE PROTECTION SECTION10
SCALE 1:50
LATERAL PERF PIPE DTL11
NTS
NOTES
1. REFER SPECIFICATION FOR SELECTED FILL NOTES
2. HEAVY EQUIPMENT SHALL BE KEPT OUT OF THE
ABSORPTIONS AREA
3. FILL MATERIAL SHALL BE CAREFULLY PLACED AROUND
THE ABSORPTION AREA
4. FOR PIPE PLEASE REFER SPECIFICATION
5. USE WASHED GRAVEL OR CRUSHED STONE OF SIIZE
20-50MM
6. THE REQUIRED ABSORPTIONS BED BOTTOM AREA IS
EXCAVATED TO THE DESIGN DEPTH AS LEVEL AS
PRACTICAL
7. THE BOTTOM AND SIDES OF THE BED SHALL BE HAND
RAKED TO PREPARE THE SOIL INFILTRATIVE SURFACE
8. FOR INLET AND OUTLET PIPE DIAMETERS AND INVERTS,
REFER TO SEWER INVERT SCHEDULES
9. PERFORATED PIPE NOTES
9.1. THE LATERAL SHALL BE PERFORATED AND LAID AT A
SLOPE OF 2%;
9.2. HOLES IN GRAVITY DISTRIBUTION LATERALS SHALL BE
6.35 MM IN DIA. AND SPACED AT 900 MM ON CENTERS;
9.3. THE FIRST HOLE IN THE LATERALS SHALL BE 457.2 MM
FROM THE BEGINNING OF THE MANIFOLD;
9.4. THE END CAP HOLES SHALL BE 457.2 MM FROM THE
END OF THE AGGREGATE BED(Soil wall);
9.5. THE SPACING FOR THE LAST HOLE IN THE LATERALS
BEFORE THE END CAP SHALL BE AT NO LESS THAN
457.2 MM AND NO MORE THAN 914.4 MM.
PIPE BEDDING DTL FOR SOAK AWAY PIT12
SCALE: 1:50
PVC VENT CAP @ 30CM
ABOVE FINISHED GRADE
SEEPAGE BED
Ø110 PVC,
2% SLOPE, TYP
PVC PIPE FROM
SEPTIC TANK/ MH,
SEE INVERT SCHEDULE
Ø50 VENT PIPE
Ø110 PERFORATED PVC.
REF 6/CX-576, 2% SLOPE, TYP
1500 5500
CX-576
MONITOR WELL, REF 5/CX-576
PERFORATED PIPE
1500 PERFORATED PIPE 1500
PIPE BEDDING DETAIL
PER 7/CX-576
Ø110 PERFORATED PVC
DISTRIBUTION PIPE
N
BED ROCK, GROUND WATER
OR IMPERMEABLE STRATA LINE
M
I N
NATURAL SOIL
0.5MM POLY SHEET MEMBRANE,
400 MM OFFSET F/ SEEPAGE BED ALL
AROUND (SUBMITTAL REQUIRED)
SELECTED FILL,
PROVIDE SEEDING
REF SITE GRADING PLAN F/ SLOPE
WASHED AND SCREENED
STONE AGGREGATE.
EFFECTIVE SIZE RANGE 20
TO 50 MM
FRICTION KEY, 50MM DEEP
CONCRETE COLLAR
Ø110 SLOTTED
PVC WELL PIPE (PERFORATED)
SEEPAGE BED
SELECTED FILL PROVIDE SEEDLING
Ø110 UPVC CAPPNG
Ø110 PERFORATED
PVC DISTRIBUTION PIPE
NATURAL SOIL
PERFORATION BEGINNING 50MM
BELOW DISTRIBUTION PIPE
ALTERNATING 3MM
PERFORATION
LOCATIONS @100 O.C.
110 SCHD
40 PVC
FINISHED GRADE
BACKFILL
PLACE SAND (RED ASH) AGAINST
UNDISTURBED SIDES & BOTTOM
OF TRENCH TO 300 ABOVE TOP (MIN)
300 MIN BELOW PIPE
M
I N
NATURAL SOIL
WARNING TAPE AS PER SPEC SEC 2316,2.2
STANDARD
DETAIL BOOK
w w w t e t r a t e c h c o m
O n e
G r a n t
S t r e e t
F r a m i n g h a m
M
A
P
M
P
D
O C
S S
I T
E S
R
E N
O V
A T
I O
N S
R
E N
O V
A T
I O
N
S
T A
N D
A R
D
D
E T
A
L
B
O O
K S
H E
E T
F I L
E S
E
H I P
C
X
S
O A
K A
W A
Y P
I T
D T
L S
D
W G
E L
E S
E
M
I S
I K
I R
S E
E P
A G
E
B
T
A I L
S
CX-576
SEEPAGE BED PLAN
SCALE: 1:50
NOTES
1. REFER SPECIFICATION FOR SELECTED FILL NOTES
2. HEAVY EQUIPMENT SHALL BE KEPT OUT OF THE
ABSORPTIONS AREA
3. FILL MATERIAL SHALL BE CAREFULLY PLACED AROUND
THE ABSORPTION AREA
4. FOR PIPE PLEASE REFER SPECIFICATION
5. USE WASHED GRAVEL OR CRUSHED STONE OF SIIZE
20-50MM
6. THE REQUIRED ABSORPTIONS BED BOTTOM AREA IS
EXCAVATED TO THE DESIGN DEPTH AS LEVEL AS
PRACTICAL
7. THE BOTTOM AND SIDES OF THE BED SHALL BE HAND
RAKED TO PREPARE THE SOIL INFILTRATIVE SURFACE
8. FOR INLET AND OUTLET PIPE DIAMETERS AND INVERTS,
REFER TO SEWER INVERT SCHEDULES
9. PERFORATED PIPE NOTES
9.1. THE LATERAL SHALL BE PERFORATED AND LAID AT A
SLOPE OF 2%;
9.2. HOLES IN GRAVITY DISTRIBUTION LATERALS SHALL BE
6.35 MM IN DIA. AND SPACED AT 900 MM ON CENTERS;
9.3. THE FIRST HOLE IN THE LATERALS SHALL BE 457.2 MM
FROM THE BEGINNING OF THE MANIFOLD;
9.4. THE END CAP HOLES SHALL BE 457.2 MM FROM THE
END OF THE AGGREGATE BED(Soil wall);
9.5. THE SPACING FOR THE LAST HOLE IN THE LATERALS
BEFORE THE END CAP SHALL BE AT NO LESS THAN
457.2 MM AND NO MORE THAN 914.4 MM.
SEEPAGE BED SECT3
SCALE: 1:20
MONITOR WELL DTL5
SCALE 1:20
LATERAL PERFORATED PIPE DTL6
SCALE: 1:30
PIPE BEDDING DTL FOR SEEPAGE BED7
SCALE: 1:50
| 150128-EHIP200-CX-575-SoakAwayPitDtls-CX-575 |