CLIN_-_001_RFI_00007-GalvStlWaterSvcPiping.pdf
PDF 85 KB Posted
- Solicitation number
- SOL-663-15-000028
About this file
CLIN_-_001_RFI_00007-GalvStlWaterSvcPiping
View the file
Other files
Show 40 more
Latest 50 of 69 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
USAID/EHIP
New Health Center Construction Task Order 8, Combined RFI Log
Durame Site 202 Batu Site 251 Gimbichu Site 208 Arsi Negele Site 277 Waka Site 213 Meki Site 290
RFI No. Date Rec'd Item No. Question TT Response Response Date Follow-up
Arsi Negele 00007 Batu 00012
Durame 00008 Gimbichu 00014
Meki 00010 Waka 00011
21-Apr-14 1 The Water Service Detail calls for the use of Dia. 300mm UV protected PVC pipes as cover for water supp ly lines. We request your approval to use GS pipes instead of using UV protected PVC pipes since these pipes make it difficult to access the gate valyes, even though there is a removable lid on top of the PVC pipes. These pipes are also not readily available in the local market.
Proposal to use Galvanized Steel pipes and eliminate the need for above ground PVC covers for water supply lines is acceptable.
Provide product data submittal for GS piping through the Submittal Process.
29-Apr-14
P:\01298\127-01298-11002\Construction\RFIs\TO#8 - Combined RFI's\RFI Log TO#8 COMBINED
International RtHef& Development
TK International Building NO.2 5th Floor Addis Ababa, TRANSMITTAL
No. 00020
PROJECT: TO-14-00003 TO#8 HC Renovations DATE: Monday, April21, 2014
TO:
ATTN:
USAID/ET
US Embassy Addis Ababa, Roger Sydney
.. WEARESENDING: ..... ,e: ·i;':;;.' .;)".
D Shop Drawings
D Letter
D Prints
D Change Order
D Plans
D Samples
D Speeifieations
Il!'! Other: Request for Information
ITEM PAeKAGE
RPI
Remarks:
CC: IRD Document Control
P.O. Box 6005
REF: Request for Information
.SUBNlI't'TEDlrOJl::", . ;;;;~.'.·ij.: . ; ., .... ".' ..•.. '; .. "ACTION'Tl\:KEN: ., ....... "'o. , " '. '.
D Approval D Approved as Submitted
D YourUse D Approved as Noted
D As Requested D Retumed After Loan i ~ Review and Comment D Resubmit
~ Submit
SENTVIA; D Retumed
'l!'! Attaehed D Retumed for Correetions
D Separate Cover Via: Mail D DueDate:
.eOPlES l>EseRIPTION .
412112014 Water Service Detail OPN www.ird.org TeL: +251-016-630023
International Relief & Development JmpllJrJin ... ~ Lnles. Bu.iMing Ll1lflihoods, TK International Building NO.2 5th Floor Addis Ababa
TITLE: Water Service Detail
PROJECT: TO-14-00003 TO#8 HC Renovations
TO: USAID/ET
Addis Ababa
ATTN: Roger Sydney
QUESTION:
REQUEST FOR INFORMATION
ARSI NEGELLE No. 00007
BATUNo.00012
GIMBICHU No. 00014
DURAME No. 00008
MEKI No. 00010
WAKA No. 00011
DATE: Monday, April21, 2014
Contract No.: TO#8
US Embassy
TO#8
The Water Service Detail calls for the use of Dia. 300mm UV protected PVC pipes as cover for water supp ly lines. We request your approval to use GS pipes instead of using UV protected PVC pipes since these pipes make it diffkult to access the gate valyes, even though there is a removable lid on top of the PVC pipes. These pipes are also not readily available in the local market.
Note: IRD has not assessed the full impact of this issue in terms of additional eost and extension of time. IRD reserves the right to submit a elaim as provided in Contraet Seetion I.
P.O. Box 6005 www.ird.org Tel.: +251-0116-630023
File details come from the government source that posted it. Updated .