S02 - SOW - Att 42 - Cut Sheet 20 - EHRM Infra Upgrades - Constr - Togus.pdf

PDF 1 MB Posted

Attached to
Electronic Health Record Modernization Infrastructure Upgrades - Construction - Togus, ME
Solicitation number
36C77626R0062
Issued by

About this file

This document is a technical specification and dimensional data collection for Liebert cooling equipment systems, including multiple product lines and their installation requirements.

The primary equipment specified includes: DSE Model DA125DP-2xMCL165E1 downflow air-cooled units with humidification and reheat capabilities (460VAC, 3PH, 60Hz with 79.9 FLA, 92.2 WSA, 100 OPD); Liebert MC Condenser units (MCL165 model requiring 460VAC, 3PH, 60Hz with 8.4 FLA, 9.1 WSA, 15.0 OPD, two condensers required per indoor unit); Liebert Econophase pumped economizer systems (PR050-PR250 models with various voltage options and specifications); and Liebert Heat Rejection Skid (MCV330 with integrated PR125 pump set, requiring 460VAC, 3PH, 60Hz with 23.8 FLA, 24.7 WSA, 25.0 OPD). The document provides comprehensive cabinet dimensional data, electrical specifications, component details including compressors, evaporators, condensers, cooling fans, and humidification systems. Physical specifications include unit weights ranging from 217 to 5000 pounds depending on model, various height configurations (18" to 60" leg options), and detailed anchor and mounting requirements. All equipment is AHRI certified in accordance with Datacom Cooling Certification Program standards and ASHRAE guidelines.

View the file

Other files

File Type Posted
S30 - SAM - Special Notice - Cancellation - 36C77626R0062_2 - EHRM Infra Upgrades - Togus.pdf PDF
S06 - Amend 0002 - Att 03 - Corrected Agenda - RFP - 07202026 - EHRM Infra - Togus.pdf PDF
S06 - Amend 0002 - 36C77626R0062 - 07202026 - EHRM Infra - Togus.pdf PDF
S06 - Amend 0001 - Att 02 - SV - Attendance SHT - 06292026 - EHRM Infra - Togus.pdf PDF
S06 - Amend 0001 - 36C77626R0062 - 07142026 - EHRM Infra - Togus.pdf PDF
S06 - Amend 0001 - RFIs - 07132026 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S06 - Amend 0001 - Att 01 - Rvd Structural Drwg - 06192026 - EHRM Infra - Togus.pdf PDF
S06 - Amend 0001 - Att 03 - SV - Agenda - RFP - 06292026 - EHRM Infra - Togus.pdf PDF
S02 - SOW - Att 05 - Drwg - Vol 3 - 02182026 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - SOW - Att 13 - Const Sch - 02132026 - EHRM Infra Upgrades - Constr Togus.pdf PDF
S02 - SOW - Att 26 - Cut Sheet 04 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - Att 03 -Prj Info Sheet for KTR - EHRM Infra Upgrade - Togus.docx DOCX document
S02 - SOW - Att 03 - Drwg - Vol 1C - 02182026 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - SOW - Att 22 - TS-000 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - Att 07 - 852.219-75 - 06172026 - EHRM Infra Upgrade - Togus.pdf PDF
S02 - Att 04 - Memo - Brand Name - 04092026 - EHRM Infra Upgrade - Togus.pdf PDF
S02 - SOW - Att 35 - Cut Sheet 13 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - SOW - Att 17 - Memo - Phy Sec Compliance - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - SOW - Att 27 - Cut Sheet 05 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - SOW - Att 09 - Specs - Vol 3- 02182026 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - SOW - Att 30 - Cut Sheet 08 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - SOW - Att 24 - Cut Sheet 02 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - Att 05 - Division Cost Breakdown - EHRM Infra Upgrade - Togus.xlsx XLSX spreadsheet
S02 - SOW - Att 29 - Cut Sheet 07 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - SOW - Att 37 - Cut Sheet 15 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - SOW - Att 16 - Submittal Reg - 02182026 - EHRM Infra - Upgrades - Constr - Togus.xlsx XLSX spreadsheet
S02 - SOW - Att 14 - Design Calcs - 02182026 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - SOW - Att 18 - Memo - Prj Stnd Compliance - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - SOW - Att 21 - PCRA 3 - MCR and Trench Work - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - SOW - Att 40 - Cut Sheet 18 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - SOW - Att 33 - Cut Sheet 11 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - SOW - Att 01 - Drwg - Vol 1A - 02182026 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - SOW - Att 38 - Cut Sheet 16 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - SOW - Att 06 - Drwg - Vol 4 - 02182026 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - SOW - Att 11 - Haz Mat Report - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - SOW - Att 12 - Geotechnical Report - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - SOW - Att 32 - Cut Sheet 10 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - SOW - Att 08 - Specs - Vol 1 - Div 02-14 - 02182026 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - SOW - Att 20 - PCRA 2 - Cabling and Data Outlets - EHRM Infra Upgrades - Constr - Togus.pdf PDF
RFP - EHRM Infra Upgrade - 36C77626R0062 - 06172026 - Togus.pdf PDF
S02 - SOW - Att 19 - PCRA 1 - TR Constr - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - SOW - Att 07 - Specs - Vol 1 - Div 00-01 - 02182026 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - SOW - Att 15 - Design Narrative - 02182026 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - SOW - Att 23 - Cut Sheet 01 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - SOW - Att 31 - Cut Sheet 09 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - Att 02 - PPQ - EHRM Infra Upgrade - Togus.docx DOCX document
S02 - SOW - Att 02 - Drwg - Vol 1B - 02182026 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - SOW - Att 34 - Cut Sheet 12 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - Att 01 - SOW - 05112026 - EHRM Infra Upgrades - Togus.pdf PDF
S02 - SOW - Att 10 - Specs - Vol 4 - 02182026 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
Show 40 more

Latest 50 of 57 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

campbem12129 Text Box

ELECTRICAL REQUIREMENTS FOR DA125DP WITH HUMIDIFICATION AND REHEAT:

460VAC, 3PH, 60HZ

FLA: 79.9

WSA: 92.2

OPD: 100

REV : 6

REV DATE : 2/19

DPN003175

Page :1 /1

DOWNFLOW AIR COOLED DA125, DA150 & DA165 MODELS

F or m N o.

: D

P N

_R

E V

CABINET DIMENSIONAL DATA

LIEBERT DSE

Model No. Approximate Dry Weight lb(kg)

DA125 3465 (1572)

DA150/DA165 3574 (1621)

48" 1219mm

24" 610mm

Filter Plenum Shipped separately

Striated area indicates the recommended minmum clearance to be provided for component access.

Shaded area indicates the required minimum clearance below the unit to lower the fans into the floor.Fans may also remain in their shipped position if desired.

Filters are removed thru front of plenum

Front View

Top View

117 11/16" 2989mm Opening

42" 1067mm Opening

5/16" 8mm Bezel

47" 1194mm

45" 1143mm

1 3/16" 29mm Handle

144" 3658mm

18" 457mm

76" 1930mm Base Unit

142" 3607mm

94" 2388mm

Total Height

1" 25mm Typ.

45" 1143mm Plenum

47" 1194mm

45" 1143mm

1" 25mm Typ.

Secondary Refrigerant Piping Entrance

19" 483mm

2 5/8" 67mm

3 3/8" 86mm

7" 178mm1

Notes:

1. 7" for DA125, 4" for DA150 & DA165.

campbem12129 Rectangle

REV : 9

REV DATE : 4/23

DPN002326

Page :1 /1

PR050 - PR250

F or m N o.

: D

P N

_R

E V

CABINET DIMENSIONAL DATA

LIEBERT ECONOPHASE

9 3/8" 238mm

36 15/16" 939mm

4 13/16" 123mm

21 5/16" 541mm

4 13/16" 122mm

21 3/8" 543mm

40 1/8" 1019mm

42 1/8" 1071mm

40 11/16" 1033mm

35 7/8" 911mm

36 3/16" 919mm

A A

SECTION A-A

2 15/16" 74mm

12 15/16" 328mm

22 15/16" 582mm

32 15/16" 836mm

35 7/8" 911mm

System Circuit 1 Liquid In

System Circuit 2 Liquid In

System Circuit 2 Liquid Out

System Circuit 1 Liquid Out

REAR VIEW

(PIPING END)

LEFT SIDE VIEW

FRONT VIEW

1-3/8" Liquid from Condenser to PR085-PR200 1-5/8" Liquid from Condenser to PR250

7/8" Liquid from PR085-PR200 to indoor unit 1-3/8" Liquid from PR250 to indoor unit

ISOMETRIC VIEW

42" 1067mm

Minimum Clearance

36" 914mm

Minimum Clearance

36" 914mm

Minimum Clearance

Electric Box End of Unit

Pump Access Typical Both Sides

B

DETAIL B

O 7/16" Typical 8 Places (11mm) for unit mounting

O 7/16" Typical 8 Places (11mm) for unit mounting

Model Circuits Unit Voltage, Hz Approximate Dry Weight lbs (kg)

208/230V, 460V 60Hz 217 (98)

380V, 575V 60Hz 242 (110)

415V 50Hz 217 (98)

208/230V, 460V 60Hz 340 (154)

380V, 575V 60Hz 390 (177)

415V 50Hz 347 (157)

PR200 2 460V 60Hz 350 (159)

PR085-125

and PR250

PR050 1

40" 1016mm

39 3/8" 1000mm

5/8" 16mm

1-3/8" Liquid from Condenser to PR050

7/8" Liquid from PR050 indoor unit campbem12129 Text Box

PUMPED ECONOMIZER PUMP SET

USED WITH MCL165 CONDENSERS, 1 PUMP SET PER INDOOR UNIT.

campbem12129 Text Box

PR125AA ELECTRICAL:

460VAC, 3PH, 60HZ

FLA: 7.0

WSA: 7.9

OPD: 15

REV : 3

REV DATE : 12/16

DPN003438

Page :1 /1

3 FAN (MCL165)

F or m N o.

: D

P N

_R

E V

CABINET & ANCHOR DIMENSIONAL DATA

LIEBERT MC CONDENSER

Lee-Temp or DSE Receiver

Left Side of Unit

K L

A A*

G

H

TOP OF

FAN GUARD

F

Note:

1. Liebert recommends a clearance of 36” (915mm) on each side for proper operation and component access.

Cross Bracing required for legs longer than 18" (457.2mm). quantity varies per model & options selected.

For DSE models only, 6-1/2" (165mm) dimension is 9-1/4" (235mm) and 15-1/4 (387mm) dimension is not applicable.

MCL165 18 (457) 36 (914) 48 (1219) 60 (1524)

DIM "G" 35-7/8 (911) 53-7/8 (1368) 65-7/8 (1673) 77-7/8 (1978)

DIM "H" 43-5/8 (1108) 61-5/8 (1565) 73-5/8 (1870) 85-5/8 (2175)

LIEBERT

MODEL

NUMBER

F

LEG HEIGHT DIMENSIONS in. (mm)

Front View (Lee-Temp shown)

Anchor Plan

54 1/8" 1374mm

Typ.

B

A

DETAIL A

Typical All Legs

1 7/8" 48mm Typ.

3 5/8" 93mm Typ.13/16"

21mm Typ.

7" 178mm

Typ.

1/2" (13mm) X 1" (25mm) Obround Typ.

C E D

J Lee Temp or DSE Only

M

K

MCL165 180-1/4 (4578) 189-1/4 (4807) 73-7/16 (1866) 168-1/4 (4274) 110-1/2 (2806) 56-1/8 (1425) 54-3/8 (1381) 55-1/2 (1410) 53-7/8 (1368) 48-3/4 (1238)

DB C

LIEBERT

MODEL

NUMBER

A A*

(575V ONLY)

Dimensions in. (mm)

J

Lee-Temp or

DSE Reciever

K L ME

Full height Leg supplied for each Lee-Temp or DSE Receiver required

6 1/2" 165mm Ref.

575V Option

Entering Hot Gas and Leaving Liquid Piping

Main Electric

Box End

Lifting Eyebolts Typ. (4) Places

575V Option

15 1/4" 387mm campbem12129 Text Box

2 CONDENSERS REQUIRED PER INDOOR UNIT

campbem12129 Line campbem12129 Line campbem12129 Line campbem12129 Line campbem12129 Line campbem12129 Text Box

MCL165 ELECTRICAL:

460VAC, 3 PH, 60HZ

FLA: 8.4

WSA: 9.1

OPD: 15.0

REV : 6

REV DATE : 2/20

DPN003889

Page :1 /2

MCV330 + ECONOPHASE + BASE ASSEMBLY

F or m N o.

: D

P N

_R

E V

CABINET & ANCHOR DIMENSIONAL DATA

LIEBERT® HEAT REJECTION SKID

NOTES:

1) Minimum clearance on the Main Unit Disconnect Enclosure shall be 48" (1219mm) or per local code.

2) Recommended minimum 48" (1219mm) clearance when multiple skids are mounted side by side to ensure proper airflow. Contact the factory for other spacing requirements.

Main Electrical Box End

101 1/4" 2572mm

132" 3353mm Cabinet

132 11/16" 3370mm Overall

111" 2819mm Overall

99 5/8" 2530mm Cabinet

MCV330 Single Skid 5000 (2268) 4980 (2258)

Dry weight with a receiver and without crating lb (kg) Model

Shipping weight lb (kg) campbem12129 Text Box ALTERNATE CONDENSER SELECTION, 1 CONDENSER REQUIRED PER INDOOR UNIT. THIS CONDENSER INCLUDES THE ECONOMIZER PUMP SET FACTORY INSTALLED AS PART OF THIS CONDENSER ASSEMBLY.

campbem12129 Text Box

MCV330 ELECTRICAL,

INCLUDES PR125:

460 VAC, 3 PH, 60HZ

FLA: 23.8

WSA: 24.7

OPD: 25.0