S02 - SOW - Att 42 - Cut Sheet 20 - EHRM Infra Upgrades - Constr - Togus.pdf
PDF 1 MB Posted
- Attached to
- Electronic Health Record Modernization Infrastructure Upgrades - Construction - Togus, ME
- Solicitation number
- 36C77626R0062
About this file
This document is a technical specification and dimensional data collection for Liebert cooling equipment systems, including multiple product lines and their installation requirements.
The primary equipment specified includes: DSE Model DA125DP-2xMCL165E1 downflow air-cooled units with humidification and reheat capabilities (460VAC, 3PH, 60Hz with 79.9 FLA, 92.2 WSA, 100 OPD); Liebert MC Condenser units (MCL165 model requiring 460VAC, 3PH, 60Hz with 8.4 FLA, 9.1 WSA, 15.0 OPD, two condensers required per indoor unit); Liebert Econophase pumped economizer systems (PR050-PR250 models with various voltage options and specifications); and Liebert Heat Rejection Skid (MCV330 with integrated PR125 pump set, requiring 460VAC, 3PH, 60Hz with 23.8 FLA, 24.7 WSA, 25.0 OPD). The document provides comprehensive cabinet dimensional data, electrical specifications, component details including compressors, evaporators, condensers, cooling fans, and humidification systems. Physical specifications include unit weights ranging from 217 to 5000 pounds depending on model, various height configurations (18" to 60" leg options), and detailed anchor and mounting requirements. All equipment is AHRI certified in accordance with Datacom Cooling Certification Program standards and ASHRAE guidelines.
View the file
Other files
Show 40 more
Latest 50 of 57 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
campbem12129 Text Box
ELECTRICAL REQUIREMENTS FOR DA125DP WITH HUMIDIFICATION AND REHEAT:
460VAC, 3PH, 60HZ
FLA: 79.9
WSA: 92.2
OPD: 100
REV : 6
REV DATE : 2/19
DPN003175
Page :1 /1
DOWNFLOW AIR COOLED DA125, DA150 & DA165 MODELS
F or m N o.
: D
P N
_R
E V
CABINET DIMENSIONAL DATA
LIEBERT DSE
Model No. Approximate Dry Weight lb(kg)
DA125 3465 (1572)
DA150/DA165 3574 (1621)
48" 1219mm
24" 610mm
Filter Plenum Shipped separately
Striated area indicates the recommended minmum clearance to be provided for component access.
Shaded area indicates the required minimum clearance below the unit to lower the fans into the floor.Fans may also remain in their shipped position if desired.
Filters are removed thru front of plenum
Front View
Top View
117 11/16" 2989mm Opening
42" 1067mm Opening
5/16" 8mm Bezel
47" 1194mm
45" 1143mm
1 3/16" 29mm Handle
144" 3658mm
18" 457mm
76" 1930mm Base Unit
142" 3607mm
94" 2388mm
Total Height
1" 25mm Typ.
45" 1143mm Plenum
47" 1194mm
45" 1143mm
1" 25mm Typ.
Secondary Refrigerant Piping Entrance
19" 483mm
2 5/8" 67mm
3 3/8" 86mm
7" 178mm1
Notes:
1. 7" for DA125, 4" for DA150 & DA165.
campbem12129 Rectangle
REV : 9
REV DATE : 4/23
DPN002326
Page :1 /1
PR050 - PR250
F or m N o.
: D
P N
_R
E V
CABINET DIMENSIONAL DATA
LIEBERT ECONOPHASE
9 3/8" 238mm
36 15/16" 939mm
4 13/16" 123mm
21 5/16" 541mm
4 13/16" 122mm
21 3/8" 543mm
40 1/8" 1019mm
42 1/8" 1071mm
40 11/16" 1033mm
35 7/8" 911mm
36 3/16" 919mm
A A
SECTION A-A
2 15/16" 74mm
12 15/16" 328mm
22 15/16" 582mm
32 15/16" 836mm
35 7/8" 911mm
System Circuit 1 Liquid In
System Circuit 2 Liquid In
System Circuit 2 Liquid Out
System Circuit 1 Liquid Out
REAR VIEW
(PIPING END)
LEFT SIDE VIEW
FRONT VIEW
1-3/8" Liquid from Condenser to PR085-PR200 1-5/8" Liquid from Condenser to PR250
7/8" Liquid from PR085-PR200 to indoor unit 1-3/8" Liquid from PR250 to indoor unit
ISOMETRIC VIEW
42" 1067mm
Minimum Clearance
36" 914mm
Minimum Clearance
36" 914mm
Minimum Clearance
Electric Box End of Unit
Pump Access Typical Both Sides
B
DETAIL B
O 7/16" Typical 8 Places (11mm) for unit mounting
O 7/16" Typical 8 Places (11mm) for unit mounting
Model Circuits Unit Voltage, Hz Approximate Dry Weight lbs (kg)
208/230V, 460V 60Hz 217 (98)
380V, 575V 60Hz 242 (110)
415V 50Hz 217 (98)
208/230V, 460V 60Hz 340 (154)
380V, 575V 60Hz 390 (177)
415V 50Hz 347 (157)
PR200 2 460V 60Hz 350 (159)
PR085-125
and PR250
PR050 1
40" 1016mm
39 3/8" 1000mm
5/8" 16mm
1-3/8" Liquid from Condenser to PR050
7/8" Liquid from PR050 indoor unit campbem12129 Text Box
PUMPED ECONOMIZER PUMP SET
USED WITH MCL165 CONDENSERS, 1 PUMP SET PER INDOOR UNIT.
campbem12129 Text Box
PR125AA ELECTRICAL:
460VAC, 3PH, 60HZ
FLA: 7.0
WSA: 7.9
OPD: 15
REV : 3
REV DATE : 12/16
DPN003438
Page :1 /1
3 FAN (MCL165)
F or m N o.
: D
P N
_R
E V
CABINET & ANCHOR DIMENSIONAL DATA
LIEBERT MC CONDENSER
Lee-Temp or DSE Receiver
Left Side of Unit
K L
A A*
G
H
TOP OF
FAN GUARD
F
Note:
1. Liebert recommends a clearance of 36” (915mm) on each side for proper operation and component access.
Cross Bracing required for legs longer than 18" (457.2mm). quantity varies per model & options selected.
For DSE models only, 6-1/2" (165mm) dimension is 9-1/4" (235mm) and 15-1/4 (387mm) dimension is not applicable.
MCL165 18 (457) 36 (914) 48 (1219) 60 (1524)
DIM "G" 35-7/8 (911) 53-7/8 (1368) 65-7/8 (1673) 77-7/8 (1978)
DIM "H" 43-5/8 (1108) 61-5/8 (1565) 73-5/8 (1870) 85-5/8 (2175)
LIEBERT
MODEL
NUMBER
F
LEG HEIGHT DIMENSIONS in. (mm)
Front View (Lee-Temp shown)
Anchor Plan
54 1/8" 1374mm
Typ.
B
A
DETAIL A
Typical All Legs
1 7/8" 48mm Typ.
3 5/8" 93mm Typ.13/16"
21mm Typ.
7" 178mm
Typ.
1/2" (13mm) X 1" (25mm) Obround Typ.
C E D
J Lee Temp or DSE Only
M
K
MCL165 180-1/4 (4578) 189-1/4 (4807) 73-7/16 (1866) 168-1/4 (4274) 110-1/2 (2806) 56-1/8 (1425) 54-3/8 (1381) 55-1/2 (1410) 53-7/8 (1368) 48-3/4 (1238)
DB C
LIEBERT
MODEL
NUMBER
A A*
(575V ONLY)
Dimensions in. (mm)
J
Lee-Temp or
DSE Reciever
K L ME
Full height Leg supplied for each Lee-Temp or DSE Receiver required
6 1/2" 165mm Ref.
575V Option
Entering Hot Gas and Leaving Liquid Piping
Main Electric
Box End
Lifting Eyebolts Typ. (4) Places
575V Option
15 1/4" 387mm campbem12129 Text Box
2 CONDENSERS REQUIRED PER INDOOR UNIT
campbem12129 Line campbem12129 Line campbem12129 Line campbem12129 Line campbem12129 Line campbem12129 Text Box
MCL165 ELECTRICAL:
460VAC, 3 PH, 60HZ
FLA: 8.4
WSA: 9.1
OPD: 15.0
REV : 6
REV DATE : 2/20
DPN003889
Page :1 /2
MCV330 + ECONOPHASE + BASE ASSEMBLY
F or m N o.
: D
P N
_R
E V
CABINET & ANCHOR DIMENSIONAL DATA
LIEBERT® HEAT REJECTION SKID
NOTES:
1) Minimum clearance on the Main Unit Disconnect Enclosure shall be 48" (1219mm) or per local code.
2) Recommended minimum 48" (1219mm) clearance when multiple skids are mounted side by side to ensure proper airflow. Contact the factory for other spacing requirements.
Main Electrical Box End
101 1/4" 2572mm
132" 3353mm Cabinet
132 11/16" 3370mm Overall
111" 2819mm Overall
99 5/8" 2530mm Cabinet
MCV330 Single Skid 5000 (2268) 4980 (2258)
Dry weight with a receiver and without crating lb (kg) Model
Shipping weight lb (kg) campbem12129 Text Box ALTERNATE CONDENSER SELECTION, 1 CONDENSER REQUIRED PER INDOOR UNIT. THIS CONDENSER INCLUDES THE ECONOMIZER PUMP SET FACTORY INSTALLED AS PART OF THIS CONDENSER ASSEMBLY.
campbem12129 Text Box
MCV330 ELECTRICAL,
INCLUDES PR125:
460 VAC, 3 PH, 60HZ
FLA: 23.8
WSA: 24.7
OPD: 25.0
File details come from the government source that posted it. Updated .