This is a product specifications document for the RA200 Remote Audible/Visual Alarm Annunciator manufactured by Pneumercator Company, Inc.
The RA200 series is a remote alarm annunciator system designed to replicate critical alarm warnings from a TMS tank management console to remote locations. The system is typically deployed where operational and supervisory personnel at different locations require immediate notification of critical alarms, or where alarm warnings are needed at multiple indoor and outdoor on-site locations. The product line consists of three components: the RA200 main annunciator unit, the RA200PM compact variant, and the optional RS2 remote test and reset module. All units are housed in NEMA 4X (IP56) rated enclosures suitable for harsh environments. Power requirements are 115/230 VAC switchable, 50-60 Hz, 8 W maximum. The audible alarm produces 110 dba at 3 feet, and the visual alarm provides 15 candela amber indication. Operating temperature range is -31°F to 150°F with 100% non-condensing humidity tolerance. Two complete package models are offered: RA200K (RA200 with RA200PM) and RA200KR (RA200 with RA200PM and RS2). The specification document was issued April 1, 2013.
View the file
Other files
Show 40 more
Latest 50 of 57 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Pneumercator Company, Inc. Tel: 631-293-8450
1785 Expressway Drive North Fax: 631-293-8533 Hauppauge, New York 11788 http://www.pneumercator.com
RA200 Specifications
Remote Audible / Visual Alarm Annunciator
In NEMA 4X (IP56) Enclosure
RA200 RA200PM RS2
Product Description
The RA200 series Remote Annunciator is used in applications where it is desired to have access to audible and optional visual alarms from an on-sight location remote to the TMS tank management console. The RA200 replicates critical alarm warnings, and is typically used in applications where both operational personnel in the active service area and supervisory personnel in a remote office require immediate warning of critical alarms, or where critical alarm warnings are required at both on-sight indoor and outdoor locations. The optional RS2 can be used to test the annunciator as well as reset the audible alarm from a remote location.
Specifications
Dimensions (W x H x D): 5.13” x 5.13” x 4.75” (130 mm x 130 mm x 120 mm) (RA200)
3.54” x 4.53” x 2.17” (90 mm x 115 mm x 55 mm) (RA200PM)
2.55” x 4.53” x 2.62” (65 mm x 115 mm x 67 mm) (RS2)
Weight: 1.15 lb (0.5 kg) (RA200)
1.05 lb (0.5 kg) (RA200PM)
0.4 lb (0.2 kg) (RS2)
Operating Temperature: -31 ºF to 150 ºF (-35 ºC to 66 °C)
Humidity: 100%, Non-condensing
Enclosure Rating: NEMA 4X (IP56)
Power Requirements: 115/230 VAC Switchable, 50-60 Hz, 8 W Max.
Audible Alarm: 110 dba at 3 feet (1 m)
Visual Alarm: 15 candela (Amber)
Model Numbers
RA200K RA200 with RA200PM
RA200KR RA200 with RA200PM and RS2
Note: Specifications subject to change without notice. 04-01-2013