S02 - SOW - Att 30 - Cut Sheet 08 - EHRM Infra Upgrades - Constr - Togus.pdf

PDF 6 MB Posted

Attached to
Electronic Health Record Modernization Infrastructure Upgrades - Construction - Togus, ME
Solicitation number
36C77626R0062
Issued by

About this file

This is a preliminary submittal document for a Liebert PDX air-cooled cooling system specified for the VA TOGUS MAINE project. The submittal includes detailed engineering specifications, dimensional data, piping schematics, electrical connections, and product documentation for the indoor unit model PX011UA1AD and outdoor condenser model MCS028E1AD, with a quantity of one unit each dated August 14, 2023.

The system is configured with the following key specifications: 460/208 volt, 3-phase, 60 Hz power supply with a 65,000 amp short circuit current rating; net total cooling capacity of 44.2 KBTUH and net sensible cooling capacity of 38.8 KBTUH at 75°F DB and 45% RH; direct expansion cooling coil with R-410A refrigerant in a single circuit; digital scroll compressor with variable capacity operation from 20-100%; electronically commutated (EC) fan with 1,800 CFM airflow; 2-stage electric reheat rated at 20.4 KBTUH (6 kW); infrared humidifier with 7.7 lb/h capacity; MERV 8 filter; and Liebert iCOM control system with 7-inch high-definition color touchscreen display featuring BACnet IP, Modbus TCP/IP, and SNMP connectivity. Standard features include a locking disconnect switch, three alarm contacts, smoke sensor, Liebert Liqui-Tect 410 point leak detection sensor, dual-float condensate pump, and 18-inch grilled discharge plenum with two grilles. The condenser includes microchannel aluminum coils, variable speed EC fan motor, premium efficiency fan control, and field-supplied CANbus communication capability with the indoor unit. All electrical, piping, and interconnection requirements are detailed with dimensional data, connection locations, and technical specifications for system installation and commissioning.

View the file

Other files

File Type Posted
S30 - SAM - Special Notice - Cancellation - 36C77626R0062_2 - EHRM Infra Upgrades - Togus.pdf PDF
S06 - Amend 0002 - Att 03 - Corrected Agenda - RFP - 07202026 - EHRM Infra - Togus.pdf PDF
S06 - Amend 0002 - 36C77626R0062 - 07202026 - EHRM Infra - Togus.pdf PDF
S06 - Amend 0001 - Att 02 - SV - Attendance SHT - 06292026 - EHRM Infra - Togus.pdf PDF
S06 - Amend 0001 - 36C77626R0062 - 07142026 - EHRM Infra - Togus.pdf PDF
S06 - Amend 0001 - RFIs - 07132026 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S06 - Amend 0001 - Att 01 - Rvd Structural Drwg - 06192026 - EHRM Infra - Togus.pdf PDF
S06 - Amend 0001 - Att 03 - SV - Agenda - RFP - 06292026 - EHRM Infra - Togus.pdf PDF
S02 - SOW - Att 05 - Drwg - Vol 3 - 02182026 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - SOW - Att 13 - Const Sch - 02132026 - EHRM Infra Upgrades - Constr Togus.pdf PDF
S02 - SOW - Att 26 - Cut Sheet 04 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - Att 03 -Prj Info Sheet for KTR - EHRM Infra Upgrade - Togus.docx DOCX document
S02 - SOW - Att 03 - Drwg - Vol 1C - 02182026 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - SOW - Att 22 - TS-000 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - Att 07 - 852.219-75 - 06172026 - EHRM Infra Upgrade - Togus.pdf PDF
S02 - Att 04 - Memo - Brand Name - 04092026 - EHRM Infra Upgrade - Togus.pdf PDF
S02 - SOW - Att 35 - Cut Sheet 13 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - SOW - Att 17 - Memo - Phy Sec Compliance - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - SOW - Att 27 - Cut Sheet 05 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - SOW - Att 09 - Specs - Vol 3- 02182026 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - SOW - Att 24 - Cut Sheet 02 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - Att 05 - Division Cost Breakdown - EHRM Infra Upgrade - Togus.xlsx XLSX spreadsheet
S02 - SOW - Att 29 - Cut Sheet 07 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - SOW - Att 37 - Cut Sheet 15 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - SOW - Att 16 - Submittal Reg - 02182026 - EHRM Infra - Upgrades - Constr - Togus.xlsx XLSX spreadsheet
S02 - SOW - Att 14 - Design Calcs - 02182026 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - SOW - Att 18 - Memo - Prj Stnd Compliance - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - SOW - Att 21 - PCRA 3 - MCR and Trench Work - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - SOW - Att 40 - Cut Sheet 18 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - SOW - Att 33 - Cut Sheet 11 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - SOW - Att 01 - Drwg - Vol 1A - 02182026 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - SOW - Att 38 - Cut Sheet 16 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - SOW - Att 06 - Drwg - Vol 4 - 02182026 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - SOW - Att 11 - Haz Mat Report - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - SOW - Att 12 - Geotechnical Report - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - SOW - Att 32 - Cut Sheet 10 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - SOW - Att 08 - Specs - Vol 1 - Div 02-14 - 02182026 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - SOW - Att 20 - PCRA 2 - Cabling and Data Outlets - EHRM Infra Upgrades - Constr - Togus.pdf PDF
RFP - EHRM Infra Upgrade - 36C77626R0062 - 06172026 - Togus.pdf PDF
S02 - SOW - Att 19 - PCRA 1 - TR Constr - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - SOW - Att 07 - Specs - Vol 1 - Div 00-01 - 02182026 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - SOW - Att 15 - Design Narrative - 02182026 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - SOW - Att 23 - Cut Sheet 01 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - SOW - Att 31 - Cut Sheet 09 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - Att 02 - PPQ - EHRM Infra Upgrade - Togus.docx DOCX document
S02 - SOW - Att 02 - Drwg - Vol 1B - 02182026 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - SOW - Att 34 - Cut Sheet 12 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - Att 01 - SOW - 05112026 - EHRM Infra Upgrades - Togus.pdf PDF
S02 - SOW - Att 10 - Specs - Vol 4 - 02182026 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - SOW - Att 36 - Cut Sheet 14 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
Show 40 more

Latest 50 of 57 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Liebert Products & Service

World Headquarters United States

1050 Dearborn Drive, P.O. Box 29186 Columbus, Ohio 43229 Telephone: 614-888-0246

LIEBERT PDX

AIR-COOLED SYSTEM

Job Name VA TOGUS MAINE

Model PX011UA1AD / MCS028E1AD

Quantity 1 / 1

Date 8/14/2023

Invoice #

Purchaser

P.O. #

Tag #

Submitted By Matt Campbell

PRELIMINARY SUBMITTAL

Page 1 of 42 08/14/2023

LIEBERT PDX

ENGINEERING SPECIFICATION SHEET

Air Cooled Systems

Project Name: VA TOGUS MAINE Date: August 14, 2023 Reference No.: PRELIMINARY SUBMITTAL Submitted By: MATTHEW CAMPBELL

Indoor Model Number: PX011UA1AD Qty: 1 Outdoor Model Number: MCS028E1AD Qty: 1

INDOOR UNIT ELECTRICAL SUPPLY REQUIREMENTS for 460 VAC:

460 Volt, 3 Phase, 60 Hertz, Short Circuit Current Rating (SCCR): 65,000 amps

FLA: 18.8

WSA: 22.7

OPD: 25.0

INDOOR UNIT ELECTRICAL SUPPLY REQUIREMENTS for 208 VAC:

208 Volt, 3 Phase, 60 Hertz, Short Circuit Current Rating (SCCR): 65,000 amps

FLA: 39.9

WSA: 48.6

OPD: 60.0

OUTDOOR UNIT ELECTRICAL SUPPLY REQUIREMENTS for 460 VAC:

460 Volt, 3 Phase, 60 Hertz, Short Circuit Current Rating (SCCR): 65,000 amps

FLA: 1.4

WSA: 1.8

OPD: 15

OUTDOOR UNIT ELECTRICAL SUPPLY REQUIREMENTS for 460 VAC:

208/230 Volt, 3 Phase, 60 Hertz, Short Circuit Current Rating (SCCR): 65,000 amps

FLA: 3.0

WSA: 3.8

OPD: 15

NET COOLING CAPACITY DATA

75 °F DB

45% RH

Net Total Cooling Capacity: 44.2 KBTUH Net Sensible Cooling Capacity: 38.8 KBTUH

Air Flow Configuration:

Up flow Front Air Return

PRELIMINARY SUBMITTAL

Page 2 of 42 08/14/2023

ADR

Line

ADR

Text Box

Color:

RAL 7021, Black Gray Matte

Cooling System Type:

Air-Cooled

Refrigerant and Circuits:

R-410A Refrigerant, Field Supplied Single Refrigerant Circuit

Compressor:

Digital Scroll Thermal Expansion Valve Crankcase Heater

Fan And Motor:

EC Fan Fan Motor HP: 1.28 Air Volume: 1,800 CFM External Static Pressure: 0.2 Inches of Water

Electric Reheat:

2-Stage Electric Reheat, 20.4 KBTUH (6 kW)

Humidifier:

Infrared Humidifier Capacity: 7.7 lb/h (3.5 kg/h)

Filter:

Filter Rating: MERV 8 per ASHRAE 52.2-2007 Filter Clog Alarm

Control, Sensors, and Monitoring:

Liebert iCOM Control with High-Definition Display o Integrated Controls and High-Definition Color User Interface o Display Language is English o Audible and Visual Alarms iCOM based communication o Base Comms & Connectivity includes one Ethernet port and one RS-485 port on iCOM controller, dedicated to supporting BACnet IP, Modbus TCP/IP, BACnet 485, Modbus 485 and SNMP v1/v2c/v3

Supply Air Sensor Internal Temperature/Humidity Sensors for return air sensing.

Common Alarm Contact

Optional Equipment:

Dual-float condensate pump One Remote Shut Down Contact

Page 3 of 42 08/14/2023

Three Alarm Contacts Smoke Sensor LT410 Point Leak-Detection Sensor, quantity 1 per unit

Plenum:

18” Grilled Discharge Plenum, with (2) grilles per plenum.

Condensate Pump:

The dual-float condensate pump is complete with integral primary and secondary float switches, pump, motor assembly and reservoir. The secondary float sends a signal to the local alarm and shut down the unit upon high water condition. Condensate pump is factory-mounted internal to the unit.

Locking Disconnect Switch:

A manual fused disconnect switch is mounted in the electrical panel and be capable of disrupting the flow of power to the unit operation from the outside of the unit. The electric panel compartment is accessible only with the switch in the Off position. The electric panel is conveniently located behind the Liebert iCOM™ display door for quick access. Main fuses are located within disconnect.

Short Circuit Current Rating (SCCR):

All 60 Hz units are manufactured with components necessary to provide a 65,000 Amp RMS Short Circuit Current Rating for the entire unit.

Cabinet Description:

The exterior panels are 20-gauge galvanized steel and powder coated with RAL 7021 Black Gray Matte color paint to protect against corrosion. The exterior panels are insulated with 1/2" to 1" (12.7 to 25.4mm) 1-1/2 lb (0.68 kg) insulation. Front and side panels are captive, 1/4 turn fasteners. The cabinet is designed so that all components are serviceable and removable using the front and right sides of the unit. The front door can be opened for service without shutting off the system.

System Type:

Air-Cooled Single refrigeration circuit including a liquid line filter drier, a refrigerant sight glass with moisture indicator, an externally equalized expansion valve, pressure safety switches, and a liquid line solenoid valve.

Refrigerant:

The system is designed for use with R410A refrigerant, which meets the U.S. Clean Air Act for phaseout of HCFC refrigerants.

Compressor:

Digital Scroll The compressor is scroll-type with variable capacity operation from 20-100%, commonly known as a Digital Scroll. The compressor solenoid valve will unload the compressor to provide variable capacity operation. The controller engages and disengages the compressor on a 15 second control cycle.

Includes a suction gas cooled motor, vibration isolators, internal thermal overloads, automatic reset high pressure switch, rotalock service valves, low pressure transducer, Crankcase heater, internal centrifugal oil pump and an operating speed of 3500 RPM at 60Hz. The Crankcase heater and a discharge check valve is provided for additional system protection from refrigerant migration during Off cycles.

Page 4 of 42 08/14/2023

Coil Description:

The direct expansion tilted-slab cooling coil is constructed of copper tubes and hydrophilic coated aluminum fins. The hydrophilic coating significantly improves the speed of condensate drainage from the fins and provides superior water carryover resistance. One stainless steel condensate drain pan is provided.

Fan and Motor:

EC Fan The unit is equipped with one plug fan: direct driven with backward curved blades and Electronically Commutated DC motor; commonly referred to as EC plug fan. The fan speed is variable and automatically regulated by the Liebert iCOM™ control through all modes of operation. The fan has a dedicated motor, fault monitoring circuitry and speed controller which provides a level of redundancy.

Impeller is made of aluminum and factory balanced. This design uses less energy than standard centrifugal blowers by lowering motor kW. The EC Plug Fan uses 10-30% less energy on average than standard AC motor. The EC Plug Fan is located within the unit.

Air Flow Configuration:

Up flow with Front Air Return. The supply air exits from the top of the unit. The return air enters through the front of the unit.

Filter:

Filter Rating: MERV 8 per ASHRAE 52.2 Includes a Filter Clog Alarm

Liebert iCOM:

The Liebert iCOM unit control is factory-set for Intelligent Control which uses 'fuzzy logic' and 'expert systems' methods. Proportional and Tunable PID are user selectable options. Internal unit component control includes the following: System Auto Restart, Sequential Load Activation, Hot Water Flush Cycles (if hot water coil is present), and Predictive Humidity Control. The control system and electronic circuitry is provided with self-diagnostics to aid in troubleshooting. The microcontroller board is diagnosed and reported as pass/not pass. Control inputs are indicated as on or off at the front monitor panel. Control outputs are able to be turned On or Off from the front monitor panel without using jumpers or a service terminal.

The display and housing are viewable while the unit panels are open or closed. The display is organized into three main sections: User Menus, Service Menus and Advanced Menus. The system displays user menus for: active alarms, event log, graphic data, unit view/status overview (including the monitoring of room conditions, operational status in % of each function, date and time), total run hours, various sensors, display setup, and service contacts. A password is required to make system changes within the service or advanced menus.

The Liebert iCOM control can activate an audible and visual alarm in event of any of the following conditions: High/Low Temperature, High/Low Humidity, Change Filters, Loss of Air Flow or Power, and four separate Custom Alarms.

Unit-to-Unit communication with another Liebert PDX/PCW unit included as standard using a private ethernet network between iCOM controllers. Optional network switch required for unit-to-unit communication between three or more PDX/PCW.

Page 5 of 42 08/14/2023 iCOM – High-Definition Color Display:

The standard user interface is the 7” High-Definition Color Display which presents system information and allows all parameters to be viewed and adjusted. It features a capacitive touchscreen for navigation ease and LED color indicating operational status.

Supply Air Sensor:

A factory installed and commissioned supply air sensor ships with the unit for sensor location in the field by others. The sensor is terminated on the Liebert iCOM unit controller terminal strip and the associated cable wiring is coiled within the unit for shipment. It is the responsibility of others to uncoil and locate the sensor in accordance with acceptable best practices and any local codes.

Temperature & Humidity Sensors:

Internal Temperature/Humidity Sensors Factory installed, and commissioned return air temperature/humidity sensors are mounted inside the unit and are factory wired to the Liebert iCOM unit controller. Sensors are used for unit control and monitoring.

Common Alarm Contact:

The common alarm contacts provide the customer with a set of normally open contacts for remote indication of unit alarms.

Base-Comms for BMS Connectivity:

The Liebert iCOM controller provides one Ethernet Port and one RS-485 Port dedicated for BMS Connectivity. Provides ground fault isolated RS-485 Modbus, BACnet IP & Modbus IP network connectivity to Building Management Systems for unit monitoring and management. Also, provides ground fault isolated 10/100 baseT Ethernet connectivity for unit monitoring and management. The supported management interfaces include SNMP for Network Management Systems, HTTP for web page viewing, SMTP for email, and SMS for mobile messaging. The iCOM controller can support dual IP on one network and one 485 protocol simultaneously.

Smoke Sensor:

The smoke sensor samples the return air, shuts down the unit upon activation and sends visual and audible alarms. Dry contacts are available for a remote customer alarm. This smoke sensor is not intended to function as or replace any room smoke detection system that may be required by local or national codes.

Liebert Liqui-Tect® 410 Point Leak Detection Sensor:

The solid-state water sensor has no moving parts and is hermetically sealed to keep out dust and dirt.

The Liebert Liqui-tect 410 (LT410) provides a single-point detection of leaks. The point detection sensor has two gold-plated sensing probes to prevent corrosion resistance and to provide accurate readings. The LT410 constantly monitors points for leaks, internal faults and power failures and warn of any abnormal conditions. Mounting brackets allow for sensor height adjustment and leveling. The LT410 provides two independent outputs to signal both a local alarm panel and a remote building management system or external equipment. Ships loose for field installation.

Page 6 of 42 08/14/2023

Liebert MC Condenser Detailed Description:

Standard Features:

Microchannel aluminum coil(s) Integrated fan motor/blade/guard assembly Electronic control of fan speed Fused, locking and lockable electrical disconnect switch Variable fan speed motor Short Circuit Current Rating of 65,000 Amps, rms Factory wired and mounted NEMA 3R box containing main electrical panel.

Cabinet:

Bright aluminum exterior panels Bright aluminum NEMA 3R box containing electrical panel Bright aluminum 36” legs

Control/Communication/Fan:

Variable speed EC fan Premium electronic control & communication board CANbus connection terminals for communication with iCOM

Refrigerant & Circuits:

R-410A set points Single refrigerant circuit

Optional Features:

E-Coated Coils with UV Topcoat

Page 7 of 42 08/14/2023

Page 8 of 42 08/14/2023

© 2023 Liebert Corporation. All Rights Reserved

Liebert Rating System (LRS) 3.6.0.10w 4.4.3.18e

System: [Digital Loading: 100%, SC: 10 °F, SH: 12 °F] [ESP:0.2]

Ent

DB

(°F)

Ent

WB

(°F)

Ent

RH

Ent

DP

(°F)

Return Air Vol

(ACFM)

Supply Air Vol

(ACFM)

Air Face

Vel (ft/min)

Unit Air Vol

(SCFM)

Amb

DB

(°F)

NTCC

(kBtu/hr)

NSCC

(kBtu/hr)

THR

(kBtu/hr)

Cond.

Airflow

(ACFM)

Lvg

DB

(°F)

Lvg

WB

(°F)

Tot Comp

Pwr (kW)

Sys Power

Input (kW)

Sys

SCOP

(W/W)

Sys NSenCOP

(W/W)

Fan kW

(kW)

Airflow Calibration

(V)

75 61.1 45 52.3 1800 1730 191 1758 95 44.2 38.8 57 4649 54.9 52.2 3.11 4.27 2.67 2.67 0.52 8.07

System

Compressor Power (kW) Sat. Discharge Temp. (°F) Sat. Suction Temp. (°F)

3.11 111.2 45.1

Project Name:

Customer Name:

Sales Rep. Name:

Office Name:

Phone Number:

PDX Model PX011UA1*D~MCS028E1; Air Cooled Manufacturer:

Unit Power Supply:

Refrigerant:

Internal Filter Class:

Spec.sheet output date:

Return Airflow (std. motor):

Altitude:

ESP:

Width:

Depth:

Height:

Weight:

Condenser(s)

Manufacturer:

Model:

Condenser Type:

Design Ambient:

Power Option:

Compressor(s)

Manufacturer:

Model:

Compressor Type:

Power Supply:

Evaporator(s)

Manufacturer:

Model:

Fin Type:

Number of Rows:

Fin Density:

Face Area:

Surface Area:

Miscellaneous

Humidifier Type:

Bypass airflow:

Cooling Fan(s)

Model:

Description:

Air Supply:

Power Supply:

Quantity of Motors:

1. Capacities shown have been reduced by fan motor(s) heat (net).

2. System Power Input includes Compressor(s), Blower Motor(s), Condenser(s), and Control Power.

3. Coil airflow has not been reduced by a bypass.

4. Capacity Tolerance is 5%.

5. ACFM/ACMH is the unit actual air flow rate when measured at the specific return or supply temperature and barometric conditions that define a unique air density.

6. SCFM/SCMH is the unit air flow rate when converted to standard air density of 0.075 lb/ft3 at sea level.

7. NTCC, Net Total Cooling Capacity

8. NSCC, Net Sensible Cooling Capacity

Certified in accordance with the AHRI Datacom Cooling Certification Program at AHRI Standard 1360 (I-P) and ASHRAE Standard 127- 2007 Standard Rating Conditions. Certified units may be found in the AHRI Directory at www.ahridirectory.org.

Notes

VA TOGUS

MATTHEW CAMPBELL

Vertiv, Seattle Office +1 206 763 5000

Liebert North America 208/3/60 R410A Merv 8 Std. - 2 inch (51 mm) 03-Apr-23

1800 ACFM

0 ft

0.20 InH2O

34.5 in

32.3 in

77.6 in 600 lb

Liebert North America

MCS028E1

MCH Condenser 105 °F 208-230/3/60

Copeland ZPD42K5E-60Hz Digital 208/3/60

Liebert North America RTPX011UEvapx1 Lanced 12 fpi

9.46 ft² 540 ft²

No Humidifier 0 %

EC-355

U - DX Cooling Only Top 208/3/60

Page 9 of 42 08/14/2023

REV : 5

REV DATE : 9/18

DPN003380

Page :1 /2

AIR COOLED

Fo rm

N o.

: D P

N

_R E

V

STANDARD FEATURES

LIEBERT PDX

DX COOLING COIL The evaporator coil is constructed of copper tubes and hydrophilic coated aluminum fins. A stainless steel condensate drain pan is provided.

REFRIGERATION SYSTEM Single refrigeration circuit shall include a liquid line filter drier, a refrigerant sight glass with moisture indicator, an expansion valve, pressure safety switch, and a liquid line solenoid valve.

DIGITAL SCROLL COMPRESSOR The compressor is an R-410A scroll-type with variable capacity operation from 20-100%.

Compressor solenoid valve unloads the compressor to provide variable capacity operation. The compressor has a suction gas cooled motor, EPDM vibration isolators, internal thermal overloads, automatic reset high pressure switch with lockout after three failure occurrences, RotoLock service valves, low pressure transducer and crankcase heater.

ELECTRONICALLY COMMUTATED (EC) FAN is plug type, integral direct driven fan with backward curved blades and Electronically Commutated DC motor; commonly referred to as an EC fan. The fan speed shall be variable and automatically regulated by the Liebert iCOM® control through all modes of operation. The impeller shall be made of aluminum and dynamically balanced. The fan shall be located to draw air through the coil to ensure even air distribution and maximum coil performance.

CABINET The exterior panels are 20 gauge steel and powder coated with RAL7021 black gray matte color paint to protect against corrosion. Exterior panels are insulated with ½” (sides) or 1”(front and rear), 1-1/2 lb insulation. Front and side panels have captive, 1/4 turn fasteners to allow quick panel removal. The cabinet is designed so that all components are serviceable and removable using the front and right sides of the unit.

FILTER - The filter shall be deep-pleated, 2 in (51mm) thick with a MERV8 rating efficiency based on ASHRAE 52.2-2007.

LIEBERT iCOM CONTROL SYSTEM The Liebert PDX is controlled by the iCOM Control System. A 7-inch, high definition, capacitive, color touchscreen presents system information and allows parameters to be viewed and adjusted. The controls shall be menu driven and shall display user menus for active alarms, event log, graphic data, unit view/status overview (including the monitoring of room conditions, operational status in percentage of each function, date and time), total run hours, various sensors, display setup and service contacts. It features a 3-level password protection system. Unit–to-Unit communication capability with other Liebert PDX units is included as standard.

BASE-COMMS FOR BMS CONNECTIVITY The Liebert iCOM controller provides one Ethernet Port and one RS-485 Port dedicated for BMS connectivity. Provides ground fault isolated RS-485 Modbus, BACnet IP & Modbus IP network connectivity to Building Management Systems for unit monitoring and management. Also, provides ground fault isolated 10/100 baseT Ethernet connectivity for unit monitoring and management. The supported management interfaces include: SNMP v1/v2c/v3 for Network Management Systems, HTTP for web page viewing, SMTP for e-mail, and SMS for mobile messaging. The iCOM controller can support dual IP on one network and one 485 protocol simultaneously.

UNIT DISCONNECT SWITCH A “Locking-Type” fused disconnect switch is available. The “Locking-Type” consists of a main unit switch operational from the outside of the unit. Access to the high voltage electric panel can be obtained only with the switch in the “off” position. The disconnect has main fuses within the disconnect.

65,000 AMP SHORT CIRCUIT CURRENT RATING (SCCR) The 60Hz electrical panel provides 65kA SCCR.

REMOTE SHUTDOWN TERMINAL The remote shutdown terminal shall provide the customer with a location to remotely shut down the unit, complying with the National Fire Code.

Document generated 26 July 2023 04:51 PM (EST).

Page 10 of 42 08/14/2023

REV DATE : 9/18

DPN003380

Page :2 /2

AIR COOLED

Fo rm

N o.

: D P

N

_R E

V

STANDARD FEATURES

LIEBERT PDX

COMMON ALARM CONTACT The common alarm contacts shall provide the customer with a set of normally open contacts for remote indication of unit alarms. Four alarm contacts shall be provided for units without a condensate pump. Three alarm contacts shall be provided for units with a condensate pump.

SUPPLY AIR SENSOR The supply air temperature sensor shall provide real-time, direct feedback to the downflow raised floor cooling unit to provide a consistent supply air temperature by adjusting the compressor capacity or the chilled water valve accordingly to maintain set point. The supply air temperature sensor will provide real-time, monitoring of discharge air temperature on all other units.

INFRARED HUMIDIFIER High intensity infrared quartz lamps over a stainless steel humidifier pan. An automatic water supply system maintains water level in the pan and a timed flush system greatly reduces mineral precipitation, and is field adjustable to change the cycle time. A 1" (25mm) air-gap within the water supply piping assembly shall prevent backflow of the humidifier supply water.

ELECTRIC REHEAT Electric low watt density 304/304 stainless steel fin tubular electric reheat elements provide reheat to control room dry bulb temperature.

Document generated 26 July 2023 04:51 PM (EST).

Page 11 of 42 08/14/2023

REV : 3

REV DATE : 8/18

DPN003381

Page :1 /2

AIR COOLED

F or m N o.

: D

P N

_R

E V

OPTIONAL FEATURES

LIEBERT PDX

(Refer to specification sheet for options supplied)

STEAM GENERATING HUMIDIFIER is factory-installed in the cooling unit and is operated by the Liebert iCOM control system. It is complete with disposable cylinder, all supply and drain valves, steam distributor and electronic controls. The need to change the canister is indicated on the Liebert iCOM display. The humidifier is designed to operate with water conductivity from 330-670 (60Hz) microS/cm. System automatically fills and drains as well as maintains the required water level based on conductivity. A 1” (25mm) air-gap within the humidifier assembly shall prevent backflow of the humidifier supply water.

SCR REHEAT is a 6kw electric reheat element controlled by a variable output Silicon Controlled Rectifier (SCR) control. The SCR reheat option provides precise temperature control. PX011 models only.

DUAL-FLOAT CONDENSATE PUMP has a capacity of 5 GPM (18.9 l/min) at 40ft (12.2 m) head. Pump is complete with integral primary and secondary float switches, pump, motor assembly and reservoir. The secondary float shall send a signal to the local alarm and shut down the unit upon high water condition. The condensate pump shall be factory-installed on upflow units and field-installed on downflow units.

DIGITAL SCROLL COMPRESSOR SOUND JACKET The compressor sound jacket shall reduce the level of sound emitted from the compressor. It shall consist of a 3/8 inch closed cell polymeric 4.5 - 8.5 lb/ft3 density jacket that encloses the compressor.

STANDARD SCROLL COMPRESSOR The compressor is an R-410A scroll-type with a suction gas-cooled motor, EPDM vibration isolators, internal thermal overloads, automatic reset high pressure switch with lockout after three failures, Rotolock service valves, and low pressure transducer. The crankcase heater and a discharge check valve shall be provided for additional system protection from refrigerant migration during off cycles.

DUAL COOL consists of an additional free-cooling chilled water/glycol coil and is constructed of copper tubes and hydrophilic coated aluminum fins. A 2-way or 3-way modulating valve controls the chilled water flow passing through the cooling coil. The free cooling coil is strategically located in the return air stream of an air-cooled unit to either precool or totally cool the air before entering the refrigeration coil. Liebert iCOM controls the activation/deactivation and modulation of the cooling sources allowing the system to function as a modulating chilled water/glycol system, as a compressorized system, or combination of both. Standard pressure rating is 150 psig (1034 kPa). Optional pressure rating is 400 psig (2758 kPa). This is a 4-pipe system.

ELECTRONIC EXPANSION VALVE shall be of stepper-motor type. The EEV shall maintain consistent superheat of the refrigerant vapor at the outlet of the evaporator coil over the unit’s operating range. The valve shall be controlled by a separate electronic controller.

Superheat shall be determined through the suction pressure-temperature method.

FILTER - The filter shall be deep-pleated, 2 in (51mm) thick with a MERV11 rating efficiency based on ASHRAE 52.2-2007.

DOUBLE SKIN PANELS The exterior panels shall be internally lined with 20 gauge galvanized steel, sandwiching the insulation between the panels for easy cleaning.

SMOKE SENSOR - The Smoke Sensor samples the return air and shuts down the unit upon activation and sends visual and audible alarms. Dry contacts are available for a remote customer alarm. This smoke sensor is not intended to function as or replace any room smoke detection system that may be required by local or national codes.

Document generated 26 July 2023 04:51 PM (EST).

Page 12 of 42 08/14/2023 campbem12129 Cross-out campbem12129 Cross-out

REV DATE : 8/18

DPN003381

Page :2 /2

AIR COOLED

F or m N o.

: D

P N

_R

E V

OPTIONAL FEATURES

LIEBERT PDX

HIGH TEMPERATURE SENSOR - The High Temperature Sensor is mounted in the electric panel with the sensing element in the return air flow. The high temperature sensor shall immediately shut down the system when high temperatures are detected.

COMPRESSOR OVERLOAD SENSOR A pair of N/O contacts shall be factory-installed and wired to each compressor to indicate

Compressor Overload.

REMOTE TEMPERATURE AND HUMIDITY SENSORS Are provided in a vented case for mounting in the room to be conditioned.

Includes 30 ft. (9m), 60 ft. (18m), 90 ft. (27m), 120 ft. (36m), or 150 ft. (45m) of cable supplied for connecting sensors to unit.

REHEAT/ HUMIDIFIER LOCKOUT – The option includes the relays necessary to disable the reheat and humidifier from an external customer supplied 24 Volt AC signal while on emergency power.

LOW VOLTAGE TERMINAL PACKAGE One (1) extra N/O common alarm contacts shall be provided. Two (2) extra remote shutdown terminals shall be provided. One (1) pair of N/O contacts shall be factory-installed and wired to indicate Main Fan Overload. One (1) pair of N/O contacts shall be provided for Liqui-tect signal shut down. (Liqui-tect not included).

REMOTE HUMIDITY CONTACT allows the unit’s humidity controller to control a humidifier outside the unit. Power to operate the remote humidifier does not come from the Liebert PDX unit.

FLOOR STAND Is constructed of galvanized steel and available in heights from 6” to 24” (150mm to 610mm) with vibration isolation pads provided on the adjustable legs.

RETURN AIR FLOOR STAND ASSEMBLY The upflow unit with rear return air configuration shall be supplied with a skirted-floor stand assembly. The floor stand assembly shall be constructed of galvanized steel with powder coated panels and supplied with air filter. The floor stand assembly shall be 24-1/8 in (613mm) high and have adjustable legs with vibration isolation pads. It provides a rear return duct flange and removable panel for filter access.

UPFLOW UNIT PLENUM(S) are available in various configurations for upflow units: ducted air discharge with solid panels or 2 way, 3 way, or 4 way air discharge with grilles. Each plenum is constructed of 20 gauge steel with 1” (25.4mm), 1 1/2 Ib. (.68kg) insulation and is powder-coated with RAL7021 black gray matte color paint to protect against corrosion. The ducted air discharge plenum is available in 18

in. (457mm), 24 in. (610mm), 30 in. (762mm), 36 in. (914mm), 42 in. (1067mm), or 48 in. (1219mm), and the air discharge with grilles plenum is 18 in. (457mm) high.

DOWNFLOW UNIT PLENUM(S) are available in various heights. Each plenum is constructed of 20 gauge steel with 1” (25mm), 1-1/2lb (0.68kg) insulation and is powder-coated with RAL7021 black gray matte color paint to protect against corrosion. The ducted air return plenum is available in 18” (457mm), 24” (610mm), 30” (762mm), 36” (914mm), 42” (1067mm), or 48” (1219mm).

LIQUI-TECT SENSOR - The water sensor is a hermetically sealed solid state device with no moving parts. When the sensor detects the presence of moisture, the alarm system is activated.

Page 13 of 42 08/14/2023 campbem12129 Cross-out campbem12129 Cross-out campbem12129 Cross-out campbem12129 Cross-out campbem12129 Cross-out

REV : 8

REV DATE : 12/17

DPN002929

Page :1 /1

AIR COOLED MODELS WITH TXV

F or m N o.

: D

P N

_R

E V

PIPING SCHEMATIC

LIEBERT PDX

Filter DrierSight Glass

SUCTION

LIQUID

COMPRESSOR

Thermal Expansion Valve

EVAPORATOR

COIL

Check Valve

CONDENSER COIL

FACTORY REFRIGERANT PIPING

FIELD PIPING

For rises over 25ft. (7.6m), trap every 20ft. (6m) or evenly divided

SERVICE / SCHRADER (ACCESS) CONNECTION NO VALVE CORE

LIQUID RETURN

HOT GAS DISCHARGE

Sensing Bulb

External Equalizer

Service Valve

Service Valve

SERVICE / SCHRADER (ACCESS) CONNECTION WITH VALVE CORE

LEE-TEMP RECEIVER

Service Valve

Relief Valve Check Valve

Head Pressure Control Valve

LIQUID RETURN

Digital Solenoid Valve

Optional Field Installed Fusible Plug

HOT GAS

DISCHARGE

LIEBERT MC CONDENSER

LIEBERT PDX UNIT

LIEBERT MC CONDENSER

WITH LEE-TEMP RECEIVER

LIQUID

LIQUID

HOT GAS DISCHARGE

Solenoid Valve

CONDENSER COIL

Includes factory provided inverted trap. No external trap required.

Includes factory provided inverted trap. No external trap required.

Notes:

1. Schematic representation shown. Do not use for specific connection locations.

2. Components are not supplied by Liebert but are required for proper circuit operation and maintenance.

3. Traps must be installed and horizontal lines pitched to ensure proper oil return and to reduce liquid floodback to compressor. Pitch horizontal hot gas piping at a minimum of 1/2" per 10 feet (42mm per 10m) so that gravity will aid in moving oil in the direction of the refrigeration flow.

4. Do not isolate any refrigerant circuits from over pressurization protection.

Trap at base of risers over 5ft. (1.5m)

INTERCONNECTING

PIPING

Pressure Transducer

Document generated 26 July 2023 04:51 PM (EST).

PRELIMINARY SUBMITTAL

Page 14 of 42 08/14/2023 campbem12129 Line

Line

REV : 7

REV DATE : 4/18

DPN002937

Page :1 /1

UPFLOW MODELS

F or m N o.

: D

P N

_R

E V

CABINET DIMENSIONAL DATA

LIEBERT PDX & PCW

Note: Unit with front return shown. Bottom return with rear return floorstand is also available (24" height rear return floorstand is required for use with bottom return unit).

Liebert PDX Model No. PX011 PX018-023 PX029

Air Cooled 600 (272) 670 (304) 700 (317)

Air Cooled w/dual cool 700 (317) 750 (340) 790 (358)

Water/Glycol 620 (281) 690 (313) 720 (327)

GLYCOOL™ or Water/Glycol w/dual cool 720 (327) 770 (349) 810 (367)

Liebert PCW Model No. PW011 PW017 PW029

Chilled Water 575 (260) 600 (272) 650 (294)

DRY WEIGHT lb (kg) APPROXIMATE

Top View

Front View

1 1/4" 32mm

30 1/4" 768mm

Duct Flange

32 5/8" 827mm

Duct Flange

34 1/2" 876mm

77 1/2" 1970mm

3/4" 19mm

34" 864mm

24" 610mm

Shaded area indicates a recommended minimum clearance be provided for component access.

Recommended Clearance for unit installation and for servicing these components if equipped:

Reheat, Filter Clog Switch, Econ-O-Coil Valve, or Gravity Drain Connections.

5 5/8" 143mm

34 3/8" 874mm

Document generated 26 July 2023 04:51 PM (EST).

PRELIMINARY SUBMITTAL

Page 15 of 42 08/14/2023 campbem12129 Cross-out campbem12129 Cross-out campbem12129 Rectangle campbem12129 Cross-out

REV : 8

REV DATE : 3/19

DPN002981

Page :1 /1

UPFLOW DISCHARGE GRILLE

F or m N o.

: D

P N

_R

E V

PLENUM DIMENSIONAL DATA

LIEBERT PDX & PCW

WITH GRILLE

FRONT VIEW - UNIT WITH PLENUM

FRONT VIEWS - CHECK ONE (1):

REAR VIEWS - CHECK ONE (1):

LEFT SIDE VIEWS -

CHECK ONE (1): RIGHT SIDE VIEWS -

CHECK ONE (1):

WITH GRILLE

WITHOUT GRILLE

WITH GRILLE

WITHOUT GRILLE

WITHOUT GRILLEWITHOUT GRILLE

WITH GRILLE

SIDE VIEW - UNIT WITH PLENUM

ECS

ECR

E1

E2

LV1

LV2

L1 (PDX)

WS

G1 (PDX)

WR

CDP

HUM

Notes:

1. Two grilles minimum per plenum required.

The nominal grille size is 24" (609mm) x 14" (355mm).

2. All Plenums are shipped flat (non-assembled) and must be assembled on site.

3. Upflow bottom return units are available with required rear return floorstand with filter.

4. Units supplied with Dual Cooling systems only (4 pipe system).

5. Concentric knockouts to be used based on field supplied conduit diameter.

POINT DESCRIPTION X in. (mm) Y in. (mm) KNOCKOUT SIZE, in. (mm)

L1 LIQUID LINE SYSTEM 1

G1 HOT GAS DISCHARGE 1

CDP CONDENSATE DRAIN WITH PUMP 3-1/2 (89) 6-1/8 (155) 3/4 (19)

HUM HUMIDIFIER SUPPLY LINE 29-1/2 (748) 26 (662) 1/2 (13)

WS SUPPLY-CW/WATER/GLYCOL

WR RETURN-CW/WATER/GLYCOL/GLYCOOL™

ECS ECON-O-COIL SUPPLY / GLYCOOL™ SUPPLY 3-1/8 (80)

ECR ECON-O-COIL RETURN 8-1/4 (210)

E1 ELECTRICAL CONN. (HIGH VOLT) 29-1/8 (739) 28-5/8 (728)

E2 ELECTRICAL CONN. (HIGH VOLT) 31-1/4 (793) 27-5/8 (702)

LV1 ELECTRICAL CONN. (LOW VOLT) 32-1/4 (818)

LV2 ELECTRICAL CONN. (LOW VOLT) 30-1/2 (775)

5-1/8 (130)

4-1/4 (109)

5-1/8 (130)

1 (25)

25-5/8 (651)

25-5/8 (651)

25-5/8 (652)

7/8 (23), 1-3/8 (35), 1-3/4 (44)

2 (51)

2 (51)

31 3/4" 807mm

1 3/8" 35mm

77 1/2" 1970mm

18" 458mm

34 1/2" 876mm

PRELIMINARY SUBMITTAL

Page 16 of 42 08/14/2023 campbem12129 Cross-out

REV : 10

REV DATE : 5/19

DPN002939

Page :1 /1

UPFLOW AIR COOLED MODELS

F or m N o.

: D

P N

_R

E V

PRIMARY CONNECTION LOCATIONS

LIEBERT PDX

FRONT VIEW

PX011 PX018, PX023 PX029

L1 LIQUID LINE SYSTEM 25-5/8 (651) 3/8 1/2 5/8

G1 HOT GAS DISCHARGE 27-7/8 (708) 1/2 5/8 7/8

CD CONDENSATE DRAIN N/A 16-5/8 (422) 3-1/8 (89)

CDP CONDENSATE DRAIN WITH PUMP 3-1/4 (83) 5-7/8 (149)

HUM HUMIDIFIER SUPPLY LINE 29-1/2 (749) 26 (660)

ECS ECON-O-COIL SUPPLY 3-1/4 (83)

ECR ECON-O-COIL RETURN 8-1/4(210)

E1 ELECTRICAL CONN. (HIGH VOLT) 30 (762)

E2 ELECTRICAL CONN. (HIGH VOLT) 27-3/4 (705)

LV1 ELECTRICAL CONN. (LOW VOLT) 27-1/2 (699)

LV2 ELECTRICAL CONN. (LOW VOLT) 26-1/2 (673)

7/8, 1-3/8, 1-3/4

7/8

Z in. (mm)

N/A

N/A

1-1/8

CONNECTION SIZE in.

3/4 NPT FEMALE

1/2

1/4

POINT DESCRIPTION X in. (mm) Y in. (mm)

1-1/2 (38)

31-1/4 (794)

5-1/8 (130)

4-1/4 (108)

Notes:

1. Drawing not to scale. All dimensions from rear corner of unit including panels and have a tolerance of ± 1/2" (13mm).

2. Field pitch Condensate drain line a minimum of 1/8" (3mm) per 12" (305mm) All units contain a factory installed condensate trap. Do not trap external to the unit.

Drain line may contain boiling water. Select appropriate drain system materials The drain line must comply with local codes.

3. Supplied on Dual Cooling Systems only.

4. Unit with front return shown. Bottom return with rear return floorstand also available.

5. All refrigerant & water piping connections are O.D. Copper except as noted.

6. Concentric knockouts to be used based on field supplied conduit diameter.

LV1

ECS

LV2

X

Y

O

TOP VIEW

FRONT OF UNIT

L1

E1 E2

HUM

CDP

RIGHT SIDE VIEW

G1

ECR

ECSECR

L1G1

CD 25 5/8"

143mm

Document generated 26 July 2023 04:51 PM (EST).

PRELIMINARY SUBMITTAL

Page 17 of 42 08/14/2023

REV : 0

REV DATE : 3/18

DPN004594

Page: 1/3

UPFLOW & DOWNFLOW MODELS

Fo rm

N o.

: D P

N

_R E

V

ELECTRICAL FIELD CONNECTIONS

LIEBERT PDX & PCW

1. High Voltage Entrance. Supplied on top and bottom of electric box. Knockout size Ø1.75in (44.5mm).

2. Low Voltage Entrance. Ø1.375 in. (34.9mm) hole located on bottom of Electric Box.

3. Three phase Electric Service and earth ground. Field supplied.

4. Three phase connection. Electric service connection terminals on disconnect.

5. Factory installed disconnect switch. Fused disconnect switch provided on units.

6. Earth ground connection. Connection terminals for field supplied earth grounding wire.

7. Earth ground bar. Connection terminals with factory ground from each high voltage component for field supplied earth grounding wire.

8. Control and monitoring section of electric box.

9. Remote unit shutdown. Replace existing jumper between terminals 37 & 38 with normally closed switch having a minimum 75VA, 24VAC rating. Use field supplied Class 1 wiring. Two additional contact pairs available as an option (labeled as 37B & 38B, 37C & 38C). Replace existing jumper for appropriate pair as done for 37 & 38.

10. Remote Alarm Device (RAD) Connections. Alarm connections may be factory wired or field wired. See schematic, RAD1- 4, for factory wired alarms. For field wired alarms, use Class 1 wiring to connect normally open contacts between terminals 24 & 50, 24 & 51, 24 & 55, or 24 & 56. Suitable for 24VAC.

11. Smoke detector alarm connections. Field supplied Class 1 wiring to 1 Amp, 24VAC maximum remote alarm circuits.

Factory wired contacts from optional smoke detector are #91-Common, #92-NO, and #93-NC. Optional smoke detector trouble (SDT) connections #80 & # 81.

12. Common alarm connection. Field supplied Class 1 wiring to common alarm terminals 75 & 76 (and optional 94 & 95, and 96 & 97), which are factory connected to normally open contacts, 1 Amp, 24VAC maximum on common alarm relay (R3).

13. Heat rejection connection. Field supplied Class 1 wiring to heat rejection interlock terminals 70 & 71 which are factory connected to normally open compressor side switch (self contained units only) or to GLYCOOL relay K11 (GLYCOOL units only). On Dual Cool units only, connect auxilliary cooling source terminals 72 & 73 to relay K11. See indoor and outdoor electric schematic for more information.

14. Reheat and Humidifier Lockout. Optional emergency power lockout of reheat and/or humidifier: Connections #82 & #83 are provided for remote 24VAC source and Class 1 wiring by others.

15. Main Fan Auxiliary Switch. Optional main fan auxiliary side switch. Terminals located on customer connection terminal block for remote indication that the evaporator fan motor/unit is on. Field to connect 24V maximum, Class 1 wiring to connections #84 & #85.

16. Optional Condensate Alarm (Dual Float Condensate Pump only). Relay terminals located on customer connection terminal block for remote indication. Field supplied Class 1 wiring to connections #88 & #89.

17. Optional Remote Liquitect Indicator. Optional remote liquitect indicator for unit shutdown. Terminals located on customer connection terminal block. Field to connect 24V maximum, Class 1 wiring to connections #58 & #59.

18. Optional Analog Inputs #3 & #4. Customer connection to terminals 41, 42, 43, 44 for analog inputs.

19. Spare Terminals for Optional Devices. Customer connection when optional device is supplied. See unit schematic.

Document generated 26 July 2023 04:51 PM (EST).

PRELIMINARY SUBMITTAL

Page 18 of 42 08/14/2023 campbem12129 Cross-out

DPN004594

Page: 2/3

UPFLOW & DOWNFLOW MODELS

Fo rm

N o.

: D P

N

_R E

V

ELECTRICAL FIELD CONNECTIONS

LIEBERT PDX & PCW

20. CANbus Connector. Terminal block with terminals 49-1 (CAN-H) and 49-3 (CAN-L) + SH (shield connection).

The terminals are used to connect the CANbus communication cable (provided by others) from the indoor unit to the Liebert MC Condenser.

21. CANbus Cable. CANbus cable provided by others to connect to the outdoor condenser and optional PRE unit.

No special considerations are required when the total external cable connection between the indoor unit and outdoor unit(s) is less than 450FT (137M). For total external cable connections greater than 450FT (137M). For external cable connections greater than 450FT (137M), but less than 800FT (243M) a CANbus isolator is required (Contact Factory).

Cable must have the following specifications:

- Braided shield or foil shield with drain wire

- Shield must be wired to ground at indoor unit

- 22-18AWG stranded tinned copper

- Twisted pair (minimum 4 twists per foot)

- Low Capacitance (15pF/FT or less)

- Must be rated to meet local codes and conditions

- EXAMPLES BELDEN 89207 (PLENUM RATED), OR ALPHA WIRE 6454 CATEGORY 5, 5E, OR HIGHER

22. Do not run in same conduit, raceway, or chase as high voltage wiring.

23. For CANbus network lengths greater than 450FT (137M) call Factory.

OPTIONAL COMMUNICATION CONNECTIONS

24. Unit-To-Unit – Plug 64 is reserved for U2U communication.

25. Site and BMS – Plug 74 and terminal block 3 are reserved for Site and BMS connections. Plug 74 is an eight pin RJ45 for a Cat 5 cable. Terminal block 3 is a two position screw terminal block for use with twisted pair wires. Only one of these connections can be used at a time.

NOTE: Refer to specification sheet for total unit full load amps, wire size amps, and max overcurrent protective device size.

Page 19 of 42 08/14/2023

DPN004594

Page: 3/3

UPFLOW & DOWNFLOW MODELS

Fo rm

N o.

: D P

N

_R E

V

ELECTRICAL FIELD CONNECTIONS

LIEBERT PDX & PCW

UPFLOW UNIT

38B

38B

37B 38C

37C

37B 38C

37C S

H

S H

49-3 49-1

49-3 49-1

37 37

1 High Voltage Entrance

6 87

DOWNFLOW UNIT

Terminal Block For Customer Connection

2Low Voltage Entrance

24 25

Document generated 26 July 2023 04:51 PM (EST).

PRELIMINARY SUBMITTAL

Page 20 of 42 08/14/2023 campbem12129 Line

DPN004596

Page: 1/1

UPFLOW MODELS

F or m N o.

: D

P N

_R

E V

ELECTRICAL FIELD CONNECTIONS

LIEBERT PDX & PCW

1 Opening for field wiring. Suggested entry point for HV field wiring to unit.

2 Opening for field wiring. Suggested entry point for LV field wiring to unit.

3. Wire tie anchors. Use to secure customer wiring.

Notes:

1. Wire needs to be routed outside Electric Box to Low Voltage knockout on bottom of Electric Box.

Page 21 of 42 08/14/2023

REV DATE : 2/21

DPN004350

Page :1 /3

UNIT MOUNTED DISPLAY

Fo rm

N o.

: D P

N

_R E

V

PRODUCT INFORMATION

LIEBERT® iCOM™

The Liebert® iCOM™ display is a 7-inch capacitive, color-touchscreen display in an ergonomic, aesthetically pleasing housing. The display and housing will be viewable while the unit accent panels are open or closed.

The display can be easily detached to view while the panel is open.

Menu Layout- The menus will be broken out into two main menu screens: User screen and Service screen.

The User screen contains the menus to access parameters required for basic unit control and setup.

The Service screen is designed for service personal and provides access to advanced control setup features and diagnostic information.

Password Protection- The display will contain two unique passwords to protect against unauthorized changes.

An auto hide/show feature allows the user to see applicable information based on the login used. These four-digit passwords may be customized according to User preference.

Unit Backup and Restore- The user shall have the ability to create safety copies of important control parameters.

The display has the ability for the user to automatically backup unit configuration settings to internal memory or USB storage drive. Configuration settings may be transferred to another unit for a more streamlined unit startup.

Parameter Search- The display has search fields for efficient navigation and parameter lookup.

Parameter Download- The Liebert® iCOM™ shall enable the user to download a report that lists parameter names, factory default settings, and the user programmed settings in .csv format for remote reference.

Parameter Directory- The Liebert® iCOM™ shall provide a directory that lists all parameters in the control. The list shall provide Line ID numbers, parameter labels, and current parameter values.

Page 22 of 42 08/14/2023

DPN004350

Page :2 /3

UNIT MOUNTED DISPLAY

Fo rm

N o.

: D P

N

_R E

V

PRODUCT INFORMATION

LIEBERT® iCOM™

Context Sensitive Help- The display will have an onboard help database. The database will provide context sensitive help to assist with setup and navigation of the menus.

Display Setup- The user has the ability to configure the display information based on the specific user’s preference.

Language, units of measure, screen contrast, home screen layout, back light timer and the hide/show of certain readouts will be configurable through the display.

Additional Readouts- The display has the ability for the user to configure custom widgets on the main screen.

Widget options will include items such as fan speed, call for cooling, call for free cooling, maintenance status, call for hot water reheat, call for electric reheat, call for dehumidification, call for humidification, airflow, static pressure, fluid flow rate and cooling capacity.

Status LEDs- The display will provide the user with the unit’s operating status using an integrated LED.

The LED will indicate if the unit has an active alarm; if the unit has an active alarm that has been acknowledged;

or if the unit is on, off, or in a standby status.

Unit Alarms – All unit alarms are annunciated through both audio and visual cues, clearly displayed on the screen, automatically recorded in the event log, and communicated to monitoring plug connections.

Event Log – The display will automatically store the last 400 unit-only events (messages, warnings, and alarms).

Service Contact Information – The display has the ability to store the local service or sales contact information.

Upgradeable –Display and Control Board software upgrades are performed through a USB connection.

Unit-to-Unit (U2U) Communication – Communication via private Ethernet network allows for advanced control functionality (Teamwork modes, sharing sensor data, Standby Rotation, Lead-Lag, and Cascade operation).

Temperature Control- Precision temperature control is maintained while maximizing efficiency based on a user entered setpoint and tolerance.

Various Control Types- Proportional, PI (proportional-integral), or Intelligent control types can be selected for supply or return temperature. These control types have been developed to maximize component life and maintain precise environmental control.

Timers/Sleep Mode- The menus shall allow various customer settings for turning the unit On or Off.

Sensor Calibration- The menus shall allow unit sensors to be calibrated with external sensors.

Maintenance/Wellness Settings- The menus shall allow reporting of potential component problems before they occur.

Page 23 of 42 08/14/2023

DPN004350

Page :3 /3

UNIT MOUNTED DISPLAY

Fo rm

N o.

: D P

N

_R E

V

PRODUCT INFORMATION

LIEBERT® iCOM™

Options Setup- The menus shall provide operation settings for the installed components.

Auto Restart- The unit will return to its previous operating status after loss of power. Units can be stagger started to minimize system current draw.

Auxiliary Boards- The menus shall allow setup of optional expansion boards.

Various Sensors: The menus shall allow setup and display of optional custom sensors. The control shall include four customer accessible analog inputs for field-supplied sensors. The analog inputs shall accept a 4 to 20mA signal. The user shall be able to change the input to 0 to 5VDC or 0 to 10VDC. The gains for each analog input shall be programmable from the front display. The analog inputs shall be able to be monitored from the front display.

Diagnostics/Service Mode- The Liebert® iCOM™ control shall be provided with self-diagnostics to aid in troubleshooting. The microcontroller board shall be diagnosed and reported as pass/not pass. Control inputs shall be indicated as On or Off at the front display. Control outputs shall be able to be turned On or Off from the front display without using jumpers or a service terminal. Each control output shall be indicated by an LED on a circuit board.

Page 24 of 42 08/14/2023

DPN004351

Page :2 /2

Fo rm

N o.

: D P

N

_R E

V

UNIT TO UNIT NETWORK CONNECTIONS

LIEBERT

iCOM™

LIEBERT® CW, LIEBERT® CWA, LIEBERT® DS, LIEBERT® DSE,

LIEBERT® PDX, LIEBERT® PCW

ETHERNET CABLE

(FIELD SUPPLIED)

TB3

P71 P72

P74 P64

E5

P

P

P

P

P

P

P

P

P76

P95

P100

P75

LIEBERT® iCOM™

MICROPROCESSOR

AND I/O BOARD

TB3

P71 P72

P74 P64

E5

P

P

P

P

P

P

P

P

P76

P95

P100

P75

LIEBERT® iCOM™

MICROPROCESSOR

AND I/O BOARD

NOTE* For dual-unit network configurations only

P95 DVI-D CABLE CONNECTION

TO 7-INCH LIEBERT® iCOM™ DISPLAY

P100 POWER SUPPLY TO

7-INCH LIEBERT® iCOM™ DISPLAY

P95 DVI-D CABLE CONNECTION

TO 7-INCH LIEBERT® iCOM™ DISPLAY

P100 POWER SUPPLY TO

7-INCH LIEBERT® iCOM™ DISPLAY

Document generated 26 July 2023 04:51 PM (EST).

Page 25 of 42 08/14/2023

SL-31050_Rev3_07-20

LIEBERT® LIQUI-TECT™ 410

POINT LEAK DETECTION SENSOR

Product Specification/Installation Guide

The Liebert® Liqui-Tect™ 410 (LT410) provides single-point detection of leaks. The point-detection sensor has two gold-plated sensing probes to prevent corrosion and to provide accurate readings. The LT410 constantly monitors for leaks, internal faults, and power failures and warns of any abnormal conditions. Mounting brackets allow for sensor height adjustment and leveling.

The LT410 is the ideal solution for sensing leaks under a raised computer floor or air conditioning drip pans.

Two independent outputs provide added flexibility with the capacity to signal both a local alarm panel, Liebert cooling unit and a remote building management system or external equipment, such as motorized water shutoff valves.

LT410 APPLICATIONS

The LT410 is ideally suited for:

• Glycol and chilled water cooling,

• Humidification supply water piping,

• Condensate pumps and drains,

• Unit and ceiling auxillary drip pans,

• Overhead piping troughs.

LOCATIONS/PLACEMENT

The LT410 is an excellent choice for:

• Large scale network control centers,

• Data centers,

• Server rooms and closets,

• Unattended, remote shelters,

• Mechanical equipment rooms,

• Sensitive areas with overhead piping,

• Industrial process control rooms.

COMPONENTS OF THE

LIQUI-TECT™ 410 MODULE

The LT410 consists of a metal enclosure with a hinged top door that provides access to the internal wiring termination. It includes side access through a box connector for installation of the power and contact wiring. The mounting brackets attach to the enclosure with adjustable slots to allow custom setting of the height of the sensing probes.

Document generated 26 July 2023 04:51 PM (EST).

Page 26 of 42 08/14/2023

LIEBERT® LIQUI-TECT™ 410 POINT LEAK DETECTION SENSOR

Product Specification/Installation Guide

SPECIFICATIONS

Power Requirements 24 VAC 100 mA, 50/60 Hz, 3 VA (max.)

Dimensions, W x D x H 6.35 in. x 2.25 in. x 4.46 in. (161.2 mm x 57.2 mm x 113.2 mm)

Weight (assembled) 2.0 lb. (0.9 kg)

Metal Enclosure NEMA 1, IP 30

ENVIRONMENTAL CONDITIONS

Operating Temperature 50°F to 104°F (10°C to 40°C)

Operating Humidity 10% to 95% relative humidity (non-condensing)

Operating Altitude 0 to 10,000 ft. (0 to 3,048 m)

Output Relay Contact Rating 2 Form-C; 3 A rating at 24 VAC

AGENCY LISTINGS

UL UL916

C-UL C22.2, No. 205-M1983

CE Yes

FCC Compliance 47 CFR, Part 15

TOP VIEW

FRONT VIEW SIDE VIEW5.85”

(148.5mm)

4.46” (113.2mm)

6.35” (161.2mm) 2.25”

(57.2mm)

Form-C relay outputs and power wiring

Adjustable probe height

0.0 - 0.5” (0.0 - 12.7mm)

DIMENSIONS -

TOP, FRONT AND SIDE

Document generated 26 July 2023 04:51 PM (EST).

Page 27 of 42 08/14/2023

LIEBERT® LIQUI-TECT™ 410 POINT LEAK DETECTION SENSOR

Product Specification/Installation Guide

WIRING INTERCONNECTIONS

Circuits are shown in powered, non-alarm state.

NOTE: All power and alarm connections must be Class 2 circuits.

Red Wires Orange Wires Yellow Wires

24 V, AC/DC

@ 0.10A, 50-60 Hz, DC Class 2 Circuit Only

Alarm Contact Rating

24 VAC @ 3A

Class 2 Circuit Only

Alarm Contact Rating

24 VAC @ 3A

Class 2 Circuit Only

PO

W

ER

PO

W

ER

1- N

O

1- N

C

1- C

O M

2- N

O

2- N

C

2- C

O M

Gold-plated Probes

Height adjustable 0-0.5” (0-12.7mm)

PLACEMENT ON SUBFLOOR

UNDER COOLING SUPPORT

EQUIPMENT

To a Liebert cooling unit and an optional monitoring panel

To external power supply or directly from unit (see Power Wiring on page 4)

Leak detection zone (directly beneath unit)

Document generated 26 July 2023 04:51 PM (EST).

Page 28 of 42 08/14/2023

Vertiv.com | Vertiv Headquarters, 1050 Dearborn Drive, Columbus, OH, 43085, USA © 2020 Vertiv Group Corp. All rights reserved. Vertiv and the Vertiv logo are trademarks or registered trademarks of Vertiv Group Corp. All other names and logos referred to are trade names, trademarks or registered trademarks of their respective owners. While every precaution has been taken to ensure accuracy and completeness herein, Vertiv Group.

Co. assumes no responsibility, and disclaims all liability, for damages…