S02 - SOW - Att 31 - Cut Sheet 09 - EHRM Infra Upgrades - Constr - Togus.pdf

PDF 143 KB Posted

Attached to
Electronic Health Record Modernization Infrastructure Upgrades - Construction - Togus, ME
Solicitation number
36C77626R0062
Issued by

About this file

This is a product specification and performance document for the Greenheck Spun Aluminum Model GRSI/GRSR/GRSF gravity ventilators. The document provides detailed construction features, dimensions, and performance data for intake and relief ventilation units designed for natural gravity or positive pressure systems.

The GRSI model serves as an intake ventilator while the GRSR model functions as a relief unit, with both available in sizes ranging from 8 to 48 inches. Key construction features include all-aluminum exterior for corrosion resistance, integral birdscreen to prevent bird and debris entry, built-in curb cap with pre-punched attachment holes, and an optional flashing flange (GRSF model) for installations without roof curbs. The units deliver broad performance capacity up to 18,400 CFM (31,300 m³/hr) with advanced weather protection and extended durability through extensive life testing. A comprehensive dimensions table specifies measurements, damper sizes, curb and shroud thickness, and unit weights for all available model sizes. Performance tables present intake and relief capacities at varying total pressure drops from 0.04 to 0.35 inches water gauge, with maximum recommended intake velocities not exceeding 600 feet per minute to prevent moisture intrusion. Recommended maximum intake CFM values are provided for each size based on 600 ft/min velocity standards, and the document includes guidance that 12-inch or higher curbs are advisable in areas with significant snow depths. Complementary accessories include gravity or motorized dampers, prefab curbs, and protective coatings to enhance performance and service life.

View the file

Other files

File Type Posted
S30 - SAM - Special Notice - Cancellation - 36C77626R0062_2 - EHRM Infra Upgrades - Togus.pdf PDF
S06 - Amend 0002 - Att 03 - Corrected Agenda - RFP - 07202026 - EHRM Infra - Togus.pdf PDF
S06 - Amend 0002 - 36C77626R0062 - 07202026 - EHRM Infra - Togus.pdf PDF
S06 - Amend 0001 - Att 02 - SV - Attendance SHT - 06292026 - EHRM Infra - Togus.pdf PDF
S06 - Amend 0001 - 36C77626R0062 - 07142026 - EHRM Infra - Togus.pdf PDF
S06 - Amend 0001 - RFIs - 07132026 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S06 - Amend 0001 - Att 01 - Rvd Structural Drwg - 06192026 - EHRM Infra - Togus.pdf PDF
S06 - Amend 0001 - Att 03 - SV - Agenda - RFP - 06292026 - EHRM Infra - Togus.pdf PDF
S02 - SOW - Att 05 - Drwg - Vol 3 - 02182026 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - SOW - Att 13 - Const Sch - 02132026 - EHRM Infra Upgrades - Constr Togus.pdf PDF
S02 - SOW - Att 26 - Cut Sheet 04 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - Att 03 -Prj Info Sheet for KTR - EHRM Infra Upgrade - Togus.docx DOCX document
S02 - SOW - Att 03 - Drwg - Vol 1C - 02182026 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - SOW - Att 22 - TS-000 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - Att 07 - 852.219-75 - 06172026 - EHRM Infra Upgrade - Togus.pdf PDF
S02 - Att 04 - Memo - Brand Name - 04092026 - EHRM Infra Upgrade - Togus.pdf PDF
S02 - SOW - Att 35 - Cut Sheet 13 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - SOW - Att 17 - Memo - Phy Sec Compliance - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - SOW - Att 27 - Cut Sheet 05 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - SOW - Att 09 - Specs - Vol 3- 02182026 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - SOW - Att 30 - Cut Sheet 08 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - SOW - Att 24 - Cut Sheet 02 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - Att 05 - Division Cost Breakdown - EHRM Infra Upgrade - Togus.xlsx XLSX spreadsheet
S02 - SOW - Att 29 - Cut Sheet 07 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - SOW - Att 37 - Cut Sheet 15 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - SOW - Att 16 - Submittal Reg - 02182026 - EHRM Infra - Upgrades - Constr - Togus.xlsx XLSX spreadsheet
S02 - SOW - Att 14 - Design Calcs - 02182026 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - SOW - Att 18 - Memo - Prj Stnd Compliance - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - SOW - Att 21 - PCRA 3 - MCR and Trench Work - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - SOW - Att 40 - Cut Sheet 18 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - SOW - Att 33 - Cut Sheet 11 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - SOW - Att 01 - Drwg - Vol 1A - 02182026 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - SOW - Att 38 - Cut Sheet 16 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - SOW - Att 06 - Drwg - Vol 4 - 02182026 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - SOW - Att 11 - Haz Mat Report - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - SOW - Att 12 - Geotechnical Report - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - SOW - Att 32 - Cut Sheet 10 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - SOW - Att 08 - Specs - Vol 1 - Div 02-14 - 02182026 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - SOW - Att 20 - PCRA 2 - Cabling and Data Outlets - EHRM Infra Upgrades - Constr - Togus.pdf PDF
RFP - EHRM Infra Upgrade - 36C77626R0062 - 06172026 - Togus.pdf PDF
S02 - SOW - Att 19 - PCRA 1 - TR Constr - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - SOW - Att 07 - Specs - Vol 1 - Div 00-01 - 02182026 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - SOW - Att 15 - Design Narrative - 02182026 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - SOW - Att 23 - Cut Sheet 01 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - Att 02 - PPQ - EHRM Infra Upgrade - Togus.docx DOCX document
S02 - SOW - Att 02 - Drwg - Vol 1B - 02182026 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - SOW - Att 34 - Cut Sheet 12 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - Att 01 - SOW - 05112026 - EHRM Infra Upgrades - Togus.pdf PDF
S02 - SOW - Att 10 - Specs - Vol 4 - 02182026 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - SOW - Att 36 - Cut Sheet 14 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
Show 40 more

Latest 50 of 57 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Construction Features When you buy a Greenheck gravity ventilator, you receive a ventilator with the industry’s best performance and durability for intake (model GRSI) or relief (model GRSR) for natural gravity or positive pressure systems. Exceptional low silhouette design and construction features make this unit a rugged, efficient, and economical air inlet or outlet.

• Broadest performance in the industry, up to 18,400 cfm (31,300 m3/hr)

• Most advanced weather protection of any ventilator in its class

• Greenheck subjects these products to extensive life testing, ensuring the ventilator will provide years of reliable performance

Optional Flashing Flange

Integral Birdscreen

Dimensions Model Size

A B C D E F Damper

Size Curb

Thickness Shroud

Thickness Unit

Weight

8 19 (483)

201⁄2 (521)

71⁄4 (184)

11⁄2 (38)

201⁄4 (514)

81⁄4

(210) 8 x 8

(203 x 203) 0.051 (1.3)

0.051 (1.3)

(3)

10 19 (483)

201⁄2 (521)

73⁄4 (197)

(51)

201⁄4 (514)

101⁄4 (260)

10 x 10 (254 x 254)

0.051 (1.3)

0.051 (1.3)

(4)

12 22 (559)

(737)

(254)

31⁄2 (89)

231⁄4 (591)

121⁄4 (311)

12 x 12 (305 x 305)

0.064 (1.6)

0.064 (1.6)

(5)

15 22 (559)

(737)

(254)

31⁄2 (89)

231⁄4 (591)

141⁄4 (362)

16 x 16 (406 x 406)

0.064 (1.6)

0.064 (1.6)

(6)

16 26 (660)

(737)

(279)

41⁄4 (108)

271⁄4

(692) 161⁄4 (413)

16 x 16 (406 x 406)

0.064 (1.6)

0.064 (1.6)

(7)

18 30 (762)

351⁄2 (902)

93⁄4 (248)

13⁄4 (44)

311⁄4 (794)

201⁄4 (514)

18 x 18 (457 x 457)

0.064 (1.6)

0.064 (1.6)

(9)

20 30 (762)

351⁄2 (902)

111⁄4 (286)

33⁄4 (95)

311⁄4 (794)

201⁄4 (514)

18 x 18 (457 x 457)

0.064 (1.6)

0.064 (1.6)

(11)

24 34 (864)

381⁄4

(972)

(279)

(102) 351⁄4 (895)

241⁄2 (622)

24 x 24 (610 x 610)

0.064 (1.6)

0.064 (1.6)

(13)

30 40 (1016)

(1219)

183⁄4 (476)

57⁄16

(138) - 301⁄2

(775) 30 x 30

(762 x 762) 0.064 (1.6)

0.064 (1.6)

(16)

36 46 (1168)

563⁄4 (1441)

211⁄4 (540)

(254) - 361⁄2

(927) 36 x 36

(914 x 914) 0.064 (1.6)

0.080 (2.0)

(20)

42 52 (1321)

631⁄4 (1607)

241⁄4 (616)

111⁄4

(286) - 421⁄2

(1089) 42 x 42

(1067 x 1067) 0.064 (1.6)

0.080 (2.0)

(27)

48 58 (1473)

(1829)

261⁄4 (667)

111⁄4

(286) - 481⁄2

(1232) 48 x 48

(1219 x 1219) 0.064 (1.6)

0.080 (2.0)

(36)

GRSI/GRSR - Sizes 30 - 48

B

F

F

F

1¾ (44)

1¾ (44)

D

D

D

A

A

E

C

C

C

B

B

GRSI/GRSR Sizes 8 - 24

B

F

F

F

1¾ (44)

1¾ (44)

D

D

D

A

A

E

C

C

C

B

B

All dimensions are in inches (millimeters) and the weight in pounds (kilograms). NOTE: Sizes GRS-8 through 24 have a one-piece cover and shroud. Access is gained through the removal of screws. Sizes GRS-30 through 48 have a removable cover, separate from the shroud, to facilitate maintenance and servicing of dampers.

GRSF - Sizes 8 - 24 with Optional Flashing Flange

B

F

F

F

1¾ (44)

1¾ (44)

D

D

D

A

A

E

C

C

C

B

B

• All aluminum exterior for corrosion-resistant construction

• Integral birdscreen to prevent the entry of birds and/or small objects

• Built-in curb cap with pre-punched holes for easy attachment to roof curbs

• Optional built-in flashing flange (model GRSF) with pre-punched holes for quick and easy installations without a roof curb.

Use the GRS with the following accessories:

Gravity or motorized dampers to ensure weather tightness.

Prefab curbs to reduce installation time.

Protective coatings to extend the life of the unit or blend its color with other equipment.

GRSF

Spun Aluminum Model GRSI/GRSR/GRSF

Volume (CFM) Recommended Maximum Intake Capacities

GRSI

Size

Throat Area (ft2 )

Total Pressure Drop (in. wg) Intake Area (ft2) Max. CFM Intake

0.04 0.06 0.08 0.10 0.15 0.20 0.25 0.30 0.35

M o d el

G R

S I

In ta ke P er fo rm an ce

8 0.37 178 218 252 282 345 398 445 488 527 1.30 780

10 0.57 279 342 395 442 541 624 698 765 826 1.72 1032

12 0.82 400 490 566 633 775 895 1001 1097 1184 2.52 1512

15 1.12 553 677 782 874 1071 1237 1383 1515 1636 2.57 1542

16 1.45 742 908 1049 1173 1436 1658 1854 2031 2194 3.02 1812

18 1.83 901 1104 1274 1425 1745 2015 2253 2468 2665 3.42 2052

20 2.25 1096 1343 1550 1733 2123 2452 2741 3002 3243 4.43 2658

24 3.24 1542 1888 2180 2438 2985 3447 3854 4222 4560 4.95 2970

30 5.03 2013 2465 2847 3183 3898 4501 5032 5512 5954 7.49 4496

36 7.29 2921 3577 4130 4618 5656 6531 7301 7998 8639 10.2 6111

42 9.77 3911 4791 5532 6185 7574 8746 9779 10712 11570 12.0 7159

48 12.8 5139 6294 7268 8126 9952 11491 12848 14074 15201 15.5 9286

GRSR

Size

Throat Area (ft2 )

Total Pressure Drop (in. wg)

0.04 0.06 0.08 0.10 0.15 0.20 0.25 0.30 0.35

M o d el

G R

S R

R el ie f

P er fo rm an ce

8 0.37 231 282 326 365 446 516 576 631 682

10 0.57 331 406 468 524 641 741 828 907 980

12 0.82 468 573 662 740 907 1047 1171 1282 1385

15 1.12 663 811 937 1048 1283 1481 1656 1814 1960

16 1.45 870 1065 1230 1375 1685 1945 2175 2382 2573

18 1.83 1060 1298 1499 1676 2052 2370 2649 2902 3135

20 2.25 1284 1572 1815 2029 2486 2870 3209 3515 3797

24 3.24 1879 2301 2657 2971 3638 4201 4697 5145 5558

30 5.03 2281 2794 3226 3607 4418 5101 5703 6247 6748

36 7.29 3279 4016 4637 5184 6349 7331 8197 8979 9699

42 9.77 4672 5722 6607 7387 9047 10447 11680 12795 13820

48 12.8 6211 7607 8783 9820 12027 13888 15527 17009 18372

Performance Performance data for these units was obtained through actual testing.

The information is presented in capacity versus total pressure drop through the GRS. Total pressure drop includes the static and velocity pressure drops. To find the static drop alone, use the following equations.

The data is presented for both discharge and intake units. The intake velocity of the intake unit should not exceed 600 feet per minute. Above this velocity, airborne particles may be carried into the building. The table below displays the maximum recommended values for the respective intake units. In areas where snow depths may be a problem, 12 inch (305 mm) or higher curbs are recommended.

Table is based on 600 ft/min.

maximum intake velocity. Above these values (numbers in gray), provisions should be made to contain incoming moisture.

Throat Velocity = [ ] CFM Throat Area

Static Pressure = [ ]

[ ]Total Pressure

Velocity Pressure = [ ]Throat Velocity

4008.6

Velocity Pressure

(in. wg)*

*1 inch wg = 249 Pa

Spun Aluminum Model GRSI/GRSR

ADR

Rectangle

ADR

Rectangle