S02 - SOW - Att 14 - Design Calcs - 02182026 - EHRM Infra Upgrades - Constr - Togus.pdf
PDF 37 MB Posted
- Attached to
- Electronic Health Record Modernization Infrastructure Upgrades - Construction - Togus, ME
- Solicitation number
- 36C77626R0062
About this file
This is a 100% Construction Documents submittal containing design calculations for infrastructure upgrades at the VA Togus Medical Center in Augusta, Maine, reissued February 18, 2026. The document supports the Electronic Health Record Modernization (EHRM) Infrastructure Upgrades project, identified as VA Project No. 402-22-700 under Contract No. 36C77623C0002. The calculations were prepared by GDM-AE, Inc. and are submitted to the Department of Veterans Affairs Program Contracting Activity Central (PCAC) located in Independence, Ohio.
The submittal includes comprehensive design calculations across multiple engineering disciplines: civil calculations for 6-inch and 8-inch sewer lateral and main pipe sizing, domestic water pipe sizing, fire sprinkler system calculations, mechanical calculations including CFD analysis, fuel tank sizing, heat load analysis, roof drain sizing, and systems design for all other buildings, as well as structural calculations and blast analysis. These calculations support the detailed infrastructure design necessary for construction of the EHRM upgrades at the Togus VA Medical Center facility in Augusta, Maine.
View the file
Other files
Show 40 more
Latest 50 of 57 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Construction Documents – 100% Submittal: Calculations Reissued February 18th, 2025
Department of Veterans Health Administration
Electronic Health Record Modernization (EHRM) Infrastructure
Upgrades – Togus, ME Project No. 402-22-700
Contract No. 36C77623C0002
Togus VA Medical Center
1 VA Center, Augusta, ME 04330
US Department of Veterans Affairs
Program Contracting Activity Central (PCAC)
6150 Oak Tree Blvd., Suite 300
Independence, OH 44131
Prepared by:
GDM-AE, Inc.
1308 NE 134th St Suite A Vancouver, WA 98685
VA Togus Medical Center Augusta, ME
100% Construction Documents Reissued 02-18-2026
Electronic Health Records Modernization (EHRM) Infrastructure Upgrades – Togus, ME VA Project No. 402-22-700
TABLE OF CONTENTS
Civil - MCR 6 in Sewer Lateral Pipe Size
Civil - MCR 8 in Sewer Main Pipe Size
Civil - MCR Domestic Water Pipe Sizing Calculations Fire -
MCR Fire Sprinkler Calculations
Mechanical - MCR CFD Analysis
Mechanical - MCR Fuel Tank Sizing
Mechanical - MCR Heat Load
Mechanical - MCR Roof Drain Sizing
Mechanical - Systems Design Report - All Other Buildings
Structural - MCR Structural Calculations
Blast Analysis Calculations
Electronic Health Records Modernization (EHRM) Infrastructure Upgrades – Togus, ME VA Project No. 402-22-700
Civil - MCR 6 in Sewer Lateral Pipe Size
100% Construction Documents Reissued 02-18-2026
����������������� � � �������������� !� "�#�$�%�&'()�*)��!+��,(&�'(�,(� ���-)�. � � �����" &�/�/($�0 &(��%�!�%��"�"��� � � �1���� ��2��34567�89:;6<�=4�>:;6�>?@6<A��B9:C;:95=?4<�=4�D6::?E � � �� 1�� �� � � � � � � �� � � � � � � � �F�/(�#��0(�(&)�G�H � I �! � � � �#(/�%� "�J� K)���H � L�M �! � � � �� �����N0�$�%�,(�-�O#PLQ � � � � � � �� � � � � � � � �R����F�/(�S�!!�!' �� � � � � �& �'%!($$)�� �H � T�TUL � � � � ��%�!!(��V �� 0 � � � � � � �� $� /()���H � T�TU "�P"�� � � �� � �� � � � � ����� �� �� � � � � �������������������W� ��H �U�LXUY � � � � �F�&�����-�R����S�!!�!' �� � � � � �& �'%!($$)���H � T�TUI � � � � �� � � � � � � � �� � � � � � � � �� F�/(�#��0(�(&)�G�H T�M "� � � � �� F�/(�Z�+��$)���H T�LM "� � � � �� � �� � � � � �� ��&���[('0(!��\(�'%�)]�H T�LXL "� � � � �� � �� � � � � �� �(!�&���̂!'�()�_�H �̀ab &�+��!$ � � � �� �& $$c[(����̂&(�)�d�H T�Tb "�� � � � �� � �� � � � � �� e(��(+�F(&�0(�(&)���H T�Y "� � � � �� \-+&������Z�+��$)�f�H T�UU "� � � � �� #�$�%�&'()�g�H T�UY �"$ � � � �� ,̂(��.(� ���-)�h�H L�LU "�P$(� � � � �� � �� � � � � ���������/�/(�i�"����jN̂P̂ QkUTTil�H� X̀�ai � � � � �� � � � � � � � � m m
L
Celyn Dezmain CJD Stamp
100% Construction Documents Reissued 02-18-2026
Electronic Health Records Modernization (EHRM) Infrastructure Upgrades – Togus, ME VA Project No. 402-22-700
Civil - MCR 8 in Sewer Main Pipe Size
����������������� � � �������������� !� "�#�$�%�&'()�*)��!+��,(&�'(�,(� ���-)�. � � �����" &�/�/($�0 &(��%�!�%��"�"��� � � �1���� ��2��34567�89:;6<�=4�>:;6�>?@6<A��B9:C;:95=?4<�=4�D6::?E � � �� 1�� �� � � � � � � �� � � � � � � � �F�/(�#��0(�(&)�G�H � I �! � � � �#(/�%� "�J� K)���H � L�M �! � � � �� �����N0�$�%�,(�-�O#PQR � � � � � � �� � � � � � � � �S����F�/(�T�!!�!' �� � � � � �& �'%!($$)�� �H � U�UVQ � � � � ��%�!!(��W �� 0 � � � � � � �� $� /()���H � U�UUX "�P"�� � � �� � �� � � � � ����� �� �� � � � � �������������������Y� ��H �V�QIZX � � � � �F�&�����-�S����T�!!�!' �� � � � � �& �'%!($$)���H � U�UVX � � � � �� � � � � � � � �� � � � � � � � �� F�/(�#��0(�(&)�G�HU�[[[[[[[[ "� � � � �� F�/(�\�+��$)���HU�LLLLLLLL "� � � � �� � �� � � � � �� ��&���]('0(!��̂(�'%�)_�H U�LIL "� � � � �� � �� � � � � �� �(!�&���̀!'�()�a�H L�MM &�+��!$ � � � �� �& $$b](����̀&(�)�c�H U�VM "�� � � � �� � �� � � � � �� d(��(+�F(&�0(�(&)���H U�e "� � � � �� -̂+&������\�+��$)�f�H U�VX "� � � � �� #�$�%�&'()�g�H U�QZ �"$ � � � �� ,̀(��.(� ���-)�h�H V�eQ "�P$(� � � � �� � �� � � � � ���������/�/(�i�"����jǸP̀ RkVUUil�H� MU�Xi � � � � �� � � � � � � � � m m
Q
100% Construction Documents Reissued 02-18-2026
Electronic Health Records Modernization (EHRM) Infrastructure Upgrades – Togus, ME
Civil - MCR Domestic Water Pipe Sizing Calculations
402-22-700 36C77623C0002 Togus VAMC EHRM Infrastructure Upgrades
Domestic and Fire Protection Water Distribution Pipe Sizing Calculations
Calculations below demonstrate the min pipe size requirement for the shared domestic and fire protection water service:
Known:
Domestic Water Demand Qd 33 GPM Fire Protection Water Demand Qf 585.56 GPM @ 39.89PSI
Total Water Demand Qt 618 GPM ~ 1.37 cfs
Pipe Material PVC Pipe Material C Value 150
Pipe Length (L) 210 LF Pipe Size (D) 6 in
Residual Pressure at existing Main 58 PSI @ 1,113 GPM Static Pressure at existing Main 65 PSI @ 0 GPM
Min Pipe Size Required:
Q=V*A
Q=V*πr2 r=SQRT(Q/V π) r=SQRT(1.37cfs/7.0fps*3.14) r=0.25ft ~ 3”
Min Pipe Size 6” diameter
Pressure loss due to friction:
Ploss = 4.53*L*(Q/C)1.852 / D4.857
L eq = 210 + (2-90 bend)*8.9 + (1 tee)*18 + (3-45 bends)*5.6
=210+17.8+18+16.8 = 262.6 ft = 4.53*262.6*(655/150)1.852 / 64.857
= 3.05 PSI
Helevation = 6” elevation change from water main connection to building connection is considered negligible.
Pressure in a 6” PVC Water Service line at the new standalone MCR connection 61.95PSI @ 618 GPM;
Therefore, a 6” PVC Water and Fire Service line will sufficiently serve the MCR water demand.
Electronic Health Records Modernization (EHRM) Infrastructure Upgrades – Togus, ME VA Project No. 402-22-700
Fire - MCR Fire Sprinkler Calculations
Location: VA Togus Medical Center, Augusta, Maine, Project Name: Togus EHRM Infrastructure Upgrades
Drawing Name: 22117_MCR_Fire_Protection_r25 Calculation Date:11/9/2025
Hydraulic Calculations Summary for
Design
Ordinary Hazard Group 1
MAIN COMPUTER ROOM
0.15/Square feet
Remote Area Name:
Occupancy Classification:
Density
Area of Application: 1500.00 (Actual Area: 1501.17)
Coverage per Sprinkler:
Type of Sprinklers Calculated:
No. of Sprinklers Calculated:
91.41 (average) at Node:
Fire Protection Wet
N/AN/A
1250.00
0.0 galType of System:
In-rack Demand:
Hose Streams:
Volume of Dry or PreAction System:
at Node:
Type Allowance at Source
Total Water Required (including Hose Streams where applicable)
39.89@585.58FROM: Water Supply at Node 1:
22.98Safety Margin:
Hazen-Williams
None.
Applied Friction Loss Method:
Darcy-Weisbach Suppression Agent:
Conrad Chandler, PE
Department of Veterans Affairs
1308 NE 134th Street, Suite A, Vancouver, WA 98685
541-426-4723
Contact Name
Address:
Phone Number:
Authority Having Jurisdiction:
Name of Designer:
Notes: HYDRAULIC CALCULATIONS ARE PROVIDED TO VERIFY UNDERGROUND PIPE SIZE ONLY. CONTRACTORS FOR FIRE SUPPRESSION SYSTEMS ARE REQUIRED TO PROVIDE CALCULATIONS AND WORKING DRAWINGS FOR NEW OR MODIFIED SYSTEMS. NOTE: SPRINKLER HEADS WITHIN THE REMOTE AREA WERE CALCULATED AT ACTUAL COVERAGE AREA. FOR UNDERGROUND PIPING CALCULATION INCLUDES 262' EQUIVALENT LENGTH
OF 6" DIP.
11/9/2025 Page 1AutoSPRINK RVT v8.3.13.0 1:15:10PMMAIN COMPUTER ROOM@ M.E.P.CAD
Conrad Chandler 11-10-2025
Hydraulic Graph
Water Supply
Node: 1
Job Name: Togus EHRM Infrastructure Upgrades
Remote Area Name: MAIN COMPUTER ROOM Date: 11/9/2025 N 1.85
Summary Sheet
No pressure is being required from the Source/Supply to meet the demand (by a margin of this negative value).
A negative result in Required Pressure indicates that the Pump is capable of furnishing all of the pressure required by the demand reported within this calculation.
11/9/2025 Page 1AutoSPRINK RVT v8.3.13.0 1:15:11PM@ M.E.P.CAD
(US gallons per minute) (US gallons per minute) (K) (Pounds force per square inch)
Outflowing Devices Report Description: Ordinary Hazard Group 1
Job Number: 402-22-700
Device
Actual Flow Minimum Flow K-Factor Pressure
Sprinkler 101 19.12 14.82 5.6 11.65
Sprinkler 102 18.95 14.82 5.6 11.45
Sprinkler 103 20.09 14.82 5.6 12.87
Sprinkler 104 17.70 17.70 5.6 9.99
Sprinkler 105 18.65 17.70 5.6 11.09
Sprinkler 117 20.65 15.00 5.6 13.60
Sprinkler 112 20.19 15.00 5.6 13.00
Sprinkler 107 19.99 15.00 5.6 12.74
Sprinkler 116 19.92 15.00 5.6 12.66
Sprinkler 111 19.72 15.00 5.6 12.40
Sprinkler 115 19.44 15.00 5.6 12.06
Sprinkler 110 19.25 15.00 5.6 11.82
Sprinkler 114 19.75 15.00 5.6 12.43
Sprinkler 109 19.55 15.00 5.6 12.19
Sprinkler 113 21.54 15.00 5.6 14.80
Sprinkler 108 21.07 15.00 5.6 14.16
Sprinkler 106 19.99 15.00 5.6 12.75
Most Demanding Sprinkler Data
11/9/2025 Page 1AutoSPRINK RVT v8.3.13.0 1:15:11PM@ M.E.P.CAD
Job Name: Togus EHRM Infrastructure Upgrades
Remote Area Name: MAIN COMPUTER ROOM Date: 11/9/2025
(Pounds force per square inch) (Pounds force per square inch)(US gallons per minute)(Pounds force per square inch)(US gallons per minute)(Pounds force per square inch)
Supply Analysis
Node Name Static Residual Flow Available Total Demand Required Pressure
58.001 39.89585.581113.00 62.8765.00Water Supply
Node Analysis
Discharge at
Node
(US gallons per
Pressure at
Node
(Pounds force
Elevation (ft)Node Number Node Type Notes
100' - 0" 335.5839.891 Supply
111' - 1" 19.1211.65101 Sprinklers
111' - 1" 18.9511.45102 Sprinklers
111' - 1" 20.0912.87103 Sprinklers
113' - 8" 17.709.99104 Sprinklers
113' - 8" 18.6511.09105 Sprinklers
118' - 4" 19.9912.75106 Sprinklers
118' - 4" 19.9912.74107 Sprinklers
118' - 4" 21.0714.16108 Sprinklers
118' - 4" 19.5512.19109 Sprinklers
118' - 4" 19.2511.82110 Sprinklers
118' - 4" 19.7212.40111 Sprinklers
118' - 4" 20.1913.00112 Sprinklers
118' - 4" 21.5414.80113 Sprinklers
118' - 4" 19.7512.43114 Sprinklers
118' - 4" 19.4412.06115 Sprinklers
118' - 4" 19.9212.66116 Sprinklers
118' - 4" 20.6513.60117 Sprinklers
100' - 0" 38.862
11/9/2025 Page 1AutoSPRINK RVT v8.3.13.0 1:15:12PM@ M.E.P.CAD
Discharge at
Node
(US gallons per
Pressure at
Node
(Pounds force
Elevation (ft)Node Number Node Type Notes
102' - 11 1/4" 37.343
102' - 11 1/4" 37.464
102' - 11 1/4" 37.525
108' - 0 1/4" 34.176
108' - 0 1/4" 33.277
111' - 0 3/8" 31.638
113' - 6" 10.2910
113' - 6" 11.4111
117' - 4 5/8" 16.8712
117' - 4 5/8" 14.6013
117' - 4 5/8" 14.1714
117' - 4 5/8" 14.8515
117' - 4 5/8" 15.5416
117' - 4 5/8" 14.5617
117' - 4 5/8" 14.1318
117' - 4 5/8" 14.1319
117' - 4 5/8" 13.7120
117' - 4 5/8" 14.3721
117' - 4 5/8" 16.6422
117' - 4 5/8" 14.0623
117' - 4 5/8" 13.6524
117' - 4 5/8" 14.3125
117' - 4 5/8" 15.3326
11/9/2025 Page 2AutoSPRINK RVT v8.3.13.0 1:15:12PM@ M.E.P.CAD
Discharge at
Node
(US gallons per
Pressure at
Node
(Pounds force
Elevation (ft)Node Number Node Type Notes
117' - 4 5/8" 17.6727
117' - 4 5/8" 16.9528
117' - 4 5/8" 16.5329
117' - 4 5/8" 16.3530
117' - 4 5/8" 16.2831
117' - 4 5/8" 16.2732
117' - 4 5/8" 15.9333
117' - 4 5/8" 14.4034
117' - 4 5/8" 14.4035
117' - 4 5/8" 15.4836
117' - 4 5/8" 13.6637
11/9/2025 Page 3AutoSPRINK RVT v8.3.13.0 1:15:12PM@ M.E.P.CAD
Date: 11/9/2025
Remote Area Name: MAIN COMPUTER ROOM
Flow added this step
Pipe Information
Node 1
Node 2
Elev 1 ft
Elev 2 ft
K-Factor
Q
Total Flow
Q
Nominal ID
Actual ID
Fittings &
Devices
Equiv.
Length ft
Length ft
Fitting ft
Total ft
C Factor or
Roughness
Pf Friction Loss
Per Unit
Pounds force per square inch
Total(Pt)
Elev(Pe)
Friction(Pf)
Notes
Fitting/Device (Equivalent Length)
Fixed Pressure Losses, when applicable, are added directly to (Pf) and shown as a negative value.
Velocity
2' - 0"
113' - 6" 2' - 2"
0.07
0.22
113' - 8" 0' - 2"
1"
• • • • • Route 1 • • • • •
(See
Notes)
1"
9.99
0.10
Sprinkler, 17.70
5.6
E(2' - 0"), HW
6.57
17.70
8' - 0"
117' - 4 5/8" 17' - 8 3/8"
-1.68
5.95
113' - 6" 9' - 8 3/8"
3/4" (See
Notes)
7/8"
10.29
0.3417.70 2E(2' - 0"), PO(4' - 0"), HW
10.65
117' - 4 5/8" 0' - 4 3/8" 0.04
117' - 4 5/8" 0' - 4 3/8"
1 1/2" (See
Notes)
1 5/8"
14.56
0.11
Flow (q) from Route 5
56.56 Tr, HW
8.91
38.86
8' - 0"
117' - 4 5/8" 12' - 3 1/4"
0.00
2.35
117' - 4 5/8" 4' - 3 1/4"
1 1/2" (See
Notes)
1 5/8"
14.60
0.19
Flow (q) from Route 7
76.11 PO(8' - 0"), HW
11.99
19.55
117' - 4 5/8" 9' - 8" 0.72
117' - 4 5/8" 9' - 8"
3" (See
Notes)
3 1/4"
16.95
0.07
Flow (q) from Route 2
292.97 Tr, HW
11.26
216.85
41' - 0"
111' - 0 3/8" 99' - 7 1/8"
2.76
11.21
117' - 4 5/8" 58' - 7 1/8"
3" (See
Notes)
3 1/4"
17.67
0.10
Flow (q) from Route 16
335.58 5E(7' - 0"), 3red, E(6' - 0"), Tr, HW
12.90
42.61
10' - 0"
108' - 0 1/4" 13' - 0 1/8"
1.30
0.34
111' - 0 3/8" 3' - 0 1/8"
4" (See
Notes)
4 1/4"
31.63
0.03335.58 E(10' - 0"), HW
7.55
32' - 0"
108' - 0 1/4" 34' - 2 3/8" 0.89
108' - 0 1/4" 2' - 2 3/8"
4" (See
Notes)
4 1/4"
33.27
0.03335.58 BV(12' - 0"), PO(20' - 0"), HW
7.55
32' - 0"
102' - 11 1/4" 37' - 1"
2.20
0.97
108' - 0 1/4" 5' - 1"
4" (See
Notes)
4 1/4"
34.17
0.03335.58 CV(22' - 0"), E(10' - 0"), HW
7.55
102' - 11 1/4" 4' - 10 5/8" 0.13
102' - 11 1/4" 4' - 10 5/8"
4" (See
Notes)
4 1/4"
37.34
0.03335.58 BFP, red, HW
7.55
14' - 0"
102' - 11 1/4" 15' - 1 3/8" 0.06
102' - 11 1/4" 1' - 1 3/8"
6" (See
Notes)
6 3/8"
37.46
0.00335.58 E(14' - 0"), HW
3.39
11/9/2025 Page 1AutoSPRINK RVT v8.3.13.0 1:15:12PMMAIN COMPUTER ROOM@ M.E.P.CAD
Remote Area Name: MAIN COMPUTER ROOM
Flow added this step
Pipe Information
Node 1
Node 2
Elev 1 ft
Elev 2 ft
K-Factor
Q
Total Flow
Q
Nominal ID
Actual ID
Fittings &
Devices
Equiv.
Length ft
Length ft
Fitting ft
Total ft
C Factor or
Roughness
Pf Friction Loss
Per Unit
Pounds force per square inch
Total(Pt)
Elev(Pe)
Friction(Pf)
Notes
Fitting/Device (Equivalent Length)
Fixed Pressure Losses, when applicable, are added directly to (Pf) and shown as a negative value.
Velocity
14' - 0"
100' - 0" 16' - 11 1/4"
1.27
0.06
102' - 11 1/4" 2' - 11 1/4"
6" (See
Notes)
6 3/8"
37.52
0.00335.58 E(14' - 0"), HW
3.39
100' - 0" 262' - 6 1/2" 1.03
100' - 0" 262' - 6 1/2"
6" (See
Notes)
6 1/4"
38.86
0.00335.58 Water Supply, HW
3.47
Hose Allowance At Source
585.58 Route 1
39.89
Total(Pt)
250.00
2' - 0"
113' - 6" 2' - 2"
0.07
0.25
113' - 8" 0' - 2"
1"
• • • • • Route 2 • • • • •
(See
Notes)
1"
11.09
0.11
Sprinkler, 18.65
5.6
E(2' - 0"), HW
6.92
18.65
6' - 0"
117' - 4 5/8" 11' - 10 5/8"
-1.68
4.40
113' - 6" 5' - 10 5/8"
3/4" (See
Notes)
7/8"
11.41
0.3718.65 E(2' - 0"), PO(4' - 0"), HW
11.22
117' - 4 5/8" 0' - 4 3/8" 0.04
117' - 4 5/8" 0' - 4 3/8"
1 1/2" (See
Notes)
1 5/8"
14.13
0.11
Flow (q) from Route 3
57.05 Tr, HW
8.99
38.39
8' - 0"
117' - 4 5/8" 12' - 3 1/4"
0.00
2.36
117' - 4 5/8" 4' - 3 1/4"
1 1/2" (See
Notes)
1 5/8"
14.17
0.19
Flow (q) from Route 4
76.30 PO(8' - 0"), HW
12.02
19.25
117' - 4 5/8" 9' - 8" 0.41
117' - 4 5/8" 9' - 8"
3" (See
Notes)
3 1/4"
16.53
0.04
Flow (q) from Route 8
216.85 Tr, HW
8.34
140.56
16.95 Route 2Total(Pt)
6' - 0"
117' - 4 5/8" 13' - 1"
-2.73
4.99
111' - 1" 7' - 1"
3/4"
• • • • • Route 3 • • • • •
(See
Notes)
7/8"
11.45
0.38
Sprinkler, 18.95
5.6
E(2' - 0"), PO(4' - 0"), HW
11.40
18.95
117' - 4 5/8" 7' - 9 1/4" 0.42
117' - 4 5/8" 7' - 9 1/4"
1 1/2" (See
Notes)
1 5/8"
13.71
0.05
Flow (q) from Route 6
38.39 Tr, HW
6.05
19.44
14.13 Route 3Total(Pt)
11/9/2025 Page 2AutoSPRINK RVT v8.3.13.0 1:15:12PMMAIN COMPUTER ROOM@ M.E.P.CAD
Remote Area Name: MAIN COMPUTER ROOM
Flow added this step
Pipe Information
Node 1
Node 2
Elev 1 ft
Elev 2 ft
K-Factor
Q
Total Flow
Q
Nominal ID
Actual ID
Fittings &
Devices
Equiv.
Length ft
Length ft
Fitting ft
Total ft
C Factor or
Roughness
Pf Friction Loss
Per Unit
Pounds force per square inch
Total(Pt)
Elev(Pe)
Friction(Pf)
Notes
Fitting/Device (Equivalent Length)
Fixed Pressure Losses, when applicable, are added directly to (Pf) and shown as a negative value.
Velocity
4' - 0"
117' - 4 5/8" 4' - 11 3/8"
0.41
1.94
118' - 4" 0' - 11 3/8"
3/4"
• • • • • Route 4 • • • • •
(See
Notes)
7/8"
11.82
0.39
Sprinkler, 19.25
5.6
PO(4' - 0"), HW
11.58
19.25
14.17 Route 4Total(Pt)
6' - 0"
117' - 4 5/8" 13' - 5"
-2.73
5.21
111' - 1" 7' - 5"
3/4"
• • • • • Route 5 • • • • •
(See
Notes)
7/8"
11.65
0.39
Sprinkler, 19.12
5.6
E(2' - 0"), PO(4' - 0"), HW
11.50
19.12
117' - 4 5/8" 7' - 9 1/4" 0.43
117' - 4 5/8" 7' - 9 1/4"
1 1/2" (See
Notes)
1 5/8"
14.13
0.06
Flow (q) from Route 9
38.86 Tr, HW
6.12
19.75
14.56 Route 5Total(Pt)
2' - 0"
117' - 4 5/8" 2' - 11 3/8"
0.41
1.18
118' - 4" 0' - 11 3/8"
3/4"
• • • • • Route 6 • • • • •
(See
Notes)
7/8"
12.06
0.40
Sprinkler, 19.44
5.6
E(2' - 0"), HW
11.70
19.44
117' - 4 5/8" 4' - 3 1/2" 0.07
117' - 4 5/8" 4' - 3 1/2"
1 1/2" (See
Notes)
1 5/8"
13.65
0.0219.44 Tr, HW
3.06
13.71 Route 6Total(Pt)
4' - 0"
117' - 4 5/8" 4' - 11 3/8"
0.41
2.00
118' - 4" 0' - 11 3/8"
3/4"
• • • • • Route 7 • • • • •
(See
Notes)
7/8"
12.19
0.40
Sprinkler, 19.55
5.6
PO(4' - 0"), HW
11.76
19.55
14.60 Route 7Total(Pt)
4' - 0"
117' - 4 5/8" 4' - 11 3/8"
0.41
2.03
118' - 4" 0' - 11 3/8"
3/4"
• • • • • Route 8 • • • • •
(See
Notes)
7/8"
12.40
0.41
Sprinkler, 19.72
5.6
PO(4' - 0"), HW
11.87
19.72
8' - 0"
117' - 4 5/8" 12' - 3 1/4"
0.00
1.50
117' - 4 5/8" 4' - 3 1/4"
1 1/2" (See
Notes)
1 5/8"
14.85
0.12
Flow (q) from Route 10
59.73 PO(8' - 0"), HW
9.41
40.01
117' - 4 5/8" 9' - 8" 0.19
117' - 4 5/8" 9' - 8"
3" (See
Notes)
3 1/4"
16.35
0.02
Flow (q) from Route 11
140.56 Tr, HW
5.40
80.83
11/9/2025 Page 3AutoSPRINK RVT v8.3.13.0 1:15:12PMMAIN COMPUTER ROOM@ M.E.P.CAD
Remote Area Name: MAIN COMPUTER ROOM
Flow added this step
Pipe Information
Node 1
Node 2
Elev 1 ft
Elev 2 ft
K-Factor
Q
Total Flow
Q
Nominal ID
Actual ID
Fittings &
Devices
Equiv.
Length ft
Length ft
Fitting ft
Total ft
C Factor or
Roughness
Pf Friction Loss
Per Unit
Pounds force per square inch
Total(Pt)
Elev(Pe)
Friction(Pf)
Notes
Fitting/Device (Equivalent Length)
Fixed Pressure Losses, when applicable, are added directly to (Pf) and shown as a negative value.
Velocity
16.53 Route 8Total(Pt)
2' - 0"
117' - 4 5/8" 2' - 11 3/8"
0.41
1.21
118' - 4" 0' - 11 3/8"
3/4"
• • • • • Route 9 • • • • •
(See
Notes)
7/8"
12.43
0.41
Sprinkler, 19.75
5.6
E(2' - 0"), HW
11.88
19.75
117' - 4 5/8" 4' - 3 1/2" 0.07
117' - 4 5/8" 4' - 3 1/2"
1 1/2" (See
Notes)
1 5/8"
14.06
0.0219.75 Tr, HW
3.11
14.13 Route 9Total(Pt)
2' - 0"
117' - 4 5/8" 2' - 11 3/8"
0.41
1.24
118' - 4" 0' - 11 3/8"
3/4"
• • • • • Route 10 • • • • •
(See
Notes)
7/8"
12.66
0.42
Sprinkler, 19.92
5.6
E(2' - 0"), HW
11.99
19.92
117' - 4 5/8" 4' - 3 1/2" 0.07
117' - 4 5/8" 4' - 3 1/2"
1 1/2" (See
Notes)
1 5/8"
14.31
0.0219.92 Tr, HW
3.14
117' - 4 5/8" 8' - 1 5/8" 0.47
117' - 4 5/8" 8' - 1 5/8"
1 1/2" (See
Notes)
1 5/8"
14.37
0.06
Flow (q) from Route 14
40.01 Tr, HW
6.31
20.09
14.85 Route 10Total(Pt)
2' - 0"
117' - 4 5/8" 2' - 11 3/8"
0.41
1.24
118' - 4" 0' - 11 3/8"
3/4"
• • • • • Route 11 • • • • •
(See
Notes)
7/8"
12.74
0.42
Sprinkler, 19.99
5.6
E(2' - 0"), HW
12.03
19.99
5' - 0"
117' - 4 5/8" 8' - 4 1/8" 1.09
117' - 4 5/8" 3' - 4 1/8"
1" (See
Notes)
1"
14.40
0.1319.99 PO(5' - 0"), HW
7.42
3' - 0"
117' - 4 5/8" 3' - 7 7/8" 0.45
117' - 4 5/8" 0' - 7 7/8"
1 1/4" (See
Notes)
1 3/8"
15.48
0.12
Flow (q) from Route 12
39.98 E(3' - 0"), HW
8.58
19.99
10' - 0"
117' - 4 5/8" 19' - 8 3/4" 0.34
117' - 4 5/8" 9' - 8 3/4"
2" (See
Notes)
2 1/8"
15.93
0.0239.98 2E(5' - 0"), HW
3.82
11/9/2025 Page 4AutoSPRINK RVT v8.3.13.0 1:15:12PMMAIN COMPUTER ROOM@ M.E.P.CAD
Remote Area Name: MAIN COMPUTER ROOM
Flow added this step
Pipe Information
Node 1
Node 2
Elev 1 ft
Elev 2 ft
K-Factor
Q
Total Flow
Q
Nominal ID
Actual ID
Fittings &
Devices
Equiv.
Length ft
Length ft
Fitting ft
Total ft
C Factor or
Roughness
Pf Friction Loss
Per Unit
Pounds force per square inch
Total(Pt)
Elev(Pe)
Friction(Pf)
Notes
Fitting/Device (Equivalent Length)
Fixed Pressure Losses, when applicable, are added directly to (Pf) and shown as a negative value.
Velocity
117' - 4 5/8" 5' - 7 1/4" 0.01
117' - 4 5/8" 5' - 7 1/4"
3" (See
Notes)
3 1/4"
16.27
0.0039.98 Tr, HW
1.54
117' - 4 5/8" 9' - 8" 0.07
117' - 4 5/8" 9' - 8"
3" (See
Notes)
3 1/4"
16.28
0.01
Flow (q) from Route 13
80.83 Tr, HW
3.11
40.84
16.35 Route 11Total(Pt)
2' - 0"
117' - 4 5/8" 2' - 11 3/8"
0.41
1.24
118' - 4" 0' - 11 3/8"
3/4"
• • • • • Route 12 • • • • •
(See
Notes)
7/8"
12.75
0.42
Sprinkler, 19.99
5.6
E(2' - 0"), HW
12.03
19.99
5' - 0"
117' - 4 5/8" 8' - 3 1/2" 1.08
117' - 4 5/8" 3' - 3 1/2"
1" (See
Notes)
1"
14.40
0.1319.99 PO(5' - 0"), HW
7.42
15.48 Route 12Total(Pt)
4' - 0"
117' - 4 5/8" 4' - 11 3/8"
0.41
2.12
118' - 4" 0' - 11 3/8"
3/4"
• • • • • Route 13 • • • • •
(See
Notes)
7/8"
13.00
0.43
Sprinkler, 20.19
5.6
PO(4' - 0"), HW
12.15
20.19
8' - 0"
117' - 4 5/8" 12' - 3 1/4"
0.00
0.74
117' - 4 5/8" 4' - 3 1/4"
1 1/2" (See
Notes)
1 5/8"
15.54
0.06
Flow (q) from Route 15
40.84 PO(8' - 0"), HW
6.44
20.65
16.28 Route 13Total(Pt)
2' - 0"
117' - 4 5/8" 8' - 3 5/8"
-2.73
3.53
111' - 1" 6' - 3 5/8"
3/4"
• • • • • Route 14 • • • • •
(See
Notes)
7/8"
12.87
0.43
Sprinkler, 20.09
5.6
E(2' - 0"), HW
12.09
20.09
5' - 0"
117' - 4 5/8" 5' - 4 7/8"
0.00
0.71
117' - 4 5/8" 0' - 4 7/8"
1" (See
Notes)
1"
13.66
0.1320.09 PO(5' - 0"), HW
7.46
14.37 Route 14Total(Pt)
2' - 0"
117' - 4 5/8" 2' - 11 3/8"
0.41
1.32
118' - 4" 0' - 11 3/8"
3/4"
• • • • • Route 15 • • • • •
(See
Notes)
7/8"
13.60
0.45
Sprinkler, 20.65
5.6
E(2' - 0"), HW
12.42
20.65
11/9/2025 Page 5AutoSPRINK RVT v8.3.13.0 1:15:12PMMAIN COMPUTER ROOM@ M.E.P.CAD
Remote Area Name: MAIN COMPUTER ROOM
Flow added this step
Pipe Information
Node 1
Node 2
Elev 1 ft
Elev 2 ft
K-Factor
Q
Total Flow
Q
Nominal ID
Actual ID
Fittings &
Devices
Equiv.
Length ft
Length ft
Fitting ft
Total ft
C Factor or
Roughness
Pf Friction Loss
Per Unit
Pounds force per square inch
Total(Pt)
Elev(Pe)
Friction(Pf)
Notes
Fitting/Device (Equivalent Length)
Fixed Pressure Losses, when applicable, are added directly to (Pf) and shown as a negative value.
Velocity
117' - 4 5/8" 12' - 5 1/8" 0.21
117' - 4 5/8" 12' - 5 1/8"
1 1/2" (See
Notes)
1 5/8"
15.33
0.0220.65 Tr, HW
3.25
15.54 Route 15Total(Pt)
4' - 0"
117' - 4 5/8" 4' - 11 3/8"
0.41
2.30
118' - 4" 0' - 11 3/8"
3/4"
• • • • • Route 16 • • • • •
(See
Notes)
7/8"
14.16
0.46
Sprinkler, 21.07
5.6
PO(4' - 0"), HW
12.68
21.07
8' - 0"
117' - 4 5/8" 12' - 3 1/4"
0.00
0.80
117' - 4 5/8" 4' - 3 1/4"
1 1/2" (See
Notes)
1 5/8"
16.87
0.07
Flow (q) from Route 17
42.61 PO(8' - 0"), HW
6.72
21.54
17.67 Route 16Total(Pt)
2' - 0"
117' - 4 5/8" 2' - 11 3/8"
0.41
1.43
118' - 4" 0' - 11 3/8"
3/4"
• • • • • Route 17 • • • • •
(See
Notes)
7/8"
14.80
0.48
Sprinkler, 21.54
5.6
E(2' - 0"), HW
12.96
21.54
117' - 4 5/8" 12' - 5 1/8" 0.23
117' - 4 5/8" 12' - 5 1/8"
1 1/2" (See
Notes)
1 5/8"
16.64
0.0221.54 Tr, HW
3.39
16.87 Route 17Total(Pt)
11/9/2025 Page 6AutoSPRINK RVT v8.3.13.0 1:15:12PMMAIN COMPUTER ROOM@ M.E.P.CAD
Remote Area Name: MAIN COMPUTER ROOM
1.51
Notes Legend
BFP Backflow Preventer BV Butterfly Valve CV Check Valve
E 90° Elbow HW Hazen-Williams PO Pipe Outlet red Reducer/Adapter S Supply Spr Sprinkler
Tr Tee run
4.87
1.33
1.16
0.713
Equivalent Pipe Lengths of Valves and Fittings (C=120 only)
Actual Inside Diameter
Schedule 40 Steel Pipe Inside Diameter = Factor
C Value Multiplier
Value Of C
Multiplying Factor
11/9/2025 Page 7AutoSPRINK RVT v8.3.13.0 1:15:12PMMAIN COMPUTER ROOM@ M.E.P.CAD
Electronic Health Records Modernization (EHRM) Infrastructure Upgrades – Togus, ME VA Project No. 402-22-700
Mechanical - MCR CFD Analysis
EHRM Infrastructure Upgrades
Togus VA Medical Center Togus, Maine
Project Number 402-22-700
November 10, 2025
CFD Analysis
GDM AE, Inc.
1308 NE 134th Street, Suite A
Vancouver, WA 98685
22-055 CFD Analysis – 100% Construction Documents
2025/11/10 Page 1 of 24
MECHANICAL DESIGN - MCR
The HVAC design for the MCR utilizes a pair of downflow CRAC units, connected to a hot aisle containment system by overhead return ductwork.
The CRAC unit configuration included in the current design and calculations meet the N+1 minimum redundancy required by DCIE/OIT. Each unit is capable of handling the required cooling load on its own, with the other unit in standby or shut down.
The CRAC units can operate concurrently at reduced airflow and compressor settings for optimized energy efficiency, or can operate with fewer units at higher loading to meet the required capacity.
Staging and fail-over functionality is handled by the CRAC system integrated controls. Both CRAC units are networked together to enable this control functionality.
The CRAC units included in the design are Liebert DSE125 indoor units with nominal sensible cooling capacity of 125kW each. Heat rejection from the CRAC units is accomplished using dedicated outdoor condensing units. These systems will also include a refrigerant-side economizer for increased efficiency.
Arranged in a hot-aisle configuration, the CRAC units draw hot supply air from the containment area and flood the MCR with cooled supply air. This configuration is proposed for this project as it offers greater occupant comfort compared to a cold-aisle containment system which results in elevated temperatures throughout the rest of the room, and also may mitigate potential hot-spots that could otherwise occur due to the nature of the in-row CRAC units.
ANALYSIS CONDITIONS
CFD analysis performed using Autodesk CFD 2019 software.
The following design conditions are utilized in the CFD model for this facility:
• Exact loads for each data cabinet, and the distribution of loads within each cabinet, are unknown and may change over time. The CFD analysis utilizes the following heat loads (as specified in the
VA CFD Guidelines and ISTS v3.1) for each cabinet/equipment type:
o SD cabinets: 5.0kW each o HD cabinets: 10.0kW each o HDA cabinets: 2.8kW each o MDA cabinets: 3.5kW each o UPS units: 5kw per active section (10.0kw total)
• Based on the telecommunications documents, the total loads included in the CFD model for the
MCR include 86.6kW in data cabinets (SD, HDA, & MDA types) as well as 10kW estimated load for the UPS units for a total design heat load of 96.6kW. The actual installed kW load following
2025/11/10 Page 2 of 24 this project will be less than the calculated load in the CFD model. The ultimate data cabinet load in the MCR per the DCIE standard small data center layout is 79.6kW.
• Airflows for each cabinet/equipment type utilized are modeled as follows:
o SD cabinets: 1040 cfm each o HDA cabinets: 585 cfm each o MDA cabinets: 725 cfm each
• (2) CRAC units provide data center conditioning for the main data cabinet set in the MCR. The
CFD model reflects (1) CRAC units operating at 100% airflow (18,000 cfm), with the other unit being inactive (redundant/standby or failed).
• The UPS units are nominally 100kW rated each, with a nominal maximum heat output of 10kW.
Sample manufacturer’s data indicates that actual heat output from the UPS units will be much lower (example - 3.1kW for Schneider Galaxy VS 100kW).
DESIGN GOALS
The objectives for the MCR cooling system are to achieve the following conditions:
• Supply air temperature setpoints between 64-81°F.
• Inlet temperatures at data equipment between 72-80.6°F.
• Rack/cabinet exhaust temperatures below 106°F (with up to 108°F acceptable at 1-2 racks).
• Minimize cold and hot spots near data equipment.
• Maintain room ambient conditions below 85°F for human comfort. Note that required rack inlet temperatures are lower than this temperature (supply air temperatures between 64-81°F).
• Maintain suitable temperatures for UPS unit operation, within manufacturer typical ambient temperature range of 41-104°F.
2025/11/10 Page 3 of 24
MCR LAYOUT
MCR DATA CABINET INFORMATION
Label Type Modeled KW Heat Load
F5 HDA 2.8
G5 SD (Oracle FDS) 5.0 I5 SD (Oracle FDS) 5.0
J5 SD 5.0
K5 SD 5.0
L5 SD 5.0
M5 SD 5.0
N5 SD 5.0
O5 SD 5.0
P5 SD 5.0
Q5 SD 5.0
R5 SD 5.0
S5 SD 5.0
T5 HDA 2.8
G10 MDA 3.5
I10 MDA 3.5
K10 MDA 3.5
L10 MDA 3.5
N10 MDA 3.5
P10 MDA 3.5
MCR-UPS-A UPS 5.0
MCR-UPS-B UPS 5.0
Total Load 96.6
2025/11/10 Page 4 of 24
VIEW LEGENDS - MCR
The views shown for each scenario are cut at the following locations.
Plane 1 – Horizontal orientation, approximately 48” above raised floor
Plane 2 – Vertical (north-south) orientation, through MCR-CRAC-1
Plane 3 – Vertical (north-south) orientation, through MCR-CRAC-2
2025/11/10 Page 5 of 24
MCR - SCENARIO 1A
Scenario conditions: 65°F supply air, CRAC unit MCR-CRAC-1 on, MCR-CRAC-2 off.
Figure 1a.1 – Plane 1
Figure 1a.2 – Plane 2
2025/11/10 Page 6 of 24
Figure 1a.3 – Plane 3
2025/11/10 Page 7 of 24
MCR - SCENARIO 1B
Scenario conditions: 65°F supply air, CRAC unit MCR-CRAC-2 on, MCR-CRAC-1 off.
Figure 1b.1 – Plane 1
Figure 1b.2 – Plane 2
2025/11/10 Page 8 of 24
Figure 1b.3 – Plane 3
2025/11/10 Page 9 of 24
MCR - SCENARIO 2A
Scenario conditions: 70°F supply air, CRAC unit MCR-CRAC-1 on, MCR-CRAC-2 off.
Figure 2a.1 – Plane 1
Figure 2a.2 – Plane 2
2025/11/10 Page 10 of 24
Figure 2a.3 – Plane 3
2025/11/10 Page 11 of 24
MCR - SCENARIO 2B
Scenario conditions: 70°F supply air, CRAC unit MCR-CRAC-2 on, MCR-CRAC-1 off.
Figure 2b.1 – Plane 1
Figure 2b.2 – Plane 2
2025/11/10 Page 12 of 24
Figure 2b.3 – Plane 3
2025/11/10 Page 13 of 24
MCR - SCENARIO 3A
Scenario conditions: 75°F supply air, CRAC unit MCR-CRAC-1 on, MCR-CRAC-2 off.
Figure 3a.1 – Plane 1
Figure 3a.2 – Plane 2
2025/11/10 Page 14 of 24
Figure 3a.3 – Plane 3
2025/11/10 Page 15 of 24
MCR - SCENARIO 3B
Scenario conditions: 75°F supply air, CRAC unit MCR-CRAC-2 on, MCR-CRAC-1 off.
Figure 3b.1 – Plane 1
Figure 3b.2 – Plane 2
2025/11/10 Page 16 of 24
Figure 3b.3 – Plane 3
2025/11/10 Page 17 of 24
MCR - SCENARIO 4A
Scenario conditions: 80°F supply air, CRAC unit MCR-CRAC-1 on, MCR-CRAC-2 off.
Figure 4a.1 – Plane 1
Figure 4a.2 – Plane 2
2025/11/10 Page 18 of 24
Figure 4a.3 – Plane 3
2025/11/10 Page 19 of 24
MCR - SCENARIO 4B
Scenario conditions: 80°F supply air, CRAC unit MCR-CRAC-2 on, MCR-CRAC-1 off.
Figure 4b.1 – Plane 1
Figure 4b.2 – Plane 2
2025/11/10 Page 20 of 24
Figure 4b.3 – Plane 3
2025/11/10 Page 21 of 24
MCR - TEMPERATURE DATA
Temperature data for each modeled scenario is provided on the following pages.
Inlet temperature points are located at the inlet side of the data cabinet, centered on the face of the cabinet, at approximately 48” above floor level.
Outlet temperature points are located at the outlet side of the data cabinet, centered on the face of the cabinet, at approximately 48” above floor level.
2025/11/10 Page 22 of 24
2025/11/10 Page 23 of 24
2025/11/10 Page 24 of 24
CONCLUSIONS - MCR
1. The model demonstrates that a hot aisle configuration with CRAC units located as shown is suitable for meeting the requirements for VA data center conditioning.
2. Based on temperature data from the modeled scenarios at the maximum design cabinet loading, the ideal supply air temperature setpoint for the MCR CRAC systems is 72-78°F as demonstrated in Scenario 3.
3. As demonstrated in Scenarios 1 & 2, a setpoint below approximately 72°F will likely result in data cabinet inlet air temperatures below 72°F.
4. As demonstrated in Scenario 4, a setpoint above approximately 78°F will likely result in data cabinet inlet air temperatures above 80.6°F.
5. As demonstrated in all included scenarios, none of the modeled setpoints result in cabinet outlet air temperatures above 106°F.
6. As demonstrated in all included scenarios, none of the modeled setpoints result in ambient temperatures at the UPS unit locations outside of manufacturer’s typical temperature recommendations (41-104°F).
7. At the design data equipment load of 96.6kW (including data cabinets and UPS units), the proposed arrangement of (2) 125kW nominal capacity CRAC units appear to be capable of maintaining space conditions within VA OIT standards while meeting N+1 redundancy. Note that this calculation includes data cabinet loads per the VA CFD Manual which is higher than the VA small data center template ultimate load of 79.6kW.
8. Future data equipment changes will need to be modeled to verify load distribution and any system adjustments or upgrades that might be required.
100% Construction Documents Reissued 02-18-2026
Electronic Health Records Modernization (EHRM) Infrastructure Upgrades – Togus, ME
Mechanical - MCR Fuel Tank Sizing
By Chkd. of
A 100% Load Fuel Consumption
B Integrated Fuel Tank - Useable Capacity
C Hours required per RFI #13 response
D Useable Gallons Required in System
(C * D)
E Gallons Required in Tank
(D - B)
F Safety Factor
G Gallons for Stand-by Tank Sizing
(E * F)
H Gallons from Ullage assumed: 90%
SPACE ABOVE MAX FILL
I Gallons from Drop Tube assumed: 10%
SPACE BELOW SUCTION TUBE
J Gallons for Generator Testing assumed: 10%
VOLUME USED FOR TESTING NOT TO IMPACT VOLUME FOR TANK CAPACITY
K NOMINAL CAPACITY FOR TANK
267.2 gal
267.2 gal
3,473.1 gal
2,671.6 gal
SIZE OF ABOVE GROUND FUEL TANK
674.4 gal
96 hr
2,683.1 gal
2,008.7 gal
33%
105.8 L/hr
27.9 gal/hr
2,553.0 L
267.2 gal
ADR
TOGUS EHRM22-055 Job Name
Subject
Job#
Date
Sheet
FUEL TANK CALCULATIONS 11/10/2025
Electronic Health Records Modernization (EHRM) Infrastructure Upgrades – Togus, ME VA Project No. 402-22-700
Mechanical - MCR Heat Load
Dedicated Outdoor Air System (DOAS) Sizing Summary for MCR - OFFICE Project Name: 22-055 TOGUS 95% 08/01/2023 Prepared by: GDM-AE 10:36AM
Air System Information Air System Name MCR - OFFICE Equipment Class TERM Air System Type VRF
Number of zones 6 Floor Area 2795.0 ft² Location Portland, Maine
Sizing Calculation Information Calculation Months Jan to Dec Sizing Data Calculated
Zone CFM Sizing Sum of space airflow rates Space CFM Sizing Individual peak space loads
Cooling Coil Sizing Data Total coil load 0.8 Tons Total coil load 9.5 MBH Total coil load 344.6 CFM/Ton Sensible coil load 7.3 MBH Coil CFM at Jul 1500 274 CFM Max coil CFM 274 CFM Sensible heat ratio 0.766 Water flow @ 10.0 °F rise N/A
Load occurs at Jul 1500
OA DB / WB 86.0 / 71.0 °F
Entering DB / WB 86.0 / 71.0 °F Leaving DB / WB 61.2 / 60.6 °F Bypass Factor 0.100
Heating Coil Sizing Data Max coil load 21.5 MBH Coil CFM at Des Htg 274 CFM Max coil CFM 274 CFM Water flow @ 20.0 °F drop N/A
Load occurs at Des Htg Ent. DB / Lvg DB -3.0 / 70.0 °F
Humidifier Sizing Data Max steam flow at Des Htg 5.29 lb/hr Airflow Rate 274 CFM
Air mass flow 1228.25 lb/hr Moisture gain .00431 lb/lb
Ventilation Fan Sizing Data Actual max CFM 274 CFM Standard CFM 273 CFM Actual max CFM/ft² 0.10 CFM/ft²
Fan motor BHP 0.00 BHP Fan motor kW 0.00 kW Fan static 0.00 in wg
Outdoor Ventilation Air Data Design airflow CFM 274 CFM CFM/ft² 0.10 CFM/ft²
CFM/person 54.71 CFM/person
Hourly Analysis Program 5.11 Page 1 of 25
Zone Sizing Summary for MCR - OFFICE
Prepared by: GDM-AE 10:36AM
Air System Information Air System Name MCR - OFFICE Equipment Class TERM Air System Type VRF
Number of zones 6 Floor Area 2795.0 ft² Location Portland, Maine
Sizing Calculation Information Calculation Months Jan to Dec Sizing Data Calculated
Zone CFM Sizing Sum of space airflow rates Space CFM Sizing Individual peak space loads
Terminal Unit Sizing Data - Cooling
Total Sens Coil Coil Water Time
Coil Coil Entering Leaving Flow of
Load Load DB / WB DB / WB @ 10.0 °F Peak Coil Zone
Zone Name (MBH) (MBH) (°F) (°F) (gpm) Load CFM/ft²
Ship / Recieve 3.5 3.3 74.8 / 65.1 61.1 / 60.2 - Aug 1400 0.61
Support 5.9 5.7 75.1 / 65.2 61.1 / 60.2 - Jul 1700 0.54
Working 4.5 4.3 75.3 / 64.5 59.8 / 58.8 - Jul 1600 1.26
MCR 355.2 353.7 76.0 / 63.9 59.0 / 57.8 - Jul 1600 16.08
Entrance B 31.0 30.8 75.9 / 63.9 58.9 / 57.8 - Jul 1600 10.54
Entrance A 31.0 30.8 75.8 / 63.9 58.9 / 57.7 - Aug 1500 10.02
Terminal Unit Sizing Data - Heating, Fan, Ventilation
Heating Htg Coil
Heating Coil Water Fan OA Vent
Coil Ent/Lvg Flow Design Fan Fan Design
Load DB @20.0 °F Airflow Motor Motor Airflow
Zone Name (MBH) (°F) (gpm) (CFM) (BHP) (kW) (CFM)
Ship / Recieve 4.4 69.1 / 87.1 - 225 0.000 0.000 45
Support 6.6 69.4 / 85.5 - 377 0.000 0.000 72
Working 4.1 69.2 / 83.9 - 256 0.000 0.000 30
MCR 16.1 69.7 / 70.5 - 19301 0.000 0.000 103
Entrance B 5.8 70.4 / 73.6 - 1687 0.000 0.000 12
Entrance A 4.1 69.9 / 72.1 - 1683 0.000 0.000 13
VRF Outdoor Unit Sizing Data
Cooling
[MBH]
Cooling [Tons]
Heating
[MBH]
Peak Coincident Indoor Unit Loads 430.8 35.9 41.0
Estimated Piping / Line Losses 0.0 0.0 0.0
Total Required ODU Capacity 430.8 35.9 41.0
Note: VRF piping / line losses are based on typical loss factors for this class of equipment. Actual line loss varies widely from one product to another.
Therefore, when selecting equipment it is critical to consult manufacturer's guidance to utilize actual line loss data.
Zone Peak Sensible Loads
Zone Zone Zone
Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (MBH) Cooling Load (MBH) (ft²)
Ship / Recieve 3.8 Jul 1400 4.5 372.0
Support 6.6 Jul 1700 6.5 692.0
Working 4.6 Aug 1600 4.1 203.0
MCR 353.6 Jul 1700 16.0 1200.0
Entrance B 30.9 Jul 1700 5.7 160.0
Entrance A 30.8 Aug 1500 4.1 168.0
Hourly Analysis Program 5.11 Page 2 of 25
Zone Sizing Summary for MCR - OFFICE
Prepared by: GDM-AE 10:36AM
Space Loads and Airflows
Zone Name / Space Name Mult.
Cooling Sensible
(MBH)
Time of Peak
Sensible Load
Air Flow
(CFM)
Heating Load
(MBH)
Floor Area (ft²)
Space CFM/ft²
Ship / Recieve
MCR - RECEIVING - 101 1 0.8 Jul 1500 59 1.6 87.0 0.68
MCR - UNBOX - 102 1 1.1 Jul 1500 60 0.7 143.0 0.42
MCR - SUPPLIES - 103 1 0.7 Aug 1500 41 0.7 89.0 0.46
MCR - VESTIBULE - 113 1 1.2 Jul 0900 66 1.5 53.0 1.24
Support
MCR - HAC - 106 1 0.3 Jul 1400 14 0.1 36.0 0.40
MCR - MECH - 104 1 1.1 Aug 1700 72 1.9 105.0 0.69
MCR - ELEC - 105 1 2.7 Jul 1800 147 3.1 203.0 0.72
MCR - CLEAN AGENT - 107 1 0.9 Jul 1600 48 0.8 78.0 0.61
MCR - TOILET - 112 1 0.5 Jul 1400 26 0.1 46.0 0.58
MCR - CORRIDOR 1 1.3 Jul 1400 69 0.5 224.0 0.31
Working
MCR - WORK STATION - 110 1 2.7 Jul 1500 149 1.2 134.0 1.11
MCR - STORAGE - 109 1 1.9 Aug 1600 108 2.9 69.0 1.56
MCR
MCR - DATA CENTER - 111 1 353.6 Jul 1700 19301 16.0 1200.0 16.08
Entrance B
MCR - ENTRANCE B - 112 1 30.9 Jul 1700 1687 5.7 160.0 10.54
Entrance A
MCR - ENTRANCE A - 100 1 30.8 Aug 1500 1683 4.1 168.0 10.02
Hourly Analysis Program 5.11 Page 3 of 25
Ventilation Sizing Summary for MCR - OFFICE
Prepared by: GDM-AE 10:36AM
1. Summary Ventilation Sizing Method ASHRAE Std 62.1-2013 Design Condition Heating operation
Zone Name
Zone Outdoor
Airflow
(CFM)
Uncorrected Outdoor Air
Intake
(CFM)
Ventilation Efficiency
Outdoor Air Intake
(CFM)
(Voz) (Vou) (Ev) (Vot)
Ship / Recieve 36 0.802 45
Support 54 0.752 72
Working 27 0.912 30
MCR 103 1.000 103
Entrance B 12 1.000 12
Entrance A 13 1.000 13
System Total 274
Note: For terminal systems, Standard 62.1 considers each terminal unit to be a "ventilation system". Standard 62.1 calculations are performed separately for each terminal unit zone.
Outdoor air intake flow rates for all terminal zones are summed to determine the total system outdoor air flow rate.
2. Space Ventilation Analysis
2.1 Zone: Ship / Recieve
Supply Air
(CFM)
Space Floor Area (ft²)
Area Outdoor Air Rate
(CFM/ft²)
Time Averaged
Occupancy (Occupants)
People Outdoor Air
Rate (CFM/person)
Air Distribution
Effectiveness
Space Outdoor Air
(CFM)
Breathing Zone
Outdoor Air
(CFM)
Space Ventilation Efficiency
Zone Name / Space Name Mult. (Vpz) (Az) (Ra) (Pz) (Rp) (Ez) (Voz) (Vbz) (Evz)
Ship / Recieve
MCR - RECEIVING - 101 1 59 87.0 0.12 0.0 10.00 0.8 13 10 0.939
MCR - UNBOX - 102 1 60 143.0 0.12 0.0 7.50 0.8 21 17 0.802
MCR - SUPPLIES - 103 1 41 89.0 0.06 0.0 5.00 0.8 7 5 0.997
MCR - VESTIBULE - 113 1 66 53.0 0.06 0.0 5.00 0.8 4 3 1.100
Totals (incl. Space Multipliers) 225 36 0.802
Hourly Analysis Program 5.11 Page 4 of 25
Prepared by: GDM-AE 10:36AM
2.2 Zone: Support
Space Floor Area (ft²)
Area Outdoor Air Rate
(CFM/ft²)
Time Averaged
Occupancy (Occupants)
People Outdoor Air
Rate (CFM/person)
Air Distribution
Effectiveness
Space Outdoor Air
(CFM)
Breathing Zone
Outdoor Air
(CFM)
Space Ventilation Efficiency
Zone Name / Space Name Mult. (Vpz) (Az) (Ra) (Pz) (Rp) (Ez) (Voz) (Vbz) (Evz)
Support
MCR - HAC - 106 1 14 36.0 0.12 0.0 5.00 0.8 5 4 0.766
MCR - MECH - 104 1 72 105.0 0.06 0.0 5.00 0.8 8 6 1.034
MCR - ELEC - 105 1 147 203.0 0.06 0.0 5.00 0.8 15 12 1.039
MCR - CLEAN AGENT - 107 1 48 78.0 0.12 0.0 5.00 0.8 12 9 0.898
MCR - TOILET - 112 1 26 46.0 0.18 0.0 10.00 0.8 10 8 0.752
MCR - CORRIDOR 1 69 224.0 0.06 0.0 0.00 0.8 17 13 0.900
Totals (incl. Space Multipliers) 377 54 0.752
2.3 Zone: Working
Space Floor Area (ft²)
Area Outdoor Air Rate
(CFM/ft²)
Time Averaged
Occupancy (Occupants)
People Outdoor Air
Rate (CFM/person)
Air Distribution
Effectiveness
Space Outdoor Air
(CFM)
Breathing Zone
Outdoor Air
(CFM)
Space Ventilation Efficiency
Zone Name / Space Name Mult. (Vpz) (Az) (Ra) (Pz) (Rp) (Ez) (Voz) (Vbz) (Evz)
Working
MCR - WORK STATION - 110 1 149 134.0 0.06 3.0 5.00 0.8 29 23 0.912
MCR - STORAGE - 109 1 108 69.0 0.06 0.0 5.00 0.8 5 4 1.058
Totals (incl. Space Multipliers) 256 27 0.912
2.4 Zone: MCR
Space Floor Area (ft²)
Area Outdoor Air Rate
(CFM/ft²)
Time Averaged
Occupancy (Occupants)
People Outdoor Air
Rate (CFM/person)
Air Distribution
Effectiveness
Space Outdoor Air
(CFM)
Breathing Zone
Outdoor Air
(CFM)
Space Ventilation Efficiency
Zone Name / Space Name Mult. (Vpz) (Az) (Ra) (Pz) (Rp) (Ez) (Voz) (Vbz) (Evz)
MCR
MCR - DATA CENTER - 111 1 19301 1200.0 0.06 2.0 5.00 0.8 103 82 1.000
Totals (incl. Space Multipliers) 19301 82 1.000
2.5 Zone: Entrance B
Space Floor Area (ft²)
Area Outdoor Air Rate
(CFM/ft²)
Time Averaged
Occupancy (Occupants)
People Outdoor Air
Rate (CFM/person)
Air Distribution
Effectiveness
Space Outdoor Air
(CFM)
Breathing Zone
Outdoor Air
(CFM)
Space Ventilation Efficiency
Zone Name / Space Name Mult. (Vpz) (Az) (Ra) (Pz) (Rp) (Ez) (Voz) (Vbz) (Evz)
Entrance B
MCR - ENTRANCE B - 112 1 1687 160.0 0.06 0.0 5.00 0.8 12 10 1.000
Totals (incl. Space Multipliers) 1687 10 1.000
Hourly Analysis Program 5.11 Page 5 of 25
Prepared by: GDM-AE 10:36AM
2.6 Zone: Entrance A
Space Floor Area (ft²)
Area Outdoor Air Rate
(CFM/ft²)
Time Averaged
Occupancy (Occupants)
People Outdoor Air
Rate (CFM/person)
Air Distribution
Effectiveness
Space Outdoor Air
(CFM)
Breathing Zone
Outdoor Air
(CFM)
Space Ventilation Efficiency
Zone Name / Space Name Mult. (Vpz) (Az) (Ra) (Pz) (Rp) (Ez) (Voz) (Vbz) (Evz)
Entrance A
MCR - ENTRANCE A - 100 1 1683 168.0 0.06 0.0 5.00 0.8 13 10 1.000
Totals (incl. Space Multipliers) 1683 10 1.000
Hourly Analysis Program 5.11 Page 6 of 25
Air System Design Load Summary for MCR - OFFICE
Prepared by: GDM-AE 10:36AM
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 85.4 °F / 70.8 °F HEATING OA DB / WB -3.0 °F / -4.3 °F
Sensible Latent Sensible Latent
ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 4 ft² 103 - 4 ft² - -
Wall Transmission 4745 ft² 4854 - 4745 ft² 27713 -
Roof Transmission 2858 ft² 2187 - 2858 ft² 6676 -
Window Transmission 4 ft² 13 - 4 ft² 123 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 195 ft² 3482 - 195 ft² 6506 -
Floor Transmission 2693 ft² 0 - 2693 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 3395 W 10607 - 0 0 -
Task Lighting 0 W 0 - 0 0 -
Electric Equipment 19950 W 67851 - 0 0 -
People 5 1043 1025 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 339849 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 429990 1025 - 41019 0
Zone Conditioning - 430194 1025 - 41119 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Exhaust Fan Load 274 CFM 0 - 274 CFM 0 -
Ventilation Load 274 CFM 2759 3041 274 CFM 21361 5584
Ventilation Fan Load 274 CFM 0 - 274 CFM 0 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 432952 4066 - 62481 5584
Cooling Coil - 7134 2227 - 0 0
Heating Coil - -2583 - - 21519 -
Terminal Unit Cooling - 428401 2362 - 0 0
Terminal Unit Heating - 0 - - 40953 -
Humidification Load - - 0 - - 5584
>> Total Conditioning - 432952 4589 - 62472 5584
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads
Hourly Analysis Program 5.11 Page 7 of 25
Zone Design Load Summary for MCR - OFFICE
Prepared by: GDM-AE 10:36AM
Ship / Recieve DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1400 HEATING DATA AT DES HTG
COOLING OA DB / WB 85.4 °F / 70.8 °F HEATING OA DB / WB -3.0 °F / -4.3 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 0 ft² 0 - 0 ft² - -
Wall Transmission 315 ft² 293 - 315 ft² 1840 -
Roof Transmission 376 ft² 351 - 376 ft² 878 -
Window Transmission 0 ft² 0 - 0 ft² 0 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 111 ft² 774 - 111 ft² 1785 -
Floor Transmission 364 ft² 0 - 364 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 372 W 1147 - 0 0 -
Task Lighting 0 W 0 - 0 0 -
Electric Equipment 372 W 1222 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 3788 0 - 4503 0
Support DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 84.1 °F / 70.5 °F HEATING OA DB / WB -3.0 °F / -4.3 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 0 ft² 0 - 0 ft² - -
Wall Transmission 822 ft² 968 - 822 ft² 4800 -
Roof Transmission 744 ft² 451 - 744 ft² 1738 -
Window Transmission 0 ft² 0 - 0 ft² 0 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 602 ft² 0 - 602 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 692 W 2175 - 0 0 -
Task Lighting 0 W 0 - 0 0 -
Electric Equipment 907 W 2986 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 6580 0 - 6538 0
Hourly Analysis Program 5.11 Page 8 of 25
Prepared by: GDM-AE 10:36AM
Working DESIGN COOLING DESIGN HEATING
COOLING DATA AT Aug 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 85.4 °F / 70.8 °F HEATING OA DB / WB -3.0 °F / -4.3 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 4 ft² 93 - 4 ft² - -
Wall Transmission 403 ft² 453 - 403 ft² 2356 -
Roof Transmission 210 ft² 140 - 210 ft² 491 -
Window Transmission 4 ft² 13 - 4 ft² 123 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 21 ft² 1077 - 21 ft² 1180 -
Floor Transmission 199 ft² 0 - 199 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 203 W 634 - 0 0 -
Task Lighting 0 W 0 - 0 0 -
Electric Equipment 471 W 1547 - 0 0 -
People 3 626 615 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 4582 615 - 4149 0
MCR DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 84.1 °F / 70.5 °F HEATING OA DB / WB -3.0 °F / -4.3 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 0 ft² 0 - 0 ft² - -
Wall Transmission 2064 ft² 2443 - 2064 ft² 12054 -
Roof Transmission 1200 ft² 728 - 1200 ft² 2803 -
Window Transmission 0 ft² 0 - 0 ft² 0 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 21 ft² 381 - 21 ft² 1180 -
Floor Transmission 1200 ft² 0 - 1200 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 1800 W 5658 - 0 0 -
Task Lighting 0 W 0 - 0 0 -
Electric Equipment 1200 W 4094 - 0 0 -
People 2 422 410 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 339849 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 353575 410 - 16037 0
Hourly Analysis Program 5.11 Page 9 of 25
Prepared by: GDM-AE 10:36AM
Entrance B DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 84.1 °F / 70.5 °F HEATING OA DB / WB -3.0 °F / -4.3 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 0 ft² 0 - 0 ft² - -
Wall Transmission 715 ft² 738 - 715 ft² 4176 -
Roof Transmission 160 ft² 97 - 160 ft² 374 -
Window Transmission 0 ft² 0 - 0 ft² 0 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 21 ft² 557 - 21 ft² 1180 -
Floor Transmission 160 ft² 0 - 160 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 160 W 503 - 0 0 -
Task Lighting 0 W 0 - 0 0 -
Electric Equipment 8500 W 29002 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 30898 0 - 5730 0
Entrance A DESIGN COOLING DESIGN HEATING
COOLING DATA AT Aug 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 86.0 °F / 71.0 °F HEATING OA DB / WB -3.0 °F / -4.3 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 0 ft² 0 - 0 ft² - -
Wall Transmission 426 ft² 463 - 426 ft² 2488 -
Roof Transmission 168 ft² 132 - 168 ft² 392 -
Window Transmission 0 ft² 0 - 0 ft² 0 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 21 ft² 707 - 21 ft² 1180 -
Floor Transmission 168 ft² 0 - 168 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 168 W 522 - 0 0 -
Task Lighting 0 W 0 - 0 0 -
Electric Equipment 8500 W 29002 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 30825 0 - 4061 0
Hourly Analysis Program 5.11 Page 10 of 25
Space Design Load Summary for MCR - OFFICE
Prepared by: GDM-AE 10:36AM
TABLE 1.1.A. Component Loads For Space "MCR - RECEIVING - 101" In Zone "Ship / Recieve"
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 86.0 °F / 71.0 °F HEATING OA DB / WB -3.0 °F / -4.3 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 0 ft² 0 - 0 ft² - -
Wall Transmission 132 ft² 125 - 132 ft² 771 -
Roof Transmission 91 ft² 80 - 91 ft² 213 -
Window Transmission 0 ft² 0 - 0 ft² 0 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 90 ft² 63 - 90 ft² 604 -
Floor Transmission 87 ft² 0 - 87 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 87 W 270 - 0 0 -
Task Lighting 0 W 0 - 0 0 -
Electric Equipment 87 W 285 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 823 0 - 1588 0
TABLE 1.1.B. Envelope Loads For Space "MCR - RECEIVING - 101" In Zone "Ship / Recieve"
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft²) (BTU/(hr·ft²·°F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
ENE EXPOSURE
WALL 60 0.080 - 50 - 350
DOOR 90 0.092 - 63 - 604
SSE EXPOSURE
WALL 72 0.080 - 74 - 420
H EXPOSURE
ROOF 91 0.032 - 80 - 213
Hourly Analysis Program 5.11 Page 11 of 25
Prepared by: GDM-AE 10:36AM
TABLE 1.2.A. Component Loads For Space "MCR - UNBOX - 102" In Zone "Ship / Recieve"
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 86.0 °F / 71.0 °F HEATING OA DB / WB -3.0 °F / -4.3 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 0 ft² 0 - 0 ft² - -
Wall Transmission 58 ft² 60 - 58 ft² 339 -
Roof Transmission 143 ft² 125 - 143 ft² 334 -
Window Transmission 0 ft² 0 - 0 ft² 0 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 135 ft² 0 - 135 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 143 W 444 - 0 0 -
Task Lighting 0 W 0 - 0 0 -
Electric Equipment 143 W 468 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 1097 0 - 673 0
TABLE 1.2.B. Envelope Loads For Space "MCR - UNBOX - 102" In Zone "Ship / Recieve"
COOLING COOLING…