S02 - SOW - Att 14 - Design Calcs - 02182026 - EHRM Infra Upgrades - Constr - Togus.pdf

PDF 37 MB Posted

Attached to
Electronic Health Record Modernization Infrastructure Upgrades - Construction - Togus, ME
Solicitation number
36C77626R0062
Issued by

About this file

This is a 100% Construction Documents submittal containing design calculations for infrastructure upgrades at the VA Togus Medical Center in Augusta, Maine, reissued February 18, 2026. The document supports the Electronic Health Record Modernization (EHRM) Infrastructure Upgrades project, identified as VA Project No. 402-22-700 under Contract No. 36C77623C0002. The calculations were prepared by GDM-AE, Inc. and are submitted to the Department of Veterans Affairs Program Contracting Activity Central (PCAC) located in Independence, Ohio.

The submittal includes comprehensive design calculations across multiple engineering disciplines: civil calculations for 6-inch and 8-inch sewer lateral and main pipe sizing, domestic water pipe sizing, fire sprinkler system calculations, mechanical calculations including CFD analysis, fuel tank sizing, heat load analysis, roof drain sizing, and systems design for all other buildings, as well as structural calculations and blast analysis. These calculations support the detailed infrastructure design necessary for construction of the EHRM upgrades at the Togus VA Medical Center facility in Augusta, Maine.

View the file

Other files

File Type Posted
S30 - SAM - Special Notice - Cancellation - 36C77626R0062_2 - EHRM Infra Upgrades - Togus.pdf PDF
S06 - Amend 0002 - Att 03 - Corrected Agenda - RFP - 07202026 - EHRM Infra - Togus.pdf PDF
S06 - Amend 0002 - 36C77626R0062 - 07202026 - EHRM Infra - Togus.pdf PDF
S06 - Amend 0001 - Att 02 - SV - Attendance SHT - 06292026 - EHRM Infra - Togus.pdf PDF
S06 - Amend 0001 - 36C77626R0062 - 07142026 - EHRM Infra - Togus.pdf PDF
S06 - Amend 0001 - RFIs - 07132026 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S06 - Amend 0001 - Att 01 - Rvd Structural Drwg - 06192026 - EHRM Infra - Togus.pdf PDF
S06 - Amend 0001 - Att 03 - SV - Agenda - RFP - 06292026 - EHRM Infra - Togus.pdf PDF
S02 - SOW - Att 05 - Drwg - Vol 3 - 02182026 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - SOW - Att 13 - Const Sch - 02132026 - EHRM Infra Upgrades - Constr Togus.pdf PDF
S02 - SOW - Att 26 - Cut Sheet 04 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - Att 03 -Prj Info Sheet for KTR - EHRM Infra Upgrade - Togus.docx DOCX document
S02 - SOW - Att 03 - Drwg - Vol 1C - 02182026 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - SOW - Att 22 - TS-000 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - Att 07 - 852.219-75 - 06172026 - EHRM Infra Upgrade - Togus.pdf PDF
S02 - Att 04 - Memo - Brand Name - 04092026 - EHRM Infra Upgrade - Togus.pdf PDF
S02 - SOW - Att 35 - Cut Sheet 13 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - SOW - Att 17 - Memo - Phy Sec Compliance - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - SOW - Att 27 - Cut Sheet 05 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - SOW - Att 09 - Specs - Vol 3- 02182026 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - SOW - Att 30 - Cut Sheet 08 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - SOW - Att 24 - Cut Sheet 02 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - Att 05 - Division Cost Breakdown - EHRM Infra Upgrade - Togus.xlsx XLSX spreadsheet
S02 - SOW - Att 29 - Cut Sheet 07 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - SOW - Att 37 - Cut Sheet 15 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - SOW - Att 16 - Submittal Reg - 02182026 - EHRM Infra - Upgrades - Constr - Togus.xlsx XLSX spreadsheet
S02 - SOW - Att 18 - Memo - Prj Stnd Compliance - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - SOW - Att 21 - PCRA 3 - MCR and Trench Work - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - SOW - Att 40 - Cut Sheet 18 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - SOW - Att 33 - Cut Sheet 11 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - SOW - Att 01 - Drwg - Vol 1A - 02182026 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - SOW - Att 38 - Cut Sheet 16 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - SOW - Att 06 - Drwg - Vol 4 - 02182026 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - SOW - Att 11 - Haz Mat Report - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - SOW - Att 12 - Geotechnical Report - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - SOW - Att 32 - Cut Sheet 10 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - SOW - Att 08 - Specs - Vol 1 - Div 02-14 - 02182026 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - SOW - Att 20 - PCRA 2 - Cabling and Data Outlets - EHRM Infra Upgrades - Constr - Togus.pdf PDF
RFP - EHRM Infra Upgrade - 36C77626R0062 - 06172026 - Togus.pdf PDF
S02 - SOW - Att 19 - PCRA 1 - TR Constr - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - SOW - Att 07 - Specs - Vol 1 - Div 00-01 - 02182026 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - SOW - Att 15 - Design Narrative - 02182026 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - SOW - Att 23 - Cut Sheet 01 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - SOW - Att 31 - Cut Sheet 09 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - Att 02 - PPQ - EHRM Infra Upgrade - Togus.docx DOCX document
S02 - SOW - Att 02 - Drwg - Vol 1B - 02182026 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - SOW - Att 34 - Cut Sheet 12 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - Att 01 - SOW - 05112026 - EHRM Infra Upgrades - Togus.pdf PDF
S02 - SOW - Att 10 - Specs - Vol 4 - 02182026 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - SOW - Att 36 - Cut Sheet 14 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
Show 40 more

Latest 50 of 57 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Construction Documents – 100% Submittal: Calculations Reissued February 18th, 2025

Department of Veterans Health Administration

Electronic Health Record Modernization (EHRM) Infrastructure

Upgrades – Togus, ME Project No. 402-22-700

Contract No. 36C77623C0002

Togus VA Medical Center

1 VA Center, Augusta, ME 04330

US Department of Veterans Affairs

Program Contracting Activity Central (PCAC)

6150 Oak Tree Blvd., Suite 300

Independence, OH 44131

Prepared by:

GDM-AE, Inc.

1308 NE 134th St Suite A Vancouver, WA 98685

VA Togus Medical Center Augusta, ME

100% Construction Documents Reissued 02-18-2026

Electronic Health Records Modernization (EHRM) Infrastructure Upgrades – Togus, ME VA Project No. 402-22-700

TABLE OF CONTENTS

Civil - MCR 6 in Sewer Lateral Pipe Size

Civil - MCR 8 in Sewer Main Pipe Size

Civil - MCR Domestic Water Pipe Sizing Calculations Fire -

MCR Fire Sprinkler Calculations

Mechanical - MCR CFD Analysis

Mechanical - MCR Fuel Tank Sizing

Mechanical - MCR Heat Load

Mechanical - MCR Roof Drain Sizing

Mechanical - Systems Design Report - All Other Buildings

Structural - MCR Structural Calculations

Blast Analysis Calculations

Electronic Health Records Modernization (EHRM) Infrastructure Upgrades – Togus, ME VA Project No. 402-22-700

Civil - MCR 6 in Sewer Lateral Pipe Size

100% Construction Documents Reissued 02-18-2026

����������������� � � �������������� !� "�#�$�%�&'()�*)��!+��,(&�'(�,(� ���-)�. � � �����" &�/�/($�0 &(��%�!�%��"�"��� � � �1���� ��2��34567�89:;6<�=4�>:;6�>?@6<A��B9:C;:95=?4<�=4�D6::?E � � �� 1�� �� � � � � � � �� � � � � � � � �F�/(�#��0(�(&)�G�H � I �! � � � �#(/�%� "�J� K)���H � L�M �! � � � �� �����N0�$�%�,(�-�O#PLQ � � � � � � �� � � � � � � � �R����F�/(�S�!!�!' �� � � � � �& �'%!($$)�� �H � T�TUL � � � � ��%�!!(��V �� 0 � � � � � � �� $� /()���H � T�TU "�P"�� � � �� � �� � � � � ����� �� �� � � � � �������������������W� ��H �U�LXUY � � � � �F�&�����-�R����S�!!�!' �� � � � � �& �'%!($$)���H � T�TUI � � � � �� � � � � � � � �� � � � � � � � �� F�/(�#��0(�(&)�G�H T�M "� � � � �� F�/(�Z�+��$)���H T�LM "� � � � �� � �� � � � � �� ��&���[('0(!��\(�'%�)]�H T�LXL "� � � � �� � �� � � � � �� �(!�&���̂!'�()�_�H �̀ab &�+��!$ � � � �� �& $$c[(����̂&(�)�d�H T�Tb "�� � � � �� � �� � � � � �� e(��(+�F(&�0(�(&)���H T�Y "� � � � �� \-+&������Z�+��$)�f�H T�UU "� � � � �� #�$�%�&'()�g�H T�UY �"$ � � � �� ,̂(��.(� ���-)�h�H L�LU "�P$(� � � � �� � �� � � � � ���������/�/(�i�"����jN̂P̂ QkUTTil�H� X̀�ai � � � � �� � � � � � � � � m m

L

Celyn Dezmain CJD Stamp

100% Construction Documents Reissued 02-18-2026

Electronic Health Records Modernization (EHRM) Infrastructure Upgrades – Togus, ME VA Project No. 402-22-700

Civil - MCR 8 in Sewer Main Pipe Size

����������������� � � �������������� !� "�#�$�%�&'()�*)��!+��,(&�'(�,(� ���-)�. � � �����" &�/�/($�0 &(��%�!�%��"�"��� � � �1���� ��2��34567�89:;6<�=4�>:;6�>?@6<A��B9:C;:95=?4<�=4�D6::?E � � �� 1�� �� � � � � � � �� � � � � � � � �F�/(�#��0(�(&)�G�H � I �! � � � �#(/�%� "�J� K)���H � L�M �! � � � �� �����N0�$�%�,(�-�O#PQR � � � � � � �� � � � � � � � �S����F�/(�T�!!�!' �� � � � � �& �'%!($$)�� �H � U�UVQ � � � � ��%�!!(��W �� 0 � � � � � � �� $� /()���H � U�UUX "�P"�� � � �� � �� � � � � ����� �� �� � � � � �������������������Y� ��H �V�QIZX � � � � �F�&�����-�S����T�!!�!' �� � � � � �& �'%!($$)���H � U�UVX � � � � �� � � � � � � � �� � � � � � � � �� F�/(�#��0(�(&)�G�HU�[[[[[[[[ "� � � � �� F�/(�\�+��$)���HU�LLLLLLLL "� � � � �� � �� � � � � �� ��&���]('0(!��̂(�'%�)_�H U�LIL "� � � � �� � �� � � � � �� �(!�&���̀!'�()�a�H L�MM &�+��!$ � � � �� �& $$b](����̀&(�)�c�H U�VM "�� � � � �� � �� � � � � �� d(��(+�F(&�0(�(&)���H U�e "� � � � �� -̂+&������\�+��$)�f�H U�VX "� � � � �� #�$�%�&'()�g�H U�QZ �"$ � � � �� ,̀(��.(� ���-)�h�H V�eQ "�P$(� � � � �� � �� � � � � ���������/�/(�i�"����jǸP̀ RkVUUil�H� MU�Xi � � � � �� � � � � � � � � m m

Q

100% Construction Documents Reissued 02-18-2026

Electronic Health Records Modernization (EHRM) Infrastructure Upgrades – Togus, ME

Civil - MCR Domestic Water Pipe Sizing Calculations

402-22-700 36C77623C0002 Togus VAMC EHRM Infrastructure Upgrades

Domestic and Fire Protection Water Distribution Pipe Sizing Calculations

Calculations below demonstrate the min pipe size requirement for the shared domestic and fire protection water service:

Known:

Domestic Water Demand Qd 33 GPM Fire Protection Water Demand Qf 585.56 GPM @ 39.89PSI

Total Water Demand Qt 618 GPM ~ 1.37 cfs

Pipe Material PVC Pipe Material C Value 150

Pipe Length (L) 210 LF Pipe Size (D) 6 in

Residual Pressure at existing Main 58 PSI @ 1,113 GPM Static Pressure at existing Main 65 PSI @ 0 GPM

Min Pipe Size Required:

Q=V*A

Q=V*πr2 r=SQRT(Q/V π) r=SQRT(1.37cfs/7.0fps*3.14) r=0.25ft ~ 3”

Min Pipe Size 6” diameter

Pressure loss due to friction:

Ploss = 4.53*L*(Q/C)1.852 / D4.857

L eq = 210 + (2-90 bend)*8.9 + (1 tee)*18 + (3-45 bends)*5.6

=210+17.8+18+16.8 = 262.6 ft = 4.53*262.6*(655/150)1.852 / 64.857

= 3.05 PSI

Helevation = 6” elevation change from water main connection to building connection is considered negligible.

Pressure in a 6” PVC Water Service line at the new standalone MCR connection 61.95PSI @ 618 GPM;

Therefore, a 6” PVC Water and Fire Service line will sufficiently serve the MCR water demand.

Electronic Health Records Modernization (EHRM) Infrastructure Upgrades – Togus, ME VA Project No. 402-22-700

Fire - MCR Fire Sprinkler Calculations

Location: VA Togus Medical Center, Augusta, Maine, Project Name: Togus EHRM Infrastructure Upgrades

Drawing Name: 22117_MCR_Fire_Protection_r25 Calculation Date:11/9/2025

Hydraulic Calculations Summary for

Design

Ordinary Hazard Group 1

MAIN COMPUTER ROOM

0.15/Square feet

Remote Area Name:

Occupancy Classification:

Density

Area of Application: 1500.00 (Actual Area: 1501.17)

Coverage per Sprinkler:

Type of Sprinklers Calculated:

No. of Sprinklers Calculated:

91.41 (average) at Node:

Fire Protection Wet

N/AN/A

1250.00

0.0 galType of System:

In-rack Demand:

Hose Streams:

Volume of Dry or PreAction System:

at Node:

Type Allowance at Source

Total Water Required (including Hose Streams where applicable)

39.89@585.58FROM: Water Supply at Node 1:

22.98Safety Margin:

Hazen-Williams

None.

Applied Friction Loss Method:

Darcy-Weisbach Suppression Agent:

Conrad Chandler, PE

Department of Veterans Affairs

1308 NE 134th Street, Suite A, Vancouver, WA 98685

541-426-4723

Contact Name

Address:

Phone Number:

Authority Having Jurisdiction:

Name of Designer:

Notes: HYDRAULIC CALCULATIONS ARE PROVIDED TO VERIFY UNDERGROUND PIPE SIZE ONLY. CONTRACTORS FOR FIRE SUPPRESSION SYSTEMS ARE REQUIRED TO PROVIDE CALCULATIONS AND WORKING DRAWINGS FOR NEW OR MODIFIED SYSTEMS. NOTE: SPRINKLER HEADS WITHIN THE REMOTE AREA WERE CALCULATED AT ACTUAL COVERAGE AREA. FOR UNDERGROUND PIPING CALCULATION INCLUDES 262' EQUIVALENT LENGTH

OF 6" DIP.

11/9/2025 Page 1AutoSPRINK RVT v8.3.13.0 1:15:10PMMAIN COMPUTER ROOM@ M.E.P.CAD

Conrad Chandler 11-10-2025

Hydraulic Graph

Water Supply

Node: 1

Job Name: Togus EHRM Infrastructure Upgrades

Remote Area Name: MAIN COMPUTER ROOM Date: 11/9/2025 N 1.85

Summary Sheet

No pressure is being required from the Source/Supply to meet the demand (by a margin of this negative value).

A negative result in Required Pressure indicates that the Pump is capable of furnishing all of the pressure required by the demand reported within this calculation.

11/9/2025 Page 1AutoSPRINK RVT v8.3.13.0 1:15:11PM@ M.E.P.CAD

(US gallons per minute) (US gallons per minute) (K) (Pounds force per square inch)

Outflowing Devices Report Description: Ordinary Hazard Group 1

Job Number: 402-22-700

Device

Actual Flow Minimum Flow K-Factor Pressure

Sprinkler 101 19.12 14.82 5.6 11.65

Sprinkler 102 18.95 14.82 5.6 11.45

Sprinkler 103 20.09 14.82 5.6 12.87

Sprinkler 104 17.70 17.70 5.6 9.99

Sprinkler 105 18.65 17.70 5.6 11.09

Sprinkler 117 20.65 15.00 5.6 13.60

Sprinkler 112 20.19 15.00 5.6 13.00

Sprinkler 107 19.99 15.00 5.6 12.74

Sprinkler 116 19.92 15.00 5.6 12.66

Sprinkler 111 19.72 15.00 5.6 12.40

Sprinkler 115 19.44 15.00 5.6 12.06

Sprinkler 110 19.25 15.00 5.6 11.82

Sprinkler 114 19.75 15.00 5.6 12.43

Sprinkler 109 19.55 15.00 5.6 12.19

Sprinkler 113 21.54 15.00 5.6 14.80

Sprinkler 108 21.07 15.00 5.6 14.16

Sprinkler 106 19.99 15.00 5.6 12.75

Most Demanding Sprinkler Data

11/9/2025 Page 1AutoSPRINK RVT v8.3.13.0 1:15:11PM@ M.E.P.CAD

Job Name: Togus EHRM Infrastructure Upgrades

Remote Area Name: MAIN COMPUTER ROOM Date: 11/9/2025

(Pounds force per square inch) (Pounds force per square inch)(US gallons per minute)(Pounds force per square inch)(US gallons per minute)(Pounds force per square inch)

Supply Analysis

Node Name Static Residual Flow Available Total Demand Required Pressure

58.001 39.89585.581113.00 62.8765.00Water Supply

Node Analysis

Discharge at

Node

(US gallons per

Pressure at

Node

(Pounds force

Elevation (ft)Node Number Node Type Notes

100' - 0" 335.5839.891 Supply

111' - 1" 19.1211.65101 Sprinklers

111' - 1" 18.9511.45102 Sprinklers

111' - 1" 20.0912.87103 Sprinklers

113' - 8" 17.709.99104 Sprinklers

113' - 8" 18.6511.09105 Sprinklers

118' - 4" 19.9912.75106 Sprinklers

118' - 4" 19.9912.74107 Sprinklers

118' - 4" 21.0714.16108 Sprinklers

118' - 4" 19.5512.19109 Sprinklers

118' - 4" 19.2511.82110 Sprinklers

118' - 4" 19.7212.40111 Sprinklers

118' - 4" 20.1913.00112 Sprinklers

118' - 4" 21.5414.80113 Sprinklers

118' - 4" 19.7512.43114 Sprinklers

118' - 4" 19.4412.06115 Sprinklers

118' - 4" 19.9212.66116 Sprinklers

118' - 4" 20.6513.60117 Sprinklers

100' - 0" 38.862

11/9/2025 Page 1AutoSPRINK RVT v8.3.13.0 1:15:12PM@ M.E.P.CAD

Discharge at

Node

(US gallons per

Pressure at

Node

(Pounds force

Elevation (ft)Node Number Node Type Notes

102' - 11 1/4" 37.343

102' - 11 1/4" 37.464

102' - 11 1/4" 37.525

108' - 0 1/4" 34.176

108' - 0 1/4" 33.277

111' - 0 3/8" 31.638

113' - 6" 10.2910

113' - 6" 11.4111

117' - 4 5/8" 16.8712

117' - 4 5/8" 14.6013

117' - 4 5/8" 14.1714

117' - 4 5/8" 14.8515

117' - 4 5/8" 15.5416

117' - 4 5/8" 14.5617

117' - 4 5/8" 14.1318

117' - 4 5/8" 14.1319

117' - 4 5/8" 13.7120

117' - 4 5/8" 14.3721

117' - 4 5/8" 16.6422

117' - 4 5/8" 14.0623

117' - 4 5/8" 13.6524

117' - 4 5/8" 14.3125

117' - 4 5/8" 15.3326

11/9/2025 Page 2AutoSPRINK RVT v8.3.13.0 1:15:12PM@ M.E.P.CAD

Discharge at

Node

(US gallons per

Pressure at

Node

(Pounds force

Elevation (ft)Node Number Node Type Notes

117' - 4 5/8" 17.6727

117' - 4 5/8" 16.9528

117' - 4 5/8" 16.5329

117' - 4 5/8" 16.3530

117' - 4 5/8" 16.2831

117' - 4 5/8" 16.2732

117' - 4 5/8" 15.9333

117' - 4 5/8" 14.4034

117' - 4 5/8" 14.4035

117' - 4 5/8" 15.4836

117' - 4 5/8" 13.6637

11/9/2025 Page 3AutoSPRINK RVT v8.3.13.0 1:15:12PM@ M.E.P.CAD

Date: 11/9/2025

Remote Area Name: MAIN COMPUTER ROOM

Flow added this step

Pipe Information

Node 1

Node 2

Elev 1 ft

Elev 2 ft

K-Factor

Q

Total Flow

Q

Nominal ID

Actual ID

Fittings &

Devices

Equiv.

Length ft

Length ft

Fitting ft

Total ft

C Factor or

Roughness

Pf Friction Loss

Per Unit

Pounds force per square inch

Total(Pt)

Elev(Pe)

Friction(Pf)

Notes

Fitting/Device (Equivalent Length)

Fixed Pressure Losses, when applicable, are added directly to (Pf) and shown as a negative value.

Velocity

2' - 0"

113' - 6" 2' - 2"

0.07

0.22

113' - 8" 0' - 2"

1"

• • • • • Route 1 • • • • •

(See

Notes)

1"

9.99

0.10

Sprinkler, 17.70

5.6

E(2' - 0"), HW

6.57

17.70

8' - 0"

117' - 4 5/8" 17' - 8 3/8"

-1.68

5.95

113' - 6" 9' - 8 3/8"

3/4" (See

Notes)

7/8"

10.29

0.3417.70 2E(2' - 0"), PO(4' - 0"), HW

10.65

117' - 4 5/8" 0' - 4 3/8" 0.04

117' - 4 5/8" 0' - 4 3/8"

1 1/2" (See

Notes)

1 5/8"

14.56

0.11

Flow (q) from Route 5

56.56 Tr, HW

8.91

38.86

8' - 0"

117' - 4 5/8" 12' - 3 1/4"

0.00

2.35

117' - 4 5/8" 4' - 3 1/4"

1 1/2" (See

Notes)

1 5/8"

14.60

0.19

Flow (q) from Route 7

76.11 PO(8' - 0"), HW

11.99

19.55

117' - 4 5/8" 9' - 8" 0.72

117' - 4 5/8" 9' - 8"

3" (See

Notes)

3 1/4"

16.95

0.07

Flow (q) from Route 2

292.97 Tr, HW

11.26

216.85

41' - 0"

111' - 0 3/8" 99' - 7 1/8"

2.76

11.21

117' - 4 5/8" 58' - 7 1/8"

3" (See

Notes)

3 1/4"

17.67

0.10

Flow (q) from Route 16

335.58 5E(7' - 0"), 3red, E(6' - 0"), Tr, HW

12.90

42.61

10' - 0"

108' - 0 1/4" 13' - 0 1/8"

1.30

0.34

111' - 0 3/8" 3' - 0 1/8"

4" (See

Notes)

4 1/4"

31.63

0.03335.58 E(10' - 0"), HW

7.55

32' - 0"

108' - 0 1/4" 34' - 2 3/8" 0.89

108' - 0 1/4" 2' - 2 3/8"

4" (See

Notes)

4 1/4"

33.27

0.03335.58 BV(12' - 0"), PO(20' - 0"), HW

7.55

32' - 0"

102' - 11 1/4" 37' - 1"

2.20

0.97

108' - 0 1/4" 5' - 1"

4" (See

Notes)

4 1/4"

34.17

0.03335.58 CV(22' - 0"), E(10' - 0"), HW

7.55

102' - 11 1/4" 4' - 10 5/8" 0.13

102' - 11 1/4" 4' - 10 5/8"

4" (See

Notes)

4 1/4"

37.34

0.03335.58 BFP, red, HW

7.55

14' - 0"

102' - 11 1/4" 15' - 1 3/8" 0.06

102' - 11 1/4" 1' - 1 3/8"

6" (See

Notes)

6 3/8"

37.46

0.00335.58 E(14' - 0"), HW

3.39

11/9/2025 Page 1AutoSPRINK RVT v8.3.13.0 1:15:12PMMAIN COMPUTER ROOM@ M.E.P.CAD

Remote Area Name: MAIN COMPUTER ROOM

Flow added this step

Pipe Information

Node 1

Node 2

Elev 1 ft

Elev 2 ft

K-Factor

Q

Total Flow

Q

Nominal ID

Actual ID

Fittings &

Devices

Equiv.

Length ft

Length ft

Fitting ft

Total ft

C Factor or

Roughness

Pf Friction Loss

Per Unit

Pounds force per square inch

Total(Pt)

Elev(Pe)

Friction(Pf)

Notes

Fitting/Device (Equivalent Length)

Fixed Pressure Losses, when applicable, are added directly to (Pf) and shown as a negative value.

Velocity

14' - 0"

100' - 0" 16' - 11 1/4"

1.27

0.06

102' - 11 1/4" 2' - 11 1/4"

6" (See

Notes)

6 3/8"

37.52

0.00335.58 E(14' - 0"), HW

3.39

100' - 0" 262' - 6 1/2" 1.03

100' - 0" 262' - 6 1/2"

6" (See

Notes)

6 1/4"

38.86

0.00335.58 Water Supply, HW

3.47

Hose Allowance At Source

585.58 Route 1

39.89

Total(Pt)

250.00

2' - 0"

113' - 6" 2' - 2"

0.07

0.25

113' - 8" 0' - 2"

1"

• • • • • Route 2 • • • • •

(See

Notes)

1"

11.09

0.11

Sprinkler, 18.65

5.6

E(2' - 0"), HW

6.92

18.65

6' - 0"

117' - 4 5/8" 11' - 10 5/8"

-1.68

4.40

113' - 6" 5' - 10 5/8"

3/4" (See

Notes)

7/8"

11.41

0.3718.65 E(2' - 0"), PO(4' - 0"), HW

11.22

117' - 4 5/8" 0' - 4 3/8" 0.04

117' - 4 5/8" 0' - 4 3/8"

1 1/2" (See

Notes)

1 5/8"

14.13

0.11

Flow (q) from Route 3

57.05 Tr, HW

8.99

38.39

8' - 0"

117' - 4 5/8" 12' - 3 1/4"

0.00

2.36

117' - 4 5/8" 4' - 3 1/4"

1 1/2" (See

Notes)

1 5/8"

14.17

0.19

Flow (q) from Route 4

76.30 PO(8' - 0"), HW

12.02

19.25

117' - 4 5/8" 9' - 8" 0.41

117' - 4 5/8" 9' - 8"

3" (See

Notes)

3 1/4"

16.53

0.04

Flow (q) from Route 8

216.85 Tr, HW

8.34

140.56

16.95 Route 2Total(Pt)

6' - 0"

117' - 4 5/8" 13' - 1"

-2.73

4.99

111' - 1" 7' - 1"

3/4"

• • • • • Route 3 • • • • •

(See

Notes)

7/8"

11.45

0.38

Sprinkler, 18.95

5.6

E(2' - 0"), PO(4' - 0"), HW

11.40

18.95

117' - 4 5/8" 7' - 9 1/4" 0.42

117' - 4 5/8" 7' - 9 1/4"

1 1/2" (See

Notes)

1 5/8"

13.71

0.05

Flow (q) from Route 6

38.39 Tr, HW

6.05

19.44

14.13 Route 3Total(Pt)

11/9/2025 Page 2AutoSPRINK RVT v8.3.13.0 1:15:12PMMAIN COMPUTER ROOM@ M.E.P.CAD

Remote Area Name: MAIN COMPUTER ROOM

Flow added this step

Pipe Information

Node 1

Node 2

Elev 1 ft

Elev 2 ft

K-Factor

Q

Total Flow

Q

Nominal ID

Actual ID

Fittings &

Devices

Equiv.

Length ft

Length ft

Fitting ft

Total ft

C Factor or

Roughness

Pf Friction Loss

Per Unit

Pounds force per square inch

Total(Pt)

Elev(Pe)

Friction(Pf)

Notes

Fitting/Device (Equivalent Length)

Fixed Pressure Losses, when applicable, are added directly to (Pf) and shown as a negative value.

Velocity

4' - 0"

117' - 4 5/8" 4' - 11 3/8"

0.41

1.94

118' - 4" 0' - 11 3/8"

3/4"

• • • • • Route 4 • • • • •

(See

Notes)

7/8"

11.82

0.39

Sprinkler, 19.25

5.6

PO(4' - 0"), HW

11.58

19.25

14.17 Route 4Total(Pt)

6' - 0"

117' - 4 5/8" 13' - 5"

-2.73

5.21

111' - 1" 7' - 5"

3/4"

• • • • • Route 5 • • • • •

(See

Notes)

7/8"

11.65

0.39

Sprinkler, 19.12

5.6

E(2' - 0"), PO(4' - 0"), HW

11.50

19.12

117' - 4 5/8" 7' - 9 1/4" 0.43

117' - 4 5/8" 7' - 9 1/4"

1 1/2" (See

Notes)

1 5/8"

14.13

0.06

Flow (q) from Route 9

38.86 Tr, HW

6.12

19.75

14.56 Route 5Total(Pt)

2' - 0"

117' - 4 5/8" 2' - 11 3/8"

0.41

1.18

118' - 4" 0' - 11 3/8"

3/4"

• • • • • Route 6 • • • • •

(See

Notes)

7/8"

12.06

0.40

Sprinkler, 19.44

5.6

E(2' - 0"), HW

11.70

19.44

117' - 4 5/8" 4' - 3 1/2" 0.07

117' - 4 5/8" 4' - 3 1/2"

1 1/2" (See

Notes)

1 5/8"

13.65

0.0219.44 Tr, HW

3.06

13.71 Route 6Total(Pt)

4' - 0"

117' - 4 5/8" 4' - 11 3/8"

0.41

2.00

118' - 4" 0' - 11 3/8"

3/4"

• • • • • Route 7 • • • • •

(See

Notes)

7/8"

12.19

0.40

Sprinkler, 19.55

5.6

PO(4' - 0"), HW

11.76

19.55

14.60 Route 7Total(Pt)

4' - 0"

117' - 4 5/8" 4' - 11 3/8"

0.41

2.03

118' - 4" 0' - 11 3/8"

3/4"

• • • • • Route 8 • • • • •

(See

Notes)

7/8"

12.40

0.41

Sprinkler, 19.72

5.6

PO(4' - 0"), HW

11.87

19.72

8' - 0"

117' - 4 5/8" 12' - 3 1/4"

0.00

1.50

117' - 4 5/8" 4' - 3 1/4"

1 1/2" (See

Notes)

1 5/8"

14.85

0.12

Flow (q) from Route 10

59.73 PO(8' - 0"), HW

9.41

40.01

117' - 4 5/8" 9' - 8" 0.19

117' - 4 5/8" 9' - 8"

3" (See

Notes)

3 1/4"

16.35

0.02

Flow (q) from Route 11

140.56 Tr, HW

5.40

80.83

11/9/2025 Page 3AutoSPRINK RVT v8.3.13.0 1:15:12PMMAIN COMPUTER ROOM@ M.E.P.CAD

Remote Area Name: MAIN COMPUTER ROOM

Flow added this step

Pipe Information

Node 1

Node 2

Elev 1 ft

Elev 2 ft

K-Factor

Q

Total Flow

Q

Nominal ID

Actual ID

Fittings &

Devices

Equiv.

Length ft

Length ft

Fitting ft

Total ft

C Factor or

Roughness

Pf Friction Loss

Per Unit

Pounds force per square inch

Total(Pt)

Elev(Pe)

Friction(Pf)

Notes

Fitting/Device (Equivalent Length)

Fixed Pressure Losses, when applicable, are added directly to (Pf) and shown as a negative value.

Velocity

16.53 Route 8Total(Pt)

2' - 0"

117' - 4 5/8" 2' - 11 3/8"

0.41

1.21

118' - 4" 0' - 11 3/8"

3/4"

• • • • • Route 9 • • • • •

(See

Notes)

7/8"

12.43

0.41

Sprinkler, 19.75

5.6

E(2' - 0"), HW

11.88

19.75

117' - 4 5/8" 4' - 3 1/2" 0.07

117' - 4 5/8" 4' - 3 1/2"

1 1/2" (See

Notes)

1 5/8"

14.06

0.0219.75 Tr, HW

3.11

14.13 Route 9Total(Pt)

2' - 0"

117' - 4 5/8" 2' - 11 3/8"

0.41

1.24

118' - 4" 0' - 11 3/8"

3/4"

• • • • • Route 10 • • • • •

(See

Notes)

7/8"

12.66

0.42

Sprinkler, 19.92

5.6

E(2' - 0"), HW

11.99

19.92

117' - 4 5/8" 4' - 3 1/2" 0.07

117' - 4 5/8" 4' - 3 1/2"

1 1/2" (See

Notes)

1 5/8"

14.31

0.0219.92 Tr, HW

3.14

117' - 4 5/8" 8' - 1 5/8" 0.47

117' - 4 5/8" 8' - 1 5/8"

1 1/2" (See

Notes)

1 5/8"

14.37

0.06

Flow (q) from Route 14

40.01 Tr, HW

6.31

20.09

14.85 Route 10Total(Pt)

2' - 0"

117' - 4 5/8" 2' - 11 3/8"

0.41

1.24

118' - 4" 0' - 11 3/8"

3/4"

• • • • • Route 11 • • • • •

(See

Notes)

7/8"

12.74

0.42

Sprinkler, 19.99

5.6

E(2' - 0"), HW

12.03

19.99

5' - 0"

117' - 4 5/8" 8' - 4 1/8" 1.09

117' - 4 5/8" 3' - 4 1/8"

1" (See

Notes)

1"

14.40

0.1319.99 PO(5' - 0"), HW

7.42

3' - 0"

117' - 4 5/8" 3' - 7 7/8" 0.45

117' - 4 5/8" 0' - 7 7/8"

1 1/4" (See

Notes)

1 3/8"

15.48

0.12

Flow (q) from Route 12

39.98 E(3' - 0"), HW

8.58

19.99

10' - 0"

117' - 4 5/8" 19' - 8 3/4" 0.34

117' - 4 5/8" 9' - 8 3/4"

2" (See

Notes)

2 1/8"

15.93

0.0239.98 2E(5' - 0"), HW

3.82

11/9/2025 Page 4AutoSPRINK RVT v8.3.13.0 1:15:12PMMAIN COMPUTER ROOM@ M.E.P.CAD

Remote Area Name: MAIN COMPUTER ROOM

Flow added this step

Pipe Information

Node 1

Node 2

Elev 1 ft

Elev 2 ft

K-Factor

Q

Total Flow

Q

Nominal ID

Actual ID

Fittings &

Devices

Equiv.

Length ft

Length ft

Fitting ft

Total ft

C Factor or

Roughness

Pf Friction Loss

Per Unit

Pounds force per square inch

Total(Pt)

Elev(Pe)

Friction(Pf)

Notes

Fitting/Device (Equivalent Length)

Fixed Pressure Losses, when applicable, are added directly to (Pf) and shown as a negative value.

Velocity

117' - 4 5/8" 5' - 7 1/4" 0.01

117' - 4 5/8" 5' - 7 1/4"

3" (See

Notes)

3 1/4"

16.27

0.0039.98 Tr, HW

1.54

117' - 4 5/8" 9' - 8" 0.07

117' - 4 5/8" 9' - 8"

3" (See

Notes)

3 1/4"

16.28

0.01

Flow (q) from Route 13

80.83 Tr, HW

3.11

40.84

16.35 Route 11Total(Pt)

2' - 0"

117' - 4 5/8" 2' - 11 3/8"

0.41

1.24

118' - 4" 0' - 11 3/8"

3/4"

• • • • • Route 12 • • • • •

(See

Notes)

7/8"

12.75

0.42

Sprinkler, 19.99

5.6

E(2' - 0"), HW

12.03

19.99

5' - 0"

117' - 4 5/8" 8' - 3 1/2" 1.08

117' - 4 5/8" 3' - 3 1/2"

1" (See

Notes)

1"

14.40

0.1319.99 PO(5' - 0"), HW

7.42

15.48 Route 12Total(Pt)

4' - 0"

117' - 4 5/8" 4' - 11 3/8"

0.41

2.12

118' - 4" 0' - 11 3/8"

3/4"

• • • • • Route 13 • • • • •

(See

Notes)

7/8"

13.00

0.43

Sprinkler, 20.19

5.6

PO(4' - 0"), HW

12.15

20.19

8' - 0"

117' - 4 5/8" 12' - 3 1/4"

0.00

0.74

117' - 4 5/8" 4' - 3 1/4"

1 1/2" (See

Notes)

1 5/8"

15.54

0.06

Flow (q) from Route 15

40.84 PO(8' - 0"), HW

6.44

20.65

16.28 Route 13Total(Pt)

2' - 0"

117' - 4 5/8" 8' - 3 5/8"

-2.73

3.53

111' - 1" 6' - 3 5/8"

3/4"

• • • • • Route 14 • • • • •

(See

Notes)

7/8"

12.87

0.43

Sprinkler, 20.09

5.6

E(2' - 0"), HW

12.09

20.09

5' - 0"

117' - 4 5/8" 5' - 4 7/8"

0.00

0.71

117' - 4 5/8" 0' - 4 7/8"

1" (See

Notes)

1"

13.66

0.1320.09 PO(5' - 0"), HW

7.46

14.37 Route 14Total(Pt)

2' - 0"

117' - 4 5/8" 2' - 11 3/8"

0.41

1.32

118' - 4" 0' - 11 3/8"

3/4"

• • • • • Route 15 • • • • •

(See

Notes)

7/8"

13.60

0.45

Sprinkler, 20.65

5.6

E(2' - 0"), HW

12.42

20.65

11/9/2025 Page 5AutoSPRINK RVT v8.3.13.0 1:15:12PMMAIN COMPUTER ROOM@ M.E.P.CAD

Remote Area Name: MAIN COMPUTER ROOM

Flow added this step

Pipe Information

Node 1

Node 2

Elev 1 ft

Elev 2 ft

K-Factor

Q

Total Flow

Q

Nominal ID

Actual ID

Fittings &

Devices

Equiv.

Length ft

Length ft

Fitting ft

Total ft

C Factor or

Roughness

Pf Friction Loss

Per Unit

Pounds force per square inch

Total(Pt)

Elev(Pe)

Friction(Pf)

Notes

Fitting/Device (Equivalent Length)

Fixed Pressure Losses, when applicable, are added directly to (Pf) and shown as a negative value.

Velocity

117' - 4 5/8" 12' - 5 1/8" 0.21

117' - 4 5/8" 12' - 5 1/8"

1 1/2" (See

Notes)

1 5/8"

15.33

0.0220.65 Tr, HW

3.25

15.54 Route 15Total(Pt)

4' - 0"

117' - 4 5/8" 4' - 11 3/8"

0.41

2.30

118' - 4" 0' - 11 3/8"

3/4"

• • • • • Route 16 • • • • •

(See

Notes)

7/8"

14.16

0.46

Sprinkler, 21.07

5.6

PO(4' - 0"), HW

12.68

21.07

8' - 0"

117' - 4 5/8" 12' - 3 1/4"

0.00

0.80

117' - 4 5/8" 4' - 3 1/4"

1 1/2" (See

Notes)

1 5/8"

16.87

0.07

Flow (q) from Route 17

42.61 PO(8' - 0"), HW

6.72

21.54

17.67 Route 16Total(Pt)

2' - 0"

117' - 4 5/8" 2' - 11 3/8"

0.41

1.43

118' - 4" 0' - 11 3/8"

3/4"

• • • • • Route 17 • • • • •

(See

Notes)

7/8"

14.80

0.48

Sprinkler, 21.54

5.6

E(2' - 0"), HW

12.96

21.54

117' - 4 5/8" 12' - 5 1/8" 0.23

117' - 4 5/8" 12' - 5 1/8"

1 1/2" (See

Notes)

1 5/8"

16.64

0.0221.54 Tr, HW

3.39

16.87 Route 17Total(Pt)

11/9/2025 Page 6AutoSPRINK RVT v8.3.13.0 1:15:12PMMAIN COMPUTER ROOM@ M.E.P.CAD

Remote Area Name: MAIN COMPUTER ROOM

1.51

Notes Legend

BFP Backflow Preventer BV Butterfly Valve CV Check Valve

E 90° Elbow HW Hazen-Williams PO Pipe Outlet red Reducer/Adapter S Supply Spr Sprinkler

Tr Tee run

4.87

1.33

1.16

0.713

Equivalent Pipe Lengths of Valves and Fittings (C=120 only)

Actual Inside Diameter

Schedule 40 Steel Pipe Inside Diameter = Factor

C Value Multiplier

Value Of C

Multiplying Factor

11/9/2025 Page 7AutoSPRINK RVT v8.3.13.0 1:15:12PMMAIN COMPUTER ROOM@ M.E.P.CAD

Electronic Health Records Modernization (EHRM) Infrastructure Upgrades – Togus, ME VA Project No. 402-22-700

Mechanical - MCR CFD Analysis

EHRM Infrastructure Upgrades

Togus VA Medical Center Togus, Maine

Project Number 402-22-700

November 10, 2025

CFD Analysis

GDM AE, Inc.

1308 NE 134th Street, Suite A

Vancouver, WA 98685

22-055 CFD Analysis – 100% Construction Documents

2025/11/10 Page 1 of 24

MECHANICAL DESIGN - MCR

The HVAC design for the MCR utilizes a pair of downflow CRAC units, connected to a hot aisle containment system by overhead return ductwork.

The CRAC unit configuration included in the current design and calculations meet the N+1 minimum redundancy required by DCIE/OIT. Each unit is capable of handling the required cooling load on its own, with the other unit in standby or shut down.

The CRAC units can operate concurrently at reduced airflow and compressor settings for optimized energy efficiency, or can operate with fewer units at higher loading to meet the required capacity.

Staging and fail-over functionality is handled by the CRAC system integrated controls. Both CRAC units are networked together to enable this control functionality.

The CRAC units included in the design are Liebert DSE125 indoor units with nominal sensible cooling capacity of 125kW each. Heat rejection from the CRAC units is accomplished using dedicated outdoor condensing units. These systems will also include a refrigerant-side economizer for increased efficiency.

Arranged in a hot-aisle configuration, the CRAC units draw hot supply air from the containment area and flood the MCR with cooled supply air. This configuration is proposed for this project as it offers greater occupant comfort compared to a cold-aisle containment system which results in elevated temperatures throughout the rest of the room, and also may mitigate potential hot-spots that could otherwise occur due to the nature of the in-row CRAC units.

ANALYSIS CONDITIONS

CFD analysis performed using Autodesk CFD 2019 software.

The following design conditions are utilized in the CFD model for this facility:

• Exact loads for each data cabinet, and the distribution of loads within each cabinet, are unknown and may change over time. The CFD analysis utilizes the following heat loads (as specified in the

VA CFD Guidelines and ISTS v3.1) for each cabinet/equipment type:

o SD cabinets: 5.0kW each o HD cabinets: 10.0kW each o HDA cabinets: 2.8kW each o MDA cabinets: 3.5kW each o UPS units: 5kw per active section (10.0kw total)

• Based on the telecommunications documents, the total loads included in the CFD model for the

MCR include 86.6kW in data cabinets (SD, HDA, & MDA types) as well as 10kW estimated load for the UPS units for a total design heat load of 96.6kW. The actual installed kW load following

2025/11/10 Page 2 of 24 this project will be less than the calculated load in the CFD model. The ultimate data cabinet load in the MCR per the DCIE standard small data center layout is 79.6kW.

• Airflows for each cabinet/equipment type utilized are modeled as follows:

o SD cabinets: 1040 cfm each o HDA cabinets: 585 cfm each o MDA cabinets: 725 cfm each

• (2) CRAC units provide data center conditioning for the main data cabinet set in the MCR. The

CFD model reflects (1) CRAC units operating at 100% airflow (18,000 cfm), with the other unit being inactive (redundant/standby or failed).

• The UPS units are nominally 100kW rated each, with a nominal maximum heat output of 10kW.

Sample manufacturer’s data indicates that actual heat output from the UPS units will be much lower (example - 3.1kW for Schneider Galaxy VS 100kW).

DESIGN GOALS

The objectives for the MCR cooling system are to achieve the following conditions:

• Supply air temperature setpoints between 64-81°F.

• Inlet temperatures at data equipment between 72-80.6°F.

• Rack/cabinet exhaust temperatures below 106°F (with up to 108°F acceptable at 1-2 racks).

• Minimize cold and hot spots near data equipment.

• Maintain room ambient conditions below 85°F for human comfort. Note that required rack inlet temperatures are lower than this temperature (supply air temperatures between 64-81°F).

• Maintain suitable temperatures for UPS unit operation, within manufacturer typical ambient temperature range of 41-104°F.

2025/11/10 Page 3 of 24

MCR LAYOUT

MCR DATA CABINET INFORMATION

Label Type Modeled KW Heat Load

F5 HDA 2.8

G5 SD (Oracle FDS) 5.0 I5 SD (Oracle FDS) 5.0

J5 SD 5.0

K5 SD 5.0

L5 SD 5.0

M5 SD 5.0

N5 SD 5.0

O5 SD 5.0

P5 SD 5.0

Q5 SD 5.0

R5 SD 5.0

S5 SD 5.0

T5 HDA 2.8

G10 MDA 3.5

I10 MDA 3.5

K10 MDA 3.5

L10 MDA 3.5

N10 MDA 3.5

P10 MDA 3.5

MCR-UPS-A UPS 5.0

MCR-UPS-B UPS 5.0

Total Load 96.6

2025/11/10 Page 4 of 24

VIEW LEGENDS - MCR

The views shown for each scenario are cut at the following locations.

Plane 1 – Horizontal orientation, approximately 48” above raised floor

Plane 2 – Vertical (north-south) orientation, through MCR-CRAC-1

Plane 3 – Vertical (north-south) orientation, through MCR-CRAC-2

2025/11/10 Page 5 of 24

MCR - SCENARIO 1A

Scenario conditions: 65°F supply air, CRAC unit MCR-CRAC-1 on, MCR-CRAC-2 off.

Figure 1a.1 – Plane 1

Figure 1a.2 – Plane 2

2025/11/10 Page 6 of 24

Figure 1a.3 – Plane 3

2025/11/10 Page 7 of 24

MCR - SCENARIO 1B

Scenario conditions: 65°F supply air, CRAC unit MCR-CRAC-2 on, MCR-CRAC-1 off.

Figure 1b.1 – Plane 1

Figure 1b.2 – Plane 2

2025/11/10 Page 8 of 24

Figure 1b.3 – Plane 3

2025/11/10 Page 9 of 24

MCR - SCENARIO 2A

Scenario conditions: 70°F supply air, CRAC unit MCR-CRAC-1 on, MCR-CRAC-2 off.

Figure 2a.1 – Plane 1

Figure 2a.2 – Plane 2

2025/11/10 Page 10 of 24

Figure 2a.3 – Plane 3

2025/11/10 Page 11 of 24

MCR - SCENARIO 2B

Scenario conditions: 70°F supply air, CRAC unit MCR-CRAC-2 on, MCR-CRAC-1 off.

Figure 2b.1 – Plane 1

Figure 2b.2 – Plane 2

2025/11/10 Page 12 of 24

Figure 2b.3 – Plane 3

2025/11/10 Page 13 of 24

MCR - SCENARIO 3A

Scenario conditions: 75°F supply air, CRAC unit MCR-CRAC-1 on, MCR-CRAC-2 off.

Figure 3a.1 – Plane 1

Figure 3a.2 – Plane 2

2025/11/10 Page 14 of 24

Figure 3a.3 – Plane 3

2025/11/10 Page 15 of 24

MCR - SCENARIO 3B

Scenario conditions: 75°F supply air, CRAC unit MCR-CRAC-2 on, MCR-CRAC-1 off.

Figure 3b.1 – Plane 1

Figure 3b.2 – Plane 2

2025/11/10 Page 16 of 24

Figure 3b.3 – Plane 3

2025/11/10 Page 17 of 24

MCR - SCENARIO 4A

Scenario conditions: 80°F supply air, CRAC unit MCR-CRAC-1 on, MCR-CRAC-2 off.

Figure 4a.1 – Plane 1

Figure 4a.2 – Plane 2

2025/11/10 Page 18 of 24

Figure 4a.3 – Plane 3

2025/11/10 Page 19 of 24

MCR - SCENARIO 4B

Scenario conditions: 80°F supply air, CRAC unit MCR-CRAC-2 on, MCR-CRAC-1 off.

Figure 4b.1 – Plane 1

Figure 4b.2 – Plane 2

2025/11/10 Page 20 of 24

Figure 4b.3 – Plane 3

2025/11/10 Page 21 of 24

MCR - TEMPERATURE DATA

Temperature data for each modeled scenario is provided on the following pages.

Inlet temperature points are located at the inlet side of the data cabinet, centered on the face of the cabinet, at approximately 48” above floor level.

Outlet temperature points are located at the outlet side of the data cabinet, centered on the face of the cabinet, at approximately 48” above floor level.

2025/11/10 Page 22 of 24

2025/11/10 Page 23 of 24

2025/11/10 Page 24 of 24

CONCLUSIONS - MCR

1. The model demonstrates that a hot aisle configuration with CRAC units located as shown is suitable for meeting the requirements for VA data center conditioning.

2. Based on temperature data from the modeled scenarios at the maximum design cabinet loading, the ideal supply air temperature setpoint for the MCR CRAC systems is 72-78°F as demonstrated in Scenario 3.

3. As demonstrated in Scenarios 1 & 2, a setpoint below approximately 72°F will likely result in data cabinet inlet air temperatures below 72°F.

4. As demonstrated in Scenario 4, a setpoint above approximately 78°F will likely result in data cabinet inlet air temperatures above 80.6°F.

5. As demonstrated in all included scenarios, none of the modeled setpoints result in cabinet outlet air temperatures above 106°F.

6. As demonstrated in all included scenarios, none of the modeled setpoints result in ambient temperatures at the UPS unit locations outside of manufacturer’s typical temperature recommendations (41-104°F).

7. At the design data equipment load of 96.6kW (including data cabinets and UPS units), the proposed arrangement of (2) 125kW nominal capacity CRAC units appear to be capable of maintaining space conditions within VA OIT standards while meeting N+1 redundancy. Note that this calculation includes data cabinet loads per the VA CFD Manual which is higher than the VA small data center template ultimate load of 79.6kW.

8. Future data equipment changes will need to be modeled to verify load distribution and any system adjustments or upgrades that might be required.

100% Construction Documents Reissued 02-18-2026

Electronic Health Records Modernization (EHRM) Infrastructure Upgrades – Togus, ME

Mechanical - MCR Fuel Tank Sizing

By Chkd. of

A 100% Load Fuel Consumption

B Integrated Fuel Tank - Useable Capacity

C Hours required per RFI #13 response

D Useable Gallons Required in System

(C * D)

E Gallons Required in Tank

(D - B)

F Safety Factor

G Gallons for Stand-by Tank Sizing

(E * F)

H Gallons from Ullage assumed: 90%

SPACE ABOVE MAX FILL

I Gallons from Drop Tube assumed: 10%

SPACE BELOW SUCTION TUBE

J Gallons for Generator Testing assumed: 10%

VOLUME USED FOR TESTING NOT TO IMPACT VOLUME FOR TANK CAPACITY

K NOMINAL CAPACITY FOR TANK

267.2 gal

267.2 gal

3,473.1 gal

2,671.6 gal

SIZE OF ABOVE GROUND FUEL TANK

674.4 gal

96 hr

2,683.1 gal

2,008.7 gal

33%

105.8 L/hr

27.9 gal/hr

2,553.0 L

267.2 gal

ADR

TOGUS EHRM22-055 Job Name

Subject

Job#

Date

Sheet

FUEL TANK CALCULATIONS 11/10/2025

Electronic Health Records Modernization (EHRM) Infrastructure Upgrades – Togus, ME VA Project No. 402-22-700

Mechanical - MCR Heat Load

Dedicated Outdoor Air System (DOAS) Sizing Summary for MCR - OFFICE Project Name: 22-055 TOGUS 95% 08/01/2023 Prepared by: GDM-AE 10:36AM

Air System Information Air System Name MCR - OFFICE Equipment Class TERM Air System Type VRF

Number of zones 6 Floor Area 2795.0 ft² Location Portland, Maine

Sizing Calculation Information Calculation Months Jan to Dec Sizing Data Calculated

Zone CFM Sizing Sum of space airflow rates Space CFM Sizing Individual peak space loads

Cooling Coil Sizing Data Total coil load 0.8 Tons Total coil load 9.5 MBH Total coil load 344.6 CFM/Ton Sensible coil load 7.3 MBH Coil CFM at Jul 1500 274 CFM Max coil CFM 274 CFM Sensible heat ratio 0.766 Water flow @ 10.0 °F rise N/A

Load occurs at Jul 1500

OA DB / WB 86.0 / 71.0 °F

Entering DB / WB 86.0 / 71.0 °F Leaving DB / WB 61.2 / 60.6 °F Bypass Factor 0.100

Heating Coil Sizing Data Max coil load 21.5 MBH Coil CFM at Des Htg 274 CFM Max coil CFM 274 CFM Water flow @ 20.0 °F drop N/A

Load occurs at Des Htg Ent. DB / Lvg DB -3.0 / 70.0 °F

Humidifier Sizing Data Max steam flow at Des Htg 5.29 lb/hr Airflow Rate 274 CFM

Air mass flow 1228.25 lb/hr Moisture gain .00431 lb/lb

Ventilation Fan Sizing Data Actual max CFM 274 CFM Standard CFM 273 CFM Actual max CFM/ft² 0.10 CFM/ft²

Fan motor BHP 0.00 BHP Fan motor kW 0.00 kW Fan static 0.00 in wg

Outdoor Ventilation Air Data Design airflow CFM 274 CFM CFM/ft² 0.10 CFM/ft²

CFM/person 54.71 CFM/person

Hourly Analysis Program 5.11 Page 1 of 25

Zone Sizing Summary for MCR - OFFICE

Prepared by: GDM-AE 10:36AM

Air System Information Air System Name MCR - OFFICE Equipment Class TERM Air System Type VRF

Number of zones 6 Floor Area 2795.0 ft² Location Portland, Maine

Sizing Calculation Information Calculation Months Jan to Dec Sizing Data Calculated

Zone CFM Sizing Sum of space airflow rates Space CFM Sizing Individual peak space loads

Terminal Unit Sizing Data - Cooling

Total Sens Coil Coil Water Time

Coil Coil Entering Leaving Flow of

Load Load DB / WB DB / WB @ 10.0 °F Peak Coil Zone

Zone Name (MBH) (MBH) (°F) (°F) (gpm) Load CFM/ft²

Ship / Recieve 3.5 3.3 74.8 / 65.1 61.1 / 60.2 - Aug 1400 0.61

Support 5.9 5.7 75.1 / 65.2 61.1 / 60.2 - Jul 1700 0.54

Working 4.5 4.3 75.3 / 64.5 59.8 / 58.8 - Jul 1600 1.26

MCR 355.2 353.7 76.0 / 63.9 59.0 / 57.8 - Jul 1600 16.08

Entrance B 31.0 30.8 75.9 / 63.9 58.9 / 57.8 - Jul 1600 10.54

Entrance A 31.0 30.8 75.8 / 63.9 58.9 / 57.7 - Aug 1500 10.02

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Heating Htg Coil

Heating Coil Water Fan OA Vent

Coil Ent/Lvg Flow Design Fan Fan Design

Load DB @20.0 °F Airflow Motor Motor Airflow

Zone Name (MBH) (°F) (gpm) (CFM) (BHP) (kW) (CFM)

Ship / Recieve 4.4 69.1 / 87.1 - 225 0.000 0.000 45

Support 6.6 69.4 / 85.5 - 377 0.000 0.000 72

Working 4.1 69.2 / 83.9 - 256 0.000 0.000 30

MCR 16.1 69.7 / 70.5 - 19301 0.000 0.000 103

Entrance B 5.8 70.4 / 73.6 - 1687 0.000 0.000 12

Entrance A 4.1 69.9 / 72.1 - 1683 0.000 0.000 13

VRF Outdoor Unit Sizing Data

Cooling

[MBH]

Cooling [Tons]

Heating

[MBH]

Peak Coincident Indoor Unit Loads 430.8 35.9 41.0

Estimated Piping / Line Losses 0.0 0.0 0.0

Total Required ODU Capacity 430.8 35.9 41.0

Note: VRF piping / line losses are based on typical loss factors for this class of equipment. Actual line loss varies widely from one product to another.

Therefore, when selecting equipment it is critical to consult manufacturer's guidance to utilize actual line loss data.

Zone Peak Sensible Loads

Zone Zone Zone

Cooling Time of Heating Floor

Sensible Peak Sensible Load Area

Zone Name (MBH) Cooling Load (MBH) (ft²)

Ship / Recieve 3.8 Jul 1400 4.5 372.0

Support 6.6 Jul 1700 6.5 692.0

Working 4.6 Aug 1600 4.1 203.0

MCR 353.6 Jul 1700 16.0 1200.0

Entrance B 30.9 Jul 1700 5.7 160.0

Entrance A 30.8 Aug 1500 4.1 168.0

Hourly Analysis Program 5.11 Page 2 of 25

Zone Sizing Summary for MCR - OFFICE

Prepared by: GDM-AE 10:36AM

Space Loads and Airflows

Zone Name / Space Name Mult.

Cooling Sensible

(MBH)

Time of Peak

Sensible Load

Air Flow

(CFM)

Heating Load

(MBH)

Floor Area (ft²)

Space CFM/ft²

Ship / Recieve

MCR - RECEIVING - 101 1 0.8 Jul 1500 59 1.6 87.0 0.68

MCR - UNBOX - 102 1 1.1 Jul 1500 60 0.7 143.0 0.42

MCR - SUPPLIES - 103 1 0.7 Aug 1500 41 0.7 89.0 0.46

MCR - VESTIBULE - 113 1 1.2 Jul 0900 66 1.5 53.0 1.24

Support

MCR - HAC - 106 1 0.3 Jul 1400 14 0.1 36.0 0.40

MCR - MECH - 104 1 1.1 Aug 1700 72 1.9 105.0 0.69

MCR - ELEC - 105 1 2.7 Jul 1800 147 3.1 203.0 0.72

MCR - CLEAN AGENT - 107 1 0.9 Jul 1600 48 0.8 78.0 0.61

MCR - TOILET - 112 1 0.5 Jul 1400 26 0.1 46.0 0.58

MCR - CORRIDOR 1 1.3 Jul 1400 69 0.5 224.0 0.31

Working

MCR - WORK STATION - 110 1 2.7 Jul 1500 149 1.2 134.0 1.11

MCR - STORAGE - 109 1 1.9 Aug 1600 108 2.9 69.0 1.56

MCR

MCR - DATA CENTER - 111 1 353.6 Jul 1700 19301 16.0 1200.0 16.08

Entrance B

MCR - ENTRANCE B - 112 1 30.9 Jul 1700 1687 5.7 160.0 10.54

Entrance A

MCR - ENTRANCE A - 100 1 30.8 Aug 1500 1683 4.1 168.0 10.02

Hourly Analysis Program 5.11 Page 3 of 25

Ventilation Sizing Summary for MCR - OFFICE

Prepared by: GDM-AE 10:36AM

1. Summary Ventilation Sizing Method ASHRAE Std 62.1-2013 Design Condition Heating operation

Zone Name

Zone Outdoor

Airflow

(CFM)

Uncorrected Outdoor Air

Intake

(CFM)

Ventilation Efficiency

Outdoor Air Intake

(CFM)

(Voz) (Vou) (Ev) (Vot)

Ship / Recieve 36 0.802 45

Support 54 0.752 72

Working 27 0.912 30

MCR 103 1.000 103

Entrance B 12 1.000 12

Entrance A 13 1.000 13

System Total 274

Note: For terminal systems, Standard 62.1 considers each terminal unit to be a "ventilation system". Standard 62.1 calculations are performed separately for each terminal unit zone.

Outdoor air intake flow rates for all terminal zones are summed to determine the total system outdoor air flow rate.

2. Space Ventilation Analysis

2.1 Zone: Ship / Recieve

Supply Air

(CFM)

Space Floor Area (ft²)

Area Outdoor Air Rate

(CFM/ft²)

Time Averaged

Occupancy (Occupants)

People Outdoor Air

Rate (CFM/person)

Air Distribution

Effectiveness

Space Outdoor Air

(CFM)

Breathing Zone

Outdoor Air

(CFM)

Space Ventilation Efficiency

Zone Name / Space Name Mult. (Vpz) (Az) (Ra) (Pz) (Rp) (Ez) (Voz) (Vbz) (Evz)

Ship / Recieve

MCR - RECEIVING - 101 1 59 87.0 0.12 0.0 10.00 0.8 13 10 0.939

MCR - UNBOX - 102 1 60 143.0 0.12 0.0 7.50 0.8 21 17 0.802

MCR - SUPPLIES - 103 1 41 89.0 0.06 0.0 5.00 0.8 7 5 0.997

MCR - VESTIBULE - 113 1 66 53.0 0.06 0.0 5.00 0.8 4 3 1.100

Totals (incl. Space Multipliers) 225 36 0.802

Hourly Analysis Program 5.11 Page 4 of 25

Prepared by: GDM-AE 10:36AM

2.2 Zone: Support

Space Floor Area (ft²)

Area Outdoor Air Rate

(CFM/ft²)

Time Averaged

Occupancy (Occupants)

People Outdoor Air

Rate (CFM/person)

Air Distribution

Effectiveness

Space Outdoor Air

(CFM)

Breathing Zone

Outdoor Air

(CFM)

Space Ventilation Efficiency

Zone Name / Space Name Mult. (Vpz) (Az) (Ra) (Pz) (Rp) (Ez) (Voz) (Vbz) (Evz)

Support

MCR - HAC - 106 1 14 36.0 0.12 0.0 5.00 0.8 5 4 0.766

MCR - MECH - 104 1 72 105.0 0.06 0.0 5.00 0.8 8 6 1.034

MCR - ELEC - 105 1 147 203.0 0.06 0.0 5.00 0.8 15 12 1.039

MCR - CLEAN AGENT - 107 1 48 78.0 0.12 0.0 5.00 0.8 12 9 0.898

MCR - TOILET - 112 1 26 46.0 0.18 0.0 10.00 0.8 10 8 0.752

MCR - CORRIDOR 1 69 224.0 0.06 0.0 0.00 0.8 17 13 0.900

Totals (incl. Space Multipliers) 377 54 0.752

2.3 Zone: Working

Space Floor Area (ft²)

Area Outdoor Air Rate

(CFM/ft²)

Time Averaged

Occupancy (Occupants)

People Outdoor Air

Rate (CFM/person)

Air Distribution

Effectiveness

Space Outdoor Air

(CFM)

Breathing Zone

Outdoor Air

(CFM)

Space Ventilation Efficiency

Zone Name / Space Name Mult. (Vpz) (Az) (Ra) (Pz) (Rp) (Ez) (Voz) (Vbz) (Evz)

Working

MCR - WORK STATION - 110 1 149 134.0 0.06 3.0 5.00 0.8 29 23 0.912

MCR - STORAGE - 109 1 108 69.0 0.06 0.0 5.00 0.8 5 4 1.058

Totals (incl. Space Multipliers) 256 27 0.912

2.4 Zone: MCR

Space Floor Area (ft²)

Area Outdoor Air Rate

(CFM/ft²)

Time Averaged

Occupancy (Occupants)

People Outdoor Air

Rate (CFM/person)

Air Distribution

Effectiveness

Space Outdoor Air

(CFM)

Breathing Zone

Outdoor Air

(CFM)

Space Ventilation Efficiency

Zone Name / Space Name Mult. (Vpz) (Az) (Ra) (Pz) (Rp) (Ez) (Voz) (Vbz) (Evz)

MCR

MCR - DATA CENTER - 111 1 19301 1200.0 0.06 2.0 5.00 0.8 103 82 1.000

Totals (incl. Space Multipliers) 19301 82 1.000

2.5 Zone: Entrance B

Space Floor Area (ft²)

Area Outdoor Air Rate

(CFM/ft²)

Time Averaged

Occupancy (Occupants)

People Outdoor Air

Rate (CFM/person)

Air Distribution

Effectiveness

Space Outdoor Air

(CFM)

Breathing Zone

Outdoor Air

(CFM)

Space Ventilation Efficiency

Zone Name / Space Name Mult. (Vpz) (Az) (Ra) (Pz) (Rp) (Ez) (Voz) (Vbz) (Evz)

Entrance B

MCR - ENTRANCE B - 112 1 1687 160.0 0.06 0.0 5.00 0.8 12 10 1.000

Totals (incl. Space Multipliers) 1687 10 1.000

Hourly Analysis Program 5.11 Page 5 of 25

Prepared by: GDM-AE 10:36AM

2.6 Zone: Entrance A

Space Floor Area (ft²)

Area Outdoor Air Rate

(CFM/ft²)

Time Averaged

Occupancy (Occupants)

People Outdoor Air

Rate (CFM/person)

Air Distribution

Effectiveness

Space Outdoor Air

(CFM)

Breathing Zone

Outdoor Air

(CFM)

Space Ventilation Efficiency

Zone Name / Space Name Mult. (Vpz) (Az) (Ra) (Pz) (Rp) (Ez) (Voz) (Vbz) (Evz)

Entrance A

MCR - ENTRANCE A - 100 1 1683 168.0 0.06 0.0 5.00 0.8 13 10 1.000

Totals (incl. Space Multipliers) 1683 10 1.000

Hourly Analysis Program 5.11 Page 6 of 25

Air System Design Load Summary for MCR - OFFICE

Prepared by: GDM-AE 10:36AM

DESIGN COOLING DESIGN HEATING

COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG

COOLING OA DB / WB 85.4 °F / 70.8 °F HEATING OA DB / WB -3.0 °F / -4.3 °F

Sensible Latent Sensible Latent

ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)

Window & Skylight Solar Loads 4 ft² 103 - 4 ft² - -

Wall Transmission 4745 ft² 4854 - 4745 ft² 27713 -

Roof Transmission 2858 ft² 2187 - 2858 ft² 6676 -

Window Transmission 4 ft² 13 - 4 ft² 123 -

Skylight Transmission 0 ft² 0 - 0 ft² 0 -

Door Loads 195 ft² 3482 - 195 ft² 6506 -

Floor Transmission 2693 ft² 0 - 2693 ft² 0 -

Partitions 0 ft² 0 - 0 ft² 0 -

Ceiling 0 ft² 0 - 0 ft² 0 -

Overhead Lighting 3395 W 10607 - 0 0 -

Task Lighting 0 W 0 - 0 0 -

Electric Equipment 19950 W 67851 - 0 0 -

People 5 1043 1025 0 0 0

Infiltration - 0 0 - 0 0

Miscellaneous - 339849 0 - 0 0

Safety Factor 0% / 0% 0 0 0% 0 0

>> Total Zone Loads - 429990 1025 - 41019 0

Zone Conditioning - 430194 1025 - 41119 0

Plenum Wall Load 0% 0 - 0 0 -

Plenum Roof Load 0% 0 - 0 0 -

Plenum Lighting Load 0% 0 - 0 0 -

Exhaust Fan Load 274 CFM 0 - 274 CFM 0 -

Ventilation Load 274 CFM 2759 3041 274 CFM 21361 5584

Ventilation Fan Load 274 CFM 0 - 274 CFM 0 -

Space Fan Coil Fans - 0 - - 0 -

Duct Heat Gain / Loss 0% 0 - 0% 0 -

>> Total System Loads - 432952 4066 - 62481 5584

Cooling Coil - 7134 2227 - 0 0

Heating Coil - -2583 - - 21519 -

Terminal Unit Cooling - 428401 2362 - 0 0

Terminal Unit Heating - 0 - - 40953 -

Humidification Load - - 0 - - 5584

>> Total Conditioning - 432952 4589 - 62472 5584

Key: Positive values are clg loads Positive values are htg loads

Negative values are htg loads Negative values are clg loads

Hourly Analysis Program 5.11 Page 7 of 25

Zone Design Load Summary for MCR - OFFICE

Prepared by: GDM-AE 10:36AM

Ship / Recieve DESIGN COOLING DESIGN HEATING

COOLING DATA AT Jul 1400 HEATING DATA AT DES HTG

COOLING OA DB / WB 85.4 °F / 70.8 °F HEATING OA DB / WB -3.0 °F / -4.3 °F

OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F

Sensible Latent Sensible Latent

ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)

Window & Skylight Solar Loads 0 ft² 0 - 0 ft² - -

Wall Transmission 315 ft² 293 - 315 ft² 1840 -

Roof Transmission 376 ft² 351 - 376 ft² 878 -

Window Transmission 0 ft² 0 - 0 ft² 0 -

Skylight Transmission 0 ft² 0 - 0 ft² 0 -

Door Loads 111 ft² 774 - 111 ft² 1785 -

Floor Transmission 364 ft² 0 - 364 ft² 0 -

Partitions 0 ft² 0 - 0 ft² 0 -

Ceiling 0 ft² 0 - 0 ft² 0 -

Overhead Lighting 372 W 1147 - 0 0 -

Task Lighting 0 W 0 - 0 0 -

Electric Equipment 372 W 1222 - 0 0 -

People 0 0 0 0 0 0

Infiltration - 0 0 - 0 0

Miscellaneous - 0 0 - 0 0

Safety Factor 0% / 0% 0 0 0% 0 0

>> Total Zone Loads - 3788 0 - 4503 0

Support DESIGN COOLING DESIGN HEATING

COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG

COOLING OA DB / WB 84.1 °F / 70.5 °F HEATING OA DB / WB -3.0 °F / -4.3 °F

OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F

Sensible Latent Sensible Latent

ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)

Window & Skylight Solar Loads 0 ft² 0 - 0 ft² - -

Wall Transmission 822 ft² 968 - 822 ft² 4800 -

Roof Transmission 744 ft² 451 - 744 ft² 1738 -

Window Transmission 0 ft² 0 - 0 ft² 0 -

Skylight Transmission 0 ft² 0 - 0 ft² 0 -

Door Loads 0 ft² 0 - 0 ft² 0 -

Floor Transmission 602 ft² 0 - 602 ft² 0 -

Partitions 0 ft² 0 - 0 ft² 0 -

Ceiling 0 ft² 0 - 0 ft² 0 -

Overhead Lighting 692 W 2175 - 0 0 -

Task Lighting 0 W 0 - 0 0 -

Electric Equipment 907 W 2986 - 0 0 -

People 0 0 0 0 0 0

Infiltration - 0 0 - 0 0

Miscellaneous - 0 0 - 0 0

Safety Factor 0% / 0% 0 0 0% 0 0

>> Total Zone Loads - 6580 0 - 6538 0

Hourly Analysis Program 5.11 Page 8 of 25

Prepared by: GDM-AE 10:36AM

Working DESIGN COOLING DESIGN HEATING

COOLING DATA AT Aug 1600 HEATING DATA AT DES HTG

COOLING OA DB / WB 85.4 °F / 70.8 °F HEATING OA DB / WB -3.0 °F / -4.3 °F

OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F

Sensible Latent Sensible Latent

ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)

Window & Skylight Solar Loads 4 ft² 93 - 4 ft² - -

Wall Transmission 403 ft² 453 - 403 ft² 2356 -

Roof Transmission 210 ft² 140 - 210 ft² 491 -

Window Transmission 4 ft² 13 - 4 ft² 123 -

Skylight Transmission 0 ft² 0 - 0 ft² 0 -

Door Loads 21 ft² 1077 - 21 ft² 1180 -

Floor Transmission 199 ft² 0 - 199 ft² 0 -

Partitions 0 ft² 0 - 0 ft² 0 -

Ceiling 0 ft² 0 - 0 ft² 0 -

Overhead Lighting 203 W 634 - 0 0 -

Task Lighting 0 W 0 - 0 0 -

Electric Equipment 471 W 1547 - 0 0 -

People 3 626 615 0 0 0

Infiltration - 0 0 - 0 0

Miscellaneous - 0 0 - 0 0

Safety Factor 0% / 0% 0 0 0% 0 0

>> Total Zone Loads - 4582 615 - 4149 0

MCR DESIGN COOLING DESIGN HEATING

COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG

COOLING OA DB / WB 84.1 °F / 70.5 °F HEATING OA DB / WB -3.0 °F / -4.3 °F

OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F

Sensible Latent Sensible Latent

ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)

Window & Skylight Solar Loads 0 ft² 0 - 0 ft² - -

Wall Transmission 2064 ft² 2443 - 2064 ft² 12054 -

Roof Transmission 1200 ft² 728 - 1200 ft² 2803 -

Window Transmission 0 ft² 0 - 0 ft² 0 -

Skylight Transmission 0 ft² 0 - 0 ft² 0 -

Door Loads 21 ft² 381 - 21 ft² 1180 -

Floor Transmission 1200 ft² 0 - 1200 ft² 0 -

Partitions 0 ft² 0 - 0 ft² 0 -

Ceiling 0 ft² 0 - 0 ft² 0 -

Overhead Lighting 1800 W 5658 - 0 0 -

Task Lighting 0 W 0 - 0 0 -

Electric Equipment 1200 W 4094 - 0 0 -

People 2 422 410 0 0 0

Infiltration - 0 0 - 0 0

Miscellaneous - 339849 0 - 0 0

Safety Factor 0% / 0% 0 0 0% 0 0

>> Total Zone Loads - 353575 410 - 16037 0

Hourly Analysis Program 5.11 Page 9 of 25

Prepared by: GDM-AE 10:36AM

Entrance B DESIGN COOLING DESIGN HEATING

COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG

COOLING OA DB / WB 84.1 °F / 70.5 °F HEATING OA DB / WB -3.0 °F / -4.3 °F

OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F

Sensible Latent Sensible Latent

ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)

Window & Skylight Solar Loads 0 ft² 0 - 0 ft² - -

Wall Transmission 715 ft² 738 - 715 ft² 4176 -

Roof Transmission 160 ft² 97 - 160 ft² 374 -

Window Transmission 0 ft² 0 - 0 ft² 0 -

Skylight Transmission 0 ft² 0 - 0 ft² 0 -

Door Loads 21 ft² 557 - 21 ft² 1180 -

Floor Transmission 160 ft² 0 - 160 ft² 0 -

Partitions 0 ft² 0 - 0 ft² 0 -

Ceiling 0 ft² 0 - 0 ft² 0 -

Overhead Lighting 160 W 503 - 0 0 -

Task Lighting 0 W 0 - 0 0 -

Electric Equipment 8500 W 29002 - 0 0 -

People 0 0 0 0 0 0

Infiltration - 0 0 - 0 0

Miscellaneous - 0 0 - 0 0

Safety Factor 0% / 0% 0 0 0% 0 0

>> Total Zone Loads - 30898 0 - 5730 0

Entrance A DESIGN COOLING DESIGN HEATING

COOLING DATA AT Aug 1500 HEATING DATA AT DES HTG

COOLING OA DB / WB 86.0 °F / 71.0 °F HEATING OA DB / WB -3.0 °F / -4.3 °F

OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F

Sensible Latent Sensible Latent

ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)

Window & Skylight Solar Loads 0 ft² 0 - 0 ft² - -

Wall Transmission 426 ft² 463 - 426 ft² 2488 -

Roof Transmission 168 ft² 132 - 168 ft² 392 -

Window Transmission 0 ft² 0 - 0 ft² 0 -

Skylight Transmission 0 ft² 0 - 0 ft² 0 -

Door Loads 21 ft² 707 - 21 ft² 1180 -

Floor Transmission 168 ft² 0 - 168 ft² 0 -

Partitions 0 ft² 0 - 0 ft² 0 -

Ceiling 0 ft² 0 - 0 ft² 0 -

Overhead Lighting 168 W 522 - 0 0 -

Task Lighting 0 W 0 - 0 0 -

Electric Equipment 8500 W 29002 - 0 0 -

People 0 0 0 0 0 0

Infiltration - 0 0 - 0 0

Miscellaneous - 0 0 - 0 0

Safety Factor 0% / 0% 0 0 0% 0 0

>> Total Zone Loads - 30825 0 - 4061 0

Hourly Analysis Program 5.11 Page 10 of 25

Space Design Load Summary for MCR - OFFICE

Prepared by: GDM-AE 10:36AM

TABLE 1.1.A. Component Loads For Space "MCR - RECEIVING - 101" In Zone "Ship / Recieve"

DESIGN COOLING DESIGN HEATING

COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG

COOLING OA DB / WB 86.0 °F / 71.0 °F HEATING OA DB / WB -3.0 °F / -4.3 °F

OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F

Sensible Latent Sensible Latent

SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)

Window & Skylight Solar Loads 0 ft² 0 - 0 ft² - -

Wall Transmission 132 ft² 125 - 132 ft² 771 -

Roof Transmission 91 ft² 80 - 91 ft² 213 -

Window Transmission 0 ft² 0 - 0 ft² 0 -

Skylight Transmission 0 ft² 0 - 0 ft² 0 -

Door Loads 90 ft² 63 - 90 ft² 604 -

Floor Transmission 87 ft² 0 - 87 ft² 0 -

Partitions 0 ft² 0 - 0 ft² 0 -

Ceiling 0 ft² 0 - 0 ft² 0 -

Overhead Lighting 87 W 270 - 0 0 -

Task Lighting 0 W 0 - 0 0 -

Electric Equipment 87 W 285 - 0 0 -

People 0 0 0 0 0 0

Infiltration - 0 0 - 0 0

Miscellaneous - 0 0 - 0 0

Safety Factor 0% / 0% 0 0 0% 0 0

>> Total Zone Loads - 823 0 - 1588 0

TABLE 1.1.B. Envelope Loads For Space "MCR - RECEIVING - 101" In Zone "Ship / Recieve"

COOLING COOLING HEATING

Area U-Value Shade TRANS SOLAR TRANS

(ft²) (BTU/(hr·ft²·°F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)

ENE EXPOSURE

WALL 60 0.080 - 50 - 350

DOOR 90 0.092 - 63 - 604

SSE EXPOSURE

WALL 72 0.080 - 74 - 420

H EXPOSURE

ROOF 91 0.032 - 80 - 213

Hourly Analysis Program 5.11 Page 11 of 25

Prepared by: GDM-AE 10:36AM

TABLE 1.2.A. Component Loads For Space "MCR - UNBOX - 102" In Zone "Ship / Recieve"

DESIGN COOLING DESIGN HEATING

COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG

COOLING OA DB / WB 86.0 °F / 71.0 °F HEATING OA DB / WB -3.0 °F / -4.3 °F

OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F

Sensible Latent Sensible Latent

SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)

Window & Skylight Solar Loads 0 ft² 0 - 0 ft² - -

Wall Transmission 58 ft² 60 - 58 ft² 339 -

Roof Transmission 143 ft² 125 - 143 ft² 334 -

Window Transmission 0 ft² 0 - 0 ft² 0 -

Skylight Transmission 0 ft² 0 - 0 ft² 0 -

Door Loads 0 ft² 0 - 0 ft² 0 -

Floor Transmission 135 ft² 0 - 135 ft² 0 -

Partitions 0 ft² 0 - 0 ft² 0 -

Ceiling 0 ft² 0 - 0 ft² 0 -

Overhead Lighting 143 W 444 - 0 0 -

Task Lighting 0 W 0 - 0 0 -

Electric Equipment 143 W 468 - 0 0 -

People 0 0 0 0 0 0

Infiltration - 0 0 - 0 0

Miscellaneous - 0 0 - 0 0

Safety Factor 0% / 0% 0 0 0% 0 0

>> Total Zone Loads - 1097 0 - 673 0

TABLE 1.2.B. Envelope Loads For Space "MCR - UNBOX - 102" In Zone "Ship / Recieve"

COOLING COOLING…