This is a product specification document for Ruskin FSD60 and FSD60LP combination fire and smoke dampers, effective July 2020.

The FSD60 series provides point-of-origin fire and smoke containment with a 1½-hour UL555 rating and UL555S Leakage Class I classification. The FSD60 standard model features a 16-gauge galvanized hat-shaped channel frame, one-piece airfoil blades of 14-gauge equivalent strength, and stainless steel sleeve-type bearings. Maximum operational ratings include 4,000 FPM velocity and 8 inches water gauge pressure at 350°F. The FSD60LP ultra-low leakage variant offers an integral sleeve/frame design with 20-gauge galvanized construction, low-profile aerodynamic blade design, and superior performance characteristics including less than 0.03 inches water gauge pressure drop at 1,000 FPM, with maximum ratings of 2,000 FPM and 4 inches water gauge. Both models are AMCA licensed, meet NFPA standards (80, 90A, 92A, 92B, 101, 105), comply with ICC International Building Codes and California State Fire Marshal requirements, and carry a five-year limited warranty. Available options include damper test switches, reopenable operation packages, duct smoke detectors, remote position indication switches, control panels, factory sleeves, and angle installation hardware. Dampers are available in multiple sizes ranging from 8" × 6" (FSD60) to 36" × 14" (FSD60LP) for single-section installations, with electric or pneumatic actuator configurations and various duct transition styles (round, oval, rectangular) to accommodate specific installation requirements.

View the file

Other files

File Type Posted
S30 - SAM - Special Notice - Cancellation - 36C77626R0062_2 - EHRM Infra Upgrades - Togus.pdf PDF
S06 - Amend 0002 - Att 03 - Corrected Agenda - RFP - 07202026 - EHRM Infra - Togus.pdf PDF
S06 - Amend 0002 - 36C77626R0062 - 07202026 - EHRM Infra - Togus.pdf PDF
S06 - Amend 0001 - Att 02 - SV - Attendance SHT - 06292026 - EHRM Infra - Togus.pdf PDF
S06 - Amend 0001 - 36C77626R0062 - 07142026 - EHRM Infra - Togus.pdf PDF
S06 - Amend 0001 - RFIs - 07132026 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S06 - Amend 0001 - Att 01 - Rvd Structural Drwg - 06192026 - EHRM Infra - Togus.pdf PDF
S06 - Amend 0001 - Att 03 - SV - Agenda - RFP - 06292026 - EHRM Infra - Togus.pdf PDF
S02 - SOW - Att 05 - Drwg - Vol 3 - 02182026 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - SOW - Att 13 - Const Sch - 02132026 - EHRM Infra Upgrades - Constr Togus.pdf PDF
S02 - SOW - Att 26 - Cut Sheet 04 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - Att 03 -Prj Info Sheet for KTR - EHRM Infra Upgrade - Togus.docx DOCX document
S02 - SOW - Att 03 - Drwg - Vol 1C - 02182026 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - SOW - Att 22 - TS-000 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - Att 07 - 852.219-75 - 06172026 - EHRM Infra Upgrade - Togus.pdf PDF
S02 - Att 04 - Memo - Brand Name - 04092026 - EHRM Infra Upgrade - Togus.pdf PDF
S02 - SOW - Att 35 - Cut Sheet 13 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - SOW - Att 17 - Memo - Phy Sec Compliance - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - SOW - Att 27 - Cut Sheet 05 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - SOW - Att 09 - Specs - Vol 3- 02182026 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - SOW - Att 30 - Cut Sheet 08 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - SOW - Att 24 - Cut Sheet 02 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - Att 05 - Division Cost Breakdown - EHRM Infra Upgrade - Togus.xlsx XLSX spreadsheet
S02 - SOW - Att 29 - Cut Sheet 07 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - SOW - Att 37 - Cut Sheet 15 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - SOW - Att 16 - Submittal Reg - 02182026 - EHRM Infra - Upgrades - Constr - Togus.xlsx XLSX spreadsheet
S02 - SOW - Att 14 - Design Calcs - 02182026 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - SOW - Att 18 - Memo - Prj Stnd Compliance - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - SOW - Att 21 - PCRA 3 - MCR and Trench Work - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - SOW - Att 40 - Cut Sheet 18 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - SOW - Att 33 - Cut Sheet 11 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - SOW - Att 01 - Drwg - Vol 1A - 02182026 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - SOW - Att 38 - Cut Sheet 16 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - SOW - Att 06 - Drwg - Vol 4 - 02182026 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - SOW - Att 11 - Haz Mat Report - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - SOW - Att 12 - Geotechnical Report - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - SOW - Att 32 - Cut Sheet 10 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - SOW - Att 08 - Specs - Vol 1 - Div 02-14 - 02182026 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - SOW - Att 20 - PCRA 2 - Cabling and Data Outlets - EHRM Infra Upgrades - Constr - Togus.pdf PDF
RFP - EHRM Infra Upgrade - 36C77626R0062 - 06172026 - Togus.pdf PDF
S02 - SOW - Att 19 - PCRA 1 - TR Constr - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - SOW - Att 07 - Specs - Vol 1 - Div 00-01 - 02182026 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - SOW - Att 15 - Design Narrative - 02182026 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - SOW - Att 23 - Cut Sheet 01 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - SOW - Att 31 - Cut Sheet 09 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - Att 02 - PPQ - EHRM Infra Upgrade - Togus.docx DOCX document
S02 - SOW - Att 02 - Drwg - Vol 1B - 02182026 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - Att 01 - SOW - 05112026 - EHRM Infra Upgrades - Togus.pdf PDF
S02 - SOW - Att 10 - Specs - Vol 4 - 02182026 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - SOW - Att 36 - Cut Sheet 14 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
Show 40 more

Latest 50 of 57 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Spec FSD60-0720/Replaces FSD60-0117 ALL STATED SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE OR OBLIGATION. © Ruskin July 2020

FSD60/FSD60LP

Combination Fire and Smoke Damper 1 1/2 Hour UL555 Rated, UL555S Leakage Class 1

Ruskin FSD60 Series ultra low leakage combination fire and smoke dampers provide point-of-origin fire and smoke containment. The FSD60 includes high strength one-piece airfoil blades to ensure the lowest resistance to airflow and leakage up to 4000 fpm (20.3 m/s) and 8 in. wg (2 kPa).

Ruskin FSD60LP ultra low leakage, low profile, and low pressure drop combination fire and smoke damper is provided with an integral sleeve/frame design. The FSD60LP has the lowest pressure drop of less than .03 at 1000 FPM (5.1 m/s) of any fire smoke damper.

All FSD60 series dampers may be installed vertically in walls or horizontally in masonry floors and are rated for airflow and leakage in either direction.

APPLICATION

STANDARD CONSTRUCTION

Description FSD60 FSD60LP

Frame

5” x 16 gauge (127 x 1.6) galvanized, single piece, hat-shaped channel, structurally superior to 13 (2.4) gauge channel frame.

Integral sleeve and frame 20 (1.0) gauge galvanized single piece.

Blades

One-piece airfoil, nominal 6” (152) wide and 14 (2.0) gauge galvanized steel equivalent strength. Blades are approximately 6” (152) on center.

Low profile aerodynamic shaped, double skin of 16 (1.6) and 20 (1.0) gauge galvanized steel.

Bearings Stainless steel sleeve type, pressed into frame.

Stainless steel sleeve type, pressed into frame.

Jamb Seal Stainless steel, flexible metal compression type.

Stainless steel, flexible metal compression type.

Blade Seal

Silicone edge type for smoke seal to 450°F (232°C) and galvanized steel for flame seal to 1900°F (1038°C) mechanically fastened to the blade edge.

Stainless steel, flexible metal compression type.

Linkage Concealed in frame. Not Required

MAXIMUM OPERATIONAL RATINGS

Description FSD60 FSD60LP

UL555S

Leakage Rating Class I Class I

UL555

Hourly Rating 1 1/2 Hour 1 1/2 Hour

Maximum Velocity 4000 FPM (20.3 m/s) 2000 FPM (10.2 m/s)

Maximum Pressure 8 in. wg (2 kPa) 4 in. wg (1 kPa)

Temperature 350°F (177°C) 350°F (177°C)

OPTIONS

DTS (Damper Test Switch) test switch for cycle testing.

TS150 for reopenable operation in dynamic smoke management systems.

DSDF/DSDN Duct Smoke Detector (Flow rated or No- Flow). FSD60 only.

SP100 Switch Package to allow remote indication of damper blade position.

MCP control panels for testing or monitoring purposes or smoke management systems.

Factory Sleeves of various lengths and gauges to ensure field compliance with UL installation requirements.

FSD60 only.

FAST Angle factory supplied for labor saving angle one-side installation. Other angles of various sizes and gauges also available for one-side or two-side installation.

Note:

- Dampers are furnished approximately 1/4” (6) smaller than given opening dimensions.

- Dimensions shown in parentheses ( ) indicate millimeters.

AUTHORITY IN AIR CONTROL

Models FSD60 and FSD60LP series meets the requirements for combination fire and smoke dampers established by:

National Fire Protection Association NFPA Standards 80, 90A, 92A, 92B, 101 and 105

ICC International Building Codes

CSFM California State Fire Marshal Listing (#3235-0245:0126) Listing (#3235-0245:0129)

UL CLASSIFIED

UL555S Listing R5531

Spec FSD60-0720/Replaces FSD60-0117 ALL STATED SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE OR OBLIGATION. © Ruskin July 2020

To determine the AMCA Licensed air performance:

Locate the applicable feet per minute face velocity on the bottom of the velocity vs. pressure drop chart below. Move up the chart to the most appropriate size damper line. From the intersection point, move left to determine the pressure drop on the left side of the chart.

For other damper sizes refer to Air Performance Data For All Fire and Smoke Dampers spec sheet.

AMCA LICENSED AIR PERFORMANCE DATA

DAMPER SIZES

Sizes indicated below are for ratings of 2000 FPM (10.2 m/s) and 4 in. w.g. (1 kPa).

FSD60 FSD60LP

Minimum Size 8”w x 6”h (203 x 152) 6”w x 6”h (152 x 152) (actual size)

Maximum Size

Single Section Vertical – 32”w x 48”h (813 x 1219)

Single Section Horizontal – 30”w x 48”h (762 x 1219)

Multiple Section Vertical 120”w x 96”h (3048 x 2438)

Multiple Section Horizontal Electric Actuator – 120”w x 96”h (3048 x 2438) Pneumatic Actuators – 144”w x 96”h (3658 x 2438)

Single Section Vertical or Horizontal – 36”w x 14”h (914 x 356)

Controlled Closure Device (Heat-Actuated)

EFL (Electric Fuse Link) - 165°F (74°C) standard. 212°F (100°C), 250°F (121°C), 350°F (177°C) available.

PFL (Pneumatic Fuse Link) - 165°F (74°C) standard. 212°F (100°C), 285°F (141°C) available.

Ruskin Company certifies that the FSD60 and FSD60LP shown hereon is licensed to bear the AMCA Seal. The ratings shown are based on tests and procedures performed in accordance with AMCA Publication 511 and comply with the requirements of the AMCA Certified Ratings Program. The AMCA Certified Ratings Seal applies to air performance for the FSD60.

VELOCITY VS. PRESSURE DROP

PR

ES

SU

R E

D

RO

P

(IN

CH

ES

W .G

FACE VELOCITY – FEET/MINUTE

AMCA Fig. 5.3

1.0 0.9 0.8 0.7

0.6

0.5

0.4

0.3

0.2

0.1 .09 .08 .07

.06

.05

.04

.03

.02

.01 2 3 4 6 7 8 9 2 3 4 6 7 8 9

100 500 1000 5000 10000

12” x 12” FSD60

48” x 12” FSD60

36” x 36” FSD60

12” x 48” FSD60

24” x 24” FSD60

12” x 12” FSD60LP

Spec FSD60-0720/Replaces FSD60-0117 ALL STATED SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE OR OBLIGATION. © Ruskin July 2020

FSD60LP SLEEVE DIMENSIONAL DATA

The drawing shows the standard position of the FSD60LP when installed.

The mounting location provides enough space for the actuators, controls (FAST) retaining angles and duct connections. The minimum sleeve length is 20” (508). Consult Ruskin for shorter sleeve lengths.

Note:

1. The entire frame is not required to be installed within the wall or floor.

The center line of the closed blade, should be contained within the wall or floor.

2. See basic UL installation instructions for complete installation requirements.

EXTENDED OPERATIONAL RATINGS (FSD60 ONLY)

UL555S Test Standards require all fire and smoke dampers to prove closure and operation against heated air flow. The minimum rantings are 2,000 fpm (10.2 m/s) and 4” w.g. (1 kPa) and minimum of 250°F (121°C).

Safety Factor - UL555S has a built in safety factor of 400 fpm (2.03 m/s) and 0.5” w.g. (0.12 kPa). For example, to achieve a dynamic closure rating of 2,000 fpm and 4 in wg the damper must operate against an actual airflow rate of at least 2,400 fpm (12 m/s) and pressure of at least 4.5” w.g. (1.12 kPa).

All Ruskin fire smoke dampers meet or exceed the minimum UL555S requirements. In addition, Ruskin’s FSD60 damper exceeds these minimum requirements in many cases. See the chart below for minimum and extended UL555S listings for the FSD60 dampers.

Model Size Static Pressure Temperature Installation

2,000 FPM

FSD60 120” X 96” 4” w.g. 3500 Vertical

FSD60 144” X 96” 4” w.g. 3500 Horizontal

FSD60LP 36” X14” 4” w.g. 3500 Vertical or Horizontal

3,000 FPM

FSD60

64” x 72” 120” x 36” 32” x 96”

4” w.g. 2500 Vertical

FSD60

60” x 72” 120” x 36” 30” x 96”

4" w.g. 250° Horizontal

FSD60LP

64” x 64” 120” x 32” 32” x 96”

4" w.g. 350° Vertical

FSD60

60” x 64” 120” x 32” 30” x 96”

4” w.g. 3500 Horizontal

FSD60 120" x 96" 6" w.g. 250° Vertical

FSD60 144" x 96" 6" w.g. 250° Horizontal

4,000 FPM

FSD60

48” x 48” 96” x 24” 24” x 96”

8" w.g. 250° Vertical or Horizontal

ACTUATOR REQUIREMENTS

• UL555S requires that all fire smoke dampers have factory mounted actuators in order to bear the UL label.

• Fire smoke dampers larger than single section may require multiple actuators. See “Fire Smoke Damper Multiple Section Detail” spec sheet for details.

• Ruskin’s fire smoke dampers are UL555S labeled with either electric or pneumatic actuators mounted internal (in air stream) or external (out of air stream).

• Fire smoke dampers utilizing multiple actuators must have all actuators field wired to a common point for simultaneous closure. All field wiring shall be in accordance with applicable codes, ordinances and regulations.

20” (508) or 24” (610)

Wall Depth

10 1/2” (267) Min.

12” (305) Max.

‘B” Dim.

Spec FSD60-0720/Replaces FSD60-0117 ALL STATED SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE OR OBLIGATION. © Ruskin July 2020

FSD60 SLEEVE DIMENSIONAL DATA

Note: The 21” (4533) dimension becomes 32” (813) when the MS4120, FSNF, FSAF and GGD series are utilized.

FSD60 SERIES SPACE ENVELOPE

Combination fire smoke dampers are required by the UL listing to have all actuators and accessories factory mounted, wired and/or piped. The Ruskin standard is for the actuator to be located on the right hand side of the damper (onto a factory installed sleeve or side plate) as viewed from the jackshaft face of the unit. Larger units may require multiple actuators which are located on the right, left and maybe internal mount locations.

See the “Multiple Section Detail” specification sheet for details. Ruskin’s fire smoke dampers are not air flow directional, so the dampers may be rotated 180° or turned over as long as the blades are running horizontally in a position to accommodate installation obstructions.

The adjacent chart indicates an “S” and a “T” dimension for the space envelope that each actuator requires for installation. The “S” dimension is the “side” clearance, the “T” dimension is the “top” clearance required for the various actuators approved for use with Ruskin fire smoke dampers.

Ruskin recommends 6” (152) of additional space beyond the “S” dimension for ease of maintenance.

‘S’

‘T’

Note:

1. The dimensions shown in the chart above are for dampers 14” (356) tall.

2. Dampers shorter than 14” (356) tall, increase the “T” dimension by 1” (25) for every 1” (25) the damper is less than 14” (356).

3. Dampers taller than 14” (356) high reduce the “T” dimension by 1” (25) for every 1” (25) the damper height is greater than 14” (356).

Example

• 12” (305) tall damper with a FSLF actuator, “T” = 2” (52) and “S” = 4” (102).

• 18” (457) tall damper with a FSNF actuator, “T” = 1” (25) and “S” = 5” (127).

• FSAFA and MS4120 Tandem Mount, T stays the same, “S” = 10 1/2”.

Actuators S T

FSLF, FSTF 4" (102) 0" (0)

MS4104, MS4109 4” (102) 6” (152)

FSNF, FSAF, MS4120 5" (127) 5" (127)

331-4827 5" (127) 6" (152)

331-2961 8" (203) 8" (203)

331-3060 9" (229) 11" (279)

The ‘L’ dimension is the distance from the end of the sleeve to the damper. the standard damper location in the sleeve provides enough space for the actuator, controls, mounting angles and duct connection. the standard sleeve length for FSD’s is 20” (508) long and the standard ‘L’ dimension is 10 5/8” (270). The standard ‘L’ dimension allows the end of the sleeve to be a minimum of 10 5/8” (270) to the wall/floor and up to a maximum of 12 1/2” (318) to the wall/floor.

*The EFL, PFL, SP100 or TS150 location may be located above, below or on the side of the actuator depending upon the dampers height.

Optional 17” (432) long sleeve length available. Due to space limitations for actuators and controls with 17” (432) long sleeves, the damper height (‘B’ dimension) is restricted to the dimensions shown on the chart below. Consult Ruskin for other sleeve lengths.

7 1/8” (181) ‘L’ Dim. for Sleeves Shorter than 20” (508) Long

Without Accessories Without Accessories (TS150, SP100 or DTS)

Electric or Pneumatic Actuators

Electric Actuators

Pneumatic Actuators

331-4827 331-2961 331-3060

Over 10" (250) 'B' Dim.

Over 21" (533) 'B' Dim.

Over 28" (711) 'B' Dim.

Over 32" (813) 'B' Dim.

Over 40" (1016) 'B' Dim.

20” (508)

‘L’ Dim.

Wall (Ref.)

‘B’

Spec FSD60-0720/Replaces FSD60-0117 ALL STATED SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE OR OBLIGATION. © Ruskin July 2020

FSD60 INTERNAL MOUNT ACTUATOR DIMENSION

Actuators B Dim and Above B Dim and Above

B X B X

FSLF, FSTF 10" (254) 10" (254) 18" (457) 7 1/2" (191)

MS4104,

MS4109 9” (229) 13 1/2” (343) 18” (457) 7” (178)

FSNF, FSAF,

MS4120 12" (305) 12 3/4" (324) 21" (533) 5 1/2" (140)

331-4827 16" (406) 15" (381) 21" (533) 7 1/2" (191)

331-2961 16" (406) 17" (432) 24" (610) 7 1/2" (191)

331-3060 20" (508) 19" (483) 26" (660) 9" (229)

‘B’ Dim.

‘X’ Dim.

‘B’ Dim.

‘X’ Dim.

Ruskin model FSD60 has been tested for internal mount actuators and accessories. These applications may be preferred where space is limited on the outside of the damper. Internally mounted actuators do not require the damper to have a factory installed sleeve or side plate.

(Model FSD60LP not available with internal mount actuators)

FSD60 LEAKAGE TO ATMOSPHERE / DUCT LEAKAGE TO ATMOSPHERE

When Ruskin’s Smoke Dampers are supplied with a factory installed damper sleeve, the sealed sleeve meets the lowest duct leakage requirements set fourth by SMACNA. See Details Below

Duct Leakage Class 2

Duct Leakage Class 3

FSD60 Leakage

Power (FSD60 Leakage)

0.1

0.1

M ea su re d Le ak ag e C

FM

Test Pressure in. w.g.

Spec FSD60-0720/Replaces FSD60-0117 ALL STATED SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE OR OBLIGATION. © Ruskin July 2020

DIMENSIONAL INFORMATION

FSD60(LP) Style B

FSD60 Style R, CR and WR & FSD60LP Style R & CR

FSD60 Style A

FSD60LP Style A

Height B

Width A

DUCT TRANSITION CONNECTIONS

FSD60 Series dampers may be supplied with round, oval and rectangular duct connections.

Style Description

B Units under 6” (152) tall

R Round non-sealed (Low pressure)

CR Round sealed (Medium pressure)

WR Round welded (High pressure)

C Rectangular sealed (Low and medium pressure)

WC Rectangular welded (High pressure)

LO Oval non-sealed (Low pressure)

CO Oval sealed (Medium pressure)

WO Oval welded (High pressure)

The square damper size will be 2” (51) larger in width and height than the round, oval or rectangular duct size ordered.

Approximate damper assembly weight: 17 lbs. per sq. ft. for Style A

MINIMUM and MAXIMUM SIZES

Round Transitions Minimum 4” (102) diameter Maximum 94” (2388) diameter

Rectangular and Oval Transitions Minimum 6”w x 4”h (152 x 102) Maximum 118”w x 94”h (2997 x 2388) in diameter

‘B’ Style Transitions Minimum height 4” (102) ‘B’ style transitions are utilized on units where the damper height is less than 6” (152).

Consult Ruskin for other available styles and sizes.

Note: For low and medium pressure units (Styles R, CR, C and CO) the collar extends 1 1/2” (38) beyond the sleeve length and for high pressure units (Styles WR, WC and WO) the collar extends 2 1/2” (64) beyond the sleeve length.

FSD60 Style Lo,Co & Wo & FSD60LP Style Lo & Co

See note

Sleeve length

‘B’+2”(51)

‘A’+2”(51)

‘B’

‘A’

FSD60 Style C and WC & FSD60LP Style C

See note

Sleeve length

‘B’

‘A’

‘B’+2”(51)

‘A’+2”(51)

6”

(152) Min.

‘A’

‘B’

Sleeve length

Dia.+2” (51)

Dia + 2” (51)

Sleeve length

Diameter See note

Height B

Width A

Spec FSD60-0720/Replaces FSD60-0117 ALL STATED SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE OR OBLIGATION. © Ruskin July 2020

3900 Doctor Greaves Road Grandview, MO 64030 Website: www.ruskin.com Phone: (816) 761-7476AUTHORITY IN AIR CONTROL

SPECIFICATION

Combination fire smoke dampers meeting or exceeding the following specifications shall be furnished and installed at locations shown on plans or as described in schedules. Combination fire smoke dampers shall be produced in an ISO 9001 certified factory and shall be warranted to be free from defects in material and workmanship for a period of 5 years after date of shipment. Dampers shall meet the requirements of NFPA80, 90A, 92A and 92B and shall have a fire rating of 1 1/2 hours in accordance with the latest edition of UL555 and shall be classified as Leakage Class I Smoke Dampers in accordance with the latest version of UL555S. Dampers shall be AMCA Licensed and the product literature shall bear the AMCA certified rating seal for air performance. AMCA certified testing shall verify pressure drop does not exceed .03” w.g. on a 12” x 12” (305 x 305) damper at a face velocity of 1000 fpm.

Damper frame (when size permits) shall be constructed using the UniFrame Design Concept (UDC) and shall be minimum 16 gauge (1.6) galvanized steel formed into a structural hat channel superior to 13 gauge (2.4) channel frame. Assemblies less than 36” (914) wide x 14” (356) high shall be Low Profile (LP) design to maximize the free area of these smaller dampers. Damper blades shall be single piece airfoil shaped with 14 (2.0) gauge equivalent strength and units less than 36” (914) wide x 14” (356) high low profile aerodynamic shaped, double skin 16 (1.6) and 20 (1.0) gauge galvanized steel. Blade edge seals shall be inflatable silicone mechanically locked into blade edge and units less than 36” (914) wide x 14” (356) high stainless steel, flexible metal compression type. Jamb seals shall be stainless steel compression type. Bearings shall be stainless steel, permanently lubricated sleeve type turning in an extruded hole in the frame for maximum life.

Combination fire smoke dampers and their actuators shall be qualified in accordance with UL555S to an elevated temperature of 250°F (121°C) or 350°F (177°C) depending upon the actuator. Appropriate electric or pneumatic actuators (specifier select one) shall be installed by the damper manufacturer at time of damper fabrication. Electric actuators, factory installed on dampers, shall have been tested for prolonged periods of holding (minimum 1 year) with no evidence of reduced spring return performance. Each damper shall be rated for leakage and airflow in either direction through the damper. In addition to the leakage ratings already specified, the dampers shall be AMCA licensed for Air Performance.

Combination fire smoke dampers shall be Ruskin FSD60 and units less than 36” (914) wide x 14” (356) high model FSD60LP.

(Consult www.ruskin.com for electronic version of this “Quick” spec as well as for complete 3-part CSI MasterFormat Specifications)

Document Title

Limited Warranty Document

LINKS TO IMPORTANT DOCUMENTS