This is an Engineering Specification document for the Watts Series LF009 Reduced Pressure Zone (RPZ) Assemblies, a potable water backflow prevention device available in sizes from ¼" to 3".

The LF009 assemblies are designed to protect potable water supplies in compliance with national plumbing codes and water authority requirements, preventing health hazard cross-connections in piping systems and service line entrances. The product features two independent in-line check valves with captured springs, replaceable check seats, and an intermediate relief valve. Construction includes Lead Free cast copper silicon alloy bodies (¼" to 2") or fused epoxy-coated cast iron bodies (2½" to 3"), with ArmorTek™ coating technology on larger models to resist microbial-induced corrosion. Sizes ½" to 3" include a flood sensor for detecting excessive water discharges from the relief valve, which requires an add-on connection kit for activation and can integrate with Building Management Systems and cellular communication. The assemblies meet USC, ASSE Standard 1013, AWWA Standard C511, and CSA B64.4 standards, with approvals from ASSE, AWWA, CSA, IAPMO, and the Foundation for Cross-Connection Control and Hydraulic Research at the University of Southern California. Operating parameters include supply pressures up to 175 psi and water temperatures ranging from 33°F to 180°F (¼" to 2" models) or 110°F continuous/140°F intermittent (2½" to 3" models). The specification includes detailed dimensional drawings, weight specifications, and capacity performance charts showing flow rates and pressure drops across all available sizes.

View the file

Other files

File Type Posted
S30 - SAM - Special Notice - Cancellation - 36C77626R0062_2 - EHRM Infra Upgrades - Togus.pdf PDF
S06 - Amend 0002 - Att 03 - Corrected Agenda - RFP - 07202026 - EHRM Infra - Togus.pdf PDF
S06 - Amend 0002 - 36C77626R0062 - 07202026 - EHRM Infra - Togus.pdf PDF
S06 - Amend 0001 - Att 02 - SV - Attendance SHT - 06292026 - EHRM Infra - Togus.pdf PDF
S06 - Amend 0001 - 36C77626R0062 - 07142026 - EHRM Infra - Togus.pdf PDF
S06 - Amend 0001 - RFIs - 07132026 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S06 - Amend 0001 - Att 01 - Rvd Structural Drwg - 06192026 - EHRM Infra - Togus.pdf PDF
S06 - Amend 0001 - Att 03 - SV - Agenda - RFP - 06292026 - EHRM Infra - Togus.pdf PDF
S02 - SOW - Att 05 - Drwg - Vol 3 - 02182026 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - SOW - Att 13 - Const Sch - 02132026 - EHRM Infra Upgrades - Constr Togus.pdf PDF
S02 - SOW - Att 26 - Cut Sheet 04 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - Att 03 -Prj Info Sheet for KTR - EHRM Infra Upgrade - Togus.docx DOCX document
S02 - SOW - Att 03 - Drwg - Vol 1C - 02182026 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - SOW - Att 22 - TS-000 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - Att 07 - 852.219-75 - 06172026 - EHRM Infra Upgrade - Togus.pdf PDF
S02 - Att 04 - Memo - Brand Name - 04092026 - EHRM Infra Upgrade - Togus.pdf PDF
S02 - SOW - Att 35 - Cut Sheet 13 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - SOW - Att 17 - Memo - Phy Sec Compliance - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - SOW - Att 27 - Cut Sheet 05 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - SOW - Att 09 - Specs - Vol 3- 02182026 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - SOW - Att 30 - Cut Sheet 08 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - SOW - Att 24 - Cut Sheet 02 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - Att 05 - Division Cost Breakdown - EHRM Infra Upgrade - Togus.xlsx XLSX spreadsheet
S02 - SOW - Att 29 - Cut Sheet 07 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - SOW - Att 37 - Cut Sheet 15 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - SOW - Att 16 - Submittal Reg - 02182026 - EHRM Infra - Upgrades - Constr - Togus.xlsx XLSX spreadsheet
S02 - SOW - Att 14 - Design Calcs - 02182026 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - SOW - Att 18 - Memo - Prj Stnd Compliance - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - SOW - Att 21 - PCRA 3 - MCR and Trench Work - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - SOW - Att 40 - Cut Sheet 18 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - SOW - Att 33 - Cut Sheet 11 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - SOW - Att 01 - Drwg - Vol 1A - 02182026 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - SOW - Att 38 - Cut Sheet 16 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - SOW - Att 06 - Drwg - Vol 4 - 02182026 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - SOW - Att 11 - Haz Mat Report - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - SOW - Att 12 - Geotechnical Report - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - SOW - Att 32 - Cut Sheet 10 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - SOW - Att 08 - Specs - Vol 1 - Div 02-14 - 02182026 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - SOW - Att 20 - PCRA 2 - Cabling and Data Outlets - EHRM Infra Upgrades - Constr - Togus.pdf PDF
RFP - EHRM Infra Upgrade - 36C77626R0062 - 06172026 - Togus.pdf PDF
S02 - SOW - Att 19 - PCRA 1 - TR Constr - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - SOW - Att 07 - Specs - Vol 1 - Div 00-01 - 02182026 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - SOW - Att 15 - Design Narrative - 02182026 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - SOW - Att 23 - Cut Sheet 01 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - SOW - Att 31 - Cut Sheet 09 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - Att 02 - PPQ - EHRM Infra Upgrade - Togus.docx DOCX document
S02 - SOW - Att 02 - Drwg - Vol 1B - 02182026 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - SOW - Att 34 - Cut Sheet 12 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
S02 - Att 01 - SOW - 05112026 - EHRM Infra Upgrades - Togus.pdf PDF
S02 - SOW - Att 10 - Specs - Vol 4 - 02182026 - EHRM Infra Upgrades - Constr - Togus.pdf PDF
Show 40 more

Latest 50 of 57 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

ES-LF009

Engineering Specification

Job Name ––––––––––––––––––––––––––––––––––––––––––––

Job Location

Engineer

Approval

Contractor ––––––––––––––––––––––––––––––––––––––––––––

–––––––––––––––––––––––––––––––––––––––––– Approval ––––––––––––––––––––––––––––––––––––––––––––––

––––––––––––––––––––––––––––––––––––––––––––– Contractor’s P.O. No. –––––––––––––––––––––––––––––––––––

––––––––––––––––––––––––––––––––––––––––––––– Representative –––––––––––––––––––––––––––––––––––––––––

LEAD FREE*

Series LF009 Reduced Pressure Zone Assemblies 1⁄4" – 3" Series LF009 Reduced Pressure Zone assemblies are designed to protect potable water supplies in accordance with national plumbing codes and water authority requirements. These series are used in a variety of installations, including the prevention of health hazard cross-connections in piping systems or for containment at the service line entrance. They are also used in irrigation systems, boiler feed, water lines, and other installations requiring maximum protection. The body construction is fused with ArmorTek™ coating technology to resist corrosion due to microbial induced corrosion (MIC) or exposed metal substrate.* The series also features Lead Free* construction to comply with Lead Free* installation requirements.

The series features two in-line, independent check valves, captured springs, and replaceable check seats with an intermediate relief valve. Its compact modular design facilitates maintenance and assembly access. Sizes 1⁄4" to 1" shutoffs have tee handles.

Series LF009 assemblies of sizes ½" to 3" include a flood sensor to detect excessive water discharges from the relief valve. The sensor is installed on the assembly exterior and does not alter assembly functions or certifications. The sensor relays a signal that triggers notification to facility personnel who can take corrective action, thus avoiding the possibility of ruinous flooding and costly damage.

NOTICE

An add-on connection kit is required to activate the flood sensor.

Without the connection kit, the sensor is a passive component that has no communication with any other device. (For more information, download RP/IS-009.)

Features

• Single access cover and modular check construction for ease of maintenance

• Top entry to all internals for immediate accessibility

• Captured springs for safe maintenance

• Internal relief valve for reduced installation clearances

• Replaceable seats for economical repair

• ArmorTek™ coating technology to resist internal corrosion†

†Amortek coating applied to the 2½" and 3" models only.

LF009M2-QT-FS

• Lead Free cast copper silicon alloy body construction (1⁄4" – 2") *

• Fused epoxy coated cast iron body (21⁄2" – 3")

• Ball valve test cocks — screwdriver slotted (1⁄4" – 2")

• Large body passages provides low pressure drop

• Compact, space saving design

• No special tools required for servicing

• Sensor on the relief valve for flood detection (½" – 3")

• Flood alerts feature activated with add-on sensor connection kit, compatible with BMS and cellular communication

NOTICE

Use of the flood sensor does not replicate the need to comply with all required instructions, codes, and regulations related to installation, operation, and maintenance of this product, including Watts® is not responsible for the failure of alerts due to connectivity or power issues.

NOTICE

The information contained herein is not intended to replace the full product installation and safety information available or the experience of a trained product installer. You are required to thoroughly read all installation instructions and product safety information before beginning the installation of this product.

Inquire with governing authorities for local installation requirements.

*The wetted surface of this product contacted by consumable water con tains less than 0.25% of lead by weight.

Watts product specifications in U.S. customary units and metric are approximate and are provided for reference only. For precise measurements, please contact Watts Technical Service. Watts reserves the right to change or modify product design, construction, specifications, or materials with out prior notice and without incurring any obligation to make such changes and modifications on Watts products previously or subsequently sold.

Specification A Reduced Pressure Zone Assembly shall be installed at each potential health hazard location to prevent backflow due to backsiphonage and/or backpressure. The assembly shall consist of an internal pressure differential relief valve located in a zone between two positive seating check modules with captured springs and silicone seat discs. Seats and seat discs shall be replaceable in both check modules and the relief valve. There shall be no threads or screws in the waterway exposed to line fluids. Service of all internal components shall be through a single access cover secured with stainless steel bolts. Body and shutoffs shall be constructed using Lead Free* cast copper silicon alloy materials. Lead Free* reduced pressure zone assembly shall comply with state codes and standards, where applicable, requiring reduced lead content.

The assembly shall also include two resilient seated isolation valves, four resilient seated test cocks, and an air gap drain fitting. The valve body shall utilize a coating system with built-in electrochemical corrosion inhibitor and microbial inhibitor. The assembly shall meet the requirements of USC; ASSE Std. 1013;

AWWA Std. C511; CSA B64.4. Shall be a Watts Series LF009, and shall include a sensor on the relief valve for flood detection on sizes ½" to 3".

Materials 1/4" – 2"

Lead Free* cast copper silicon alloy body construction, silicone rubber disc material in the first and second check plus the relief valve. Replaceable polymer check seats for first and second checks. Removable relief valve seats. Stainless steel cover bolts.

Standardly furnished with NPT body connections. Model LF009QT furnished with quarter-turn, full port, resilient seated, Lead Free* cast copper silicon alloy body ball valve shutoffs.

21/2" – 3"

• FDA-approved epoxy-coated cast iron unibody with plastic seats

• Relief valve with stainless steel seat and trim

• Lead Free* cast copper silicon alloy body ball valve test cocks

Model/Option 1/4" – 2"

Prefix:

U – Union connections

Suffix:

FS – Flood detection sensor (1⁄2" – 2") LF – Without shutoff valves PC – Internal polymer coating Press**

** Viega ProPress® connections are optional factory-installed fitting on each end of the approved/certified assembly.

– Press inlet x press outlet (1⁄2" – 2") QT – Quarter-turn ball valves S – Strainer 21/2" – 3"

Suffix:

FS – Flood detection sensor LF – Without shutoff valves NRS – Non-rising stem resilient seated gate valves OSY – UL Classified and FM Appr oved outside stem and yoke resilient seated gate valves S-FDA – FDA epoxy coated strainer NOTE: The installation of a drain line is recommended. When installing a drain line, an air gap is necessary. (For more informa tion download ES-AG/EL/TC at watts.com.)

Pressure – Temperature 1/4" – 2"

Suitable for supply pressure up to 175 psi (12.1 bar) Water temperature: 33°F – 180°F (0.5° – 82°C)

21/2" – 3"

Suitable for supply pressures up to 175 psi (12.1 bar) Water temperature: 110°F (43°C) continuous; 140°F (60°C) intermittent

Test Cock No. 3

Ball Type Test Cocks

Test Cock No. 2

First Check Module Assembly

R.P. Zone

Relief Valve Assembly

Test Cock No. 4

Second

Check

Module

Assembly

Water Outlet http://watts.com

Standards

USC

ASSE No. 1013

AWWA C511

CSA B64.4

IAPMO File No. 1563

Approvals

ASSE, AWWA, CSA, IAPMO

Approved by the Foundation for Cross-Connection Control and Hydraulic Research at the University of Southern California

Approval models NRS, OSY, PC, QT

UL Classified 21⁄2" – 3" with OSY gate valves 3/4" – 2" without shutoff valves (-LF), except LF009M3LF

Insulated Enclosure The WattsBox insulated enclosure is available for Series LF009.

For more information download ES-WB at watts.com.

Air Gaps and Elbows Call customer service if you need assistance with technical details.

MODEL DRAIN OUTLET DIMENSIONS WEIGHT

A B For 909, 009, and 993 sizes in. mm in. mm in. mm lb kg

909AGA 1⁄4"–1⁄2" 009,

3⁄4" 009M2/M3

1⁄2 13 23⁄8 60 31⁄8 79 0.625 0.28

909AGC 3⁄4"–1" 009/909,

1"–11⁄2" 009M2

1 25 31⁄4 83 47⁄8 124 1.5 0.68

909AGF 11⁄4"–2" 009M1,

11⁄4"–3" 009/909, 2" 009M2, 4"–6" 993

2 51 43⁄8 111 63⁄4 171 3.25 1.47

909AGK 4"–6" 909,

8"–10" 909M1

3 76 63⁄8 162 95⁄8 244 6.25 2.83

909AGM 8"–10" 909 4 102 73⁄8 187 111⁄4 286 15.5 7.03

909ELA 1⁄4"–1⁄2" 009, 3⁄4" 009M2/M3 – – – – – – – –

909ELC 3⁄4"–1" 009/909 – – 23⁄8 60 23⁄8 60 0.38 0.17

909ELF* 11⁄4"-2" 009M1,

11⁄4"–2" 009/909, 2" 009M2, 4"–6" 993

– – 35⁄8 92 35⁄8 92 2 0.91

909ELH*

Vertical

21⁄2"–3" 009/909 – – – – – – – –

*Epoxy coated

A

B

A

B http://watts.com

Dimensions – Weight Call customer service if you need assistance with technical details.

1⁄4" – 3⁄8"

N

M A

L

D

C

B

1⁄2" – 2"

C

B

N

L A

M

D

SIZE DIMENSIONS (APPROX.) WEIGHT

A B C D L M N

in. in. mm in. mm in. mm in. mm in. mm in mm in mm lb kg 1⁄4 10 250 45⁄8 117 33⁄8 86 11⁄4 32 51⁄2 140 23⁄8 60 21⁄2 64 5 2 3⁄8 10 250 45⁄8 117 33⁄8 86 11⁄4 32 51⁄2 140 23⁄8 60 21⁄2 64 5 2 1⁄2 10 250 57⁄8 149 33⁄8 86 21⁄2 64 51⁄2 140 23⁄4 70 21⁄4 57 5 2 3⁄4 103⁄4 273 61⁄4 159 31⁄2 89 23⁄4 70 63⁄4 171 33⁄16 81 23⁄4 70 6 3 1 141⁄2 368 61⁄4 159 3 76 31⁄4 83 91⁄2 241 33⁄4 95 3 76 12 5

11⁄4 173⁄8 441 63⁄4 169 31⁄2 89 31⁄4 83 113⁄8 289 47⁄16 113 31⁄2 89 15 6 11⁄2 177⁄8 454 63⁄4 169 31⁄2 89 31⁄4 83 111⁄8 283 47⁄8 124 4 102 16 7 2 213⁄8 543 83⁄4 222 41⁄2 114 41⁄4 108 131⁄2 343 55⁄16 151 5 127 30 13

21⁄2" – 3"

M

N1 N

E

A

L

C open

D

U

R

Watts G-4000 Series QT – Ball Valves

STRAINER SIZE DIMENSIONS (APPROX.) WEIGHT

M N N1†

†Clearance for servicing

in. mm in. mm in. mm in. mm lb kg

21⁄2 65 10 254 61⁄2 165 93⁄4 248 28 12.7 3 80 101⁄8 257 7 178 10 254 34 15.4

MODEL SIZE DIMENSIONS (APPROX.) WEIGHT

A C D E L R U

in. in. mm in. mm in. mm in. mm in. mm in. mm in. mm lb kg

LF009LF 21⁄2 — — — — 55⁄8 143 — — 181⁄8 460 — — 105⁄8 270 76 34.5

LF009OSY 21⁄2 331⁄4 845 157⁄8 403 55⁄8 143 163⁄8 416 181⁄8 460 73⁄4 197 105⁄8 270 166 75.3 LF009NRS 21⁄2 331⁄4 845 113⁄8 289 55⁄8 143 163⁄8 416 181⁄8 460 73⁄4 197 105⁄8 270 161 73.0

LF009LF 3 — — — — 55⁄8 143 — — 181⁄8 460 — — 105⁄8 270 76 34.5

LF009OSY 3 341⁄4 870 181⁄2 470 55⁄8 143 165⁄8 422 181⁄8 460 83⁄4 222 105⁄8 270 198 89.8 LF009NRS 3 341⁄4 870 123⁄4 324 55⁄8 143 165⁄8 422 181⁄8 460 83⁄4 222 105⁄8 270 191 86.6

Capacity Performance as established by an independent testing laboratory. The asterisk (*) indicates the typical maximum system flow rate

(7.5 ft/s, 2.3 m/s).

kPa psi

1⁄4" LF009QT

0 .25 .60 .75 1 1.17

138 20 117 17 96 14

76 11

55 8

35 5 gpm∆P 0 .95 1.9 2.9 3.8 4.5 lpm

3 kPa psi ⁄8" LF009QT 138 20

117 17 96 14 76 11

0 .25 .50 .75 1 1.25 1.50 2.5 3.1 gpm ∆P 0 .95 1.9 2.9 3.8 4.8 5.7 9.4 11.8 lpm

1⁄2" LF009QT kPa psi 172 25

0 1 2.5 5 7.5 10 12.5 15

138 20

103 15

69 10

35 5 gpm

∆P 0 3.8 9.5 19 28.5 38 47.5 57 lpm 5 7.5 15 fps

1.5 2.3 4.6 mps

3⁄4" LF009M3QT

kPa psi * 207 30

165 24

124 18

83 12

41 6

0 0

0 2 6 10 14 18 22 26 30 34 38 42 46 gpm ∆P 0 7.6 23 38 53 68 84 99 114 129 144 160 175 lpm

7.5 15fps
2.34.6 mps

1" LF009M2QT

kPa psi * gpm ∆P 0 19 38 76 114 152 190 228 266 304 lpm

7.5 15 fps

2.3 4.6 mps

0 5 10 20 30 40 50 60 70 80

11⁄4" LF009M2QT

psi

0 10 20 30 40 50 60 70 80

* kPa gpm∆P 0 38 76 114 152 190 228 266 304 lpm

5 7.5 10 15 fps

1.5 2.3 3.0 4.6 mps

0 10 20 30 40 50 60 70 80 90 100 110 120 gpm

11⁄2" LF009M2QT

kPa psi

∆P 0 38 76 114 152 190 228 266 304 342 380 418 456 lpm

2" LF009M2QTkPa psi

* 207

0 76 152 228 304 380 456 532 608 684 760 lpm 5 7.5 10 15 fps

1.5 2.3 3.0 4.6 mps

0 20 40 60 80 100 120 140 160 180 200 gpm∆P psi

0 25 50 75 100 125 150 175 200 225 250

* kPa 21⁄2" LF009 gpm ∆P 0 05 10- 295 380 475 570 665 760 885 950 lpm

0 25 50 75 100 125 150 175 200 225 250 275 300 325

3" LF009kPa psi gpm∆P 0 95 190 285 380 475 570 665 760 855 950 1045 1140 1235 lpm 5 7.5 10 fps

1.5 2.3 3.0 mps

USA: T: (978) 689-6066 •

Watts.com Canada: T: (888) 208-8927 Watts.ca

Latin America: T: (52) 55-4122-0138 Watts.com

ES-LF009 2318 © 2023 Watts http://watts.com http://Watts.ca http://watts.com

Series LF009
Reduced Pressure Zone Assemblies
NOTICE
Features
NOTICE
NOTICE
Specification
Materials
Model/Option
Pressure – Temperature
Standards
Approvals
Insulated Enclosure
Air Gaps and Elbows
Dimensions – Weight
Capacity