EW611 Rev 3.pdf
PDF 188 KB Posted
- Attached to
- Amendment 0010 -Use the applicable Small Business Forms attached Federal contract opportunity
- Solicitation number
- n44255
About this file
This document contains a SCADA diagram and one-line diagram for a proposed electrical system upgrade project. The diagrams outline the scope of work to replace aging control and monitoring systems for a pier, vessel maintenance facility, fuel distribution and storage, and related infrastructure. Key elements of the proposed upgrade include installing new programmable logic controllers, meters, sensors and related hardware to monitor and control electrical systems, fuel distribution, leak detection, pump stations and other site utilities. Communication infrastructure is also specified, such as fiber optic cable and networking equipment to integrate the various control systems. The project aims to modernize systems that support maritime security operations in the Strait of Juan de Fuca for the Department of the Navy.
View the file
Other files for this federal contract opportunity
Show all 50
Amendment 0010 -Use the applicable Small Business Forms attached has more files on GovTribe.
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PACHMI
NET
SW
AMI
NET
SW
PIER
SCADA
CABINET
TPP PIER
EXISTING
SCADA
CABINET
MFR1 MFR4 MFR3 MFR6
FIBER PATCH
PANEL (TYP)
ENET
SW
SERIAL OVER FIBER (TYP)
CAT 6 ETHERNET (TYP)
NFSC
E
AMI
E
AMI
E
AMI
E
AMI
E
AMI
FM2FM3
ELECTRICAL METER
FOR AMI SYSTEM (TYP)
OILY WASTE SENSOR
SANITARY SEWER SENSOR
SEE MECHANICAL FOR DETAILS
NET
SW
MV SWGR UTILITY BUILDING
E
AMI
MFR1 MFR1
VR
VR
GOV
GOV
SYNCSYNC
1.1MW
GENERATOR
NFSC
NIAGARA FRAMEWORK
SUPERVISORY CONTROLLER
FOR FUEL SYSTEM
NIAGARA FRAMEWORK
SUPERVISORY CONTROLLER FOR
ELECTRICAL AND GENERATOR
SYNCHRONIZER CONTROLS BETWEEN
GENERATOR AND SWITCHGEAR.
REPLACE EXISTING GOVERNOR AND
VOLTAGE REGULATOR WITH NEW UNITS
THAT WILL ALLOW CLOSED TRANSITIONS
AND PARALLEL OPERATION WITH THE
UTILITY.
PROVIDE THE FOLLOWING CONTROL
SIGNALS AT A MINIMUM:
1. GENERATOR START
2. GENERATOR EMERGENCY STOP
3. PARALLELING CONTROLS
PROVIDE THE FOLLOWING ALARMS FROM
THE GENERATOR:
1. LOW LUBRICATING OIL PRESSURE
2. LOW WATER TEMPERATURE
(BELOW THAT REQUIRED)
3. COOLING HIGH TEMPERATURE
4. LOW FUEL
5. OVERCRANK (FAIL TO START)
6. OVERSPEED
FM1
FM2FM3 FM1
SEE MECHANICAL FOR DETAILS
SEE MECHANICAL FOR DETAILS
WATER SENSOR
PROVIDE MODBUS TO MODBUS OVER
ETHER NET CONVERTER FOR
TRANSMISSION TO THE AMI HEAD END
MECHANICAL METERING ENCLOSURE
WATER METER
SANITARY SEWER METER
OILY WASTE METER
SENSOR CABLING BY MECHANICAL
MODBUS CABLE
PIER LEAK
DETECTION
PANEL ALARMS
PIER SUMP
PUMP HIGH
ALARMS
SANITARY
SEWER LIFT
STATION
PANEL ALARMS
SEE MECHANICAL PLANS FOR
THE NUMBER OF ALARMS FOR
EACH SUB SYSTEM
KB PIER
(E-07)
KB PIER
(E-08)
KB PIER FUEL
CONTROL
COLLECTION BOX
BY MECHANICAL
DISCRETE CONTROLS TO
FUEL PUMPS (NUMBER OF
SIGNALS TO BE DETERMINED
BY FUEL SYSTEM PROVIDER)
KB DOCK AREA FUEL LEAK
DETECTION
BY MECHANICAL
FIBER TO DISCRETE CONTROLS
(BY FUEL SYSTEM PROVIDER)
FIBER TO DISCRETE CONTROLS
(BY LEAK DETECTION PROVIDER)
PIER HEAT
TRACE PANEL
ALARMS
LDS-2
LDS-3
B7136
EXISTING UMCS
NETWORK (TO
B1305)
VIL
FIBER TO VIL CONTROLLER
(BY VIL PROVIDER)
DISCRETE CONTROLS OR
COMMUNICATIONS TO VIL DEVICES
(NUMBER OF SIGNALS TO BE
DETERMINED BY VIL PROVIDER)
PROVIDE FLEXIBLE
WIRING SYSTEM ON
FLOATING PIER
DISCRETE CONTROLS TO
LEAK DETECTORS (NUMBER OF
SIGNALS TO BE DETERMINED
BY LEAK DETECTION PROVIDER)
DISCRETE SIGNALS AS
REQUIRED BY MECHANICAL
UTILITY BUILDING
WALL MOUNT
COMM CABINET
FIBER TO DISCRETE
CONTROLS (BY FUEL
SYSTEM PROVIDER)
LDS-1
FIBER TO DISCRETE CONTROLS
(BY VIL PROVIDER)
FIBER TO DISCRETE CONTROLS
(BY LEAK DETECTION PROVIDER)
FIBER TO DISCRETE CONTROLS
(BY FUEL SYSTEM PROVIDER)
C-06
C-07 C-10
C-08
C-09
DISCRETE
SIGNALS AS
REQUIRED BY
MECHANICAL
SPD
100AF
30AT
3Ø 4W
250AF
150AT
100AF
100AT
100AF
30AT3Ø 4W
100AF
100AT
SPD
100AF
60AT 2P
1Ø 3W
GEN PNL
125A, 208/120V, FUEL PNL
100A, 208Y/120V, MV SWGR PNL
225A, 208Y/120V, TO MV SWGR CPT
SEE SHEET EW602
FOR CONTINUATION
3#4+1#8EGC
4#2+1#6EGC
4#1/0+1#6EGC
CONNECTION TO PANEL IN
RELOCATED GENERATOR
ENCLOSURE
MV SWGR
DC PNL
48V, 20A/1P 20A/1P 20A/1P
RECEPTACLES LIGHTS HVAC
BREAKER
TRIP PWR
BREAKER
CLOSE
PWR
BREAKER
AUX PWR
COMM
RACK PWR
CONTRACTOR TO SIZE
BREAKERS AND FEEDERS
TO MATCH EQUIPMENT.
20A/1P
OUTDOOR RECEPTACLES
SCALE:
EPROJECT NO.:
CONSTR. CONTR. NO.
NAVFAC DRAWING NO.
SHEET OF
DRAWFORM REVISION: 31 JANUARY 2017
CHIEF ENG/ARCH
BRANCH MANAGER
PM/DM
AS NOTED
DES DRW CHK
SATISFACTORY TO DATE
ACTIVITY
FOR COMMANDER NAVFAC
APPROVED
A/E INFO
SEAL
D E P A R T M E N T
O F
T H E
N A V Y
N A V F A C
N W
N A V A L
F A C
IL
IT
IE
S
E N G
IN
E E R
IN
G
C O M M A N D
S
IL
V E R D A L E W A S H
IN
G T O N
N A V A L
B A S E
K
IT
S A P B A N G O R
S
IL
V E R D A L E W A S H
IN
G T O N
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
S
YM
D
ES
C R
IP
TI
O N
D A
TE
A P P R
FIRE PROTECTION
D. GIBSON/T. BOLING
1389895
:4 :1
A M
C U s e rs S b o ll e n D o c u m e n ts P M O D P
IE
R E L E C R S b o ll e n .r vt
F Y
M
C O
N P
R O
J E
C T
P -9
T P
P P
IE
R
A N
D M
A
IN
T E
N A
N C
E F
A C
IL
IT
Y
S C A D A
AN
D
M V
S W G R
FU
EL
TA
N K
LO
W
V O
LT
AG
E O N E-
LI
N E
N A V A L
FA
C
IL
IT
IE
S
EN
G
IN
EE
R
IN
G
C O M M A N D
N O R
TH
W
ES
T
BCPSMB BGA
EW611
254 269
16046602
DOUG BUSSARD
B. GALLOWAY
B. NIXON
SCALE: NONE
SCADA DIAGRAM
A2
SCALE: NONE
MV SWGR & FUEL TANK LOW VOLTAGE
ONE-LINE
C4
EW6021
P
PI
P
AL
P
PI
0/
S M B
P
PI
0/
| Sheets |
| EW611 - SCADA AND MV SWGR & FUEL TANK LOW VOLTAGE ONE-LINE |