This document is a mechanical engineering control system diagram for a Design Wing Relocation project at Marine Corps Base Camp Lejeune, specifically focusing on Building 1005's exhaust fan and unit heater control systems. The technical drawing details multiple point lists including VHF points, exhaust fan/unit heater points, and communication room temperature sensor points, with comprehensive sequence of operations for various HVAC components. The diagram illustrates the control system architecture, showing interconnections between Air Handling Unit (AHU), Variable Frequency Drive (VFD), Variable Air Volume (VAV), and telecom space sensors on an existing bacnet bus. The document is part of construction documents for mechanical systems, specifically labeled as sheet M802 for Marine Corps Base construction work, indicating it is a detailed technical specification for HVAC control system design and integration.
View the file
Other files
Show 40 more
50 files listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DESIGN WING RELOCATION
BUILDING 1005
EXHAUST FAN/UNIT HEATER CONTROL DIAGRAM2
COMM ROOM 313 TEMPERATURE3
VAV CONTROL DIAGRAM1
CONTROL SYSTEM ARCHITECTURE4
AutoCAD SHX Text
J F ORR PE
AutoCAD SHX Text
SATISFACTORY TO: DATE
AutoCAD SHX Text
APPROVED: PWO OR OICC DATE
AutoCAD SHX Text
DESIGN DIR.
AutoCAD SHX Text
SUBMITTED BY:
AutoCAD SHX Text
DR.
AutoCAD SHX Text
CHK.
AutoCAD SHX Text
DES.
AutoCAD SHX Text
R DUNCAN
AutoCAD SHX Text
C MAAS
AutoCAD SHX Text
CAMP LEJEUNE, NORTH CAROLINA
AutoCAD SHX Text
CONST. CONTR.
AutoCAD SHX Text
MARINE CORPS BASE
AutoCAD SHX Text
DEPARTMENT OF THE NAVY NAVAL FACILITIES ENGINEERING SYSTEMS COMMAND
AutoCAD SHX Text E1
AutoCAD SHX Text
SIZE
AutoCAD SHX Text 80091
AutoCAD SHX Text
CODE IDENT. NO
AutoCAD SHX Text
NAVFAC DRAWING NO.
AutoCAD SHX Text M802
AutoCAD SHX Text
C MAAS
AutoCAD SHX Text
K ROOT
AutoCAD SHX Text
NA
AutoCAD SHX Text 60036683
AutoCAD SHX Text 21-0019
AutoCAD SHX Text
SCALE: NOTED
AutoCAD SHX Text
SHEET OF
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
SPEC.
AutoCAD SHX Text 05-21-0019
AutoCAD SHX Text
SYM
AutoCAD SHX Text
DATE
AutoCAD SHX Text
APPROVED
AutoCAD SHX Text
REVISIONS
AutoCAD SHX Text
NC
AutoCAD SHX Text
OUTSIDE AIR
AutoCAD SHX Text
NC
AutoCAD SHX Text
EXHAUST TO EXTERIOR
AutoCAD SHX Text
MECHANICAL ROOM
AutoCAD SHX Text S
AutoCAD SHX Text
GRAVITY BACKDRAFT DAMPER
AutoCAD SHX Text
CT
AutoCAD SHX Text M
AutoCAD SHX Text
BI - EF1 STATUS
AutoCAD SHX Text
AI - ZONE TEMPERATURE
AutoCAD SHX Text
BI - ZONE OCCUPANCY OVERRIDE
AutoCAD SHX Text
EXHAUST FAN/UNIT HEATER POINTS LIST
AutoCAD SHX Text
SOFTWARE POINTS
AutoCAD SHX Text
MECH. ZONE TEMPERATURE
AutoCAD SHX Text
POINT NAME
AutoCAD SHX Text
MECH. ZONE OVERRIDE
AutoCAD SHX Text
EF1 STATUS
AutoCAD SHX Text
UH1 STATUS
AutoCAD SHX Text
HARDWARE POINTS
AutoCAD SHX Text X
AutoCAD SHX Text
AI
AutoCAD SHX Text
AO
AutoCAD SHX Text
BI
AutoCAD SHX Text
BO
AutoCAD SHX Text
AV
AutoCAD SHX Text
BV
AutoCAD SHX Text
LOOP
AutoCAD SHX Text
SCHED
AutoCAD SHX Text
TREND
AutoCAD SHX Text
ALARM
AutoCAD SHX Text
SHOW ON
AutoCAD SHX Text
GRAPHIC
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text
SCALE: N.T.S.
AutoCAD SHX Text M802
AutoCAD SHX Text GENERAL: WHEN THE SPACE TEMPERATURE IS ABOVE 85°F (ADJUSTABLE), THE MOTORIZED OUTSIDE AIR DAMPER SHALL OPEN AND THE EXHAUST FAN SHALL ENERGIZE. WHEN THE SPACE TEMPERATURE IS BELOW 85°F (ADJUSTABLE), THE MOTORIZED OUTSIDE AIR DAMPER SHALL CLOSE AND THE EXHAUST FAN SHALL DE-ENERGIZE. WHEN THE SPACE TEMPERATURE IS BELOW 50°F (ADJUSTABLE), THE UNIT HEATER SHALL ENERGIZE. WHEN THE SPACE TEMPERATURE IS ABOVE 60°F (ADJUSTABLE), THE UNIT HEATER SHALL DE-ENERGIZE. MANUAL: WHEN INITIATED, THE MOTORIZED OUTSIDE AIR DAMPER SHALL OPEN AND THE EXHAUST FAN SHALL RUN FOR A MAXIMUM DURATION OF 60 MINUTES (ADJUSTABLE). AFTER 60 MINUTES (ADJUSTABLE), THE MOTORIZED OUTSIDE AIR DAMPER SHALL CLOSE AND THE EXHAUST FAN SHALL DE-ENERGIZE. ALARMS: IF THE MOTORIZED OUTSIDE AIR DAMPER STATUS DOES NOT MATCH THE COMMAND AFTER 90 SECONDS (ADJUSTABLE) AFTER BEING COMMANDED OPEN, AN ALARM WILL BE GENERATED. IF THE UNIT HEATER STATUS DOES NOT MATCH THE COMMAND AFTER 90 SECONDS (ADJUSTABLE) AFTER BEING COMMANDED ON, AN ALARM WILL BE GENERATED. IF THE EXHAUST FAN STATUS DOES NOT MATCH THE COMMAND AFTER 90 SECONDS (ADJUSTABLE) AFTER BEING COMMANDED ON, AN ALARM WILL BE GENERATED. MECH. ZONE TEMPERATURE SHALL HAVE AN ADJUSTABLE LOW AND HIGH ALARM LIMIT.
AutoCAD SHX Text
EXHAUST FAN/UNIT HEATER SEQUENCE OF OPERATIONS
AutoCAD SHX Text
UH1 FAILURE
AutoCAD SHX Text X
AutoCAD SHX Text
OUTSIDE AIR DAMPER FAILURE
AutoCAD SHX Text X
AutoCAD SHX Text
OUTSIDE AIR DAMPER STATUS
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text
EF1 FAILURE
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text
BI - OUTSIDE AIR DAMPER STATUS
AutoCAD SHX Text
UNIT HEATER
AutoCAD SHX Text X
AutoCAD SHX Text
COMMUNICATION ROOM 313 TEMPERATURE SENSOR POINTS LIST
AutoCAD SHX Text
SOFTWARE POINTS
AutoCAD SHX Text
ZONE TEMPERATURE
AutoCAD SHX Text
POINT NAME
AutoCAD SHX Text
HIGH ZONE TEMPERATURE
AutoCAD SHX Text
HARDWARE POINTS
AutoCAD SHX Text X
AutoCAD SHX Text
AI
AutoCAD SHX Text
AO
AutoCAD SHX Text
BI
AutoCAD SHX Text
BO
AutoCAD SHX Text
AV
AutoCAD SHX Text
BV
AutoCAD SHX Text
LOOP
AutoCAD SHX Text
SCHED
AutoCAD SHX Text
TREND
AutoCAD SHX Text
ALARM
AutoCAD SHX Text
SHOW ON
AutoCAD SHX Text
GRAPHIC
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text
SCALE: N.T.S.
AutoCAD SHX Text M802
AutoCAD SHX Text GENERAL: TEMPERATURE SENSOR SHALL MONITOR THE ZONE TEMPERATURE OF THE COMMUNICATIONS ROOM. ALARMS: ZONE TEMPERATURE SHALL HAVE AN ADJUSTABLE HIGH ALARM LIMIT INITIALLY SET TO 80°F (ADJ.).
AutoCAD SHX Text
COMMUNICATION ROOM 313 SEQUENCE OF OPERATIONS
AutoCAD SHX Text X
AutoCAD SHX Text
DA
AutoCAD SHX Text
SA
AutoCAD SHX Text
AI - AIRFLOW
AutoCAD SHX Text M
AutoCAD SHX Text
AO - ZONE DAMPER
AutoCAD SHX Text
HHW
AutoCAD SHX Text
AI - DISCHARGE AIR TEMP
AutoCAD SHX Text T
AutoCAD SHX Text
AO - HEATING VALVE
AutoCAD SHX Text M
AutoCAD SHX Text
HHWR
AutoCAD SHX Text
HHWS
AutoCAD SHX Text
VAV POINTS LIST
AutoCAD SHX Text
SOFTWARE POINTS
AutoCAD SHX Text
ZONE TEMPERATURE
AutoCAD SHX Text
POINT NAME
AutoCAD SHX Text
ZONE WARM/COOL ADJUST
AutoCAD SHX Text
ZONE TEMPERATURE SETPOINT
AutoCAD SHX Text
AIRFLOW
AutoCAD SHX Text
HARDWARE POINTS
AutoCAD SHX Text X
AutoCAD SHX Text
AI
AutoCAD SHX Text
AO
AutoCAD SHX Text
BI
AutoCAD SHX Text
BO
AutoCAD SHX Text
AV
AutoCAD SHX Text
BV
AutoCAD SHX Text
LOOP
AutoCAD SHX Text
SCHED
AutoCAD SHX Text
TREND
AutoCAD SHX Text
ALARM
AutoCAD SHX Text
SHOW ON
AutoCAD SHX Text
GRAPHIC
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text
AIRFLOW SETPOINT
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text
ZONE DAMPER SETPOINT
AutoCAD SHX Text X
AutoCAD SHX Text
ZONE DAMPER
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text
EFFECTIVE HEATING SETPOINT
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text
HEATING VALVE
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text
EFFECTIVE COOLING SETPOINT
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text
HEATING VALVE SETPOINT
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text
ZONE OCCUPANCY OVERRIDE
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text
DISCHARGE AIR TEMPERATURE
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text
HIGH ZONE TEMEPRATURE
AutoCAD SHX Text X
AutoCAD SHX Text
LOW ZONE TEMPERATURE
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text
SCALE: N.T.S.
AutoCAD SHX Text M802
AutoCAD SHX Text X
AutoCAD SHX Text
AI - ZONE WARM/COOL ADJUST
AutoCAD SHX Text T
AutoCAD SHX Text
AI - MECH. ZONE TEMPERATURE
AutoCAD SHX Text
BI - MECH. ZONE OVERRIDE
AutoCAD SHX Text T
AutoCAD SHX Text
AI - ZONE TEMPERATURE
AutoCAD SHX Text T
AutoCAD SHX Text A. SETPOINTS AND AIRFLOW SETTINGS SETPOINTS AND AIRFLOW SETTINGS 1. PROGRAM TEMPERATURE SETPOINTS PROGRAM TEMPERATURE SETPOINTS a. OCCUPIED ACTIVE TEMPERATURE SETPOINT (°F) PER RESET SCHEDULE OCCUPIED ACTIVE TEMPERATURE SETPOINT (°F) PER RESET SCHEDULE 1) 70°F @ 50°F OUTSIDE AMBIENT 70°F @ 50°F OUTSIDE AMBIENT 2) 76°F @ 80°F OUTSIDE AMBIENT 76°F @ 80°F OUTSIDE AMBIENT 3) BETWEEN 50°F AND 80°F, RESET ADJUSTMENTS SHALL BE LINEAR BETWEEN 50°F AND 80°F, RESET ADJUSTMENTS SHALL BE LINEAR b. UNOCCUPIED TEMPERATURE SETPOINTS (°F) UNOCCUPIED TEMPERATURE SETPOINTS (°F) 1) 60°F HEATING 60°F HEATING 2) 80°F COOLING 80°F COOLING c. THE ZONE EFFECTIVE SETPOINT SHALL BE THE OCCUPIED ZONE SETPOINT PLUS THE ZONE EFFECTIVE SETPOINT SHALL BE THE OCCUPIED ZONE SETPOINT PLUS THE OCCUPANT OFFSET OF +/-2°F (ADJ.). d. THE OFFSET BETWEEN HEATING VALVE (HEATING), THE PRIMARY AIR DAMPER THE OFFSET BETWEEN HEATING VALVE (HEATING), THE PRIMARY AIR DAMPER (COOLING) AND THE ZONE EFFECTIVE SETPOINT SHALL BE NO LESS THAN +/- 1F. 2. PROGRAM ALL VAV TERMINAL UNIT FLOW SET POINTS PER SCHEDULE PROGRAM ALL VAV TERMINAL UNIT FLOW SET POINTS PER SCHEDULE a. COOLING MAXIMUM AIRFLOW SETPOINT (CFM) COOLING MAXIMUM AIRFLOW SETPOINT (CFM) b. COOLING MINIMUM AIRFLOW SETPOINT (CFM) COOLING MINIMUM AIRFLOW SETPOINT (CFM) c. HEATING AIRFLOW SETPOINT (CFM) HEATING AIRFLOW SETPOINT (CFM) B. OCCUPIED CONTROL SEQUENCE: OCCUPIED CONTROL SEQUENCE: OCCUPIED AND UNOCCUPIED MODE SHALL BE DETERMINED BY THE ASSOCIATED AHU SCHEDULE. HEATING VALVE AND PRIMARY AIR DAMPER SHALL MODULATE TO MAINTAIN THE ZONE EFFECTIVE SETPOINT. 1. HEATING MODE: HEATING MODE: a. MODULATE THE HOT WATER RE-HEAT VALVE TO MAINTAIN ZONE EFFECTIVE MODULATE THE HOT WATER RE-HEAT VALVE TO MAINTAIN ZONE EFFECTIVE TEMPERATURE SETPOINT. 2. COOLING MODE: COOLING MODE: a. MODULATE THE ZONE DAMPER BETWEEN SCHEDULED COOLING MINIMUM AIRFLOW MODULATE THE ZONE DAMPER BETWEEN SCHEDULED COOLING MINIMUM AIRFLOW AND COOLING MAXIMUM AIRFLOW TO MAINTAIN ZONE EFFECTIVE TEMPERATURE SETPOINT. C. UNOCCUPIED CONTROL SEQUENCE: UNOCCUPIED CONTROL SEQUENCE: 1. VAV UNITS SHALL CONTROL TO THEIR UNOCCUPIED HEATING OR COOLING SETPOINTS VAV UNITS SHALL CONTROL TO THEIR UNOCCUPIED HEATING OR COOLING SETPOINTS DURING UNOCCUPIED PERIODS. 2. THE AHU WILL START ONLY DURING UNOCCUPIED COOLING MODE BASED ON ITS THE AHU WILL START ONLY DURING UNOCCUPIED COOLING MODE BASED ON ITS UNOCCUPIED SEQUENCE. 3. UNOCCUPIED HEATING MODE: UNOCCUPIED HEATING MODE: a. ON A DROP IN ZONE TEMPERATURE BELOW THE UNOCCUPIED SETPOINT THE ON A DROP IN ZONE TEMPERATURE BELOW THE UNOCCUPIED SETPOINT THE TERMINAL UNIT SHALL BE ENERGIZED, AND THE HOT WATER REHEAT VALVE SHALL BE SET TO 100% OPEN. b. ON A RISE IN ZONE TEMPERATURE 5 DEG F (ADJ.) ABOVE THE UNOCCUPIED ON A RISE IN ZONE TEMPERATURE 5 DEG F (ADJ.) ABOVE THE UNOCCUPIED SETPOINT, THE VALVE SHALL CLOSE, AND THE FAN SHALL BE DE-ENERGIZED. 4. UNOCCUPIED COOLING MODE: UNOCCUPIED COOLING MODE: a. ON A RISE IN ZONE TEMPERATURE ABOVE THE UNOCCUPIED SETPOINT, MODULATE ON A RISE IN ZONE TEMPERATURE ABOVE THE UNOCCUPIED SETPOINT, MODULATE THE ZONE DAMPER TO MAINTAIN COOLING MAXIMUM AIRFLOW. b. THE HOT WATER REHEAT VALVE SHALL REMAIN CLOSED. THE HOT WATER REHEAT VALVE SHALL REMAIN CLOSED. c. THE AVERAGE OF ALL ZONE COOLING DEMAND VALUES DETERMINES WHEN THE THE AVERAGE OF ALL ZONE COOLING DEMAND VALUES DETERMINES WHEN THE ASSOCIATED AHU STARTS IN UNOCCUPIED MODE. REFER TO THE AHU SEQUENCE OF OPERATION FOR SPECIFIC SETTINGS AND PROVIDE COOLING DEMAND VALUES TO THE AHU FIELD CONTROLLER. 5. THE TIMED OVERRIDE BUTTON, IF ACTIVATED, SHALL SET ASSOCIATED VAV THE TIMED OVERRIDE BUTTON, IF ACTIVATED, SHALL SET ASSOCIATED VAV TEMPERATURE SETPOINTS TO THE OCCUPIED MODE FOR 2 HOURS (ADJ.). D. DISCHARGE AIR TEMPERATURE DISCHARGE AIR TEMPERATURE 1. A DISCHARGE AIR TEMPERATURE SENSOR SHALL BE PROVIDED ON EACH BOX FOR A DISCHARGE AIR TEMPERATURE SENSOR SHALL BE PROVIDED ON EACH BOX FOR MONITORING PURPOSES. E. EMERGENCY ATFP EMERGENCY ATFP 1. ACTIVATION OF THE EMERGENCY ATFP SWITCH SHALL, VIA SOFTWARE COMMANDS, ACTIVATION OF THE EMERGENCY ATFP SWITCH SHALL, VIA SOFTWARE COMMANDS, OVERRIDE VAV UNIT OPERATION AND CLOSE THE ZONE DAMPER. F. ALARM SETTINGS ALARM SETTINGS 1. GENERATE AN ALARM AT THE BAS IF THE ZONE TEMPERATURE EXCEEDS +/- 5 DEG GENERATE AN ALARM AT THE BAS IF THE ZONE TEMPERATURE EXCEEDS +/- 5 DEG F (ADJ.) FROM THE EFFECTIVE SETPOINT FOR MORE THAN 60 MINUTES (ADJ.).
AutoCAD SHX Text
VAV SEQUENCE OF OPERATIONS
AutoCAD SHX Text
EXISTING BACNET BUS
AutoCAD SHX Text
AHU
AutoCAD SHX Text
ENABLE SPEED STATUS
AutoCAD SHX Text
VFD
AutoCAD SHX Text
VAV (TYP.)
AutoCAD SHX Text
TELECOM SPACE SENSOR
AutoCAD SHX Text
SCALE: N.T.S.
AutoCAD SHX Text M802
AutoCAD SHX Text
MECHANICAL - HVAC CONTROLS
AutoCAD SHX Text NOTES: BACNET MS/TP COMMUNICATION LOOP SHALL BE HOME RUN CONNECTION BACK TO BUILDING AUTOMATION CONTROLLER LOCATED IN COMMUNICATION CLOSET A. INTEGRATE NEW DDC DEVICES TO JACE BUILDING AUTOMATION CONTROLLER LOCATED IN COMMUNICATION CLOSET A.