This document is a mechanical engineering control system diagram for a Design Wing Relocation project at Marine Corps Base Camp Lejeune, specifically focusing on Building 1005's exhaust fan and unit heater control systems. The technical drawing details multiple point lists including VHF points, exhaust fan/unit heater points, and communication room temperature sensor points, with comprehensive sequence of operations for various HVAC components. The diagram illustrates the control system architecture, showing interconnections between Air Handling Unit (AHU), Variable Frequency Drive (VFD), Variable Air Volume (VAV), and telecom space sensors on an existing bacnet bus. The document is part of construction documents for mechanical systems, specifically labeled as sheet M802 for Marine Corps Base construction work, indicating it is a detailed technical specification for HVAC control system design and integration.

View the file

Other files

File Type Posted
N4008524R2785 Amendment 0007.pdf PDF
M101_rev 2.pdf PDF
N4008524R2785 Amendment 0006.pdf PDF
VMR- uncapped.jpg JPG image
E-101.pdf PDF
E-105.pdf PDF
M103.pdf PDF
M104.pdf PDF
M602.pdf PDF
23 73 33_Amendment 2.pdf PDF
E-103.pdf PDF
E-104.pdf PDF
E-107.pdf PDF
M601.pdf PDF
VMR- capped.jpg JPG image
T-1.pdf PDF
25 05 11.00.pdf PDF
A-105.pdf PDF
A-501.pdf PDF
E-102.pdf PDF
M501.pdf PDF
N4008524R2785 Amendment 0005.pdf PDF
23 09 00.pdf PDF
23 09 23.13 20 Attachment 4.pdf PDF
01 32 16.00 20.pdf PDF
22 00 00.pdf PDF
23 09 23.13 20 Attachment 2.pdf PDF
23 09 13.pdf PDF
23 09 23.02.pdf PDF
Attachment N - Revised Eletrical-Telecomm Sheets.pdf PDF
Attachment O - Revised Specs pg3.pdf PDF
Attachment M - Specifications TOC.pdf PDF
N4008524R2785 Amendment 0003.pdf PDF
Attachment P - Site Visit Log.pdf PDF
N4008524R2785 Amendment 0002.pdf PDF
Attachment I - Site Visit Information REVISED.pdf PDF
Attachment I - Site Visit Information.pdf PDF
Attachment J - Site Visit Participant Log.xlsx XLSX spreadsheet
Attachment L - Electrical Room.pdf PDF
N4008524R2785 Amendment 0001.pdf PDF
Attachment K - Asbestos Inspection Report.pdf PDF
Attachment A - PPI LOG TEMPLATE.xlsx XLSX spreadsheet
Attachment B - CONSTRUCTION AND DESIGN EXPERIENCE PROJECT DATA.docx DOCX document
Attachment E - B1005 Drawings.pdf PDF
Attachment F - B1005 Specifications.pdf PDF
Attachment H - PIEE VENDOR ACCESS INSTRUCTIONS.pdf PDF
N4008524R2785 Small Business Marine Corps MACC for General Construction.pdf PDF
Attachment C- PAST PERFORMANCE QUESTIONNAIRE.docx DOCX document
Attachment D - B1005 Price Proposal Form.docx DOCX document
Attachment G - B1005 Statement of Work.pdf PDF
Show 40 more

50 files listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

DESIGN WING RELOCATION

BUILDING 1005

EXHAUST FAN/UNIT HEATER CONTROL DIAGRAM2

COMM ROOM 313 TEMPERATURE3

VAV CONTROL DIAGRAM1

CONTROL SYSTEM ARCHITECTURE4

AutoCAD SHX Text

J F ORR PE

AutoCAD SHX Text

SATISFACTORY TO: DATE

AutoCAD SHX Text

APPROVED: PWO OR OICC DATE

AutoCAD SHX Text

DESIGN DIR.

AutoCAD SHX Text

SUBMITTED BY:

AutoCAD SHX Text

DR.

AutoCAD SHX Text

CHK.

AutoCAD SHX Text

DES.

AutoCAD SHX Text

R DUNCAN

AutoCAD SHX Text

C MAAS

AutoCAD SHX Text

CAMP LEJEUNE, NORTH CAROLINA

AutoCAD SHX Text

CONST. CONTR.

AutoCAD SHX Text

MARINE CORPS BASE

AutoCAD SHX Text

DEPARTMENT OF THE NAVY NAVAL FACILITIES ENGINEERING SYSTEMS COMMAND

AutoCAD SHX Text E1

AutoCAD SHX Text

SIZE

AutoCAD SHX Text 80091

AutoCAD SHX Text

CODE IDENT. NO

AutoCAD SHX Text

NAVFAC DRAWING NO.

AutoCAD SHX Text M802

AutoCAD SHX Text

C MAAS

AutoCAD SHX Text

K ROOT

AutoCAD SHX Text

NA

AutoCAD SHX Text 60036683

AutoCAD SHX Text 21-0019

AutoCAD SHX Text

SCALE: NOTED

AutoCAD SHX Text

SHEET OF

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

SPEC.

AutoCAD SHX Text 05-21-0019

AutoCAD SHX Text

SYM

AutoCAD SHX Text

DATE

AutoCAD SHX Text

APPROVED

AutoCAD SHX Text

REVISIONS

AutoCAD SHX Text

NC

AutoCAD SHX Text

OUTSIDE AIR

AutoCAD SHX Text

NC

AutoCAD SHX Text

EXHAUST TO EXTERIOR

AutoCAD SHX Text

MECHANICAL ROOM

AutoCAD SHX Text S

AutoCAD SHX Text

GRAVITY BACKDRAFT DAMPER

AutoCAD SHX Text

CT

AutoCAD SHX Text M

AutoCAD SHX Text

BI - EF1 STATUS

AutoCAD SHX Text

AI - ZONE TEMPERATURE

AutoCAD SHX Text

BI - ZONE OCCUPANCY OVERRIDE

AutoCAD SHX Text

EXHAUST FAN/UNIT HEATER POINTS LIST

AutoCAD SHX Text

SOFTWARE POINTS

AutoCAD SHX Text

MECH. ZONE TEMPERATURE

AutoCAD SHX Text

POINT NAME

AutoCAD SHX Text

MECH. ZONE OVERRIDE

AutoCAD SHX Text

EF1 STATUS

AutoCAD SHX Text

UH1 STATUS

AutoCAD SHX Text

HARDWARE POINTS

AutoCAD SHX Text X

AutoCAD SHX Text

AI

AutoCAD SHX Text

AO

AutoCAD SHX Text

BI

AutoCAD SHX Text

BO

AutoCAD SHX Text

AV

AutoCAD SHX Text

BV

AutoCAD SHX Text

LOOP

AutoCAD SHX Text

SCHED

AutoCAD SHX Text

TREND

AutoCAD SHX Text

ALARM

AutoCAD SHX Text

SHOW ON

AutoCAD SHX Text

GRAPHIC

AutoCAD SHX Text X

AutoCAD SHX Text X

AutoCAD SHX Text X

AutoCAD SHX Text X

AutoCAD SHX Text X

AutoCAD SHX Text X

AutoCAD SHX Text X

AutoCAD SHX Text X

AutoCAD SHX Text X

AutoCAD SHX Text X

AutoCAD SHX Text X

AutoCAD SHX Text X

AutoCAD SHX Text

SCALE: N.T.S.

AutoCAD SHX Text M802

AutoCAD SHX Text GENERAL: WHEN THE SPACE TEMPERATURE IS ABOVE 85°F (ADJUSTABLE), THE MOTORIZED OUTSIDE AIR DAMPER SHALL OPEN AND THE EXHAUST FAN SHALL ENERGIZE. WHEN THE SPACE TEMPERATURE IS BELOW 85°F (ADJUSTABLE), THE MOTORIZED OUTSIDE AIR DAMPER SHALL CLOSE AND THE EXHAUST FAN SHALL DE-ENERGIZE. WHEN THE SPACE TEMPERATURE IS BELOW 50°F (ADJUSTABLE), THE UNIT HEATER SHALL ENERGIZE. WHEN THE SPACE TEMPERATURE IS ABOVE 60°F (ADJUSTABLE), THE UNIT HEATER SHALL DE-ENERGIZE. MANUAL: WHEN INITIATED, THE MOTORIZED OUTSIDE AIR DAMPER SHALL OPEN AND THE EXHAUST FAN SHALL RUN FOR A MAXIMUM DURATION OF 60 MINUTES (ADJUSTABLE). AFTER 60 MINUTES (ADJUSTABLE), THE MOTORIZED OUTSIDE AIR DAMPER SHALL CLOSE AND THE EXHAUST FAN SHALL DE-ENERGIZE. ALARMS: IF THE MOTORIZED OUTSIDE AIR DAMPER STATUS DOES NOT MATCH THE COMMAND AFTER 90 SECONDS (ADJUSTABLE) AFTER BEING COMMANDED OPEN, AN ALARM WILL BE GENERATED. IF THE UNIT HEATER STATUS DOES NOT MATCH THE COMMAND AFTER 90 SECONDS (ADJUSTABLE) AFTER BEING COMMANDED ON, AN ALARM WILL BE GENERATED. IF THE EXHAUST FAN STATUS DOES NOT MATCH THE COMMAND AFTER 90 SECONDS (ADJUSTABLE) AFTER BEING COMMANDED ON, AN ALARM WILL BE GENERATED. MECH. ZONE TEMPERATURE SHALL HAVE AN ADJUSTABLE LOW AND HIGH ALARM LIMIT.

AutoCAD SHX Text

EXHAUST FAN/UNIT HEATER SEQUENCE OF OPERATIONS

AutoCAD SHX Text

UH1 FAILURE

AutoCAD SHX Text X

AutoCAD SHX Text

OUTSIDE AIR DAMPER FAILURE

AutoCAD SHX Text X

AutoCAD SHX Text

OUTSIDE AIR DAMPER STATUS

AutoCAD SHX Text X

AutoCAD SHX Text X

AutoCAD SHX Text X

AutoCAD SHX Text X

AutoCAD SHX Text

EF1 FAILURE

AutoCAD SHX Text X

AutoCAD SHX Text X

AutoCAD SHX Text

BI - OUTSIDE AIR DAMPER STATUS

AutoCAD SHX Text

UNIT HEATER

AutoCAD SHX Text X

AutoCAD SHX Text

COMMUNICATION ROOM 313 TEMPERATURE SENSOR POINTS LIST

AutoCAD SHX Text

SOFTWARE POINTS

AutoCAD SHX Text

ZONE TEMPERATURE

AutoCAD SHX Text

POINT NAME

AutoCAD SHX Text

HIGH ZONE TEMPERATURE

AutoCAD SHX Text

HARDWARE POINTS

AutoCAD SHX Text X

AutoCAD SHX Text

AI

AutoCAD SHX Text

AO

AutoCAD SHX Text

BI

AutoCAD SHX Text

BO

AutoCAD SHX Text

AV

AutoCAD SHX Text

BV

AutoCAD SHX Text

LOOP

AutoCAD SHX Text

SCHED

AutoCAD SHX Text

TREND

AutoCAD SHX Text

ALARM

AutoCAD SHX Text

SHOW ON

AutoCAD SHX Text

GRAPHIC

AutoCAD SHX Text X

AutoCAD SHX Text X

AutoCAD SHX Text X

AutoCAD SHX Text

SCALE: N.T.S.

AutoCAD SHX Text M802

AutoCAD SHX Text GENERAL: TEMPERATURE SENSOR SHALL MONITOR THE ZONE TEMPERATURE OF THE COMMUNICATIONS ROOM. ALARMS: ZONE TEMPERATURE SHALL HAVE AN ADJUSTABLE HIGH ALARM LIMIT INITIALLY SET TO 80°F (ADJ.).

AutoCAD SHX Text

COMMUNICATION ROOM 313 SEQUENCE OF OPERATIONS

AutoCAD SHX Text X

AutoCAD SHX Text

DA

AutoCAD SHX Text

SA

AutoCAD SHX Text

AI - AIRFLOW

AutoCAD SHX Text M

AutoCAD SHX Text

AO - ZONE DAMPER

AutoCAD SHX Text

HHW

AutoCAD SHX Text

AI - DISCHARGE AIR TEMP

AutoCAD SHX Text T

AutoCAD SHX Text

AO - HEATING VALVE

AutoCAD SHX Text M

AutoCAD SHX Text

HHWR

AutoCAD SHX Text

HHWS

AutoCAD SHX Text

VAV POINTS LIST

AutoCAD SHX Text

SOFTWARE POINTS

AutoCAD SHX Text

ZONE TEMPERATURE

AutoCAD SHX Text

POINT NAME

AutoCAD SHX Text

ZONE WARM/COOL ADJUST

AutoCAD SHX Text

ZONE TEMPERATURE SETPOINT

AutoCAD SHX Text

AIRFLOW

AutoCAD SHX Text

HARDWARE POINTS

AutoCAD SHX Text X

AutoCAD SHX Text

AI

AutoCAD SHX Text

AO

AutoCAD SHX Text

BI

AutoCAD SHX Text

BO

AutoCAD SHX Text

AV

AutoCAD SHX Text

BV

AutoCAD SHX Text

LOOP

AutoCAD SHX Text

SCHED

AutoCAD SHX Text

TREND

AutoCAD SHX Text

ALARM

AutoCAD SHX Text

SHOW ON

AutoCAD SHX Text

GRAPHIC

AutoCAD SHX Text X

AutoCAD SHX Text X

AutoCAD SHX Text X

AutoCAD SHX Text X

AutoCAD SHX Text X

AutoCAD SHX Text X

AutoCAD SHX Text X

AutoCAD SHX Text X

AutoCAD SHX Text X

AutoCAD SHX Text X

AutoCAD SHX Text

AIRFLOW SETPOINT

AutoCAD SHX Text X

AutoCAD SHX Text X

AutoCAD SHX Text

ZONE DAMPER SETPOINT

AutoCAD SHX Text X

AutoCAD SHX Text

ZONE DAMPER

AutoCAD SHX Text X

AutoCAD SHX Text X

AutoCAD SHX Text X

AutoCAD SHX Text

EFFECTIVE HEATING SETPOINT

AutoCAD SHX Text X

AutoCAD SHX Text X

AutoCAD SHX Text X

AutoCAD SHX Text X

AutoCAD SHX Text X

AutoCAD SHX Text X

AutoCAD SHX Text X

AutoCAD SHX Text

HEATING VALVE

AutoCAD SHX Text X

AutoCAD SHX Text X

AutoCAD SHX Text X

AutoCAD SHX Text

EFFECTIVE COOLING SETPOINT

AutoCAD SHX Text X

AutoCAD SHX Text X

AutoCAD SHX Text X

AutoCAD SHX Text

HEATING VALVE SETPOINT

AutoCAD SHX Text X

AutoCAD SHX Text X

AutoCAD SHX Text X

AutoCAD SHX Text

ZONE OCCUPANCY OVERRIDE

AutoCAD SHX Text X

AutoCAD SHX Text X

AutoCAD SHX Text X

AutoCAD SHX Text

DISCHARGE AIR TEMPERATURE

AutoCAD SHX Text X

AutoCAD SHX Text X

AutoCAD SHX Text X

AutoCAD SHX Text

HIGH ZONE TEMEPRATURE

AutoCAD SHX Text X

AutoCAD SHX Text

LOW ZONE TEMPERATURE

AutoCAD SHX Text X

AutoCAD SHX Text X

AutoCAD SHX Text

SCALE: N.T.S.

AutoCAD SHX Text M802

AutoCAD SHX Text X

AutoCAD SHX Text

AI - ZONE WARM/COOL ADJUST

AutoCAD SHX Text T

AutoCAD SHX Text

AI - MECH. ZONE TEMPERATURE

AutoCAD SHX Text

BI - MECH. ZONE OVERRIDE

AutoCAD SHX Text T

AutoCAD SHX Text

AI - ZONE TEMPERATURE

AutoCAD SHX Text T

AutoCAD SHX Text A. SETPOINTS AND AIRFLOW SETTINGS SETPOINTS AND AIRFLOW SETTINGS 1. PROGRAM TEMPERATURE SETPOINTS PROGRAM TEMPERATURE SETPOINTS a. OCCUPIED ACTIVE TEMPERATURE SETPOINT (°F) PER RESET SCHEDULE OCCUPIED ACTIVE TEMPERATURE SETPOINT (°F) PER RESET SCHEDULE 1) 70°F @ 50°F OUTSIDE AMBIENT 70°F @ 50°F OUTSIDE AMBIENT 2) 76°F @ 80°F OUTSIDE AMBIENT 76°F @ 80°F OUTSIDE AMBIENT 3) BETWEEN 50°F AND 80°F, RESET ADJUSTMENTS SHALL BE LINEAR BETWEEN 50°F AND 80°F, RESET ADJUSTMENTS SHALL BE LINEAR b. UNOCCUPIED TEMPERATURE SETPOINTS (°F) UNOCCUPIED TEMPERATURE SETPOINTS (°F) 1) 60°F HEATING 60°F HEATING 2) 80°F COOLING 80°F COOLING c. THE ZONE EFFECTIVE SETPOINT SHALL BE THE OCCUPIED ZONE SETPOINT PLUS THE ZONE EFFECTIVE SETPOINT SHALL BE THE OCCUPIED ZONE SETPOINT PLUS THE OCCUPANT OFFSET OF +/-2°F (ADJ.). d. THE OFFSET BETWEEN HEATING VALVE (HEATING), THE PRIMARY AIR DAMPER THE OFFSET BETWEEN HEATING VALVE (HEATING), THE PRIMARY AIR DAMPER (COOLING) AND THE ZONE EFFECTIVE SETPOINT SHALL BE NO LESS THAN +/- 1F. 2. PROGRAM ALL VAV TERMINAL UNIT FLOW SET POINTS PER SCHEDULE PROGRAM ALL VAV TERMINAL UNIT FLOW SET POINTS PER SCHEDULE a. COOLING MAXIMUM AIRFLOW SETPOINT (CFM) COOLING MAXIMUM AIRFLOW SETPOINT (CFM) b. COOLING MINIMUM AIRFLOW SETPOINT (CFM) COOLING MINIMUM AIRFLOW SETPOINT (CFM) c. HEATING AIRFLOW SETPOINT (CFM) HEATING AIRFLOW SETPOINT (CFM) B. OCCUPIED CONTROL SEQUENCE: OCCUPIED CONTROL SEQUENCE: OCCUPIED AND UNOCCUPIED MODE SHALL BE DETERMINED BY THE ASSOCIATED AHU SCHEDULE. HEATING VALVE AND PRIMARY AIR DAMPER SHALL MODULATE TO MAINTAIN THE ZONE EFFECTIVE SETPOINT. 1. HEATING MODE: HEATING MODE: a. MODULATE THE HOT WATER RE-HEAT VALVE TO MAINTAIN ZONE EFFECTIVE MODULATE THE HOT WATER RE-HEAT VALVE TO MAINTAIN ZONE EFFECTIVE TEMPERATURE SETPOINT. 2. COOLING MODE: COOLING MODE: a. MODULATE THE ZONE DAMPER BETWEEN SCHEDULED COOLING MINIMUM AIRFLOW MODULATE THE ZONE DAMPER BETWEEN SCHEDULED COOLING MINIMUM AIRFLOW AND COOLING MAXIMUM AIRFLOW TO MAINTAIN ZONE EFFECTIVE TEMPERATURE SETPOINT. C. UNOCCUPIED CONTROL SEQUENCE: UNOCCUPIED CONTROL SEQUENCE: 1. VAV UNITS SHALL CONTROL TO THEIR UNOCCUPIED HEATING OR COOLING SETPOINTS VAV UNITS SHALL CONTROL TO THEIR UNOCCUPIED HEATING OR COOLING SETPOINTS DURING UNOCCUPIED PERIODS. 2. THE AHU WILL START ONLY DURING UNOCCUPIED COOLING MODE BASED ON ITS THE AHU WILL START ONLY DURING UNOCCUPIED COOLING MODE BASED ON ITS UNOCCUPIED SEQUENCE. 3. UNOCCUPIED HEATING MODE: UNOCCUPIED HEATING MODE: a. ON A DROP IN ZONE TEMPERATURE BELOW THE UNOCCUPIED SETPOINT THE ON A DROP IN ZONE TEMPERATURE BELOW THE UNOCCUPIED SETPOINT THE TERMINAL UNIT SHALL BE ENERGIZED, AND THE HOT WATER REHEAT VALVE SHALL BE SET TO 100% OPEN. b. ON A RISE IN ZONE TEMPERATURE 5 DEG F (ADJ.) ABOVE THE UNOCCUPIED ON A RISE IN ZONE TEMPERATURE 5 DEG F (ADJ.) ABOVE THE UNOCCUPIED SETPOINT, THE VALVE SHALL CLOSE, AND THE FAN SHALL BE DE-ENERGIZED. 4. UNOCCUPIED COOLING MODE: UNOCCUPIED COOLING MODE: a. ON A RISE IN ZONE TEMPERATURE ABOVE THE UNOCCUPIED SETPOINT, MODULATE ON A RISE IN ZONE TEMPERATURE ABOVE THE UNOCCUPIED SETPOINT, MODULATE THE ZONE DAMPER TO MAINTAIN COOLING MAXIMUM AIRFLOW. b. THE HOT WATER REHEAT VALVE SHALL REMAIN CLOSED. THE HOT WATER REHEAT VALVE SHALL REMAIN CLOSED. c. THE AVERAGE OF ALL ZONE COOLING DEMAND VALUES DETERMINES WHEN THE THE AVERAGE OF ALL ZONE COOLING DEMAND VALUES DETERMINES WHEN THE ASSOCIATED AHU STARTS IN UNOCCUPIED MODE. REFER TO THE AHU SEQUENCE OF OPERATION FOR SPECIFIC SETTINGS AND PROVIDE COOLING DEMAND VALUES TO THE AHU FIELD CONTROLLER. 5. THE TIMED OVERRIDE BUTTON, IF ACTIVATED, SHALL SET ASSOCIATED VAV THE TIMED OVERRIDE BUTTON, IF ACTIVATED, SHALL SET ASSOCIATED VAV TEMPERATURE SETPOINTS TO THE OCCUPIED MODE FOR 2 HOURS (ADJ.). D. DISCHARGE AIR TEMPERATURE DISCHARGE AIR TEMPERATURE 1. A DISCHARGE AIR TEMPERATURE SENSOR SHALL BE PROVIDED ON EACH BOX FOR A DISCHARGE AIR TEMPERATURE SENSOR SHALL BE PROVIDED ON EACH BOX FOR MONITORING PURPOSES. E. EMERGENCY ATFP EMERGENCY ATFP 1. ACTIVATION OF THE EMERGENCY ATFP SWITCH SHALL, VIA SOFTWARE COMMANDS, ACTIVATION OF THE EMERGENCY ATFP SWITCH SHALL, VIA SOFTWARE COMMANDS, OVERRIDE VAV UNIT OPERATION AND CLOSE THE ZONE DAMPER. F. ALARM SETTINGS ALARM SETTINGS 1. GENERATE AN ALARM AT THE BAS IF THE ZONE TEMPERATURE EXCEEDS +/- 5 DEG GENERATE AN ALARM AT THE BAS IF THE ZONE TEMPERATURE EXCEEDS +/- 5 DEG F (ADJ.) FROM THE EFFECTIVE SETPOINT FOR MORE THAN 60 MINUTES (ADJ.).

AutoCAD SHX Text

VAV SEQUENCE OF OPERATIONS

AutoCAD SHX Text

EXISTING BACNET BUS

AutoCAD SHX Text

AHU

AutoCAD SHX Text

ENABLE SPEED STATUS

AutoCAD SHX Text

VFD

AutoCAD SHX Text

VAV (TYP.)

AutoCAD SHX Text

TELECOM SPACE SENSOR

AutoCAD SHX Text

SCALE: N.T.S.

AutoCAD SHX Text M802

AutoCAD SHX Text

MECHANICAL - HVAC CONTROLS

AutoCAD SHX Text NOTES: BACNET MS/TP COMMUNICATION LOOP SHALL BE HOME RUN CONNECTION BACK TO BUILDING AUTOMATION CONTROLLER LOCATED IN COMMUNICATION CLOSET A. INTEGRATE NEW DDC DEVICES TO JACE BUILDING AUTOMATION CONTROLLER LOCATED IN COMMUNICATION CLOSET A.

AutoCAD SHX Text

CONSTRUCTION DOCUMENTS

AutoCAD SHX Text

AMENDMENT 2. UPDATED DSS SEQUENCE

AutoCAD SHX Text 03/28/25

AutoCAD SHX Text

AutoCAD SHX Text

Sheets and Views
M802