About this file

This document is an electrical design drawing (E-101) for the Design Wing Relocation project at Marine Corps Base, specifically Building 1005. The drawing provides a comprehensive electrical devices mounting height legend and a set of 40 detailed general notes covering electrical installation requirements. Key specifications include:

Electrical installation guidelines cover critical aspects such as code compliance (NFPA 70), equipment installation standards, conductor and raceway routing, grounding requirements, and safety protocols. Specific technical requirements include using flexible conduit for vibrating equipment, maintaining minimum conductor sizes (#12 or #10 AWG), installing ground fault circuit interrupters, coordinating with mechanical trades, and following precise mounting height standards for electrical devices like receptacles, switches, and exit signs. The drawing also emphasizes contractor responsibilities for site verification, equipment coordination, and ensuring fully functional and code-compliant electrical systems.

View the file

Other files

File Type Posted
N4008524R2785 Amendment 0007.pdf PDF
N4008524R2785 Amendment 0006.pdf PDF
VMR- uncapped.jpg JPG image
E-105.pdf PDF
M103.pdf PDF
M104.pdf PDF
M602.pdf PDF
23 73 33_Amendment 2.pdf PDF
E-103.pdf PDF
E-104.pdf PDF
E-107.pdf PDF
M601.pdf PDF
A-202.pdf PDF
E-106.pdf PDF
M802.pdf PDF
VMR- capped.jpg JPG image
T-1.pdf PDF
N4008524R2785 Amendment 0005.pdf PDF
23 09 00.pdf PDF
23 09 23.13 20 Attachment 4.pdf PDF
01 32 16.00 20.pdf PDF
22 00 00.pdf PDF
23 09 23.13 20 Attachment 2.pdf PDF
N4008524R2785 Amendment 0004.pdf PDF
Attachment Q - Revised Drawings.pdf PDF
23 09 23.13 20 Attachment 5.pdf PDF
23 09 13.pdf PDF
23 09 23.02.pdf PDF
Attachment N - Revised Eletrical-Telecomm Sheets.pdf PDF
Attachment O - Revised Specs pg3.pdf PDF
Attachment M - Specifications TOC.pdf PDF
N4008524R2785 Amendment 0003.pdf PDF
Attachment P - Site Visit Log.pdf PDF
N4008524R2785 Amendment 0002.pdf PDF
Attachment I - Site Visit Information REVISED.pdf PDF
Attachment I - Site Visit Information.pdf PDF
Attachment J - Site Visit Participant Log.xlsx XLSX spreadsheet
Attachment L - Electrical Room.pdf PDF
N4008524R2785 Amendment 0001.pdf PDF
Attachment K - Asbestos Inspection Report.pdf PDF
N4008524R2785 Small Business Marine Corps MACC for General Construction.pdf PDF
Attachment A - PPI LOG TEMPLATE.xlsx XLSX spreadsheet
Attachment B - CONSTRUCTION AND DESIGN EXPERIENCE PROJECT DATA.docx DOCX document
Attachment E - B1005 Drawings.pdf PDF
Attachment F - B1005 Specifications.pdf PDF
Attachment H - PIEE VENDOR ACCESS INSTRUCTIONS.pdf PDF
N4008524R2785 Small Business Marine Corps MACC for General Construction.pdf PDF
Attachment C- PAST PERFORMANCE QUESTIONNAIRE.docx DOCX document
Attachment D - B1005 Price Proposal Form.docx DOCX document
Attachment G - B1005 Statement of Work.pdf PDF
Show 40 more

50 files listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

CONST. CONTR. NO.

REVISION 1.2 E-101

K. BROWN

K. BROWN

K. BROWN

K. ROOT

F. ORR

DESIGN WING RELOCATION

BUILDING 1005

LEGEND, NOTES, AND ABBREVIATIONS

60036661 21-0019

NOTED NA 14 36

GENERAL NOTESELECTRICAL LEGEND

LIGHTING PANEL, LIGHT POLE

LIGHTING

MAIN CIRCUIT BREAKER

MOTOR CONTROL CENTER

MOTOR CIRCUIT PROTECTOR

MAIN DISTRIBUTION PANEL

MANUFACTURER

MANHOLE

MAIN LUGS ONLY

MOUNTED

MOUNTING

MANUAL TRANSFER SWITCH

MEDIUM VOLTAGE

NEUTRAL

NOT APPLICABLE

NORMALLY CLOSED

NATIONAL ELECTRIC CODE

NOT IN CONTRACT

NIGHT LIGHT

NORMALLY OPEN

NOT TO SCALE

POLE

PUBLIC ADDRESS

PULL BOX, PUSH-BUTTON

POWER FACTOR

PHASE

PROGRAMMABLE LOGIC CONTROLLER

PANEL

POWER PANEL, POWER POLE

PORTABLE POWER EQUIPMENT CABLE

POTENTIAL TRANSFORMER

POWER

RECEPTACLE

REQUIRED

RIGID GALVANIZED STEEL CONDUIT

ROOM

REMOTE TELEMETRY UNIT

DC MOTOR DRIVE

SHEET

SURGE PROTECTION DEVICE

SPECIFICATION

SELECTOR SWITCH

STAINLESS STEEL

SWITCH

SWITCHBOARD

SWITCH GEAR

TELEPHONE

TWISTED PAIR SHIELDED

TRANSIENT VOLTAGE SURGE SUPPRESSER

TYPICAL

UNDERGROUND

UNIT HEATER

UNLESS OTHERWISE NOTED

UTILITY

VOLTS

VARIABLE FREQUENCY DRIVE

WIRE, WATT

WATT-HOUR

WEATHERPROOF

WEATHERPROOF TELEPHONE ENCLOSURE

TRANSFORMER

EXISTING RELOCATED

A, AMP

AFF

AFG

AHU

AIC

ATS

AWG

BOF

BRKR

C, CND

CAB

CAT

CL

CB

CCTV

CKT

CLG

CP

CR

CS

CV

CT

CU

EF

EMER

EMT

ENCL

EQUIP

EWC

EWH

EPRF

FA

FAAP

FACP

FBO

FLA

FLUOR

FLR

FWE

GEN

G, GND

GFCI

HH

HID

HOA

HP

HPF

HPS

HTR

HV

Hz

IMC

INCAND

JB

K

KCMIL

KVA

KW

KWH

AMPERE

ABOVE FINISHED FLOOR

ABOVE FINISHED GRADE

AIR HANDLING UNIT

AMPERE INTERRUPTING CAPACITY

AUTOMATIC TRANSFER SWITCH

AMERICAN WIRE GAUGE

BOTTOM OF FIXTURE

BREAKER

CONDUIT

CABINET

CATALOG

CHLORINE

CIRCUIT BREAKER

CLOSED CIRCUIT TELEVISION

CIRCUIT

CEILING

CONTROL PANEL

CONTROL RELAY, CORROSION RESISTANT

CONTROL SWITCH

CONTROL VALVE

CURRENT TRANSFORMER

COPPER

EXHAUST FAN

EMERGENCY

ELECTRICAL METALLIC TUBING

ENCLOSURE

EQUIPMENT

ELECTRIC WATER COOLER

ELECTRIC WATER HEATER

EXPLOSION PROOF

FIRE ALARM

FIRE ALARM ANNUNCIATOR PANEL

FIRE ALARM CONTROL PANEL

FURNISHED BY OTHERS

FULL LOAD AMPS

FLUORESCENT

FLOOR

FURNISHED WITH EQUIPMENT

GENERATOR

GROUND

GROUND FAULT CURRENT INTERRUPTER

HANDHOLE

HIGH INTENSITY DISCHARGE

HAND-OFF-AUTO

HORSE POWER

HIGH POWER FACTOR

HIGH PRESSURE SODIUM

HEATER

HIGH VOLTAGE

HERTZ

INTERMEDIATE METALLIC CONDUIT

INCANDESCENT

JUNCTION BOX

THOUSAND

THOUSAND CIRCULAR MILLS

KILOVOLT AMPERE

KILOWATTS

KILOWATT-HOURS

SYMBOL DESCRIPTION

LP

LTG

MCB

MCC

MCP

MDP

MFR

MH

MLO

MTD

MTG

MTS

MV

N / NEUT

NA

NC

NEC

NIC

NL

NO

NTS

P

PA

PB

PF

PH

PLC

PNL

P

PPE

PT

PWR

RECPT, RCP

REQ'D

RGS

RM

RTU

DCM

SH

SPD

SPEC

SS

SST

SW

SWBD

SWGR

TEL

TPS

TVSS

TYP

UGND

UH

UON

UTIL

V

VFD

W

WH

WP

WTE

XFMR

X/R

1. ALL ELECTRICAL WORK MUST BE IN FULL COMPLIANCE WITH NFPA 70 THE NORTH

CAROLINA STATE BUILDING CODE, ALL LOCAL CODES AND ORDINANCES AND IN

ACCORDANCE WITH THE REQUIREMENTS OF THE LOCAL AUTHORITY HAVING

JURISDICTION.

2. ALL EQUIPMENT PROVIDED BY THE CONTRACTOR MUST BE LISTED AND LABELED

BY A NATIONALLY-RECOGNIZED TESTING AGENCY, ACCEPTABLE TO THE

AUTHORITY HAVING JURISDICTION, FOR THE CONDITIONS OF INSTALLATION. ALL

MATERIAL, EQUIPMENT AND DEVICES MUST BE NEW CURRENT PRODUCTS OF

MANUFACTURERS REGULARLY ENGAGED IN THE PRODUCTION OF SUCH

PRODUCTS. EQUIPMENT MUST BE SUITABLE FOR ITS APPLICATION (E.G. WHEN

INSTALLED OUTDOORS, IT MUST BE WEATHERPROOF, ETC.)

3. THE CONTRACTOR MUST REVIEW ALL DRAWINGS AND SPECIFICATIONS FOR

WORK REQUIREMENTS, THE AMOUNT OF SPACE AVAILABLE FOR ELECTRICAL

EQUIPMENT, AND LAYOUT HIS WORK IN A COMPATIBLE AND FUNCTIONAL MANNER.

4. UNLESS SPECIFICALLY NOTED OTHERWISE, SYSTEMS PROVIDED OR INSTALLED

BY THE CONTRACTOR MUST BE COMPLETE AND FULLY-FUNCTIONING AFTER

INSTALLATION. INCIDENTAL COMPONENTS MAY NOT BE SHOWN, AND ALL WORK

WHICH MAY BE REASONABLY IMPLIED AS BEING INCIDENTAL TO THIS WORK, BUT

REQUIRED FOR THE PROPER OPERATION OF THE EQUIPMENT OR SYSTEM MUST

BE PROVIDED BY THE CONTRACTOR AND INCLUDED IN THE BID. ADDITIONAL

CIRCUITS MUST BE INSTALLED WHEREVER NEEDED TO CONFORM TO THE

SPECIFIC REQUIREMENTS OF EQUIPMENT.

5. TEMPORARY POWER CONNECTIONS AS REQUIRED MUST BE PROVIDED BY THE

CONTRACTOR AND INCLUDED IN THE BID. ALL TEMPORARY EQUIPMENT WIRING

MUST BE IN ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE. THE

CONTRACTOR MUST PROVIDE DETAILS, METHODS, MATERIALS, ETC. FOR REVIEW

PRIOR TO MAKING TEMPORARY CONNECTIONS. FURNISH AND INSTALL ALL

EQUIPMENT AND MATERIALS INCLUDING CONTROL EQUIPMENT, MOTOR

STARTERS, BRANCH AND FEEDER CIRCUIT BREAKERS, PANELBOARDS,

TRANSFORMERS, ETC. FOR TEMPORARY POWER. COORDINATE WITH THE UTILITY

PROVIDER AS REQUIRED.

6. THE WORK MUST INCLUDE COMPLETE TESTING OF ALL EQUIPMENT AND WIRING

AT THE COMPLETION OF WORK AND ANY MINOR CORRECTIONS, CHANGES OR

ADJUSTMENTS NECESSARY FOR THE PROPER FUNCTIONING OF THE SYSTEM AND

EQUIPMENT.

7. ALL ELECTRICAL EQUIPMENT MUST, AT ALL TIMES DURING CONSTRUCTION, BE

ADEQUATELY PROTECTED AGAINST MECHANICAL INJURY, OR DAMAGE BY WATER

AND/OR THE ELEMENTS. ELECTRICAL EQUIPMENT MUST NOT BE STORED OUT OF

DOORS, BUT MUST BE STORED IN DRY PERMANENT SHELTERS. IF AN APPARATUS

HAS BEEN DAMAGED, OR HAS BEEN SUBJECT TO POSSIBLE INJURY BY WATER OR

THE ELEMENTS, SUCH DAMAGE MUST BE REPLACED AT NO ADDITIONAL COST.

8. DO NOT SCALE ELECTRICAL DRAWINGS. CONTRACTOR MUST FIELD VERIFY ALL

DIMENSIONS.

9. CIRCUIT LAYOUTS ARE NOT INTENDED TO SHOW THE NUMBER OF FITTINGS, OR

OTHER INSTALLATION DETAILS. UNLESS NOTED OTHERWISE, THE EXACT

ROUTING OF FEEDER AND BRANCH CIRCUIT RACEWAYS AND CABLES IS THE

RESPONSIBILITY OF THE CONTRACTOR. RISER AND GENERAL CIRCUIT

ARRANGEMENTS ARE SHOWN SCHEMATICALLY/DIAGRAMMATICALLY ONLY. THE

CONTRACTOR MUST ROUTE CONDUITS AS REQUIRED BY THE CONDITIONS OF THE

INSTALLATION.

10. DEVICE LOCATIONS SHOWN ON THE DRAWINGS ARE APPROXIMATE. ADJUST

EXACT LOCATIONS AS REQUIRED TO SERVE THE INTENDED PURPOSE AND TO

AVOID CONFLICTS AND INTERFERENCES WITH OTHER TRADES. IF NOT SHOWN ON

THE ARCHITECTURAL DRAWINGS OR DIMENSIONED ON THE ELECTRICAL

DRAWINGS, VERIFY EXACT LOCATION WITH THE GOVERNMENT PRIOR TO

ROUGH-IN.

11. CONDUIT TERMINATING IN PRESSED STEEL BOXES MUST HAVE DOUBLE

LOCKNUTS AND INSULATED BUSHINGS. CONDUITS TERMINATING IN GASKETED

ENCLOSURES MUST BE TERMINATED WITH GROUNDING TYPE CONDUIT HUBS.

12. BRANCH CIRCUIT HOMERUNS SHOWN ON DRAWINGS INDICATE PHASE

CONDUCTORS, NEUTRAL, EQUIPMENT GROUND CONDUCTORS AS REQUIRED.

ADDITIONAL CONDUCTORS REQUIRED FOR CONTROL MUST BE INCLUDED EVEN IF

NOT EXPLICITLY SHOWN.

13. SEAL ALL CONDUIT OPENINGS THROUGH EXTERIOR BUILDING WALLS AND ROOF

WATERTIGHT.

14. IN WET LOCATIONS AND EXTERIOR, ALL WIRING DEVICES MUST BE

WEATHER-RESISTANT LISTED WITH WEATHERPROOF WHILE IN USE COVER.

15. RACEWAYS PENETRATING FLOORS, CEILINGS OR WALLS MUST BE PROPERLY

SEALED SMOKETIGHT.

16. ALL RACEWAYS MUST BE CONCEALED WHERE POSSIBLE.

17. INSTALL EXPOSED RACEWAYS PARALLEL TO OR AT RIGHT ANGLES TO NEARBY

SURFACES OR STRUCTURAL MEMBERS, AND FOLLOW THE SURFACE CONTOURS

AS MUCH AS POSSIBLE. NO DIAGONAL RUNS WILL BE ALLOWED. ALL CONDUITS

MUST BE RUN STRAIGHT WITH QUALITY WORKMANSHIP-LIKE MANNER. RUN

PARALLEL OR BANKED RACEWAYS TOGETHER ON COMMON SUPPORTS WHERE

PRACTICAL. MAKE BENDS IN PARALLEL OR BANKED RUNS FROM SAME

CENTERLINE TO MAKE BENDS PARALLEL.

18. PATCHING OF WATERPROOFED SURFACES MUST RENDER THE AREA OF THE

PATCHING COMPLETELY WATERPROOF.

19. ALL MOTORS AND OTHER VIBRATING EQUIPMENT MUST BE CONNECTED TO THE

CONDUIT SYSTEM BY MEANS OF A SHORT SECTION (18 INCH MINIMUM) OF

FLEXIBLE CONDUIT UNLESS OTHERWISE INDICATED. AN EQUIPMENT GROUNDING

CONDUCTOR MUST BE INSTALLED INSIDE THE FLEXIBLE CONDUIT AND TERMINATE

AT THE LOAD END WITH AN APPROVED GROUNDING CLAMP OR LUG.

20. SURFACE MOUNTED PANELBOARDS, JUNCTION, OUTLET AND PULL BOXES,

RACEWAYS, ETC., INSTALLED ON EXTERIOR SURFACES OR INSIDE ON EXTERIOR

WALLS MUST BE SUPPORTED BY SPACERS TO PROVIDE A MINIMUM 1/4" MINIMUM

CLEARANCE BETWEEN THE WALL AND EQUIPMENT.

21. TYPED PANELBOARD DIRECTORIES INSTALLED IN THE PANELBOARD DOOR

POCKET MUST REFLECT FINAL CONDITIONS AND ACTUAL ROOM NAMES AND

NUMBERS IN ADDITION TO THE GENERAL DESCRIPTION SHOWN ON THE PANEL

SCHEDULES ON THE DRAWINGS.

22. THE CONTRACTOR MUST VERIFY, PRIOR TO INSTALLATION OF CONDUCTORS OR

CONDUIT FEEDING ANY EQUIPMENT, THE ELECTRICAL EQUIPMENT IS RATED FOR

USE WITH 75 DEGREE C. WIRING. IF ANY EQUIPMENT IS RATED FOR USE WITH

LESS THAN 75 DEGREE C. CONDUCTORS, THE CONTRACTOR MUST NOTIFY THE

GOVERNMENT IMMEDIATELY FOR EVALUATION/CORRECTION.

23. DO NOT PULL CONDUCTORS UNTIL THE CONDUIT SYSTEM IS COMPLETE IN EVERY

DETAIL. IN THE CASE OF CONCEALED WORK, "COMPLETE" MEANS UNTIL ALL

ROUGH PLASTERING OR MASONRY HAS BEEN COMPLETED.

24. WHERE SIZE IS NOT SHOWN ON THE DRAWINGS, BRANCH CIRCUITS MUST

CONSIST OF #12 OR #10 AWG MINIMUM PHASE, NEUTRAL AND EQUIPMENT

GROUND CONDUCTORS IN 3/4” MINIMUM RACEWAY.

25. USE #10 AWG CONDUCTORS FOR 20 AMPERE, 120 VOLT BRANCH CIRCUITS WITH A

TOTAL INSTALLED LENGTH GREATER THAN 75 FEET AND/OR BRANCH CIRCUIT

HOMERUNS LONGER THAN 50 FEET, I.E.; #12 AWG INCREASED TO #10 AWG FOR

RECEPTACLE BRANCH CIRCUITS OVER 75 FEET TOTAL LENGTH (INCLUDING THE

HOMERUN SEGMENT) AND HOMERUNS OVER 50 FEET. IF 277 VOLT CIRCUITS ARE

SHOWN, USE #10 AWG CONDUCTORS FOR 20 AMPERE, 277 VOLT BRANCH

CIRCUITS WITH TOTAL INSTALLED LENGTH GREATER THAN 200 FEET AND/OR

BRANCH CIRCUIT HOMERUNS LONGER THAN 125 FEET, I.E.; #12 AWG INCREASED

TO #10 AWG FOR RECEPTACLE BRANCH CIRCUITS OVER 75 FEET TOTAL LENGTH

(INCLUDING THE HOMERUN SEGMENT) AND HOMERUNS OVER 50 FEET.

26. KEEP CONDUCTOR SPLICES TO A MINIMUM. INSTALL SPLICES AND TAPES THAT

POSSESS EQUIVALENT OR BETTER MECHANICAL STRENGTH AND INSULATION

RATINGS THAN CONDUCTORS BEING SPLICED. USE SPLICE AND TAP

CONNECTORS COMPATIBLE WITH CONDUCTOR MATERIAL. INSTALL CONDUCTORS

AT EACH OUTLET WITH AT LEAST 6 INCHES OF SLACK. CONNECT OUTLETS AND

COMPONENTS TO WIRING AND TO GROUND AS INDICATED AND INSTRUCTED BY

THE MANUFACTURER.

27. DO NOT SPLICE BRANCH CIRCUIT HOMERUNS WITHOUT THE PERMISSION OF THE

GOVERNMENT. HOMERUNS MUST BE CONTINUOUS FROM THE LAST OUTLET BOX

TO THE SERVING PANELBOARD.

28. DO NOT COMBINE BRANCH CIRCUIT HOMERUNS UNLESS SPECIFICALLY INDICATED

ON THE DRAWINGS.

29. INSTALL WIRING DEVICES AT HEIGHTS AS SHOWN ON THE DRAWINGS.

30. PROTECT ALL EXISTING POWER, COMMUNICATIONS, DATA, LIFE SAFETY SYSTEMS,

FIRE ALARM AND PUBLIC ADDRESS SYSTEMS AND MAINTAIN THEM IN OPERATION

THROUGHOUT THE PROGRESS OF THE WORK. NOTIFY THE GOVERNMENT IF

SHUTDOWNS ARE REQUIRED PRIOR TO ANY OUTAGE OF SERVICE. WHERE THE

DURATION OF A PROPOSED OUTAGE CANNOT BE TOLERATED BY THE

GOVERNMENT, PROVIDE TEMPORARY CONNECTIONS AS REQUIRED TO MAINTAIN

SERVICE.

31. PROVIDE GROUND FAULT CIRCUIT-INTERRUPTER PROTECTION FOR PERSONNEL

IN ACCORDANCE WITH THE NEC INCLUDING EXTERIOR RECEPTACLES AND

RECEPTACLES IN AREAS SUBJECT TO POSSIBLE WET CONDITIONS.

32. COORDINATE LOCATIONS OF MECHANICAL EQUIPMENT WITH THE RESPECTIVE

CONTRACTOR, VENDORS AND THE GOVERNMENT BEFORE ROUGH-IN. ADJUST

LIGHTING FIXTURES, RECEPTACLES AND ELECTRICAL EQUIPMENT TO

ACCOMMODATE THIS EQUIPMENT. ADVISE THE GOVERNMENT OF CONFLICTS

BEFORE ROUGH-IN.

33. BEFORE COMMENCING WORK OR ORDERING MATERIALS, THE CONTRACTOR MUST

COORDINATE WITH OTHER TRADES AND VERIFY THE NAMEPLATE RATINGS OF ALL

EQUIPMENT (MOTORS, HEATERS, COMPRESSORS, ETC.) AND ADJUST THE

RATINGS OF THE ELECTRICAL EQUIPMENT (SWITCHES, FUSES, CIRCUIT

BREAKERS, FEEDERS, ETC.) AS APPROPRIATE TO SERVE THIS EQUIPMENT.

34. ENERGIZE EQUIPMENT ONLY AFTER OBTAINING PERMISSION FROM THE

CONTRACTOR PROVIDING THE EQUIPMENT.

35. UNLESS SPECIFICALLY NOTED OTHERWISE, THE CONTRACTOR MUST MAKE FINAL

CONNECTIONS TO ALL UTILIZATION EQUIPMENT SHOWN ON THE DRAWINGS.

VERIFY THE TYPE OF FINAL CONNECTION AND PROVIDE APPROPRIATE WIRING

METHOD. THE CONTRACTOR MUST COORDINATE WITH THE MECHANICAL TRADE,

PRIOR TO ORDERING OR INSTALLATION OF ANY EQUIPMENT, TO VERIFY

MECHANICAL EQUIPMENT REQUIREMENTS ARE PROVIDED IN THE ELECTRICAL

DESIGN. THE CONTRACTOR WILL NOT BE COMPENSATED FOR COSTS

ASSOCIATED WITH CHANGING THE ELECTRICAL SYSTEMS TO MATCH UTILIZATION

EQUIPMENT, EVEN IF THE ELECTRICAL WORK IS INSTALLED PER THE ELECTRICAL

DRAWINGS.

36. THE CONTRACTOR MUST COORDINATE ALL EQUIPMENT TERMINATIONS, PLUGS

AND CORDSETS WITH VENDOR EQUIPMENT AND VERIFY ALL DEVICE LOCATIONS

FOR SPECIALITY EQUIPMENT WITH CASEWORK PRIOR TO ROUGH-IN.

37. INSTALLATION INFORMATION PACKED WITH DEVICES AND EQUIPMENT MUST BE

RETAINED FOR INCLUSION IN THE OPERATIONS AND MAINTENANCE MANUALS.

38. THE CONTRACTOR MUST VISIT THE SITE AND BECOME FAMILIAR WITH THE

EXISTING ELECTRICAL SYSTEMS AND THE EXISTING BUILDING. THE SUBMISSION

OF THE PROPOSAL BY THE CONTRACTOR SHALL BE CONSIDERED EVIDENCE THAT

HE OR HIS REPRESENTATIVE HAS VISITED THE SITE AND BUILDINGS AND NOTED

THE LOCATION AND CONDITIONS UNDER WHICH THE WORK WILL BE PERFORMED

AND THAT HE TAKES FULL RESPONSIBILITY OF ALL FACTORS GOVERNING HIS

WORK. NO EXTRAS WILL BE CONSIDERED BECAUSE OF ADDITIONAL WORK

NECESSITATED BY EXISTING JOB CONDITIONS THAT ARE NOT INDICATED ON THE

DRAWINGS.

39. ELECTRICAL DEVICES OR COMPONENTS INDICATED MUST BE PROVIDED WITH

CONDUCTORS, CONDUIT, BACKBOXES, MOUNTING BRACKETS, AND ALL RELATED

INCIDENTAL MATERIALS REQUIRED FOR FULLY FUNCTIONAL AND CODE

COMPLIANT INSTALLATION.

40. SAFETY

A. COMPLY WITH OSHA AND NEC ARC FLASH PROTECTION REQUIREMENTS.

B. FOR EQUIPMENT BEING REMOVED AND REPLACED, THE CONTRACTOR SHALL

DE-ENERGIZE THE EQUIPMENT AND MAKE IT SAFE PRIOR TO REMOVAL AND

COMPLY WITH OSHA REQUIREMENTS FOR LOCKING-OUT AND TAGGING

EQUIPMENT TO PREVENT INADVERTENT RE-ENERGIZING.

ABBREVIATIONS

PANELBOARD, SIZE AND TYPE AS INDICATED

LUMINAIRE, SIZE AND TYPE AS INDICATED (2X4)

SWITCHED LEG, MINIMUM 2-#12,1-#12 EGC IN 1/2 C.

NON-SWITCHED LEG, MINIMUM 2-#12,1-#12 EGC IN 1/2 C.

WALL SWITCH, LOW VOLTAGE, SEE OCC. SENSOR DIAGRAM.

46" AFF UNLESS OTHERWISE NOTED. ASSOCIATED LOW VOLTAGE

WIRING IS NOT SHOWN ON DRAWINGS FOR CLARITY.

X = TYPE:

3 = 3 WAY SWITCH

LV = LOW VOLTAGE, COMPATIBLE WITH LIGHTING CONTROL

SYSTEM. FUNCTION AND CONFIGURATION AS INDICATED IN OCC.

SENSOR DIAGRAM.

LV4=LOW VOLTAGE 4 BUTTON KEYPAD WITH RAISE AND LOWER

COMMUNICATION OUTLET; SEE DETAILS

CABLE TV OUTLET; SEE DETAILS

EMERGENCY LIGHTING UNIT, 2-HEAD WITH BATTERY BACK-UP,

WALL MOUNTED, CONNECT TO NON-SWITCHED LEG. SEE DETAIL

NL-26 & LUMNINAIRE SCHEDULE.

RECEPTACLE, DUPLEX, 120VAC, 20A, UNLESS OTHERWISE NOTED.

SEE MOUNTING HEIGHT DETAIL THIS SHEET.

GF - GROUND FAULT CIRCUIT INTERRUPTER, 120VAC, 20A

TV - COORDINATE LOCATION WITH AV DRAWINGS

EMERGENCY EXIT LIGHTING; SEE LIGHTING FIXTURE SCHEDULE

COMMUNICATION OUTLET, IN FLOOR, FLUSH MOUNTED, RECESSED

INTO EXISTING SLAB W/ FLOOR BOX

RECEPTACLE, DUPLEX, IN FLOOR, RECESSED IN SLAB W/ FLOOR BOX

AUDIO VISUAL CONNECTION, HDMI, FLUSH MOUNTED IN WALLS OR

RECESSED IN FLOOR SLAB W/ FLOOR BOX

CEILING MOUNTED, LOW VOLTAGE, DUAL TECH, OCCUPANCY

SENSOR, WITH POWER/RELAY PACK MOUNTED ABOVE DROP CEILING,

DIMMABLE AS INDICATED. PROVIDE ACCESS PANELS FOR ANY

MOUNTING ABOVE DRYWALL CEILINGS.

CEILING MOUNTED, LOW VOLTAGE, DUAL TECH, COORIDOR

OCCUPANCY SENSOR, WITH POWER/RELAY PACK MOUNTED ABOVE

DROP CEILING, DIMMABLE AS INDICATED. PROVIDE ACCESS PANELS

FOR ANY MOUNTING ABOVE DRYWALL CEILINGS.

CEILING MOUNTED, LOW VOLTAGE, DUAL TECH, VACANCY SENSOR,

WITH POWER/RELAY PACK MOUNTED ABOVE DROP CEILING,

DIMMABLE AS INDICATED. PROVIDE ACCESS PANELS FOR ANY

MOUNTING ABOVE DRYWALL CEILINGS.

LIGHTING CONTROL PANEL

WIRELESS ACCESS POINT LOCATED ABOVE ACCESSIBLE CEILING

SPACE. PROVIDE DOUBLE GANG BOX, (2) DATA DROPS W/ (2) CAT6A ,

AND NO PULL STRING.

DISCONNECT, SIZE AND TYPE AS INDICATED

EXIT

FINISHED CEILING

FLOOR

DOOR

ABOVE COUNTER

RECEPTACLE/DATA3"

NOTE:

DETAIL SHOWN FOR REFERENCE ONLY, NOT ALL DEVICES ARE INDICATED ON PLANS.

BACK SPLASHSTRIKE SIDE

HINGE SIDE

COUNTER TOP

LIGHT SWITCH

/DIMMER

CABLE, VOICE/DATA, DUPLEX &

QUADRAPLEX RECEPTACLES

GANG

SWITCHING

MECHANICAL

CASETTE

CLOCK HANGER

RECEPTACLE

WALL MOUNTED EXIT SIGN

ABOVE DOOR (MAX. MT. HT. OF

80" ABOVE TOP OF DOOR)

6"6"

EQ

EQ

EQ.EQ.EQ.

ELECTRICAL DEVICES MOUNTING HEIGHT

CABLE TV

OUTLET

TV RECEPTACLE

A/V OUTLET

(HDMI)

AV

TV

LCP

x

WAP

LUMINAIRE, DOWNLIGHT, SIZE AND TYPE AS INDICATED

S

LUMINAIRE, SIZE AND TYPE AS INDICATED (2X2)

AutoCAD SHX Text

SHEET:

AutoCAD SHX Text 80091

AutoCAD SHX Text E1

AutoCAD SHX Text

MARINE CORPS BASE

AutoCAD SHX Text

DEPARTMENT OF THE NAVY NAVAL FACILITIES ENGINEERING SYSTEMS COMMAND

AutoCAD SHX Text

CAMP LEJEUNE, NORTH CAROLINA

AutoCAD SHX Text

DESIGN DIR.

AutoCAD SHX Text

SUBMITTED BY:

AutoCAD SHX Text

NAVFAC DRAWING NO.

AutoCAD SHX Text

CODE IDENT. NO

AutoCAD SHX Text

SIZE

AutoCAD SHX Text

SPEC.

AutoCAD SHX Text

SCALE:

AutoCAD SHX Text

SATISFACTORY TO:

AutoCAD SHX Text

APPROVED: PWO OR OICC:

AutoCAD SHX Text

DR.

AutoCAD SHX Text

DES.

AutoCAD SHX Text

CHK.

AutoCAD SHX Text

DATE:

AutoCAD SHX Text

DATE:

AutoCAD SHX Text

OF

File details come from the government source that posted it. Updated .