This document is an electrical design drawing (E-101) for the Design Wing Relocation project at Marine Corps Base, specifically Building 1005. The drawing provides a comprehensive electrical devices mounting height legend and a set of 40 detailed general notes covering electrical installation requirements. Key specifications include:
Electrical installation guidelines cover critical aspects such as code compliance (NFPA 70), equipment installation standards, conductor and raceway routing, grounding requirements, and safety protocols. Specific technical requirements include using flexible conduit for vibrating equipment, maintaining minimum conductor sizes (#12 or #10 AWG), installing ground fault circuit interrupters, coordinating with mechanical trades, and following precise mounting height standards for electrical devices like receptacles, switches, and exit signs. The drawing also emphasizes contractor responsibilities for site verification, equipment coordination, and ensuring fully functional and code-compliant electrical systems.
View the file
Other files
Show 40 more
50 files listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
CONST. CONTR. NO.
REVISION 1.2 E-101
K. BROWN
K. BROWN
K. BROWN
K. ROOT
F. ORR
DESIGN WING RELOCATION
BUILDING 1005
LEGEND, NOTES, AND ABBREVIATIONS
60036661 21-0019
NOTED NA 14 36
GENERAL NOTESELECTRICAL LEGEND
LIGHTING PANEL, LIGHT POLE
LIGHTING
MAIN CIRCUIT BREAKER
MOTOR CONTROL CENTER
MOTOR CIRCUIT PROTECTOR
MAIN DISTRIBUTION PANEL
MANUFACTURER
MANHOLE
MAIN LUGS ONLY
MOUNTED
MOUNTING
MANUAL TRANSFER SWITCH
MEDIUM VOLTAGE
NEUTRAL
NOT APPLICABLE
NORMALLY CLOSED
NATIONAL ELECTRIC CODE
NOT IN CONTRACT
NIGHT LIGHT
NORMALLY OPEN
NOT TO SCALE
POLE
PUBLIC ADDRESS
PULL BOX, PUSH-BUTTON
POWER FACTOR
PHASE
PROGRAMMABLE LOGIC CONTROLLER
PANEL
POWER PANEL, POWER POLE
PORTABLE POWER EQUIPMENT CABLE
POTENTIAL TRANSFORMER
POWER
RECEPTACLE
REQUIRED
RIGID GALVANIZED STEEL CONDUIT
ROOM
REMOTE TELEMETRY UNIT
DC MOTOR DRIVE
SHEET
SURGE PROTECTION DEVICE
SPECIFICATION
SELECTOR SWITCH
STAINLESS STEEL
SWITCH
SWITCHBOARD
SWITCH GEAR
TELEPHONE
TWISTED PAIR SHIELDED
TRANSIENT VOLTAGE SURGE SUPPRESSER
TYPICAL
UNDERGROUND
UNIT HEATER
UNLESS OTHERWISE NOTED
UTILITY
VOLTS
VARIABLE FREQUENCY DRIVE
WIRE, WATT
WATT-HOUR
WEATHERPROOF
WEATHERPROOF TELEPHONE ENCLOSURE
TRANSFORMER
EXISTING RELOCATED
A, AMP
AFF
AFG
AHU
AIC
ATS
AWG
BOF
BRKR
C, CND
CAB
CAT
CL
CB
CCTV
CKT
CLG
CP
CR
CS
CV
CT
CU
EF
EMER
EMT
ENCL
EQUIP
EWC
EWH
EPRF
FA
FAAP
FACP
FBO
FLA
FLUOR
FLR
FWE
GEN
G, GND
GFCI
HH
HID
HOA
HP
HPF
HPS
HTR
HV
Hz
IMC
INCAND
JB
K
KCMIL
KVA
KW
KWH
AMPERE
ABOVE FINISHED FLOOR
ABOVE FINISHED GRADE
AIR HANDLING UNIT
AMPERE INTERRUPTING CAPACITY
AUTOMATIC TRANSFER SWITCH
AMERICAN WIRE GAUGE
BOTTOM OF FIXTURE
BREAKER
CONDUIT
CABINET
CATALOG
CHLORINE
CIRCUIT BREAKER
CLOSED CIRCUIT TELEVISION
CIRCUIT
CEILING
CONTROL PANEL
CONTROL RELAY, CORROSION RESISTANT
CONTROL SWITCH
CONTROL VALVE
CURRENT TRANSFORMER
COPPER
EXHAUST FAN
EMERGENCY
ELECTRICAL METALLIC TUBING
ENCLOSURE
EQUIPMENT
ELECTRIC WATER COOLER
ELECTRIC WATER HEATER
EXPLOSION PROOF
FIRE ALARM
FIRE ALARM ANNUNCIATOR PANEL
FIRE ALARM CONTROL PANEL
FURNISHED BY OTHERS
FULL LOAD AMPS
FLUORESCENT
FLOOR
FURNISHED WITH EQUIPMENT
GENERATOR
GROUND
GROUND FAULT CURRENT INTERRUPTER
HANDHOLE
HIGH INTENSITY DISCHARGE
HAND-OFF-AUTO
HORSE POWER
HIGH POWER FACTOR
HIGH PRESSURE SODIUM
HEATER
HIGH VOLTAGE
HERTZ
INTERMEDIATE METALLIC CONDUIT
INCANDESCENT
JUNCTION BOX
THOUSAND
THOUSAND CIRCULAR MILLS
KILOVOLT AMPERE
KILOWATTS
KILOWATT-HOURS
SYMBOL DESCRIPTION
LP
LTG
MCB
MCC
MCP
MDP
MFR
MH
MLO
MTD
MTG
MTS
MV
N / NEUT
NA
NC
NEC
NIC
NL
NO
NTS
P
PA
PB
PF
PH
PLC
PNL
P
PPE
PT
PWR
RECPT, RCP
REQ'D
RGS
RM
RTU
DCM
SH
SPD
SPEC
SS
SST
SW
SWBD
SWGR
TEL
TPS
TVSS
TYP
UGND
UH
UON
UTIL
V
VFD
W
WH
WP
WTE
XFMR
X/R
1. ALL ELECTRICAL WORK MUST BE IN FULL COMPLIANCE WITH NFPA 70 THE NORTH
CAROLINA STATE BUILDING CODE, ALL LOCAL CODES AND ORDINANCES AND IN
ACCORDANCE WITH THE REQUIREMENTS OF THE LOCAL AUTHORITY HAVING
JURISDICTION.
2. ALL EQUIPMENT PROVIDED BY THE CONTRACTOR MUST BE LISTED AND LABELED
BY A NATIONALLY-RECOGNIZED TESTING AGENCY, ACCEPTABLE TO THE
AUTHORITY HAVING JURISDICTION, FOR THE CONDITIONS OF INSTALLATION. ALL
MATERIAL, EQUIPMENT AND DEVICES MUST BE NEW CURRENT PRODUCTS OF
MANUFACTURERS REGULARLY ENGAGED IN THE PRODUCTION OF SUCH
PRODUCTS. EQUIPMENT MUST BE SUITABLE FOR ITS APPLICATION (E.G. WHEN
INSTALLED OUTDOORS, IT MUST BE WEATHERPROOF, ETC.)
3. THE CONTRACTOR MUST REVIEW ALL DRAWINGS AND SPECIFICATIONS FOR
WORK REQUIREMENTS, THE AMOUNT OF SPACE AVAILABLE FOR ELECTRICAL
EQUIPMENT, AND LAYOUT HIS WORK IN A COMPATIBLE AND FUNCTIONAL MANNER.
4. UNLESS SPECIFICALLY NOTED OTHERWISE, SYSTEMS PROVIDED OR INSTALLED
BY THE CONTRACTOR MUST BE COMPLETE AND FULLY-FUNCTIONING AFTER
INSTALLATION. INCIDENTAL COMPONENTS MAY NOT BE SHOWN, AND ALL WORK
WHICH MAY BE REASONABLY IMPLIED AS BEING INCIDENTAL TO THIS WORK, BUT
REQUIRED FOR THE PROPER OPERATION OF THE EQUIPMENT OR SYSTEM MUST
BE PROVIDED BY THE CONTRACTOR AND INCLUDED IN THE BID. ADDITIONAL
CIRCUITS MUST BE INSTALLED WHEREVER NEEDED TO CONFORM TO THE
SPECIFIC REQUIREMENTS OF EQUIPMENT.
5. TEMPORARY POWER CONNECTIONS AS REQUIRED MUST BE PROVIDED BY THE
CONTRACTOR AND INCLUDED IN THE BID. ALL TEMPORARY EQUIPMENT WIRING
MUST BE IN ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE. THE
CONTRACTOR MUST PROVIDE DETAILS, METHODS, MATERIALS, ETC. FOR REVIEW
PRIOR TO MAKING TEMPORARY CONNECTIONS. FURNISH AND INSTALL ALL
EQUIPMENT AND MATERIALS INCLUDING CONTROL EQUIPMENT, MOTOR
STARTERS, BRANCH AND FEEDER CIRCUIT BREAKERS, PANELBOARDS,
TRANSFORMERS, ETC. FOR TEMPORARY POWER. COORDINATE WITH THE UTILITY
PROVIDER AS REQUIRED.
6. THE WORK MUST INCLUDE COMPLETE TESTING OF ALL EQUIPMENT AND WIRING
AT THE COMPLETION OF WORK AND ANY MINOR CORRECTIONS, CHANGES OR
ADJUSTMENTS NECESSARY FOR THE PROPER FUNCTIONING OF THE SYSTEM AND
EQUIPMENT.
7. ALL ELECTRICAL EQUIPMENT MUST, AT ALL TIMES DURING CONSTRUCTION, BE
ADEQUATELY PROTECTED AGAINST MECHANICAL INJURY, OR DAMAGE BY WATER
AND/OR THE ELEMENTS. ELECTRICAL EQUIPMENT MUST NOT BE STORED OUT OF
DOORS, BUT MUST BE STORED IN DRY PERMANENT SHELTERS. IF AN APPARATUS
HAS BEEN DAMAGED, OR HAS BEEN SUBJECT TO POSSIBLE INJURY BY WATER OR
THE ELEMENTS, SUCH DAMAGE MUST BE REPLACED AT NO ADDITIONAL COST.
8. DO NOT SCALE ELECTRICAL DRAWINGS. CONTRACTOR MUST FIELD VERIFY ALL
DIMENSIONS.
9. CIRCUIT LAYOUTS ARE NOT INTENDED TO SHOW THE NUMBER OF FITTINGS, OR
OTHER INSTALLATION DETAILS. UNLESS NOTED OTHERWISE, THE EXACT
ROUTING OF FEEDER AND BRANCH CIRCUIT RACEWAYS AND CABLES IS THE
RESPONSIBILITY OF THE CONTRACTOR. RISER AND GENERAL CIRCUIT
ARRANGEMENTS ARE SHOWN SCHEMATICALLY/DIAGRAMMATICALLY ONLY. THE
CONTRACTOR MUST ROUTE CONDUITS AS REQUIRED BY THE CONDITIONS OF THE
INSTALLATION.
10. DEVICE LOCATIONS SHOWN ON THE DRAWINGS ARE APPROXIMATE. ADJUST
EXACT LOCATIONS AS REQUIRED TO SERVE THE INTENDED PURPOSE AND TO
AVOID CONFLICTS AND INTERFERENCES WITH OTHER TRADES. IF NOT SHOWN ON
THE ARCHITECTURAL DRAWINGS OR DIMENSIONED ON THE ELECTRICAL
DRAWINGS, VERIFY EXACT LOCATION WITH THE GOVERNMENT PRIOR TO
ROUGH-IN.
11. CONDUIT TERMINATING IN PRESSED STEEL BOXES MUST HAVE DOUBLE
LOCKNUTS AND INSULATED BUSHINGS. CONDUITS TERMINATING IN GASKETED
ENCLOSURES MUST BE TERMINATED WITH GROUNDING TYPE CONDUIT HUBS.
12. BRANCH CIRCUIT HOMERUNS SHOWN ON DRAWINGS INDICATE PHASE
CONDUCTORS, NEUTRAL, EQUIPMENT GROUND CONDUCTORS AS REQUIRED.
ADDITIONAL CONDUCTORS REQUIRED FOR CONTROL MUST BE INCLUDED EVEN IF
NOT EXPLICITLY SHOWN.
13. SEAL ALL CONDUIT OPENINGS THROUGH EXTERIOR BUILDING WALLS AND ROOF
WATERTIGHT.
14. IN WET LOCATIONS AND EXTERIOR, ALL WIRING DEVICES MUST BE
WEATHER-RESISTANT LISTED WITH WEATHERPROOF WHILE IN USE COVER.
15. RACEWAYS PENETRATING FLOORS, CEILINGS OR WALLS MUST BE PROPERLY
SEALED SMOKETIGHT.
16. ALL RACEWAYS MUST BE CONCEALED WHERE POSSIBLE.
17. INSTALL EXPOSED RACEWAYS PARALLEL TO OR AT RIGHT ANGLES TO NEARBY
SURFACES OR STRUCTURAL MEMBERS, AND FOLLOW THE SURFACE CONTOURS
AS MUCH AS POSSIBLE. NO DIAGONAL RUNS WILL BE ALLOWED. ALL CONDUITS
MUST BE RUN STRAIGHT WITH QUALITY WORKMANSHIP-LIKE MANNER. RUN
PARALLEL OR BANKED RACEWAYS TOGETHER ON COMMON SUPPORTS WHERE
PRACTICAL. MAKE BENDS IN PARALLEL OR BANKED RUNS FROM SAME
CENTERLINE TO MAKE BENDS PARALLEL.
18. PATCHING OF WATERPROOFED SURFACES MUST RENDER THE AREA OF THE
PATCHING COMPLETELY WATERPROOF.
19. ALL MOTORS AND OTHER VIBRATING EQUIPMENT MUST BE CONNECTED TO THE
CONDUIT SYSTEM BY MEANS OF A SHORT SECTION (18 INCH MINIMUM) OF
FLEXIBLE CONDUIT UNLESS OTHERWISE INDICATED. AN EQUIPMENT GROUNDING
CONDUCTOR MUST BE INSTALLED INSIDE THE FLEXIBLE CONDUIT AND TERMINATE
AT THE LOAD END WITH AN APPROVED GROUNDING CLAMP OR LUG.
20. SURFACE MOUNTED PANELBOARDS, JUNCTION, OUTLET AND PULL BOXES,
RACEWAYS, ETC., INSTALLED ON EXTERIOR SURFACES OR INSIDE ON EXTERIOR
WALLS MUST BE SUPPORTED BY SPACERS TO PROVIDE A MINIMUM 1/4" MINIMUM
CLEARANCE BETWEEN THE WALL AND EQUIPMENT.
21. TYPED PANELBOARD DIRECTORIES INSTALLED IN THE PANELBOARD DOOR
POCKET MUST REFLECT FINAL CONDITIONS AND ACTUAL ROOM NAMES AND
NUMBERS IN ADDITION TO THE GENERAL DESCRIPTION SHOWN ON THE PANEL
SCHEDULES ON THE DRAWINGS.
22. THE CONTRACTOR MUST VERIFY, PRIOR TO INSTALLATION OF CONDUCTORS OR
CONDUIT FEEDING ANY EQUIPMENT, THE ELECTRICAL EQUIPMENT IS RATED FOR
USE WITH 75 DEGREE C. WIRING. IF ANY EQUIPMENT IS RATED FOR USE WITH
LESS THAN 75 DEGREE C. CONDUCTORS, THE CONTRACTOR MUST NOTIFY THE
GOVERNMENT IMMEDIATELY FOR EVALUATION/CORRECTION.
23. DO NOT PULL CONDUCTORS UNTIL THE CONDUIT SYSTEM IS COMPLETE IN EVERY
DETAIL. IN THE CASE OF CONCEALED WORK, "COMPLETE" MEANS UNTIL ALL
ROUGH PLASTERING OR MASONRY HAS BEEN COMPLETED.
24. WHERE SIZE IS NOT SHOWN ON THE DRAWINGS, BRANCH CIRCUITS MUST
CONSIST OF #12 OR #10 AWG MINIMUM PHASE, NEUTRAL AND EQUIPMENT
GROUND CONDUCTORS IN 3/4” MINIMUM RACEWAY.
25. USE #10 AWG CONDUCTORS FOR 20 AMPERE, 120 VOLT BRANCH CIRCUITS WITH A
TOTAL INSTALLED LENGTH GREATER THAN 75 FEET AND/OR BRANCH CIRCUIT
HOMERUNS LONGER THAN 50 FEET, I.E.; #12 AWG INCREASED TO #10 AWG FOR
RECEPTACLE BRANCH CIRCUITS OVER 75 FEET TOTAL LENGTH (INCLUDING THE
HOMERUN SEGMENT) AND HOMERUNS OVER 50 FEET. IF 277 VOLT CIRCUITS ARE
SHOWN, USE #10 AWG CONDUCTORS FOR 20 AMPERE, 277 VOLT BRANCH
CIRCUITS WITH TOTAL INSTALLED LENGTH GREATER THAN 200 FEET AND/OR
BRANCH CIRCUIT HOMERUNS LONGER THAN 125 FEET, I.E.; #12 AWG INCREASED
TO #10 AWG FOR RECEPTACLE BRANCH CIRCUITS OVER 75 FEET TOTAL LENGTH
(INCLUDING THE HOMERUN SEGMENT) AND HOMERUNS OVER 50 FEET.
26. KEEP CONDUCTOR SPLICES TO A MINIMUM. INSTALL SPLICES AND TAPES THAT
POSSESS EQUIVALENT OR BETTER MECHANICAL STRENGTH AND INSULATION
RATINGS THAN CONDUCTORS BEING SPLICED. USE SPLICE AND TAP
CONNECTORS COMPATIBLE WITH CONDUCTOR MATERIAL. INSTALL CONDUCTORS
AT EACH OUTLET WITH AT LEAST 6 INCHES OF SLACK. CONNECT OUTLETS AND
COMPONENTS TO WIRING AND TO GROUND AS INDICATED AND INSTRUCTED BY
THE MANUFACTURER.
27. DO NOT SPLICE BRANCH CIRCUIT HOMERUNS WITHOUT THE PERMISSION OF THE
GOVERNMENT. HOMERUNS MUST BE CONTINUOUS FROM THE LAST OUTLET BOX
TO THE SERVING PANELBOARD.
28. DO NOT COMBINE BRANCH CIRCUIT HOMERUNS UNLESS SPECIFICALLY INDICATED
ON THE DRAWINGS.
29. INSTALL WIRING DEVICES AT HEIGHTS AS SHOWN ON THE DRAWINGS.
30. PROTECT ALL EXISTING POWER, COMMUNICATIONS, DATA, LIFE SAFETY SYSTEMS,
FIRE ALARM AND PUBLIC ADDRESS SYSTEMS AND MAINTAIN THEM IN OPERATION
THROUGHOUT THE PROGRESS OF THE WORK. NOTIFY THE GOVERNMENT IF
SHUTDOWNS ARE REQUIRED PRIOR TO ANY OUTAGE OF SERVICE. WHERE THE
DURATION OF A PROPOSED OUTAGE CANNOT BE TOLERATED BY THE
GOVERNMENT, PROVIDE TEMPORARY CONNECTIONS AS REQUIRED TO MAINTAIN
SERVICE.
31. PROVIDE GROUND FAULT CIRCUIT-INTERRUPTER PROTECTION FOR PERSONNEL
IN ACCORDANCE WITH THE NEC INCLUDING EXTERIOR RECEPTACLES AND
RECEPTACLES IN AREAS SUBJECT TO POSSIBLE WET CONDITIONS.
32. COORDINATE LOCATIONS OF MECHANICAL EQUIPMENT WITH THE RESPECTIVE
CONTRACTOR, VENDORS AND THE GOVERNMENT BEFORE ROUGH-IN. ADJUST
LIGHTING FIXTURES, RECEPTACLES AND ELECTRICAL EQUIPMENT TO
ACCOMMODATE THIS EQUIPMENT. ADVISE THE GOVERNMENT OF CONFLICTS
BEFORE ROUGH-IN.
33. BEFORE COMMENCING WORK OR ORDERING MATERIALS, THE CONTRACTOR MUST
COORDINATE WITH OTHER TRADES AND VERIFY THE NAMEPLATE RATINGS OF ALL
EQUIPMENT (MOTORS, HEATERS, COMPRESSORS, ETC.) AND ADJUST THE
RATINGS OF THE ELECTRICAL EQUIPMENT (SWITCHES, FUSES, CIRCUIT
BREAKERS, FEEDERS, ETC.) AS APPROPRIATE TO SERVE THIS EQUIPMENT.
34. ENERGIZE EQUIPMENT ONLY AFTER OBTAINING PERMISSION FROM THE
CONTRACTOR PROVIDING THE EQUIPMENT.
35. UNLESS SPECIFICALLY NOTED OTHERWISE, THE CONTRACTOR MUST MAKE FINAL
CONNECTIONS TO ALL UTILIZATION EQUIPMENT SHOWN ON THE DRAWINGS.
VERIFY THE TYPE OF FINAL CONNECTION AND PROVIDE APPROPRIATE WIRING
METHOD. THE CONTRACTOR MUST COORDINATE WITH THE MECHANICAL TRADE,
PRIOR TO ORDERING OR INSTALLATION OF ANY EQUIPMENT, TO VERIFY
MECHANICAL EQUIPMENT REQUIREMENTS ARE PROVIDED IN THE ELECTRICAL
DESIGN. THE CONTRACTOR WILL NOT BE COMPENSATED FOR COSTS
ASSOCIATED WITH CHANGING THE ELECTRICAL SYSTEMS TO MATCH UTILIZATION
EQUIPMENT, EVEN IF THE ELECTRICAL WORK IS INSTALLED PER THE ELECTRICAL
DRAWINGS.
36. THE CONTRACTOR MUST COORDINATE ALL EQUIPMENT TERMINATIONS, PLUGS
AND CORDSETS WITH VENDOR EQUIPMENT AND VERIFY ALL DEVICE LOCATIONS
FOR SPECIALITY EQUIPMENT WITH CASEWORK PRIOR TO ROUGH-IN.
37. INSTALLATION INFORMATION PACKED WITH DEVICES AND EQUIPMENT MUST BE
RETAINED FOR INCLUSION IN THE OPERATIONS AND MAINTENANCE MANUALS.
38. THE CONTRACTOR MUST VISIT THE SITE AND BECOME FAMILIAR WITH THE
EXISTING ELECTRICAL SYSTEMS AND THE EXISTING BUILDING. THE SUBMISSION
OF THE PROPOSAL BY THE CONTRACTOR SHALL BE CONSIDERED EVIDENCE THAT
HE OR HIS REPRESENTATIVE HAS VISITED THE SITE AND BUILDINGS AND NOTED
THE LOCATION AND CONDITIONS UNDER WHICH THE WORK WILL BE PERFORMED
AND THAT HE TAKES FULL RESPONSIBILITY OF ALL FACTORS GOVERNING HIS
WORK. NO EXTRAS WILL BE CONSIDERED BECAUSE OF ADDITIONAL WORK
NECESSITATED BY EXISTING JOB CONDITIONS THAT ARE NOT INDICATED ON THE
DRAWINGS.
39. ELECTRICAL DEVICES OR COMPONENTS INDICATED MUST BE PROVIDED WITH
CONDUCTORS, CONDUIT, BACKBOXES, MOUNTING BRACKETS, AND ALL RELATED
INCIDENTAL MATERIALS REQUIRED FOR FULLY FUNCTIONAL AND CODE
COMPLIANT INSTALLATION.
40. SAFETY
A. COMPLY WITH OSHA AND NEC ARC FLASH PROTECTION REQUIREMENTS.
B. FOR EQUIPMENT BEING REMOVED AND REPLACED, THE CONTRACTOR SHALL
DE-ENERGIZE THE EQUIPMENT AND MAKE IT SAFE PRIOR TO REMOVAL AND
COMPLY WITH OSHA REQUIREMENTS FOR LOCKING-OUT AND TAGGING
EQUIPMENT TO PREVENT INADVERTENT RE-ENERGIZING.
ABBREVIATIONS
PANELBOARD, SIZE AND TYPE AS INDICATED
LUMINAIRE, SIZE AND TYPE AS INDICATED (2X4)
SWITCHED LEG, MINIMUM 2-#12,1-#12 EGC IN 1/2 C.
NON-SWITCHED LEG, MINIMUM 2-#12,1-#12 EGC IN 1/2 C.
WALL SWITCH, LOW VOLTAGE, SEE OCC. SENSOR DIAGRAM.
46" AFF UNLESS OTHERWISE NOTED. ASSOCIATED LOW VOLTAGE
WIRING IS NOT SHOWN ON DRAWINGS FOR CLARITY.
X = TYPE:
3 = 3 WAY SWITCH
LV = LOW VOLTAGE, COMPATIBLE WITH LIGHTING CONTROL
SYSTEM. FUNCTION AND CONFIGURATION AS INDICATED IN OCC.
SENSOR DIAGRAM.
LV4=LOW VOLTAGE 4 BUTTON KEYPAD WITH RAISE AND LOWER
COMMUNICATION OUTLET; SEE DETAILS
CABLE TV OUTLET; SEE DETAILS
EMERGENCY LIGHTING UNIT, 2-HEAD WITH BATTERY BACK-UP,
WALL MOUNTED, CONNECT TO NON-SWITCHED LEG. SEE DETAIL
NL-26 & LUMNINAIRE SCHEDULE.
RECEPTACLE, DUPLEX, 120VAC, 20A, UNLESS OTHERWISE NOTED.
SEE MOUNTING HEIGHT DETAIL THIS SHEET.
GF - GROUND FAULT CIRCUIT INTERRUPTER, 120VAC, 20A
TV - COORDINATE LOCATION WITH AV DRAWINGS
EMERGENCY EXIT LIGHTING; SEE LIGHTING FIXTURE SCHEDULE
COMMUNICATION OUTLET, IN FLOOR, FLUSH MOUNTED, RECESSED
INTO EXISTING SLAB W/ FLOOR BOX
RECEPTACLE, DUPLEX, IN FLOOR, RECESSED IN SLAB W/ FLOOR BOX
AUDIO VISUAL CONNECTION, HDMI, FLUSH MOUNTED IN WALLS OR
RECESSED IN FLOOR SLAB W/ FLOOR BOX
CEILING MOUNTED, LOW VOLTAGE, DUAL TECH, OCCUPANCY
SENSOR, WITH POWER/RELAY PACK MOUNTED ABOVE DROP CEILING,
DIMMABLE AS INDICATED. PROVIDE ACCESS PANELS FOR ANY
MOUNTING ABOVE DRYWALL CEILINGS.
CEILING MOUNTED, LOW VOLTAGE, DUAL TECH, COORIDOR
OCCUPANCY SENSOR, WITH POWER/RELAY PACK MOUNTED ABOVE
DROP CEILING, DIMMABLE AS INDICATED. PROVIDE ACCESS PANELS
FOR ANY MOUNTING ABOVE DRYWALL CEILINGS.
CEILING MOUNTED, LOW VOLTAGE, DUAL TECH, VACANCY SENSOR,
WITH POWER/RELAY PACK MOUNTED ABOVE DROP CEILING,
DIMMABLE AS INDICATED. PROVIDE ACCESS PANELS FOR ANY
MOUNTING ABOVE DRYWALL CEILINGS.
LIGHTING CONTROL PANEL
WIRELESS ACCESS POINT LOCATED ABOVE ACCESSIBLE CEILING
SPACE. PROVIDE DOUBLE GANG BOX, (2) DATA DROPS W/ (2) CAT6A ,
AND NO PULL STRING.
DISCONNECT, SIZE AND TYPE AS INDICATED
EXIT
FINISHED CEILING
FLOOR
DOOR
ABOVE COUNTER
RECEPTACLE/DATA3"
NOTE:
DETAIL SHOWN FOR REFERENCE ONLY, NOT ALL DEVICES ARE INDICATED ON PLANS.
BACK SPLASHSTRIKE SIDE
HINGE SIDE
COUNTER TOP
LIGHT SWITCH
/DIMMER
CABLE, VOICE/DATA, DUPLEX &
QUADRAPLEX RECEPTACLES
GANG
SWITCHING
MECHANICAL
CASETTE
CLOCK HANGER
RECEPTACLE
WALL MOUNTED EXIT SIGN
ABOVE DOOR (MAX. MT. HT. OF
80" ABOVE TOP OF DOOR)
6"6"
EQ
EQ
EQ.EQ.EQ.
ELECTRICAL DEVICES MOUNTING HEIGHT
CABLE TV
OUTLET
TV RECEPTACLE
A/V OUTLET
(HDMI)
AV
TV
LCP
x
WAP
LUMINAIRE, DOWNLIGHT, SIZE AND TYPE AS INDICATED
S
LUMINAIRE, SIZE AND TYPE AS INDICATED (2X2)
AutoCAD SHX Text
SHEET:
AutoCAD SHX Text 80091
AutoCAD SHX Text E1
AutoCAD SHX Text
MARINE CORPS BASE
AutoCAD SHX Text
DEPARTMENT OF THE NAVY NAVAL FACILITIES ENGINEERING SYSTEMS COMMAND
AutoCAD SHX Text
CAMP LEJEUNE, NORTH CAROLINA
AutoCAD SHX Text
DESIGN DIR.
AutoCAD SHX Text
SUBMITTED BY:
AutoCAD SHX Text
NAVFAC DRAWING NO.
AutoCAD SHX Text
CODE IDENT. NO
AutoCAD SHX Text
SIZE
AutoCAD SHX Text
SPEC.
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
SATISFACTORY TO:
AutoCAD SHX Text
APPROVED: PWO OR OICC:
AutoCAD SHX Text
DR.
AutoCAD SHX Text
DES.
AutoCAD SHX Text
CHK.
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
OF
File details come from the government source that posted it. Updated .