This document is a detailed lighting fixture specification sheet for a Marine Corps Base construction project involving design wing relocation in Building 1005. The specification outlines precise requirements for multiple LED lighting fixtures, including direct/indirect LED luminaires, emergency lighting units, edge-lit exit signs, surface LED wraparounds, and LED industrial lights. Each fixture type has comprehensive technical specifications addressing housing materials (ranging from extruded aluminum to cold-rolled steel), light source characteristics (solid-state LEDs at 3500K color temperature), driver specifications (high-efficiency with 120-277V operating voltage), certification standards (UL listed, ROHS compliant), and mounting options.
The lighting fixture schedule details specific models with their respective dimensions, voltage requirements, lumen outputs, and color specifications. Key models include NL-1 (2x4 direct/indirect troffer), NL-26 (emergency fixture), NL-27 (edge-lit exit sign), NL-12 (fixed recessed downlight), and NL-23 (LED industrial strip light). Additional features include options for emergency battery backup, occupancy/vacancy sensors, and various mounting configurations. The document includes a ceiling occupancy/vacancy sensor dimming diagram illustrating operational sequences, such as continuous dimming based on input and automatic shutdown after 15 minutes of no occupancy.
View the file
Other files
Show 40 more
50 files listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
CONST. CONTR. NO.
REVISION 1.2 E-105
K.BROWN
K.BROWN
K.BROWN
K.ROOT
F. ORR
DESIGN WING RELOCATION
BUILDING 1005
PLATES, DETAILS, AND SCHEDULES
60036665 21-0019
NOTED NA 18 36
LUMINAIRE REQUIREMENTS:
1. HOUSING - HEAVY GAUGE COLD ROLLED STEEL OR DIE CAST ALUMINUM. SIZE
SHOWN AS INDICATED IN LUMINAIRE SCHEDULE.
2. OPTICS - FROSTED ACRYLIC OR POLYCARBONATE LENS WITH DIE FORMED
COLD ROLLED SHEET STEEL REFLECTORS.
3. LIGHT SOURCE - SOLID STATE LEDS, 3500K CCT UON, MINIMUM 80 CRI UON, AND
MINIMUM EFFICACY OF 100 LUMENS/WATT UON. INITIAL LUMEN OUTPUT AS
INDICATED IN LUMINAIRE SCHEDULE.
4. DRIVER - REPLACEABLE, INTEGRAL, HIGH-EFFICIENCY DIMMABLE DRIVER WITH
MINIMUM 0.9 PF, OPERATING VOLTAGE OF 120-277V, THERMAL MANAGEMENT,
AND < 20% THD. ON/OFF CONTROL AND FULLY DIMMABLE DOWN TO 10%
MINIMUM OR AS INDICATED IN LUMINAIRE SCHEDULE.
5. CERTIFICATION - UL LISTED FOR DRY OR DAMP LOCATION, ROHS COMPLIANT.
DLC QUALIFIED. COMPLIES WITH IES LM79, LM80 AND TM21 TESTING
STANDARDS.
6. MOUNTING - RECESSED IN HARD OR ACOUSTICAL TILE CEILING.
7. OPTIONS - EMERGENCY BATTERY BACK-UP, INTEGRAL OCCUPANCY/VACANCY
SENSOR, VARIOUS SIZE AND OUTPUT OPTIONS, SURFACE-MOUNTING KIT.
NOTE: THIS SKETCH IS A NON-PROPRIETARY GRAPHIC REPRESENTATION OF A LUMINAIRE THAT MAY MEET
THE
SPECIFICATION REQUIREMENTS. IT IS NOT INTENDED TO INDICATE A CERTAIN MANUFACTURER OR
PREFERENCE.
LUMINAIRE REQUIREMENTS:
1. HOUSING - HIGH-IMPACT, UV-STABILIZED, INJECTION-MOLDED THERMOPLASTIC
HOUSING.
2. LIGHT SOURCE - SOLID STATE LEDS.
3. DRIVER - INTEGRAL, HIGH-EFFICIENCY DRIVER WITH MINIMUM 0.9 PF,
OPERATING VOLTAGE OF 120-277V, THERMAL MANAGEMENT, AND < 20% THD.
ON/OFF CONTROL AND BATTERY BACKUP INTEGRAL TO UNIT.
4. CERTIFICATION - NFPA 101. UL LISTED FOR DAMP OR WET LOCATION, ROHS
COMPLIANT. COMPLIES WITH IES LM79, LM80 AND TM21 TESTING STANDARDS.
5. MOUNTING - WALL SURFACE MOUNTED.
6. OPTIONS - WHITE OR BLACK FINISH.
NOTE: THIS SKETCH IS A NON-PROPRIETARY GRAPHIC REPRESENTATION OF A LUMINAIRE THAT MAY MEET
THE
SPECIFICATION REQUIREMENTS. IT IS NOT INTENDED TO INDICATE A CERTAIN MANUFACTURER OR
PREFERENCE.
LUMINAIRE REQUIREMENTS:
1. HOUSING - EXTRUDED ALUMINUM WITH CLEAR ACRYLIC EDGE-LIT PANEL.
2. LIGHT SOURCE - SOLID STATE LEDS.
3. DRIVER - INTEGRAL, HIGH-EFFICIENCY DRIVER WITH MINIMUM 0.9 PF,
OPERATING VOLTAGE OF 120-277V, THERMAL MANAGEMENT, AND < 20% THD.
4. CERTIFICATION - NFPA 101, UL LISTED FOR DAMP OR WET LOCATION, AND ROHS
COMPLIANT.
5. MOUNTING - SURFACE MOUNTED ON CEILING AND/OR WALL.
6. OPTIONS - RED OR GREEN LETTERING, ONE- OR TWO-SIDED. BATTERY BACKUP.
NOTE: THIS SKETCH IS A NON-PROPRIETARY GRAPHIC REPRESENTATION OF A LUMINAIRE THAT MAY MEET
THE
SPECIFICATION REQUIREMENTS. IT IS NOT INTENDED TO INDICATE A CERTAIN MANUFACTURER OR
PREFERENCE.
LUMINAIRE REQUIREMENTS:
1. HOUSING - COLD-ROLLED STEEL OR DIE CAST ALUMINUM, WITH HEAT SINK.
APERTURE SIZE AND SHAPE AS INDICATED IN LUMINAIRE SCHEDULE.
2. LIGHT SOURCE - SOLID STATE LEDS, 3500K CCT UON, MINIMUM 80 CRI UON, AND
MINIMUM EFFICACY OF 70 LUMENS/WATT UON. INITIAL LUMEN OUTPUT AS
INDICATED IN LUMINAIRE SCHEDULE.
3. DRIVER - REPLACEABLE, INTEGRAL, HIGH-EFFICIENCY DIMMABLE DRIVER WITH
MINIMUM 0.9 PF, OPERATING VOLTAGE OF 120-277V, THERMAL MANAGEMENT,
AND < 20% THD. ON/OFF CONTROL AND FULLY DIMMABLE DOWN TO 10%
MINIMUM OR AS INDICATED IN LUMINAIRE SCHEDULE.
4. CERTIFICATION - UL LISTED FOR DRY OR DAMP LOCATION, ROHS COMPLIANT.
COMPLIES WITH IES LM79, LM80 AND TM21 TESTING STANDARDS.
5. MOUNTING - RECESSED IN HARD OR ACOUSTICAL TILE CEILING. PROVIDE T-BAR
HANGERS FOR INSTALLATION IN ACOUSTICAL TILE CEILINGS OR TABS WHEN
MOUNTING IN HARD CEILINGS.
6. OPTIONS - EMERGENCY BATTERY BACK-UP, VARIOUS ACRYLIC OR
POLYCARBONATE LENSES, REFLECTORS, LOUVERS AND TRIMS. VARIOUS BEAM
ANGLES. IC RATED HOUSING.
NOTE: THIS SKETCH IS A NON-PROPRIETARY GRAPHIC REPRESENTATION OF A LUMINAIRE THAT MAY MEET
THE
SPECIFICATION REQUIREMENTS. IT IS NOT INTENDED TO INDICATE A CERTAIN MANUFACTURER OR
PREFERENCE.
CEILING OCCUPANCY/VACANCY SENSOR DIMMING DIAGRAM
OPERATION SEQUENCE
1. LIGHT FIXTURE MUST CONTINUOUSLY DIM/BRIGHTEN BASED UPON INPUT FROM
THE DIMMER.
2. AFTER 15 MINUTES OF NO OCCUPANCY, LIGHT FIXTURE MUST TURN OFF.
LUMINAIRE REQUIREMENTS:
1. HOUSING - DIE-FORMED, COLD ROLLED STEEL, WITH REINFORCEMENT RIBS FOR
RIGIDITY; ENDCAPS SAME MATERIAL AS HOUSING, SECURED TABS, SCREWS, OR
RIVETS. SIZE AS INDICATED IN LUMINAIRE SCHEDULE.
2. OPTICS - ACRYLIC OR POLYCARBONATE LENS AS INDICATED IN LUMINAIRE
SCHEDULE.
3. LIGHT SOURCE - SOLID STATE LEDS, 3500K CCT UON, MINIMUM 80 CRI UON, AND
MINIMUM EFFICACY OF 110 LUMENS/WATT UON. INITIAL LUMEN OUTPUT AS
INDICATED IN LUMINAIRE SCHEDULE.
4. DRIVER - REPLACEABLE, INTEGRAL, HIGH-EFFICIENCY DRIVER WITH MINIMUM 0.9
PF, OPERATING VOLTAGE OF 120-277V, THERMAL MANAGEMENT, AND < 20% THD.
ON/OFF CONTROL AND FULLY DIMMABLE DOWN TO 10% MINIMUM OR AS
INDICATED IN LUMINAIRE SCHEDULE.
5. CERTIFICATION - UL LISTED FOR DRY OR DAMP LOCATION, ROHS COMPLIANT,
DLC QUALIFIED. COMPLIES WITH IES LM79, LM80 AND TM21 TESTING
STANDARDS.
6. MOUNTING - SURFACE MOUNTED.
7. OPTIONS - EMERGENCY BATTERY BACK-UP, INTEGRAL OCCUPANCY/VACANCY
SENSOR, VARIOUS SIZE AND OUTPUT OPTIONS.
NOTE: THIS SKETCH IS A NON-PROPRIETARY GRAPHIC REPRESENTATION OF A LUMINAIRE THAT MAY MEET
THE
SPECIFICATION REQUIREMENTS. IT IS NOT INTENDED TO INDICATE A CERTAIN MANUFACTURER OR
PREFERENCE.
LUMINAIRE REQUIREMENTS:
1. HOUSING - EXTRUDED ALUMINUM OR WELDED STEEL HOUSING WITH SNAP-ON
END CAPS. SIZE AS INDICATED IN LUMINAIRE SCHEDULE.
2. OPTICS - DIFFUSE ACRYLIC LENS.
3. LIGHT SOURCE - SOLID STATE LEDS, 3500K CCT UON, MINIMUM 80 CRI UON, AND
MINIMUM EFFICACY OF 90 LUMENS/WATT UON. INITIAL LUMEN OUTPUT AS
INDICATED IN LUMINAIRE SCHEDULE.
4. DRIVER - REPLACEABLE, INTEGRAL, HIGH-EFFICIENCY DIMMABLE DRIVER WITH
MINIMUM 0.9 PF, OPERATING VOLTAGE OF 120-277V, THERMAL MANAGEMENT,
AND < 20% THD. ON/OFF CONTROL AND FULLY DIMMABLE DOWN TO 10%
MINIMUM OR AS INDICATED IN LUMINAIRE SCHEDULE.
5. CERTIFICATION - UL LISTED FOR DAMP OR WET LOCATION, ROHS COMPLIANT.
DLC QUALIFIED. COMPLIES WITH IES LM79, LM80 AND TM21 TESTING
STANDARDS.
6. MOUNTING - PENDANT, STEM, OR SURFACE MOUNTED WITH STAINLESS STEEL
MOUNTING HARDWARE.
7. OPTIONS - INTEGRAL OCCUPANCY SENSOR, EMERGENCY BATTERY BACK-UP,
VARIOUS PROFILE DIMENSIONS AND RUN LENGTHS, AND VARIOUS CLEAR OR
FROSTED POLYCARBONATE LENSES.
NOTE: THIS SKETCH IS A NON-PROPRIETARY GRAPHIC REPRESENTATION OF A LUMINAIRE THAT MAY MEET
THE
SPECIFICATION REQUIREMENTS. IT IS NOT INTENDED TO INDICATE A CERTAIN MANUFACTURER OR
PREFERENCE.
MARK DESCRIPTION SIZE/APERATURE VOLTS LAMPS WATTS COLOR
A
B
NL-1, DIRECT/INDIRECT TROFFER, RECESSED, DIMMABLE 2x4 120V LED 3500K
4000 LUMENS
C
D
NL-26, EMERGENCY FIXTURE 120V LED 4
3500K
640 LUMENS
12.5"W X 3.75"D X 3.75"H
NL-27, EXIT SIGN, EDGE LIT 12"W X 8"H X 2"D 5LED120V
WHITE
WHITE
WHITE
PROVIDE 90 MIN. BACKUP BATTERY PACK.
PROVIDE 90 MIN. BACKUP BATTERY PACK.
E
NL-12, FIXED RECESSED DOWNLIGHT 120V LED
3500K
1500 LUMEN
WHITE156" RECESSED
LIGHTING FIXTURE SCHEDULE
F
NL-23, LED INDUSTRIAL STRIP LIGHT, PENDANT MOUNT,
W/ 90 MINUTE BACKUP BATTERY
120V LED
3500K
4000 LUMEN
404' STRIP WHITE
NL-1, DIRECT/INDIRECT TROFFER, RECESSED 120V LED
3500K
3000 LUMEN
WHITE222X2
G NL-3, SURFACE LED WRAPAROUND 2x4 120V LED
3500K
4000 LUMENS
33 WHITE
AutoCAD SHX Text
SHEET:
AutoCAD SHX Text 80091
AutoCAD SHX Text E1
AutoCAD SHX Text
MARINE CORPS BASE
AutoCAD SHX Text
DEPARTMENT OF THE NAVY NAVAL FACILITIES ENGINEERING SYSTEMS COMMAND
AutoCAD SHX Text
CAMP LEJEUNE, NORTH CAROLINA
AutoCAD SHX Text
DESIGN DIR.
AutoCAD SHX Text
SUBMITTED BY:
AutoCAD SHX Text
NAVFAC DRAWING NO.
AutoCAD SHX Text
CODE IDENT. NO
AutoCAD SHX Text
SIZE
AutoCAD SHX Text
SPEC.
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
SATISFACTORY TO:
AutoCAD SHX Text
APPROVED: PWO OR OICC:
AutoCAD SHX Text
DR.
AutoCAD SHX Text
DES.
AutoCAD SHX Text
CHK.
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
OF
AutoCAD SHX Text
DIRECT/INDIRECT LED LUMINAIRE
AutoCAD SHX Text
REVISED:
AutoCAD SHX Text
NOVEMBER 2020
AutoCAD SHX Text
NL-1
AutoCAD SHX Text
LIGHTING PLATE:
AutoCAD SHX Text
LED EMERGENCY LIGHTING UNIT (ELU)
AutoCAD SHX Text
REVISED:
AutoCAD SHX Text
NL-26
AutoCAD SHX Text
LIGHTING PLATE:
AutoCAD SHX Text
NOVEMBER 2020
AutoCAD SHX Text
EDGE-LIT EXIT SIGN
AutoCAD SHX Text
REVISED:
AutoCAD SHX Text
NOVEMBER 2020
AutoCAD SHX Text
NL-27
AutoCAD SHX Text
LIGHTING PLATE:
AutoCAD SHX Text
FIXED RECESSED DOWNLIGHT
AutoCAD SHX Text
REVISED:
AutoCAD SHX Text
NOVEMBER 2020
AutoCAD SHX Text
NL-12
AutoCAD SHX Text
LIGHTING PLATE:
AutoCAD SHX Text
ON
AutoCAD SHX Text
OFF
AutoCAD SHX Text
ON
AutoCAD SHX Text
OFF
AutoCAD SHX Text
CAT 5E
AutoCAD SHX Text
CAT 5E
AutoCAD SHX Text N
AutoCAD SHX Text H
AutoCAD SHX Text N
AutoCAD SHX Text
LOAD
AutoCAD SHX Text
WHITE
AutoCAD SHX Text
BLK/ORANGE
AutoCAD SHX Text
DIMMING
AutoCAD SHX Text
RED
AutoCAD SHX Text
BLUE
AutoCAD SHX Text
VIOLET
AutoCAD SHX Text
GREY
AutoCAD SHX Text
PACK
AutoCAD SHX Text
POWER
AutoCAD SHX Text
CAT5 SPLITTER
AutoCAD SHX Text
LOW VOLTAGE
AutoCAD SHX Text
CEILING SENSOR
AutoCAD SHX Text
LV
AutoCAD SHX Text
LV4
AutoCAD SHX Text
AUX.
AutoCAD SHX Text
INPUT/OUTPUT
AutoCAD SHX Text
DEVICE INTERFACE
AutoCAD SHX Text
WHERE REQUIRED FOR FIRE ALARM INTERFACE
AutoCAD SHX Text
TO FIRE ALARM MODULE
AutoCAD SHX Text
CAT 5E
AutoCAD SHX Text
SURFACE LED WRAPAROUND
AutoCAD SHX Text
REVISED:
AutoCAD SHX Text
NOVEMBER 2020
AutoCAD SHX Text
NL-3
AutoCAD SHX Text
LIGHTING PLATE:
AutoCAD SHX Text
LED INDUSTRIAL LIGHT
AutoCAD SHX Text
REVISED:
AutoCAD SHX Text
NOVEMBER 2020
AutoCAD SHX Text
NL-23
AutoCAD SHX Text
LIGHTING PLATE:
File details come from the government source that posted it. Updated .