This document is an attachment to a federal contract that details the Niagara Building Automation System (BAS) Alarms Policy for Camp Lejeune's Public Works Department, dated January 2020. The policy defines six distinct alarm classes for supervisory controllers, specifying how different types of alarms will be managed and escalated: Default Alarm Class (non-critical alarms remaining local), Critical Monitoring Alarm Class (panel door tamper switches), Critical Temperature Alarm Class (equipment performance and occupant comfort), Critical HVAC Alarm Class (system failures requiring maintenance response), Critical Boiler Alarm Class, and Critical Chiller Alarm Class. Each alarm class is designed to determine whether alarms will be pushed up to the FX Niagara 4 Server, ensuring appropriate monitoring and rapid response for critical infrastructure and facility systems.
View the file
Other files
Show 40 more
50 files listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Camp Lejeune – Niagara BAS Alarms Policy January 2020
SECTION 23 09 23.13 – ATTACHMENT 4 – PAGE 1
Camp Lejeune – Public Works Department Niagara BAS Alarms Policy
Alarms for each given supervisory controller shall be managed by the following Alarm Class definitions:
Default Alarm Class: Non‐critical alarms that will remain at the local level and not pushed up to the FX Niagara 4 Server.
Critical Monitoring Alarm Class: The Supervisory controller panel door tamper monitoring switch. This type of alarm will be pushed up to the FX Niagara 4 Server.
Critical Temperature Alarm Class: All critical temperature alarm types related to equipment performance failures and/or high priority zones where temperature and/or occupant comfort is a priority that requires escalated response from Base maintenance. These types of alarms will be pushed up to the FX Niagara 4 Server.
Critical HVAC Alarm Class: All critical AHU, VAV, FCU, WSHP, etc., alarm types such as, but not limited to, Fan Failure, Low Temperature Limit, High/Low Duct Pressure Safety, Smoke Detector, ATFP, etc., that requires escalated response from Base maintenance. These types of alarms will be pushed up to the FX Niagara 4 Server.
Critical Boiler Alarm Class: All critical boiler/heating system alarms defined in the specifications and requiring immediate attention from Base maintenance. These types of alarms will be pushed up to the FX Niagara 4 Server.
Critical Chiller Alarm Class: All critical chiller/chilled water system alarms defined in the specifications and requiring immediate attention from Base maintenance. Theses type of alarms will be pushed up to the FX Niagara 4 Server.