This document is a detailed architectural drawing (Sheet A-501) for a construction project at Marine Corps Base Camp Lejeune, North Carolina. The drawing focuses on wall partition types, construction details, and specific building requirements for Design Wing Relocation, Building 1005. The document includes a comprehensive partition schedule detailing wall types across various locations, specifying components such as:
- Wall assembly configurations with specific requirements for studs (wood and metal), insulation (R-15 batt, fiberglass), gypsum wallboard (5/8" GWB), and sound/fire ratings
- Roof and ceiling assembly details, including 1-hour rated assemblies with specifications for truss configurations, resilient channels, and acoustic ceiling systems
- Specific technical notes about wall penetrations, sealant applications, roofing details (including vent and gooseneck configurations), and existing wall assembly verification requirements
- Precise construction specifications for wall types with annotations about moisture resistance, sound transmission class (STC) ratings, and insulation requirements
View the file
Other files
Show 40 more
50 files listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
NOTES:
1. FIELD VERIFY: THE CONTRACTOR MUST FIELD VERIFY ALL THE CONDITIONS SHOWN. THESE DETAILS ARE BASED ON DATA FROM THE 1984 ORIGINAL CONSTRUCTION DOCUMENTS. REFER TO SOLICITATION FOR OTHER INFORMATION.
2. HAZARDOUS MATERIALS: REFER TO SPECIFICATIONS FOR INSTRUCTIONS IN CASE HAZARDOUS MATERIALS ARE ENCOUNTERED. ACCORDING TO THE 1961 INFORMATION THE EXISTING SHEATHING/INSULATION CONTAINS ASBESTOS
3. ROOF WORK: ALL ROOF WORK MUST BE COORDINATED WITH THE ROICC. BUILDING STRUCTURE MUST BE KEPT WATER TIGHT AT ALL TIMES
4. SHOP DRAWINGS: IT IS THE CONTRACTOR'S RESPONSIBILITY TO DEVELOP SHOP DRAWINGS IN SUFFICIENT DETAILS TO COMPLY WITH ALL CODES AND STANDARDS. THE SECTIONS AND DETAILS PROVIDED IN THESE DOCUMENTS ARE GENERIC IN NATURE AND NOT THE FINAL CONFIGURATION. THE SHOP DRAWINGS MUST CONTAIN ALL THE NECESSARY
CALCULATIONS TO DETERMINE APPROPRIATE MATERIALS, LOADS, CODE COMPLIANCE REQUIREMENTS, ETC.
5. FLASHING: FLASHING SHOP DRAWINGS: PROVIDE FULLY DEVELOPED FLASHING FOR EACH CONDITION. GENERIC FLASHING WILL BE REJECTED. FLASHING MUST HAVE THE ACTUAL ITEM TO BE INSTALLED (FOR EXAMPLE: WINDOWS, ROOF, CANT, WALL PENETRATIONS, ETC.). SHOP DRAWINGS WITH STATEMENTS SUCH AS "FLASHING BY OTHERS" WILL BE REJECTED.
THE FLASHING MUST BE DONE BY EITHER THE PARTICULAR ITEM VENDOR OR BY FLASHING SUBCONTRACTOR SHOWING THE ACTUAL ITEM SELECTED FOR THIS PROJECT
6. BUILDING ENVELOPE: COMPLY WITH ASHRAE 90.1 FOR THE REQUIRED U AND R-VALUES
7. EXTERIOR COLORS: ALL EXTERIOR COLORS MUST BE APPROVED BY THE LATEST EDITION OF THE BASE EXTERIOR ARCHITECTURAL PLAN (BEAP). PROVIDE ACTUAL SAMPLES OF MATERIALS ONLY, PHOTOCOPIES OR COLOR WHEELS WILL NOT BE ACCEPTED. COORDINATE WITH THE ROICC
LINE OF FINISHED
CEILING
EXIST WOOD OR METAL
STUDS/CHANNELS WHERE
OCCURS, FIELD VERIFY - INFILL
ENTIRE CAVITY WITH NEW
SOUND BATTS INSULATION
EXIST INTERIOR WALL, DEPTH
AND COMPOSITION VARIES,
FIELD VERIFY
CONTINUOUS SEALANT
UNDERSIDE OF ROOF/CEILING
ASSEMBLY GWB
CONTINUOUS SEALANT
NEW 5/8" GWB, REFER TO
PARTITION SCHEDULE FOR
TYPE - STC 45 PER TEST No.
NGC 2391
LOWEST PRIORITY
FIRE & STC
WALL FINISHES TO ALIGN
HIGHEST PRIORITY
FIRE & STC
NEW 5/8" GWB, REFER TO PARTITION
SCHEDULE FOR TYPE - STC 45 PER
TEST No. NGC 2391
EXIST WALL ASSEMBLY- FIELD VERIFY
-STUCCO SYSTEM
-STRUCTURAL CLAY TILE
-METAL STUD
NEW RIGID INSULATION
NEW 2X4 WOOD STUDS AT 16" O.C.,
NEW R-15 BATT INSULATION W/ V.R.
NEW 5/8" GWB, REFER TO PARTITION
SCHEDULE FOR TYPE - STC 45 PER
TEST No. NGC 2391
EXIST WALL ASSEMBLY- FIELD VERIFY
-STUCCO SYSTEM
-STRUCTURAL CLAY TILE
EXIST WALL ASSEMBLY- FIELD VERIFY
-STUCCO SYSTEM
-STRUCTURAL CLAY TILE
NEW R-15 BATT INSULATION W/ V.R.
NEW 5/8" GWB, REFER TO PARTITION
SCHEDULE FOR TYPE - STC 45 PER
TEST No. NGC 2391 - ALIGN NEW WALL
WITH EXISTING PILASTERS ADJACENT
NEW 6" METAL STUDS AT 16" O.C.
NEW 5/8" GWB, REFER TO PARTITION
SCHEDULE FOR TYPE - STC 45 PER
TEST No. NGC 2391
EXIST WALL ASSEMBLY, FIELD VERIFY
-EIFIS SYSTEM
-VAPOR BARRIER (15 LB ASPHALT
FELT)
-SHEATHING (5/8" OSB)
-WOOD STUDS
NEW R-15 BATT INSULATION W/ V.R.
NEW R 38 FIBERGLASS BATT INSULATION
DRAPED OVER FURRING CHANNELS
UL ASSEMBLY No. P533
1-HOUR RATED
NEW 5/8" TYPE X GWB
EXIST TRUSS, FIELD VERIFY
NEW 1/2" RESILIENT CHANNEL AT 12" O.C.
FASTENED PERPENDICULAR TO LOWER
TRUSS CORD
UL ASSEMBLY No. P533
1-HOUR RATED
NEW 5/8" TYPE X GWB
EXIST TRUSS, FIELD VERIFY
ACOUSTICAL CEILING SYSTEM
HANGER WIRE
LINE OF FINISHED
CEILING
EXIST WOOD OR METAL
STUDS/CHANNELS WHERE
OCCURS, FIELD VERIFY - INFILL
ENTIRE CAVITY WITH NEW
SOUND BATTS INSULATION
EXIST INTERIOR WALL, DEPTH
AND COMPOSITION VARIES,
FIELD VERIFY
CONTINUOUS SEALANT
UNDERSIDE OF ROOF/CEILING
ASSEMBLY GWB
CONTINUOUS SEALANT
NEW 5/8" GWB, REFER TO
PARTITION SCHEDULE FOR
TYPE - STC 45 PER TEST No.
NGC 2391
LINE OF FINISHED
CEILING
NEW 2x4 WOOD OR 3 5/8" METAL
STUDS AT 16" O.C., MATCH
EXISTING
NEW 5/8" GWB, REFER TO
PARTITION SCHEDULE FOR
TYPE - STC 45 PER TEST
No. NGC 2391
CONTINUOUS SEALANT
UNDERSIDE OF ROOF/CEILING
ASSEMBLY GWB
CONTINUOUS SEALANT
LINE OF FINISHED
CEILING
NEW 2x4 WOOD OR 3 5/8" METAL
STUDS AT 16" O.C., MATCH
EXISTING
NEW 5/8" GWB, REFER TO
PARTITION SCHEDULE FOR
TYPE - STC 45 PER TEST
No. NGC 2391 - ALIGN NEW
WALL WITH EXISTING
PILASTERS ADJACENT
CONTINUOUS SEALANT
UNDERSIDE OF ROOF
ASSEMBLY GWB
CONTINUOUS SEALANT
WALL PARTITION NOTES
1. FOR SMOKE AND FIRE RATED PARTITION SEAL AROUND ALL OPENINGS AND PENETRATIONS
WITH FIRE/SMOKE RETARDANT SEALANT. REFER TO OTHER DOCUMENTS FOR THE
APPROPRIATE U.L. DESIGN
2. STC WALL RATING: AS INDICATED IN WALL TYPE DETAILS
3. ALL WALLS MUST BE SEALED AROUND ALL OPENINGS AND PENETRATIONS WITH SEALANT
OR ACOUSTIC BATT INSULATION, OR SELF-EXPANDING INSULATION
4. ALL PARTITIONS MUST BE FROM FINISH FLOOR TO UNDERSIDE OF THE TYPE X GWB OF THE
UL ROOF ASSEMBLY. REFER TO OTHER DOCUMENTS FOR THE UL DESIGN
5. LEVEL 5 FINISH REQUIRED THROUGHOUT
6. COORDINATE ALL INTERIOR FINISHES WITH INTERIOR DESIGN SHEETS TO VERIFY EXTENTS
OF FINISHES, COLORS AND PREPARATION OF WALL TO RECEIVE FINISH.
7. DO NOT ALLOW G.W.B. TO TOUCH CONC. SLAB - STOP G.W.B. 1/4" ABOVE FLOOR SLAB AND
FILL JOINT WITH SEALANT OR REQUIRED ACOUSTIC TREATMENT. USE FIRE RETARDANT
SEALANT WHEN PARTITION IS FIRE AND/OR SMOKE RATED.
8. THE GAUGE OF METAL STUDS IS TO BE DETERMINED BY THE MANUFACTURER'S
REQUIREMENTS FOR THE INSTALLED LENGTH, U.L. RATING ASSEMBLIES, AND PROJECT
CONDITIONS UNLESS OTHERWISE NOTED. STUDS SHALL CONFORM TO ASTM C 645.
APPROXIMATELY 25 GAUGE MINIMUM ROLL FORMED, ELECTRO-GALVANIZED OR HOT-DIPPED
GALVANIZED STEEL CHANNELS IN REQUIRED WIDTHS, HAVING NOT LESS THAN 1-1/4 INCH
WIDE FLANGES, PIERCED WEBS AND SECTION PROPERTIES EQUAL TO OR EXCEEDING U.S.
GYPSUM METAL STUDS. IF STUD HEIGHT EXCEEDS MANUFACTURER'S RECOMMENDATIONS
FOR INDICATED SIZE, SPACING OR SURFACE MATERIAL, PROVIDE HEAVIER GAUGE STUDS IN
CONFORMANCE WITH THE MANUFACTURER'S PUBLISHED RECOMMENDATIONS. PROVIDE 20
GAUGE STUDS AT PARTITIONS RECEIVING TILE FINISH. PROVIDE DOUBLE STUDS, 20 GAUGE
EACH, AT EACH SIDE OF DOOR OPENINGS, AND AT EACH SIDE OF PARTITION OPENINGS
EXCEEDING 32 INCHES IN WIDTH. SCREW FASTEN STUDS TOGETHER WITH 6 INCH LONG
PIECES OF CHANNEL RUNNERS AT 1/4 POINTS OF FLOOR TO CEILING HEIGHT. FOUR (4)
SCREWS MINIMUM. SEE SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.
9. ALL WALL TYPE DETAILS ARE NOT TO SCALE.
10. ALL EXPOSED G.W.B. SHALL BE PAINTED UNLESS OTHERWISE NOTED OR FINISHED WITH
OTHER MATERIAL. SEE FINISH SCHEDULE AND PLANS.
11. ALL GYPSUM WALL BOARD MATERIAL IS TO BE REGULAR TYPE 5/8" THICK U.O.N. SEE
OTHER DOCUMENTS FOR OTHER THICKNESS AND TYPE 'X' (FIRE RATED) GWB CONDITIONS.
12. ALL SMOKE-STOP PARTITIONS, HORIZONTAL EXIT PARTITIONS, EXIST ENCLOSURES, AND
FIRE RATED WALLS SHALL BE EFFECTIVELY AND PERMANENTLY IDENTIFIED WITH SIGNS OR
STENCILING ABOVE ANY DECORATIVE CEILING AND/OR CONCEALED SPACE WITH LETTERS A
MINIMUM OF TWELVE (12") HIGH ON CONTRASTING BACKGROUND SPACED A MINIMUM OF
ONE PER WALL OR BARRIER. THE TYPE OR HOURLY RATING SHALL BE INCLUDED AT ALL
SIGN CONDITIONS. SUGGESTED WORDING: "(RATING TYPE AND HOUR) RATED BARRIER -
PROTECT ALL OPENINGS". PROVIDE DESIGNATION AT 20'-0" O.C. MIN. CONTRACTOR TO
COORDINATE WITH BUILDING INSPECTOR TO CONFIRM TYPE, LANGUAGE, SIZE AND
LOCATION OF ALL DESIGNATIONS.
13. ALL VERTICAL PIPING EXPOSED IN ROOMS SHALL BE FURRED WITH SAME MATERIAL AS
ADJACENT WALLS, WITH EXCEPTIONS FOR MECHANICAL, ELECTRICAL AND
DATA/TELEPHONE ROOMS UNLESS OTHERWISE DESIGNATED.
14. FIRE RATED GYPSUM WALL BOARD SHALL BE USED IN ALL FIRE RATED AND SMOKE BARRIER
AND SMOKE PARTITIONS, INCLUSIVE OF MOISTURE AND IMPACT RESISTANT PANELS. REFER
TO LIFE SAFETY PLANS FOR SPECIFIC PARTITION LOCATIONS.
15. ALL EXTERIOR AND INTERIOR BEARING AND NONBEARING EXTERIOR WALLS SHALL BE
PROTECTED IN ACCORDANCE WITH IBC CHAPTER 6 TABLE 601 AND CHAPTER 7 TABLE 704.8
REQUIREMENTS FOR DESIGNATED TYPE OF CONSTRUCTION.
16. STC RATED ASSEMBLIES TO BE PROVIDED WITH PRODUCT SUBMISSION FOR PARTITION
MATERIALS IN ACCORDANCE WITH MANUFACTURER'S RECOMMENDATIONS, A.N.S.I. AND
USGBC LEED NC (CURRENT EDITION) REQUIREMENTS.
SHEET:
80091E1
MARINE CORPS BASE
DEPARTMENT OF THE NAVY NAVAL FACILITIES ENGINEERING COMMAND
CAMP LEJEUNE, NORTH CAROLINA
DESIGN DIR.
SUBMITTED BY:
NAVFAC DRAWING NO.CODE IDENT. NOSIZE
SPEC.SCALE:
SATISFACTORY TO:
APPROVED: PWO OR OICC:
DR.
DES.
CHK.
DATE:
DATE:
OF
NTS
RATING/STC PRIORITIES
A501
NTS (SEE SCHEDULE ABOVE)
P5, P5A A501
NTS (SEE SCHEDULE ABOVE)
P1, P1A A501
NTS (SEE SCHEDULE ABOVE)
P2 A501
NTS (SEE SCHEDULE ABOVE)
P3 A501
NTS (SEE SCHEDULE ABOVE)
P4 A501
NTS
ROOF/CEILING ASSEMBLY - 1 HR RATED
A501
NTS (SEE SCHEDULE ABOVE)
P6, P6A A501
NTS (SEE SCHEDULE ABOVE)
P7, P7A A501
NTS (SEE SCHEDULE ABOVE)
P8 A501
R O
U N
D P
EN
ET
R
AT
IO
NUNDER NO
CIRCUMSTANCES
CAN THE PIPE
PENETRATE OR
COME WITHIN 4" OF
THE PANEL SEAM
NTS
ROOF VENT DETAIL
A501
CONTINUOUS BEAD OF SEALANT.
SET ALL FLANGES IN FULL BED
OF SEALANT.
STAINLESS STEEL CLAMPING
RING IN BED OF SEALANT.
STANDING SEAM HOLD DOWN
CLIPS INSIDE MECHANICAL
SEAMS.
MANUFACTURER RECOMMENDED
GASKETED FASTENERS 3" O.C.
MAXIMUM VENT BOOT FLASHING
COVER.
SET IN FULL PERIMETER BED OF
SEALANT AND SECURE FLANGES
PER MANUFACTURER'S
REQUIREMENTS
PREFINISHED METAL FLASHING
FORMING CRICKET ON HIGH
SIDE. SET IN SEALANT/ADHESIVE
LAP SEALANT, TYP.
NTS
GOOSENECK DETAIL
A501
SELF ADHERING ICE AND WATER
MEMBRANE WATERPROOFING
PREFINISHED METAL ROOF VENT
W/ INTEGRAL BASE, LAP
SEALANT AND FASTENERS AT
ALL PERIMETERS
AutoCAD SHX Text
CONST. CONTR. NO.
AutoCAD SHX Text
CONSTRUCTION DOCUMENTS
AutoCAD SHX Text A-501
AutoCAD SHX Text
K. ROOT
AutoCAD SHX Text
K. ROOT / S. CONTRERAS
AutoCAD SHX Text
K. ROOT
AutoCAD SHX Text
K. ROOT
AutoCAD SHX Text
J. FRANKLIN ORR
AutoCAD SHX Text
DESIGN WING RELOCATION
AutoCAD SHX Text
BUILDING 1005
AutoCAD SHX Text
PARTITION TYPES
AutoCAD SHX Text 60036660
AutoCAD SHX Text 21-0019
AutoCAD SHX Text
NOTED
AutoCAD SHX Text
NA
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
PARTITION SCHEDULE - WALL TYPES
AutoCAD SHX Text No.
AutoCAD SHX Text
LOCATION
AutoCAD SHX Text
REG GWB
AutoCAD SHX Text
ABUSE RESIST GWB
AutoCAD SHX Text
TYPE X GWB
AutoCAD SHX Text
SOUND REDUCING GWB
AutoCAD SHX Text
MOIST. RESIST. GWB
AutoCAD SHX Text
STUDS
AutoCAD SHX Text
INSULATION
AutoCAD SHX Text P1
AutoCAD SHX Text
INTERIOR SIDE OF EXISTING EXTERIOR STUCCO WALL
AutoCAD SHX Text
5/8" ROOM SIDE
AutoCAD SHX Text
AT CONFERENCE ROOMS
AutoCAD SHX Text
AT BREAK ROOM
AutoCAD SHX Text
EXISTING METAL
AutoCAD SHX Text
1 1/2" RIGID INSULATION
AutoCAD SHX Text P1A
AutoCAD SHX Text
INTERIOR SIDE OF EXISTING EXTERIOR STUCCO WALL
AutoCAD SHX Text
5/8" CORRIDOR SIDE
AutoCAD SHX Text
5/8" CORRIDOR
AutoCAD SHX Text
EXISTING METAL
AutoCAD SHX Text
1 1/2" RIGID INSULATION
AutoCAD SHX Text P2
AutoCAD SHX Text
FURRED OUT ON INTERIOR SIDE OF EXISTING EXTERIOR STUCCO WALL
AutoCAD SHX Text
5/8" ROOM SIDE
AutoCAD SHX Text
2X4 WOOD
AutoCAD SHX Text
3 1/2" BATT INSULATION
AutoCAD SHX Text P3
AutoCAD SHX Text
FURRED OUT ON INTERIOR SIDE OF EXISTING EXTERIOR STUCCO WALL
AutoCAD SHX Text
5/8" ROOM SIDE
AutoCAD SHX Text
AT CONFERENCE ROOMS
AutoCAD SHX Text
AT BREAK ROOM
AutoCAD SHX Text
6" METAL
AutoCAD SHX Text
MIN. 3 1/2" BATT INSULATION
AutoCAD SHX Text P4
AutoCAD SHX Text
INTERIOR SIDE OF EXISTING EXTERIOR EIFIS WALL
AutoCAD SHX Text
5/8" ROOM SIDE
AutoCAD SHX Text
EXISTING WOOD
AutoCAD SHX Text
3 1/2" BATT INSULATION
AutoCAD SHX Text P5
AutoCAD SHX Text
SEE A102
AutoCAD SHX Text
5/8" ROOM SIDE
AutoCAD SHX Text
AT CONFERENCE ROOMS
AutoCAD SHX Text
EXISTING
AutoCAD SHX Text
BATT INSULATION
AutoCAD SHX Text P5A
AutoCAD SHX Text
SEE A102
AutoCAD SHX Text
5/8" ROOM SIDE
AutoCAD SHX Text
EXISTING
AutoCAD SHX Text
BATT INSULATION
AutoCAD SHX Text P6
AutoCAD SHX Text
SEE A102
AutoCAD SHX Text
5/8" ROOM SIDE
AutoCAD SHX Text
AT CONF. & MOTHER'S RM
AutoCAD SHX Text
AT BREAK ROOM
AutoCAD SHX Text
EXISTING
AutoCAD SHX Text
BATT INSULATION
AutoCAD SHX Text P6A
AutoCAD SHX Text
SEE A102
AutoCAD SHX Text
5/8" CORRIDOR SIDE
AutoCAD SHX Text
5/8" CORRIDOR & ROOM SIDE
AutoCAD SHX Text
AT CONF. & MOTHER'S RM
AutoCAD SHX Text
AT BREAK ROOM
AutoCAD SHX Text
EXISTING
AutoCAD SHX Text
BATT INSULATION
AutoCAD SHX Text P7
AutoCAD SHX Text
SEE A102
AutoCAD SHX Text
5/8" ROOM SIDE
AutoCAD SHX Text
AT CONF. & MOTHER'S RM
AutoCAD SHX Text
AT BREAK ROOM
AutoCAD SHX Text
2X4 WOOD OR 3 5/8" METAL
AutoCAD SHX Text
3 1/2" FIBER GLASS MATTS
AutoCAD SHX Text P7A
AutoCAD SHX Text
SEE A102
AutoCAD SHX Text
5/8" CORRIDOR SIDE
AutoCAD SHX Text
5/8" CORRIDOR & ROOM SIDE
AutoCAD SHX Text
AT CONF. & MOTHER'S RM
AutoCAD SHX Text
AT BREAK ROOM
AutoCAD SHX Text
2X4 WOOD OR 3 5/8" METAL
AutoCAD SHX Text
3 1/2" FIBERGLASS MATTS
AutoCAD SHX Text P8
AutoCAD SHX Text
SEE A102
AutoCAD SHX Text
5/8" ROOM SIDE
AutoCAD SHX Text
2X4 WOOD OR 3 5/8" METAL
AutoCAD SHX Text
BATT INSULATION
AutoCAD SHX Text
EXISTING
AutoCAD SHX Text
EXISTING
AutoCAD SHX Text
EXISTING
AutoCAD SHX Text
EXISTING
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
MIN 7'-6" TO F.F.
AutoCAD SHX Text
| Sheets and Views |
| A-501 PARTITION TYPES |
File details come from the government source that posted it. Updated .