This document is an electrical Power and Communication Plan drawing (E-104) for a Wing Relocation project at Marine Corps Base, specifically Building 1005. The plan details comprehensive electrical and communication infrastructure modifications, including:
Key work elements include providing new panelboards (LA, LB, LC, LBCR) to serve the 300 wing, installing new power and communication systems, connecting mechanical equipment, adding receptacles with labeling, extending communication infrastructure, and transferring existing electrical circuits to new panelboards. Specific technical requirements include installing new conduits, conductors, disconnects, and breakers for various systems like mechanical units (AHU-2, SS-1), water heater, lighting controls, fire alarm panel, and communication fiber. The plan emphasizes coordination with existing systems, minimizing power outages, and ensuring all work complies with industry standards and environmental/vapor mitigation requirements.
View the file
Other files
Show 40 more
50 files listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
X X
X X
FAV
AV
TV
AC-26,28,30
LA-6 LA-7
LA-8
LA-9
LA-10
LA-11
GF
GF GF GF
TV
TV
LA-12
L-13
LA-15,17
LA-16,18
LA-19
LA-20
LA-21
LA-22
LA-23
LA-24
LA-25
LA-26
LCP
LB-3
LB-4
LB-5
LB-6
WAP
WAP
WAP
WAP
WAP
LB-7 LB-8
LB-9
LB-10
LB-11
LB-12
LB-13
LB-14
LB-15
LB-17
LB-16
LC-4
LC-5
LC-6
LC-7
LC-8
LC-9
LC-10 LC-11
LC-13 LC-12
LC-14
LC-15
LC-16
LC-17
LC-18
LC-19
L6-30
LC-20
LB
-1
LB-19
L5-20
L5-20
L5-20
L5-20
LBCR-6,8
GF GF
LB-31
LB-32,34,36
EF-1
UH-1
AHU-2
AV
AV
TV
TV
TV
LA-32
LA-30
CONST. CONTR. NO.
REVISION 1.2 E-104
K. BROWN
K. BROWN
K. BROWN
K. ROOT
F. ORR
DESIGN WING RELOCATION
BUILDING 1005
POWER AND COMMUNICATION PLAN
60036664 21-0019
NOTED NA 17 36
0 10' 20' 40'5'
GENERAL NOTES
1. THE CONTRACTOR MUST REVIEW THE ELECTRICAL DRAWINGS AND SPECIFICATIONS AND CARRY OUT HIS WORK IN A COMPATIBLE AND
COMPLEMENTARY MANNER. SURVEY THE AFFECTED AREAS AS ALL EXISTING CONDITIONS ARE NOT COMPLETELY DEPICTED ON THE
DRAWINGS AND SOME UNUSUAL CONDITIONS EXIST.
2. EXISTING ELECTRICAL EQUIPMENT AND DEVICES MUST REMAIN UNLESS SPECIFICALLY NOTED TO BE REMOVED.
3. COORDINATE POWER OUTAGES WITH THE GOVERNMENT. MAINTAIN EXISTING ELECTRICAL SYSTEMS IN SERVICE. DISABLE SYSTEMS ONLY
TO MAKE SWITCHOVERS AND CONNECTIONS. OBTAIN PERMISSION FROM THE CONTRACTING OFFICER AT LEAST 5 DAYS BEFORE PARTIALLY
OR COMPLETELY DISABLING SYSTEM. MINIMIZE OUTAGE DURATION.
4. WHERE THE DURATION OF A PROPOSED OUTAGE CANNOT BE TOLERATED BY THE GOVERNMENT, PROVIDE TEMPORARY CONNECTIONS AS
REQUIRED TO MAINTAIN SERVICE.
5. THE CONTRACTOR MUST FIELD VERIFY ALL CIRCUITS, WIRING, CONDUIT, DIMENSIONS, POINTS OF ACCESS AND ALL FIELD CONDITIONS AFFECTING HIS WORK. BEGINNING WORK MEANS THE CONTRACTOR ACCEPTS EXISTING CONDITIONS.
6. PLAN IS A GENERAL REPRESENTATION OF EXISTING CONDITIONS. PLAN DOES NOT REFLECT ALL COMPONENTS OR CONFIGURATIONS. WORK DESCRIBED HERE-IN SHALL BE APPLIED TO ACTUAL FIELD CONDITIONS. DRAWINGS, AS A REPRESENTATION FOR EXISTING CONDITIONS, HAVE
BEEN SIMPLIFIED FOR CLARITY.
7. ROUTING OF CONDUIT AND CIRCUITS ARE AT THE DISCRETION OF THE CONTRACTOR. ROUTING SHALL ALIGN WITH GENERALLY ACCEPTED GOOD PRACTICE AND INDUSTRY STANDARDS. ALL CIRCUITS AND CONDUITS MUST BE CONCEALED IN WALLS OR ABOVE DROP CEILINGS.
8. CONDUIT AND CIRCUITS ROUTING SHALL BE PROVIDED TO AVOID INTERFERENCE WITH EXISTING SYSTEMS.
4. BRANCH CIRCUITS ARE MINIMUM 2-#12, 1-#12 EGC IN 12"C. INCREASE TO #10 CONDUCTOR TO ACCOUNT FOR VOLTAGE DROP FOR RUNS OVER
80'. LOW VOLTAGE WIRING IS NOT SHOWN FOR CLARITY. LUMINAIRE CIRCUITS SHOWN ARE DIAGRAMMATIC ONLY INDICATING CIRCUITS AND
SWITCHED/NON-SWITCHED LEGS.
5. DO NOT SCALE ELECTRICAL DRAWINGS.
KEYED NOTES
PROVIDE DEDICATED CIRCUIT CONNECTIONS FOR REFRIGERATOR(S), STOVE(S), MICROWAVE(S), RANGE HOOD(S), AND EXHAUST FAN(S).
COORDINATE LOCATIONS WITH ARCHITECTURAL PLAN. SEE BASIS OF DESIGN FOR EQUIPMENT ON SHEET A-104. MIN. (2-#12, 1-#12 EGC, IN 2"C) FOR 15A/20A APPLIANCES. (TYP.) MIN. (3-#8, #12 EGC IN 1" C.) FOR 40A/2 APPLIANCE(S) (TYP.).
PROVIDE DEDICATED CIRCUIT TO BF-1 BOTTLE FILLING STATION MIN. (2-#12, 1-#12 EGC IN 1/.2"C). EXTEND AND CONNECT. PROVIDE NEW
BREAKER AND CIRCUIT FOR CONNECTION IN PANEL LC.
PROVIDE NEW CONFERENCE ROOM MEDIA A/V PLAN. SEE CONFERENCE ROOM MEDIA ELEVATION & DETAIL. PROVIDE RECEPTACLES, A/V CONNECTIONS, TELECOM OUTLETS, & CABLE TV OUTLET. PROVIDE HDMI CONNECTION FROM WALL TO CENTER OF FLOOR. FLOOR CONNECTIONS MUST BE RAN FLUSH IN SLAB. CREATE CHANNEL IN EXISTING SLAB BUT DO NOT FULLY PENETRATE. ENVIRONMENTAL AND VAPOR MITIGATION REQUIREMENTS PROHIBIT FULL PENETRATION OF THE SLAB. RESEAL CHANNEL AND RELATED CRACKS.
PROVIDE NEW CONDUCTORS IN CONDUIT FROM PANEL AC (#26.28,30) TO NEW MECHANICAL UNIT AHU-2. PROVIDE NEW DISCONNECT (60A/3/3R) AND NEW 60A/3 BREAKER TO SUPPLY AHU-2. REMOVE EXISTING 50A/3 BREAKER FROM PANEL AC & PROVIDE NEW 60A/2 BREAKER.
CONDUCTORS MUST BE MINIMUM (3 - #4, 1 - #4 N, 1-#8 EGC IN 2" C.). EXISTING PANELBOARD AC IS LOCATED IN THE MAIN ELECTRICAL ROOM CENTRALLY LOCATED IN THE BUILDING. PROVIDE CONNECTION IS ACCORDANCE WITH MANUFACTURER RECOMMENDATIONS.
PROVIDE NEW CONNECTION TO WATER HEATER WH-1. EXTEND AND CONNECT MIN. (3-#10, 1-#10 EGC IN 34" CONDUIT). PROVIDE NEW 30A/3/3R DISCONNECT NEXT TO WATER HEATER. PROVIDE NEW 30A/2 BREAKER TO FEED NEW WATER HEATER CIRCUIT.
PROVIDE CIRCUIT CONNECTION TO LIGHTING CONTROL PANEL IN ACCORDANCE MANUFACTURER RECOMMENDATIONS.
APPROXIMATE LOCATION OF PANEL AC.
PROVIDE NEW CIRCUIT TO FIRE ALARM NAC PANEL. PROVIDE SURGE SUPPRESSION DEVICE AS REQUIRED. SEE ARCHITECTURAL SHEETS
FOR DETAILS.
PROVIDE NEW CONDUCTORS IN CONDUIT MIN. (3-#10, 1-#10 EGC) FROM PANEL LBCR TO NEW MECHANICAL UNIT SS-1. PROVIDE NEW 30A/3/3R DISCONNECT FOR SS-1. PROVIDE CIRCUIT CONNECTION IN COORDINATION WITH MANUFACTURER RECOMMENDATIONS. SEE
MECHANICAL SHEETS FOR DETAILS.
PROVIDE NEW CONDUIT FOR COMMUNICATION FIBER, TO MATCH EXISTING COMM. ROOM CONDUIT SIZING. SEE DETAILS ON
COMMUNICATION RISER DIAGRAM.
PROVIDE NEW CONNECTION FOR UH-1. PROVIDE NEW 30A/3/3R DISCONNECT (3-#10,1-#10 EGC IN 1" C).
PROVIDE NEW CONNECTION FOR EF-1 (2-#12, 1-#12 EGC IN 12"C).
POWER AND COMMUNICATION PLAN
COMM.
ROOM
WORK NOTES
"LA"
"LC"
"LB"
1. PROVIDE NEW POWER AND COMMUNICATION PLAN.
2. PROVIDE NEW PANELBOARDS LA, LB, LC, & LBCR TO SERVE THE 300 WING. PROVIDE BREAKERS AND GROUNDING FOR EACH PANELBOARD AS
REQUIRED. SEE PANELBOARD SCHEDULES AND RISER DIAGRAM FOR DETAILS.
3. PROVIDE CONNECTIONS TO MECHANICAL EQUIPMENT. SEE MECHANICAL SHEETS FOR ADDITIONAL DETAILS. PROVIDE NEW CONNECTIONS
FOR VAVS.
4. PROVIDE NEW RECEPTACLES (MINIMUM 2-#12, 1-#12 EGC IN 12" C). PROVIDE LABELS ON EACH RECEPTACLE COVER PLATE INDICATING THE
SERVING PANELBOARD AND CIRCUIT NUMBER.
5. PROVIDE NEW COMMUNICATION SYSTEM TO SERVE THE 300 WING. PROVIDE OUTLET(S), BACKBOX(ES), CABLE(S), CABLE TRAYS, AND
CONDUIT(S). EXTEND CONDUIT 18" INTO THE SPACE BETWEEN THE DROP CEILING AND THE HARD CEILING. FULL COMMUNICATION SYSTEM MUST BE PROVIDED BY CONTRACTOR IN ACCORDANCE WITH DRAWINGS AND COMMUNICATION 27 10 00. SPEC. SEE COMM. RISER DIAGRAM.
6. PROVIDE NEW COMMUNICATION ROOM AND COMMUNICATION SYSTEM TO SERVE THE 300 WING. PROVIDE SETUP AS INDICATED ON COMMUNICATION RISER DIAGRAM. EXTEND AND CONNECT EXISTING PULLED BACK FIBER IN CONDUIT TO NEW COMMUNICATION ROOM. MATCH
EXISTING SYSTEM CHARACTERISTICS AND SIZES.
7. PROVIDE CIRCUIT FOR ELECTROMAGNETIC DOOR HOLDER. PROVIDE 24V CIRCUIT AS RECOMMENDED BY MANUFACTURER. BASIS OF DESIGN FOR DOOR HOLDER IS DORMAKABA EM 500A. SEE ARCHITECTURAL SHEETS FOR ADDITIONAL INFORMATION.
8. FEEDERS AND CIRCUITS (ORIGINATING FROM EXISTING PANELS L1, L2, AND M) THAT SUPPLY POWER TO SPACES OUTSIDE THE AREA OF WORK MUST BE TRANSFERRED TO NEW PANELBOARDS LA, LB, OR LC. THESE CIRCUITS ARE NOT IDENTIFIED ON PLANS. PROVIDE NEW BREAKERS IN PANELBOARD LA, LB, OR LC TO SERVE THESE MISCELLANEOUS LOADS. RECONNECT SUB PANELS "S", "H", OR OTHERS IDENTIFIED, TO NEW PANELBOARDS. PROVIDE NEW CIRCUITS OR FEEDERS WHERE EXISTING CAN NOT BE REUSED & MATCH EXISTING ELECTRICAL
CHARACTERISTICS. SEE POWER RISER DIAGRAM FOR DETAILS.
9. EXTEND AND CONNECT EXISTING VAPOR INTRUSION MITIGATION SYSTEM CIRCUITS TO NEW PANELBOARD SPACE. MATCH EXISTING
CONFIGURATION.
10. EXTEND AND CONNECT EXISTING EXTERIOR LIGHTING CIRCUITS TO NEW PANELBOARD SPACE.
11. EXTEND AND CONNECT EXISTING VAPOR INTRUSION MITIGATION SYSTEM CIRCUITS TO NEW PANELBOARDS SPACE.
12. EXTEND AND CONNECT ANY OTHER UNIDENTIFIED CIRCUITS, NOT SCHEDULED FOR DEMOLITION, TO NEW PANELBOARD SPACE.
NEW
PANELBOARD
NEW
PANELBOARD
NEW
PANELBOARD
"LBCR"
PANELBOARD
NEW
LIGHTING
CONTROL
PANEL
COMM.
ROOM
AutoCAD SHX Text E
AutoCAD SHX Text
SHEET:
AutoCAD SHX Text 80091
AutoCAD SHX Text E1
AutoCAD SHX Text
MARINE CORPS BASE
AutoCAD SHX Text
DEPARTMENT OF THE NAVY NAVAL FACILITIES ENGINEERING SYSTEMS COMMAND
AutoCAD SHX Text
CAMP LEJEUNE, NORTH CAROLINA
AutoCAD SHX Text
DESIGN DIR.
AutoCAD SHX Text
SUBMITTED BY:
AutoCAD SHX Text
NAVFAC DRAWING NO.
AutoCAD SHX Text
CODE IDENT. NO
AutoCAD SHX Text
SIZE
AutoCAD SHX Text
SPEC.
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
SATISFACTORY TO:
AutoCAD SHX Text
APPROVED: PWO OR OICC:
AutoCAD SHX Text
DR.
AutoCAD SHX Text
DES.
AutoCAD SHX Text
CHK.
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
OF
kyle.t.brown Cloud kyle.t.brown Cloud kyle.t.brown Cloud kyle.t.brown Cloud
File details come from the government source that posted it. Updated .