This document is an electrical Power and Communication Plan drawing (E-104) for a Wing Relocation project at Marine Corps Base, specifically Building 1005. The plan details comprehensive electrical and communication infrastructure modifications, including:

Key work elements include providing new panelboards (LA, LB, LC, LBCR) to serve the 300 wing, installing new power and communication systems, connecting mechanical equipment, adding receptacles with labeling, extending communication infrastructure, and transferring existing electrical circuits to new panelboards. Specific technical requirements include installing new conduits, conductors, disconnects, and breakers for various systems like mechanical units (AHU-2, SS-1), water heater, lighting controls, fire alarm panel, and communication fiber. The plan emphasizes coordination with existing systems, minimizing power outages, and ensuring all work complies with industry standards and environmental/vapor mitigation requirements.

View the file

Other files

File Type Posted
N4008524R2785 Amendment 0008.pdf PDF
N4008524R2785 Amendment 0007.pdf PDF
M101_rev 2.pdf PDF
23 73 33_Amendment 2.pdf PDF
E-103.pdf PDF
E-107.pdf PDF
M601.pdf PDF
N4008524R2785 Amendment 0006.pdf PDF
VMR- uncapped.jpg JPG image
E-101.pdf PDF
E-105.pdf PDF
M103.pdf PDF
M104.pdf PDF
M602.pdf PDF
VMR- capped.jpg JPG image
T-1.pdf PDF
25 05 11.00.pdf PDF
A-105.pdf PDF
A-501.pdf PDF
E-102.pdf PDF
M501.pdf PDF
N4008524R2785 Amendment 0005.pdf PDF
01 32 16.00 20.pdf PDF
22 00 00.pdf PDF
23 09 23.13 20 Attachment 2.pdf PDF
23 09 00.pdf PDF
23 09 23.13 20 Attachment 4.pdf PDF
23 09 13.pdf PDF
23 09 23.02.pdf PDF
Attachment M - Specifications TOC.pdf PDF
Attachment N - Revised Eletrical-Telecomm Sheets.pdf PDF
Attachment O - Revised Specs pg3.pdf PDF
N4008524R2785 Amendment 0003.pdf PDF
Attachment P - Site Visit Log.pdf PDF
N4008524R2785 Amendment 0002.pdf PDF
Attachment I - Site Visit Information REVISED.pdf PDF
Attachment J - Site Visit Participant Log.xlsx XLSX spreadsheet
Attachment L - Electrical Room.pdf PDF
Attachment I - Site Visit Information.pdf PDF
N4008524R2785 Amendment 0001.pdf PDF
Attachment K - Asbestos Inspection Report.pdf PDF
Attachment A - PPI LOG TEMPLATE.xlsx XLSX spreadsheet
Attachment B - CONSTRUCTION AND DESIGN EXPERIENCE PROJECT DATA.docx DOCX document
Attachment E - B1005 Drawings.pdf PDF
Attachment F - B1005 Specifications.pdf PDF
Attachment H - PIEE VENDOR ACCESS INSTRUCTIONS.pdf PDF
N4008524R2785 Small Business Marine Corps MACC for General Construction.pdf PDF
Attachment C- PAST PERFORMANCE QUESTIONNAIRE.docx DOCX document
Attachment D - B1005 Price Proposal Form.docx DOCX document
Attachment G - B1005 Statement of Work.pdf PDF
Show 40 more

50 files listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

X X

X X

FAV

AV

TV

AC-26,28,30

LA-6 LA-7

LA-8

LA-9

LA-10

LA-11

GF

GF GF GF

TV

TV

LA-12

L-13

LA-15,17

LA-16,18

LA-19

LA-20

LA-21

LA-22

LA-23

LA-24

LA-25

LA-26

LCP

LB-3

LB-4

LB-5

LB-6

WAP

WAP

WAP

WAP

WAP

LB-7 LB-8

LB-9

LB-10

LB-11

LB-12

LB-13

LB-14

LB-15

LB-17

LB-16

LC-4

LC-5

LC-6

LC-7

LC-8

LC-9

LC-10 LC-11

LC-13 LC-12

LC-14

LC-15

LC-16

LC-17

LC-18

LC-19

L6-30

LC-20

LB

-1

LB-19

L5-20

L5-20

L5-20

L5-20

LBCR-6,8

GF GF

LB-31

LB-32,34,36

EF-1

UH-1

AHU-2

AV

AV

TV

TV

TV

LA-32

LA-30

CONST. CONTR. NO.

REVISION 1.2 E-104

K. BROWN

K. BROWN

K. BROWN

K. ROOT

F. ORR

DESIGN WING RELOCATION

BUILDING 1005

POWER AND COMMUNICATION PLAN

60036664 21-0019

NOTED NA 17 36

0 10' 20' 40'5'

GENERAL NOTES

1. THE CONTRACTOR MUST REVIEW THE ELECTRICAL DRAWINGS AND SPECIFICATIONS AND CARRY OUT HIS WORK IN A COMPATIBLE AND

COMPLEMENTARY MANNER. SURVEY THE AFFECTED AREAS AS ALL EXISTING CONDITIONS ARE NOT COMPLETELY DEPICTED ON THE

DRAWINGS AND SOME UNUSUAL CONDITIONS EXIST.

2. EXISTING ELECTRICAL EQUIPMENT AND DEVICES MUST REMAIN UNLESS SPECIFICALLY NOTED TO BE REMOVED.

3. COORDINATE POWER OUTAGES WITH THE GOVERNMENT. MAINTAIN EXISTING ELECTRICAL SYSTEMS IN SERVICE. DISABLE SYSTEMS ONLY

TO MAKE SWITCHOVERS AND CONNECTIONS. OBTAIN PERMISSION FROM THE CONTRACTING OFFICER AT LEAST 5 DAYS BEFORE PARTIALLY

OR COMPLETELY DISABLING SYSTEM. MINIMIZE OUTAGE DURATION.

4. WHERE THE DURATION OF A PROPOSED OUTAGE CANNOT BE TOLERATED BY THE GOVERNMENT, PROVIDE TEMPORARY CONNECTIONS AS

REQUIRED TO MAINTAIN SERVICE.

5. THE CONTRACTOR MUST FIELD VERIFY ALL CIRCUITS, WIRING, CONDUIT, DIMENSIONS, POINTS OF ACCESS AND ALL FIELD CONDITIONS AFFECTING HIS WORK. BEGINNING WORK MEANS THE CONTRACTOR ACCEPTS EXISTING CONDITIONS.

6. PLAN IS A GENERAL REPRESENTATION OF EXISTING CONDITIONS. PLAN DOES NOT REFLECT ALL COMPONENTS OR CONFIGURATIONS. WORK DESCRIBED HERE-IN SHALL BE APPLIED TO ACTUAL FIELD CONDITIONS. DRAWINGS, AS A REPRESENTATION FOR EXISTING CONDITIONS, HAVE

BEEN SIMPLIFIED FOR CLARITY.

7. ROUTING OF CONDUIT AND CIRCUITS ARE AT THE DISCRETION OF THE CONTRACTOR. ROUTING SHALL ALIGN WITH GENERALLY ACCEPTED GOOD PRACTICE AND INDUSTRY STANDARDS. ALL CIRCUITS AND CONDUITS MUST BE CONCEALED IN WALLS OR ABOVE DROP CEILINGS.

8. CONDUIT AND CIRCUITS ROUTING SHALL BE PROVIDED TO AVOID INTERFERENCE WITH EXISTING SYSTEMS.

4. BRANCH CIRCUITS ARE MINIMUM 2-#12, 1-#12 EGC IN 12"C. INCREASE TO #10 CONDUCTOR TO ACCOUNT FOR VOLTAGE DROP FOR RUNS OVER

80'. LOW VOLTAGE WIRING IS NOT SHOWN FOR CLARITY. LUMINAIRE CIRCUITS SHOWN ARE DIAGRAMMATIC ONLY INDICATING CIRCUITS AND

SWITCHED/NON-SWITCHED LEGS.

5. DO NOT SCALE ELECTRICAL DRAWINGS.

KEYED NOTES

PROVIDE DEDICATED CIRCUIT CONNECTIONS FOR REFRIGERATOR(S), STOVE(S), MICROWAVE(S), RANGE HOOD(S), AND EXHAUST FAN(S).

COORDINATE LOCATIONS WITH ARCHITECTURAL PLAN. SEE BASIS OF DESIGN FOR EQUIPMENT ON SHEET A-104. MIN. (2-#12, 1-#12 EGC, IN 2"C) FOR 15A/20A APPLIANCES. (TYP.) MIN. (3-#8, #12 EGC IN 1" C.) FOR 40A/2 APPLIANCE(S) (TYP.).

PROVIDE DEDICATED CIRCUIT TO BF-1 BOTTLE FILLING STATION MIN. (2-#12, 1-#12 EGC IN 1/.2"C). EXTEND AND CONNECT. PROVIDE NEW

BREAKER AND CIRCUIT FOR CONNECTION IN PANEL LC.

PROVIDE NEW CONFERENCE ROOM MEDIA A/V PLAN. SEE CONFERENCE ROOM MEDIA ELEVATION & DETAIL. PROVIDE RECEPTACLES, A/V CONNECTIONS, TELECOM OUTLETS, & CABLE TV OUTLET. PROVIDE HDMI CONNECTION FROM WALL TO CENTER OF FLOOR. FLOOR CONNECTIONS MUST BE RAN FLUSH IN SLAB. CREATE CHANNEL IN EXISTING SLAB BUT DO NOT FULLY PENETRATE. ENVIRONMENTAL AND VAPOR MITIGATION REQUIREMENTS PROHIBIT FULL PENETRATION OF THE SLAB. RESEAL CHANNEL AND RELATED CRACKS.

PROVIDE NEW CONDUCTORS IN CONDUIT FROM PANEL AC (#26.28,30) TO NEW MECHANICAL UNIT AHU-2. PROVIDE NEW DISCONNECT (60A/3/3R) AND NEW 60A/3 BREAKER TO SUPPLY AHU-2. REMOVE EXISTING 50A/3 BREAKER FROM PANEL AC & PROVIDE NEW 60A/2 BREAKER.

CONDUCTORS MUST BE MINIMUM (3 - #4, 1 - #4 N, 1-#8 EGC IN 2" C.). EXISTING PANELBOARD AC IS LOCATED IN THE MAIN ELECTRICAL ROOM CENTRALLY LOCATED IN THE BUILDING. PROVIDE CONNECTION IS ACCORDANCE WITH MANUFACTURER RECOMMENDATIONS.

PROVIDE NEW CONNECTION TO WATER HEATER WH-1. EXTEND AND CONNECT MIN. (3-#10, 1-#10 EGC IN 34" CONDUIT). PROVIDE NEW 30A/3/3R DISCONNECT NEXT TO WATER HEATER. PROVIDE NEW 30A/2 BREAKER TO FEED NEW WATER HEATER CIRCUIT.

PROVIDE CIRCUIT CONNECTION TO LIGHTING CONTROL PANEL IN ACCORDANCE MANUFACTURER RECOMMENDATIONS.

APPROXIMATE LOCATION OF PANEL AC.

PROVIDE NEW CIRCUIT TO FIRE ALARM NAC PANEL. PROVIDE SURGE SUPPRESSION DEVICE AS REQUIRED. SEE ARCHITECTURAL SHEETS

FOR DETAILS.

PROVIDE NEW CONDUCTORS IN CONDUIT MIN. (3-#10, 1-#10 EGC) FROM PANEL LBCR TO NEW MECHANICAL UNIT SS-1. PROVIDE NEW 30A/3/3R DISCONNECT FOR SS-1. PROVIDE CIRCUIT CONNECTION IN COORDINATION WITH MANUFACTURER RECOMMENDATIONS. SEE

MECHANICAL SHEETS FOR DETAILS.

PROVIDE NEW CONDUIT FOR COMMUNICATION FIBER, TO MATCH EXISTING COMM. ROOM CONDUIT SIZING. SEE DETAILS ON

COMMUNICATION RISER DIAGRAM.

PROVIDE NEW CONNECTION FOR UH-1. PROVIDE NEW 30A/3/3R DISCONNECT (3-#10,1-#10 EGC IN 1" C).

PROVIDE NEW CONNECTION FOR EF-1 (2-#12, 1-#12 EGC IN 12"C).

POWER AND COMMUNICATION PLAN

COMM.

ROOM

WORK NOTES

"LA"

"LC"

"LB"

1. PROVIDE NEW POWER AND COMMUNICATION PLAN.

2. PROVIDE NEW PANELBOARDS LA, LB, LC, & LBCR TO SERVE THE 300 WING. PROVIDE BREAKERS AND GROUNDING FOR EACH PANELBOARD AS

REQUIRED. SEE PANELBOARD SCHEDULES AND RISER DIAGRAM FOR DETAILS.

3. PROVIDE CONNECTIONS TO MECHANICAL EQUIPMENT. SEE MECHANICAL SHEETS FOR ADDITIONAL DETAILS. PROVIDE NEW CONNECTIONS

FOR VAVS.

4. PROVIDE NEW RECEPTACLES (MINIMUM 2-#12, 1-#12 EGC IN 12" C). PROVIDE LABELS ON EACH RECEPTACLE COVER PLATE INDICATING THE

SERVING PANELBOARD AND CIRCUIT NUMBER.

5. PROVIDE NEW COMMUNICATION SYSTEM TO SERVE THE 300 WING. PROVIDE OUTLET(S), BACKBOX(ES), CABLE(S), CABLE TRAYS, AND

CONDUIT(S). EXTEND CONDUIT 18" INTO THE SPACE BETWEEN THE DROP CEILING AND THE HARD CEILING. FULL COMMUNICATION SYSTEM MUST BE PROVIDED BY CONTRACTOR IN ACCORDANCE WITH DRAWINGS AND COMMUNICATION 27 10 00. SPEC. SEE COMM. RISER DIAGRAM.

6. PROVIDE NEW COMMUNICATION ROOM AND COMMUNICATION SYSTEM TO SERVE THE 300 WING. PROVIDE SETUP AS INDICATED ON COMMUNICATION RISER DIAGRAM. EXTEND AND CONNECT EXISTING PULLED BACK FIBER IN CONDUIT TO NEW COMMUNICATION ROOM. MATCH

EXISTING SYSTEM CHARACTERISTICS AND SIZES.

7. PROVIDE CIRCUIT FOR ELECTROMAGNETIC DOOR HOLDER. PROVIDE 24V CIRCUIT AS RECOMMENDED BY MANUFACTURER. BASIS OF DESIGN FOR DOOR HOLDER IS DORMAKABA EM 500A. SEE ARCHITECTURAL SHEETS FOR ADDITIONAL INFORMATION.

8. FEEDERS AND CIRCUITS (ORIGINATING FROM EXISTING PANELS L1, L2, AND M) THAT SUPPLY POWER TO SPACES OUTSIDE THE AREA OF WORK MUST BE TRANSFERRED TO NEW PANELBOARDS LA, LB, OR LC. THESE CIRCUITS ARE NOT IDENTIFIED ON PLANS. PROVIDE NEW BREAKERS IN PANELBOARD LA, LB, OR LC TO SERVE THESE MISCELLANEOUS LOADS. RECONNECT SUB PANELS "S", "H", OR OTHERS IDENTIFIED, TO NEW PANELBOARDS. PROVIDE NEW CIRCUITS OR FEEDERS WHERE EXISTING CAN NOT BE REUSED & MATCH EXISTING ELECTRICAL

CHARACTERISTICS. SEE POWER RISER DIAGRAM FOR DETAILS.

9. EXTEND AND CONNECT EXISTING VAPOR INTRUSION MITIGATION SYSTEM CIRCUITS TO NEW PANELBOARD SPACE. MATCH EXISTING

CONFIGURATION.

10. EXTEND AND CONNECT EXISTING EXTERIOR LIGHTING CIRCUITS TO NEW PANELBOARD SPACE.

11. EXTEND AND CONNECT EXISTING VAPOR INTRUSION MITIGATION SYSTEM CIRCUITS TO NEW PANELBOARDS SPACE.

12. EXTEND AND CONNECT ANY OTHER UNIDENTIFIED CIRCUITS, NOT SCHEDULED FOR DEMOLITION, TO NEW PANELBOARD SPACE.

NEW

PANELBOARD

NEW

PANELBOARD

NEW

PANELBOARD

"LBCR"

PANELBOARD

NEW

LIGHTING

CONTROL

PANEL

COMM.

ROOM

AutoCAD SHX Text E

AutoCAD SHX Text

SHEET:

AutoCAD SHX Text 80091

AutoCAD SHX Text E1

AutoCAD SHX Text

MARINE CORPS BASE

AutoCAD SHX Text

DEPARTMENT OF THE NAVY NAVAL FACILITIES ENGINEERING SYSTEMS COMMAND

AutoCAD SHX Text

CAMP LEJEUNE, NORTH CAROLINA

AutoCAD SHX Text

DESIGN DIR.

AutoCAD SHX Text

SUBMITTED BY:

AutoCAD SHX Text

NAVFAC DRAWING NO.

AutoCAD SHX Text

CODE IDENT. NO

AutoCAD SHX Text

SIZE

AutoCAD SHX Text

SPEC.

AutoCAD SHX Text

SCALE:

AutoCAD SHX Text

SATISFACTORY TO:

AutoCAD SHX Text

APPROVED: PWO OR OICC:

AutoCAD SHX Text

DR.

AutoCAD SHX Text

DES.

AutoCAD SHX Text

CHK.

AutoCAD SHX Text

DATE:

AutoCAD SHX Text

DATE:

AutoCAD SHX Text

OF

kyle.t.brown Cloud kyle.t.brown Cloud kyle.t.brown Cloud kyle.t.brown Cloud

File details come from the government source that posted it. Updated .