Attachment 6 - Drawings Vol 1 Part4.pdf
PDF 39 MB Posted
- Solicitation number
- 36C77625R0092-RFP
About this file
This file is a set of structural construction drawings for the EHRM Infrastructure Upgrades project at James A. Haley Veterans Hospital in Tampa, Florida, issued by the U.S. Department of Veterans Affairs Office of Construction and Facilities Management. The drawings are marked "Issued for Construction" dated April 4, 2025, and are not intended for construction purposes based on notation.
The document comprises detailed structural plans and specifications for Building 1, including the first floor, second floor, and roof structural systems. The project involves upgrades to an existing facility with both demolition and new construction work. Structural elements include composite concrete slabs on metal deck (1½" and 3" composite metal deck with 4½" concrete fill), steel beams (W14x22, W18x40, and other wide-flange sections conforming to ASTM A992 with 50 KSI yield strength), cast-in-place concrete slabs on grade (9" thick with #5 reinforcing bars at 12" on-center), and grade beams with specified reinforcement schedules. The project design complies with the 2023 Florida Building Code, 2021 IBC, ASCE 7-22 for seismic and wind loads (155 mph basic wind speed, Seismic Design Category A), and VA design criteria. Structural design includes moment connections for lateral load resistance in the north-south direction and connections to existing building structure for east-west stability. The drawings designate architect CB Design Group (Alexandria, VA) and structural/MEP consultants, with a professional seal dated 07/13/2022. Contractor responsibilities include verification of all existing conditions, dimensions, and site coordinates prior to construction, coordination of MEP penetrations, and submission of shop drawings for fabrication and erection procedures with structural engineer review required before work begins.
View the file
Other files
Show 40 more
50 files listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
VA Project Number:
Building:
Drawing Number:
Project Title:
Project Location:
Issue Date:
Checked By: Drawn By:
Drawing Title:
FULLY
SPRINKLER
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
A
Submission:
ARCHITECT / ENGINEER OF RECORD:
Revisions: Date:
CONSULTANTS:
/8
'-0
4 '
8 ' 6 '
/4
'-0
/8
'-0
/2
'-0
/4
'-0
'-0
-1
/2
'-0
'-0
CONSULTANT:
COMPASS
8734 GALLOWAY TRAIL
NOVELTY, OH. 44072
619-925-1647
ARCHITECT:
CB DESIGN GROUP
421 KING ST
SUITE 301
ALEXANDRIA, VA 22314
703-772-4213
PROFESSIONAL SEAL:
James A. Haley Veterans Hospital 13000 Bruce B. Downs Blvd.
Tampa, FL. 33612
2345678910111213141516
B
C
D
E
F
G
H
I
J
12345678910111213141516
CONSULTANT:
SCOTT PRZYBYSZ
15 SUNNEN DR.
SUITE 104
ST. LOUIS, MO 63143
CONSULTANT:
MARK DYCK
148 S. QUEEN ST.
SUITE 201
MARTINSBURG, WV.
CONSULTANT:
CLARE KRAMER
2815 DIRECTORS
ROW SUITE 500
ORLANDO, FL. 32809
407-917-2430
04/04/2025
673-20-107
AuthorChecker
EHRM INFRASTRUCTURE UPGRADES
TAMPA, FL.
ISSUED FOR CONSTRUCTION
EXISTING LIFE SAFETY PLAN
LS-101-5
3-
-1
. L
S-
1- 5.
7/
/2
2.
pd f
BUILDING 1 - FIFTH FLOOR
LIFE SAFETY DRAWINGS PROVIDED BY THE VA AND
ALL CONDITIONS TO BE VERIFIED BY CONTRACTOR
Drawing Number:
Project Title:
Project Location:
Issue Date:
Checked By: Drawn By:
Drawing Title:
FULLY
SPRINKLER
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
A
Submission:
ARCHITECT / ENGINEER OF RECORD:
Revisions: Date:
CONSULTANTS:
/8
'-0
4 '
8 ' 6 '
/4
'-0
/8
'-0
/2
'-0
/4
'-0
'-0
-1
/2
'-0
'-0
CONSULTANT:
COMPASS
8734 GALLOWAY TRAIL
NOVELTY, OH. 44072
619-925-1647
ARCHITECT:
CB DESIGN GROUP
421 KING ST
SUITE 301
ALEXANDRIA, VA 22314
703-772-4213
PROFESSIONAL SEAL:
James A. Haley Veterans Hospital 13000 Bruce B. Downs Blvd.
Tampa, FL. 33612
2345678910111213141516
B
C
D
E
F
G
H
I
J
12345678910111213141516
CONSULTANT:
SCOTT PRZYBYSZ
15 SUNNEN DR.
SUITE 104
ST. LOUIS, MO 63143
CONSULTANT:
MARK DYCK
148 S. QUEEN ST.
SUITE 201
MARTINSBURG, WV.
CONSULTANT:
CLARE KRAMER
2815 DIRECTORS
ROW SUITE 500
ORLANDO, FL. 32809
407-917-2430
04/04/2025
673-20-107
AuthorChecker
EHRM INFRASTRUCTURE UPGRADES
TAMPA, FL.
ISSUED FOR CONSTRUCTION
EXISTING LIFE SAFETY PLAN
LS-101-6
3-
-1
. L
S-
1- 6.
7/
/2
2.
pd f
BUILDING 1 - SIXTH FLOOR
Drawing Number:
Project Title:
Project Location:
Issue Date:
Checked By: Drawn By:
Drawing Title:
FULLY
SPRINKLER
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
A
Submission:
ARCHITECT / ENGINEER OF RECORD:
Revisions: Date:
CONSULTANTS:
/8
'-0
4 '
8 ' 6 '
/4
'-0
/8
'-0
/2
'-0
/4
'-0
'-0
-1
/2
'-0
'-0
CONSULTANT:
COMPASS
8734 GALLOWAY TRAIL
NOVELTY, OH. 44072
619-925-1647
ARCHITECT:
CB DESIGN GROUP
421 KING ST
SUITE 301
ALEXANDRIA, VA 22314
703-772-4213
PROFESSIONAL SEAL:
James A. Haley Veterans Hospital 13000 Bruce B. Downs Blvd.
Tampa, FL. 33612
2345678910111213141516
B
C
D
E
F
G
H
I
J
12345678910111213141516
CONSULTANT:
SCOTT PRZYBYSZ
15 SUNNEN DR.
SUITE 104
ST. LOUIS, MO 63143
CONSULTANT:
MARK DYCK
148 S. QUEEN ST.
SUITE 201
MARTINSBURG, WV.
CONSULTANT:
CLARE KRAMER
2815 DIRECTORS
ROW SUITE 500
ORLANDO, FL. 32809
407-917-2430
04/04/2025
673-20-107
AuthorChecker
EHRM INFRASTRUCTURE UPGRADES
TAMPA, FL.
ISSUED FOR CONSTRUCTION
EXISTING LIFE SAFETY PLAN
LS-101-7
3-
-1
. L
S-
1- 7.
7/
/2
2.
pd f
BUILDING 1 - SEVENTH FLOOR
Drawing Number:
Project Title:
Project Location:
Issue Date:
Checked By: Drawn By:
Drawing Title:
FULLY
SPRINKLER
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
A
Submission:
ARCHITECT / ENGINEER OF RECORD:
Revisions: Date:
CONSULTANTS:
/8
'-0
4 '
8 ' 6 '
/4
'-0
/8
'-0
/2
'-0
/4
'-0
'-0
-1
/2
'-0
'-0
CONSULTANT:
COMPASS
8734 GALLOWAY TRAIL
NOVELTY, OH. 44072
619-925-1647
ARCHITECT:
CB DESIGN GROUP
421 KING ST
SUITE 301
ALEXANDRIA, VA 22314
703-772-4213
PROFESSIONAL SEAL:
James A. Haley Veterans Hospital 13000 Bruce B. Downs Blvd.
Tampa, FL. 33612
2345678910111213141516
B
C
D
E
F
G
H
I
J
12345678910111213141516
CONSULTANT:
SCOTT PRZYBYSZ
15 SUNNEN DR.
SUITE 104
ST. LOUIS, MO 63143
CONSULTANT:
MARK DYCK
148 S. QUEEN ST.
SUITE 201
MARTINSBURG, WV.
CONSULTANT:
CLARE KRAMER
2815 DIRECTORS
ROW SUITE 500
ORLANDO, FL. 32809
407-917-2430
04/04/2025
673-20-107
AuthorChecker
EHRM INFRASTRUCTURE UPGRADES
TAMPA, FL.
ISSUED FOR CONSTRUCTION
EXISTING LIFE SAFETY PLAN
LS-101-8
3-
-1
. L
S-
1- 8.
7/
/2
2.
pd f
BUILDING 1 - EIGHTH FLOOR
Drawing Number:
Project Title:
Project Location:
Issue Date:
Checked By: Drawn By:
Drawing Title:
FULLY
SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
A
Submission:
ARCHITECT / ENGINEER OF RECORD:
Revisions: Date:
CONSULTANTS:
/8
/4
/8
/2
/4
-1
/2
CONSULTANT:
COMPASS
8734 GALLOWAY TRAIL
NOVELTY, OH. 44072
619-925-1647
ARCHITECT:
CB DESIGN GROUP
421 KING ST
SUITE 301
ALEXANDRIA, VA 22314
703-772-4213
PROFESSIONAL SEAL:
James A. Haley Veterans Hospital 13000 Bruce B. Downs Blvd.
Tampa, FL. 33612
2345678910111213141516
B
C
D
E
F
G
H
I
J
12345678910111213141516
DRAWINGS NOT INTENDED FOR
CONSTRUCTION.
CONSULTANT:
SCOTT PRZYBYSZ
15 SUNNEN DR. SUITE 104
ST. LOUIS, MO 63143
314-951-2535
CONSULTANT:
MARK DYCK
148 S. QUEEN ST. SUITE 201
MARTINSBURG, WV. 25401
304-266-3115
CONSULTANT:
CLARE KRAMER
2815 DIRECTORS ROW
SUITE 500
ORLANDO, FL. 32809
407-917-2430
04/04/2025
673-20-107
PRIPANJUSSTU
EHRM INFRASTRUCTURE UPGRADES
TAMPA, FL.
ISSUED FOR CONSTRUCTION
GENERAL NOTES
01-ST000
-2
-1
-S
T
/1
/2
.p d f
DESIGN CRITERIA
1. STRUCTURE HAS BEEN DESIGNED TO COMPLY WITH:
FLORIDA BUILDING CODE 2023
IBC 2021
U.S. DEPARTMENT OF VETERANS AFFAIRS 2023
ASCE 7-22
ACI 318-19
AISC 360-16
AISI S100
AWS D1.1, D1.3
2. RISK CATEGORY IV
3. LIVE LOADS:
TYPICAL ROOF 20 PSF (UNREDUCIBLE)
TYPICAL FLOOR COMPUTER ROOMS 100 PSF (UNREDUCIBLE) @ EXISTING BLDG 100
125 PSF (UNREDUCIBLE) @ ADDITION
4. SNOW:
GROUND SNOW 6 PSF
SNOW EXPOSURE FACTOR 1.0
THERMAL FACTOR 1.0
IMPORTANCE FACTOR 1.2
FLAT-ROOF SNOW 8 PSF
DESIGN SNOW 15 PSF
RAIN-ON-SNOW SURCHARGE 5 PSF
5. SEISMIC:
SEISMIC DESIGN CATEGORY A
IMPORTANCE FACTOR 1.50
SOIL CLASS D
Ss 0.07 g
S1 0.031 g
Sds 0.063 g
Sd1 0.044 g
SEISMIC FORCE RESISTING SYSTEM STEEL SYSTEM NOT SPECIFICALLY DESIGNED FOR
SEISMIC RESISTANCE
ALLOWABLE STORY DRIFT 0.01 h
R 3.0
Cd 3.0
Ωo 3.0 ρ 1.0
ANALYSIS PROCEDURE GENERAL STRUCTURAL INTEGRITY
DESIGN BASE SHEAR, STRENGTH
LEVEL
V = Cs x W = 0.01 x W
6. WIND:
BASIC WIND SPEED V ULT = 155 MPH
EXPOSURE CLASS B
STORY DRIFT h/300
INTERNAL PRESSURE COEFFICIENT,
GCpi
± 0.18
MWFRS DESIGN WIND PRESSURE 40 PSF (WINDWARD)
ROOF COMPONENTS: ZONE 1 ZONE 2 ZONE 3
SUPPORT BEAMS (A > 100 SF) 70 PSF 111 PSF 153 PSF
ROOF SHEATHING (A = 50 SF) 74 PSF 118 PSF 162 PSF
DECK FASTENERS (A ≤ 10 SF) 85 PSF 133 PSF 182 PSF
WALL COMPONENTS: ZONE 4 ZONE 5
A = 200 SF 34 PSF 34 PSF
A = 50 SF 39 PSF 39 PSF
A ≤ 10 SF 42 PSF 42 PSF
C & C NOTES:
a. THE PRESSURES LISTED ARE IN ACCORDANCE IBC AND ASCE 7, AND THE DESIGN
FORCES USED BY THE SUBCONTRACTOR FOR A SPECIFIC APPLICATION ARE THE
RESPONSIBILITY OF THE SUBCONTRACTOR.
b. WIND PRESSURES ARE ULTIMATE DESIGN LEVEL.
c. SEE ASCE 7 FOR ZONE DEFINITIONS AND EXTENT OF ZONES.
d. SUBMIT DESIGN CALCULATIONS PREPARED BY A QUALIFIED PROFESSIONAL
ENGINEER, REGISTERED IN THE STATE WHERE THE PROJECT IS LOCATED, FOR ANY
DESIRED MODIFICATION TO THE STATED PRESSURES.
7. NORTH SOUTH DIRECTION: ALL LATERAL LOAD RESISTANCE AND STABILITY OF THE
BUILDING IN THE COMPLETED STRUCTURE IS PROVIDED BY STEEL MOMENT FRAME SEE
PLANS FOR LOCATIONS. THE CONCRETE FLOOR SERVE AS HORIZONTAL DIAPHRAGMS
DISTRIBUTING THE LATERAL FORCES TO THE VERTICAL LATERAL ELEMENTS WHICH IN
TURN CARRY THE LOAD TO THE BUILDING FOUNDATIONS.
EAST WEST DIRECTION: BUILDING LEAN TO AGAINST EXISTING BUILDING. ALL LATERAL
LOAD RESISTANCE AND STABILITY OF THE BUILDING IN THE EXISTING STRUCTURE IS
PROVIDED BY STEEL MOMENT FRAME SEE PLANS FOR LOCATIONS. THE CONCRETE
FLOOR SERVE AS HORIZONTAL DIAPHRAGMS DISTRIBUTING THE LATERAL FORCES TO THE
VERTICAL LATERAL ELEMENTS WHICH IN TURN CARRY THE LOAD TO THE BUILDING
FOUNDATIONS.
GENERAL
1. DURING THE CONSTRUCTION PERIOD, THE CONTRACTOR SHALL BE RESPONSIBLE FOR
THE SAFETY OF PERSONNEL AND PROPERTY ON AND AROUND THE JOBSITE. THE
CONTRACTOR SHALL PROVIDE ADEQUATE SHORING, BRACING, GUYS, ETC. IN
ACCORDANCE WITH ALL NATIONAL, STATE, AND LOCAL SAFETY ORDINANCES.
2. ALL DRAWINGS ARE CONSIDERED TO BE A PART OF THE CONTRACT DOCUMENTS. THE
GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR THE REVIEW AND COORDINATION
OF ALL DRAWINGS PRIOR TO THE START OF CONSTRUCTION. ANY DISCREPANCIES SHALL
BE BROUGHT TO THE ATTENTION OF THE ARCHITECT PRIOR TO THE START OF
CONSTRUCTION SO A CLARIFICATION CAN BE ISSUED. ANY WORK PERFORMED IN
CONFLICT WITH THE CONTRACT DOCUMENTS OR ANY CODE REQUIREMENTS SHALL BE
CORRECTED BY THE CONTRACTOR AT THEIR OWN EXPENSE AND AT NO EXPENSE TO THE
OWNER OR ARCHITECT.
3. STRUCTURAL SUBSTITUTIONS MAY BE ALLOWED WITH THE APPROVAL OF THE
STRUCTURAL ENGINEER. SUPPLIER SHALL PROVIDE SEALED DESIGN CALCULATIONS OR
SUITABLE PRODUCT LITERATURE FOR THE COMPONENTS.
4. ALL DIMENSIONS AND SITE CONDITIONS SHALL BE VERIFIED BY THE CONTRACTOR AT THE
JOBSITE PRIOR TO CONSTRUCTION, START OF SHOP DRAWINGS, START OF
CONSTRUCTION, AND/OR FABRICATION OF MATERIALS. IF DISCREPANCIES ARE
ENCOUNTERED, OR CONDITIONS DEVELOP THAT ARE NOT COVERED BY THE CONTRACT
DOCUMENTS, THE ARCHITECT SHALL BE NOTIFIED FOR CLARIFICATION.
5. CONTRACTOR SHALL PROVIDE AND BE RESPONSIBLE FOR THE PROTECTION AND REPAIR
OF ADJACENT EXISTING SURFACES AND AREAS WHICH MAY BE DAMAGED AS A RESULT OF
NEW WORK.
6. STRUCTURAL DRAWINGS INCLUDE DESIGN REQUIREMENTS AND DIMENSIONS FOR
STRUCTURAL INTEGRITY BUT DO NOT SHOW ALL DETAIL DIMENSIONS TO FIT INTRICATE
ARCHITECTURAL AND MECHANICAL DETAILS. CONTRACTOR SHALL SO CONSTRUCT THE
WORK SO IT WILL CONFORM TO THE CLEARANCES REQUIRED BY ARCHITECTURAL,
MECHANICAL AND ELECTRICAL DESIGN.
7. ALL SYMBOLS AND ABBREVIATIONS USED ON THE DRAWINGS ARE CONSIDERED TO BE
CONSTRUCTION STANDARDS. IF CLARIFICATION IS REQUIRED, THE CONTRACTOR SHALL
NOTIFY THE ARCHITECT PRIOR TO PROCEEDING WITH THE WORK.
8. DO NOT SCALE DRAWINGS. PRINTED DIMENSIONS HAVE PRECEDENCE OVER SCALED
DRAWINGS AND LARGE-SCALE OVER SMALL-SCALE DRAWINGS. CONTRACTOR TO
DETERMINE FINAL DIMENSION WITH ARCHITECT.
9. TYPICAL DETAILS SHALL APPLY TO SITUATIONS OCCURRING ON THE PROJECT THAT ARE
THE SAME OR SIMILAR TO THOSE SPECIFICALLY REFERENCED. WHERE NO DETAILS ARE
GIVEN, CONSTRUCTION SHALL BE AS SHOWN FOR SIMILAR WORK.
10. THE CONTRACT DOCUMENTS REPRESENT THE FINISHED STRUCTURE. THEY DO NOT
INDICATE THE METHOD OF CONSTRUCTION. THE CONTRACTOR SHALL PROVIDE ALL
MEASURES NECESSARY TO PROTECT THE STRUCTURE AND SAFETY OF WORKMEN
DURING CONSTRUCTION. SUCH MEASURES SHALL INCLUDE, BUT NOT BE LIMITED TO,
BRACING AND SHORING FOR LOADS DUE TO CONSTRUCTION EQUIPMENT, ETC.
OBSERVATION VISITS TO THE SITE BY THE ARCHITECT OR STRUCTURAL ENGINEER SHALL
NOT INCLUDE INSPECTION OR APPROVAL OF THE ABOVE ITEMS AND DO NOT IN ANY WAY
RELIEVE THE CONTRACTOR OF THEIR RESPONSIBILITIES FOR THE ABOVE.
11. SEE ARCHITECTURAL, ELECTRICAL AND MECHANICAL DRAWINGS FOR DETAILS,
CONDITIONS, PITS, TRENCHES, PADS, DEPRESSIONS, ROOF/FLOOR OPENINGS, STAIRS,
SLEEVES, ITEMS TO BE EMBEDDED OR ATTACHED TO STRUCTURAL ELEMENTS, ETC., NOT
SHOWN ON THE STRUCTURAL DRAWINGS.
12. ESTABLISH AND VERIFY ALL OPENINGS AND INSERTS FOR MECHANICAL, ELECTRICAL AND
PLUMBING WITH APPROPRIATE TRADE CONTRACTORS. OPENING SIZES AND LOCATIONS
SHOWN FOR DUCTS, PIPE, INSERTS AND OTHER PENETRATIONS WHEN SHOWN ARE FOR
GENERAL INFORMATION ONLY AND SHALL BE VERIFIED PRIOR TO FORMING.
13. NO HOLES, BLOCK-OUTS, ETC. ARE ALLOWED IN STRUCTURAL ELEMENTS UNLESS
SPECIFICALLY DETAILED ON THE STRUCTURAL DRAWINGS OR APPROVED BY THE
STRUCTURAL ENGINEER.
14. PENETRATIONS SHALL BE CAST-IN-PLACE AND SHALL NOT BE PERMITTED EXCEPT AS
SHOWN IN THE STRUCTURAL DRAWINGS.
15. BEFORE SUBMITTING A PROPOSAL FOR THIS WORK, CONTRACTOR SHALL VISIT THE
PREMISES AND BECOME FULLY ACQUAINTED WITH CONDITIONS IN FIELD, TEMPORARY
CONSTRUCTION REQUIRED, QUANTITIES AND TYPE OF EQUIPMENT, ETC. THE PROPOSAL
SHALL INCLUDE ALL SUMS REQUIRED TO DO THE WORK.
SUBMITTALS
1. SUBMITTALS ARE:
a. CONCRETE MIX DESIGNS
b. MATERIAL PRODUCT DATA FOR STRUCTURAL MATERIALS
c. CONCRETE AND MASONRY REINFORCING
d. STEEL DECK
e. COLD FORMED STEEL FRAMING
f. STRUCTURAL STEEL
2. SUBMITTALS SHALL BE REVIEWED AND COORDINATED PRIOR TO SUBMITTING TO THE
ARCHITECT. EACH SHOP DRAWING SUBMITTED SHALL BE STAMPED INDICATING REVIEW
BY THE CONSTRUCTION MANAGER/GENERAL CONTRACTOR AND REVIEW BY THE
ARCHITECT SHALL NOT BEGIN UNTIL THIS IS COMPLETE. WORK SHALL NOT BEGIN
WITHOUT REVIEW BY THE ARCHITECT/STRUCTURAL ENGINEER.
3. SUBMITTALS SHALL BE REVIEWED BY THE ARCHITECT/STRUCTURAL ENGINEER FOR
GENERAL CONFORMANCE WITH DESIGN CONCEPT ONLY. NOTATIONS MADE BY THE
ARCHITECT/STRUCTURAL ENGINEER ON THE SHOP DRAWINGS DOES NOT RELIEVE THE
CONTRACTOR FROM COMPLYING WITH THE REQUIREMENTS OF THE DRAWINGS.
4. FOR ADDITIONAL INFORMATION ON REQUIRED SUBMITTALS, SEE INDIVIDUAL MATERIAL
SECTIONS.
DELEGATED DESIGN
1. DELEGATED DESIGNS PER SECTION 107.3.4.1 SHALL BE SUBMITTED TO THE BUILDING
OFFICIAL AND THE DESIGN PROFESSIONALS AND REVIEWED PRIOR TO INSTALLATION.
2. DELEGATED DESIGNS ARE
a. EXCAVATION, SHORING, AND UNDERPINNING
b. EXTERIOR WALL SYSTEMS
c. COLD FORMED STEEL FRAMING
3. ALL DELEGATED DESIGNS SHALL BEAR THE STAMP AND SIGNATURE OF THE QUALIFIED
PROFESSIONAL ENGINEER, REGISTERED IN THE STATE WHERE THE PROJECT IS LOCATED,
RESPONSIBLE FOR THE PREPARATION OF THESE DOCUMENTS.
EXISTING CONDITIONS / DEMOLITION
1. EXISTING CONDITIONS:
a. EXISTING STRUCTURAL INFORMATION SHOWN WAS OBTAINED FROM EXISTING
DRAWINGS:
i. DATED AUGUST 15, 1968 BY SCHMIDT, GARDEN & ERIKSON.
ii. DATED JANUARY 03, 2023 BY PAGE SOUTHERLAND PAGE, INC.
b. EXISTING STRUCTURAL INFORMATION SHOWN WAS OBTAINED FROM FIELD TAKE-OFF
BY IMEG AS PERMITTED BY ACCESS RESTRICTIONS DURING DESIGN.
c. ALL INFORMATION SHOWN ON THE DRAWINGS RELATIVE TO EXISTING CONDITIONS IS
GIVEN AS THE BEST PRESENT KNOWLEDGE. CONTRACTOR TO VERIFY EXISTING
INFORMATION, DIMENSIONS AND SIZES AS REQUIRED TO COMPLETE THEIR WORK.
WHERE ACTUAL CONDITIONS CONFLICT WITH THE DRAWINGS, THEY SHALL BE
REPORTED TO THE ARCHITECT OR STRUCTURAL ENGINEER SO PROPER
CLARIFICATION MAY BE MADE. MODIFICATION OF CONSTRUCTION DETAILS SHALL NOT
BE MADE WITHOUT WRITTEN APPROVAL OF THE ARCHITECT OR STRUCTURAL
ENGINEER.
2. EXISTING BUILDING MATERIAL PROPERTIES:
a. ALL EXISTING STEEL AT BUILDING 001 IS ASSUMED TO BE A36 (Fy=36 KSI)
b. ALL EXSTING STEEL AT BUILDING 100 IS ASSUMED TO BE SAME AS NEW STEEL PER
CURRENT STANDARDS LISTED HEREIN.
c. ALL EXISTING CONCRETE AT BUILDING 001 IS ASSUMED TO BE F’c=3,000.
3. ALL DEMOLITION SHALL BE CARRIED OUT IN SUCH A WAY SO AS TO NOT DAMAGE
EXISTING ELEMENTS WHICH ARE TO REMAIN.
4. ALL ELEMENTS WHICH ARE TO REMAIN AND WHICH ARE DAMAGED DURING DEMOLITION
WORK SHALL BE REPLACED AT NO ADDED COST. EXISTING ELEMENTS ARE TO BE
PROTECTED TO THE FULLEST EXTENT POSSIBLE TO REDUCE SUCH DAMAGE TO A
MINIMUM.
EARTHWORK
1. FOUNDATION DESIGN IS BASED ON THE GEOTECHNICAL REPORT DATED MAY 24, 2018 BY
PROFESSIONAL SERVICE INDUSTRIES, INC. REPORT IS ON FILE WITH THE ARCHITECT.
2. SOIL PROPERTIES PER THE GEOTECHNICAL REPORT:
ALLOWABLE NET SOIL BEARING PRESSURE:
FOOTINGS 2500 PSF
ANTICIPATE DEPTH TO ALLOWABLE SOIL BEARING 1’-6” BELOW EXISTING GRADE
EQUIVALENT FLUID PRESSURE
ACTIVE PRESSURE 35 PSF/FT, DRAINED 80 PSF/FT,
UNDRAINED
AT REST PRESSURE 55 PSF/FT, DRAINED 85 PSF/FT,
UNDRAINED
PASSIVE PRESSURE 330 PSF/FT, DRAINED 130 PSF/FT,
UNDRAINED
COEFFICIENT OF FRICTION 0.45
3. ALL EXCAVATIONS SHALL BE PROPERLY AND SAFELY BACKFILLED.
4. CONTRACTOR SHALL PROVIDE FOR DE-WATERING OF EXCAVATIONS FROM SURFACE
WATER, GROUND WATER OR SEEPAGE. FREE GROUND WATER WAS NOT ENCOUNTERED
IN THE BORINGS. DETAILS OF GROUND WATER INFORMATION CAN BE OBTAINED FROM
THE ABOVE-MENTIONED GEOTECHNICAL REPORT. IF GROUND WATER SHOULD OCCUR
DURING EXCAVATION, SPECIAL PROCEDURES SHALL BE IMPLEMENTED AS
RECOMMENDED BY THE GEOTECHNICAL ENGINEER.
5. WHERE THERE IS NOT SUFFICIENT SPACE FOR SLOPED EMBANKMENTS, SHORING WILL BE
REQUIRED. SEE THE GEOTECHNICAL REPORT FOR INFORMATION REGARDING THE DESIGN
AND INSTALLATION OF THE SHORING. SHORING THAT IS NOT PART OF THE PERMANENT
BUILDING SUPPORT IS THE CONTRACTOR’S RESPONSIBILITY AND OUTSIDE THIS PERMIT.
6. CARE SHALL BE EXERCISED WHEN EXCAVATING OR GRADING ADJACENT TO EXISTING
STRUCTURES OR IMPROVEMENTS TO NOT DAMAGE OR UNDERMINE FOUNDATIONS,
WALLS, SLABS, UTILITIES, ETC.
7. CONTRACTOR SHALL INVESTIGATE SITE DURING CLEARING AND EARTHWORK
OPERATIONS FOR FILL MATERIAL OR BURIED STRUCTURES SUCH AS CESSPOOLS,
CISTERNS AND FOUNDATIONS. IF ANY SUCH MATERIAL OR STRUCTURES ARE FOUND,
ARCHITECT/ENGINEER SHALL BE NOTIFIED IMMEDIATELY. ALL ABANDONED FOUNDATIONS,
UTILITIES AND OTHER STRUCTURES THAT INTERFERE WITH NEW CONSTRUCTION SHALL
BE REMOVED.
8. ALL FOOTINGS AND SLABS ON GRADE SHALL BE PLACED ONTO FIRM UNDISTURBED SOIL
OR CONTROLLED COMPACTED FILL, REMOVING ANY EXISTING FILL, ORGANIC MATERIAL,
OR UNSUITABLE SOILS, AS RECOMMENDED BY THE GEOTECHNICAL REPORT. EXPOSED
NATURAL SOIL SHALL BE PROOF ROLLED BELOW SLABS ON GRADE.
9. THE PREPARATION OF THE SUBGRADE FOR THE SLAB ON GRADE SHALL BE IN STRICT
ACCORDANCE WITH THE PROJECT GEOTECHNICAL REPORT REFERENCED ABOVE.hh
10. FOUNDATION ELEVATIONS SHOWN DESIGNATE A MINIMUM DEPTH WHERE AN ADEQUATE
SOIL BEARING PRESSURE IS EXPECTED. FOOTINGS, PIERS AND/OR WALLS SHALL BE
LOWERED OR EXTENDED AS REQUIRED TO REACH SOIL MEETING THE DESIGN BEARING
PRESSURE.
11. ANY REQUIRED IMPORT FILL SOIL SHALL HAVE A LOW POTENTIAL FOR EXPANSION AND
SHALL BE APPROVED BY THE GEOTECHNICAL ENGINEER PRIOR TO IMPORTING.
UNDERPINNING
1. UNDERPIN EXISTING WALLS AND FOOTINGS AND PLACE NEW FOOTINGS AS SHOWN ON
THE FOUNDATION PLAN AND DETAILS.
2. NO EXCAVATION CAN BE DONE WITHIN 6’-0” OF THE EXISTING BUILDING UNTIL
UNDERPINNING IS COMPLETE.
3. POURED CONCRETE WALL UNDERPINNING PROCEDURE SHALL BE AS FOLLOWS:
a. WHERE NOTED ON THE PLAN AND DETAILS, UNDERPINNING SHALL BE PERFORMED AT
INTERVALS NOT TO EXCEED 6 FEET IN LENGTH. REPEAT PROCEDURES BELOW
ALTERNATING SECTIONS UNTIL UNDERPINNING IS COMPLETE.
b. PLACE HORIZONTAL REINFORCEMENT WITH 90° BENDS SO THEY MAY BE
STRAIGHTENED TO LAP WITH BARS OF ADJACENT UNDERPINNING SECTIONS.
c. PLACE CONCRETE OF NEW WALL TO WITHIN 3” OF THE UNDERSIDE OF EXISTING
FOOTING WHERE APPLICABLE. AFTER 2 DAYS, PACK FINAL DIMENSION WITH 7000 PSI
DRY GROUT AT 28-DAY STRENGTH. GROUT IS TO SET AT LEAST 7 DAYS BEFORE
ADJACENT SECTION IS EXCAVATED. SHORE AND BRACE EACH SECTION AS SOON AS
FORMS ARE REMOVED. WHEN EXCAVATION IS STARTED IN ANY SECTION, ALL WORK IN
THAT SECTION MUST BE COMPLETED PROMPTLY AND PRIOR TO STARTING ANOTHER
SECTION IN THE IMMEDIATE AREA.
d. UNLESS OTHERWISE NOTED, NEW FOUNDATION WALL AND FOOTING TO MATCH
EXISTING THICKNESS AND SIZE.
4. CONTRACTOR SHALL SUBMIT A SEQUENCE OF UNDERPINNING OPERATIONS FOR REVIEW
BY THE ARCHITECT/STRUCTURAL ENGINEER.
5. CONTRACTOR SHALL SURVEY EXISTING FOOTING AND WALL ELEVATIONS PRIOR TO,
DURING, AND AFTER UNDERPINNING OPERATIONS TO MONITOR POTENTIAL MOVEMENT.
SURVEY RESULTS SHALL BE SUBMITTED TO THE ARCHITECT/STRUCTURAL ENGINEER.
REINFORCING STEEL
1. ALL REINFORCING STEEL SHALL BE DETAILED AND PLACED IN CONFORMANCE WITH THE
AMERICAN CONCRETE INSTITUTE “ACI DETAILING MANUAL” (SP-066) EXCEPT AS
OTHERWISE SHOWN, NOTED OR SPECIFIED.
2. CONCRETE REINFORCING STEEL SHALL BE HIGH STRENGTH NEW BILLET STEEL
CONFORMING TO THE FOLLOWING STANDARDS:
DEFORMED BARS ASTM A615, GR 60 Fy = 60 KSI
WELDED WIRE REINFORCING ASTM A1064 Fy = 65 KSI
STEEL WIRE ASTM A1064 Fy = 60 KSI
3. MINIMUM CONCRETE COVER SHALL BE PROVIDED AS FOLLOWS TO THE OUTERMOST
REINFORCING BARS:
CAST AGAINST AND PERMANENTLY IN CONTACT WITH GROUND 3”
EXPOSED TO WEATHER OR IN CONTACT WITH GROUND
#6 BARS OR LARGER 2”
#5 BARS OR SMALLER 1 1/2”
4. BAR SPLICES SHALL BE PROVIDED WHERE INDICATED ON THE DRAWINGS. ALL SPLICES
SHALL BE CLASS 'B' AS DEFINED IN ACI 318. IF SPLICE LENGTH IS NOT GIVEN ON THE
DRAWINGS, PROVIDE LAP LENGTH (IN INCHES) AS FOLLOWS:
3000 PSI CONCRETE 4000 PSI CONCRETE
BAR SIZE OTHER TOP OTHER TOP
#3 22 28 19 25
#4 29 38 25 33
#5 36 47 31 41
#6 43 56 37 49
LAP LENGTHS ASSUME CLEAR SPACING BETWEEN BARS OF 2 BAR DIAMETERS, AND A
MINIMUM COVER OF 1 BAR DIAMETER. FOR DEVELOPMENT LENGTHS, DIVIDE BY 1.3. TOP
BARS ARE DEFINED AS HORIZONTAL BARS WITH MORE THAN 1'-0" OF FRESH CONCRETE
BELOW.
5. DOWELS BETWEEN FOOTINGS AND WALLS OR CONCRETE PIER SHALL BE THE SAME
GRADE, SIZE AND SPACING OR NUMBER AS THE VERTICAL REINFORCING, RESPECTIVELY,
UNLESS OTHERWISE NOTED. PROVIDE FOUNDATION DOWELS TO MATCH SIZE AND
SPACING OF WALL OR CONCRETE PIER REINFORCEMENT. EXTEND DOWELS A LAP SPLICE
LENGTH INTO WALL OR CONCRETE PIER AND TERMINATE WITH STANDARD HOOK AT
BOTTOM OF FOOTING, UNLESS OTHERWISE NOTED.
6. FIELD WELDING OR BENDING OF REINFORCING IS NOT PERMITTED EXCEPT AS INDICATED
ON THE DRAWINGS OR AS APPROVED BY THE STRUCTURAL ENGINEER.
7. SUBMIT SHOP DRAWINGS FOR FABRICATION AND PLACEMENT OF REINFORCING STEEL.
INCLUDE SCHEDULES AND DIAGRAMS OF BENT BARS AND SHOW ARRANGEMENT OF
REINFORCEMENT, INCLUDING CONCRETE COVER. STRUCTURAL ENGINEER’S REVIEW WILL
BE FOR COMPLIANCE WITH DESIGN REQUIREMENTS. THE CONTRACTOR SHALL BE
RESPONSIBLE FOR VERIFYING DIMENSIONS AND QUANTITIES.
8. ALL CONCRETE NOT OTHERWISE SPECIFIED SHALL BE REINFORCED TO THE MINIMUM
REQUIREMENT OF ACI 318.
CAST-IN-PLACE CONCRETE
1. ALL CONCRETE WORK SHALL CONFORM TO THE CORRESPONDING EDITION OF THE
AMERICAN CONCRETE INSTITUTE PUBLICATIONS: ACI 117, ACI 301, ACI 305.1, ACI 306.1, ACI
308.1, ACI 318 AND SP-066, UNLESS OTHERWISE NOTED.
2. CONCRETE MATERIALS SHALL CONFORM TO:
CEMENT ASTM C150, TYPE I OR II
FLY ASH ASTM C618, TYPE C OR F
FINE AND COARSE AGGREGATE ASTM C33
WATER POTABLE
AIR-ENTRAINING ADMIXTURE ASTM C260
WATER REDUCING ADMIXTURE ASTM C494
CONCRETE STRENGTHS SHALL CONFORM TO:
INTENDEDUSE STRENGTH(PSI) EXPOSURE
CLASS
FOOTINGS 3000 N/A
FOUNDATIONS 4000 N/A
SLAB ON GRADE 4000 N/A
UNLESS OTHERWISE NOTED 4000 N/A
NORMAL-WEIGHT 28-DAY STRENGTH UNLESS OTHERWISE NOTED.
3.THE MODULUS OF ELASTICITY OF ALL CONCRETE SHALL EXCEED 57,000 SQRT(f’c) FOR NORMAL-WEIGHT CONCRETE OR wc1.5 33 SQRT(f’c).
4. DRYPACK OR GROUT SHALL HAVE A MINIMUM 28-DAY STRENGTH OF 7000 PSI.
5. SLAB-ON-GRADE CONSTRUCTION: LOCATE SAW-CUT CONTROL JOINTS ALONG COLUMN
LINES WITH INTERMEDIATE JOINTS SPACED PER THE TABLE BELOW, UNLESS OTHERWISE
NOTED. SLAB PANELS SHALL HAVE A MAXIMUM LENGTH TO WIDTH RATIO OF 1.5:1.
PROVIDE ADDITIONAL CONTROL JOINTS AT ALL RE-ENTRANT CORNERS. SEE PLAN FOR
SPECIAL CASES.
THICKNESS (IN) MAXIMUM JOINT SPACING EACH WAY (FT)
9 18
6. CROSS REFERENCE ARCHITECTURAL AND STRUCTURAL DRAWINGS TO ENSURE PROPER
DIMENSIONS AND PLACEMENT OF ALL ANCHOR BOLTS, INSERTS, NOTCHES, AND EDGES
OF WALLS/FOUNDATIONS PRIOR TO PLACING CONCRETE.
7. UNLESS OTHERWISE NOTED, ALL FOOTINGS SHALL BE CENTERED UNDER WALLS, PIERS
OR COLUMNS.
8. CONSTRUCTION JOINTS SHALL BE THOROUGHLY ROUGHENED TO 1/4” AMPLITUDE BY
SAND BLASTING OR MECHANICAL MEANS. CLEAN BEFORE POUR. LOCATION TO BE
APPROVED BY THE STRUCTURAL ENGINEER. SUBMIT LOCATION PLAN OF ALL PROPOSED
JOINTS NOT INDICATED ON DRAWINGS FOR APPROVAL PRIOR TO BEGINNING WORK.
9. PRIOR TO PLACING CONCRETE, THE CONTRACTOR SHALL ENSURE ALL REINFORCING AND
EMBEDMENTS, INCLUDING COLUMN ANCHOR BOLTS, ARE PROPERLY LOCATED AND
SECURELY TIED IN PLACE.
10. PROVIDE SLEEVES FOR PLUMBING AND ELECTRICAL PENETRATIONS THROUGH
CONCRETE BEFORE PLACING. SECURE SLEEVES TO PREVENT MOVEMENT DURING
PLACING OPERATIONS. SEE MECHANICAL AND ELECTRICAL DRAWINGS FOR LOCATIONS.
11. SLOPE SLABS TO DRAINS OR FOR POSITIVE DRAINAGE IF NO DRAINS ARE PRESENT AND
PROVIDE DEPRESSIONS WHERE SHOWN ON THE STRUCTURAL AND/OR ARCHITECTURAL
DRAWINGS WITHOUT REDUCING THE THICKNESS OF SLAB INDICATED. FOR SLAB-ON-
GRADE DEPRESSIONS GREATER THAN 1 INCH, SEE DETAILS FOR ADDITIONAL
REINFORCING.
12. CONCRETE FILL THICKNESS SHOWN ON FRAMING PLANS AND DETAIL SHEETS IS MINIMUM
THICKNESS. NO ALLOWANCES HAVE BEEN SHOWN FOR ADDITIONAL CONCRETE FILL
REQUIRED TO COMPENSATE FOR BEAM OR DECK DEFLECTIONS AND TO MAINTAIN
SURFACE TOLERANCES SPECIFIED.
13. GENERAL CONTRACTOR TO PROVIDE SHOP DRAWINGS FOR SIZE, LOCATION AND HEIGHT
OF MECHANICAL EQUIPMENT PADS ON CONCRETE SLAB ON STEEL DECK AND SLAB-ON-
GRADE.
14. THE PROPOSED MATERIALS AND MIX DESIGN SHALL BE FULLY DOCUMENTED AND
REVIEWED BY THE TESTING AGENCY. RESPONSIBILITY FOR OBTAINING THE REQUIRED
DESIGN STRENGTH IS THE CONTRACTOR’S. SUBMIT TEST DATA ON EACH PROPOSED MIX
FOR REVIEW IN ACCORDANCE WITH THE APPLICABLE CODE. MIX DESIGNS SUBMITTED
WITHOUT THE REQUIRED TEST DATA WILL BE RETURNED WITHOUT REVIEW.
15. PROVIDE SLAB COORDINATION DRAWING SUBMITTAL INDICATING COORDINATED
LOCATIONS OF: MEP PENETRATIONS, SLEEVES, OPENINGS, IN-SLAB CONDUIT/DUCT (IF
ALLOWED), EMBEDS, CAST-IN ANCHORS, AND OTHER ITEMS EMBEDDED OR PENETRATING
STRUCTURAL ELEVATED SLABS.
LINTELS
1. PROVIDE LINTELS OVER ALL OPENINGS AND RECESSES IN MASONRY CONSTRUCTION.
LINTELS ARE NOT REQUIRED OVER OPENINGS 12” WIDE OR LESS THAT IS AT LEAST 1
COURSE BELOW THE BOND BEAM AT THE TOP OF WALL.
2. PENETRATIONS NOT IDENTIFIED ON THE DOCUMENTS ARE TO BE TREATED IN A MANNER
SIMILAR TO THE IDENTIFIED LOCATIONS.
3. LINTELS IN NON-BEARING WALLS SHALL BE SIZED PER THE FOLLOWING:
SPAN, L STEEL OPTION (FOR EA 4” OF MASONRY) *
0’ < L ≤ 4’-0” L3 1/2x3 1/2x1/4
4’-0” < L ≤ 6’-0” L4x3 1/2x5/16 (LLV)
6’-0” < L ≤ 8’-0” L5x3 1/2x5/16 (LLV)
8’-0” < L ≤ 10’-0” L6x3 1/2x3/8 (LLV)
*ALL ANGLES THAT ARE BACK-TO-BACK SHALL BE WELDED TOP AND BOTTOM 3” @ 12” OC
MINIMUM.
4. ALL LINTELS SHALL HAVE A MINIMUM OF 8” END BEARING AND DO NOT REQUIRE BEARING
PLATES, UNLESS OTHERWISE NOTED.
5. TEMPORARY SHORING OF MASONRY LINTELS MUST BE PROVIDED UNTIL MASONRY HAS
REACHED 75% OF DESIGN STRENGTH.
STEEL
1. STRUCTURAL STEEL SHALL BE DETAILED IN ACCORDANCE WITH THE AMERICAN INSTITUTE
OF STEEL CONSTRUCTION (AISC) “DETAILING FOR STEEL CONSTRUCTION” AND
FABRICATED AND ERECTED IN ACCORDANCE WITH THE “SPECIFICATION FOR STRUCTURAL
STEEL BUILDINGS”.
2. STRUCTURAL STEEL SHALL CONFORM TO ASTM STANDARDS AS NOTED BELOW:
WIDE FLANGE SHAPES ASTM A992 Fy = 50 KSI
OTHER ROLLED SHAPES ASTM A36 Fy = 36 KSI
PIPE SECTIONS ASTM A53, GR B Fy = 35 KSI
HSS SECTIONS, ROUND ASTM A500, GR C Fy = 46 KSI
HSS SECTION, SQ/RECT ASTM A500, GR C Fy = 50 KSI
HP SHAPES ASTM A572 Fy = 50 KSI
BASE AND CONNECTION PLATES ASTM A36 Fy = 36 KSI
ANCHOR RODS ASTM F1554, GR 36 Fy = 36 KSI
HIGH STRENGTH BOLTS ASTM F3125, GR A325 Fv = 120 KSI
HIGH STRENGTH TWIST-OFF BOLTS ASTM F3125, GR F1852 Fv = 120 KSI
HEAVY HEX NUTS ASTM A563
WASHERS ASTM F436
HEADED STUD ANCHORS ASTM A108, TYPE B
ELECTRODES FOR ARC WELDING AWS 5.1, E70XX
3. HIGH STRENGTH BOLTS SHALL BE INSTALLED IN ACCORDANCE WITH AISC
“SPECIFICATIONS FOR STRUCTURAL JOINTS USING HIGH-STRENGTH BOLTS”. SEE DETAILS
FOR BOLT SIZE AND MATERIAL ASTM DESIGNATION.
4. ALL BOLTED CONNECTIONS SHALL BE GRADE A325N BEARING TYPE BOLTS, UNLESS
OTHERWISE NOTED. ALL BOLTS SHALL BE INSTALLED TO A MINIMUM “SNUG TIGHT”
CONDITION, UNLESS OTHERWISE NOTED.
5. FULLY TENSIONED HIGH STRENGTH BOLTS AND SLIP CRITICAL HIGH STRENGTH BOLTS
SHALL USE TENSION-CONTROL “TWIST-OFF” BOLTS OR BE INSTALLED USING THE TURN OF
THE NUT METHOD.
6. WELD LENGTHS INDICATED ON THE DRAWINGS ARE THE NET EFFECTIVE LENGTH
REQUIRED. WHERE WELD LENGTH IS NOT SPECIFIED, PROVIDE WELD ALONG ENTIRE
INTERSECTION OF THE JOINED PARTS. WHERE FILLET WELD SYMBOL IS GIVEN WITHOUT
INDICATION OF SIZE, USE MINIMUM WELD SIZE AS SPECIFIED IN AISC 360, TABLE J2.4.
7. SPLICING OF STEEL MEMBERS WHERE NOT DETAILED ON THE DRAWINGS IS PROHIBITED
WITHOUT THE PRIOR APPROVAL OF THE STRUCTURAL ENGINEER AS TO LOCATION, TYPE
OF SPLICE AND CONNECTION TO BE MADE.
8. HEADED STUD ANCHORS (HSA): SHALL BE INSTALLED IN ACCORDANCE WITH AWS D1.1
AND SHALL BE AUTOMATICALLY END WELDED IN ACCORDANCE WITH THE
MANUFACTURER’S RECOMMENDATIONS IN SUCH A MANNER AS TO PROVIDE COMPLETE
FUSION BETWEEN THE END OF THE HSA AND THE STEEL SHAPE. THERE SHOULD BE NO
POROSITY OR EVIDENCE OF LACK OF FUSION BETWEEN THE WELDED END OF THE HSA
AND THE STEEL SHAPE. THE HSA SHALL DECREASE IN LENGTH DURING WELDING
9. APPROXIMATELY 1/8”FOR 5/8”ø AND SMALLER AND 3/16” FOR LARGER THAN 5/8”ø.
14. GROUT FOR BASE AND BEARING PLATES SHALL BE A NON-SHRINK, NON-METALLIC
PRODUCT. MINIMUM COMPRESSIVE STRENGTH AT 28 DAYS SHALL BE 10,000 PSI. INSTALL
GROUT PRIOR TO APPLYING SIGNIFICANT LOADING TO MEMBER.
15. THE STRUCTURAL STEEL FABRICATOR SHALL FURNISH SHOP DRAWINGS OF ALL
STRUCTURAL STEEL FOR ARCHITECT/STRUCTURAL ENGINEER’S REVIEW BEFORE
FABRICATION.
STEEL DECK
1. MATERIAL, DETAILING, DESIGN, MANUFACTURE, AND ERECTION OF STEEL DECKS SHALL
BE IN ACCORDANCE WITH THE STEEL DECK INSTITUTE (SDI) SPECIFICATION.
2. DECK SIZE AND GAUGE INDICATED ON THE DRAWINGS ARE BASED ON THE FOLLOWING:
A. CURRENT VERSION OF VULCRAFT CATALOG FOR GRAVITY DESIGN LOADS AND
UNSHORED CONSTRUCTION SPANS
B. STEEL DECK INSTITUTE (SDI) DIAPHRAGM DESIGN MANUAL 4TH EDITION FOR
DIAPHRAGM LOADS
3. STEEL DECK GALVANIZING SHALL CONFORM TO ASTM A653 WITH A MINIMUM COATING OF
G60.
4. PAINTED STEEL ROOF DECK SHALL CONFORM TO ASTM A1008, GRADE C.
5. PROVIDE MINIMUM DECK BEARING AND LAP LENGTHS PER MANUFACTURER’S
RECOMMENDATIONS.
6. USE SUMP PANS AT ALL ROOF DRAINS. MINIMUM THICKNESS FOR SUMP PANS SHALL BE 14
GAUGE.
7. DECK MANUFACTURER SHALL FURNISH ALL RIDGE AND VALLEY PLATES, SUMP PANS,
DRAIN PLATES, AND OTHER ACCESSORIES REQUIRED FOR A COMPLETE INSTALLATION.
DECK MANUFACTURER SHALL PROVIDE ALL CLOSURE PLATES AND POUR STOPS NOT
PROVIDED BY THE STEEL FABRICATOR.
8. CUTTING AND FRAMING OF OPENINGS FOR OTHER TRADES SHALL BE THE RESPONSIBILITY
OF THE TRADES INVOLVED. HOLES THAT ARE LOCATED AND DIMENSIONED ON THE
DRAWINGS SHALL BE THE RESPONSIBILITY OF THE DECK ERECTOR.
9. CONDUITS SHOULD NOT BE PLACED IN CONCRETE SLAB ON STEEL DECK WITHOUT
COORDINATION WITH THE STRUCTURAL ENGINEER, UNLESS OTHERWISE NOTED.
10. COORDINATE ALL PENETRATIONS, EMBEDS, AND RECESSES IN COMPOSITE FLOOR
SYSTEMS WITH THE STRUCTURAL ENGINEER, UNLESS OTHERWISE NOTED.
11. DO NOT EXCEED 25 LBS PER HANGER AND A MINIMUM SPACING OF 2’-0” ON CENTER WHEN
ATTACHING TO STEEL ROOF DECK. THIS 25 LBS LOAD AND 2’-0” SPACING INCLUDES
ADJACENT MECHANICAL, ELECTRICAL, AND ARCHITECTURAL ITEMS HANGING FROM THE
DECK. IF THE HANGER RESTRICTIONS CANNOT BE ACHIEVED, SUPPLEMENTAL FRAMING
SUPPORTED OFF STEEL FRAMING WILL NEED TO BE ADDED. THE GENERAL CONTRACTOR
IS RESPONSIBLE FOR COORDINATING LOCATION AND WEIGHT OF ALL THE ELEMENTS
BEING HUNG WITH STRUCTURAL ENGINEER, UNLESS OTHERWISE NOTED.
12. STEEL FORM OR COMPOSITE DECKING HAS BEEN DESIGNED FOR THE UNSHORED CLEAR
SPAN. CONCRETE FILL THICKNESS SHOWN ON FRAMING PLANS AND DETAIL SHEETS IS A
MINIMUM THICKNESS. NO ALLOWANCES HAVE BEEN SHOWN FOR ADDITIONAL CONCRETE
FILL REQUIRED TO COMPENSATE FOR BEAM OR DECK DEFLECTIONS AND TO MAINTAIN
SURFACE TOLERANCES SPECIFIED.
13. SUBMIT SHOP DRAWINGS SHOWING ERECTION PROCEDURES, WELDING PROCEDURES,
VERTICAL LOAD AND DIAPHRAGM SHEAR CAPACITY FURNISHED, DECK SHORING
REQUIREMENTS, UNDERWRITER’S LABORATORIES (UL) FIRE RATING NUMBER AND
COMPOSITE BEAM AND GIRDER STUD PROFILES TO THE ARCHITECT/STRUCTURAL
ENGINEER FOR REVIEW. FABRICATION SHALL NOT BEGIN WITHOUT APPROVED SHOP
DRAWINGS.
POST-INSTALLED ANCHORS
1. ANCHORS SERVING AS THE BASIS OF DESIGN ARE SHOWN ON THE DRAWINGS.
ACCEPTABLE ALTERNATIVE ANCHORS MAY BE SUPPLIED PROVIDED THE QUANTITY AND
CONFIGURATION MATCH THE CAPACITY OF THE DESIGN ANCHOR QUANTITY AND
CONFIGURATION. ANY ALTERNATES ARE TO BE SUBMITTED TO THE STRUCTURAL
ENGINEER FOR REVIEW. INSTALL IN ACCORDANCE WITH MANUFACTURER’S WRITTEN
INSTRUCTIONS. BELOW SUMMARIZES EACH ANCHOR TYPE USED ON THE PROJECT.
2. MECHANICAL ANCHORS:
a. EXPANSION ANCHORS
ANCHORED
INTO
BASIS OF DESIGN ACCEPTABLE ALTERNATES
UNCRACKED
CONCRETE
HILTI KB3 (ESR-2302) DEWALT POWER STUD+ SD2 (ESR-2502) RED
HEAD TRUBOLT+ (ESR-2427) SIMPSON STRONG
BOLT 2 (ESR-3037)
CRACKED
CONCRETE
HILTI KBTZ (ESR-1917) DEWALT POWER STUD+ SD2 (ESR-2502) RED
HEAD TRUBOLT+ (ESR-2427) SIMPSON STRONG
BOLT 2 (ESR-3037)
b. THREADED SCREW ANCHORS
ANCHORED
INTO
BASIS OF DESIGN ACCEPTABLE ALTERNATES
UNCRACKED
CONCRETE
HILTI KWIK HUS-EZ
(ESR-3027)
DEWALT POWER SCREW-BOLT+ (ESR-3889)
SIMPSON TITEN HD (ESR-2713)
CRACKED
CONCRETE
HILTI KWIK HUS-EZ
(ESR-3027)
DEWALT POWER SCREW-BOLT+ (ESR-3889)
SIMPSON TITEN HD (ESR-2713)
3. ADHESIVE ANCHORS: SHALL CONSIST OF DEFORMED REINFORCING BARS OR ASTM A193
GRADE B7 RODS, HEAVY DUTY NUTS AND WASHERS AND A TWO COMPONENT
STRUCTURAL ADHESIVE. WHERE ANCHORING INTO HOLLOW MASONRY, A SCREEN TUBE
SHALL BE PROVIDED.
ANCHORED
INTO
BASIS OF DESIGN ACCEPTABLE ALTERNATES
CONCRETE HILTI HIT-HY 200
(ESR-3187)
DEWALT AC 200+ (ESR-4027) SIMPSON SET-3G
(ESR-4057)
4. CRACKED CONCRETE REPRESENTS ALL CONCRETE FOR PROJECTS LOCATED IN SEISMIC
DESIGN CATEGORY C OR HIGHER, TENSILE ZONES SUCH AS BOTTOMS OF BEAMS AND
SLABS, OR WHERE NOTED ON THE DRAWINGS.
4/4/2025
EXP: 7/31/2026
PLAN OR DETAIL NUMBER
PLAN OR DETAIL NAME
PLAN OR DETAIL SCALE
DETAIL REFERRED TO BY SECTION CUT
SHEET DETAIL IS LOCATED ON
NAME
VIEW NAME
1/8" = 1'-0"
S300
SIM
INDICATES SIMILAR DETAIL REFERENCED
IN MULTIPLE LOCATIONS
LEVEL NAME
10'-0" HEIGHT ABOVE
PROJECT 0'-0"
INDICATES NOTE USED TO DESCRIBE
ADDITIONAL INFORMATION ABOUT
WORK REQUIRED, SPECIFIC TO THE
SHEET AND/OR DETAIL
INDICATES DIRECTION OF TRUE NORTH
VIEW KEY
LINE TYPE KEY:
NEW WORK
(DARK SOLID LINE/LINE WEIGHT WILL VARY)
NEW WORK BELOW OR BEYOND VIEW
(DARK DASH LINE)
EXISTING TO BE REMOVED
(DARK DASH LINE)
EXISTING WORK TO REMAIN
(HALFTONED SOLID LINE/LINE WEIGHT WILL VARY)
NON STRUCTURAL
(HALFTONED LIGHT SOLID LINE)
GRID OR CENTERLINE
MATERIAL LEGEND:
CONCRETE - CAST-IN-PLACE
CONCRETE - EXISTING
EARTH
GRAVEL OR GRANULAR FILL
GROUT OR DRYPACK OR SAND
MASONRY
WOOD / COLD-FORM STUD
PRECAST CONCRETE
STEEL
COLUMN DESIGNATION
BASE PLATE MARK
SF#(+X'-X")
P# (+X'-X")
FOOTING MARK (TOP ELEVATION)
PIER MARK (TOP ELEVATION)
N O R
HT
W XxX
BPX
STRUCTURAL SYMBOL LIST
GENERAL SYMBOLS:
SYMBOL DESCRIPTION DETAIL REFERENCE
TOP OF STRUCTURAL FRAMING ABOVE
ELEVATION (+0'-0")
(+16'-3")
TOP OF STRUCTURAL FOUNDATION
BELOW ELEVATION (+0'-0")
(-2'-0")
-1" SLAB DEPRESSION
S STEP IN FOOTING
FOUNDATION SYMBOLS:
SYMBOL DESCRIPTION DETAIL REFERENCE
N/A
N/A
BEAM CAMBER
HEADED STUD ANCHORS (HSA) ON BEAM(##)
c=X"
STEEL SYMBOLS:
SYMBOL DESCRIPTION DETAIL REFERENCE
BEAM SPLICE
N/A
N/A
STEEL DECK (DIRECTION)
NON-FRAME KICKER BRACE
MOMENT CONNECTION
STRUCTURAL ABBREVIATION KEY
ABBR: DESCRIPTION: ABBR: DESCRIPTION:
KSF
KSI
L
LBS
LL
LLH
LLV
LONG.
LSH
LSV
LT WT
MAX
MECH
MANUF
MIN
NIC
NTS
OC
OH
OPNG
OSB
PCF
P.H.
PJP
PL
PLF
PSF
PSI
PT
R
REINF
REQD
RTU
SC
SCHED
SFRS
SIM
SL
S.M.S.
SP
SPECS
SQ
STIFF
STL
SYM
T&B T.O.C T.O.
TC
TEMP
tf
THK
TRANS
TYP
UON
VERT
VIF
w/
WP
WT
W.W.F
WWR
(E) A.B.
ARCH
B.O.
bf
BF
BM
B.N.
BOTT
BTWN
CFSF
CGS
CJP
CLR
CL
CMU
COL
CONC
CONN
CONST
CONT
COORD
DIA
DL
DET
DWG
DWL
EA
EF
EFF
EL
ELEC
EMBED
E.N.
EOD
EOS
EQ
EQUIP
ETC
EW
EXP
EXT
f 'c
FDN
F.N.
FT
FTG
Fy
GA
GALV
GLB
GT
HORIZ
HSA
HSB
JT
K, KIP
NUMBER OR POUNDS
AT
DEGREE
DIAMETER
EXISTING
ANCHOR BOLT
ARCHITECT, -URE, -URAL
BOTTOM OF
BEAM FLANGE WIDTH
BRACE FRAME
BEAM
BOUNDARY NAILING
BOTTOM
BETWEEN
COLD FORM STEEL FRAMING
CENTER OF GRAVITY OF THE TENDON
COMPLETE JOINT PENETRATION WELD
CLEAR
CENTERLINE
CONCRETE MASONRY UNIT
COLUMN
CONCRETE
CONNECTION
CONSTRUCTION
CONTINUOUS
COORDINATION
DIAMETER
DEAD LOAD
DETAIL
DRAWING
DOWEL
EACH
EACH FACE
EFFECTIVE
ELEVATION
ELECTRICAL
EMBEDMENT
EDGE NAILING
EDGE OF DECK
EDGE OF SLAB
EQUAL
EQUIPMENT
ETCETERA
EACH WAY
EXPANSION
EXTERIOR
CONCRETE COMPRESSIVE STRENGTH
FOUNDATION
FIELD NAILING
FOOT
FOOTING
YIELD STRESS
GAGE OR GAUGE
GALVANIZED
GLULAM BEAM
GIRDER TRUSS
HORIZONTAL
HEADED STUD ANCHOR
HIGH STRENGTH BOLT
JOINT
KILOPOUND (1,000 POUNDS)
KIPS PER SQUARE FOOT
KIPS PER SQUARE INCH
LENGTH
POUNDS
LIVE LOAD
LONG LEG HORIZONTAL
LONG LEG VERTICAL
LONGITUDINAL
LONG SIDE HORIZONTAL
LONG SIDE VERTICAL
LIGHTWEIGHT
MAXIMUM
MECHANICAL
MANUFACTURER
MINIMUM
NOT IN CONTRACT
NOT TO SCALE
ON CENTER
OPPOSITE HAND
OPENING
ORIENTED STRAND BOARD
POUNDS PER CUBIC FOOT
PENTHOUSE
PARTIAL JOINT PENETRATION WELD
PLATE
POUNDS PER LINEAR FOOT
POUNDS PER SQUARE FOOT
POUNDS PER SQUARE INCH
POST-TENSION, -ED, -ING
RADIUS
REINFORCING, -MENT, -ED
REQUIRED
ROOF TOP UNIT
SLIP CRITICAL
SCHEDULE
SEISMIC FORCE-RESISTING SYSTEM
SIMILAR
SNOW LOAD
SHEET METAL SCREW
SPACE(S)
SPECIFICATION(S)
SQUARE
STIFFENER
STEEL
SYMMETRICAL
TOP AND BOTTOM
TOP OF CONCRETE
TOP OF
PRE-TENSIONED BOLT
TEMPERATURE
BEAM FLANGE THICKNESS
THICK
TRANSVERSE
TYPICAL
UNLESS OTHERWISE NOTED
VERTICAL
VERIFY IN FIELD
WITH
WORK POINT
WEIGHT
WELDED WIRE FABRIC
WELDED WIRE REINFORCING
VA Project Number:
Building:
Drawing Number:
Project Title:
Project Location:
Issue Date:
Checked By: Drawn By:
Drawing Title:
FULLY
SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
A
Submission:
ARCHITECT / ENGINEER OF RECORD:
Revisions: Date:
CONSULTANTS:
/8
/4
/8
/2
/4
-1
/2
CONSULTANT:
COMPASS
8734 GALLOWAY TRAIL
NOVELTY, OH. 44072
619-925-1647
ARCHITECT:
CB DESIGN GROUP
421 KING ST
SUITE 301
ALEXANDRIA, VA 22314
703-772-4213
PROFESSIONAL SEAL:
James A. Haley Veterans Hospital 13000 Bruce B. Downs Blvd.
Tampa, FL. 33612
2345678910111213141516
B
C
D
E
F
G
H
I
J
12345678910111213141516
DRAWINGS NOT INTENDED FOR
CONSTRUCTION.
CONSULTANT:
SCOTT PRZYBYSZ
15 SUNNEN DR. SUITE 104
ST. LOUIS, MO 63143
314-951-2535
CONSULTANT:
MARK DYCK
148 S. QUEEN ST. SUITE 201
MARTINSBURG, WV. 25401
304-266-3115
CONSULTANT:
CLARE KRAMER
2815 DIRECTORS ROW
SUITE 500
ORLANDO, FL. 32809
407-917-2430
04/04/2025
673-20-107
PRIPANJUSSTU
EHRM INFRASTRUCTURE UPGRADES
TAMPA, FL.
ISSUED FOR CONSTRUCTION
SYMBOL LIST, ABBREVIATION KEY
AND VIEW KEY
01-ST001
-2
-1
-S
T
/1
/2
.p d f
TESTING, INSPECTIONS, AND OBSERVATIONS
1. THE STRUCTURAL ENGINEER DOES NOT PROVIDE INSPECTIONS OF CONSTRUCTION. STRUCTURAL ENGINEER MAY MAKE PERIODIC OBSERVATIONS OF THE CONSTRUCTION. SUCH OBSERVATIONS SHALL NOT REPLACE REQUIRED INSPECTIONS BY THE GOVERNING AUTHORITIES OR SERVE AS “SPECIAL INSPECTIONS” AS MAY BE REQUIRED BY CHAPTER 17 OF THE INTERNATIONAL BUILDING CODE.
2. SEE ARCHITECTURAL, CIVIL, MECHANICAL, PLUMBING, AND ELECTRICAL DRAWINGS OR SPECIFICATIONS FOR TESTING AND INSPECTION
REQUIREMENTS OF NON-STRUCTURAL COMPONENTS.
3. DUTIES OF THE INSPECTION AGENCY PER IBC CHAPTER 17:
a. SUBMIT A PROPOSED TESTING AND INSPECTION PROGRAM TO THE OWNER, THE ARCHITECT AND THE STRUCTURAL ENGINEER FOR REVIEW AND
APPROVAL AT LEAST TWO WEEKS PRIOR TO COMMENCEMENT OF WORK.
b. PERFORM ALL TESTING AND INSPECTION REQUIRED PER APPROVED TESTING AND INSPECTION PROGRAM.
c. FURNISH INSPECTION REPORT TO THE BUILDING OFFICIAL, THE OWNER, THE ARCHITECT, STRUCTURAL ENGINEER AND THE GENERAL CONTRACTOR. THE REPORTS SHALL BE COMPLETED AND FURNISHED WITHIN 48 HOURS OF INSPECTED WORK.
d. SUBMIT A FINAL SIGNED REPORT STATING WHETHER THE WORK REQUIRING SPECIAL INSPECTION WAS, TO THE BEST OF THE SPECIAL INSPECTION
AGENCY’S KNOWLEDGE, IN CONFORMANCE WITH THE APPROVED PLANS AND SPECIFICATIONS.
4. SPECIAL INSPECTIONS AND TESTS ARE REQUIRED FOR MATERIALS AND SYSTEMS REQUIRED TO BE INSTALLED IN ACCORDANCE WITH ADDITIONAL MANUFACTURER’S INSTRUCTIONS THAT PRESCRIBE REQUIREMENTS NOT CONTAINED IN CHAPTER 17 OF THE IBC OR IN STANDARDS REFERENCED BY
THE IBC. THESE ITEMS INCLUDE:
a. POST-INSTALLED ANCHORS - INSPECTION
5. THE FOLLOWING WORK SHALL BE INSPECTED BY THE SPECIAL INSPECTOR UNLESS SPECIFICALLY WAIVED BY THE BUILDING OFFICIAL.
VERIFICATION AND INSPECTION TASK CONTINUOUS PERIODIC MATERIAL STD
REFERENCE
IBC
REFERENCE
CONCRETE CONSTRUCTION
1. INSPECT REINFORCEMENT, INCLUDING PRESTRESSING TENDONS, AND VERIFY
PLACEMENT
X ACI 318: CH 20,
25.2, 25.3, 26.2.1-26.6.3
1908.4
2. MATERIAL IDENTIFICATION OF REINFORCING (TYPE/GRADE) X
3. REINFORCING STEEL HAS NOT BEEN REBENT IN THE FIELD X
4. REINFORCING STEEL HAS BEEN TIED AND SUPPORTED AS REQUIRED X
5. REINFORCING STEEL CLEARANCES HAVE BEEN PROVIDED X
6. COMPOSITE STEEL MEMBERS HAVE REQUIRED SIZE X
8. INSPECT ANCHORS CAST IN CONCRETE X ACI 318: 17.8.2
9. INSPECT ANCHORS POST-INSTALLED IN HARDENED CONCRETE MEMBERS:
a. ADHESIVE ANCHORS INSTALLED IN HORIZONTALLY OR UPWARDLY INCLINED
ORIENTATIONS TO RESIST SUSTAINED TENSION LOADS
X ACI 318: 17.8.2.4
b. MECHANICAL ANCHORS AND ADHESIVE ANCHORS NOT DEFINED IN 9.a X ACI 318: 17.8.2
10. VERIFY USE OF REQUIRED DESIGN MIX X ACI 318: CH 19,
26.4.2, 26.4.4
1904.1, 1904.2, 1908.2, 1908.3
11. PRIOR TO CONCRETE PLACEMENT, FABRICATE SPECIMENS FOR STRENGTH TESTS,
PERFORM SLUMP AND AIR CONTENT TESTS, AND DETERMINE THE TEMPERATURE OF
THE CONCRETE
X ASTM C172, ASTM
C31, ACI 318: 26.5,
26.12
1907.10
12. INSPECT CONCRETE AND SHOTCRETE PLACEMENT FOR PROPER APPLICATION
TECHNIQUES
X ACI 318: 26.5 1908.6, 1908.7,
1908.8
13. VERIFY MAINTENANCE OF SPECIFIED CURING TEMPERATURE AND TECHNIQUES X ACI 318:
26.5.3-26.5.5
1908.9
14. VERIFY IN-SITU CONCRETE STRENGTH PRIOR TO REMOVAL OF SHORES AND FORMS
FROM BEAMS AND STRUCTURAL SLABS
X ACI 318: 26.11.2
15. INSPECT FORMWORK FOR SHAPE, LOCATION, AND DIMENSIONS OF THE CONCRETE
MEMBER BEING FORMED
X ACI 318: 26.11.2(b)
VERIFICATION AND INSPECTION TASK QC QA MATERIAL STD
REFERENCE
STRUCTURAL STEEL - FABRICATION
1. FABRICATION FACILITY X
2. CONNECTION ERECTION AND ASSEMBLY X X
3. PRETENSIONED AND SLIP-CRITICAL BOLTS/JOINTS USING TURN-OF-NUT METHOD WITHOUT
MATCHMAKING OF CALIBRATED WRENCH METHODS OF INSTALLATION
X X
4. SINGLE PASS FILLET WELDS 5/16” OR LESS X X X
5. ALL OTHER WELDS INCLUDING COMPLETE AND PARTIAL PENETRATION WELDS X X X
6. SHEAR STUD PLACEMENT X X
VERIFICATION AND INSPECTION TASK QC QA MATERIAL STD
REFERENCE
STRUCTURAL STEEL - ERECTION
1. STRUCTURAL STEEL ERECTION X X
2. CONNECTION ERECTION AND ASSEMBLY X X
3. PRETENSIONED AND SLIP-CRITICAL BOLTS/JOINTS USING TURN-OF-NUT METHOD WITHOUT
MATCHMAKING OF CALIBRATED WRENCH METHODS OF INSTALLATION
X X
4. SINGLE PASS FILLET WELDS 5/16” OR LESS X X X
5. ALL OTHER WELDS INCLUDING COMPLETE AND PARTIAL PENETRATION WELDS X X X
6. SHEAR STUD PLACEMENT X X
7. BEAM CAMBER (IN-PLACE) X
VERIFICATION AND INSPECTION TASK QC QA MATERIAL STD
REFERENCE
RCSC
CLAUSES
STRUCTURAL STEEL PRIOR TO BOLTING - MINIMUM INSPECTION
1. MANUFACTURER’S CERTIFICATIONS AVAILABLE FOR FASTENER MATERIALS O P TABLE C-N5.6-1 2.1, 9.1
2. FASTENERS MARKED IN ACCORDANCE WITH ASTM REQUIREMENTS O O TABLE C-N5.6-1 6.5.1
3. CORRECT FASTENERS SELECTED FOR THE JOINT DETAIL (GRADE, TYPE, BOLT
LENGTH IF THREADS ARE TO BE EXCLUDED FROM THE SHEAR PLANE)
O O TABLE C-N5.6-1 2.3.2, 2.7.2, 9.1
4. CORRECT BOLTING PROCEDURE SELECTED FOR JOINT DETAIL O O TABLE C-N5.6-1 4, 8
5. CONNECTING ELEMENTS, INCLUDING THE APPROPRIATE FAYING SURFACE
CONDITION AND HOLE PREPARATION, IF SPECIFIED, MEET APPLICABLE REQUIREMENTS
O O TABLE C-N5.6-1 TABLE 6.1(2)
6. PRE-INSTALLATION VERIFICATION TESTING BY INSTALLATION PERSONNEL
OBSERVED AND DOCUMENTED FOR FASTENER ASSEMBLIES AND METHODS USED
P1 O1 TABLE C-N5.6-1 3, 9.1, 9.3
7. PROTECTION STORAGE PROVIDED FOR BOLTS, NUTS, WASHERS, AND OTHER
FASTENER COMPONENTS
O O TABLE C-N5.6-1 2.2, 8, 9.1
1 DOCUMENT - THE INSPECTOR SHALL PREPARE REPORTS INDICATING THE WORK HAS BEEN PERFORMED IN ACCORDANCE WITH THE CONTRACT DOCUMENTS. THE REPORTS NEED NOT PROVIDE DETAILED MEASUREMENTS FOR JOINT FIT-UPS, WPS SETTINGS, COMPLETED WELDS, OR OTHER INDIVIDUAL ITEMS LISTED IN THE TABLES. FOR SHOP FABRICATION, THE REPORT SHALL INDICATE THE PIECE MARK OF THE PIECE INSPECTED. FOR FIELD WORK, THE REPORT SHALL INDICATE THE REFERENCE GRID LINES AND FLOOR OR ELEVATION INSPECTED. WORK NOT IN COMPLIANCE WITH THE CONTRACT DOCUMENTS AND WHETHER THE NONCOMPLIANCE HAS BEEN SATISFACTORILY REPAIRED SHALL BE NOTED IN THE INSPECTION.
VERIFICATION AND INSPECTION TASK QC QA MATERIAL STD
REFERENCE
RCSC
CLAUSES
STRUCTURAL STEEL AFTER BOLTING - MINIMUM INSPECTION
1. DOCUMENT ACCEPTANCE OR REJECTION OF BOLTED CONNECTIONS P P TABLE C-N5.6-3 N/A
VERIFICATION AND INSPECTION TASK QC QA MATERIAL STD
REFERENCE
AWS D1.1
CLAUSES
STRUCTURAL STEEL PRIOR TO WELDING - MINIMUM INSPECTION
1. WELDING PROCEDURE SPECIFICATIONS (WPS) AVAILABLE P P TABLE C-N5.4-1 6.3
2. MANUFACTURER CERTIFICATES FOR WELDING CONSUMABLES AVAILABLE P P TABLE C-N5.4-1 6.2
3. MATERIAL IDENTIFICATION O O TABLE C-N5.4-1 6.2
4. WELDER IDENTIFICATION O O TABLE C-N5.4-1 6.4 (WELDER
QUALIFICATIO
N)
5. FIT-UP OF GROOVE WELDS (INCLUDING JOINT GEOMETRY) O O TABLE C-N5.4-1
a. JOINT PREPARATION O O TABLE C-N5.4-1 6.5.2
b. DIMENSIONS (ALIGNMENT, ROOT OPENING, ROOT FACE, BEVEL) O O TABLE C-N5.4-1 5.22
c. CLEANLINESS (CONDITION OF STEEL SURFACE) O O TABLE C-N5.4-1 5.14
d. TACKING (TACK WELD QUALITY AND LOCATION) O O TABLE C-N5.4-1 5.17
e. BACKING TYPE AND FIT (IF APPLICABLE) O O TABLE C-N5.4-1 5.9, 5.21.1.1
6. FIT-UP OF CJP GROOVE WELDS OF HSS T-, Y- & K--JOINTS WITHOUT BACKING
(INCLUDING JOINT GEOMETRY)
P/O1 O TABLE C-N5.4-1 9.11.2
a. JOINT PREPARATION P/O1 O TABLE C-N5.4-1 9.11.2
b. DIMENSIONS (ALIGNMENT, ROOT OPENING, ROOT FACE, BEVEL) P/O1 O TABLE C-N5.4-1 9.11.2
c. CLEANLINESS (CONDITION OF STEEL SURFACE) P/O1 O TABLE C-N5.4-1 9.11.2
d. TACKING (TACK WELD QUALITY AND LOCATION) P/O1 O TABLE C-N5.4-1 9.11.2
7. CONFIGURATION AND FINISH OF ACCESS HOLES O TABLE C-N5.4-1 6.5.2, 5.16 (&
SEE AISC 360
SECT. J1.6)
8. FIT-UP OF FILLET WELDS P/O1 O TABLE C-N5.4-1
a. DIMENSIONS (ALIGNMENT, GAPS AT ROOT) P/O1 O TABLE C-N5.4-1 5.21.1
b. CLEANLINESS (CONDITION OF STEEL SURFACES) P/O1 O TABLE C-N5.4-1 5.14
c. TACKING (TACK WELD QUALITY AND LOCATION) P/O1 O TABLE C-N5.4-1 5.17
9. CHECK WELDING EQUIPMENT O O TABLE C-N5.4-1 6.2, 5.10
VERIFICATION AND INSPECTION TASK QC QA MATERIAL STD
REFERENCE
AWS D1.1
CLAUSES
STRUCTURAL STEEL DURING WELDING - MINIMUM INSPECTION
1. USE OF QUALIFIED WELDERS O O TABLE C-N5.4-2 6.4
2. CONTROL AND HANDLING OF WELDING CONSUMABLES O O TABLE C-N5.4-2 6.2
a. PACKAGING O O TABLE C-N5.4-2 5.3.1
b. EXPOSURE CONTROL O O TABLE C-N5.4-2 5.3.2 (FOR
SMAW), 5.3.3
(FOR SAW)
3. ENVIRONMENT CONDITIONS O O TABLE C-N5.4-2
a. WIND SPEED WITHIN LIMITS O O TABLE C-N5.4-2 5.11.1
b. PRECIPITATION AND TEMPERATURE O O TABLE C-N5.4-2 5.11.2
4. WPS FOLLOWED O O TABLE C-N5.4-2 6.3.3, 6.5.2, 5.5,
5.20
a. SETTINGS ON WELDING EQUIPMENT O O TABLE C-N5.4-2
b. TRAVEL SPEED O O TABLE C-N5.4-2
c. SELECTED WELDING MATERIALS O O TABLE C-N5.4-2
d. SHIELDING GAS TYPE/FLOW RATE O O TABLE C-N5.4-2
e. PREHEAT APPLIED O O TABLE C-N5.4-2 5.6, 5.7
f. INTERPASS TEMPERATURE MAINTAINED (MIN/MAX) O O TABLE C-N5.4-2
g. PROPER POSITION (F, V, H, OH) O O TABLE C-N5.4-2
h. INTERMIX OF FILLER METALS AVOIDED UNLESS APPROVED O O TABLE C-N5.4-2
5. WELDING TECHNIQUES O O TABLE C-N5.4-2 6.5.2, 6.5.3, 5.23
a. INTERPASS AND FINAL CLEANING O O TABLE C-N5.4-2 5.29.1
b. EACH PASS WITHIN PROFILE LIMITATIONS O O TABLE C-N5.4-2
c. EACH PASS MEETS QUALITY REQUIREMENTS O O TABLE C-N5.4-2
VERIFICATION AND INSPECTION TASK QC QA MATERIAL STD
REFERENCE
AWS D1.1
CLAUSES
STRUCTURAL STEEL AFTER WELDING - MINIMUM INSPECTION
1. WELDS CLEANED O O TABLE C-N5.4-3 5.29.1
2. SIZE, LENGTH AND LOCATION OF WELDS P P TABLE C-N5.4-3 6.5.1
3. WELDS MEET VISUAL ACCEPTANCE CRITERIA P2 P2 TABLE C-N5.4-3 6.5.3
a. CRACK PROHIBITION P2 P2 TABLE C-N5.4-3 TABLE 6.1(1)
b. WELD/BASE-METAL FUSION P2 P2 TABLE C-N5.4-3 TABLE 6.1(2)
c. CRATER CROSS-SECTION P2 P2 TABLE C-N5.4-3 TABLE 6.1(3)
d. WELD PROFILES P2 P2 TABLE C-N5.4-3 TABLE 6.1(4), 5.24
e. WELD SIZE P2 P2 TABLE C-N5.4-3 TABLE 6.1(6)
f. UNDERCUT P2 P2 TABLE C-N5.4-3 TABLE 6.1(7)
g. POROSITY P2 P2 TABLE 6.1(8)
4. ARC STRIKES P P TABLE C-N5.4-3 5.28
5. K-AREA3 P2 P2 TABLE C-N5.4-3 N/A
6. WELD ACCESS HOLES IN ROLLED HEAVY SHAPES AND BUILT-UP HEAVY SHAPES P P TABLE C-N5.4-3 5.16, 6.5.2 (&
SEE AISC 360
SECT. J1.6)
7. BACKING REMOVED AND WELD TABS REMOVED (IF REQUIRED) P2 P2 TABLE C-N5.4-3 5.9, 5.30
8. REPAIR ACTIVITIES P P2 TABLE C-N5.4-3 6.5.3, 5.25
9. DOCUMENT ACCEPTANCE OR REJECTION OF WELDED JOINT OR MEMBER P P TABLE C-N5.4-3 6.5.4, 6.5.5
10. PLACEMENT OF REINFORCING OR CONTOURING FILLET WELDS (IF REQUIRED) P2 P2 TABLE C-N5.4-3 6.5.4, 6.5.5
1 FOLLOWING PERFORMANCE OF THIS INSPECTION TASK FOR TEN WELDS TO BE MADE BY A GIVEN WELDER, WITH THE WELDER DEMONSTRATING UNDERSTANDING OF REQUIREMENTS AND POSSESSION OF THE SKILLS TO VERIFY THESE ITEMS, THE PERFORM DESIGNATION OF THIS TASK SHALL BE REDUCED TO OBSERVE, AND THE WELDER SHALL PERFORM THIS TASK. SHOULD THE INSPECTOR DETERMINE THE WELDER HAS DISCONTINUED PERFORMANCE OF THIS TASK, THE TASK SHALL BE RETURNED TO PERFORM UNTIL SUCH TIME AS THE INSPECTOR HAS RE-ESTABLISHED ADEQUATE
ASSURANCE THE WELDER WILL PERFORM THE INSPECTION TASKS LISTED.
2 DOCUMENT - THE INSPECTOR SHALL PREPARE REPORTS INDICATING THE WORK HAS BEEN PERFORMED IN ACCORDANCE WITH THE CONTRACT DOCUMENTS. THE REPORT NEED NOT PROVIDE DETAILED MEASUREMENTS FOR JOINT FIT-UPS, WPS SETTINGS, COMPLETED WELDS, OR OTHER INDIVIDUAL ITEMS LISTED IN THE TABLES. FOR SHOP FABRICATION, THE REPORT SHALL INDICATE THE PIECE MARK OF THE PIECE INSPECTED. FOR FIELD WORK, THE REPORT SHALL INDICATE THE REFERENCE GRID LINES AND FLOOR OR ELEVATION INSPECTED. WORK NOT IN COMPLIANCE WITH THE CONTRACT DOCUMENTS AND WHETHER THE NONCOMPLIANCE HAS BEEN SATISFACTORILY REPAIRED SHALL BE NOTED IN THE INSPECTION.
3 WHEN WELDING OF DOUBLER PLATES, CONTINUITY PLATES OR STIFFENERS HAS BEEN PERFORMED IN THE K-AREA, VISUALLY INSPECT THE WEB K- AREA FOR CRACKS WITHIN 3” OF THE WELD. THE VISUAL INSPECTION SHALL BE PERFORMED NO SOONER THAN 48 HOURS FOLLOWING COMPLETION
OF THE WELDING.
VERIFICATION AND INSPECTION TASK CONTINUOUS PERIODIC MATERIAL STD
REFERENCE
IBC
REFERENCE
STRUCTURAL DECKING
1. DECK PLACEMENT AND ATTACHMENT X X
VERIFICATION AND INSPECTION TASK CONTINUOUS PERIODIC MATERIAL STD
REFERENCE
IBC
REFERENCE
SOILS
1. VERIFY MATERIALS BELOW SHALLOW FOUNDATIONS ARE ADEQUATE TO ACHIEVE
THE DESIGN BEARING CAPACITY
X
2. VERIFY EXCAVATIONS ARE EXTENDED TO PROPER DEPTH AND HAVE REACHED
PROPER MATERIAL
X
3. PERFORM CLASSIFICATIONS AND TESTING OF COMPACTED FILL MATERIAL X
4. VERIFY USE OF PROPER MATERIALS, DENSITIES, AND LIFT THICKNESSES DURING
PLACEMENT AND COMPACTION OF COMPACTED FILL
X
5. PRIOR TO PLACEMENT OF COMPACTED FILL, INSPECT SUBGRADE AND VERIFY THAT
SITE HAS BEEN PREPARED PROPERLY
X
STRUCTURAL SHEET INDEX
SHEET NUMBER SHEET NAME
01-ST000 GENERAL NOTES
01-ST001 SYMBOL LIST, ABBREVIATION KEY AND VIEW KEY
01-ST101 BUILDING 01-1ST FLOOR - ENLARGED PLANS-DEMO AND NEW WORK
01-ST102 BUILDING 01 -2ND FLOOR - ENLARGED PLANS-DEMO AND NEW WORK
01-ST103 BUILDING 01 - ROOF - ENLARGED PLANS -DEMO AND NEW WORK
01-ST300 CONCRETE DETAILS
01-ST500 STEEL DETAILS
01-ST501 STEEL DETAILS
GRAND TOTAL: 8
VERIFICATION AND INSPECTION TASK QC QA MATERIAL STD
REFERENCE
RCSC
CLAUSES
STRUCTURAL STEEL DURING TO BOLTING - MINIMUM INSPECTION
1. FASTENER ASSEMBLIES PLACED IN ALL HOLES AND WASHERS AND NUTS ARE
POSITIONED AS REQUIRED
O P TABLE C-N5.6-2 7.1(1), 8.1, 9.1
2. JOINT BROUGHT TO THE SNUG-TIGHT CONDITION PRIOR TO THE PRETENSIONING
OPERATION
O O TABLE C-N5.6-2 8.1, 9.1
3. FASTENER COMPONENT NOT TURNED BY THE WRENCH PREVENTED FROM
ROTATING
O O TABLE C-N5.6-2 8.2, 9.2
4. FASTENERS ARE PRETENSIONED IN ACCORDANCE WITH THE RCSC SPECIFICATION,
PROGRESSING SYSTEMATICALLY FROM THE MOST RIGID POINT TOWARDS THE FREE
EDGES
O O TABLE C-N5.6-2 8.2, 9.2
AC
B
8 9
AD
AB.9
Z1
AD.9
8.1
Z2
NOTE:
1. NO STRUCTURAL ELEMENTS DEMOLISHED IN THE SCOPE OF THIS PROJECT. SEE ARCH FOR
ARCHITECTURAL COMPONENTS TO BE DEMOLISHED.
AC
B
8 9
AD
8.5
AB.9
(11'-9 1/4")
(E) GB5 (36x18)
(11'-9 1/4")
(E) GB5 (36x18)
(11'-9 1/4")
(E) GB5 (36x18)
(11'-9 1/4")
(E) GB5 (36x18)
(1
/4
(E
G B x
(E
G B x
Z1
(E) 12B14(E) 12B14
(E) 12B14
(E) 12B14
(E) L2 1/2x2 1/2x1/4
(E
L
/2 x
/2 x /4
(E) L2 1/2x2 1/2x1/4
(E) 14B17.2
(E) GB2 (48x28)
(E ) G
B (4 x
(E
G B x
13'-6" 12'-10"
G B
(4 x
(E
B
.2
(E) FLOATING SLAB
ON…
This is the start of the file's text. The full file is on GovTribe.