This is a technical drawing showing detailed waterproofing specifications for a steam tunnel construction project at a VA facility in Des Moines, IA. The drawing (AE521) contains five section details illustrating waterproofing system installations.

The drawing specifies a hot fluid applied waterproofing system with multiple components including: system primer/contact adhesive, 90-mil and 125-mil fluid applied waterproofing layers, reinforcing fabric, protection board, and drainage composite. Specific details are provided for waterproofing at new-to-existing tunnel connections, horizontal waterproofing terminations, vault lid waterproofing with vent pipe installations, steel hatch installations at vault lids, and tunnel inside corner waterproofing. The specifications include precise measurements and materials such as reinforced concrete, stainless steel components, sealants, and termination bars. The drawing is part of 100% Final Bid Documents for VA project number 636A6-23-101, dated 08/09/2024, with a revision on 02/07/2025.

View the file

Other files

File Type Posted
Site Visit Sign-In Sheet.pdf PDF
36C26325R0017 0005.docx DOCX document
260541 Underground Electrical Construction - 9 pages.pdf PDF
232213 Steam and Condensate Heating Piping - 26 pages.pdf PDF
336300 Steam Energy Distribution - 40 pages.pdf PDF
334613 Foundation Drainage - 7 pages.pdf PDF
329000 Planting - 11 pages.pdf PDF
230923 Direct-Digital Control Systems for HVAC - 67 pages.pdf PDF
271323-13i Communications Optical Fiber Splicing and Terminations - 1 pages.pdf PDF
36C26325R0017 0004.docx DOCX document
02833313 Lead-Based Paint Removal Disposal - 13 pages.pdf PDF
271323i Communications Optical Fiber Backbone Cabling - 3 pages.pdf PDF
265600 Exterior Lighting - 5 pages.pdf PDF
36C26325R0017 0003.docx DOCX document
Wage Determination 2.7.25 - 7 pages.pdf PDF
636A6-23-101 Steam Tunnel Questions - 12 pages.pdf PDF
MP101.pdf PDF
MP501.pdf PDF
C401-S-2.pdf PDF
E104.pdf PDF
C501-N-1.pdf PDF
AE314.pdf PDF
Building 10 Addition 1973 - 9 pages.pdf PDF
AE312.pdf PDF
C601-N.pdf PDF
S201.pdf PDF
AE311.pdf PDF
C401-N-1.pdf PDF
CL701-N.pdf PDF
C401-N-2.pdf PDF
AE520.pdf PDF
MP104.pdf PDF
S001.pdf PDF
S202.pdf PDF
36C26325R0017 0002.pdf PDF
AE101-SB.pdf PDF
S203.pdf PDF
C201-N.pdf PDF
Building 10 Original Construction 1932 - 8 pages.pdf PDF
C401-S-1.pdf PDF
C902.pdf PDF
MP302.pdf PDF
E103.pdf PDF
MV402.pdf PDF
AE313.pdf PDF
E501.pdf PDF
CD101-N.pdf PDF
Tremco Product Infomation.pdf PDF
Wage Determination 1.31.25 - 7 pages.pdf PDF
36C26325R0017 0001.docx DOCX document
Show 40 more

Latest 50 of 62 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

HOT FLUID APPLIED WATERPROOFING SYSTEM:

DRAINAGE COMPOSITE

PROTECTION BOARD

125 MILS FLUID APPLIED WATERPROOFING

REINFORCING FABRIC

90 MILS FLUID APPLIED WATERPROOFING

SYSTEM PRIMER OR CONTACT ADHESIVE

REINFORCED CONCRETE - SEE STRUCTURAL90 MILS FLUID APPLIED WATERPROOFING

SEALANT

SYSTEM PRIMER OR CONTACT ADHESIVE

125 MILS FLUID APPLIED WATERPROOFING

PROTECTION BOARD

SYSTEM PRIMER OR CONTACT ADHESIVE, 2ND COAT

PROTECTION BOARD

DRAINAGE COMPOSITE

REINFORCED CONCRETE WALL. SEE STRUCTURAL

REINFORCED CONCRETE LID. SEE STRUCTURAL

/2 AE520

EXISTING TUNNEL. SEE PLANS AND

STRUCTURAL

EXISTING TUNNEL WATERPROOFING

SYSTEM. FIELD VERIFY TYPE. CONSULT

MANUFACTURE REP OF HOT FLUID APPLIED

SYSTEM FOR APPROVED CONNECTION

DETAILS

TERMINATION BAR

SYSTEM PRIMER OR CONTACT ADHESIVE

90 MILS FLUID APPLIED WATERPROOFING

REINFORCING MATERIAL

GALVANIZED METAL FLASHING

REINFORCING MATERIAL 1ST LAYER

125 MILS FLUID APPLIED WATERPROOFING, 2ND COAT

REINFORCING MATERIAL 2ND LAYER

DRAINAGE COMPOSITE

NOTES APPLY

90 MILS FLUID APPLIED WATERPROOFING

SYSTEM PRIMER OR CONTACT ADHESIVE

125 MILS FLUID APPLIED WATERPROOFING

TERMINATION BAR

PROTECTION BOARD

DRAINAGE COMPOSITE

REINFORCED CONCRETE LID. SEE STRUCTURAL

CAP. SEE CIVIL

EXPOSED REINFORCED CONCRETE LID.

SEE STRUCTURAL

90 MILS FLUID APPLIED WATERPROOFING OR

UNCURED NEOPRENE FLASHING

GRADE. SEE CIVIL

SEALANT

FILL. SEE CIVIL

SURFACE. SEE CIVIL

STAINLESS STEEL PIPE. SEE

MECHANICAL

5" M

IN

4" M

IN

REINFORCED CONCRETE LID. SEE STRUCTURAL

CONCRETE TOPPING SLAB. SEE CIVIL &

STRUCTURAL

SLOPE. SEE CIVIL

SEALANT AND BACKER ROD 1/2"

90 MILS FLUID APPLIED WATERPROOFING

REINFORCING FABRIC

SYSTEM PRIMER OR CONTACT ADHESIVE

125 MILS FLUID APPLIED WATERPROOFING

PROTECTION BOARD

DRAINAGE COMPOSITE

SEALANT

STAINLESS STEEL CLAMPING RING

STAINLESS STEEL PIPE FLASHING

SEALANT BEAD

SEALANT

PIPE SLEEVE WITH INTEGRAL

WATER STOP. SEE

MECHANICAL

10"

4 1/2"

30.00°

4"

/4

STEEL CHANNEL FRAME WITH

ANCHOR FLANGE

5" M

IN

4" M

IN

REINFORCED CONCRETE LID. SEE STRUCTURAL

CONCRETE TOPPING SLAB. SEE CIVIL &

STRUCTURAL

SLOPE. SEE CIVIL

SEALANT AND BACKER ROD 1/2"

90 MILS FLUID APPLIED WATERPROOFING

REINFORCING FABRIC

SYSTEM PRIMER OR CONTACT ADHESIVE

125 MILS FLUID APPLIED WATERPROOFING

PROTECTION BOARD

DRAINAGE COMPOSITE

REINFORCED STEEL ACCESS

HATCH LID

ACCESS HATCH INTEGRAL

DRAIN

REINFORCED STEEL ACCESS

HATCH FRAME

10"

HOT FLUID APPLIED WATERPROOFING SYSTEM:

SYSTEM PRIMER OR CONTACT ADHESIVE

90 MILS FLUID APPLIED WATERPROOFING

REINFORCING FABRIC

125 MILS FLUID APPLIED WATERPROOFING

PROTECTION BOARD

DRAINAGE COMPOSITE

90 MILS FLUID APPLIED WATERPROOFING

REINFORCED CONCRETE TUNNEL

CEILING. -SEE STRUCTURAL

REINFORCING MATERIAL 1ST LAYER

SYSTEM PRIMER OR CONTACT ADHESIVE

SECOND COAT 90 MILS FLUID APPLIED WATERPROOFING

125 MILS FLUID APPLIED WATERPROOFING

REINFORCING MATERIAL 2ND LAYER

SYSTEM PRIMER OR CONTACT ADHESIVE, 2ND COAT

PROTECTION BOARD

DRAINAGE COMPOSITE

REINFORCED CONCRETE WALL. SEE STRUCTURAL

FILL. SEE CIVIL

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% FINAL BID

DOCUMENTS

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

DESIGNER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

623 26TH AVENUE

ROCK ISLAND, IL 61201

9555 JAMES AVE S. SUITE 200

BLOOMINGTON, MN 55431

C U s e rs

\g b a rb a ri

\D o c u m e n ts

\1

-A -R

G io v a n n i- B a rb a ri .r v t

/7

/2

:3

:2

A M

AE521

EXTERIOR SECTION DETAILS CONSTRUCT STEAM

TUNNEL

DES MOINES, IA

636A6-23-101

3, 11 & SITE

08/09/2024 GJB GJB

17270

1 1/2" = 1'-0"

SECTION DETAIL - WATERPROOFING AT NEW TO EXISTING TUNNEL

1 1/2" = 1'-0"

SECTION DETAIL - HORIZINTAL WATERPROOFING TERMINATION (TYP)

3" = 1'-0"

SECTION DETAIL - VAULT LID WATER PROOFING AND CURB AT VENT PIPE

3" = 1'-0"

SECTION DETAIL - STEEL HATCH AT VAULT LID

1 1/2" = 1'-0"

SECTION DETAIL - TUNNEL INSIDE CORNER WATER PROOFING (TYP)

Revisions: Date:

REVISION 1 02/07/2025

Sheets
AE101-SB - SOUTH TUNNEL PLAN - LINK B
AE311 - WALL, TUNNEL & VALUT SECTIONS
AE312 - VAULT LID SECTIONS
AE313 - TUNNEL SECTIONS
AE314 - VAULT & VAULT LID SECTIONS
AE520 - EXTERIOR SECTION DETAILS
AE521 - EXTERIOR SECTION DETAILS