This file contains detailed architectural drawings showing sections and elevations for a steam tunnel construction project at a VA facility in Des Moines, IA. The drawings (drawing number AE311) show wall, tunnel, and vault sections for Buildings 3, 11, and site work.
The technical details include specifications for a reinforced concrete tunnel structure with waterproofing systems, drainage boards, and mechanical components including 10" high pressure steam pipes, 4" low pressure condensate pipes, and 2" pumped condensate pipes. The drawings specify structural elements like reinforced concrete walls, footings, and lids, with steel components including W8X31 wide flange beams and posts requiring intumescent fireproofing. Key dimensions include an 8'-0" tunnel width with 6'-6" minimum clearance. The drawings show integration with existing building infrastructure, including connection details to mechanical rooms, and specify various civil engineering elements like drain tile systems, geofabric, and grading requirements. The drawings are dated 08/09/2024 and marked as 100% Final Bid Documents.
View the file
Other files
Show 40 more
Latest 50 of 62 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
LOWER LEVEL - BLDG 3
907'-1 1/4"
FIRST LEVEL - BLDG 3
919'-1 1/4"
AE520
B953
MECHANICAL
ROOM
EXISTING WALL CONSTRUCTION.
FILED VERIFY WALL THICKNESS
AND WALL CONSTRUCTION
AE520
SLOPE
AE520
REINFORCED CONCRETE
VAULT LID - SEE
STRUCTURAL
REINFORCED CONCRETE
WALL - SEE STRUCTURAL
REINFORCED CONCRETE
FLOOR - SEE STRUCTURAL
LIGHTING. -SEE ELECTRICAL
4" LOW PRESSURE STEAM
CONDENSATE PIPE - SEE
MECHANICAL
10" HIGH PRESSURE
STEAM - SEE
MECHANICAL
EXISTING STEAM PIPE. -SEE
MECHANICAL
W8X31 STEEL WIDE FLANGE
BEAM AND POST(NOT SHOW).
SEE STRUCTURAL. APPLY
INTUMESCENT FIREPROOFING
ON POST AN BEAM BEFORE
INSTALLATION.
GRADE. SEE CIVIL
FILL. SEE CIVIL
EXISTING FOOTING. FILED
VERIFY SIZE AND LOCATION
EXISTING DRAIN. FILED VERIFY
SIZE AND LOCATION
SURFACE. SEE CIVIL
CAP. SEE CIVIL
GEOFABRIC. SEE CIVIL
DRAIN TILE SYSTEM. SEE CIVIL
LOWER LEVEL - BLDG 3
907'-1 1/4"
REINFORCED CONCRETE VAULT
LID. -SEE STRUCTURAL
CONCRETE SLAB ON GRADE. -
SEE STRUCTURAL
DOOR AND FRAME AS
SCHEDULED
FIRST LEVEL - BLDG 3
919'-1 1/4"
AE520
EXISTING WALL CONSTRUCTION.
FILED VERIFY WALL THICKNESS
AND WALL CONSTRUCTION
AE520
DOOR HEAD
6'-0" FIELD VERIFY
FIELD VERIFY BLOCK / BRICK
JOINT LOCATION PRIOR TO DOOR
SUBMITTAL.
AE520
SLOPE
SIM
EXISTING FOOTING. FILED
VERIFY SIZE AND LOCATION
EXISTING DRAIN. FILED VERIFY
SIZE AND LOCATION
LOWER LEVEL - BLDG 3
907'-1 1/4"
FIRST LEVEL - BLDG 3
919'-1 1/4"
AE520
EXISTING WALL CONSTRUCTION. FILED
VERIFY WALL THICKNESS AND WALL
CONSTRUCTION
EXISTING WALL CONSTRUCTION. FILED
VERIFY WALL THICKNESS AND WALL
CONSTRUCTION
AE520
SLOPE
CONCRETE SLAB ON GRADE. -
SEE STRUCTURAL
AE520
SIM
GRADE - SEE CIVIL DRAWINGS
REINFORCED CONCRETE WALL. -SEE STRUCTURAL
REINFORCED CONCRETE LID. -SEE STRUCTURAL
REINFORCED CONCRETE FOOTING / FLOOR. -SEE STRUCTURAL
DRAIN TILE SYSTEM. SEE CIVIL
FLUID APPLIED WATERPROOFING SYSTEM AND
DRAINAGE BOARD. ALL SIDES AND TOP OF
TUNNEL. EXTEND DOWN TO TOP OF FOOTING.
AE520
AE520
10" HIGH PRESSURE STEAM - SEE MECHANICAL
PIPING SUPPORT SYSTEM. SEE MECHANICAL
LIGHTING. -SEE ELECTRICAL
4" LOW PRESSURE CONDENSATE - SEE MECHANICAL
2" PUMPED CONDENSATE - SEE MECHANICAL
FILL. SEE CIVIL
FILL. SEE CIVIL
8'-0"
S E
E S
T R
U C
T U
R A
L
6' -6
M
IN
SURFACE - SEE CIVIL DRAWINGS
CAP - SEE CIVIL DRAWINGS
GEO FABRIC - SEE CIVIL DRAWINGS
AE520
SIM
REINFORCED CONCRETE FOOTING / FLOOR. -SEE STRUCTURAL
DRAIN TILE SYSTEM. SEE CIVIL
FILL. SEE CIVIL
GEOFABRIC. SEE CIVIL
FILL. SEE CIVIL
RAILING AND GATE. SEE CIVIL
GRADE - SEE CIVIL DRAWINGS
REINFORCED CONCRETE WALL. -SEE STRUCTURAL
FLUID APPLIED WATERPROOFING SYSTEM AND
DRAINAGE BOARD. ALL SIDES AND TOP OF
TUNNEL. EXTEND DOWN TO TOP OF FOOTING.
PIPING SUPPORT SYSTEM. SEE MECHANICAL
PIPING BEYOND. - SEE MECHANICAL
REINFORCED STEEL HATCH. SEE SPECIFICATION 08 31 00
TUNNEL BEYOND. SEE STRUCTURAL & CIVIL
AE520
TYP
SLOPED SLAB. SEE CIVIL & STRUCTURAL
STEEL LADDER, SEE STRUCTURAL
CONCRETE BEAM BEYOND. SEE STRUCTURAL
WATERSTOP AT ALL JOINTS. -SEE STRUCTURAL
REINFORCED CONCRETE LID. -SEE STRUCTURAL
CAP - SEE CIVIL DRAWINGS
SURFACE - SEE CIVIL DRAWINGS
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% FINAL BID
DOCUMENTS
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
DESIGNER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
623 26TH AVENUE
ROCK ISLAND, IL 61201
9555 JAMES AVE S. SUITE 200
BLOOMINGTON, MN 55431
C U s e rs
\g b a rb a ri
\D o c u m e n ts
\1
-A -R
G io v a n n i- B a rb a ri .r v t
/7
/2
:3
:1
A M
AE311
WALL, TUNNEL & VALUT
SECTIONS
CONSTRUCT STEAM
TUNNEL
DES MOINES, IA
636A6-23-101
3, 11 & SITE
08/09/2024 GJB GJB
17270
1/2" = 1'-0"
VAULT 3 SECTION @ ACCESS HATCH - BUILDING 3
1/2" = 1'-0"
WALL SECTION - BUILDING 3 VAULT - NORTH/SOUTH
1/2" = 1'-0"
WALL SECTION - VAULT 3 @ LOUVER - BUILDING 3
1/2" = 1'-0"1
NORTH TUNNEL SECTION - TYPICAL
1/2" = 1'-0"
SECTION - VAULT 6
Revisions: Date:
REVISION 1 02/07/2025
| Sheets |
| AE101-SB - SOUTH TUNNEL PLAN - LINK B |
| AE311 - WALL, TUNNEL & VALUT SECTIONS |
| AE312 - VAULT LID SECTIONS |
| AE313 - TUNNEL SECTIONS |
| AE314 - VAULT & VAULT LID SECTIONS |
| AE520 - EXTERIOR SECTION DETAILS |
| AE521 - EXTERIOR SECTION DETAILS |