AE314.pdf
PDF 699 KB Posted
- Solicitation number
- 36C26325R0017
About this file
This engineering drawing (AE314) shows detailed sections and specifications for a steam tunnel construction project at a VA facility in Des Moines, IA. The drawing includes five cross-sectional views showing vault and vault lid details.
The sections detail the construction requirements for reinforced concrete walls, lids, footings, and floors, with fluid-applied waterproofing systems and drainage boards specified for all sides and top of the tunnel. The drawings show specifications for 10" high pressure steam, 4" low pressure condensate, and 2" pumped condensate piping systems. Additional features include reinforced steel hatches (per specification 08 31 00), steel ladders, railings, gates, and stainless steel vent pipes. The drawing is dated 08/09/2024 and marked as "100% FINAL BID DOCUMENTS" with a revision date of 02/07/2025, suggesting this is part of the final construction documentation package for bidding purposes.
View the file
Other files
Show 40 more
Latest 50 of 62 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
AE314
EXISTING TUNNEL SYSTEM -SEE
STRUCTURAL
LIGHTING. -SEE
ELECTRICAL
EXISTING TUNNEL SYSTEM. SEE
STRUCTURAL
PIPING - SEE MECHANICAL FOR
TYPE AND LOCATION
PIPING SUPPORT - SEE MECHANICAL
FOR TYPE AND LOCATION
EXISTING TUNNEL SYSTEM -SEE
STRUCTURAL
PIPING (BEHIND) - SEE
MECHANICAL FOR TYPE AND
LOCATION
REINFORCED CONCRETE LID AND BEAMS. -SEE STRUCTURAL
GRADE - SEE CIVIL
REINFORCED CONCRETE FOOTING / FLOOR. -SEE STRUCTURALFILL - SEE CIVIL
REINFORCED CONCRETE
WALLS -SEE STRUCTURAL
FLUID APPLIED WATERPROOFING
SYSTEM AND DRAINAGE BOARD. ALL
SIDES AND TOP OF TUNNEL. EXTEND
DOWN AND ONTO EXISTING TUNNEL.
10" HIGH PRESSURE STEAM - SEE MECHANICAL
4" LOW PRESSURE CONDENSATE - SEE MECHANICAL
2" PUMPED CONDENSATE - SEE MECHANICAL
AE520
AE521
SIM
AE521
SIM/MIR
RAILINGS AND GATE. SEE CIVIL
GRADE. SEE CIVIL
AE520
MIR/SIM
SURFACE. SEE CIVIL
CAP. SEE CIVIL
AE314
REINFORCED CONCRETE WALL. -SEE
STRUCTURAL
REINFORCED CONCRETE LID. -SEE
STRUCTURAL
REINFORCED CONCRETE FOOTING / FLOOR. -SEE
STRUCTURAL
DRAIN SYSTEM. SEE CIVIL
FLUID APPLIED WATERPROOFING SYSTEM AND
DRAINAGE BOARD. ALL SIDES AND TOP OF TUNNEL.
EXTEND DOWN TO TOP OF FOOTING.
10" HIGH PRESSURE STEAM - SEE MECHANICAL
4" LOW PRESSURE CONDENSATE - SEE MECHANICAL
2" PUMPED CONDENSATE - SEE MECHANICAL
REINFORCED STEEL HATCH (BEYOND). SEE
SPECIFICATION 08 31 00. PAINT
PIPING SUPPORT SYSTEM. SEE MECHANICAL
PIPING SUPPORT SYSTEM. SEE MECHANICAL
AE520
AE520
AE520
AE520
SIM/MIR
AE314
MIR/SIM
AE520
SIM
FILL. SEE CIVIL
GRADE. SEE CIVIL
GRADE. SEE CIVIL
SURFACE. SEE CIVIL
CAP. SEE CIVIL
FILL. SEE CIVIL
10"
10"
AE521
SIM/MIR
AE520
AE520
MIR
LOCKING REINFORCED STEEL HATCH.
SEE SPECIFICATION 08 31 00. PAINT
RAILING. SEE CIVIL
REINFORCED CONCRETE
WALL. SEE STRUCTURAL
REINFORCED CONCRETE
LID. SEE STRUCTURAL
CONCRETE TOPING SLAB. SEE
CIVIL & STRUCTURAL
SLOPE . SEE CIVIL
FLUID APPLIED
WATERPROOFING SYSTEM
AND DRAINAGE BOARD.
GRADE. SEE CIVIL
SURFACE. SEE CIVIL
CAP. SEE CIVIL
10"
AE521
SIM
AE521
AE520
SIM
SIM
10"
AE521
AE520
STAINLESS STEEL VENT PIPE.
SEE MECHANICALREINFORCED STEEL HATCH. SEE
SPECIFICATION 08 31 00. PAINT
RAILING. SEE CIVIL
REINFORCED CONCRETE
WALL. SEE STRUCTURAL
REINFORCED CONCRETE
LID. SEE STRUCTURAL
CONCRETE TOPING SLAB. SEE
CIVIL & STRUCTURAL
SLOPE . SEE CIVIL
FLUID APPLIED
WATERPROOFING SYSTEM
AND DRAINAGE BOARD.
DRAIN FOR STEEL HATCH
GRADE. SEE CIVIL
STEEL LADDER. SEE
STRUCTURAL
SURFACE. SEE CIVIL
CAP. SEE CIVIL
10" 10"
AE520
TYP
AE521
AE520
MIR
REINFORCED STEEL HATCH. SEE
SPECIFICATION 08 31 00. PAINT
RAILING. SEE CIVIL
REINFORCED CONCRETE
WALL. SEE STRUCTURAL
REINFORCED CONCRETE
LID. SEE STRUCTURAL
CONCRETE TOPING SLAB. SEE
CIVIL & STRUCTURAL
SLOPE . SEE CIVIL
FLUID APPLIED
WATERPROOFING SYSTEM
AND DRAINAGE BOARD.
DRAIN FOR STEEL HATCH
GRADE. SEE CIVIL
SURFACE. SEE CIVIL
CAP. SEE CIVIL
1/2" = 1'-0"
SECTION - VAULT 1 @ EXISTING TUNNEL - NORTH/SOUTH
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% FINAL BID
DOCUMENTS
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
DESIGNER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
623 26TH AVENUE
ROCK ISLAND, IL 61201
9555 JAMES AVE S. SUITE 200
BLOOMINGTON, MN 55431
C U s e rs
\g b a rb a ri
\D o c u m e n ts
\1
-A -R
G io v a n n i- B a rb a ri .r v t
/7
/2
:5
:1
A M
AE314
VAULT & VAULT LID SECTIONS CONSTRUCT STEAM
TUNNEL
DES MOINES, IA
636A6-23-101
3, 11 & SITE
08/09/2024 GJB GJB
17270
1/2" = 1'-0"
SECTION - VAULT 1 - EAST/WEST
1/2" = 1'-0"
SECTION - LID AT VAULT 2 - EAST/WEST
1/2" = 1'-0"
SECTION - LID AT VAULT 1 - NORTH/SOUTH
1/2" = 1'-0"
SECTION - LID AT VAULT 1 - LARGE HATCH
Revisions: Date:
REVISION 1 02/07/2025
| Sheets |
| AE314 - VAULT & VAULT LID SECTIONS |
File details come from the government source that posted it. Updated .