265600 Exterior Lighting - 5 pages.pdf
PDF 91 KB Posted
- Solicitation number
- 36C26325R0017
About this file
This is Section 26 56 00 Exterior Lighting specification document for the Des Moines VA Medical Center Steam Tunnel Construction Project (VA Project 636A6-23-101). The document details requirements for furnishing, installing, and connecting exterior lighting fixtures, poles, and supports.
The specification requires cast-in-place concrete foundations with 3000 psi minimum 28-day compressive strength for light poles, with specific requirements for forms, anchor bolts, and grounding. Key installation requirements include proper excavation and backfill procedures, use of anchor bolt templates from pole manufacturers, vertical positioning of poles, and non-shrink grout application between pole bases and concrete foundations. The document references multiple industry standards including NEMA, ANSI, ASTM, and UL requirements for lighting equipment and installation. For modifications to existing lighting systems, new components must be compatible with existing systems, and new poles/luminaires must match existing configurations except where drawings specify otherwise. Final acceptance requires verification of operation after installation and circuit energizing.
View the file
Other files
Show 40 more
Latest 50 of 62 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Des Moines VAMC, Des Moines IA VA Project 636A6-23-101
Construct Steam Tunnel 02/07/2025
3600 30th Street Revision 1
Des Moines, IA 50310
26 56 00 - 1
SECTION 26 56 00
EXTERIOR LIGHTING
PART 1 - GENERAL
1.1 DESCRIPTION
This section specifies the furnishing, installation, and connection of exterior fixtures, poles, and supports. The terms “lighting fixtures”, “fixture” and “luminaire” are used interchangeably.
1.2 RELATED WORK
A. Section 26 05 11, REQUIREMENTS FOR ELECTRICAL INSTALLATIONS: General electrical requirements and items that are common to more than one section of Division 26.
B. Section 26 05 19, LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES
(600 VOLTS AND BELOW): Low voltage power and lighting wiring.
C. Section 26 05 26, GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS:
Requirements for personnel safety and to provide a low impedance path for possible ground fault currents.
D. Section 26 05 33, RACEWAY AND BOXES FOR ELECTRICAL SYSTEMS: Conduits, fittings, and boxes for raceway systems.
E. Section 26 05 41, UNDERGROUND ELECTRICAL CONSTRUCTION: Underground handholes and conduits.
1.3 QUALITY ASSURANCE
A. Quality Assurance shall be in accordance with Paragraph, QUALIFICATIONS
(PRODUCTS AND SERVICES) in Section 26 05 11, REQUIREMENTS FOR
ELECTRICAL INSTALLATIONS.
1.4 APPLICABLE PUBLICATIONS
A. Publications listed below (including amendments, addenda, revisions, supplements, and errata) form a part of this specification to the extent referenced. Publications are referenced in the text by designation only.
B. American Association of State Highway and Transportation Officials
(AASHTO):
LRFDLTS-17..............Structural Supports for Highway Signs, Luminaires and Traffic Signals
C. American Concrete Institute (ACI):
318-19 .................Building Code Requirements for Structural
Concrete
D. American National Standards Institute (ANSI):
3600 30th Street Revision 1
Des Moines, IA 50310
26 56 00 - 2
H35.1/H35 1M-17.........American National Standard Alloy and Temper
Designation Systems for Aluminum
E. American Society for Testing and Materials (ASTM):
A123/A123M-17 ..........Zinc (Hot-Dip Galvanized) Coatings on Iron and
Steel Products
A153/A153M-16...........Zinc Coating (Hot-Dip) on Iron and Steel
Hardware
B108/B108M-19 ..........Aluminum-Alloy Permanent Mold Castings
C1089-19 ...............Spun Cast Prestressed Concrete Poles
F. Federal Aviation Administration (FAA):
AC 70/7460-IL-20........Obstruction Marking and Lighting
AC 150/5345-43J-19......Specification for Obstruction Lighting
Equipment
G. Illuminating Engineering Society of North America (IESNA):
RP-8-21.................Roadway Lighting
LM-72-20................Directional Positioning of Photometric Data
LM-79-19................Approved Method for the Electrical and
Photometric Measurements of Solid-Sate Lighting
Products
LM-80-21................Approved Method for Measuring Luminous Flux and
Color Maintenance of LED Packages, Arrays and
Modules
TM-15-20................Luminaire Classification System for Outdoor
Luminaires
H. National Electrical Manufacturers Association (NEMA):
C78.41-16...............Electric Lamps – Guidelines for Low-Pressure
Sodium Lamps
C78.42-09(R2016) .......Electric Lamps – Guidelines for High-Pressure
Sodium Lamps
C78.43-17 ..............Electric Lamps – Single-Ended Metal-Halide
Lamps
C78.1381-98.............Electric Lamps – 70-Watt M85 Double-Ended
Metal-Halide Lamps
C81.61-19 ..............Electrical Lamp Bases – Specifications for
Bases (Caps) for Electric Lamps
C82.4-17 ...............Ballasts for High-Intensity-Discharge and Low-
Pressure Sodium Lamps (Multiple-Supply Type)
3600 30th Street Revision 1
Des Moines, IA 50310
26 56 00 - 3
C136.3-20 ..............For Roadway and Area Lighting Equipment –
Luminaire Attachments
C136.17-05(S2017) .....Roadway and Area Lighting Equipment – Enclosed
Side-Mounted Luminaires for Horizontal-Burning
High-Intensity-Discharge Lamps – Mechanical
Interchangeability of Refractors
ICS 2-00(R2020) ........Controllers, Contactors and Overload Relays
Rated 600 Volts
ICS 6-93(R2016) ........Enclosures
I. National Fire Protection Association (NFPA):
70-23 ..................National Electrical Code (NEC)
101-21..................Life Safety Code
J. Underwriters Laboratories, Inc. (UL):
496-17 .................Lampholders
773-16..................Plug-In, Locking Type Photocontrols for Use with Area Lighting
773A-16 ................Nonindustrial Photoelectric Switches for
Lighting Control
1029-94.................High-Intensity-Discharge Lamp Ballasts
1598-21 ................Luminaires
8750-15.................Light Emitting Diode (LED) Equipment for Use in
Lighting Products
PART 2 - PRODUCTS
2.1 GENERAL REQUIREMENTS
Luminaires, materials and equipment shall be in accordance with NEC, UL, ANSI, and as shown on the drawings and specified.
2.2 FOUNDATIONS FOR POLES
A. Foundations shall be cast-in-place concrete, having 3000 psi minimum
28-day compressive strength.
B. Foundations shall support the effective projected area of the specified pole, arm(s), luminaire(s), and accessories, such as shields, banner arms, and banners, under wind conditions previously specified in this section.
C. Place concrete in spirally-wrapped treated paper forms for round foundations, and construct forms for square foundations.
3600 30th Street Revision 1
Des Moines, IA 50310
26 56 00 - 4
D. Rub-finish and round all above-grade concrete edges to approximately 6 mm (0.25-inch) radius.
E. Anchor bolt assemblies and reinforcing of concrete foundations shall be as shown on the drawings. Anchor bolts shall be in a welded cage or properly positioned by the tiewire to stirrups.
F. Prior to concrete pour, install electrode per Section 26 05 26, GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS.
2.3 EXISTING LIGHTING SYSTEMS
A. For modifications or additions to existing lighting systems, the new components shall be compatible with the existing systems.
B. New poles and luminaires shall have approximately the same configurations, dimensions, lamping and reflector type as the existing poles and luminaires, except where otherwise shown on the drawings.
PART 3 - EXECUTION
3.1 INSTALLATION
A. Install lighting in accordance with the NEC, as shown on the drawings, and in accordance with manufacturer’s recommendations.
B. Pole Foundations:
1. Excavate only as necessary to provide sufficient working clearance for installation of forms and proper use of tamper to the full depth of the excavation. Prevent surface water from flowing into the excavation. Thoroughly compact backfill with compacting arranged to prevent pressure between conductor, jacket, or sheath, and the end of conduit.
2. Set anchor bolts according to anchor-bolt templates furnished by the pole manufacturer.
3. Install poles as necessary to provide a permanent vertical position with the bracket arm in proper position for luminaire location.
4. After the poles have been installed, shimmed, and plumbed, grout the spaces between the pole bases and the concrete base with non-shrink concrete grout material. Provide a plastic or copper tube, of not less than 9 mm (0.375-inch) inside diameter through the grout, tight to the top of the concrete base to prevent moisture weeping from the interior of the pole.
C. Install lamps in each luminaire.
D. Adjust luminaires that require field adjustment or aiming.
3600 30th Street Revision 1
Des Moines, IA 50310
26 56 00 - 5
3.2 GROUNDING
Ground noncurrent-carrying parts of equipment, including metal poles, luminaires, mounting arms, brackets, and metallic enclosures, as specified in Section 26 05 26, GROUNDING AND BONDING FOR ELECTRICAL
SYSTEMS. Where copper grounding conductor is connected to a metal other than copper, provide specially-treated or lined connectors suitable and listed for this purpose.
3.3 ACCEPTANCE CHECKS AND TESTS
Verify operation after installing luminaires and energizing circuits.
- - - E N D - - -
File details come from the government source that posted it. Updated .