2026-0724 Addendum 02 Summary.docx

DOCX document 45 KB Posted

Attached to
Z2DA--621-22-121 Renovate Bldg. 204 for Cath Lab II - Engineering
Solicitation number
36C24926R0057
Issued by

About this file

This document is an Addendum 02 Summary that details updated drawings, specifications, and revisions for the "Renovate Bldg. 204 Cath Lab II" project at the James H. Quillen Veterans Affairs Medical Center in Mount Home, Tennessee (Project Number: 621-22-121). The addendum, dated 07-24-2026, incorporates responses to Request for Information (RFI) submissions and provides comprehensive modifications across multiple drawing sheets and specification sections. Key drawing modifications include the addition of water mist fire extinguisher legends and access panels for booms, clarification of steel member labeling, removal of frosted glass from scope, updates to phasing notes and door manufacturer information, amendments to epoxy floor details, and replacement of Uline shelves with contractor-provided M2080B wire shelves. Equipment modifications include the addition of two 10-lb bracket-mounted water mist fire extinguishers marked as contractor-provided, clarification that ceiling booms are Skytron brand, updates to equipment matrix descriptions, and marking of specific equipment as vendor-furnished or contractor-provided.

Specification modifications include the addition of three new specifications (07 41 13 - Insulated Metal Roof Panels, 10 51 26 - Plastic Lockers and Bench, 23 82 00 - Convection Heating and Cooling Units, and 28 23 00 - Video Surveillance), removal of commissioning-related specifications, formatting corrections to the operating room modular diffuser system specification, and updates to special inspection schedules and training requirements. Plumbing, mechanical, and electrical system modifications are also documented, including additions of medical gas system removals, lead-lined low air return ductwork, Avigilon camera systems across multiple phases with corresponding card readers and data drops, and associated mounting details and scheduling information. The addendum extends proposal response dates to 08-10-2026.

View the file

Other files

File Type Posted
00 01 10 - Table Of Contents 29072026.pdf PDF
07 42 13 - Insulated Metal Wall Panels.pdf PDF
07.314_AE301 - PENTHOUSE CONSTRUCTION.pdf PDF
09 54 00 - Operating Room Modular Diffuser System.pdf PDF
23 82 00 - Convection Heating and Cooling Units.pdf PDF
14.38_E600 - PARTIAL SINGLE LINE DIAGRAM.pdf PDF
14.20_EE102.2.2 - PHASE 2 ENLARGED TECH FIRE ALARM PLAN.pdf PDF
14.13_ED102.5.2 - PHASE 5 DEMOLITION TECH FIRE ALARM PLAN.pdf PDF
14.11_ED102.4.2 - PHASE 4 DEMOLITION TECH FIRE ALARM PLAN.pdf PDF
07.704_AF702.4 - PHASE FOUR FINISH PLANS.pdf PDF
13.10_MH102.4 - MECHANICAL SECOND FLOOR HVAC PLAN - PHASE 4.pdf PDF
S-102824-291.pdf PDF
01 45 35a - Schedule of SI.pdf PDF
28 05 00 - Common Work Results for Electronic Safety and Security.pdf PDF
07 41 13 - Insulated Metal Roof Panels.pdf PDF
14.26_EE102.5.2 - PHASE 5 ENLARGED TECH FIRE ALARM PLAN.pdf PDF
14.08_ED102.3.2 - PHASE 3 DEMOLITION TECH FIRE ALARM PLAN.pdf PDF
13.12_MH103 - MECHANICAL ROOF HVAC PLAN.pdf PDF
07.730_AQ732 - OVERALL EQUIPMENT PLAN.pdf PDF
FINAL COORDINATION STUDY -- 12-17-19.pdf PDF
10 51 26 - Plastic Lockers and Bench.pdf PDF
09 05 16 - Subsurface Preparation For Floor Finishes.pdf PDF
01 45 35b - Statement of SI.pdf PDF
14.29_E501 - TECHNOLOGY DETAILS.pdf PDF
14.06_ED102.2.2 - PHASE 2 DEMOLITION TECH FIRE ALARM PLAN.pdf PDF
14.04_ED102.1.2 - PHASE 1 DEMOLITION TECH FIRE ALARM PLAN.pdf PDF
14.02_E102 - SECOND FLOOR OVERALL PLAN.pdf PDF
14.00_E001 - ELECTRICAL LEGENDS AND ABBREVIATIONS.pdf PDF
07.705_AF702.5 - PHASE FIVE FINISH PLANS.pdf PDF
07.734_AQ732.4 - EQUIPMENT PLANS - PHASE FOUR.pdf PDF
11.22_PL601 - PLUMBING SCHEDULES and DIAGRAMS.pdf PDF
Revised Cath Shielding 2024.pdf PDF
Project 621-22-121 RFI Log - Mt Home Cath Lab to VA 7-24-26.xlsx XLSX spreadsheet
36C24926R0057 0003.pdf PDF
28 23 00 - Video Surveillance.pdf PDF
01 45 35 - Special Inspections.pdf PDF
36C24926R0057 0002.pdf PDF
621-22-121 Site Visit Sign in sheet.pdf PDF
2026-0629 Cath Lab II - BID specs - Add 01.pdf PDF
36C24926R0057 0001.pdf PDF
2026-0629 Cath Lab II - BID Dwgs - Add 01.pdf PDF
621-22-121 Renovate B204 for Cath Lab II - Bid Specifications.pdf PDF
36C24926R0057_1.pdf PDF
General Conditions Breakout.xlsx XLSX spreadsheet
Price Breakout Schedule.xlsx XLSX spreadsheet
Contractor EMR Certification Form.docx DOCX document
621-22-121 Renovate B204 for Cath Lab II - Bid Drawings.pdf PDF
Calculation of Contractor Self Performed Work.xlsx XLSX spreadsheet
WD TN20260191 2 Jan 2026.pdf PDF
Past_Performance_Questionnaire.docx DOCX document
Show 40 more

50 files listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

“RENOVATE BLDG 204 CATH LAB II” PROJECT FOR THE

JAMES H. QUILLEN VETERANS AFFAIRS MEDICAL CENTER (VAMC)

MT. HOME, TENNESSEE

PROJECT NUMBER: 621-22-121

UPDATED DRAWINGS, SPECIFICATIONS AND EXPLANATION OF REVISIONS

ADDENDUM NUMBER 02

07-24-2026

SUMMARY OF UPDATES

BID RFI RESPONSES UNDER SEPARATE COVER.

DRAWING MODIFICATIONS, BY SHEET

GI101

1. Added to legend water mist fire extinguisher.

GI110

1. General notes, drawing notes and infection and dust control notes updated to reflect RFI responses.

2. Note added to the General Notes: 3-week turnover before each phase

SE102.4

1. Labeled steel member just northwest of grid JJ-5.2 (HSS20x8x3/8).

SE103.1

1. Corrected section referenced in keynote 05.13 (should have said 20/S501).

AE112.4

1. Eight (8) access panels added for booms.

AE301

1. Added more information about penthouse roof BOD.

2. Adjusted details to more accurately reflect BOD condition.

AE502

1. Removed frosted glass from scope.

AE504

1. Added phasing note to general notes to reflect RFI responses.

AE601

1. Door general notes updated to reflect manufacturer.

AF702.1 - AE702.4

1. Marked DF-2 as not used.

2. Amended details of Epoxy floor.

AF702.5

1. Marked DF-2 as not used.

2. Amended details of Epoxy floor.

3. Six (6) signs clarified to be the IN-04.02 sign type.

4. Replaced Uline shelves with M2080B

AQ732

1. Two (2) total 10-lb bracket-mounted water mist fire extinguishers have been added across both Cath labs as Contractor-provided on the Equipment Schedule and Equipment Plan.

2. Equipment Matrix changes

a. Description of fire extinguisher changed to clarify VA is responsible for extinguisher itself.

b. A1000A Water Mist Fire Extinguisher added.

c. A1067 Mirror description updated to include size.

d. All Ceiling Booms M7801A-D marked as VC.

e. M7650 Defibrator marked as VV.

f. M0750 Flowmeter marked as VV.

g. Removed uline equipment and changed to contractor provided wire shelves.

AQ732.4

1. Two (2) 10-lb bracket-mounted water mist fire extinguishers have been added as Contractor-provided on the Equipment Schedule and Equipment Plan.

2. Language of booms clarified to be Skytron.

3. Replaced Uline shelves with M2080B

PD102.5

1. Added note to remove medical gas alarm panel, pressure switches, and wiring.

PL601

1. Added P-502 to Plumbing Fixture Schedule.

MH102.4

1. Keynote added to provide low air return ductwork in L222 EP Cath Lab and L220 Cath Lab with lead lining from the floor to seven feet above the floor.

MH103

1. Keynote was updated to reflect the correct units being supplied by the new chiller.

E001

1. Added Avigilon camera symbols to the symbol legend.

E102

1. Added note in room L252 about routing coax to this location.

ED102.1.2

1. Added note that each demo WAO drop has (3) cables.

ED102.2.2

1. Added note that each demo WAO drop has (3) cables.

ED102.3.2

1. Added note that each demo WAO drop has (3) cables.

ED102.4.2

1. Added note that each demo WAO drop has (3) cables.

ED102.5.2

1. Added note that each demo WAO drop has (3) cables.

EE102.1.2

1. Two(2) Dual-head Avigilon dome cameras are added.

2. Phase 1 camera schedule is added.

3. One(1) Card Readers are added.

EE102.2.2

1. Two(2) Dual-head Avigilon Dome cameras and One(1) Triple-head Avigilon Dome camera added to corridors.

2. One(1) Dual-head Avigilon Dome camera and one(1) Triple-head Avigilon Dome camera added to Waiting L202.

3. Phase 2 Camera schedule is added.

4. Three(3) Card Readers added to plan.

EE102.3.2

1. One(1) Triple-head Avigilon Dome camera is added.

2. Added Phase 3 camera schedule.

EE102.4.2

1. Two (2) Dual-head Avigilon Dome cameras are added.

2. Phase 4 camera schedule is added.

3. Added four(4) Card Readers.

4. Added two(2) Data Drops.

5. Removed antenna from door hardware schedule.

EE102.5.2

1. One(1) Card reader is added.

2. One(1) Triple-head Avigilon camera is added.

3. Phase 5 camera schedule is added.

EE102.5.3

1. One(1) dual-head camera added.

2. Added two(2) Card Readers.

3. Added phase 5.1 camera schedule.

E501

1. Wall-mounted camera detail notes, Ceiling-mounted camera detail notes, and general camera mounting detail notes added.

E600

1. Provided note related to providing ATS labeling.

SPECIFICATION MODIFICATIONS

00 01 10 – Table of Contents

1. Removed Commissioning-related specifications.

2. Added 07 41 13.

3. Added 10 51 26.

4. Added 23 82 00.

01 45 35 – Special Inspections

1. Added Schedule of Special Inspections and Statement of Special Inspections. These two files are now attached to the Specifications.

07 41 13 – Insulated Metal Roof Panels

1. Added entire specification.

09 54 00 – Operating Room Modular Diffuser System

1. Formatted to have the correct number specification number.

10 51 26 – Plastic Lockers and Bench

1. Added entire specification.

23 82 00 – Convection Heating and Cooling Units

1. Added entire specification.

28 05 00 – Common Work Results for Electronic Safety and Security

1. Training requirements modified in section 3.4.D. to show 8 hours.

28 23 00 – Video Surveillance

1. Added entire specification.