This is a mechanical roof HVAC plan drawing for a renovation project at a medical center facility in Mt. Home, Tennessee. The document depicts four floor plan phases showing the layout and installation of air handling units (AHUs), HVAC equipment, ductwork, and associated mechanical systems across multiple levels of the building.
The drawing notes specify several key mechanical requirements: installation of a metal cap on the roof curb to seal penetration (13.10); rebalancing of existing RTU to new design conditions (13.31); connection of new exhaust ductwork to existing roof ventilator (13.32); installation of a steam unit heater for the penthouse (13.33); connection of chilled water piping from a new chiller to the house system with a three-way valve (13.34); installation of a new thermostat to serve the steam unit heater and exhaust fan (13.35); and procurement and installation of a new AHU control panel with coordination for power and data connections (13.36). The design includes new roof-top air-cooled condensing units to serve AHUs 204-AHU-D and 204-AHU-E, and existing equipment modifications to serve new prep and recovery areas. The drawing is fully sprinklered and represents 100% bid documents prepared by FFE Engineering & Architecture as the architect/engineer of record.
View the file
Other files
Show 40 more
Latest 50 of 60 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
T
TTTT
SSSS
RRRR
PPPP
NNNN
MMMM
LLLL
JJJJ
5.2 4.5 3.9
(E) 204 AHU 4
204-AHU 2
204-ACCU-113.15
L-1
32"x24" RA (DN)
24"x22" SA (DN)
EF-2
204-AHU-D 204-AHU-E
24"x24" RA 32 "x
" R
A
"x
" S
A
"x
" R
A
"x
" O
A
16"x50" OA 12"x40" OA
22"x14" EA 60"x14" EA
L-2 L-3
L-4 20"x20" SA
68"x42" SA
RRRR
PPPP
NNNN
MMMM
LLLL
JJJJ
5.2 4.5 3.9
204-ACCU-1
24"x24" RA
20"x20" SA
24"x24" RA (DN)
22"x22" SA (DN)
24"x24" RA
204-AHU-D 204-AHU-E
UUUU
TTTT
SSSS
RRRR
PPPP
NNNN
MMMM
9.7 9.2 8.5 7.7 7.2 6.3
RR-2
204-AHU-1
BLDG 204 CHILLER
13.10
(E) 204-AHU-CATH 13.14
13.10
13.31
13.32
RRRR
PPPP
NNNN
MMMM
LLLL
JJJJ
5.2 4.5 3.9
204-AHU 2
204-ACCU-113.15
4" CHR
4" CHS
204-AHU-D 204-AHU-E
3/4" MPR
3/4" MPS
1 1/2" MPR DN
2" MPS DN
204-SUH-1
1 1/4" MPR
1 1/2" MPS
3/4" MPR
3/4" MPS
1 1/2" MPS 1 1/4" MPR
3" CHS
3" CHR 2 1/2" CHS
2 1/2" CHR
4" CHR
4" CHS
3/4" MPS
3/4" MPR
1 1/4" MPS
1" MPR
1 1/2" MPR
2" MPS
13.33
4" CHR
4" CHS13.34
13.35
AHU CONTROL
PANEL 13.36
KEY PLAN ENTIRE FLOOR
EXISTING BELOW
PHASE ON SHEET SHOWN
NORTH
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Date:Revisions:No.
F
Au to de sk
D oc s:
//M t H om e
VA
C at h
La b/
FF
E_
R en ov at e C at h
La b
II_
B2
_M
EP
(2
4)
.rv t
7/
/2
:2 9:
A
M
MH103
MECHANICAL ROOF HVAC PLAN
06/12/2026 KF JV
RENOVATE BLDG 204 CATH LAB II 621-22-121
MT HOME, TENNESSEE
100% BID DOCUMENTS
MT HOME, VA
MEDICAL
CENTER Approved: Owner
D R A W I N G N O T E S :
13.10 PROVIDE A METAL CAP ON TOP OF ROOF CURB TO SEAL THE PENETRATION.
13.14 EXISTING RTU TO SERVE NEW PREP AND RECOVERY AREA.
13.15 NEW ROOF TOP AIR COOLED CONDENSING UNIT TO SERVE 204-AHU-D AND 204-AHU-E.
13.31 REBALANCE THE EXISTING AHU TO THE NEW DESIGN CONDITIONS FOUND ON SHEET M602
13.32 CONNECT NEW EXHAUST DUCTWORK TO EXISTING ROOF VENTILATOR.
13.33 INSTALL STEAM UNIT HEATER TO HEAT PENTHOUSE.
13.34 CONNECT CHILLED WATER PIPING FROM NEW CHILLER TO THE HOUSE CHILLED WATER. CONNECT WITH THREE WAY
VALVE.
13.35 NEW THERMOSTAT TO SERVE STEAM UNIT HEATER AND EXHAUST FAN IN MECHANICAL PENTHOUSE.
13.36 NEW AHU CONTROL PANEL. COORDINATE WITH OTHER DISCIPLINES TO PROVIDE POWER AND DATA.
1/8" = 1'-0"1 ROOF HVAC PLAN - PHASE 1
1/8" = 1'-0"4 ROOF HVAC PLAN - PHASE 4
1/8" = 1'-0"3 ROOF HVAC PLAN - PHASE 5
1/8" = 1'-0"2 ROOF PIPING PLAN - PHASE 1
0 100% BID DOCUMENTS 06/12/2026
1 ADDENDUM 01 06/29/2026
2 ADDENDUM 02 07/24/2026
07/24/2026