07.314_AE301 - PENTHOUSE CONSTRUCTION.pdf

PDF 610 KB Posted

Attached to
Z2DA--621-22-121 Renovate Bldg. 204 for Cath Lab II - Engineering
Solicitation number
36C24926R0057
Issued by

About this file

This is an architectural drawing set for a federal medical facility construction project. The documents depict detailed construction specifications and assembly details for the MT Home, VA Medical Center, a fully sprinklered facility managed by Penthouse Construction. The project is identified as a 100% Bid Document set for a Renovate Blog 204 Cath Lab II renovation, with drawing number AE301 and revision date EI-22-121.

The specifications detail insulated metal wall and roof panel systems using Metl-Span basis of design products, including 4-inch insulated metal wall panels with 22-gauge G-90 galvanized or aluminum-zinc alloy-coated steel in stucco embossed finish, and 1.5-inch metal roof decking with 4-inch high-strength extruded polystyrene insulation. Structural components include 6-inch and 12-inch cold-formed steel studs and joists, with 5/8-inch plywood backing. Fastening specifications call for 1/4-inch pancake stitch fasteners at 24-inch maximum spacing, concealed clip attachments, butyl and urethane sealants, and 3/4-inch PVC sheet flooring with weep holes. The drawings include multiple cross-sectional details for roof and wall penetrations, curb installations, and mechanical equipment integration, with references to structural and mechanical drawings for complete coordination. The design incorporates a 1-inch to 1-foot slope for drainage and specifies manufacturer-provided flashing and curb details for all roof penetrations.

View the file

Other files

File Type Posted
00 01 10 - Table Of Contents 29072026.pdf PDF
07 42 13 - Insulated Metal Wall Panels.pdf PDF
09 54 00 - Operating Room Modular Diffuser System.pdf PDF
23 82 00 - Convection Heating and Cooling Units.pdf PDF
14.38_E600 - PARTIAL SINGLE LINE DIAGRAM.pdf PDF
14.20_EE102.2.2 - PHASE 2 ENLARGED TECH FIRE ALARM PLAN.pdf PDF
14.13_ED102.5.2 - PHASE 5 DEMOLITION TECH FIRE ALARM PLAN.pdf PDF
14.11_ED102.4.2 - PHASE 4 DEMOLITION TECH FIRE ALARM PLAN.pdf PDF
07.704_AF702.4 - PHASE FOUR FINISH PLANS.pdf PDF
13.10_MH102.4 - MECHANICAL SECOND FLOOR HVAC PLAN - PHASE 4.pdf PDF
S-102824-291.pdf PDF
10 51 26 - Plastic Lockers and Bench.pdf PDF
09 05 16 - Subsurface Preparation For Floor Finishes.pdf PDF
01 45 35b - Statement of SI.pdf PDF
14.29_E501 - TECHNOLOGY DETAILS.pdf PDF
14.06_ED102.2.2 - PHASE 2 DEMOLITION TECH FIRE ALARM PLAN.pdf PDF
14.04_ED102.1.2 - PHASE 1 DEMOLITION TECH FIRE ALARM PLAN.pdf PDF
14.02_E102 - SECOND FLOOR OVERALL PLAN.pdf PDF
14.00_E001 - ELECTRICAL LEGENDS AND ABBREVIATIONS.pdf PDF
07.705_AF702.5 - PHASE FIVE FINISH PLANS.pdf PDF
07.734_AQ732.4 - EQUIPMENT PLANS - PHASE FOUR.pdf PDF
11.22_PL601 - PLUMBING SCHEDULES and DIAGRAMS.pdf PDF
Revised Cath Shielding 2024.pdf PDF
Project 621-22-121 RFI Log - Mt Home Cath Lab to VA 7-24-26.xlsx XLSX spreadsheet
36C24926R0057 0003.pdf PDF
01 45 35a - Schedule of SI.pdf PDF
28 05 00 - Common Work Results for Electronic Safety and Security.pdf PDF
07 41 13 - Insulated Metal Roof Panels.pdf PDF
14.26_EE102.5.2 - PHASE 5 ENLARGED TECH FIRE ALARM PLAN.pdf PDF
14.08_ED102.3.2 - PHASE 3 DEMOLITION TECH FIRE ALARM PLAN.pdf PDF
13.12_MH103 - MECHANICAL ROOF HVAC PLAN.pdf PDF
07.730_AQ732 - OVERALL EQUIPMENT PLAN.pdf PDF
FINAL COORDINATION STUDY -- 12-17-19.pdf PDF
28 23 00 - Video Surveillance.pdf PDF
01 45 35 - Special Inspections.pdf PDF
00 01 10 - Table Of Contents.pdf PDF
36C24926R0057 0002.pdf PDF
621-22-121 Site Visit Sign in sheet.pdf PDF
2026-0629 Cath Lab II - BID specs - Add 01.pdf PDF
36C24926R0057 0001.pdf PDF
2026-0629 Cath Lab II - BID Dwgs - Add 01.pdf PDF
621-22-121 Renovate B204 for Cath Lab II - Bid Specifications.pdf PDF
36C24926R0057_1.pdf PDF
General Conditions Breakout.xlsx XLSX spreadsheet
621-22-121 Renovate B204 for Cath Lab II - Bid Drawings.pdf PDF
Price Breakout Schedule.xlsx XLSX spreadsheet
Contractor EMR Certification Form.docx DOCX document
Calculation of Contractor Self Performed Work.xlsx XLSX spreadsheet
WD TN20260191 2 Jan 2026.pdf PDF
Past_Performance_Questionnaire.docx DOCX document
Show 40 more

50 files listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

FLUTE CLOSURE STRIP (1)

PER PANEL (IF REQUIRED)

SET IN URETHANE SEALANT

FLASHING SEALANT TAPE

LL (1/4"-14 x7/8") HWH TYPE 1 SELF

DRILLING LAP SCREW W/BN

WASHER @ 8"o.c.

EAVE TRIM

EXPANDABLE FOAM INSULATION

(NOT BY PANEL MANUFACTURER)

LONG LIFE (1/4"-14 x7/8") HWH TYPE 1

SELF DRILLING LAP SCREW

W/BONDED NEOPRENE WASHER @

EACH HIGH MESA

14 GA. 4 HOLE CF CLIP

1/4" HWH FASTENERS

CONTINUOUS BUTYL SEALANT WITH

MARRIAGE BEAD TO PANEL JOINT

SEALANT

1/4" HWH FASTENERS

CFR PANEL CLIP @ EACH PANEL

SIDELAP

CLIP SEALANT

6"

3"

4 1/2" 3 1/2"

14 GA. 4 HOLE CF CLIP

1/4" HWH FASTENERS

CONTINUOUS BUTYL SEALANT WITH

MARRIAGE BEAD TO PANEL JOINT

SEALANT

1/4" HWH FASTENERS

CFR PANEL CLIP @ EACH PANEL

SIDELAP

CLIP SEALANT

RIDGE CLOSURE

BUTYL TAPE SEALANT

LL (1/4"-14 x7/8") HWH TYPE 1 SELF

DRILLING LAP SCREW W/BN

WASHER @ 6"o.c.

FLUTE CLOSURE STRIP (1)

PER PANEL (IF REQUIRED)

SET IN URETHANE SEALANT

FLASHING SEALANT TAPE

(1/4"-14 x7/8") HWH TYPE 1 SELF DRILLING LAP SCREW @ 8"o.c.

HIGH EAVE TRIM

EXPANDABLE FOAM INSULATION

(NOT BY PANEL MANUFACTURER)

BACK-UP PLATE FACTORY

INSTALLED @ EACH HIGH

MESA, 4"o.c.

1/4-14 x 1-1/2" HWH TYPE 2, W/OUT WASHER @ EACH

BACK-UP PLATE 4"o.c.

BUTYL TAPE SEALANT

BUTYL TAPE SEALANT

@ SIDE JOINTS

LL 1/4-14 x 7/8" HWH TYPE 1, SELF DRILLING LAP SCREW

W/BN-WASHER @ 8"o.c.

BUTYL TAPE SEALANT

CONTINUOUS BUTYL SEALANT

1/4" HWH FASTENERS

14 GA. PANEL CLIP

FLASHING SEALANT TAPE

1/4-14 x 7/8" HWH TYPE 1, SELF DRILLING LAP SCREW

W/BN-WASHER @ 8"o.c.

FLUTE PLUG STRIP (1) PER PANEL

(IF REQUIRED)

SET IN URETHANE SEALANT

EXPANDABLE FOAM INSULATION

(NOT BY PANEL MANUFACTURER)

RAKE TRIM

1/4-14 HWH TYPE 3, W/BN WASHER

@ 12"o.c.

RAKE CLOSURE

URETHANE SEALANT.

1/4" PANCAKE STITCH

FASTENER @ 24"o.c. MAX.

BUTYL SEALANT.

1 1/2" METAL ROOF DECK

4" HIGH STRENGTH EXTRUDED POLYSTYRENE

AE301

AE301

WF BEAM. SEE STRUCTURAL DRAWINGS.

STUB POST. SEE STRUCTURAL DRAWINGS.

4" INSULATED METAL WALL

PANELS.

BASIS OF DESIGN METL-SPAN CF

MESA INSULATED WALL PANELS

GUAGE: 22 GUAGE

MATERIAL: G-90 GALVANIZED

COATED STEEL OR ALUMINUM-

ZINC ALLOY-COATED STEEL

FINISH: STUCCO EMBOSSED

FASTENERS: CONCEALED CLIP

ATTACHMENT

6" COLD-FORMED STEEL STUDS - REFER TO STRUCTURAL

1/4" PANCAKE STITCH FASTENER

@ 24"o.c. MAX.

BUTYL SEALANT.

SLOPE 1" : 1'-0"

3/4" PVC SHEET FLOORING

FIELD DRILL 3/8" MIN.

WEEP HOLES @36"o.c.

BUTYL SEALANT.

FIELD DRILL 3/8" MIN.

WEEP HOLES @36"o.c.

BASE EXTRUSION.

URETHANE SEALANT.

BUTYL SEALANT.

REFER TO MECHANICAL DRAWINGS

FOR MECHANICAL EQUIPMENT

REFER TO MECHANICAL DRAWINGS

FOR MECHANICAL EQUIPMENT

CURB PER MANUFACTURE'S DRAWINGS

CURB PER MANUFACTURE'S DRAWINGS

REFER TO MECHANICAL DRAWINGS

FOR MECHANICAL EQUIPMENT

ALUMINUM CURB SURROUNDING ROOF

PENETRATION. REFER TO MANUFACTURES

DRAWINGS FOR ROOF PENETRATION FLASHING

BASIS OF DESIGN METL-SPAN

CFR INSULATED METAL ROOF STANDING SEAM PANEL

BASIS OF DESIGN: METL-SPAN

COLOR: DARK GRAY METALLIC

GAUGE: 22 GAUGE

MATERIAL: G-90 GALVANIZED COATED STEEL OR

ALUMINUM-ZINC ALLOY-COATED STEEL

FINISH: STUCCO EMBOSSED

T/ROOF SLAB

0'-0"

T/LOW WALL

18'-6"

T/HIGH WALL

20'-6 5/8"

12" COLD-FORMED STEEL JOISTS - REFER TO STRUCTURAL

T/STEEL

5'-0"

REFER TO MANUFACTURES DRAWINGS

FOR ROOF PENETRATION FLASHING

BASIS OF DESIGN METL-SPAN

AE301

AE301

5/8" PLYWOOD

INSULATED METAL WALL PANELS.

6" COLD-FORMED STEEL STUDS - SEE STRUCTURALLY

4" INSULATED METAL ROOF PANELS.

AE301

T/ROOF SLAB

0'-0"

T/WALL

SLOPES

6" BOX HEADER.

1 1/4" METAL ROOF DECK

4" HIGH STRENGTH EXTRUDED POLYSTYRENE

3/4" PVC SHEET FLOORING

1" GALVANIZED STEEL GRATE FLOORING

1 3/16" BAR SPACING 4" CROSS BAR SPACING

HOLLOW METAL DOOR TO PENTHOUSE

T/STEEL

5'-0"

CLOSER STRIP AND FLASHING WITH DRIP

AE301

STUB POST BEYOND

EQ

EQ

PROVIDE GALVANIZED STEEL PIPE 1.5"

DIAMETER THROUGHOUT

" F

RO

M

W

AL

KI

NG

S

UR

FA

CE

SPACE POSTS AT 3'-6" MAX

TOE PL. 1/4"x4" CONTINUOUS

T/ GRATING

0'-0"

L4x3x3/8

3/16

3/16FULL

LENGTH (2) 3/4" DIA BOLTS

BEAM

PREFABRICATED LANDING FASTENED

TO PENTHOUSE

9 R

IS

ER

S

1/2 " E

AC

H

5'- 0 3

/4" V

.I.F

T/ROOF SLAB

0'-0"

8 LANDINGS @ 11" EACH

7'-6" 5'-0"

11"

6 3 /4"

T/METAL GRATE FLOOR

5'-0 3/4"

RAILING ON BOTH SIDES OF STAIR -

REFER TYPICAL EXTERIOR RAIL

DETAIL FOR REQUIREMENTS

PREFABRICATED METAL STAIR

PROVIDE BASE AND

FLASHING PER

30" TYP.

/3 AE131

1" GALVANIZED STEEL GRATE FLOORING

1 3/16" BAR SPACING 4" CROSS BAR SPACING

AE301

PREFABRICATED LANDING

STRUCTURE

S501

T/ROOF SLAB

0'-0"

PIPE PENETRATION

CAULK GRADE SEALANT

STAINLESS STEEL CLAMP

BONDING ADHESIVE

SPLIT BOOT

TIE COVERBOARD INTO EXISTING

EXISTING ROOF DECK/

SUBSTRATE

FOAM FILLED POCKET

MIN 1"

PIPE INSULATION AND INSULATION

JACKET INSTALLED OVER FLASHING

(SHOWN DASHED)

TIE INTO EXISTING ROOF

INSULATION

OVERLAP MEMBRANE WITH EXISTING

8"

ICE GUARD THRESHOLD

3/8 "1 1

/8"

1 3/4"

T/ROOF SLAB

0'-0"

FASTEN REBAR INTO EXISTING

CONCRETE AND BACKFILL WITH

EPOXY

OVERLAP MEMEBRANE WITH EXISTING AND

TURN UP AROUND ANGLE

OVERLAP INSULATION INTO EXISTING

TIE COVERBOARD INTO EXISTING

1 1 /2"

M

IN

STRINGER OF EXTERIOR STAIR

FASTEN ANGLE AROUND STRINGER

BASE

CAST-IN-PLACE CONCRETE AROUND

STRINGER

3/4" = 1'-0"5 SECTION 'B' @ PENTHOUSE

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Date:Revisions:No.

F

Au to de sk

D oc s:

//M t H om e

VA

C at h

La b/

FF

E_

R en ov at e C at h

La b

II_

B2

(2

4)

.rv t

7/

/2

1:

:2

PM

AE301

PENTHOUSE CONSTRUCTION

06/12/2026 MP NM

RENOVATE BLDG 204 CATH LAB II 621-22-121

MT. HOME, TENNESSEE

100% BID DOCUMENTS

MT HOME, VA

MEDICAL

CENTER Approved: MT HOME, VA MEDICAL CENTER

1 1/2" = 1'-0"1 LOW EAVES WITH TRIM

1 1/2" = 1'-0"2 HIGH EAVES WITH TRIM

1 1/2" = 1'-0"3 RAKE WITH HIGH PROFILE TRIM

3/4" = 1'-0"4 SECTION 'A' @ PENTHOUSE

1 1/2" = 1'-0"9 TYPICAL EXTERIOR RAILING DETAIL

3/4" = 1'-0"6 STAIR @ PENTHOUSE

1 1/2" = 1'-0"10 TYPICAL FLASHING AT EXTERIOR POST

6" = 1'-0"8 THRESHOLD DETAIL

1 1/2" = 1'-0"7 STRINGER BASE

0 100% BID DOCUMENTS 06/12/2026

1 ADDENDUM 01 06/29/2026

2 ADDENDUM 02 07/24/2026

3 ADDENDUM 03 07/29/2026

File details come from the government source that posted it. Updated .