This is a basis of design document for medical gas piping systems at a healthcare facility. The document provides technical specifications and pressure loss calculations for medical air, oxygen, and medical vacuum piping networks serving multiple clinical areas including ECHO rooms (L225A through L225D) and Prep/Recovery rooms (L227C through L227E).

The design utilizes Type K copper piping with pipe sizes ranging from 1/2 inch to 1 inch diameter, supporting flow rates between 40 and 385 liters per minute depending on the gas type and location. Pressure loss calculations are provided for each piping segment with a 20 percent correction factor applied. The system includes zone valve schedules, medical gas alarm panel specifications, combination zone valve alarm panel configurations, and a comprehensive medical gas piping diagram. The document references manufacturer model OFLO PF1731WH and Canadian standard CAN STD. 0954.004EC.020. Plumbing fixture schedules are included detailing outlet requirements throughout the facility. The design indicates a fully sprinklered system designated as "100% BID DOCUMENTS" prepared for MT Home, Tennessee, with documentation dated PL601 and prepared by FFE Engineering & Architecture.

View the file

Other files

File Type Posted
07 42 13 - Insulated Metal Wall Panels.pdf PDF
00 01 10 - Table Of Contents 29072026.pdf PDF
Appendix B - HVAC CUTSHEETS.pdf PDF
07.112_AE112.2 - PHASE TWO ENLARGED PLAN.pdf PDF
36C24926R0057 0004.pdf PDF
07.314_AE301 - PENTHOUSE CONSTRUCTION.pdf PDF
07.734_AQ732.4 - EQUIPMENT PLANS - PHASE FOUR.pdf PDF
14.20_EE102.2.2 - PHASE 2 ENLARGED TECH FIRE ALARM PLAN.pdf PDF
14.11_ED102.4.2 - PHASE 4 DEMOLITION TECH FIRE ALARM PLAN.pdf PDF
14.08_ED102.3.2 - PHASE 3 DEMOLITION TECH FIRE ALARM PLAN.pdf PDF
14.04_ED102.1.2 - PHASE 1 DEMOLITION TECH FIRE ALARM PLAN.pdf PDF
14.24_EE102.4.2 - PHASE 4 ENLARGED TECH FIRE ALARM PLAN.pdf PDF
14.22_EE102.3.2 - PHASE 3 ENLARGED TECH FIRE ALARM PLAN.pdf PDF
00 00 00 - Specification Cover.pdf PDF
14.27_EE102.5.3 - PHASE 5 ENLARGED LIGHTING TECH PLAN.pdf PDF
07 41 13 - Insulated Metal Roof Panels.pdf PDF
13.12_MH103 - MECHANICAL ROOF HVAC PLAN.pdf PDF
07.704_AF702.4 - PHASE FOUR FINISH PLANS.pdf PDF
14.13_ED102.5.2 - PHASE 5 DEMOLITION TECH FIRE ALARM PLAN.pdf PDF
23 82 00 - Convection Heating and Cooling Units.pdf PDF
28 23 00 - Video Surveillance.pdf PDF
01 45 35 - Special Inspections.pdf PDF
14.16_EE102.1.2 - PHASE 1 ENLARGED TECH FIRE ALARM PLAN.pdf PDF
00 01 10 - Table Of Contents.pdf PDF
2026-0724 Addendum 02 Summary.docx DOCX document
14.26_EE102.5.2 - PHASE 5 ENLARGED TECH FIRE ALARM PLAN.pdf PDF
14.38_E600 - PARTIAL SINGLE LINE DIAGRAM.pdf PDF
07.730_AQ732 - OVERALL EQUIPMENT PLAN.pdf PDF
FINAL COORDINATION STUDY -- 12-17-19.pdf PDF
01 45 35a - Schedule of SI.pdf PDF
28 05 00 - Common Work Results for Electronic Safety and Security.pdf PDF
11.10_PD102.5 - PLUMBING SECOND FLOOR DEMOLITION PLAN PHASE 5.pdf PDF
S-102824-291.pdf PDF
09 54 00 - Operating Room Modular Diffuser System.pdf PDF
13.10_MH102.4 - MECHANICAL SECOND FLOOR HVAC PLAN - PHASE 4.pdf PDF
36C24926R0057 0003.pdf PDF
14.02_E102 - SECOND FLOOR OVERALL PLAN.pdf PDF
14.00_E001 - ELECTRICAL LEGENDS AND ABBREVIATIONS.pdf PDF
09 05 16 - Subsurface Preparation For Floor Finishes.pdf PDF
14.06_ED102.2.2 - PHASE 2 DEMOLITION TECH FIRE ALARM PLAN.pdf PDF
Revised Cath Shielding 2024.pdf PDF
Project 621-22-121 RFI Log - Mt Home Cath Lab to VA 7-24-26.xlsx XLSX spreadsheet
10 51 26 - Plastic Lockers and Bench.pdf PDF
01 45 35b - Statement of SI.pdf PDF
07.705_AF702.5 - PHASE FIVE FINISH PLANS.pdf PDF
14.29_E501 - TECHNOLOGY DETAILS.pdf PDF
621-22-121 Site Visit Sign in sheet.pdf PDF
36C24926R0057 0002.pdf PDF
2026-0629 Cath Lab II - BID specs - Add 01.pdf PDF
36C24926R0057 0001.pdf PDF
Show 40 more

Latest 50 of 60 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

PLUMBING FIXTURE SCHEDULE

MARK DESCRIPTION

WASTE PIPE VENT PIPE COLD WATER HOT WATER

WASTE

FIXTURE UNITS

COLD WATER

FIXTURE UNITS

HOT WATER

FIXTURE UNITS

WRIST BLADE

HANDLES

ELECTRIC

SENSOR REMARKS

IN [mm] IN [mm] IN [mm] IN [mm]

P-103 WATER CLOSET, WALL MOUNTED 4 [ 100 ] 2 [ 50 ] 1 [ 25 ] - - 4 10 - N/A NO 2

P-413 LAVATORY, COUNTER MOUNTED 1-1/4 [ 30 ] 1-1/2 [ 40 ] 1/2 [ 15 ] 1/2 [ 15 ] 1 1.5 1.5 YES NO 1, 4

P-414 LAVATORY, WALL MOUNTED 1-1/4 [ 30 ] 1-1/2 [ 40 ] 1/2 [ 15 ] 1/2 [ 15 ] 1 1.5 1.5 YES NO 1, 4, 6

P-418 LAVATORY, WALL MOUNTED, SENSOR 1-1/4 [ 30 ] 1-1/2 [ 40 ] 1/2 [ 15 ] 1/2 [ 15 ] 1 1.5 1.5 NO YES 1, 5, 6

P-510 SCRUB SINK, FOOT PEDAL CONTROL 1-1/2 [ 40 ] 1-1/2 [ 40 ] 1/2 [ 15 ] 1/2 [ 15 ] 3 1.5 1.5 NO NO 1

P-528 SINK, CRS, COUNTER MOUNTED 1-1/2 [ 40 ] 1-1/2 [ 40 ] 1/2 [ 15 ] 1/2 [ 15 ] 3 1.5 1.5 YES NO 1

REMARKS:

1.

2.

3.

4.

5.

6.

7.

PROVIDE WITH ASSE 1070 THERMOSTATIC MIXING VALVE TO LIMIT HOT WATER OUTPUT TEMPERATURE TO 110 DEG F. BASIS OF DESIGN WATTS LFUSG-BM2.

PROVIDE WITH 4" x 3" SANITARY REDUCER AT SANITARY DRAIN OUTLET.

PROVIDE WITH BOTTLE FILLER.

BASIS OF DESIGN FOR FAUCET WITH WRIST BLADE HANDLES ZURN Z871B4-XL.

BASIS OF DESIGN FOR BATTERY POWERED SENSOR FAUCET ZURN Z6920-XL.

PROVIDE WITH VITREOUS CHINA SHROUD. BASIS OF DESIGN AMERICAN STANDARD 0059.020EC.

WALL BOX TO SERVE COFFEE MAKERS AND ICE MAKER.

P-604 ELECTRIC WATER COOLER, HALL

HUNG, SINGLE BOWL 1-1/2 [ 40 ] 1-1/2 [ 40 ] 1/2 [ 15 ] - - 0.5 0.25 - N/A NO 3

BASIS OF DESIGN

MANUFACTURER MODEL

PROFLO PF1731WH

AMERICAN STD. 0954.004EC.020

AMERICAN STD. 0954.004EC.020

ELKAY EMABF8WSSK

P-812 1/2 [ 15 ] - -- -- -WATER SUPPLY BOX UNIT, WALL

MOUNTED --- N/A NO - -7

P-502 MOPSINK, FLOOR MOUNTED 3 [ 75 ] 1-1/2 [ 40 ] 1/2 [ 15 ] 1/2 [ 15 ] 2 3 3 YES NO - - -

ZONE VALVE SCHEDULE

MARK SERVICE

PIPE SIZE (IN) PEAK FLOW (LITERS/MIN)

OXYGEN MEDICAL

AIR

MEDICAL

VACUUM

OXYGEN MEDICAL

AIR

MEDICAL

VACUUM

ZV-2 CATH LAB L222 1/2 1/2 3/4 40 40 100

ZV-3 EP CATH LAB L220 1/2 1/2 3/4 40 40 100

ZV-4 PREP/RECOVERY ROOMS,

STRESS LABS 3/4 3/4 3/4 103 103 115

COMBINATION ZONE VALVE ALARM PANEL SCHEDULE

MARK SERVICE

PIPE SIZE (IN) PEAK FLOW (LITERS/MIN)

OXYGEN MEDICAL

AIR

MEDICAL

VACUUM

OXYGEN MEDICAL

AIR

MEDICAL

VACUUM

SERVICE INDICATOR LIGHTS

YES

TYPE OF PANEL

COMBINATION ZONE VALVE AREA ALARM PANEL

GAGES REMARKS

1.

REMARKS:

AREA ALARM SENSORS LOCATED WITHIN THE BOX ASSEMBLY.

OXYGEN LINE PRESSURE ABNORMAL

MEDICAL AIR LINE PRESSURE ABNORMAL

MEDICAL VACUUM LINE VACUUM LOW

ZV-1 ECHO ROOMS 1/2 1/2 3/4 70 70 70

MEDICAL GAS ALARM PANEL SCHEDULE

LOCATION

CATH LAB L222

SERVICE INDICATOR LIGHTS

YES

OXYGEN LINE PRESSURE ABNORMAL

TYPE OF PANEL

AREA (ZONE) ALARM PANEL

GAGES REMARKS

1, 2MEDICAL AIR LINE PRESSURE ABNORMAL

MEDICAL VACUUM LINE VACUUM LOW

1.

2.

3.

4.

REMARKS:

PROVIDE WITH REMOTE PRESSURE SWITCH SENSORS.

SERVES ZONE ASSOCIATED WITH ZV-2.

SERVES ZONE ASSOCIATED WITH ZV-3.

SERVES ZONE ASSOCIATED WITH ZV-4.

EP CATH LAB L220 YES

OXYGEN LINE PRESSURE ABNORMAL

AREA (ZONE) ALARM PANEL 1, 3MEDICAL AIR LINE PRESSURE ABNORMAL

MEDICAL VACUUM LINE VACUUM LOW

NURSE STATION L227 YES

OXYGEN LINE PRESSURE ABNORMAL

AREA (ZONE) ALARM PANEL 1, 4MEDICAL AIR LINE PRESSURE ABNORMAL

MEDICAL VACUUM LINE VACUUM LOW

MEDICAL GAS PIPING PRESSURE LOSSES - MEDICAL AIR

SEGMENT START SEGMENT END EQUIVALENT LENGTH FLOW (LPM) PIPE SIZE (IN) PRESSURE LOSS (PSI/100') PRESSURE LOSS (PSI) RUNNING PRESSURE LOSS TOTAL (PSI) 20% CORRECTION FACTOR* (PSI)

ECHO 1 - L225A ECHO 2 - L225B TEE 35 40 1/2 0.032 0.0112 0.0112 0.01344

ECHO 2 - L225B TEE ECHO 3 - L225C TEE 15 50 1/2 0.047 0.00705 0.01825 0.0219

ECHO 3 - L225C TEE ECHO 4 - L225D TEE 15 60 1/2 0.064 0.0096 0.02785 0.03342

ECHO 4 - L225D TEE ZV-1 70 70 1/2 0.083 0.0581 0.08595 0.10314

ZV-1 ZV-3 TEE 20 70 1/2 0.083 0.0166 0.10255 0.12306

ZV-3 TEE ZV-2 TEE 60 110 1/2 0.19 0.114 0.21655 0.25986

ZV-2 TEE ZV-4 TEE 40 150 1/2 0.33 0.132 0.34855 0.41826

ZV-4 TEE EXISTING RISER 100 253 3/4 0.145 0.145 0.49355 0.59226

*20% CORRECTION FACTOR FOR TYPE K COPPER PIPING

MEDICAL GAS PIPING PRESSURE LOSSES - OXYGEN

SEGMENT START SEGMENT END EQUIVALENT LENGTH FLOW (LPM) PIPE SIZE (IN) PRESSURE LOSS (PSI/100') PRESSURE LOSS (PSI) RUNNING PRESSURE LOSS TOTAL (PSI) 20% CORRECTION FACTOR* (PSI)

ECHO 1 - L225A ECHO 2 - L225B TEE 35 40 1/2 0.035 0.01225 0.01225 0.0147

ECHO 2 - L225B TEE ECHO 3 - L225C TEE 15 50 1/2 0.051 0.00765 0.0199 0.02388

ECHO 3 - L225C TEE ECHO 4 - L225D TEE 15 60 1/2 0.07 0.0105 0.0304 0.03648

ECHO 4 - L225D TEE ZV-1 70 70 1/2 0.092 0.0644 0.0948 0.11376

ZV-1 ZV-3 TEE 20 70 1/2 0.092 0.0184 0.1132 0.13584

ZV-3 TEE ZV-2 TEE 60 110 1/2 0.21 0.126 0.2392 0.28704

ZV-2 TEE ZV-4 TEE 40 150 1/2 0.35 0.14 0.3792 0.45504

ZV-4 TEE EXISTING RISER 100 253 3/4 0.16 0.16 0.5392 0.64704

*20% CORRECTION FACTOR FOR TYPE K COPPER PIPING

MEDICAL GAS PIPING PRESSURE LOSSES - MEDICAL VACUUM

SEGMENT START SEGMENT END EQUIVALENT LENGTH FLOW (LPM) PIPE SIZE (IN) PRESSURE LOSS (PSI/100') PRESSURE LOSS (PSI) RUNNING PRESSURE LOSS TOTAL (PSI) 20% CORRECTION FACTOR* (PSI)

ECHO 1 - L225A ECHO 2 - L225B TEE 35 40 3/4 0.16 0.056 0.056 0.0672

ECHO 2 - L225B TEE ECHO 3 - L225C TEE 15 50 3/4 0.19 0.0285 0.0845 0.1014

ECHO 3 - L225C TEE ECHO 4 - L225D TEE 15 60 3/4 0.3 0.045 0.1295 0.1554

ECHO 4 - L225D TEE ZV-1 70 70 3/4 0.4 0.28 0.4095 0.4914

ZV-1 ZV-3 TEE 20 70 3/4 0.4 0.08 0.4895 0.5874

ZV-3 TEE ZV-2 TEE 60 170 1 0.52 0.312 0.8015 0.9618

ZV-2 TEE ZV-4 TEE 40 270 1 1.2 0.48 1.2815 1.5378

ZV-4 TEE EXISTING RISER 100 385 1 0.8 0.8 2.0815 2.4978

*20% CORRECTION FACTOR FOR TYPE K COPPER PIPING

(E) 1 1/4" MV

(E) 3/4" MA

(E) 3/4" O

ZV-4

PREP/REC SIX L227F

(1) MA, (1) O, (1) MV

OUTLETS

PREP/REC FIVE L227E

(1) MA, (1) O, (1) MV

OUTLETS

STRESS LAB L230

(2) MA, (2) O, (1) MV

OUTLETS

STRESS LAB L230

(2) MA, (2) O, (1) MV

OUTLETS

PREP/REC ONE L227A

(1) MA, (1) O, (1) MV

OUTLETS

PREP/REC TWO L227B

(1) MA, (1) O, (1) MV

OUTLETS

PREP/REC THREE L227C

(1) MA, (1) O, (1) MV

OUTLETS

PREP/REC FOUR L227D

(1) MA, (1) O, (1) MV

OUTLETS

PHASE 5

PHASE 5 PHASE 5

PHASE 5

PHASE 5

PHASE 5

PHASE 5 PHASE 5

TO (E) RISERS

(E) SERVICE VALVE

(TYP OF 3)

ZV-2

(E) 1" MV

(E) 3/4" MA

(E) 3/4" O

3/4" MV

3/4" MA

3/4" O

3/4" MV

3/4" MA

3/4" O

3/4" MV

1/2" MA

1/2" O

P

P

P

AREA ALARM

PANEL

PRESSURE SWITCH

(TYP OF 3)

3/4" MV

1/2" MA

1/2" O

3/4" MV

1/2" MA

1/2" O

3/4" MV

1/2" MA

1/2" O

PHASE 5

PHASE 4

(E) SERVICE VALVE

(TYP OF 3)

SERVICE VALVE

(TYP OF 3)

CATH LAB L222

(1) MA, (2) O, (5) MV

OUTLETS

PHASE 4

(E) 1" MV

(E) 1/2" MA

(E) 1/2" O

P

P

P PRESSURE SWITCH

(TYP OF 3)

1/2" O

1/2" MA

3/4" MV

1/2" O

1/2" MA

3/4" MV

AREA ALARM

PANEL

(E) 1" MV

(E) 1/2" MA

(E) 1/2" O

ZV-3

PHASE 41/2" O

1/2" MA

3/4" MV

P

P

P PRESSURE SWITCH

(TYP OF 3)3/4" MV

1/2" MA

1/2" O

EP CATH LAB L220

(1) MA, (2) O, (5) MV

OUTLETS

PHASE 4

1/2" O

1/2" MA

3/4" MV

AREA ALARM

PANEL

SERVICE VALVE

(TYP OF 3)

ZV-1

PHASE 3

1/2" O

1/2" MA

3/4" MV

COMBO

ZV/ALARM

ECHO FOUR L225D

(1) MA, (1) O, (1) MV

OUTLETS

PHASE 3

ECHO THREE L225C

(1) MA, (1) O, (1) MV

OUTLETS

PHASE 3

ECHO TWO L225B

(1) MA, (1) O, (1) MV

OUTLETS

PHASE 3

ECHO ONE L225A

(1) MA, (1) O, (1) MV

OUTLETS

PHASE 5

1/2" O

1/2" MA

3/4" MV

1/2" O

1/2" MA

3/4" MV

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Date:Revisions:No.

F

Au to de sk

D oc s:

//M t H om e

VA

C at h

La b/

FF

E_

R en ov at e C at h

La b

II_

B2

_M

EP

(2

4)

.rv t

7/

/2

9:

:3

AM

PL601

PLUMBING SCHEDULES &

DIAGRAMS

06/12/2026 PP GP

RENOVATE BLDG 204 CATH LAB II 621-22-121

MT HOME, TENNESSEE

100% BID DOCUMENTS

MT HOME, VA

MEDICAL

CENTER Approved: Owner

MEDICAL GAS PIPING DIAGRAM

0 100% BID DOCUMENTS 06/12/2026

1 ADDENDUM 01 06/29/2026

2 ADDENDUM 02 07/24/2026

06/12/2026

File details come from the government source that posted it. Updated .