11.22_PL601 - PLUMBING SCHEDULES and DIAGRAMS.pdf
PDF 332 KB Posted
- Solicitation number
- 36C24926R0057
About this file
This is a basis of design document for medical gas piping systems at a healthcare facility. The document provides technical specifications and pressure loss calculations for medical air, oxygen, and medical vacuum piping networks serving multiple clinical areas including ECHO rooms (L225A through L225D) and Prep/Recovery rooms (L227C through L227E).
The design utilizes Type K copper piping with pipe sizes ranging from 1/2 inch to 1 inch diameter, supporting flow rates between 40 and 385 liters per minute depending on the gas type and location. Pressure loss calculations are provided for each piping segment with a 20 percent correction factor applied. The system includes zone valve schedules, medical gas alarm panel specifications, combination zone valve alarm panel configurations, and a comprehensive medical gas piping diagram. The document references manufacturer model OFLO PF1731WH and Canadian standard CAN STD. 0954.004EC.020. Plumbing fixture schedules are included detailing outlet requirements throughout the facility. The design indicates a fully sprinklered system designated as "100% BID DOCUMENTS" prepared for MT Home, Tennessee, with documentation dated PL601 and prepared by FFE Engineering & Architecture.
View the file
Other files
Show 40 more
Latest 50 of 60 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PLUMBING FIXTURE SCHEDULE
MARK DESCRIPTION
WASTE PIPE VENT PIPE COLD WATER HOT WATER
WASTE
FIXTURE UNITS
COLD WATER
FIXTURE UNITS
HOT WATER
FIXTURE UNITS
WRIST BLADE
HANDLES
ELECTRIC
SENSOR REMARKS
IN [mm] IN [mm] IN [mm] IN [mm]
P-103 WATER CLOSET, WALL MOUNTED 4 [ 100 ] 2 [ 50 ] 1 [ 25 ] - - 4 10 - N/A NO 2
P-413 LAVATORY, COUNTER MOUNTED 1-1/4 [ 30 ] 1-1/2 [ 40 ] 1/2 [ 15 ] 1/2 [ 15 ] 1 1.5 1.5 YES NO 1, 4
P-414 LAVATORY, WALL MOUNTED 1-1/4 [ 30 ] 1-1/2 [ 40 ] 1/2 [ 15 ] 1/2 [ 15 ] 1 1.5 1.5 YES NO 1, 4, 6
P-418 LAVATORY, WALL MOUNTED, SENSOR 1-1/4 [ 30 ] 1-1/2 [ 40 ] 1/2 [ 15 ] 1/2 [ 15 ] 1 1.5 1.5 NO YES 1, 5, 6
P-510 SCRUB SINK, FOOT PEDAL CONTROL 1-1/2 [ 40 ] 1-1/2 [ 40 ] 1/2 [ 15 ] 1/2 [ 15 ] 3 1.5 1.5 NO NO 1
P-528 SINK, CRS, COUNTER MOUNTED 1-1/2 [ 40 ] 1-1/2 [ 40 ] 1/2 [ 15 ] 1/2 [ 15 ] 3 1.5 1.5 YES NO 1
REMARKS:
1.
2.
3.
4.
5.
6.
7.
PROVIDE WITH ASSE 1070 THERMOSTATIC MIXING VALVE TO LIMIT HOT WATER OUTPUT TEMPERATURE TO 110 DEG F. BASIS OF DESIGN WATTS LFUSG-BM2.
PROVIDE WITH 4" x 3" SANITARY REDUCER AT SANITARY DRAIN OUTLET.
PROVIDE WITH BOTTLE FILLER.
BASIS OF DESIGN FOR FAUCET WITH WRIST BLADE HANDLES ZURN Z871B4-XL.
BASIS OF DESIGN FOR BATTERY POWERED SENSOR FAUCET ZURN Z6920-XL.
PROVIDE WITH VITREOUS CHINA SHROUD. BASIS OF DESIGN AMERICAN STANDARD 0059.020EC.
WALL BOX TO SERVE COFFEE MAKERS AND ICE MAKER.
P-604 ELECTRIC WATER COOLER, HALL
HUNG, SINGLE BOWL 1-1/2 [ 40 ] 1-1/2 [ 40 ] 1/2 [ 15 ] - - 0.5 0.25 - N/A NO 3
BASIS OF DESIGN
MANUFACTURER MODEL
PROFLO PF1731WH
AMERICAN STD. 0954.004EC.020
AMERICAN STD. 0954.004EC.020
ELKAY EMABF8WSSK
P-812 1/2 [ 15 ] - -- -- -WATER SUPPLY BOX UNIT, WALL
MOUNTED --- N/A NO - -7
P-502 MOPSINK, FLOOR MOUNTED 3 [ 75 ] 1-1/2 [ 40 ] 1/2 [ 15 ] 1/2 [ 15 ] 2 3 3 YES NO - - -
ZONE VALVE SCHEDULE
MARK SERVICE
PIPE SIZE (IN) PEAK FLOW (LITERS/MIN)
OXYGEN MEDICAL
AIR
MEDICAL
VACUUM
OXYGEN MEDICAL
AIR
MEDICAL
VACUUM
ZV-2 CATH LAB L222 1/2 1/2 3/4 40 40 100
ZV-3 EP CATH LAB L220 1/2 1/2 3/4 40 40 100
ZV-4 PREP/RECOVERY ROOMS,
STRESS LABS 3/4 3/4 3/4 103 103 115
COMBINATION ZONE VALVE ALARM PANEL SCHEDULE
MARK SERVICE
PIPE SIZE (IN) PEAK FLOW (LITERS/MIN)
OXYGEN MEDICAL
AIR
MEDICAL
VACUUM
OXYGEN MEDICAL
AIR
MEDICAL
VACUUM
SERVICE INDICATOR LIGHTS
YES
TYPE OF PANEL
COMBINATION ZONE VALVE AREA ALARM PANEL
GAGES REMARKS
1.
REMARKS:
AREA ALARM SENSORS LOCATED WITHIN THE BOX ASSEMBLY.
OXYGEN LINE PRESSURE ABNORMAL
MEDICAL AIR LINE PRESSURE ABNORMAL
MEDICAL VACUUM LINE VACUUM LOW
ZV-1 ECHO ROOMS 1/2 1/2 3/4 70 70 70
MEDICAL GAS ALARM PANEL SCHEDULE
LOCATION
CATH LAB L222
SERVICE INDICATOR LIGHTS
YES
OXYGEN LINE PRESSURE ABNORMAL
TYPE OF PANEL
AREA (ZONE) ALARM PANEL
GAGES REMARKS
1, 2MEDICAL AIR LINE PRESSURE ABNORMAL
MEDICAL VACUUM LINE VACUUM LOW
1.
2.
3.
4.
REMARKS:
PROVIDE WITH REMOTE PRESSURE SWITCH SENSORS.
SERVES ZONE ASSOCIATED WITH ZV-2.
SERVES ZONE ASSOCIATED WITH ZV-3.
SERVES ZONE ASSOCIATED WITH ZV-4.
EP CATH LAB L220 YES
OXYGEN LINE PRESSURE ABNORMAL
AREA (ZONE) ALARM PANEL 1, 3MEDICAL AIR LINE PRESSURE ABNORMAL
MEDICAL VACUUM LINE VACUUM LOW
NURSE STATION L227 YES
OXYGEN LINE PRESSURE ABNORMAL
AREA (ZONE) ALARM PANEL 1, 4MEDICAL AIR LINE PRESSURE ABNORMAL
MEDICAL VACUUM LINE VACUUM LOW
MEDICAL GAS PIPING PRESSURE LOSSES - MEDICAL AIR
SEGMENT START SEGMENT END EQUIVALENT LENGTH FLOW (LPM) PIPE SIZE (IN) PRESSURE LOSS (PSI/100') PRESSURE LOSS (PSI) RUNNING PRESSURE LOSS TOTAL (PSI) 20% CORRECTION FACTOR* (PSI)
ECHO 1 - L225A ECHO 2 - L225B TEE 35 40 1/2 0.032 0.0112 0.0112 0.01344
ECHO 2 - L225B TEE ECHO 3 - L225C TEE 15 50 1/2 0.047 0.00705 0.01825 0.0219
ECHO 3 - L225C TEE ECHO 4 - L225D TEE 15 60 1/2 0.064 0.0096 0.02785 0.03342
ECHO 4 - L225D TEE ZV-1 70 70 1/2 0.083 0.0581 0.08595 0.10314
ZV-1 ZV-3 TEE 20 70 1/2 0.083 0.0166 0.10255 0.12306
ZV-3 TEE ZV-2 TEE 60 110 1/2 0.19 0.114 0.21655 0.25986
ZV-2 TEE ZV-4 TEE 40 150 1/2 0.33 0.132 0.34855 0.41826
ZV-4 TEE EXISTING RISER 100 253 3/4 0.145 0.145 0.49355 0.59226
*20% CORRECTION FACTOR FOR TYPE K COPPER PIPING
MEDICAL GAS PIPING PRESSURE LOSSES - OXYGEN
SEGMENT START SEGMENT END EQUIVALENT LENGTH FLOW (LPM) PIPE SIZE (IN) PRESSURE LOSS (PSI/100') PRESSURE LOSS (PSI) RUNNING PRESSURE LOSS TOTAL (PSI) 20% CORRECTION FACTOR* (PSI)
ECHO 1 - L225A ECHO 2 - L225B TEE 35 40 1/2 0.035 0.01225 0.01225 0.0147
ECHO 2 - L225B TEE ECHO 3 - L225C TEE 15 50 1/2 0.051 0.00765 0.0199 0.02388
ECHO 3 - L225C TEE ECHO 4 - L225D TEE 15 60 1/2 0.07 0.0105 0.0304 0.03648
ECHO 4 - L225D TEE ZV-1 70 70 1/2 0.092 0.0644 0.0948 0.11376
ZV-1 ZV-3 TEE 20 70 1/2 0.092 0.0184 0.1132 0.13584
ZV-3 TEE ZV-2 TEE 60 110 1/2 0.21 0.126 0.2392 0.28704
ZV-2 TEE ZV-4 TEE 40 150 1/2 0.35 0.14 0.3792 0.45504
ZV-4 TEE EXISTING RISER 100 253 3/4 0.16 0.16 0.5392 0.64704
*20% CORRECTION FACTOR FOR TYPE K COPPER PIPING
MEDICAL GAS PIPING PRESSURE LOSSES - MEDICAL VACUUM
SEGMENT START SEGMENT END EQUIVALENT LENGTH FLOW (LPM) PIPE SIZE (IN) PRESSURE LOSS (PSI/100') PRESSURE LOSS (PSI) RUNNING PRESSURE LOSS TOTAL (PSI) 20% CORRECTION FACTOR* (PSI)
ECHO 1 - L225A ECHO 2 - L225B TEE 35 40 3/4 0.16 0.056 0.056 0.0672
ECHO 2 - L225B TEE ECHO 3 - L225C TEE 15 50 3/4 0.19 0.0285 0.0845 0.1014
ECHO 3 - L225C TEE ECHO 4 - L225D TEE 15 60 3/4 0.3 0.045 0.1295 0.1554
ECHO 4 - L225D TEE ZV-1 70 70 3/4 0.4 0.28 0.4095 0.4914
ZV-1 ZV-3 TEE 20 70 3/4 0.4 0.08 0.4895 0.5874
ZV-3 TEE ZV-2 TEE 60 170 1 0.52 0.312 0.8015 0.9618
ZV-2 TEE ZV-4 TEE 40 270 1 1.2 0.48 1.2815 1.5378
ZV-4 TEE EXISTING RISER 100 385 1 0.8 0.8 2.0815 2.4978
*20% CORRECTION FACTOR FOR TYPE K COPPER PIPING
(E) 1 1/4" MV
(E) 3/4" MA
(E) 3/4" O
ZV-4
PREP/REC SIX L227F
(1) MA, (1) O, (1) MV
OUTLETS
PREP/REC FIVE L227E
(1) MA, (1) O, (1) MV
OUTLETS
STRESS LAB L230
(2) MA, (2) O, (1) MV
OUTLETS
STRESS LAB L230
(2) MA, (2) O, (1) MV
OUTLETS
PREP/REC ONE L227A
(1) MA, (1) O, (1) MV
OUTLETS
PREP/REC TWO L227B
(1) MA, (1) O, (1) MV
OUTLETS
PREP/REC THREE L227C
(1) MA, (1) O, (1) MV
OUTLETS
PREP/REC FOUR L227D
(1) MA, (1) O, (1) MV
OUTLETS
PHASE 5
PHASE 5 PHASE 5
PHASE 5
PHASE 5
PHASE 5
PHASE 5 PHASE 5
TO (E) RISERS
(E) SERVICE VALVE
(TYP OF 3)
ZV-2
(E) 1" MV
(E) 3/4" MA
(E) 3/4" O
3/4" MV
3/4" MA
3/4" O
3/4" MV
3/4" MA
3/4" O
3/4" MV
1/2" MA
1/2" O
P
P
P
AREA ALARM
PANEL
PRESSURE SWITCH
(TYP OF 3)
3/4" MV
1/2" MA
1/2" O
3/4" MV
1/2" MA
1/2" O
3/4" MV
1/2" MA
1/2" O
PHASE 5
PHASE 4
(E) SERVICE VALVE
(TYP OF 3)
SERVICE VALVE
(TYP OF 3)
CATH LAB L222
(1) MA, (2) O, (5) MV
OUTLETS
PHASE 4
(E) 1" MV
(E) 1/2" MA
(E) 1/2" O
P
P
P PRESSURE SWITCH
(TYP OF 3)
1/2" O
1/2" MA
3/4" MV
1/2" O
1/2" MA
3/4" MV
AREA ALARM
PANEL
(E) 1" MV
(E) 1/2" MA
(E) 1/2" O
ZV-3
PHASE 41/2" O
1/2" MA
3/4" MV
P
P
P PRESSURE SWITCH
(TYP OF 3)3/4" MV
1/2" MA
1/2" O
EP CATH LAB L220
(1) MA, (2) O, (5) MV
OUTLETS
PHASE 4
1/2" O
1/2" MA
3/4" MV
AREA ALARM
PANEL
SERVICE VALVE
(TYP OF 3)
ZV-1
PHASE 3
1/2" O
1/2" MA
3/4" MV
COMBO
ZV/ALARM
ECHO FOUR L225D
(1) MA, (1) O, (1) MV
OUTLETS
PHASE 3
ECHO THREE L225C
(1) MA, (1) O, (1) MV
OUTLETS
PHASE 3
ECHO TWO L225B
(1) MA, (1) O, (1) MV
OUTLETS
PHASE 3
ECHO ONE L225A
(1) MA, (1) O, (1) MV
OUTLETS
PHASE 5
1/2" O
1/2" MA
3/4" MV
1/2" O
1/2" MA
3/4" MV
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Date:Revisions:No.
F
Au to de sk
D oc s:
//M t H om e
VA
C at h
La b/
FF
E_
R en ov at e C at h
La b
II_
B2
_M
EP
(2
4)
.rv t
7/
/2
9:
:3
AM
PL601
PLUMBING SCHEDULES &
DIAGRAMS
06/12/2026 PP GP
RENOVATE BLDG 204 CATH LAB II 621-22-121
MT HOME, TENNESSEE
100% BID DOCUMENTS
MT HOME, VA
MEDICAL
CENTER Approved: Owner
MEDICAL GAS PIPING DIAGRAM
0 100% BID DOCUMENTS 06/12/2026
1 ADDENDUM 01 06/29/2026
2 ADDENDUM 02 07/24/2026
06/12/2026