This is a solicitation for renovation services at the Alvin C. York VA Medical Center in Murfreesboro, TN. The Department of Veterans Affairs, through the Veterans Health Administration VISN 9, is seeking offers to renovate Ward 1B including mechanical, electrical and architectural work. Offerors should have experience with healthcare construction. The period of performance is 10 months. Pricing will be fixed-price. Subcontracting opportunities are available for mechanical, electrical and technology disciplines. The set-aside category is SDVOSB. The response due date is April 14, 2023. Award is expected by May 2023 to begin work upon receiving notice to proceed.
View the file
Other files
Show all 48
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
HFR DESIGN, INC.
VA PROJECT # 626A4-19-101
AE RENOVATE WARD 1B
ALVIN C. YORK VAMC
3400 LEBANON PIKE
MURFREESBORO, TN 37129
04-14-2023
C O
N S
T R
U C
T
IO
N D
O C
U M
E N
T S
-1
-2
100% CONSTRUCTION DOCUMENTS
WEB: www.woldae.com
FAX: 612.237.3151
PHONE: 651.227.7773
CITY/STATE/ZIP: SAINT PAUL, MINNESOTA 55101
ADDRESS: 332 MINNESOTA STREET, SUITE W2000
EMAIL: jquam@woldae.com
DESIGNER: JILL QUAM
INTERIOR
DESIGNER:
HFR DESIGN
WEB: www.atriaxgroup.com
PHONE: 828.315.9962
CITY/STATE/ZIP: HICKORY, NC 28601
ADDRESS: 102 3RD AVENUE NE
EMAIL: ed.henson@atriaxgroup.com
PROJ. ARCHITECT: ED HENSON
ARCHITECT: ATRIAX, PLLC.
PROJECT NUMBER: 2019056
WEB: www.woldae.com
FAX: 615.370.8530
PHONE: 615.370.8500
CITY/STATE/ZIP: BRENTWOOD, TN 37027
ADDRESS: 214 CENTERVIEW DRIVE, STE 300
EMAIL: Atraylor@woldae.com
PROJ. MANAGER: ANTHONY TRAYLOR
EMAIL: rfranks@woldae.com
PROJ. ARCHITECT: RON FRANKS
ARCHITECT: HFR DESIGN
PROJECT NUMBER: 626A4-19-101
WEB: www.tennesseevalley.va.gov
PHONE: 615.8676000
CITY/STATE/ZIP: Murfreesboro, TN 37129
ADDRESS: 3400 Lebanon Road
EMAIL: hansjohnson2@va.gov
CONTACT PERSON: HANS JOHNSON
OWNER: VAMC MURFREESBORO - ALVIN C. YORK CAMPUS
PROJECT CONTACT LIST
WEB: www.tlc-engineers.com
FAX: 615.297.4554
PHONE: 615.297.4554
CITY/STATE/ZIP: Brentwood, TN 37027
ADDRESS: 12 Cadillac Drive, Suite 150
EMAIL: deron.mcintosh@tlc-eng.com
ELECTRICAL: DERON MCINTOSH
EMAIL: ted.hood@tlc-eng.com
TECHNOLOGY: TED HOOD
EMAIL: danny.thomas@tlc-eng.com
PLUMBING: DANNY THOMAS
EMAIL: steve.kemp@tlc-eng.com
MECHANICAL: STEVE KEMP
MECHANICAL,
PLUMBING, &
ELECTRICAL
ENGINEERS:
TLC
PROJECT CONTACTS (CONT)
12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554
©Copyright 2019
TLC No.:
www.tlc-engineers.com
118626
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg.
PROJECT TEAM:
Office of
Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
Department of Veterans Affairs
MURFREESBORO, TN
615.370.8500
615.370.8530 hfrdesign.com
214 Centerview Drive Suite 300 Brentwood, TN 37027
Phase
FULLY SPRINKLERED
C U s e rs \a tr a y lo r\ D o c u m e n ts
\M b o ro V
A W a rd b
R e n o a tr a y lo r2 X
N D
H .r v t
/1
/2
:2
:0
P
M
04-14-2023
626A4-19-101
GI 00.01
AE RENOVATE WARD 1BCOVER SHEET
AT
HFR Project No: 2019056
100% CONSTRUCTION
DOCUMENTS
No. Date Description
Anthony Traylor Snapshot
WINDOW TAG
ELEVATION TAG
GYPSUM BOARD
EARTH
CONCRETE
CONC. MASONRY UNITS
STEEL SECTION
FINISH WOOD
BATT INSULATION
GRAVEL FILL
DOOR TAG
HANDICAP ACCESSIBLE
SECTION INDICATOR
SHEET NUMBER
ENLARGED PLAN NUMBER
NOTE: THE DIRECTION OF THE SECTION INDICATOR'S
FLAG MAY REFLECT AN "OPPOSITE HAND" OR
"MIRRORED VIEW" OF BUILDING AND WALL SECTIONS
EQUIPMENT TAG
AA
CALLOUT
# / A ##.##
EIFS INSULATION BOARD
# / A ##.##
# / A ##.##
0000-000
EXIST DEMO NEW
PROJECT SITE
PROJECT LOCATION
12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554
©Copyright 2019
TLC No.:
www.tlc-engineers.com
118626
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg.
PROJECT TEAM:
Office of
Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
Department of Veterans Affairs
MURFREESBORO, TN
615.370.8500
615.370.8530 hfrdesign.com
214 Centerview Drive Suite 300 Brentwood, TN 37027
Phase
FULLY SPRINKLERED
C U s e rs \a tr a y lo r\ D o c u m e n ts
\M b o ro V
A W a rd b
R e n o a tr a y lo r2 X
N D
H .r v t
/1
/2
:2
:0
P
M
04-14-2023
626A4-19-101
GI 01.01
AE RENOVATE WARD 1BGENERAL DATA
AT
HFR Project No: 2019056
100% CONSTRUCTION
DOCUMENTS
SYMBOL LEGEND
MECH. MECHANICAL
MED. MEDICAL
MED. CAB. MEDICAL CABINET
MFR. MANUFACTURER
MGMT. MANAGEMENT
MH MANHOLE
MIN. MINIMUM
MIR. MIRROR
MISC. MISCELLANEOUS
MR/S MIRROR WITH SHELF
MTD. MOUNTED
MTL. METAL
N.I.C. NOT IN CONTRACT
NOM. NOMINAL
O.C. ON CENTER
O.D. OVERFLOW DRAIN
O.F.O.I. OWNER FURNISHED / OWNER
INSTALLED
OPER. OPERATIONS
OPNG. OPENING
OPP. OPPOSITE
P.P.G. POLISHED PLATE GLASS
P.R.V. POWER ROOF VENTILATOR
P.T. PRESSURE TREATED
PART'N(S) PARTITION(S)
PLAS. PLASTER
PLAS. LAM. PLASTIC LAMINATE
PLYWD. PLYWOOD
PREP. PREPARATION
PREV. PREVENTIVE
PROF. PROFESSIONAL
PTD PAPER TOWEL DISPENSER
Q.T. QUARRY TILE
R. RADIUS
R.D. ROOF DRAIN
R.O. ROUGH OPENING
RECEPT. RECEPTION
RECOV. RECOVERY
REF. REFRIGERATOR
REF. REFER, REFERENCE
REINF. REINFORCING, REINFORCED
REQ'D REQUIRED
RM. ROOM
S SEALANT
S.&R. SHELF AND ROD
SAN. SANITARY
SB SPLASHBLOCK
SCHED. SCHEDULE
SD SOAP DISPENSER
SEC. SECTION, SECRETARY
SGNL. SIGNAL
SHLVG. SHELVING
SIM. SIMILAR
SPECS. SPECIFICATIONS
SS STAINLESS STEEL
STD. STANDARD
STL. STEEL
STO. STORAGE
STRUCT. STRUCTURAL
SYS. SYSTEM
T./TOIL./TL
T.
TOILET
T.O.S. TOP OF STEEL
T.O.W. TOP OF WALL
TB TOWEL BAR
TBL. TABLE
TECH. TECHNICIAN
TEL. TELEPHONE
THK. THICK
THKNS. THICKNESS
TPD TOILET PAPER DISPENSER
TRAIN. TRAINING
TRANS. TRANSFORMER
TREAT. TREATMENT
TYP. TYPICAL
U.N.O. UNLESS NOTED OTHERWISE
UNEXP. UNEXPOSED
VC VA FURNISHED/CONTRACTOR
INSTALLED
VEST. VESTIBULE
VV VA FURNISHED/VA INSTALLED
W.H.F.E. WALL HUNG FIRE
EXTINGUISHER
W/ WITH
WC/W.C. WATER CLOSET
WD. WOOD
WP WATERPROOF(ING)
WP WALL PROTECTION
A.F.F. ABOVE FINISHED FLOOR
A.F.S. AT FINISHED SLAB
ACT ACOUSTICAL CEILING TILE
ADD'L ADDITIONAL
ADJ. ADJUSTABLE
ADMIN. ADMINISTRATION
ALUM. ALUMINUM
APPROX. APPROXIMATE
ASST. ASSISTANT
B.W. BOTTOM OF THE WALL
B/B BALLED & BURLAPPED
BR. BARE ROOT
BRKT. BRACKET
BRKTS. BRACKETS
C CALK
C'SNK. COUNTERSUNK
C.B. CATCH BASIN
C.J. CONTROL JOINT
C.M.U. CONCRETE MASONRY UNIT
CAB. CABINET
CC CONTRACTOR FURNISHED /
CONTRACTOR INSTALLED
CLG. CEILING
CLO. CLOSET
CNTR. COUNTER
COL. COLUMN
COMP. COMPUTER
CONC. CONCRETE
CONF. CONFERENCE
CONST. CONSTRUCTION
CONT. CONTINUOUS
CORR. CORRIDOR
DIA. DIAMETER
DIAG. DIAGONAL
DIM. DIMENSION
DIR. DIRECTOR
DISP. DISPENSER
DS DOWNSPOUT
DTL. DETAIL
DWGS. DRAWINGS
EA. EACH
ELEC. ELECTRICAL
ELEV. ELEVATION
ENCL. ENCLOSURE
EQ EQUAL
EQUIP. EQUIPMENT
EXIST. EXISTING
EXP. JT. EXPANSION JOINT
EXT. EXTERIOR
F.D. FLOOR DRAIN
F.E.C. FIRE EXTINGUISHER CABINET
F.F.E. FINISH FLOOR ELEVATION
FDS FOLD DOWN SEAT
FH FIRE HYDRANT
FIN. FINISH
FL. FLOOR
FOB FACE OF BRICK
FTG. FOOTING
FZR. FREEZER
G.B. GRAB BAR
GA. GAUGE
GAL. GALLON
GALV. GALVANIZED
GEN. GENERAL
GYP. GYPSUM
GYP. BD. GYPSUM BOARD
H.B. HOSE BIBB
H.M. HOLLOW METAL
HD. HEAD
HRDBD HARDBOARD
I.D. INSIDE DIAMETER
INFO. INFORMATION
INSUL. INSULATION
INT. INTERIOR
INV. INVERT
JT. JOINT
KIT. KITCHEN
LAB. LABORATORY
LAV. LAVATORY
LKR. LOCKER
M.O. MASONRY OPENING
MACH. MACHINE
MAINT. MAINTENANCE
MAT'L MATERIAL
MAX. MAXIMUM
GENERAL ABBREVIATIONS
● ALL OTHER NON-STRUCTURAL COMPONENTS WITHIN THE HVAC, MECHANICAL, PLUMBING, AND
ELECTRICAL SYSTEMS ARE ASSIGNED AN IMPORTANCE FACTOR OF 1.0 AND ARE ELIGIBLE FOR THE LATERAL BRACING EXEMPTIONS LISTED IN ASCE 7 SECTION 9.6. THE EXEMPTIONS APPLY TO SPECIFIC SMALLER SIZES OF PIPING AND DUCTWORK AND LESS HEAVY EQUIPMENT. NON-EXEMPT PORTIONS OF THESE SYSTEMS SHALL STILL BE LATERALLY BRACED. SYSTEMS WITH AN IMPORTANCE FACTOR OF 1.0
ARE CONSIDERED BY THE CODE TO BE NOT CRITICAL FOR THE CONTINUED OPERATION OF THE
FACILITY.
COMPONENTS WITH AN IMPORTANCE FACTOR OF 1.0:
● STORM SEWER SERVING CRITICAL CARE AREAS.
● SANITARY SEWER SERVING CRITICAL CARE AREAS.
● STEAM SYSTEM.
● HEATING HOT WATER SYSTEM.
● DOMESTIC HOT WATER SYSTEM.
● FIRE ALARM SYSTEM.
● EMERGENCY POWER DISTRIBUTION SYSTEMS INCLUDING ASSOCIATED GENERATOR, TRANSFER
SWITCHES, BUS DUCTS, SWITCHBOARDS, CONDUIT, AND TRANSFORMERS.
● GENERATOR ENGINE EXHAUST.
● DUCTWORK CARRYING RADIOACTIVE AGENTS AND INFECTIOUS ISOLATION AIR.
● MEDICAL GAS PIPING AND EQUIPMENT.
● FIRE SPRINKLERS AND EQUIPMENT.
● NATURAL GAS PIPING.
● FUEL OIL PIPING AND EQUIPMENT.
COMPONENTS WITH AN IMPORTANCE FACTOR OF 1.5:
3. ASSIGNED SEISMIC USE GROUP OR BUILDING DESIGN CATEGORY AS DEFINED IN THE IBC:
2. THE TERM "WITHSTAND" MEANS "THE SYSTEM WILL REMAIN IN PLACE WITHOUT SEPARATION OF ANY PARTS WHEN SUBJECTED TO THE SEISMIC FORCES SPECIFIED AND THE SYSTEM WILL BE FULLY OPERATIONAL
AFTER THE SEISMIC EVENT."
1. COMPONENTS SHALL WITHSTAND THE EFFECTS OF EARTHQUAKE MOTIONS DETERMINED ACCORDING TO
ASCE/SEI 7.
NON-STRUCTURAL SEISMIC NOTES
14. CONTRACTOR IS RESPONSIBLE FOR OBTAINING ALL LOCAL AND STATE CONSTRUCTION PERMITS.
13. CONTRACTOR SHALL NOT DISRUPT OR LIMIT THE FACILITY'S LIFE SAFETY PLAN AND SYSTEM.
12. SEISMIC: NON-STRUCTURAL COMPONENTS SHALL WITHSTAND THE EFFECTS OF EARTHQUAKE MOTIONS
DETERMINED ACCORDING TO ASCE/SEI 7. PROVIDE ENGINEERED SUPPORTS PER SEISMIC
CLASSIFICATION AND ASCE/SEI 7 REQUIRMENTS.
11. CODES: COMPLY WITH ALL APPLICABLE FEDERAL, STATE AND LOCAL CODES.
10. SUPPORT / BLOCKING: PROVIDE SUPPORT FOR NEW WORK. IF HANGERS, BACKERS, OR OTHER SUPPORTS ARE NOT DETAILED, NOTED, OR SPECIFIED, CONTRACTOR SHALL SUBMIT A VIABLE SUPPORT DETAIL TO THE ARCHITECT FOR APPROVAL. ALL BLOCKING SHALL BE METAL (U.N.O.) ALL WOOD
BLOCKING, WHERE SPECIFIED, SHALL BE FIRE RETARDANT (U.N.O.)
9. MAINTAIN RATINGS: MAINTAIN FIRE / SMOKE RATINGS OF EXISTING PARTITIONS AND BARRIERS.
8. SHUTDOWNS / DOWNTIME: CONTRACTOR SHALL MAKE EVERY EFFORT TO MINIMIZE DOWNTIME
ASSOCIATED WITH SCHEDULED SHUTDOWNS. COORDINATE WITH COR.
7. COORDINATE TRADES: GENERAL CONTRACTOR IS RESPONSIBLE FOR COORDINATION BETWEEN
TRADES. MECHANICAL DUCTWORK & EQUIPMENT SHALL HAVE PRIORITY OVER OTHER DISCIPLINES (FOR INSTALLATION & ROUTING). COORDINATE UTILITIES, SO THEY ARE INSTALLED IN AN ORDERLY AND
UNIFORM MANNER.
6. PROTECT / RESTORE: PROTECT EXISTING ITEMS, EQUIPMENT, FINISHES, ETC., TO REMAIN. REPAIR / REPLACE / RESTORE CONDITIONS THAT ARE DAMAGED OR DISTURBED AS A RESULT OF DEMOLITION OR
NEW WORK.
5. UTILITIES: UTILITIES AND SYSTEMS IN AREAS OUTSIDE THE CONSTRUCTION LIMITS SHALL REMAIN (U.N.O.).
4. COORDINATE NEW ITEMS: EXACT LOCATIONS OF ALL EQUIPMENT, DEVICES / OUTLETS, FIXTURES, CASEWORK, MOUNTS, AND ROUTING OF UTILITIES SHALL BE COORDINATED WITH AND APPROVED BY THE
COR.
3. DO NOT SCALE DRAWINGS.
2. VERIFY CONDITIONS: INVESTIGATE THE SITE AND VERIFY EXISTING CONDITIONS (BOTH EXPOSED AND
CONCEALED) PRIOR TO PRICING THE JOB.
1. DIAGRAMMATIC DRAWINGS: THE DRAWINGS ARE DIAGRAMMATIC IN NATURE. THE DRAWINGS
REPRESENT THE INTENT OF THE PROJECT WORK.
GENERAL PROJECT NOTES
ACCESSIBILITY: ALL PUBLIC AREAS AND EMPLOYEE COMMON AREAS - ADAAG, ANSI (SEE ADA CLINICAL
SUITE EXAMPLE DRAWING, SHEET G101.20
J. HANDICAPPED ACCESSIBILITY REQUIREMENTS:
ROOF CONSTRUCTION: 1 HR
FLOOR CONSTRUCTION: 1 HR
NON-BEARING WALLS & PARTITIONS (INTERIOR): 0 HR
NON-BEARING WALLS & PARTITIONS (EXTERIOR) TABLE 602 (IBC) NFPA 5000 SEC 7.2
BEARING WALLS (INTERIOR): 1 HR
BEARING WALLS (EXTERIOR): 1 HR
STRUCTURAL FRAME: 1 HR
I. FIRE PROTECTION REQUIREMENTS (IBC TABLE 601 & NFPA A.8.2.1.2):
COMMON PATH OF EGRESS TRAVEL = 75 FT. MAX.
TRAVEL DISTANCE TO ACCESS DOOR OF ADJACENT SMOKE COMPARTMENT = 200 FT. MAX.
8'-0" MIN WHERE BEDS/STRETCHERS ARE BEING MOVED
CORRIDORS: WIDTH 44 IN
MAX EGRESS: DISTANCE: 200 FT (SPRINKLERED)
EGRESS WIDTH: 0.2 PER OCCUPANT
H. TRAVEL DISTANCE REQUIREMENTS:
NOTE: REFER TO PLAN FOR INDIVIDUAL SPACE OCCUPANCY LOADS
COMMERCIAL KITCHEN 100 GSF / OCCUPANT (NFPA)
LOCKER ROOMS 50 GSF / OCCUPANT
SLEEPING AREAS 120 GSF / OCCUPANT
ACCESSORY STORAGE &
MECH SPACES
300 GSF / OCCUPANT
OP TREATMENT AREAS 100 GSF / OCCUPANT
IP TREATMENT AREAS 240 GSF / OCCUPANT
WAITING, CONF., & SEMINAR
AREAS
15 NSF / OCCUPANT
OFFICE AREAS 100 GSF / OCCUPANT
AREA DESCRIPTION LOAD FACTOR
G. OCCUPANT LOAD:
ACTUAL NUMBER OF STORIES: 4 STORIES
THIRD FLOOR RENOVATION: 19,252 SF FOR STORIES 1-3
45,000 SF + 11,250 SF = 56,250 SF MAX
AREA W/ FRONTAGE INCREASE AT 100% OF PERIMETER 30' OR MORE OF CLEAR =
AREA W/ SPRINKLER INCREASE: 15,000SF + 15,000 SF X 2 = 45,000SF
ALLOWED HEIGHT AND AREA:
(IBC 2012 AND 2018)
2 STORIES, 65'-0" HIGH, 15,000 SF, MAX. - W/ SPRINKLER INCREASE -
3 STORIES, 85'-0" HIGH.
F. BUILDING HEIGHT & AREA:
ZONE D
E. SEISMIC ZONE:
NFPA 2018: TYPE II (1,1,1) - FULLY SPRINKLED
IBC 2012: TYPE II-A - FULLY SPRINKLED
D. CONSTRUCTION TYPE:
NFPA 2018: EXISTING HEALTHCARE OCCUPANCY - CHAPTER 19
IBC 2012: INSTITUTIONAL HEALTHCARE OCCUPANCY - I-2
C. OCCUPANACY:
BRENT ROWLAND - BROWLAND@MURFREESBOROTN.GOV
PH: 615-893-3750 FAX: 615-217-3016
MURFREESBORO, TN 37133-1139
111 W. VINE STREET - PO BOX 1139
CITY OF MURFREESBORO - BUILDING AND CODES DEPT.
PH: 615-741-6998 FAX: 615-253-1868
NASHVILLE, TN 37243
665 MAINSTREAM DRIVE, SECOND FLOOR
OFFICE OF HEALTHCARE FACILITIES PLAN REVIEW
STATE OF TENNESSEE DEPARTMENT OF HEALTH - DIV. OF LICENSING AND REGULATION
PHONE: 615-741-7190
NASHVILLE, TN 37243-1162
500 JAMES ROBERTSON PARKWAY
TENNESSEE STATE FIRE MARSHAL
B. AUTHORITIES HAVING JURISDICTION (AHJ):
VETERANS AFFAIRS FIRE PROTECTION DESIGN MANUAL
2018 NFPA 101 LIFE SAFETY CODE
DEPARTMENT OF VETERANS AFFAIRS - OFFICE OF CONSTRUCTION AND FACILITY MANAGEMENT
2009 ICC ANSI 117.1 - ACCESSIBLE AND USABLE BUILDING AND FACILITIES
2017 NATIONAL ELECTRIC CODE (NEC)
2018 INTERNATIONAL FUEL AND GAS CODE
2018 INTERNATIONAL MECHANICAL CODE (IMC)
2018 INTERNATIONAL PLUMBING CODE (IPC)
2018 INTERNATIONAL ENERGY CONSERVATION CODE (IECC)
2018 INTERNATIONAL FIRE CODE (IFC)
2018 INTERNATIONAL BUILDING CODE (IBC)
CITY OF MURFREESBORO
2018 FGI GUIDELINES FOR DESIGN AND CONSTRUCTION OF HOSPITALS AND HEALTH CARE FACILITIES
2010 ADA ACCESSIBILITY GUIDELINES W/ AMENDMENTS
2012 INTERNATIONAL FUEL AND GAS CODE
2012 NATIONAL ELECTRIC CODE (NEC)
2012 INTERNATIONAL ENERGY CONSERVATION CODE (IECC)
2012 INTERNATIONAL MECHANICAL CODE (IMC)
2012 INTERNATIONAL PLUMBING CODE (IPC)
2012 NFPA-1, EXCLUDING NFPA 5000
2012 LSC - NFPA - 101 LIFE SAFETY CODE
2012 INTERNATIONAL BUILDING CODE (IBC)
STATE OF TENNESSEE DEPARTMENT OF HEALTH
A. APPLICABLE STATUTES:
DESCRIPTION: This project proposes to completely renovate the third floor of building 1 on the Alvin C. York VA medical center campus.
Murfreesboro, TN
LOCATION: Alvin C. York VA Medical Center
PROJECT: AE RENOVATE WARD 1B
PLAN REVIEW DATA
VACINITY MAP CAMPUS MAP
No. Date Description
DRAWING INDEX
SHEET # SHEET NAME
SUBMISSIONS
45% 65% 95% 100% BID
M-MP-02 PARTIAL THIRD FLOOR PLAN - PART B - PIPE NEW WORK ● ● ● ● ●
M-MP-03 PARTIAL THIRD FLOOR PLAN - PART C - PIPE NEW WORK ● ● ● ● ●
M-MH-07 SCHEDULES ● ● ● ● ●
M-MH-08 SCHEDULES ● ● ● ● ●
M-MH-09 MECHANICAL DETAILS ● ● ● ● ●
M-MH-10 MECHANICAL DETAILS ● ● ● ●
M-MH-11 MECHANICAL DETAILS ● ● ● ●
M-MH-12 MECHANICAL DETAILS ● ● ● ●
M-MI-01 MECHANICAL CONTROLS ● ● ● ● ●
M-MI-02 MECHANICAL CONTROLS ● ● ●
08 - PLUMBING
P-PI-01 PLUMBING LEGENDS AND NOTES ● ● ● ● ●
P-PI-02 PLUMBING SCHEDULES ● ● ● ● ●
P-PD-01 PARTIAL THIRD FLOOR - PART A - PLUMBING - DEMO ● ● ● ● ●
P-PD-02 PARTIAL THIRD FLOOR - PART B - PLUMBING - DEMO ● ● ● ● ●
P-PD-03 PARTIAL THIRD FLOOR - PART C - PLUMBING - DEMO ● ● ● ● ●
P-PD-04 PARTIAL THIRD FLOOR - PART A - MED GAS - DEMO ● ● ● ● ●
P-PD-05 PARTIAL THIRD FLOOR - PART B - MED GAS - DEMO ● ● ● ● ●
P-PD-06 PARTIAL THIRD FLOOR - PART C - MED GAS - DEMO ● ● ● ● ●
P-PD-07 FOURTH FLOOR - PLUMBING - DEMO ● ● ● ● ●
P-PP-01 PLUMBING - SECOND FLOOR ZONE PLAN ● ● ● ● ●
P-PP-02 PARTIAL THIRD FLOOR - PART A - GRAVITY - NEW WORK ● ● ● ● ●
P-PP-03 PARTIAL THIRD FLOOR - PART B - GRAVITY - NEW WORK ● ● ● ● ●
P-PP-04 PARTIAL THIRD FLOOR - PART C - GRAVITY - NEW WORK ● ● ● ●
P-PP-05 PARTIAL FOURTH FLOOR - PART A - GRAVITY - NEW WORK ● ● ● ● ●
P-PP-06 PARTIAL FOURTH FLOOR - PART B - GRAVITY - NEW WORK ● ● ● ● ●
P-PP-07 PARTIAL FOURTH FLOOR - PART C - GRAVITY - NEW WORK ● ● ● ● ●
P-PP-08 PARTIAL THIRD FLOOR - PART A - PRESSURE - NEW WORK ● ● ● ●
P-PP-09 PARTIAL THIRD FLOOR - PART B - PRESSURE - NEW WORK ● ● ● ●
P-PP-10 PARTIAL THIRD FLOOR - PART C - PRESSURE - NEW WORK ● ● ● ●
P-PG-01 PARTIAL THIRD FLOOR - PART A - MED GAS - NEW WORK ● ● ● ● ●
P-PG-02 PARTIAL THIRD FLOOR - PART B - MED GAS - NEW WORK ● ● ● ● ●
P-PG-03 PARTIAL THIRD FLOOR - PART C - MED GAS - NEW WORK ● ● ● ● ●
P-PW-01 PLUMBING RISERS PART A - PRESSURE ● ● ● ●
P-PW-02 PLUMBING RISERS PART B - PRESSURE ● ● ● ●
P-PW-03 PLUMBING RISERS PART C - PRESSURE ● ● ● ●
P-PW-04 PLUMBING RISERS PART A - GRAVITY ● ● ●
P-PW-05 PLUMBING RISERS PART B - GRAVITY ● ● ●
P-PW-06 PLUMBING RISERS PART C - GRAVITY ● ● ●
P-PI-03 PLUMBING DETAILS ● ● ● ● ●
P-PI-04 PLUMBING DETAILS ● ● ● ● ●
09 - FIRE PROTECTION
F-FI-01 FIRE PROTECTION LEGENDS, DETAILS AND NOTES ● ● ● ● ●
F-FD-01 PARTIAL THIRD FLOOR - PART A - FIRE PROTECTION - DEMO ● ● ● ● ●
F-FD-02 PARTIAL THIRD FLOOR - PART B - FIRE PROTECTION - DEMO ● ● ● ● ●
F-FD-03 PARTIAL THIRD FLOOR - PART C - FIRE PROTECTION - DEMO ● ● ● ● ●
F-FX-01 PARTIAL THIRD FLOOR - PART A - FIRE PROTECTION - NEW WORK ● ● ● ● ●
F-FX-02 PARTIAL THIRD FLOOR - PART B - FIRE PROTECTION - NEW WORK ● ● ● ● ●
F-FX-03 PARTIAL THIRD FLOOR - PART C - FIRE PROTECTION - NEW WORK ● ● ● ● ●
10 - ELECTRICAL
E-EI-00 ELECTRICAL SYMBOLS LEGEND, LIGHTING FIXTURE SCHEDULE
AND GENERAL NOTES
E-EI-01 PARTIAL ELECTRICAL ONE LINE DIAGRAM - DEMOLITION ● ● ● ● ●
E-EI-02 PARTIAL ELECTRICAL ONE LINE DIAGRAM - NEW WORK ● ● ● ● ●
E-EI-03 ELECTRICAL PANEL SCHEDULES ● ● ● ●
E-EI-04 ELECTRICAL PANEL SCHEDULES ● ● ● ●
E-EI-05 ELECTRICAL DETAILS ● ● ● ●
E-EI-06 ELECTRICAL DETAILS ● ● ● ●
E-ED-00 3RD FLOOR - DEMOLITION PLAN - ELECTRICAL - OVERALL ● ● ● ●
E-ED-01 3RD FLOOR - DEMOLITION PLAN - ELECTRICAL - PART A ● ● ● ●
E-ED-02 3RD FLOOR - DEMOLITION PLAN - ELECTRICAL - PART B ● ● ● ●
E-ED-03 3RD FLOOR - DEMOLITION PLAN - ELECTRICAL - PART C ● ● ● ●
E-EP-01 3RD FLOOR - NEW WORK PLAN - POWER - PART A ● ● ● ●
E-EP-02 3RD FLOOR - NEW WORK PLAN - POWER - PART B ● ● ● ●
E-EP-03 3RD FLOOR - NEW WORK PLAN - POWER - PART C ● ● ● ●
E-EP-04 3RD FLOOR ROOF - NEW WORK PLAN - POWER - PART A ● ●
E-EL-01 3RD FLOOR - NEW WORK PLAN - LIGHTING - PART A ● ● ● ●
E-EL-02 3RD FLOOR - NEW WORK PLAN - LIGHTING - PART B ● ● ● ●
E-EL-03 3RD FLOOR - NEW WORK PLAN - LIGHTING - PART C ● ● ● ●
E-EY-01 3RD FLOOR - NEW WORK PLAN - SYSTEMS - PART A ● ● ● ●
E-EY-02 3RD FLOOR - NEW WORK PLAN - SYSTEMS - PART B ● ● ● ●
E-EY-03 3RD FLOOR - NEW WORK PLAN - SYSTEMS - PART C ● ● ● ●
11 - TECHNOLOGY
T-TJ-00 GENERAL TECHNOLOGY INFORMATION ● ● ● ● ●
T-TD-01 PARTIAL THRID FLOOR PLAN - PART A - TECHNOLOGY DEMO ● ● ● ● ●
T-TD-02 PARTIAL THIRD FLOOR PLAN - PART B - TECHNOLOGY DEMO ● ● ● ●
T-TD-03 PARTIAL THIRD FLOOR PLAN - PART C TECHNOLOGY DEMO ● ● ● ●
T-TJ-01 PARTIAL THIRD FLOOR - PART A - TECHNOLOGY NEW WORK ● ● ● ● ●
T-TJ-02 PARTIAL THIRD FLOOR - PART B - TECHNOLOGY NEW WORK ● ● ● ● ●
T-TJ-03 PARTIAL THIRD FLOOR - PART C - TECHNOLOGY NEW WORK ● ● ● ● ●
T-TJ-04 TECHNOLOGY - ENLARGED ROOMS ● ● ● ● ●
T-TJ-06 TECHNOLOGY DETAILS ● ● ●
T-TJ-07 TECHNOLOGY DETAILS ● ● ●
T-TJ-08 TECHNOLOGY RISER ● ● ●
DRAWING INDEX
SHEET # SHEET NAME
SUBMISSIONS
45% 65% 95% 100% BID
00 - GENERAL
GI 00.01 COVER SHEET ● ● ● ● ●
GI 01.01 GENERAL DATA ● ● ● ● ●
GI 01.02 CONSTRUCTION STAGING PLAN ● ● ●
GI 01.10 WALL TYPE DETAILS ● ● ● ●
GI 01.20 ACCESSIBILITY DETAILS ● ● ● ● ●
GI 02.01 THIRD FLOOR LIFE SAFETY PLAN - OVERALL ● ● ● ● ●
GI 03.01 SECOND FLOOR ICRA PLAN ● ●
GI 03.02 THIRD FLOOR ICRA PLAN ● ●
GI 04.01 ACM DUCT WORK AND ACM PIPE INSULATION ● ●
GI 04.02 LEAD PAINT AND TRANSITE PANELS ● ●
GI 05.01 PHASING PLANS
03 - DEMOLITION
AD 01.01 THIRD FLOOR DEMOLITION PLAN - OVERALL ● ● ● ● ●
AD 01.02 PARTIAL THIRD FLOOR DEMO PLAN - AREA A ●
AD 01.03 PARTIAL THIRD FLOOR DEMO PLAN - AREA B ●
AD 01.04 PARTIAL THIRD FLOOR DEMO PLAN - AREA C ●
04 - ARCHITECTURAL
AE 01.00 SECOND FLOOR PLAN AND REFLECTED CEILING PLAN ● ● ●
AE 01.01 FOURTH FLOOR/ATTIC PLAN ● ● ●
AE 01.03 THIRD FLOOR OVERALL PLAN ● ● ● ● ●
AE 01.11 PARTIAL THIRD FLOOR PLAN - PART A NOTED ● ● ● ● ●
AE 01.12 PARTIAL THIRD FLOOR PLAN - PART B NOTED ● ● ● ● ●
AE 01.13 PARTIAL THIRD FLOOR PLAN - PART C NOTED ● ● ● ● ●
AE 01.14 PARTIAL THIRD FLOOR PLAN - PART A DIMENSIONED ● ● ● ●
AE 01.15 PARTIAL THIRD FLOOR PLAN - PART B DIMENSIONED ● ● ● ●
AE 01.16 PARTIAL THIRD FLOOR PLAN - PART C DIMENSIONED ● ● ● ●
AE 02.01 ENLARGED PLANS AND REFLECTED CEILING PLANS ● ● ● ● ●
AE 02.02 ENLARGED PLANS AND REFLECTED CEILING PLANS ● ● ● ● ●
AE 02.03 ENLARGED TOILET PLANS AND ELEVATIONS ● ● ●
AE 03.01 DOOR ELEVATIONS, SCHEDULE, & NOTES ● ● ● ●
AE 03.02 DOOR DETAILS ● ● ● ●
AE 03.03 WINDOW DETAILS ● ● ●
AE 08.01 MISC. DETAILS ● ● ● ●
AE 08.02 MISC. DETAILS ● ● ● ●
AE 08.03 MISC. DETAILS ● ● ● ●
AE 08.04 MISC. DETAILS ● ● ●
AE 08.05 MISC. INTERIOR DETAILS ● ● ●
AE 08.06 MISC CEILING DETAILS ● ● ●
AE 09.01 INTERIOR ELEVATIONS ● ● ● ● ●
AE 09.02 INTERIOR ELEVATIONS ● ● ● ● ●
AE 09.03 CORRIDOR ELEVATIONS ● ● ●
AE 09.04 CORRIDOR ELEVATIONS ● ● ●
AE 09.05 3D VIEWS ● ● ● ● ●
AE 10.01 CASEWORK SECTIONS AND DETAILS ● ● ● ●
AE 10.02 CASEWORK SECTIONS AND DETAILS ●
AE 11.01 THIRD FLOOR REFLECTED CEILING PLAN - OVERALL ● ● ● ● ●
AE 11.10 THIRD FLOOR RCP - PART A ● ● ● ● ●
AE 11.11 THIRD FLOOR RCP - PART B ● ● ● ● ●
AE 11.12 THIRD FLOOR RCP - PART C ● ● ● ● ●
AE 12.01A EQUIPMENT PLANS ● ● ● ●
AE 12.01B EQUIPMENT PLANS ● ● ● ●
AE 12.01C EQUIPMENT PLANS ● ● ● ●
AE 12.02 EQUIPMENT PLANS - PATIENT ROOMS AREA B ● ● ● ●
AE 12.02B EQUIPMENT PLANS - PATIENT ROOMS AREA C ● ● ● ●
VN 01.00 PATIENT LIFT VENDOR DRAWINGS ● ● ●
05 - INTERIOR DESIGN
IN 01.00 THIRD FLOOR FINISH LEGEND ● ● ● ● ●
IN 01.02 PARTIAL THIRD FLOOR FINISH PLAN - PART A ● ● ● ●
IN 01.03 PARTIAL THIRD FLOOR FINISH PLAN - PART B ● ● ● ●
IN 01.04 PARTIAL THIRD FLOOR FINISH PLAN - PART C ● ● ● ●
IN 01.05 THIRD FLOOR PATTERN PLAN OVERALL ● ● ● ●
IN 01.06 PARTIAL THIRD FLOOR PATTERN - PART A ● ● ● ●
IN 01.07 PARTIAL THIRD FLOOR PATTERN - PART B ● ● ● ●
IN 01.08 PARTIAL THIRD FLOOR PATTERN - PART C ● ● ● ●
IN 02.00 THIRD FLOOR SIGNAGE LEGEND ● ● ●
IN 02.01 THIRD FLOOR SIGNAGE SCHEDULE ● ● ●
IN 02.02 PARTIAL THIRD FLOOR SIGNAGE PLAN - PART A ● ● ●
IN 02.03 PARTIAL THIRD FLOOR SIGNAGE PLAN - PART B ● ● ●
IN 02.04 PARTIAL THIRD FLOOR SIGNAGE PLAN - PART C ● ● ●
07 - MECHANICAL
M-MH-01 LEGENDS, NOTES, AND SYMBOLS ● ● ● ● ●
M-MD-01 PARTIAL THIRD FLOOR PLAN - PART A - DUCT DEMO ● ● ● ● ●
M-MD-02 PARTIAL THIRD FLOOR PLAN - PART B - DUCT DEMO ● ● ● ● ●
M-MD-03 PARTIAL THIRD FLOOR PLAN - PART C - DUCT DEMO ● ● ● ● ●
M-MD-04 PARTIAL THIRD FLOOR PLAN - PART A - PIPE DEMO ● ● ● ● ●
M-MD-05 PARTIAL THIRD FLOOR PLAN - PART B - PIPE DEMO ● ● ● ● ●
M-MD-06 PARTIAL THIRD FLOOR PLAN - PART C - PIPE DEMO ● ● ● ● ●
M-MH-13 PARTIAL ATTIC PLAN - PART B - DUCT DEMO ● ● ● ●
M-MH-14 PARTIAL ATTIC PLAN - PART C - DUCT DEMO ● ● ● ●
M-MH-02 PARTIAL THIRD FLOOR PLAN - PART A - DUCT NEW WORK ● ● ● ● ●
M-MH-03 PARTIAL THIRD FLOOR PLAN - PART B - DUCT NEW WORK ● ● ● ● ●
M-MH-04 PARTIAL THIRD FLOOR PLAN - PART C - DUCT NEW WORK ● ● ● ● ●
M-MH-05 PARTIAL ATTIC PLAN - PART B - DUCT NEW WORK ● ● ● ● ●
M-MH-06 PARTIAL ATTIC PLAN - PART C - DUCT NEW WORK ● ● ● ● ●
M-MP-01 PARTIAL THIRD FLOOR PLAN - PART A - PIPE NEW WORK ● ● ● ● ●
Proposed buckhoist location
D2. Secondary dumpster site. Must meet all fencing and security requirements. May only be used during demolition phase.
D1. Primary Staging area. Will be assigned to contractor for duration of project. Contractor is responsible for mowing, maintaining cleanliness and order.
Staging Plan: Building 1 is an active Medical Facility. All care must be taken to provide a safe and clean environment. The contractor will have NO interior elevator access during construction and must make accommodation for manpower and materials to be lifted.Contractor must return all disturbed areas to original condition. Provide location for buck hoist power supply, 480V 3-phase power will be needed from the north end of building 1 at room 349.
VETERANS C
IR
CLEVETERANS CIRCLE
2 9
D2
D1
12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554
©Copyright 2019
TLC No.:
www.tlc-engineers.com
118626
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg.
PROJECT TEAM:
Office of
Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
Department of Veterans Affairs
MURFREESBORO, TN
615.370.8500
615.370.8530 hfrdesign.com
214 Centerview Drive Suite 300 Brentwood, TN 37027
Phase
FULLY SPRINKLERED
C U s e rs \a tr a y lo r\ D o c u m e n ts
\M b o ro V
A W a rd b
R e n o a tr a y lo r2 X
N D
H .r v t
/1
/2
:2
:0
P
M
04-14-2023
626A4-19-101
GI 01.02
AE RENOVATE WARD 1BCONSTRUCTION STAGING PLAN
AT
HFR Project No: 2019056
100% CONSTRUCTION
DOCUMENTS
No. Date Description
1HR FIRE/SMOKE BARRIER
UL DESIGN #:
STC RATING:
FIRE RATING:
SCALE:
16" O.C.
SECTION
PLAN
3-5/8" STUDB
U465
45 - 49
1HR
N.T.S.
DESCRIPTION:
2 43
ABOVE CEILING ID (STENCIL):
"1HR FIRE/SMOKE BARRIER"
PLAN DESIGNATION:
GENERAL NOTES:
1. ALL REQUIREMENTS OF LISTED UL
DESIGN # MUST BE MET.
WALL PRIORITY:
1/ 4"
M
IN
OPENINGS: 45 MIN
1. STEEL FLOOR AND CEILING CHANNELS - TOP AND BOTTOM CHANNELS OF WALL
ASSEMBLY SHALL BE MIN. 20 GA. GALV. STEEL SIZED TO FIT STUDS. TOP CHANNEL TO
HAVE 2" FLANGES (MIN). BOTTOM CHANNEL TO HAVE 1-1/4" FLANGES (MIN). SECURE
BOTTOM CHANNELS WITH STEEL FASTENERS AT 24" O.C. (MAX). SECURE TOP
CHANNELS TO VALLEYS OF STEEL FLOOR UNITS (OR STRUCTURE ABOVE) WITH STEEL
FASTENERS AT 12" O.C. (MAX).
2. STEEL STUDS - MIN. 3-5/8" WIDE, 1-1/4" LEGS, 3/8" FOLDED BACK RETURN. FORMED OF
20 GA.(MIN) GALV. STEEL. MAX. SPACING 16" O.C. CUT STUDS 1" LESS IN LENGTH THAN
ASSEMBLY HEIGHT WITH BOTTOM NESTING IN AND SECURED TO FLOOR CHANNEL, AND
WITH TOP NESTING IN CEILING CHANNEL WITHOUT ATTACHMENT.
3. SOUND ATTENUATION BATT INSUL. - 3-1/2" (DEPENDING ON STUD SIZE) GLASS FIBER
BATTS IN STUD CAVITY. FILL ENTIRE CAVITY FULL HEIGHT.
4. GYPSUM WALLBOARD- 5/8" THICK TYPE "X", 4' WIDE, ATTACHED TO STEEL STUDS AND
FLOOR CHANNELS WITH 1" LONG TYPE S SELF-TAPPING STEEL SCREWS AT 8" O.C.
ALONG THE VERTICAL AND BOTTOM EDGES AND 12" O.C. IN THE FIELD OF THE BOARD.
INSTALL WALLBOARD WITH A MIN. 1/2" AND MAX. 3/4" GAP BETWEEN THE TOP OF THE
WALLBOARD AND THE BOTTOM OF THE FLOOR UNIT VALLEYS (OR STRUCTURE ABOVE).
NO SCREWS ARE TO BE INSTALLED WITHIN 4" OF THE STEEL FLOOR UNIT VALLEYS AT
THE TOP OF THE WALL. ORIENT JOINTS VERTICALLY AND STAGGER JOINTS ON
OPPOSITE SIDES OF THE ASSEMBLY. WHEN ATTACHED TO FURRING CHANNELS,
WALLBOARD IS ATTACHED WITH 1" LONG TYPE S SCREWS AT 12" O.C.
5. JOINT TAPE AND COMPOUND - VINYL, DRY OR PRE-MIXED JOINT COMPOUND, APPLIED
IN TWO COATS TO JOINTS AND SCREW HEADS; PAPER TAPE 2" WIDE EMBEDDED IN
FIRST LAYER OF COMPOUND OVER ALL JOINTS. JOINTS REINFORCED.
6. FURRING CHANNELS (OPTIONAL NOT SHOWN) - RESILIENT 20 MSG GALV. STEEL
FURRING CHANNELS SPACED VERT. MAX. 24" O.C. ATTACH FLANGE TO EACH
INTERSECTING STUD WITH 1/2" LONG TYPE S-12 PANHEAD SCREWS.
7. ACOUSTICAL SEALANT.
8. PACKING MATERIAL - MIN. 4" TKNS. OF MIN. 4.0 PCF MINERAL WOOL BATT INSULATION
FIRMLY PACKED INTO FLUTES OF STEEL FLOOR UNITS AS A PERMANENT FORM.
PACKING MATERIAL TO BE RECESSED FROM BOTH SURFACES OF THE WALL AS
REQUIRED TO RECEIVE JOINT SEALANT.
9. JOINT TREATMENT MATERIAL - NON-SAG FIRE CAULK EACH SIDE MIN THICKNESS 1/2",
APPLIED WITHIN THE OPENING BETWEEN THE TOP OF THE WALLBOARD AND ALL
SURFACES OF THE STEEL FLOOR OR STRUCTURE, FLUSH WITH BOTH SURFACES OF
THE WALL ASSEMBLY.
7/
8" M
IN
1HR FIRE BARRIER
UL DESIGN #:
STC RATING:
FIRE RATING:
SCALE:
16" O.C.
SECTION
PLAN
3-5/8" STUDC
U465
45 - 49
1HR
N.T.S.
DESCRIPTION:
2 43
ABOVE CEILING ID (STENCIL):
"1HR FIRE BARRIER"
PLAN DESIGNATION:
GENERAL NOTES:
1. ALL REQUIREMENTS OF LISTED UL
DESIGN # MUST BE MET.
WALL PRIORITY:
1/ 4"
M
IN
OPENINGS: 45 MIN
1. STEEL FLOOR AND CEILING CHANNELS - TOP AND BOTTOM CHANNELS OF WALL
ASSEMBLY SHALL BE MIN. 20 GA. GALV. STEEL SIZED TO FIT STUDS. TOP CHANNEL TO
HAVE 2" FLANGES (MIN). BOTTOM CHANNEL TO HAVE 1-1/4" FLANGES (MIN). SECURE
BOTTOM CHANNELS WITH STEEL FASTENERS AT 24" O.C. (MAX). SECURE TOP
CHANNELS TO VALLEYS OF STEEL FLOOR UNITS (OR STRUCTURE ABOVE) WITH STEEL
FASTENERS AT 12" O.C. (MAX).
2. STEEL STUDS - MIN. 3-5/8" WIDE, 1-1/4" LEGS, 3/8" FOLDED BACK RETURN. FORMED OF
20 GA.(MIN) GALV. STEEL. MAX. SPACING 16" O.C. CUT STUDS 1" LESS IN LENGTH THAN
ASSEMBLY HEIGHT WITH BOTTOM NESTING IN AND SECURED TO FLOOR CHANNEL, AND
WITH TOP NESTING IN CEILING CHANNEL WITHOUT ATTACHMENT.
3. SOUND ATTENUATION BATT INSUL. - 3-1/2" (DEPENDING ON STUD SIZE) GLASS FIBER
BATTS IN STUD CAVITY. FILL ENTIRE CAVITY FULL HEIGHT.
4. GYPSUM WALLBOARD- 5/8" THICK TYPE "X", 4' WIDE, ATTACHED TO STEEL STUDS AND
FLOOR CHANNELS WITH 1" LONG TYPE S SELF-TAPPING STEEL SCREWS AT 8" O.C.
ALONG THE VERTICAL AND BOTTOM EDGES AND 12" O.C. IN THE FIELD OF THE BOARD.
INSTALL WALLBOARD WITH A MIN. 1/2" AND MAX. 3/4" GAP BETWEEN THE TOP OF THE
WALLBOARD AND THE BOTTOM OF THE FLOOR UNIT VALLEYS (OR STRUCTURE ABOVE).
NO SCREWS ARE TO BE INSTALLED WITHIN 4" OF THE STEEL FLOOR UNIT VALLEYS AT
THE TOP OF THE WALL. ORIENT JOINTS VERTICALLY AND STAGGER JOINTS ON
OPPOSITE SIDES OF THE ASSEMBLY. WHEN ATTACHED TO FURRING CHANNELS,
WALLBOARD IS ATTACHED WITH 1" LONG TYPE S SCREWS AT 12" O.C.
5. JOINT TAPE AND COMPOUND - VINYL, DRY OR PRE-MIXED JOINT COMPOUND, APPLIED
IN TWO COATS TO JOINTS AND SCREW HEADS; PAPER TAPE 2" WIDE EMBEDDED IN
FIRST LAYER OF COMPOUND OVER ALL JOINTS. JOINTS REINFORCED.
6. FURRING CHANNELS (OPTIONAL NOT SHOWN) - RESILIENT 20 MSG GALV. STEEL
FURRING CHANNELS SPACED VERT. MAX. 24" O.C. ATTACH FLANGE TO EACH
INTERSECTING STUD WITH 1/2" LONG TYPE S-12 PANHEAD SCREWS.
7. ACOUSTICAL SEALANT.
8. PACKING MATERIAL - MIN. 4" TKNS. OF MIN. 4.0 PCF MINERAL WOOL BATT INSULATION
FIRMLY PACKED INTO FLUTES OF STEEL FLOOR UNITS AS A PERMANENT FORM.
PACKING MATERIAL TO BE RECESSED FROM BOTH SURFACES OF THE WALL AS
REQUIRED TO RECEIVE JOINT SEALANT.
9. JOINT TREATMENT MATERIAL - NON-SAG FIRE CAULK EACH SIDE MIN THICKNESS 1/2",
APPLIED WITHIN THE OPENING BETWEEN THE TOP OF THE WALLBOARD AND ALL
SURFACES OF THE STEEL FLOOR OR STRUCTURE, FLUSH WITH BOTH SURFACES OF
THE WALL ASSEMBLY.
7/
8" M
IN
SMOKETIGHT PARTITION
UL DESIGN #:
STC RATING:
FIRE RATING:
SCALE:
16" O.C.
SECTION
PLAN
3-5/8" STUDD
45 - 49
N.T.S.
DESCRIPTION:
2 43
ABOVE CEILING ID (STENCIL):
"NON-RATED SMOKETIGHT"
PLAN DESIGNATION:
GENERAL NOTES:
1. ALL REQUIREMENTS OF LISTED UL
DESIGN # MUST BE MET.
WALL PRIORITY:
1/ 4"
M
IN
OPENINGS: SM
1. STEEL FLOOR AND CEILING CHANNELS - TOP AND BOTTOM CHANNELS OF WALL
ASSEMBLY SHALL BE MIN. 20 GA. GALV. STEEL SIZED TO FIT STUDS. TOP CHANNEL TO
HAVE 2" FLANGES (MIN). BOTTOM CHANNEL TO HAVE 1-1/4" FLANGES (MIN). SECURE
BOTTOM CHANNELS WITH STEEL FASTENERS AT 24" O.C. (MAX). SECURE TOP
CHANNELS TO VALLEYS OF STEEL FLOOR UNITS (OR STRUCTURE ABOVE) WITH STEEL
FASTENERS AT 12" O.C. (MAX).
2. STEEL STUDS - MIN. 3-5/8" WIDE (UNLESS NOTED OTHERWISE), 1-1/4" LEGS, 3/8" FOLDED
BACK RETURN. FORMED OF 20 GA.(MIN) GALV. STEEL. MAX. SPACING 16" O.C. CUT
STUDS 1" LESS IN LENGTH THAN ASSEMBLY HEIGHT WITH BOTTOM NESTING IN AND
SECURED TO FLOOR CHANNEL, AND WITH TOP NESTING IN CEILING CHANNEL WITHOUT
ATTACHMENT.
3. SOUND ATTENUATION BATT INSUL. - 3-1/2" (DEPENDING ON STUD SIZE) GLASS FIBER
BATTS IN STUD CAVITY. FILL ENTIRE CAVITY FULL HEIGHT.
4. GYPSUM WALLBOARD- 5/8" THICK TYPE "X", 4' WIDE, ATTACHED TO STEEL STUDS AND
FLOOR CHANNELS WITH 1" LONG TYPE S SELF-TAPPING STEEL SCREWS AT 8" O.C.
ALONG THE VERTICAL AND BOTTOM EDGES AND 12" O.C. IN THE FIELD OF THE BOARD.
INSTALL WALLBOARD WITH A MIN. 1/2" AND MAX. 3/4" GAP BETWEEN THE TOP OF THE
WALLBOARD AND THE BOTTOM OF THE FLOOR UNIT VALLEYS (OR STRUCTURE ABOVE).
NO SCREWS ARE TO BE INSTALLED WITHIN 4" OF THE STEEL FLOOR UNIT VALLEYS AT
THE TOP OF THE WALL. ORIENT JOINTS VERTICALLY AND STAGGER JOINTS ON
OPPOSITE SIDES OF THE ASSEMBLY.
5. JOINT TAPE AND COMPOUND - VINYL, DRY OR PRE-MIXED JOINT COMPOUND, APPLIED
IN TWO COATS TO JOINTS AND SCREW HEADS; PAPER TAPE 2" WIDE EMBEDDED IN
FIRST LAYER OF COMPOUND OVER ALL JOINTS. JOINTS REINFORCED.
6. ACOUSTICAL SEALANT.
7. JOINT TREATMENT MATERIAL - NON-SAG FIRE CAULK EACH SIDE MIN THICKNESS 1/2",
APPLIED WITHIN THE OPENING BETWEEN THE TOP OF THE WALLBOARD AND ALL
SURFACES OF THE STEEL FLOOR OR STRUCTURE, FLUSH WITH BOTH SURFACES OF
THE WALL ASSEMBLY.
V A
R
IE
S
NON-RATED PARTITION
16" O.C.
SECTION
PLAN
E 3-5/8" STUD
F
DESCRIPTION:
2 43
UL DESIGN #:
STC RATING:
FIRE RATING:
SCALE:
45 - 49
N.T.S.
ABOVE CEILING ID (STENCIL):
PLAN DESIGNATION:
GENERAL NOTES:
1. ALL REQUIREMENTS OF LISTED UL
DESIGN # MUST BE MET.
WALL PRIORITY:
OPENINGS: --
V
A R
IE
S
1. STEEL FLOOR AND CEILING CHANNELS - TOP AND BOTTOM CHANNELS OF WALL
ASSEMBLY SHALL BE MIN. 20 GA. GALV. STEEL SIZED TO FIT STUDS. TOP CHANNEL TO
HAVE 2" FLANGES (MIN). BOTTOM CHANNEL TO HAVE 1-1/4" FLANGES (MIN). SECURE
BOTTOM CHANNELS WITH STEEL FASTENERS AT 24" O.C. (MAX). SECURE TOP
CHANNELS TO VALLEYS OF STEEL FLOOR UNITS (OR STRUCTURE ABOVE) WITH STEEL
FASTENERS AT 12" O.C. (MAX).
2. STEEL STUDS - MIN. 3-5/8" WIDE (UNLESS NOTED OTHERWISE), 1-1/4" LEGS, 3/8" FOLDED
BACK RETURN. FORMED OF 20 GA.(MIN) GALV. STEEL. MAX. SPACING 16" O.C. CUT
STUDS 1" LESS IN LENGTH THAN ASSEMBLY HEIGHT WITH BOTTOM NESTING IN AND
SECURED TO FLOOR CHANNEL, AND WITH TOP NESTING IN CEILING CHANNEL WITHOUT
ATTACHMENT.
3. SOUND ATTENUATION BATT INSUL. - 3-1/2" (DEPENDING ON STUD SIZE) GLASS FIBER
BATTS IN STUD CAVITY. FILL ENTIRE CAVITY FULL HEIGHT.
4. GYPSUM WALLBOARD- 5/8" THICK TYPE "X", 4' WIDE, ATTACHED TO STEEL STUDS AND
FLOOR CHANNELS WITH 1" LONG TYPE S SELF-TAPPING STEEL SCREWS AT 8" O.C.
ALONG THE VERTICAL AND BOTTOM EDGES AND 12" O.C. IN THE FIELD OF THE BOARD.
INSTALL WALLBOARD WITH A MIN. 1/2" AND MAX. 3/4" GAP BETWEEN THE TOP OF THE
WALLBOARD AND THE BOTTOM OF THE FLOOR UNIT VALLEYS (OR STRUCTURE ABOVE).
NO SCREWS ARE TO BE INSTALLED WITHIN 4" OF THE STEEL FLOOR UNIT VALLEYS AT
THE TOP OF THE WALL. ORIENT JOINTS VERTICALLY AND STAGGER JOINTS ON
OPPOSITE SIDES OF THE ASSEMBLY.
5. JOINT TAPE AND COMPOUND - VINYL, DRY OR PRE-MIXED JOINT COMPOUND, APPLIED
IN TWO COATS TO JOINTS AND SCREW HEADS; PAPER TAPE 2" WIDE EMBEDDED IN
FIRST LAYER OF COMPOUND OVER ALL JOINTS. JOINTS REINFORCED.
6. ACOUSTICAL SEALANT.
1/ 4"
M
IN
6" STUD
WALL LEGEND
NOTE: REF. SHEET G01.10 OR WALL TYPE DETAILS
NON-RATED PARTITION
1-HR. RATED FIRE BARRIER
SMOKE BARRIER (1-HR. RATED)
2-HR. RATED EXISTING FIRE BARRIER
NON-RATED SMOKE PARTITION
1-HR. RATED FIRE/SMOKE BARRIER
2-HR. RATED FIRE/SMOKE BARRIER
1 HR SHAFT WALL
INTERIOR WALL TYPE LEGEND
NOTE: REF GENERAL INTERIOR WALL NOTES, WALL
CONSTRUCTION & PRIORITY DETAILS, AND FIREWALL DETAILS
FOR ADDITIONAL INFORMATION. NOT ALL WALLS WILL BE
TAGGED. REFERENCE SECTIONS, DETAILS, & PLAN NOTES FOR
UNIQUE OR SPECIAL CONDITIONS.
A
A
D
E
6" MTL. STUD W/ GYPSUM BOARD ON BOTH SIDES (NON-RATED)
C
6" MTL. STUD W/ GYPSUM BOARD ON (1) SIDES
B
3 5/8" MTL. STUD W/ 2 LAYERS GYPSUM BOARD ON BOTH SIDES
H
F
G
2 1/2" MTL. STUD W/ GYPSUM BOARD ON (1) SIDE
3 5/8" MTL. STUD W/ GYPSUM BOARD ON (1) SIDE
J 7/8" FURRING CHANNELS W/ GYPSUM BOARD ON (1) SIDE
K
L 2 1/2" MTL. STUD W/ GYPSUM BOARD ON ONE SIDE WITH 2" FOIL FACED
RIGID INSULATION AT EXTERIOR WALLS
3 5/8" MTL. STUD W/ GYPSUM BOARD ON BOTH SIDES (1 HOUR FIRE
SMOKE)
3 5/8" MTL. STUD W/ GYPSUM BOARD ON BOTH SIDES (1 HOUR)
3 5/8" MTL. STUD W/ GYPSUM BOARD ON BOTH SIDES (SMOKE)
3 5/8" MTL. STUD W/ GYPSUM BOARD ON BOTH SIDES (NON-RATED)
M 3 5/8" MTL. STUD W/ GYPSUM BOARD ON ONE SIDE WITH 2" FOIL FACED
RIGID INSULATION AT EXTERIOR WALLS
N 1" THICK SHAFT LINER WITH 2 1/2" MTL. SHAFTWALL STUDS AND 5/8"
GYP. BD.
N 1 1/2" MTL. STUD W/ GYPSUM BOARD ON (1) SIDE
SECTION
NON-RATED FURRING
ABOVE CEILING ID (STENCIL):
PLAN DESIGNATION:
GENERAL NOTES:
1. ALL REQUIREMENTS OF LISTED UL DESIGN
# MUST BE MET.
WALL PRIORITY:
ACOUSTICAL SEALANT
HAT CHANNEL- 7/8" MIN
MTL STUD - 2 1/2"
AT 16" O.C. MAX.
GYPSUM WALLBOARD - 5/8"
THICK TYPE "X"
JOINT TAPE AND COMPOUND
ACOUSTICAL SEALANT
UL DESIGN #:
FIRE RATING:
GA FILE #:
STC RATING: --
OPENINGS: --
DAMPERS: --
CEILING ASSEMBLY
GYPSUM BOARD CUT TO FIT DECK
CONFIGURATION
1/ 4"
M
IN
1/ 4"
M
IN
7/8" HAT CHANNELJ SCALE:
N.T.S.
2 1/2" STUDSK
1 1/2" STUDSN
SECTION
NON-RATED
FURRING WITH
INSULATION
ABOVE CEILING ID (STENCIL):
PLAN DESIGNATION:
GENERAL NOTES:
1. ALL REQUIREMENTS OF LISTED UL DESIGN
# MUST BE MET.
WALL PRIORITY:
ACOUSTICAL SEALANT
MTL. STUDS
AT 16" O.C. MAX.
GYPSUM WALLBOARD - 5/8"
THICK TYPE "X"
JOINT TAPE AND COMPOUND
ACOUSTICAL SEALANT
UL DESIGN #:
FIRE RATING:
GA FILE #:
STC RATING: --
OPENINGS: --
DAMPERS: --
CEILING ASSEMBLY
GYPSUM BOARD CUT TO FIT
1/ 4"
M
IN
1/ 4"
M
IN
1-5/8" STUDL SCALE:
N.T.S.
2" RIGID INSULATION
3-5/8" STUDM
2HR FIRE BARRIER
UL DESIGN #:
STC RATING:
FIRE RATING:
SCALE:
16" O.C.
SECTION
PLAN
3-5/8" STUDA
U411
55 - 59
2HR
N.T.S.
DESCRIPTION:
2 43
ABOVE CEILING ID (STENCIL):
"2HR FIRE BARRIER"
PLAN DESIGNATION:
GENERAL NOTES:
1. ALL REQUIREMENTS OF LISTED UL
DESIGN # MUST BE MET.
WALL PRIORITY:
1/ 4"
M
IN
OPENINGS: 90 MIN
1. STEEL FLOOR AND CEILING CHANNELS - TOP AND BOTTOM CHANNELS OF WALL
ASSEMBLY SHALL BE MIN. 20 GA. GALV. STEEL SIZED TO FIT STUDS. TOP CHANNEL TO
HAVE 2" FLANGES (MIN). BOTTOM CHANNEL TO HAVE 1-1/4" FLANGES (MIN). SECURE
BOTTOM CHANNELS WITH STEEL FASTENERS AT 24" O.C. (MAX). SECURE TOP
CHANNELS TO VALLEYS OF STEEL FLOOR UNITS (OR STRUCTURE ABOVE) WITH STEEL
FASTENERS AT 12" O.C. (MAX).
2. STEEL STUDS - MIN. 3-5/8" WIDE, 1-1/4" LEGS, 3/8" FOLDED BACK RETURN. FORMED OF
20 GA.(MIN) GALV. STEEL. MAX. SPACING 16" O.C. CUT STUDS 1" LESS IN LENGTH THAN
ASSEMBLY HEIGHT WITH BOTTOM NESTING IN AND SECURED TO FLOOR CHANNEL, AND
WITH TOP NESTING IN CEILING CHANNEL WITHOUT ATTACHMENT.
3. SOUND ATTENUATION BATT INSUL. - 3-1/2" (DEPENDING ON STUD SIZE) GLASS FIBER
BATTS IN STUD CAVITY. FILL ENTIRE CAVITY FULL HEIGHT.
4. GYPSUM WALLBOARD- 5/8" THICK TYPE "X", 4' WIDE. OUTER LAYER PAPER OR VINYL
SURFACED. (LAMINATED SYSTEM) WALLBOARD APPLIED VERTICALLY IN TWO LAYERS.
INNER LAYER ATTACHED TO STUDS WITH 1" LONG TYPE 'S' STEEL SCREWS AT 8" O.C.
ALONG VERT. EDGES AND 12" O.C. IN THE FIELD. OUTER LAYER LAMINATED TO INNER
LAYER WITH JOINT COMPOUND APPLIED WITH A NOTCHED SPREADER PRODUCING
CONT. BEADS OF COMPOUND ABOUT 3/8" IN DIAMETER, SPACED NOT MORE THAN 2"
O.C. JOINTS OF LAMINATED OUTER LAYER OFFSET 12" FROM INNER LAYER JOINTS.
OUTER LAYER ATTACHED TO FLOOR CHANNEL WITH 1-5/8" STEEL SCREWS AT 12" O.C.
OPTIONAL (DIRECT ATTACHED SYSTEM) - INNER LAYER ATTACHED TO STUDS WITH 1"
LONG TYPE 'S' STEEL SCREWS AT 16" O.C. ALONG VERT. EDGES AND IN THE FIELD.
OUTER LAYER ATTACHED TO THE STUDS OVER THE INNER LAYER WITH 1-5/8" LONG
TYPE S STEEL SCREWS AT 16" O.C. ALONG VERT. EDGES AND IN THE FIELD AND AT 12"
O.C. TO THE FLOOR CHANNEL. OFFSET OUTER LAYER JOINTS FROM INNER LAYER
JOINTS. OUTER LAYER JOINTS MAY BE TAPED OR UNTAPED. INSTALL WALLBOARD
WITH A MIN. 1/2" AND MAX. 3/4" GAP BETWEEN THE TOP OF THE WALLBOARD AND THE
BOTTOM OF THE FLOOR UNIT VALLEYS. NO SCREWS ARE TO BE INSTALLED WITHIN 4"
OF THE STEEL FLOOR UNIT VALLEYS AT THE TOP OF THE WALL. ORIENT JOINTS
VERTICALLY AND STAGGER JOINTS ON OPPOSITE SIDES OF THE ASSEMBLY. WHEN
ATTACHED TO FURRING CHANNELS, WALLBOARD IS ATTACHED WITH 1" LONG TYPE 'S'
SCREWS AT 12" O.C.
5. JOINT TAPE AND COMPOUND - VINYL, DRY OR PRE-MIXED JOINT COMPOUND, APPLIED
IN TWO COATS TO JOINTS AND SCREW HEADS; PAPER TAPE 2" WIDE EMBEDDED IN
FIRST LAYER OF COMPOUND OVER ALL JOINTS. JOINTS REINFORCED.
6. FURRING CHANNELS (OPTIONAL NOT SHOWN) - RESILIENT 20 MSG GALV. STEEL
FURRING CHANNELS SPACED VERT. MAX. 24" O.C. ATTACH FLANGE TO EACH
INTERSECTING STUD WITH 1/2" LONG TYPE S-12 PANHEAD SCREWS.
7. ACOUSTICAL SEALANT.
8. PACKING MATERIAL - MIN. 4" TKNS. OF MIN. 4.0 PCF MINERAL WOOL BATT INSULATION
FIRMLY PACKED INTO FLUTES OF STEEL FLOOR UNITS AS A PERMANENT FORM.
PACKING MATERIAL TO BE RECESSED FROM BOTH SURFACES OF THE WALL AS
REQUIRED TO RECEIVE JOINT SEALANT.
9. JOINT TREATMENT MATERIAL - NON-SAG FIRE CAULK EACH SIDE MIN THICKNESS 1/2",
APPLIED WITHIN THE OPENING BETWEEN THE TOP OF THE WALLBOARD AND ALL
SURFACES OF THE STEEL FLOOR OR STRUCTURE, FLUSH WITH BOTH SURFACES OF
THE WALL ASSEMBLY.
1/ 8"
M
IN
SECTION
1HR SHAFTWALL
ABOVE CEILING ID (STENCIL):
"1HR FIRE BARRIER"
LIFE SAFETY PLAN DESIGNATION:
GENERAL NOTES:
1. ALL REQUIREMENTS OF LISTED UL DESIGN
# MUST BE MET.
WALL PRIORITY:
JOINT TREATMENT MATERIAL
INSULATION - MIN. 3" MINERAL
WOOL BATTS, FRICTION FITTED TO
FILL CAVITY
VENTED STEEL CH-STUDS- 20
GA,2-1/2" MIN AT 24" O.C.
GYPSUM WALLBOARD - 5/8" THICK
TYPE "X". STAGGER JOINTS
JOINT TAPE AND COMPOUND
STEEL FLOOR J-CHANNELS 1/2"
CONTINUOUS SEALANT PER UL
DESIGN REQUIREMENTS
UL DESIGN #:
FIRE RATING:
U469
1HR
GA FILE #:
STC RATING: 35 - 39
OPENINGS: 45 MIN W/ CLOSER
DAMPERS: FIRE
CEILING ASSEMBLY
STEEL CEILING J-RUNNERS
ACOUSTICAL GASKET AT FLOOR
TRACK
GYPSUM BOARD CUT TO FIT DECK
CONFIGURATION
SHAFT ROOM
1/ 2"
M
IN
5/ 8"
M A
X
GYPSUM SHAFTLINER - 1" THICK
TYPE "X"
3 1/8"
SHAFT WALL STUDN
12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554
©Copyright 2019
TLC No.:
www.tlc-engineers.com
118626
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg.
PROJECT TEAM:
Office of
Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
Department of Veterans Affairs
MURFREESBORO, TN
615.370.8500
615.370.8530 hfrdesign.com
214 Centerview Drive Suite 300 Brentwood, TN 37027
Phase
FULLY SPRINKLERED
C U s e rs \a tr a y lo r\ D o c u m e n ts
\M b o ro V
A W a rd b
R e n o a tr a y lo r2 X
N D
H .r v t
/1
/2
:2
:0
P
M
04-14-2023
626A4-19-101
GI 01.10
AE RENOVATE WARD 1BWALL TYPE DETAILS
AT/MC
HFR Project No: 2019056
100% CONSTRUCTION
DOCUMENTS
● USE SEMI-GLOSS PAINT.
● LOCATE NOT MORE THAN 12'-0" O.C. ON CORRIDOR SIDES OF PARTITIONS, AND WITH A LEAST ONE MESSAGE
PER WALL ON ROOM SIDE OF PARTITION, AND WITHIN 15'-0" OF THE END OF EACH WALL.
● STENCIL MESSAGE SIMILAR TO: "SMOKE PARTITION" OR "1-HR FIRE BARRIER."
● IDENTIFY PARTITIONS ABOVE CEILINGS ON BOTH SIDES OF PARTITIONS EXCEPT WITHIN SHAFTS IN RED
LETTERS NOT LESS THAN 4" HIGH WITH AT LEAST A 3/8" STROKE.
12. FIRE AND SMOKE PARTITION / BARRIER IDENTIFICATION:
11. PENETRATIONS IN WALLS SHALL BE SEALED AS REQUIRED BY THE WALL RATING PER AN APPROVED UL DESIGN.
10. GYPBOARD PANELS SHALL BE PLACED A MINIMUM OF 1/4" ABOVE FLOOR AND SHALL BE CUT WITHIN 1/4" MAX TOLERANCE TO SHAPE OF DECK OR STRUCTURE ABOVE. GAPS BETWEEN PANELS SHALL BE <1/4".
● PROVIDE DEFLECTION AND BRIDGING CLIPS.
● MAINTAIN CLEARANCE UNDER STRUCTURAL BUILDING MEMBERS TO AVOID DEFLECTION TRANSFER TO STUDS.
PROVIDE NESTED OR SLOTTED EXTENDED LEG CEILING TRACK RUNNERS.
9. DO NOT TRANSFER DEFLECTION FROM STRUCTURAL BUILDING MEMBERS TO STUDS. CONTRACTOR'S OPTION, PROVIDE EITHER OF THE FOLLOWING:
8. EXTEND ALL WALL CONSTRUCTION TO THE DECK ABOVE AND SEAL U.N.O.
7. INSTALL ACOUSTICAL GASKETS AT FLOOR AND CEILING TRACK LOCATIONS.
6. PROVIDE ACOUSTICAL INSULATION FULL HEIGHT IN ALL WALLS U.N.O.
5. STAGGER JOINTS ON OPPOSITE SIDES OF PARTITIONS.
4. ALL FRAMING SHALL BE 20 GA U.N.O.
● PROVIDE FIRE RATED IMPACT RESISTANT GYPBOARD 4'-0"H ON ALL WALLS IN PATIENT ROOMS, 4'-0"H AT ALL EQUIPMENT ALCOVES AND ROOMS NOT SCHEDULED TO RECEIVE RIGID WALL PROTECTION, AND ADDITIONAL LOCATIONS AS NOTED ON DRAWINGS. (IMPACT RESISTANT GYPBOARD SHALL TAKE PRIORITY AT LOCATIONS
INDICATED TO RECEIVE GLASS FIBER FACED GYPSUM PANELS.)
● PROVIDE FIRE RATED GLASS FIBER FACED GYPSUM PANELS ON INTERIOR SURFACE OF EXTERIOR WALLS, TOILET ROOMS, JANITOR'S CLOSETS, MECHANICAL SPACES, AND WITHIN 4'-0" OF WATER SOURCES.
● ALL GYPBOARD SHALL BE 5/8" TYPE 'X' U.N.O.
3. GYPBOARD REQUIREMENTS:
2. TOILET WETWALLS AND PATIENT ROOM HEADWALLS SHALL BE 6" METAL STUDS
1. ALL WALLS SHALL BE 3-5/8" METAL STUD AT 16"0.C. MAX U.N.O.
REFERENCE WALL TYPE DETAILS, PLANS, AND SPECIFICATIONS.
GENERAL WALL NOTES
No. Date Description
GENERAL NOTES
1. THIS IS DIAGRAMMATIC IN NATURE AND SHOWS GENERIC
CONDITIONS. SEE FLOOR PLANS FOR ACTUAL CONDITIONS.
2. MAINTAIN NOTED CLEARANCES AT ALL DOORS.
MIN
18"
M
IN
(A)
FRONT APPROACH, PULL SIDE
M
IN
(B)
FRONT APPROACH, PUSH SIDE
M
IN
(C)
FRONT APPROACH, PUSH SIDE,
DOOR PROVIDED WITH BOTH
CLOSER AND LATCH
MIN
12" MIN
36"
M
IN
(D)
HINGE APPROACH, PULL SIDE
M
IN
(F)
HINGE APPROACH, PUSH SIDE
MIN
42"
M
IN
(E)
HINGE APPROACH, PULL SIDE
MIN
22" 48
M
IN
(G)
HINGE APPROACH, PUSH SIDE,
DOOR PROVIDED WITH BOTH
CLOSER AND LATCH
MIN
22"
MIN
24"
M
IN
(H)
LATCH APPROACH, PULL SIDE
MIN
24"
M
IN
(I)
LATCH APPROACH, PULL SIDE,
DOOR PROVIDED WITH
CLOSER
M
IN
(J)
LATCH APPROACH, PUSH SIDE
MIN
24" 48
M
IN
(K)
LATCH APPROACH, PUSH SIDE,
DOOR PROVIDED WITH CLOSER
MIN
24"
MIN
18"
M
IN
(A)
PULL SIDE
X > 8"
MANEUVERING CLEARANCES AT RECESSED
DOORS AND GATES
MANEUVERING CLEARANCES AT MANUAL
SWINGING DOORS AND GATES
(B)
PUSH SIDE
M
IN
X > 8"
(C)
PUSH SIDE, DOOR PROVIDED
WITH BOTH CLOSER AND
LATCH
M
IN
X > 8"
MIN
12"
DOORS IN SERIES AND GATES IN SERIES
(A)
48" MIN
(B)
48" MIN
(C)
48" MIN
(BACK)(SIDE CONTROL WALL) (SIDE)
T .O
. S E
A T
SOME ITEMS MAY NOT BE APPLICABLE
HCWV
GB/U GB/U
CONTROL
AREA
GB-24
GB-24
GB-42
HCT
GB-12
DF
HCDF
MIRROR
TPD
TB-18
FPDL
URINAL SCREEN
EXTEND MIN 18"
FROM WALL
BCS
PTD-WR
GB-18
C L P
U
LL
H A
N D
LE
C L F
LU
S
H C
O N
T R
O L
GB-18 INSULATED
SUPPLY AND
DRAIN LINES
TPD
C L F
LU
S
H C
O N
T R
O L
M A
X
M A
X
M A
X
M A
X
M A
X
M
IN
T O
S P
O U
T
M A
X
M
IN
M A
X H
.C . H
T
M
A X
MIN
13 1/2"
TO PLAN)
(REFER
AMBULATORY
36"W (±1")
60"D MIN
59"D MIN: FLOOR MNT WC
66" WIDE
56"D MIN: WALL HUNG WC
17" ±1"
H E
IG
H
T
S T
A N
D A
R D
S U
R F
A C
E
M A
X T
O R
E F
LE
C
T
IV
E
25"MAX
17"MIN
MIN
30"
MIN
60"
S U
R F
A C
E
T .O
G
R
IP
P
IN
G
M A
X
6" MAX
MIN
30" 36" 36"
1"
1"
18"
36"
18"
S U
R F
A C
E
T .O
G
R
IP
P
IN
G 6"
M A
X
1"
M
IN
T O
O U
T
LE
T
M
IN
M A
X
15" MIN
T O
S P
O U
T
M A
X
C O
N T
R O
LS
M A
X T
O
M
IN
30" MIN
MIN
12"
9"
MAX
12"
MIN
24"
MAX
24"
MIN
24"
S U
R F
A C
E
T .O
G
R
IP
P
IN
G 3"
-6
4" MAX
G R
IP
S
U R
F A
C E
T .O
1"
42" MIN
MAX
12"
40" ±1"
S U
R F
A C
E
M A
X T
O R
E F
LE
C
T
IV
E
18" OR 24"
H .C
. H T
M A
X
(FRONT) (SIDE)
M A
X
M
IN
TO PLAN)
(REFER
M
IN9"
CLEAR
30" MIN
4" MAX 32" MIN 32" MIN
1"
4" MAX
1"
(BACK) (CONTROL WALL)
GB/L
CURTAIN
ROD
CONTROL
AREA
M
IN
M A
X
FLUSH
VALVE
M A
X
6" MAX
36" MIN
60" MIN±1"
17"
GB-36
CLEAR
15" MIN
CLEAR
15" MIN
8" (±1")
M A
X
T O
S P
O U
T
C O
N T
R O
LS
H C
A C
C E
S S
IB
LE
"54
MIN
15"
M A
X
CONTROL
AREA
MAX
15"
M
IN
CONTROL
AREA, IF
SEAT
PROVIDED
PROVIDED
27" MAX
IF SEAT
M A
X
M
IN6" MAX
PTD
M A
X
M A
X
C O
N T
R O
LS
M A
X
SD
M A
X
5" MAX 42
M A
X
C O
N T
R O
LS
EHD EHD-HF
C O
N T
R O
LS
C O
N T
R O
LS
C O
N T
R O
LS
UNOBSTRUCTED ITEMS
MAX
24". 44
M A
X
C O
N T
R O
LS
PAPER TOWEL
DISPENSER & WASTE
RECEPTACLE (PTD-WR)
C O
N T
R O
LSFPDR
PAPER
TOWEL
DISPENSER
(PTD)
ELECTRIC
HAND DRYER
(EHD)
ELECTRIC
HAND DRYER -
HANDS FREE
(EHD-HF)
SOAP
DISPENSER
(SD)
MIN
15" 5" MAX
FEMININE
PRODUCT
DISPENSER
(FNDR)
M A
X
FEMININE
PRODUCT
DISPOSAL UNIT
(FNDL)
SD (ONLY) SD, PTD, EHD
OR EHD-HF
BACK WALL
MOUNTED
OBSTRUCTED ITEMS
SIDE WALL
MOUNTED
H.C.
TELEPHONE
(HCT)
DRINKING
FOUNTAIN
(DF)
H.C.
DRINKING
FOUNTAIN
(HCDF)
(FRONT) (SIDE)
TOILET PAPER
DISPENSER
(TPD)
TOWEL BAR
18" MIN
(TB-18)
BABY CHANGING STATION
(BCS)
TYPICAL PARTITION SPACING
(RE: ENLARGED PLANS FOR ACTUAL DIM'S & SPEC'S FOR ACTUAL TYPE OF PARTITIONS)
18" ±1
MIN
12".
MIN
24".
G R
IP
S
U R
F A
C E
T .O
HC WATER CLOSET
(HCWC)
GRAB BAR
42" (GB-42)
(SIDE) (FRONT)
GRAB BAR
18" (GB-18)
GRAB BAR
36" (GB-36)
M
IN
54" MIN
HC LAVATORY
(SIDE) (FRONT)
COAT HOOK
(CH)
(FRONT) (SIDE)
(FRONT)
MIRROR WITH OR
WITHOUT SHELF
(MIR/S-18X36)
(MIR-18X36)
(MIR/S-24X36)
(MIR-24X36)
(CONTROL)
GRAB BAR
18" (GB-18)
HC BATHTUB
(HCBT)
NOTE: BATHTUBS SHALL DELIVER
WATER THAT IS 120 DEGREES MAX.
GRAB BAR
24" (GB-24)
(BACK) (HEAD)
GRAB BAR
12" (GB-12)
M
IN
S U
R F
A C
E
T .O
G
R
IP
P
IN
G
REMOVABLE IN-TUB
SEAT MIN 15"-16"
MAX DEEP
ROLL IN SHOWER
(RS)
CONT. "U" SHAPED GRAB
BAR (GB/U)
MAX
6"
MAX
6"
GB/L
CONT. "L" SHAPED GRAB BAR
(GB/L)
TRANSFER SHOWER
(TS)
(SIDE)
(CONTROLS ON ANY WALL
IF NO SEAT IS PROVIDED)
EXAM
ROOM
DOCTOR'S
OFFICE
NURSE
STATION
JANITOR'S
CLOSET
RECEPTION /
FILES
MECHANICAL
SPACE
BREAK
ROOM
PUBLIC USE SPACES (SEC 201)
FULL ACCESS TO PUBLIC USE
AREAS, INCLUDING WAITING
AREAS AND CORRIDORS
MECHANICAL SPACE (SEC 203.5)
EXEMPT SPACE
EMPLOYEE WORK AREAS (SEC 203.9)
PARTIAL ACCESS TO AREAS USED
ONLY BY EMPLOYEES FOR WORK
(RECEPTION / FILE AREAS, NURSE
STATIONS, AND JANITOR'S CLOSETS
EXAM ROOMS AND OFFICES
(SEC 201 AND 203.9)
ALL EXAM ROOMS AND OFFICES
USED BY THE PUBLIC MUST BE
ACCESSIBLE, BUT ELEMENTS
WITHIN THESE ROOMS THAT
ARE USED ONLY BY EMPLOYEES
FOR WORK ARE NOT REQUIRED
TO COMPLY.
DRESSING ROOMS (SEC 222)
ACCESS IS REQUIRED TO AT
LEAST 5% (BUT NO LESS THAN 1)
OF EACH TYPE OF USE IN EACH
CLUSTER
TOILET ROOMS (SEC 213)
ACCESS IS REQUIRED TO ALL PUBLIC
AND EMPLOYEE TOILET ROOMS (OR
NO MORE THAN 50% OF SINGLE
USER TOILET ROOMS FOR EACH USE
AT EACH CLUSTER)
COMMON USE (NON-WORK)
AREAS (SEC 201)
FULL ACCESS TO BREAK ROOMS
AND TO OTHER EMPLOYEE AREAS
NOT USED FOR WORK PURPOSES.
GENERAL EXCEPTIONS (§203):
THESE STRUCTURES AND SPACES ARE FULLY EXEMPT FROM THE STANDARDS AND ARE NOT REQUIRED TO BE ACCESSIBLE OR ON AN ACCESSIBLE ROUTE:
• CONSTRUCTION SITES (§203.2): STRUCTURES DIRECTLY ASSOCIATED WITH THE ACTUAL PROCESSES OF CONSTRUCTION AND PORTABLE TOILETS USED ONLY BY CONSTRUCTION WORKERS. (EXAMPLES: SCAFFOLDING, BRIDGING, MATERIALS HOISTS, CONSTRUCTION TRAILERS)
• AREAS RAISED FOR SECURITY/ SAFETY (§203.3): AREAS RAISED PRIMARILY FOR PURPOSES OF SECURITY OR LIFE/ FIRE SAFETY. (EXAMPLES: LIFE GUARD STANDS, FIRE
TOWERS, AND PRISON GUARD TOWERS)
• RAISED WORK AREAS (§203.9): EMPLOYEE WORK AREAS UNDER 300 S.F. THAT ARE ELEVATED AT LEAST 7” AS AN ESSENTIAL FUNCTIONAL CONDITION OF THE SPACE (EXCLUDING RAISED COURTROOM STATIONS. (EXAMPLE: WORK AREAS WITH EQUIPMENT/ MACHINERY THAT MUST BE OPERATED FROM A PLATFORM)
• LIMITED ACCESS SPACES (§203.4): SPACES ACCESSED ONLY BY LADDERS, CATWALKS, CRAWL SPACES, OR VERY NARROW PASSAGEWAYS. (EXAMPLES: LIGHTING/ EQUIPMENT
CATWALKS AT STAGES AND PERFORMING AREAS, PLATFORMS SERVED ONLY BY LADDER.)
• MACHINERY SPACES (§203.5): SPACES USED ONLY BY SERVICE PERSONNEL FOR MAINTENANCE, REPAIR, OR OCCASIONAL MONITORING OF EQUIPMENT. (EXAMPLES: ELEVATOR PITS/ PENTHOUSES, MECHANICAL/ ELECTRICAL/ COMMUNICATIONS EQUIPMENT ROOMS, WATER OR SEWAGE TREATMENT PUMP ROOMS, ELECTRIC SUBSTATIONS, AND
TRANSFORMER VAULTS.)
• SINGLE OCCUPANT STRUCTURES (§203.6): SINGLE OCCUPANT STRUCTURES ACCESSED ONLY BY BELOW-GRADE PASSAGEWAYS OR ELEVATED ABOVE STANDARD CURB HEIGHT.
(EXAMPLES: TOLL BOOTHS THAT ARE ACCESSED BY UNDERGROUND TUNNELS OR ELEVATED ABOVE CURB HEIGHT, SUCH AS THOSE SERVING DEDICATED TRUCK LANES.)
ACCESSIBILITY EXAMPLE OF CLINICAL SUITE
12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554
©Copyright 2019
TLC No.:
www.tlc-engineers.com
118626
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg.
PROJECT TEAM: