About this file

This document provides wall construction details for a federal construction project to renovate Ward 1B at the Alvin C. York VA Medical Center in Murfreesboro, Tennessee. Key details include specifications for 1-hour and 2-hour fire-rated walls, smoke barriers, and non-rated partitions. Wall assemblies are to be constructed using steel studs spaced at 16 inches on center with two layers of 5/8-inch fire-rated gypsum wallboard on both sides for fire barriers. Openings in fire-rated walls must be sealed per the approved UL design to maintain the required rating. Identification messages and stenciling requirements are also provided.

The related federal contract opportunity is solicitation number 36C24923R0114 for the renovation project issued by the Department of Veterans Affairs Veterans Health Administration. The solicitation involves renovating Ward 1B at the Alvin C. York VA Medical Center located in Murfreesboro, Tennessee.

View the file

Other files

File Type Posted
36C24923R0114 0003.docx DOCX document
E-EI-01 - PARTIAL ELECTRICAL RISER DIAGRAM - DEMOLITION.pdf PDF
119437-Alvin C. York VAMC Renovate Ward 1B - Revision 1 - Electrical Narrative.pdf PDF
Government Answers to Industry Questions.pdf PDF
283100.pdf PDF
275223.pdf PDF
Bradley_GrabBar_8370-107.pdf PDF
Ward 1B - Revision 1.pdf PDF
Renovate Ward 1B Pre-Proposal Sign in Sheet - 07-06-2023.pdf PDF
E-EI-02 - PARTIAL ELECTRICAL RISER DIAGRAM - NEW WORK.pdf PDF
Bradley_GrabBar_8370-108.pdf PDF
General Decision Number TN20230187 06-30-2023 Rutherford County TN.pdf PDF
ASI 3413-25.pdf PDF
36C24923R0114 0002.docx DOCX document
GAMCO 125SwingUpTP.pdf PDF
Interior Wall Type Legend.pdf PDF
SUBCONTRACTOR INFORMATION AND CONSENT FORM.docx DOCX document
36C24923R0114 0001.docx DOCX document
MECH BINDER.pdf PDF
Ward 1B - Specs - Vol. 2.pdf PDF
GD Number TN20230187 05-12-2023.pdf PDF
GI 01-02 - CONSTRUCTION STAGING PLAN.pdf PDF
GI 03-01 - SECOND FLOOR ICRA PLAN.pdf PDF
GI 05-01 - PHASING PLANS.pdf PDF
GI 00-01 - COVER SHEET.pdf PDF
Price Schedule Project 626A4-19-101 Renovate Ward 1B.xlsx XLSX spreadsheet
GI 04-02 - LEAD PAINT AND TRANSITE PANELS.pdf PDF
36C24923R0114.docx DOCX document
General Conditions Breakout.xlsx XLSX spreadsheet
WARD 1B - ARCH BINDER.pdf PDF
GI 01-20 - ACCESSIBILITY DETAILS.pdf PDF
RFI Form.docx DOCX document
GI 04-01 - ACM DUCT WORK AND ACM PIPE INSULATION.pdf PDF
Performance Relevancy Survey Form - 626A4-19-101 Renovate Ward 1B.docx DOCX document
Ward 1B - Specs - Vol. 1.pdf PDF
VN 01-00 - PATIENT LIFT VENDOR DRAWINGS.pdf PDF
ELECTRICAL BINDER.pdf PDF
PLUMBING BINDER.pdf PDF
GI 01-01 - GENERAL DATA.pdf PDF
TECH BINDER.pdf PDF
WARD 1B - GENERAL.pdf PDF
WARD 1B - INTERIORS .pdf PDF
Calculation of Self Performed Work.docx DOCX document
GI 02-01 - THIRD FLOOR LIFE SAFETY PLAN - OVERALL.pdf PDF
AD 01-01 - THIRD FLOOR DEMOLITION PLAN - OVERALL.pdf PDF
Contractor EMR Certification Form.docx DOCX document
FP BINDER.pdf PDF
GI 03-02 - THIRD FLOOR ICRA PLAN.pdf PDF
Show all 48

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

1HR FIRE/SMOKE BARRIER

UL DESIGN #:

STC RATING:

FIRE RATING:

SCALE:

16" O.C.

SECTION

PLAN

3-5/8" STUDB

U465

45 - 49

1HR

N.T.S.

DESCRIPTION:

2 43

ABOVE CEILING ID (STENCIL):

"1HR FIRE/SMOKE BARRIER"

PLAN DESIGNATION:

GENERAL NOTES:

1. ALL REQUIREMENTS OF LISTED UL

DESIGN # MUST BE MET.

WALL PRIORITY:

1/ 4"

M

IN

OPENINGS: 45 MIN

1. STEEL FLOOR AND CEILING CHANNELS - TOP AND BOTTOM CHANNELS OF WALL

ASSEMBLY SHALL BE MIN. 20 GA. GALV. STEEL SIZED TO FIT STUDS. TOP CHANNEL TO

HAVE 2" FLANGES (MIN). BOTTOM CHANNEL TO HAVE 1-1/4" FLANGES (MIN). SECURE

BOTTOM CHANNELS WITH STEEL FASTENERS AT 24" O.C. (MAX). SECURE TOP

CHANNELS TO VALLEYS OF STEEL FLOOR UNITS (OR STRUCTURE ABOVE) WITH STEEL

FASTENERS AT 12" O.C. (MAX).

2. STEEL STUDS - MIN. 3-5/8" WIDE, 1-1/4" LEGS, 3/8" FOLDED BACK RETURN. FORMED OF

20 GA.(MIN) GALV. STEEL. MAX. SPACING 16" O.C. CUT STUDS 1" LESS IN LENGTH THAN

ASSEMBLY HEIGHT WITH BOTTOM NESTING IN AND SECURED TO FLOOR CHANNEL, AND

WITH TOP NESTING IN CEILING CHANNEL WITHOUT ATTACHMENT.

3. SOUND ATTENUATION BATT INSUL. - 3-1/2" (DEPENDING ON STUD SIZE) GLASS FIBER

BATTS IN STUD CAVITY. FILL ENTIRE CAVITY FULL HEIGHT.

4. GYPSUM WALLBOARD- 5/8" THICK TYPE "X", 4' WIDE, ATTACHED TO STEEL STUDS AND

FLOOR CHANNELS WITH 1" LONG TYPE S SELF-TAPPING STEEL SCREWS AT 8" O.C.

ALONG THE VERTICAL AND BOTTOM EDGES AND 12" O.C. IN THE FIELD OF THE BOARD.

INSTALL WALLBOARD WITH A MIN. 1/2" AND MAX. 3/4" GAP BETWEEN THE TOP OF THE

WALLBOARD AND THE BOTTOM OF THE FLOOR UNIT VALLEYS (OR STRUCTURE ABOVE).

NO SCREWS ARE TO BE INSTALLED WITHIN 4" OF THE STEEL FLOOR UNIT VALLEYS AT

THE TOP OF THE WALL. ORIENT JOINTS VERTICALLY AND STAGGER JOINTS ON

OPPOSITE SIDES OF THE ASSEMBLY. WHEN ATTACHED TO FURRING CHANNELS,

WALLBOARD IS ATTACHED WITH 1" LONG TYPE S SCREWS AT 12" O.C.

5. JOINT TAPE AND COMPOUND - VINYL, DRY OR PRE-MIXED JOINT COMPOUND, APPLIED

IN TWO COATS TO JOINTS AND SCREW HEADS; PAPER TAPE 2" WIDE EMBEDDED IN

FIRST LAYER OF COMPOUND OVER ALL JOINTS. JOINTS REINFORCED.

6. FURRING CHANNELS (OPTIONAL NOT SHOWN) - RESILIENT 20 MSG GALV. STEEL

FURRING CHANNELS SPACED VERT. MAX. 24" O.C. ATTACH FLANGE TO EACH

INTERSECTING STUD WITH 1/2" LONG TYPE S-12 PANHEAD SCREWS.

7. ACOUSTICAL SEALANT.

8. PACKING MATERIAL - MIN. 4" TKNS. OF MIN. 4.0 PCF MINERAL WOOL BATT INSULATION

FIRMLY PACKED INTO FLUTES OF STEEL FLOOR UNITS AS A PERMANENT FORM.

PACKING MATERIAL TO BE RECESSED FROM BOTH SURFACES OF THE WALL AS

REQUIRED TO RECEIVE JOINT SEALANT.

9. JOINT TREATMENT MATERIAL - NON-SAG FIRE CAULK EACH SIDE MIN THICKNESS 1/2",

APPLIED WITHIN THE OPENING BETWEEN THE TOP OF THE WALLBOARD AND ALL

SURFACES OF THE STEEL FLOOR OR STRUCTURE, FLUSH WITH BOTH SURFACES OF

THE WALL ASSEMBLY.

7/

8" M

IN

1HR FIRE BARRIER

UL DESIGN #:

STC RATING:

FIRE RATING:

SCALE:

16" O.C.

SECTION

PLAN

3-5/8" STUDC

U465

45 - 49

1HR

N.T.S.

DESCRIPTION:

2 43

ABOVE CEILING ID (STENCIL):

"1HR FIRE BARRIER"

PLAN DESIGNATION:

GENERAL NOTES:

1. ALL REQUIREMENTS OF LISTED UL

DESIGN # MUST BE MET.

WALL PRIORITY:

1/ 4"

M

IN

OPENINGS: 45 MIN

1. STEEL FLOOR AND CEILING CHANNELS - TOP AND BOTTOM CHANNELS OF WALL

ASSEMBLY SHALL BE MIN. 20 GA. GALV. STEEL SIZED TO FIT STUDS. TOP CHANNEL TO

HAVE 2" FLANGES (MIN). BOTTOM CHANNEL TO HAVE 1-1/4" FLANGES (MIN). SECURE

BOTTOM CHANNELS WITH STEEL FASTENERS AT 24" O.C. (MAX). SECURE TOP

CHANNELS TO VALLEYS OF STEEL FLOOR UNITS (OR STRUCTURE ABOVE) WITH STEEL

FASTENERS AT 12" O.C. (MAX).

2. STEEL STUDS - MIN. 3-5/8" WIDE, 1-1/4" LEGS, 3/8" FOLDED BACK RETURN. FORMED OF

20 GA.(MIN) GALV. STEEL. MAX. SPACING 16" O.C. CUT STUDS 1" LESS IN LENGTH THAN

ASSEMBLY HEIGHT WITH BOTTOM NESTING IN AND SECURED TO FLOOR CHANNEL, AND

WITH TOP NESTING IN CEILING CHANNEL WITHOUT ATTACHMENT.

3. SOUND ATTENUATION BATT INSUL. - 3-1/2" (DEPENDING ON STUD SIZE) GLASS FIBER

BATTS IN STUD CAVITY. FILL ENTIRE CAVITY FULL HEIGHT.

4. GYPSUM WALLBOARD- 5/8" THICK TYPE "X", 4' WIDE, ATTACHED TO STEEL STUDS AND

FLOOR CHANNELS WITH 1" LONG TYPE S SELF-TAPPING STEEL SCREWS AT 8" O.C.

ALONG THE VERTICAL AND BOTTOM EDGES AND 12" O.C. IN THE FIELD OF THE BOARD.

INSTALL WALLBOARD WITH A MIN. 1/2" AND MAX. 3/4" GAP BETWEEN THE TOP OF THE

WALLBOARD AND THE BOTTOM OF THE FLOOR UNIT VALLEYS (OR STRUCTURE ABOVE).

NO SCREWS ARE TO BE INSTALLED WITHIN 4" OF THE STEEL FLOOR UNIT VALLEYS AT

THE TOP OF THE WALL. ORIENT JOINTS VERTICALLY AND STAGGER JOINTS ON

OPPOSITE SIDES OF THE ASSEMBLY. WHEN ATTACHED TO FURRING CHANNELS,

WALLBOARD IS ATTACHED WITH 1" LONG TYPE S SCREWS AT 12" O.C.

5. JOINT TAPE AND COMPOUND - VINYL, DRY OR PRE-MIXED JOINT COMPOUND, APPLIED

IN TWO COATS TO JOINTS AND SCREW HEADS; PAPER TAPE 2" WIDE EMBEDDED IN

FIRST LAYER OF COMPOUND OVER ALL JOINTS. JOINTS REINFORCED.

6. FURRING CHANNELS (OPTIONAL NOT SHOWN) - RESILIENT 20 MSG GALV. STEEL

FURRING CHANNELS SPACED VERT. MAX. 24" O.C. ATTACH FLANGE TO EACH

INTERSECTING STUD WITH 1/2" LONG TYPE S-12 PANHEAD SCREWS.

7. ACOUSTICAL SEALANT.

8. PACKING MATERIAL - MIN. 4" TKNS. OF MIN. 4.0 PCF MINERAL WOOL BATT INSULATION

FIRMLY PACKED INTO FLUTES OF STEEL FLOOR UNITS AS A PERMANENT FORM.

PACKING MATERIAL TO BE RECESSED FROM BOTH SURFACES OF THE WALL AS

REQUIRED TO RECEIVE JOINT SEALANT.

9. JOINT TREATMENT MATERIAL - NON-SAG FIRE CAULK EACH SIDE MIN THICKNESS 1/2",

APPLIED WITHIN THE OPENING BETWEEN THE TOP OF THE WALLBOARD AND ALL

SURFACES OF THE STEEL FLOOR OR STRUCTURE, FLUSH WITH BOTH SURFACES OF

THE WALL ASSEMBLY.

7/

8" M

IN

SMOKETIGHT PARTITION

UL DESIGN #:

STC RATING:

FIRE RATING:

SCALE:

16" O.C.

SECTION

PLAN

3-5/8" STUDD

45 - 49

N.T.S.

DESCRIPTION:

2 43

ABOVE CEILING ID (STENCIL):

"NON-RATED SMOKETIGHT"

PLAN DESIGNATION:

GENERAL NOTES:

1. ALL REQUIREMENTS OF LISTED UL

DESIGN # MUST BE MET.

WALL PRIORITY:

1/ 4"

M

IN

OPENINGS: SM

1. STEEL FLOOR AND CEILING CHANNELS - TOP AND BOTTOM CHANNELS OF WALL

ASSEMBLY SHALL BE MIN. 20 GA. GALV. STEEL SIZED TO FIT STUDS. TOP CHANNEL TO

HAVE 2" FLANGES (MIN). BOTTOM CHANNEL TO HAVE 1-1/4" FLANGES (MIN). SECURE

BOTTOM CHANNELS WITH STEEL FASTENERS AT 24" O.C. (MAX). SECURE TOP

CHANNELS TO VALLEYS OF STEEL FLOOR UNITS (OR STRUCTURE ABOVE) WITH STEEL

FASTENERS AT 12" O.C. (MAX).

2. STEEL STUDS - MIN. 3-5/8" WIDE (UNLESS NOTED OTHERWISE), 1-1/4" LEGS, 3/8" FOLDED

BACK RETURN. FORMED OF 20 GA.(MIN) GALV. STEEL. MAX. SPACING 16" O.C. CUT

STUDS 1" LESS IN LENGTH THAN ASSEMBLY HEIGHT WITH BOTTOM NESTING IN AND

SECURED TO FLOOR CHANNEL, AND WITH TOP NESTING IN CEILING CHANNEL WITHOUT

ATTACHMENT.

3. SOUND ATTENUATION BATT INSUL. - 3-1/2" (DEPENDING ON STUD SIZE) GLASS FIBER

BATTS IN STUD CAVITY. FILL ENTIRE CAVITY FULL HEIGHT.

4. GYPSUM WALLBOARD- 5/8" THICK TYPE "X", 4' WIDE, ATTACHED TO STEEL STUDS AND

FLOOR CHANNELS WITH 1" LONG TYPE S SELF-TAPPING STEEL SCREWS AT 8" O.C.

ALONG THE VERTICAL AND BOTTOM EDGES AND 12" O.C. IN THE FIELD OF THE BOARD.

INSTALL WALLBOARD WITH A MIN. 1/2" AND MAX. 3/4" GAP BETWEEN THE TOP OF THE

WALLBOARD AND THE BOTTOM OF THE FLOOR UNIT VALLEYS (OR STRUCTURE ABOVE).

NO SCREWS ARE TO BE INSTALLED WITHIN 4" OF THE STEEL FLOOR UNIT VALLEYS AT

THE TOP OF THE WALL. ORIENT JOINTS VERTICALLY AND STAGGER JOINTS ON

OPPOSITE SIDES OF THE ASSEMBLY.

5. JOINT TAPE AND COMPOUND - VINYL, DRY OR PRE-MIXED JOINT COMPOUND, APPLIED

IN TWO COATS TO JOINTS AND SCREW HEADS; PAPER TAPE 2" WIDE EMBEDDED IN

FIRST LAYER OF COMPOUND OVER ALL JOINTS. JOINTS REINFORCED.

6. ACOUSTICAL SEALANT.

7. JOINT TREATMENT MATERIAL - NON-SAG FIRE CAULK EACH SIDE MIN THICKNESS 1/2",

APPLIED WITHIN THE OPENING BETWEEN THE TOP OF THE WALLBOARD AND ALL

SURFACES OF THE STEEL FLOOR OR STRUCTURE, FLUSH WITH BOTH SURFACES OF

THE WALL ASSEMBLY.

V A

R

IE

S

NON-RATED PARTITION

16" O.C.

SECTION

PLAN

E 3-5/8" STUD

F

DESCRIPTION:

2 43

UL DESIGN #:

STC RATING:

FIRE RATING:

SCALE:

45 - 49

N.T.S.

ABOVE CEILING ID (STENCIL):

PLAN DESIGNATION:

GENERAL NOTES:

1. ALL REQUIREMENTS OF LISTED UL

DESIGN # MUST BE MET.

WALL PRIORITY:

OPENINGS: --

V

A R

IE

S

1. STEEL FLOOR AND CEILING CHANNELS - TOP AND BOTTOM CHANNELS OF WALL

ASSEMBLY SHALL BE MIN. 20 GA. GALV. STEEL SIZED TO FIT STUDS. TOP CHANNEL TO

HAVE 2" FLANGES (MIN). BOTTOM CHANNEL TO HAVE 1-1/4" FLANGES (MIN). SECURE

BOTTOM CHANNELS WITH STEEL FASTENERS AT 24" O.C. (MAX). SECURE TOP

CHANNELS TO VALLEYS OF STEEL FLOOR UNITS (OR STRUCTURE ABOVE) WITH STEEL

FASTENERS AT 12" O.C. (MAX).

2. STEEL STUDS - MIN. 3-5/8" WIDE (UNLESS NOTED OTHERWISE), 1-1/4" LEGS, 3/8" FOLDED

BACK RETURN. FORMED OF 20 GA.(MIN) GALV. STEEL. MAX. SPACING 16" O.C. CUT

STUDS 1" LESS IN LENGTH THAN ASSEMBLY HEIGHT WITH BOTTOM NESTING IN AND

SECURED TO FLOOR CHANNEL, AND WITH TOP NESTING IN CEILING CHANNEL WITHOUT

ATTACHMENT.

3. SOUND ATTENUATION BATT INSUL. - 3-1/2" (DEPENDING ON STUD SIZE) GLASS FIBER

BATTS IN STUD CAVITY. FILL ENTIRE CAVITY FULL HEIGHT.

4. GYPSUM WALLBOARD- 5/8" THICK TYPE "X", 4' WIDE, ATTACHED TO STEEL STUDS AND

FLOOR CHANNELS WITH 1" LONG TYPE S SELF-TAPPING STEEL SCREWS AT 8" O.C.

ALONG THE VERTICAL AND BOTTOM EDGES AND 12" O.C. IN THE FIELD OF THE BOARD.

INSTALL WALLBOARD WITH A MIN. 1/2" AND MAX. 3/4" GAP BETWEEN THE TOP OF THE

WALLBOARD AND THE BOTTOM OF THE FLOOR UNIT VALLEYS (OR STRUCTURE ABOVE).

NO SCREWS ARE TO BE INSTALLED WITHIN 4" OF THE STEEL FLOOR UNIT VALLEYS AT

THE TOP OF THE WALL. ORIENT JOINTS VERTICALLY AND STAGGER JOINTS ON

OPPOSITE SIDES OF THE ASSEMBLY.

5. JOINT TAPE AND COMPOUND - VINYL, DRY OR PRE-MIXED JOINT COMPOUND, APPLIED

IN TWO COATS TO JOINTS AND SCREW HEADS; PAPER TAPE 2" WIDE EMBEDDED IN

FIRST LAYER OF COMPOUND OVER ALL JOINTS. JOINTS REINFORCED.

6. ACOUSTICAL SEALANT.

1/ 4"

M

IN

6" STUD

WALL LEGEND

NOTE: REF. SHEET G01.10 OR WALL TYPE DETAILS

NON-RATED PARTITION

1-HR. RATED FIRE BARRIER

SMOKE BARRIER (1-HR. RATED)

2-HR. RATED EXISTING FIRE BARRIER

NON-RATED SMOKE PARTITION

1-HR. RATED FIRE/SMOKE BARRIER

2-HR. RATED FIRE/SMOKE BARRIER

1 HR SHAFT WALL

INTERIOR WALL TYPE LEGEND

NOTE: REF GENERAL INTERIOR WALL NOTES, WALL

CONSTRUCTION & PRIORITY DETAILS, AND FIREWALL DETAILS

FOR ADDITIONAL INFORMATION. NOT ALL WALLS WILL BE

TAGGED. REFERENCE SECTIONS, DETAILS, & PLAN NOTES FOR

UNIQUE OR SPECIAL CONDITIONS.

A

A

D

E

6" MTL. STUD W/ GYPSUM BOARD ON BOTH SIDES (NON-RATED)

C

6" MTL. STUD W/ GYPSUM BOARD ON (1) SIDES

B

3 5/8" MTL. STUD W/ 2 LAYERS GYPSUM BOARD ON BOTH SIDES

H

F

G

2 1/2" MTL. STUD W/ GYPSUM BOARD ON (1) SIDE

3 5/8" MTL. STUD W/ GYPSUM BOARD ON (1) SIDE

J 7/8" FURRING CHANNELS W/ GYPSUM BOARD ON (1) SIDE

K

L 2 1/2" MTL. STUD W/ GYPSUM BOARD ON ONE SIDE WITH 2" FOIL FACED

RIGID INSULATION AT EXTERIOR WALLS

3 5/8" MTL. STUD W/ GYPSUM BOARD ON BOTH SIDES (1 HOUR FIRE

SMOKE)

3 5/8" MTL. STUD W/ GYPSUM BOARD ON BOTH SIDES (1 HOUR)

3 5/8" MTL. STUD W/ GYPSUM BOARD ON BOTH SIDES (SMOKE)

3 5/8" MTL. STUD W/ GYPSUM BOARD ON BOTH SIDES (NON-RATED)

M 3 5/8" MTL. STUD W/ GYPSUM BOARD ON ONE SIDE WITH 2" FOIL FACED

RIGID INSULATION AT EXTERIOR WALLS

N 1" THICK SHAFT LINER WITH 2 1/2" MTL. SHAFTWALL STUDS AND 5/8"

GYP. BD.

N 1 1/2" MTL. STUD W/ GYPSUM BOARD ON (1) SIDE

SECTION

NON-RATED FURRING

ABOVE CEILING ID (STENCIL):

PLAN DESIGNATION:

GENERAL NOTES:

1. ALL REQUIREMENTS OF LISTED UL DESIGN

# MUST BE MET.

WALL PRIORITY:

ACOUSTICAL SEALANT

HAT CHANNEL- 7/8" MIN

MTL STUD - 2 1/2"

AT 16" O.C. MAX.

GYPSUM WALLBOARD - 5/8"

THICK TYPE "X"

JOINT TAPE AND COMPOUND

ACOUSTICAL SEALANT

UL DESIGN #:

FIRE RATING:

GA FILE #:

STC RATING: --

OPENINGS: --

DAMPERS: --

CEILING ASSEMBLY

GYPSUM BOARD CUT TO FIT DECK

CONFIGURATION

1/ 4"

M

IN

1/ 4"

M

IN

7/8" HAT CHANNELJ SCALE:

N.T.S.

2 1/2" STUDSK

1 1/2" STUDSN

SECTION

NON-RATED

FURRING WITH

INSULATION

ABOVE CEILING ID (STENCIL):

PLAN DESIGNATION:

GENERAL NOTES:

1. ALL REQUIREMENTS OF LISTED UL DESIGN

# MUST BE MET.

WALL PRIORITY:

ACOUSTICAL SEALANT

MTL. STUDS

AT 16" O.C. MAX.

GYPSUM WALLBOARD - 5/8"

THICK TYPE "X"

JOINT TAPE AND COMPOUND

ACOUSTICAL SEALANT

UL DESIGN #:

FIRE RATING:

GA FILE #:

STC RATING: --

OPENINGS: --

DAMPERS: --

CEILING ASSEMBLY

GYPSUM BOARD CUT TO FIT

1/ 4"

M

IN

1/ 4"

M

IN

1-5/8" STUDL SCALE:

N.T.S.

2" RIGID INSULATION

3-5/8" STUDM

2HR FIRE BARRIER

UL DESIGN #:

STC RATING:

FIRE RATING:

SCALE:

16" O.C.

SECTION

PLAN

3-5/8" STUDA

U411

55 - 59

2HR

N.T.S.

DESCRIPTION:

2 43

ABOVE CEILING ID (STENCIL):

"2HR FIRE BARRIER"

PLAN DESIGNATION:

GENERAL NOTES:

1. ALL REQUIREMENTS OF LISTED UL

DESIGN # MUST BE MET.

WALL PRIORITY:

1/ 4"

M

IN

OPENINGS: 90 MIN

1. STEEL FLOOR AND CEILING CHANNELS - TOP AND BOTTOM CHANNELS OF WALL

ASSEMBLY SHALL BE MIN. 20 GA. GALV. STEEL SIZED TO FIT STUDS. TOP CHANNEL TO

HAVE 2" FLANGES (MIN). BOTTOM CHANNEL TO HAVE 1-1/4" FLANGES (MIN). SECURE

BOTTOM CHANNELS WITH STEEL FASTENERS AT 24" O.C. (MAX). SECURE TOP

CHANNELS TO VALLEYS OF STEEL FLOOR UNITS (OR STRUCTURE ABOVE) WITH STEEL

FASTENERS AT 12" O.C. (MAX).

2. STEEL STUDS - MIN. 3-5/8" WIDE, 1-1/4" LEGS, 3/8" FOLDED BACK RETURN. FORMED OF

20 GA.(MIN) GALV. STEEL. MAX. SPACING 16" O.C. CUT STUDS 1" LESS IN LENGTH THAN

ASSEMBLY HEIGHT WITH BOTTOM NESTING IN AND SECURED TO FLOOR CHANNEL, AND

WITH TOP NESTING IN CEILING CHANNEL WITHOUT ATTACHMENT.

3. SOUND ATTENUATION BATT INSUL. - 3-1/2" (DEPENDING ON STUD SIZE) GLASS FIBER

BATTS IN STUD CAVITY. FILL ENTIRE CAVITY FULL HEIGHT.

4. GYPSUM WALLBOARD- 5/8" THICK TYPE "X", 4' WIDE. OUTER LAYER PAPER OR VINYL

SURFACED. (LAMINATED SYSTEM) WALLBOARD APPLIED VERTICALLY IN TWO LAYERS.

INNER LAYER ATTACHED TO STUDS WITH 1" LONG TYPE 'S' STEEL SCREWS AT 8" O.C.

ALONG VERT. EDGES AND 12" O.C. IN THE FIELD. OUTER LAYER LAMINATED TO INNER

LAYER WITH JOINT COMPOUND APPLIED WITH A NOTCHED SPREADER PRODUCING

CONT. BEADS OF COMPOUND ABOUT 3/8" IN DIAMETER, SPACED NOT MORE THAN 2"

O.C. JOINTS OF LAMINATED OUTER LAYER OFFSET 12" FROM INNER LAYER JOINTS.

OUTER LAYER ATTACHED TO FLOOR CHANNEL WITH 1-5/8" STEEL SCREWS AT 12" O.C.

OPTIONAL (DIRECT ATTACHED SYSTEM) - INNER LAYER ATTACHED TO STUDS WITH 1"

LONG TYPE 'S' STEEL SCREWS AT 16" O.C. ALONG VERT. EDGES AND IN THE FIELD.

OUTER LAYER ATTACHED TO THE STUDS OVER THE INNER LAYER WITH 1-5/8" LONG

TYPE S STEEL SCREWS AT 16" O.C. ALONG VERT. EDGES AND IN THE FIELD AND AT 12"

O.C. TO THE FLOOR CHANNEL. OFFSET OUTER LAYER JOINTS FROM INNER LAYER

JOINTS. OUTER LAYER JOINTS MAY BE TAPED OR UNTAPED. INSTALL WALLBOARD

WITH A MIN. 1/2" AND MAX. 3/4" GAP BETWEEN THE TOP OF THE WALLBOARD AND THE

BOTTOM OF THE FLOOR UNIT VALLEYS. NO SCREWS ARE TO BE INSTALLED WITHIN 4"

OF THE STEEL FLOOR UNIT VALLEYS AT THE TOP OF THE WALL. ORIENT JOINTS

VERTICALLY AND STAGGER JOINTS ON OPPOSITE SIDES OF THE ASSEMBLY. WHEN

ATTACHED TO FURRING CHANNELS, WALLBOARD IS ATTACHED WITH 1" LONG TYPE 'S'

SCREWS AT 12" O.C.

5. JOINT TAPE AND COMPOUND - VINYL, DRY OR PRE-MIXED JOINT COMPOUND, APPLIED

IN TWO COATS TO JOINTS AND SCREW HEADS; PAPER TAPE 2" WIDE EMBEDDED IN

FIRST LAYER OF COMPOUND OVER ALL JOINTS. JOINTS REINFORCED.

6. FURRING CHANNELS (OPTIONAL NOT SHOWN) - RESILIENT 20 MSG GALV. STEEL

FURRING CHANNELS SPACED VERT. MAX. 24" O.C. ATTACH FLANGE TO EACH

INTERSECTING STUD WITH 1/2" LONG TYPE S-12 PANHEAD SCREWS.

7. ACOUSTICAL SEALANT.

8. PACKING MATERIAL - MIN. 4" TKNS. OF MIN. 4.0 PCF MINERAL WOOL BATT INSULATION

FIRMLY PACKED INTO FLUTES OF STEEL FLOOR UNITS AS A PERMANENT FORM.

PACKING MATERIAL TO BE RECESSED FROM BOTH SURFACES OF THE WALL AS

REQUIRED TO RECEIVE JOINT SEALANT.

9. JOINT TREATMENT MATERIAL - NON-SAG FIRE CAULK EACH SIDE MIN THICKNESS 1/2",

APPLIED WITHIN THE OPENING BETWEEN THE TOP OF THE WALLBOARD AND ALL

SURFACES OF THE STEEL FLOOR OR STRUCTURE, FLUSH WITH BOTH SURFACES OF

THE WALL ASSEMBLY.

1/ 8"

M

IN

SECTION

1HR SHAFTWALL

ABOVE CEILING ID (STENCIL):

"1HR FIRE BARRIER"

LIFE SAFETY PLAN DESIGNATION:

GENERAL NOTES:

1. ALL REQUIREMENTS OF LISTED UL DESIGN

# MUST BE MET.

WALL PRIORITY:

JOINT TREATMENT MATERIAL

INSULATION - MIN. 3" MINERAL

WOOL BATTS, FRICTION FITTED TO

FILL CAVITY

VENTED STEEL CH-STUDS- 20

GA,2-1/2" MIN AT 24" O.C.

GYPSUM WALLBOARD - 5/8" THICK

TYPE "X". STAGGER JOINTS

JOINT TAPE AND COMPOUND

STEEL FLOOR J-CHANNELS 1/2"

CONTINUOUS SEALANT PER UL

DESIGN REQUIREMENTS

UL DESIGN #:

FIRE RATING:

U469

1HR

GA FILE #:

STC RATING: 35 - 39

OPENINGS: 45 MIN W/ CLOSER

DAMPERS: FIRE

CEILING ASSEMBLY

STEEL CEILING J-RUNNERS

ACOUSTICAL GASKET AT FLOOR

TRACK

GYPSUM BOARD CUT TO FIT DECK

CONFIGURATION

SHAFT ROOM

1/ 2"

M

IN

5/ 8"

M A

X

GYPSUM SHAFTLINER - 1" THICK

TYPE "X"

3 1/8"

SHAFT WALL STUDN

12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554

©Copyright 2019

TLC No.:

www.tlc-engineers.com

118626

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Dwg.

PROJECT TEAM:

Office of

Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

Department of Veterans Affairs

MURFREESBORO, TN

615.370.8500

615.370.8530 hfrdesign.com

214 Centerview Drive Suite 300 Brentwood, TN 37027

Phase

FULLY SPRINKLERED

C U s e rs \a tr a y lo r\ D o c u m e n ts

\M b o ro V

A W a rd b

R e n o a tr a y lo r2 X

N D

H .r v t

/1

/2

:2

:0

P

M

04-14-2023

626A4-19-101

GI 01.10

AE RENOVATE WARD 1BWALL TYPE DETAILS

AT/MC

HFR Project No: 2019056

100% CONSTRUCTION

DOCUMENTS

● USE SEMI-GLOSS PAINT.

● LOCATE NOT MORE THAN 12'-0" O.C. ON CORRIDOR SIDES OF PARTITIONS, AND WITH A LEAST ONE MESSAGE

PER WALL ON ROOM SIDE OF PARTITION, AND WITHIN 15'-0" OF THE END OF EACH WALL.

● STENCIL MESSAGE SIMILAR TO: "SMOKE PARTITION" OR "1-HR FIRE BARRIER."

● IDENTIFY PARTITIONS ABOVE CEILINGS ON BOTH SIDES OF PARTITIONS EXCEPT WITHIN SHAFTS IN RED

LETTERS NOT LESS THAN 4" HIGH WITH AT LEAST A 3/8" STROKE.

12. FIRE AND SMOKE PARTITION / BARRIER IDENTIFICATION:

11. PENETRATIONS IN WALLS SHALL BE SEALED AS REQUIRED BY THE WALL RATING PER AN APPROVED UL DESIGN.

10. GYPBOARD PANELS SHALL BE PLACED A MINIMUM OF 1/4" ABOVE FLOOR AND SHALL BE CUT WITHIN 1/4" MAX TOLERANCE TO SHAPE OF DECK OR STRUCTURE ABOVE. GAPS BETWEEN PANELS SHALL BE <1/4".

● PROVIDE DEFLECTION AND BRIDGING CLIPS.

● MAINTAIN CLEARANCE UNDER STRUCTURAL BUILDING MEMBERS TO AVOID DEFLECTION TRANSFER TO STUDS.

PROVIDE NESTED OR SLOTTED EXTENDED LEG CEILING TRACK RUNNERS.

9. DO NOT TRANSFER DEFLECTION FROM STRUCTURAL BUILDING MEMBERS TO STUDS. CONTRACTOR'S OPTION, PROVIDE EITHER OF THE FOLLOWING:

8. EXTEND ALL WALL CONSTRUCTION TO THE DECK ABOVE AND SEAL U.N.O.

7. INSTALL ACOUSTICAL GASKETS AT FLOOR AND CEILING TRACK LOCATIONS.

6. PROVIDE ACOUSTICAL INSULATION FULL HEIGHT IN ALL WALLS U.N.O.

5. STAGGER JOINTS ON OPPOSITE SIDES OF PARTITIONS.

4. ALL FRAMING SHALL BE 20 GA U.N.O.

● PROVIDE FIRE RATED IMPACT RESISTANT GYPBOARD 4'-0"H ON ALL WALLS IN PATIENT ROOMS, 4'-0"H AT ALL EQUIPMENT ALCOVES AND ROOMS NOT SCHEDULED TO RECEIVE RIGID WALL PROTECTION, AND ADDITIONAL LOCATIONS AS NOTED ON DRAWINGS. (IMPACT RESISTANT GYPBOARD SHALL TAKE PRIORITY AT LOCATIONS

INDICATED TO RECEIVE GLASS FIBER FACED GYPSUM PANELS.)

● PROVIDE FIRE RATED GLASS FIBER FACED GYPSUM PANELS ON INTERIOR SURFACE OF EXTERIOR WALLS, TOILET ROOMS, JANITOR'S CLOSETS, MECHANICAL SPACES, AND WITHIN 4'-0" OF WATER SOURCES.

● ALL GYPBOARD SHALL BE 5/8" TYPE 'X' U.N.O.

3. GYPBOARD REQUIREMENTS:

2. TOILET WETWALLS AND PATIENT ROOM HEADWALLS SHALL BE 6" METAL STUDS

1. ALL WALLS SHALL BE 3-5/8" METAL STUD AT 16"0.C. MAX U.N.O.

REFERENCE WALL TYPE DETAILS, PLANS, AND SPECIFICATIONS.

GENERAL WALL NOTES

No. Date Description

Sheets
AD 01.01 - THIRD FLOOR DEMOLITION PLAN - OVERALL
AE 01.00 - SECOND FLOOR PLAN AND REFLECTED CEILING PLAN
AE 01.01 - FOURTH FLOOR/ATTIC PLAN
AE 01.03 - THIRD FLOOR OVERALL PLAN
AE 01.11 - PARTIAL THIRD FLOOR PLAN - PART A NOTED
AE 01.12 - PARTIAL THIRD FLOOR PLAN - PART B NOTED
AE 01.13 - PARTIAL THIRD FLOOR PLAN - PART C NOTED
AE 01.14 - PARTIAL THIRD FLOOR PLAN - PART A DIMENSIONED
AE 01.15 - PARTIAL THIRD FLOOR PLAN - PART B DIMENSIONED
AE 01.16 - PARTIAL THIRD FLOOR PLAN - PART C DIMENSIONED
AE 02.01 - ENLARGED PLANS AND REFLECTED CEILING PLANS
AE 02.02 - ENLARGED PLANS AND REFLECTED CEILING PLANS
AE 02.03 - ENLARGED TOILET PLANS AND ELEVATIONS
AE 03.01 - DOOR ELEVATIONS, SCHEDULE, & NOTES
AE 03.02 - DOOR DETAILS
AE 03.03 - WINDOW DETAILS
AE 08.01 - MISC. DETAILS
AE 08.02 - MISC. DETAILS
AE 08.03 - MISC. DETAILS
AE 08.04 - MISC. DETAILS
AE 08.05 - MISC. INTERIOR DETAILS
AE 08.06 - MISC CEILING DETAILS
AE 09.01 - INTERIOR ELEVATIONS
AE 09.02 - INTERIOR ELEVATIONS
AE 09.03 - CORRIDOR ELEVATIONS
AE 09.04 - CORRIDOR ELEVATIONS
AE 09.05 - 3D VIEWS
AE 10.01 - CASEWORK SECTIONS AND DETAILS
AE 10.02 - CASEWORK SECTIONS AND DETAILS
AE 11.01 - THIRD FLOOR REFLECTED CEILING PLAN - OVERALL
AE 11.10 - THIRD FLOOR RCP - PART A
AE 11.11 - THIRD FLOOR RCP - PART B
AE 11.12 - THIRD FLOOR RCP - PART C
AE 12.01A - EQUIPMENT PLANS
AE 12.01B - EQUIPMENT PLANS
AE 12.01C - EQUIPMENT PLANS
AE 12.02 - EQUIPMENT PLANS - PATIENT ROOMS AREA B
AE 12.02B - EQUIPMENT PLANS - PATIENT ROOMS AREA C
GI 00.01 - COVER SHEET
GI 01.01 - GENERAL DATA
GI 01.02 - CONSTRUCTION STAGING PLAN
GI 01.10 - WALL TYPE DETAILS
GI 01.20 - ACCESSIBILITY DETAILS
GI 02.01 - THIRD FLOOR LIFE SAFETY PLAN - OVERALL
GI 03.01 - SECOND FLOOR ICRA PLAN
GI 03.02 - THIRD FLOOR ICRA PLAN
GI 04.01 - ACM DUCT WORK AND ACM PIPE INSULATION
GI 04.02 - LEAD PAINT AND TRANSITE PANELS
GI 05.01 - PHASING PLANS
IN 01.00 - THIRD FLOOR FINISH LEGEND
IN 01.02 - PARTIAL THIRD FLOOR FINISH PLAN - PART A
IN 01.03 - PARTIAL THIRD FLOOR FINISH PLAN - PART B
IN 01.04 - PARTIAL THIRD FLOOR FINISH PLAN - PART C
IN 01.05 - THIRD FLOOR PATTERN PLAN OVERALL
IN 01.06 - PARTIAL THIRD FLOOR PATTERN - PART A
IN 01.07 - PARTIAL THIRD FLOOR PATTERN - PART B
IN 01.08 - PARTIAL THIRD FLOOR PATTERN - PART C
IN 02.00 - THIRD FLOOR SIGNAGE LEGEND
IN 02.01 - THIRD FLOOR SIGNAGE SCHEDULE
IN 02.02 - PARTIAL THIRD FLOOR SIGNAGE PLAN - PART A
IN 02.03 - PARTIAL THIRD FLOOR SIGNAGE PLAN - PART B
IN 02.04 - PARTIAL THIRD FLOOR SIGNAGE PLAN - PART C
VN 01.00 - PATIENT LIFT VENDOR DRAWINGS

File details come from the government source that posted it. Updated .