GI 02-01 - THIRD FLOOR LIFE SAFETY PLAN - OVERALL.pdf
PDF 2 MB Posted
- Attached to
- Z2DA--626A4-19-101 - Renovate Ward 1B at the Alvin C. York VA Medical Center, Murfreesboro, TN 37129
- Solicitation number
- 36C24923R0114
About this file
This life safety plan details requirements for renovating the third floor of Ward 1B at the Alvin C. York VA Medical Center in Murfreesboro, Tennessee. The renovation work includes upgrading existing partitions and barriers to the rated levels indicated, properly installing penetrations through fire-rated walls, and identifying all fire and smoke barriers in accordance with the notes and details provided. The related federal contract opportunity is solicitation number 36C24923R0114 for project 626A4-19-101 to renovate Ward 1B at the specified VA medical center. The solicitation is being issued by the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 9.
View the file
Other files
Show all 48
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
F E
C
F E
C
FEC FEC
FEC
FEC
F E
C
FEC FEC
F E
C
F E
C
CG
C G
C G
CG
C G
CG
CG
CG
CG
CG
CG
C G
CG
C
GC
G
CG C
G
C G
CG
CG
CG
CG
CG
CG
CG
C G
C G
C G
C=18015'-0"
POINT OF EGRESS
TRAVEL DISTANCE
POINT OF DECISION
FIRE EXTINGUISHER CABINET
EGRESS CAPACITY (EXIT WIDTH/.2)
LINE OF TRAVEL
FEC
EXIT EXIT LOCATION
ROOM NAME
ROOM #
ROOM TAG
LIFE SAFETY LEGEND
EXIT SIGN (SINGLE SIDED)
EXIT SIGN WITH DIRECTIONAL ARROW
T
O E
X
IT
T
O S
M O
K E
B A
R R
IE
R
147' - 6" TO SMOKE BARRIER
T
O E
X
IT
ISO ROOM
B321
PAT. TLT.
B321B
PRIVATE ROOM
B322
PRIVATE ROOM
B315
BARI PRIVATE
ROOM
B313
BARIATRIC
PATIENT TOILET
B313A
PANTRY
B338A
SERVING
KITCHEN
B338
DINING/DAY
ROOM
B337
LAUNDRY
B359
CLEAN SUPPLY
B363
RETHERM
B361
CHUTE
B360
EQUIP STORAGE
B301
INPATIENT
REHAB
B303
STAFF LOUNGE
B304
STAFF LOCKERS
B304B
CHAIR ALCOVE
B305
FAM. LOUNGE
B307
CONSULT
B310
FAM/PUB. TLT.
B308
REC.THR. STOR.
B309
TEAM ROOM
B332
DATA
B335
CLEAN LINEN
B318
NOURISH
B312
ST. TLT.
B311A
HAC.
B325
SOILED HOLD
B327
ELEC.
B326
CLEAN UTILITY
B320
HAC
B357
WOUND CART
STOR.
B311B
SUB NS.
B358
PRIVATE ROOM
B349
ISO ROOM
B347
CLEAN UTILITY
B346
ELEC.
B344
EQUIP STOR.
B343
CLEAN LINEN
B351
SOILED HOLD
B352
BARI PRIVATE
ROOM
B355
BARI. TLT.
B355A
NOURISHMENT
B356
STAFF TLT.
B358A
PAT. TLT.
B322A
PRIVATE ROOM
B314
PAT. TLT.
B331A
PRIVATE ROOM
B330
PRIVATE ROOM
B331
PRIVATE ROOM
B348
PAT. TLT.
B330A
TEAM WORK
ROOM
B329
SUB N.S.
B311
CHARGE NURSE
B336A
NURSE STATION
B336
SOCIAL WORKER
B302
DIRTY
B362
EMPTY CYL.
STOR.
B317
FULL CYL. STOR.
B316
ANTE
B347A
NURSE
MANAGER
B333
PAT. TLT.
B315A
PAT. TLT.
B314A
ANTE
B321A
T
O S
M O
K E
B A
R R
IE
R
T
O E
X
IT
147' - 6" TO SMOKE BARRIER
T
O E
X
IT
EXIT EXIT
85' - 6" TO EXIT
EXIT
TEAM WORK
B341
CORRIDOR
B370
COMM
B334
MEDS
B336B
CHASE
CHASE
87' - 0" COMMON PATH OF TRAVEL
C
O M
M O
N P
A T
H O
F T
R A
V E
L
C
O M
M O
N P
A T
H O
F T
R A
V E
L
C
O M
M O
N P
A T
H O
F T
R A
V E
L
DN DN
DN UP
CHASE
T
O S
M O
K E
B A
R R
IE
R
297' - 6" TO EXIT
SC LEGEND
SC 2-1
SC 2-2
SC 2-3
5,389 SF
SC 2-2
7,229 SF
SC 2-37,357 SF
SC 2-1
WALL LEGEND
NOTE: REF. SHEET G01.10 OR WALL TYPE DETAILS
NON-RATED PARTITION
1-HR. RATED FIRE BARRIER
SMOKE BARRIER (1-HR. RATED)
2-HR. RATED EXISTING FIRE BARRIER
NON-RATED SMOKE PARTITION
1-HR. RATED FIRE/SMOKE BARRIER
2-HR. RATED FIRE/SMOKE BARRIER
1 HR SHAFT WALL
OCCUPANCY LOAD FACTORS
SLEEPING AREAS (120 GSF/OCCUPANT)
BUSINESS (100 GSF/OCCUPANT)
4,901 SF / 100 = 50 OCCUPANTS
13,666 SF / 120 = 114 OCCUPANTS
TOTAL EXIT CAPICITY
SLEEPING AREAS (120 GSF/OCCUPANT)
BUSINESS (100 GSF/OCCUPANT) -
1 @ 32" = (1)(32)/.2 =
TOTAL EXIT CAPICITY = 160
2 @ 32" = (2)(32)/.2 =
TOTAL EXIT CAPICITY = 320
12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554
©Copyright 2019
TLC No.:
www.tlc-engineers.com
118626
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg.
PROJECT TEAM:
Office of
Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
Department of Veterans Affairs
KEYPLAN
MURFREESBORO, TN
615.370.8500
615.370.8530 hfrdesign.com
214 Centerview Drive Suite 300 Brentwood, TN 37027
BLDG 2
BLDG 1
BLDG 9
Phase
FULLY SPRINKLERED
C U s e rs \a tr a y lo r\ D o c u m e n ts
\M b o ro V
A W a rd b
R e n o a tr a y lo r2 X
N D
H .r v t
/1
/2
:2
:5
P
M
04-14-2023
626A4-19-101
GI 02.01
AE RENOVATE WARD 1B
THIRD FLOOR LIFE SAFETY PLAN -
OVERALL
MC/AT
HFR Project No: 2019056
100% CONSTRUCTION
DOCUMENTS
4. REMOVE EXISTING ANNEALED OR OTHERWISE NON-SAFETY-RATED GLASS FROM EXISTING DOORS, SIDELIGHTS, AND OTHER HAZARDOUS LOCATIONS SCHEDULED TO REMAIN WITHIN PROJECT AREA. IN NON-RATED OPENINGS, PROVIDE NEW TEMPERED GLASS TO MATCH ORIGINAL DESIGN. IN RATED OPENINGS, PROVIDE NEW IMPACT-RESISTANT, FIRE-RATED GLASS TO MATCH ORIGINAL CONFIGURATION, RATED NO LESS THAN
SURROUNDING WALL CONSTRUCTION.
3. EXIT PATHS SHALL BE MAINTAINED CLEAR OF EQUIPMENT, MATERIALS AND DEBRIS AND SHALL BE MARKED WITH
APPROVED EXIT SIGNS VISIBLE AT ALL TIMES.
2. TEMPORARY PARTITIONS REQ'D FOR DUST OR INFECTION CONTROL SHALL BE CONSTRUCTED TO MAINTAIN EXISTING FIRE BARRIER REQUIREMENTS. WHERE TEMPORARY PARTITIONS MUST INCLUDE DOORS FOR CONSTRUCTION ACCESS OR LIFE SAFETY EGRESS, INSTALL DOOR ASSEMBLIES EQUAL IN RATING TO THE CONSTRUCTION BEING PENETRATED WITH POSITIVE LATCHING HARDWARE AND EXIT DEVICES (PANIC BARS)
WHERE REQ'D.
1. ALL EXISTING PARTITIONS INDICATED TO REMAIN SHALL BE UPGRADED TO RATING NOTED IF THEY OCCUR ON OR IN A SMOKE COMPARTMENT WITHIN CONSTRUCTION AREA. EXTENT OF UPGRADE SHALL INCLUDE, BUT SHALL NOT BE LIMITED TO, EXTENDING PARTITIONS TO UNDERSIDE OF DECK, INSTALLING BLOW-OUT PATCHES, RECONSTRUCTING INTERSECTIONS AT OTHER PARTITIONS, INSTALLING UL APPROVED FIRESTOP SYSTEM AT WALL PENETRATIONS, RE-INSTALLING FIRE AND/OR FIRE/SMOKE DAMPERS, INSTALLING FIVE-SIDED ENCLOSURES OF RECESSED ITEMS, INSTALLING ADDITIONAL FRAMING, AND INSTALLING 12” WIDE STRIPS OF G.W.B OVER JOINTS NOT OFFSET FROM OPPOSING SIDE. AT CONTRACTOR'S OPTION, PARTITION MAY BE COMPLETELY STRIPPED AND REBUILT. ALL SERVICES WITHIN PARTITION MUST BE MAINTAINED AND FINISHES
RESTORED REGARDLESS OF COURSE OF ACTION.
RENOVATION WORK
15. REFER TO THE CONTRACT DOCUMENTS FOR ADDITIONAL INFORMATION RELATED TO LIFE SAFETY
CONSTRUCTION AND APPROVED UL ASSEMBLIES.
● PROVIDE WET-CHEMICAL TYPE, CLASS K WALL-HUNG FIRE EXTINGUISHERS THROUGHOUT KITCHENS.
LOCATE SO THAT A MINIMUM OF 10 FEET AND A MAXIMUM OF 20 FEET OF TRAVEL FROM ANY PIECE OF
COOKING EQUIPMENT BELOW HOOD WILL BE PROVIDED.
● PROVIDE CLEAN AGENT TYPE FIRE EXTINGUISHERS WITH UL RATING OF 1A:10B:C IN EACH DATA CENTER, MRI ROOM, AND MRI CONTROL ROOM. LOCATE SO THAT A MAXIMUM OF 75 FEET OF TRAVEL FROM ANY
SPACE WILL BE PROVIDED.
● PROVIDE DRY CHEMICAL, ABC TYPE FIRE EXTINGUISHERS WITH UL RATING OF 4A:60B:C IN ALL
MECHANICAL SPACES.
● PROVIDE MULTI-PURPOSE, DRY CHEMICAL, ABC TYPE FIRE EXTINGUISHERS WITH UL RATING OF 4A:60B:C THROUGHOUT THE ENTIRE BUILDING. LOCATE SO THAT A MAXIMUM OF 75 FEET OF TRAVEL FROM ANY
SPACE WILL BE PROVIDED.
14. FIRE EXTINGUISHER LOCATIONS: PROVIDE AS SHOWN ON PLANS AND AS INDICATED, WHICHEVER IS MORE
RESTRICTIVE. CABINETS SHALL BE FULLY RECESSED (U.N.O.):
13. DOORS, WINDOWS, AND OTHER OPENINGS SHALL BE RATED EQUAL TO THAT OF THE CONSTRUCTION BEING PENETRATED. PROVIDE POSITIVE LATCHING AT RATED DOOR ASSEMBLIES. GLAZING SHALL BE FIRE RATED EQUAL TO THE WALL CONSTRUCTION AND INSTALLED IN AN EQUALLY RATED FRAMING SYSTEM, TESTED AS AN
ASSEMBLY. WIRE GLASS IS NOT PERMITTED.
12. WHERE FIRE RATED WALL ASSEMBLIES OCCUR IN PROXIMITY TO STEEL BEAMS OR JOINTS WITH INADEQUATE DIMENSION TO INSTALL SCREWS, PROVIDE STUD FRAMING AROUND THE BEAM OR JOIST IN ACCORDANCE WITH U.L. DESIGN N-501 WITH LAYERS OF G.W.B. EQUAL IN NUMBER TO THE WALL ASSEMBLY CONSTRUCTION.
11. WHERE PARTITIONS MUST BE CONNECTED TO STRUCTURE FOR SUPPORT, INSTALL 20 GUAGE GALVANIZED METAL Z-CLIPS SPACED AS REQ'D, BUT NOT MORE THAN 2'-0” O.C. PRIOR TO APPLICATION OF FIREPROOFING.
10. WHERE DEVICES, CABINETS, OR ACCESSORIES GREATER THAN 16 SQ. IN. ARE INDICATED IN RATED CONSTRUCTION, PROVIDE A FIVE-SIDED G.W.B. ENCLOSURE CONSTRUCTED OF LAYERS OF G.W.B. EQUAL IN
NUMBER TO THE CONSTRUCTION BEING PENETRATED.
9. WHERE DEVICES ARE INDICATED IN RATED CONSTRUCTION, THE MAXIMUM ALLOWABLE AREA OF INDIVIDUAL U.L.
LISTED BACKBOXES PERMITTED IN THE WALL IS 16 SQ. IN. WITH MAXIMUM AGGREGATE AREA OF 100 SQ. IN PER 100 SF OF WALL AREA. BACKBOXES ON OPPOSITE FACES OF RATED WALLS SHALL BE OFFSET A MINIMUM HORIZONTAL DISTANCE OF 24 INCHES. WHEN PENETRATIONS EXCEED THE ALLOWABLE AREAS, DEVICES SHALL BE PROVIDED WITH A FIVE-SIDED G.W.B. ENCLOSURE OR UL LISTED INTUMESCENT FIRE PUTTY.
8. PROVIDE ENCLOSURE AND ACCESS PANEL AT EACH FIRE PROTECTION INSPECTION TEST VALVE. DO NOT LOCATE VALVES AND PIPES IN EXTERIOR WALLS. PROVIDE PAINTED STEEL ACCESS PANELS IN WALLS &
CEILINGS EQUAL IN RATING TO THE CONSTRUCTION BEING INSTALLED IN.
7. INSTALL METALLIC SLEEVES AROUND LOW VOLTAGE CABLES THAT PENETRATE THE WALL, AND SEAL AROUND
THE SLEEVE AND INSIDE THE SLEEVE WITH AN APPROVED SEALANT.
6. INSTALL G.W.B. TIGHT TO ALL DUCTS AND DUCT INSULATION. USE METALLIC DUCT TAPE TO SEAL BETWEEN THE
DUCT AND THE G.W.B.
● WHERE THE DIAMETER OF THE OPENING IS GREATER THAN 3”, THE BLOW-OUT PATCH SHALL EXTEND A MINIMUM OF 6” ABOVE AND BELOW THE OPENING AND A MINIMUM OF 3” BEYOND THE STUDS ON BOTH SIDES OF THE OPENING. RUNNER CHANNELS SHALL BE SECURED TO THE STUDS ABOVE AND BELOW THE OPENING. THE PATCHES SHALL BE FASTENED TO THE STUDS & CHANNELS A MINIMUM OF 3” FROM
THE EDGES OF THE PATCH WITH JOINT COMPOUND APPLIED TO THE BACKSIDE OF THE PATCH.
● WHERE THE DIAMETER OF THE OPENING IS LESS THAN 3”, THE BLOW-OUT PATCH SHALL EXTEND A MINIMUM OF 6” BEYOND THE OPENING IN ALL DIRECTIONS. THE PATCH SHALL BE FASTENED NOT LESS THAN 3” FROM THE EDGE OF THE PATCH WITH JOINT COMPOUND APPLIED TO THE BACKSIDE OF THE
PATCH.
5. INSTALL BLOW-OUT PATCHES MADE OF LAYERS OF G.W.B. EQUAL TO THAT OF THE PARTITION CONSTRUCTION, CUT TO FIT TIGHT TO PENETRATIONS, IN INSTANCES WHERE THE ANNULAR OPENING EXCEED THAT ALLOWED BY THE UL ASSEMBLY. DO NOT APPLY JOINT COMPOUND OVER SCREWS AT PATCHES. DO NOT REMOVE EXCESS
COMPOUND FROM EDGES OF PATCH AFTER PLACEMENT.
4. FIRESTOP ALL INTERUPTIONS TO FIRE RATED ASSEMBLIES, MATERIALS, AND COMPONENTS WITH MATERIALS WHICH HAVE BEEN TESTED ACCORDING TO ASTM E814, UL 1479, OR UL 2079 TO PROVIDE A FIRE RATING AND
SMOKE RATING EQUAL TO THAT OF CONSTRUCTION BEING PENETRATED.
AT DOUBLE LAYER G.W.B APPLICATIONS, SECURE SECOND LAYER TO FIRST WITH FASTENERS (DO NOT USE ADHESIVES). PLACE SECOND LAYER PERPENDICULAR TO FIRST LAYER. OFFSET JOINTS OF SECOND LAYER FROM JOINTS OF FIRST LAYER. FINISH JOINTS FULL HEIGHT OF WALL WITH TAPE & COMPOUND PER
SPECIFICATIONS
● SCREWS WITHIN THE FIELD OF THE BOARD SHALL NOT EXCEED 12” O.C. FASTENED TO SOLID FRAMING.
● ALL EDGES OF BOARD SHALL BE SCREWED NOT MORE THAN 8” O.C. TO SOLID FRAMING.
USE TYPE S OR S12 FASTENERS INSTALLED IN ACCORDANCE WITH APPLICABLE FIRE TEST, BUT NO LESS THAN
AS FOLLOWS:
● HORIZONTAL JOINTS OFFSET 24” VERTICALLY. HORIZONTAL JOINTS SHALL NOT OCCUR BELOW CEILING.
● VERTICAL JOINTS OFFSET 16” HORIZONTALLY
3. ALL G.W.B. SHALL BE 5/8" TYPE 'X' U.N.O. STAGGER JOINTS ON OPPOSITE SIDES OF PARTITIONS AS FOLLOWS:
7) NON-RATED PARTITIONS
6) NON-RATED SMOKETIGHT PARTITIONS
5) 1-HR FIRE (CORRIDORS WHERE REQ'D)
4) 1-HR FIRE (HAZARDOUS LOCATIONS)
3) 1-HR FIRE/SMOKE
2) 2-HR FIRE
1) 2-HR FIRE/SMOKE
2. ALL RATED BARRIERS SHALL EXTEND THROUGH THE INT. LAYER OF GYP. BD. & STUD CAVITY TIGHT TO THE BACK OF EXT SHEATHING IN EXT WALLS & OVERHANGING FASCIAS. WHERE SUCH PARTITIONS INTERSECT ONE OF LESSER FIRE RATING, THEIR LAYERS OF G.W.B. SHALL CONTINUE UNINTERRUPTED THROUGH THE WALL OF LESS
FIRE RATING. THE FOLLOWING WALL PRIORITIES SHALL BE OBSERVED:
● USE SEMI-GLOSS PAINT
● LOCATE NOT MORE THAN 12'-0" O.C. ON CORRIDOR SIDES OF PARTITIONS, AND WITH A LEAST ONE MESSAGE PER ROOM ON ROOM SIDE OF PARTITION, AND WITHIN 15'-0" OF THE END OF EACH WALL.
● STENCIL MESSAGE SIMILAR TO: "SMOKE PARTITION" OR "1-HR FIRE BARRIER."
● IDENTIFY PARTITIONS ABOVE CEILINGS ON BOTH SIDES OF PARTITIONS EXCEPT WITHIN SHAFTS IN RED
LETTERS NOT LESS THAN 4" HIGH WITH AT LEAST A 3/8" STROKE.
1. FIRE AND SMOKE PARTITION / BARRIER IDENTIFICATION:
ALL WORK
2. THE CONTRACTOR SHALL AT ALL TIMES ENDEAVOR TO CONSTRUCT THE FACILITY IN STRICTEST ACCORDANCE TO SOUND PRACTICES OF FIRE RESISTIVE CONSTRUCTION. DEVIATIONS FROM MFG RECOMMENDATIONS, INDEPENDENT FIRE TESTS, OR UL ASSEMBLY REQUIREMENTS SHALL BE CORRECTED AT NO ADDITIONAL COST.
1. DETAILS AND NOTES ABOUT RATED WALLS AND RATED PENETRATIONS ARE PROVIDED IN CASE CONTRACTOR COMES ACROSS A SITUATION WHERE THEY ARE NEEDED. SOME OF THE RATED WALL AND PENETRATION NOTES
MAY NOT APPLY TO THIS PROJECT. CONTACT THE COR IF QUESTIONS ARISE.
GENERAL
GENERAL LIFE SAFETY NOTES
NOTE: THIS DRAWING MUST BE
PRINTED IN COLOR TO REPRODUCE
ALL FIRE RATED WALL SYMBOLS.
3/32" = 1'-0"
1 WARD 1B - LIFE SAFETY PLAN
NOT TO SCALE
2 THIRD FLOOR SMOKE COMPARTMENT PLAN
0 5' 10'
LIFE SAFETY - DEAD END CORRIDOR EXEMPTION
No. Date Description
| Sheets |
| GI 02.01 - THIRD FLOOR LIFE SAFETY PLAN - OVERALL |
File details come from the government source that posted it. Updated .