ELECTRICAL BINDER.pdf
PDF 9 MB Posted
- Attached to
- Z2DA--626A4-19-101 - Renovate Ward 1B at the Alvin C. York VA Medical Center, Murfreesboro, TN 37129
- Solicitation number
- 36C24923R0114
About this file
This solicitation is for a construction project to renovate Ward 1B at the Alvin C. York VA Medical Center in Murfreesboro, Tennessee. The solicitation number is 36C24923R0114.
The project involves renovations and upgrades to patient rooms, support spaces, and building systems on the third floor of the medical center. The scope of work includes demolishing existing finishes, fixtures, and equipment to prepare for new construction. It will upgrade electrical, mechanical, plumbing and fire protection systems. New finishes, fixtures, medical equipment and furnishings will be installed. The construction drawings provide layouts and details of proposed demolition, new construction, and equipment. The estimated project completion date is 2023.
The solicitation is designated for small business set-aside and involves the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 9. The projected award date is in 2022. Pricing will be fixed-price, lump sum. The incumbent contractor was not identified.
The key information provided includes the location and scope of construction work required, federal agencies and contracting preferences involved, estimated timelines, and basic contracting terms. The document consists of construction drawings outlining demolition and new work.
View the file
Other files
Show all 48
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
CLEAN UTILITY
SOILED UT.
PT. ROOM
PT. ROOM
PT. ROOM
PT. ROOM
ELEC.
STAFF TLT.STAIR
PT. ISO ROOM
PT. ROOM
PT. ROOM
WORK RM
ANTE
OFFICE
RESIDENTS RM.
MECH.
PT. ROOM
PT. ROOM
STOR. ROOM MEDS
SUPPLY ROOM
ELEC.
NOURISHMENT
CHUTE
IT
COMM
CONSULT
PT. ROOM PT. ROOM
PT. ROOM
PT. ROOM
MECH
OFFICE
RESIDENTS
ROOM
STAIR
PT. ROOM
PT. ROOM
PT. ROOM
WORK ROOM
CLEAN UTILITY
SOILED UTILITY
PT. ROOM
PT. ROOM
PT. ROOM
PT. ROOM
HAC ELEC.
STAFF TLT
NURSE WK.
NURSE STATION
SOCIAL WORK
WAITING ROOM
STAIRS
CHASE
LOCKER RM.
RETHERM
CONF.
STAFF TLT.
CORRID
STAFF BREAK
EXAMPLE #1
EXAMPLE LEGEND
EXAMPLE #2
EXAMPLE #3
EXAMPLE #4
EXAMPLE #5
EXAMPLE #6
ISO ROOM
PAT. TLT.
PRIVATE ROOM
PRIVATE ROOM
PRIVATE ROOM
BARI PRIVATE
ROOM
BARIATRIC
PATIENT TOILET
PRIVATE ROOM
PRIVATE ROOM
PANTRY
SERVING
KITCHEN
DINING/DAY
ROOM
LAUNDRY CLEAN SUPPLY
RETHERMCHUTE
EQUIP STORAGE
INPATIENT
REHAB
STAFF LOUNGE
STAFF LOCKERS
CHAIR ALCOVE
FAM. LOUNGE
CONSULT
FAM/PUB. TLT.
REC.THR. STOR.
TEAM ROOM
DATA
CLEAN LINEN
NOURISH
ST. TLT.
HAC.
SOILED HOLD
ELEC.
CLEAN UTILITY
HAC
WOUND CART
STOR.SUB NS.
PRIVATE ROOM
PRIVATE ROOM
ISO ROOM
CLEAN UTILITY
PAT. TLT.
ELEC.
EQUIP STOR.
TEAM WORKCLEAN LINEN
SOILED HOLD
BARI PRIVATE
ROOM
BARI. TLT.
NOURISHMENT
PAT. TLT.
PAT. TLT.
STAFF TLT.
PRIVATE ROOM
PAT. TLT.
PAT. TLT.
PAT. TLT.
PRIVATE ROOM
PAT. TLT.
PRIVATE ROOM
PRIVATE ROOM
PRIVATE ROOM
PAT. TLT.
PAT. TLT.
PAT. TLT.
PAT. TLT.
TEAM WORK
ROOM
SUB N.S.
CHARGE NURSE
NURSE STATION
SOCIAL WORKER
DIRTY
EMPTY CYL.
STOR.
FULL CYL. STOR.
ANTE
NURSE
MANAGER
PAT. TLT.
PAT. TLT.
ANTE
MEDS
COMM
STAFF TLT.
PRIVATE ROOM PRIVATE ROOM
CORRIDOR
CORRIDOR
CORRIDOR
CORRIDOR
VENDING
PAT. TLT.
PAT. TLT.
CORRIDOR
CORRIDOR
CORRIDOR
CORRIDOR
STAIR 1
STAIR 2
STAIR 3
EXISTING RISER
ELEV.
ELEV.
CHASE
CHASE
CHASE
CHASE
THE INTENT WITH THIS PLAN IS TO SHOW
HOW THE AREAS BETWEEN THE SECOND
FLOOR AND THRID FLOOR ALIGN
12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554
©Copyright 2019
TLC No.:
www.tlc-engineers.com
118626
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg.
PROJECT TEAM:
Office of
Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
Department of Veterans Affairs
KEYPLAN
MURFREESBORO, TN
615.370.8500
615.370.8530 hfrdesign.com
214 Centerview Drive Suite 300 Brentwood, TN 37027
BLDG 2
BLDG 1
BLDG 9
Phase
FULLY SPRINKLERED
C U s e rs \a tr a y lo r\ D o c u m e n ts
\M b o ro V
A W a rd b
R e n o a tr a y lo r2 X
N D
H .r v t
/1
/2
:5
:4
P
M
04-14-2023
626A4-19-101
GI 05.01
AE RENOVATE WARD 1BPHASING PLANS
Author
HFR Project No: 2019056
100% CONSTRUCTION
DOCUMENTS
1 SECOND FLOOR PLAN - PHASING PLAN
0 8' 16' 32'4'
2 03 THIRD FLOOR PLAN - PHASING PLAN
0 8' 16' 32'4'
GENERAL NOTE:
1. THE PHASING PLAN IS NOTED AS EXAMPLES TO GIVE THE CONTRACTOR AN
UNDERSTANDING OF HOW THE PHASING FOR THE PROJECT NEEDS TO BE
ADDRESSED. WHILE THEY ARE LISTED BY NUMBER THESE EXAMPLES CAN BE
CONDUCTED IN ANY SEQUENCE AS DEEMED NECESSARY FOR THE MOST EFFECIENT
PROCESS POSSIBLE.
2. IN GENERAL 5 PATIENT ROOMS AT ONE TIME ON THE FLOOR BELOW WILL BE ABLE
TO BE TEMPORARLY OUT OF COMMISSION TO WORK ON VERTICAL SERVICES, THERE
MUST BE AT LEAST 15 ACTIVE PATIENT ROOMS AT ALL TIMES.
3. ALL ROOMS THAT ARE BEING WORKED ON SHALL BE PROTECTED FROM DAMAGE
AS BEST AS POSSIBILE. MOST OF THE WORK WILL TAKE PLACE IN THE CEILING,
HOWEVER DAMAGE TO ANY OTHER PART OF THE ROOM MUST BE REPARIED.
PROTECT EXISTING CEILING TILES, TILES THAT ARE DAMAGED OR BROKEN MUST BE
REPLACED TO THE ORIGINAL STATE.
4. CAREFUL COORDINATION WITH THE FACILITY MUST TAKE PLACE TO ADDRESS ANY
SHUTDOWNS THAT COULD EFFECT AREAS OUTSIDE OF THE DESIGNATED EXAMLE
ZONE.
5. IF SUPPORT SPACE INSIDE OF A DESIGNATED EXAMPLE ZONE IS SERVING
ANOTHER EXAMPLE ZONE COORDINATE SPECIFIC TIMES WITH THE FACILITY TO GAIN
ACCESS TO THIS SPACE.
6. ICRA BARRIERS MUST BE USED TO CLOSE OFF EACH AREA THAT IS BEING WORKED
ON TO PREVENT CONSTRUCTION DEBRIS AND DUST FROM INFILTRATING OCCUPIED
SPACE. BARRIERS SHALL BE INSTALLED AND SEALED ALONG WITH STICKY MATS AND
ANY OTHER INFECTION CONTROL ITEMS. IN SOME INSTANCES ICRA BARRIERS MAY
BE REQUIRED PER ROOM.
7. WORK IN THE CONNECTING CORRIDORS, ELEVATOR LOBBY AND NURSE STATION
SHALL BE CAREFULLY COORDINATED WITH THE FACILITY AND STAFF. THE NEED TO
WORK IN THESE AREAS SHALL BE EVALUATED ON A AS NEEDED BASIS. ELEVATOR
ACCESS SHALL BE MAINTAINED AT ALL TIMES
No. Date Description jim.elder Rectangle jim.elder Typewritten Text 06-13-2023 jim.elder Rectangle jacob.kelsheimer Snapshot jacob.kelsheimer Snapshot
GENERAL NOTES
NOTE: SOME SYMBOLS SHOWN ON THIS LEGEND MAY NOT PERTAIN TO THIS PROJECT.
ELECTRICAL SYMBOL LEGEND
FIRE ALARM SYSTEM CONDUIT AND WIRING
FIRE ALARM ANNUNCIATOR PANEL - FLUSH MOUNTED
FIRE ALARM TERMINAL CABINET
FIRE ALARM CONTROL PANEL
CEILING HEAT DETECTOR 135° F UNLESS OTHERWISE INDICATED
ELECTROMAGNETIC DOOR HOLD OPEN DEVICE
WITH CONNECTION TO CLOSURE/ HOLDER,
INCLUDES DETECTOR
ELECTROMAGNETIC DOOR HOLD OPEN DEVICE
WITH CONNECTION TO CLOSURE/HOLDER
ELECTROMAGNETIC DOOR HOLD OPEN DEVICE
SPRINKLER WATERFLOW SWITCH CONNECTION
SPRINKLER TAMPER SWITCH CONNECTION
FIREMAN'S PHONE JACK
VISUAL SIGNALING UNIT, WALL MOUNTED
(NO AUDIO DEVICE)
XXCD
XXCD
COMBINATION AUDIBLE/VISUAL NOTIFICATION DEVICE
CHIME/FLASHING "FIRE" LIGHT
CD = CANDELA RATING
FIRE ALARM CONTROL RELAY
DUCT SMOKE DETECTOR
R = RETURN
S = SUPPLY
CEILING SMOKE DETECTOR, PHOTO-ELECTRIC TYPE
UNLESS OTHERWISE NOTED
E = ELEVATOR WITH RECALL CONTACTS
I = IONIZATION
MANUAL PULL STATION
MOTOR CONNECTION, NUMBER DENOTES HORSEPOWER
EMERGENCY BATTERY PACK WITH TWIN HEADS
TRACK WITH TRACK LIGHT FIXTURE - TRIANGLES
INDICATE QUANTITY OF FIXTURE HEADS
EXTERIOR POLE LIGHT FIXTURE WITH
ARMS ORIENTED AS SHOWN ON PLANS
WALL MOUNTED SCONCE FIXTURE
EXIT LIGHT FIXTURE - SHADED QUADRANTS
INDICATE FACE(S), DIRAECTIONAL ARROWS
AS SHOWN ON PLANS
WALL WASH FIXTURE
COMPLETELY SHADED DENOTES UNSWITCHED
FIXTURE ON GENERATOR BRANCH CIRCUIT
DIAGONAL SHADING DENOTES SWITCHED
FIXTURE ON GENERATOR BRANCH CIRCUIT
TROFFER FIXTURE, RECESSED OR SURFACE MOUNT
LINEAR STRIP FIXTURE
EXISTING TO REMAIN
EXISTING TO BE REMOVED
FLEXIBLE CONDUIT
CONDUIT CONTINUED
CONDUIT STUB
CONDUIT TURNING DOWN
CONDUIT TURNING UP
EQUIPMENT BRANCH CONDUIT
LIFE SAFETY BRANCH CONDUIT
CRITICAL BRANCH CONDUIT
GROUND OR GROUND ROD AS NOTED
BRANCH CIRCUIT CONDUIT EXPOSED
BRANCH CIRCUIT CONDUIT CONCEALED IN SLAB,
UNDERGROUND OR UNDER FLOOR.
BRANCH CIRCUIT CONDUIT CONCEALED ABOVE CEILING OR IN WALL.
CONDUIT SHALL INCLUDE PHASE, NEUTRAL AND GROUND CONDUCTORS
AS REQUIRED FOR CIRCUITS (UNLESS OTHERWISE NOTED).
BRANCH CIRCUIT PANELBOARD, OVER 250 VOLTS, FLUSH MOUNTED
BRANCH CIRCUIT PANELBOARD, OVER 250 VOLTS, SURFACE MOUNTED
BRANCH CIRCUIT PANELBOARD, UNDER 250 VOLTS, FLUSH MOUNTED
BRANCH CIRCUIT PANELBOARD, UNDER 250 VOLTS, SURFACE MOUNTED
SHUNT-TRIP BUTTON
FLUSH MOUNTED UNLESS OTHERWISE NOTED
NEMA 3R FOR EXTERIOR LOCATIONS
SURGE SUPRESSOR
A3 = PANELBOARD DEVICE
B3 = DISTRIBUTION BOARD DEVICE
C3 = SERVICE ENTRANCE DEVICE
JUNCTION BOX
CABLE TRAY
PLUG-IN STRIP WITH RECEPTACLES, 18" O.C. UNLESS
OTHERWISE INDICATED
GROUND BAR
PHOTOCELL, MOUNTED ON ROOF FACING NORTH
DOOR ACCESS CONTROL CARD READER
SPECIAL PURPOSE RECEPTACLE, RATING AS NOTED
SPEAKER
TICK MARKS SHOWN ON ANY DEVICE REPRESENTS
RECEPTACLE CONNECTED TO THE EMERGENCY CIRCUIT
(RED DEVICE) TYPICAL FOR ANY DEVICE IN LEGEND
ISOLATED GROUND DUPLEX RECEPTACLE (ORANGE DEVICE)
TWO DUPLEX RECEPTACLES WITH COMMON COVER
MOUNTED ABOVE COUNTER
TWO DUPLEX RECEPTACLES WITH COMMON COVER
GFCI RECEPTACLE MOUNTED ABOVE COUNTER
GFCI RECEPTACLE
WP DENOTES WEATHERPROOF COVER.
SIMPLEX RECEPTACLE
DUPLEX RECEPTACLE MOUNTED ABOVE COUNTER
FLOOR OUTLET BOX WITH TWO DUPLEX RECEPTACLES
AND ONE COMBINATION W/ VOICE/DATA OUTLET
FLOOR OUTLET BOX AND DUPLEX RECEPTACLE
WITH APPROPRIATE FLANGE
M
T
WP
OC
a
1. LIGHT SWITCHES SHALL BE MOUNTED 48 INCHES ABOVE FINISHED FLOOR TO CENTER LINE OF DEVICE, UNLESS OTHERWISE NOTED.
2. RECEPTACLES SHALL BE LOCATED 18 INCHES ABOVE FINISHED FLOOR TO CENTER LINE OF DEVICE, UNLESS OTHERWISE NOTED. ABOVE COUNTER RECEPTACLES SHALL BE MOUNTED 6" ABOVE BACK
SPLASH TO CENTERLINE OF DEVICE.
3. EQUIPMENT SHALL BE OF MATERIALS SUITABLE FOR AND RATED FOR THE ENVIRONMENT IN WHICH
THEY ARE TO BE INSTALLED.
4. THE FOLLOWING NEC REQUIREMENTS SHALL BE MET:
A. WORKING CLEARANCES FOR ELECTRICAL EQUIPMENT SHALL BE IN COMPLIANCE WITH NEC 110.
B. THE EXCLUSIVELY DEDICATED SPACE EXTENDING FROM FLOOR TO STRUCTURAL CEILING WITH
A WIDTH AND DEPTH OF THE PANELBOARD OR SWITCHBOARD MUST BE CLEAR OF ALL PIPING,
DUCTS, EQUIPMENT FOREIGN TO THE ELECTRICAL EQUIPMENT OR ARCHITECTURAL
APPURTENANCES IN ACCORDANCE WITH NEC 408.
5. WHEN ELECTRICAL BOXES ARE LOCATED IN VERTICAL FIRE RESISTIVE ASSEMBLIES, (CLASSIFIED AS FIRE/SMOKE AND SMOKE PARTITIONS), THEY SHALL BE INSTALLED WITHOUT AFFECTING THE FIRE
CLASSIFICATION. ALL OF THE FOLLOWING CONDITIONS SHALL BE MET:
A. ALL ELECTRICAL BOXES SHALL BE METALLIC.
B. BOX OPENING SHALL OCCUR ONLY ON ONE SIDE OF FRAMING SPACE.
C. BOX OPENING SHALL NOT EXCEED 16 SQUARE INCHES.
D. ALL CLEARANCES BETWEEN OUTLET BOX AND GYPSUM BOARD SHALL BE COMPLETELY FILLED
WITH JOINT COMPOUND (OR OTHER APPROVED MATERIAL).
E. PROVIDE A WALL AROUND OUTLETS LARGER THAN 16 SQUARE INCHES. THE INTEGRITY OF THE
WALL RATING SHALL BE MAINTAINED.
F. THE TOTAL AGGREGATE SURFACE AREA OF THE BOXES SHALL NOT EXCEED 100 SQUARE
INCHES PER 100 SQUARE FEET.
G. OUTLET BOXES LOCATED ON OPPOSITE SIDES OF FIRE RESISTIVE ASSEMBLIES SHALL BE
SEPARATED BY A MINIMUM HORIZONTAL DISTANCE OF 24 INCHES.
H. OUTLET BOXES SHALL BE SECURELY FASTENED TO WALL FRAMING MEMBERS.
I. THE OPENING IN THE GYPSUM BOARD FACING SHALL BE CUT NOT TO EXCEED 1/8 INCH
BETWEEN THE EDGES OF THE OUTLET BOX AND THE EDGES OF THE OPENING.
6. ALL DEVICES SHALL BE MOUNTED VERTICAL, UNLESS OTHERWISE NOTED.
7. PROVIDE AN EXTENSION TO THE EXISTING LIGHTNING PROTECTION SYSTEM ON THE BUILDING IN
COMPLIANCE WITH SPEC SECTION 264113.
8. FOR BUCK HOIST POWER REQUIREMENTS DURING CONSTRUCTION, OBTAIN 480V, 3-PHASE POWER
FROM NORMAL BRANCH PANEL IN ROOM 349, NORTH END OF BUILDING 1. INSTALL CONDUIT, WIRE, CIRCUIT BREAKER, DISCONNECTING MEANS, ETC., IN COORDINATION WITH BUCK HOIST SUPPLIER.
REMOVE ALL DEVICES, FEEDERS, AND EQUIPMENT UPON COMPLETION OF CONSTRUCTION.
PEDESTAL MOUNTED RECEPTACLE
DUPLEX RECEPTACLE
DIMMER SWITCH
MANUAL MOTOR STARTER WITH OVERLOAD HEATERS
SINGLE POLE TIMER SWITCH
SINGLE POLE SWITCH WITH WEATHERPROOF COVER
SINGLE POLE SWITCH WITH OCCUPANCY SENSOR
FOUR-WAY SWITCH
THREE-WAY SWITCH
SINGLE POLE SWITCH
(SUBSCRIPT DENOTES SWITCH LEG)
TAMPER PROOF DUPLEX RECEPTACLE
TWIST LOCK RECEPTACLE
D
WALL MOUNTED LINEAR FIXTURE
FIXTURE DESIGNATION
LOWER CASE LETTER INDICATES SWITCH LEG
CIRCUIT NUMBER
LIGHTING
DESCRIPTIONSYMBOL
FIRE ALARM/DETECTION SYSTEMBASIC MATERIALS CONT.BASIC MATERIALS
F
AUTOMATIC TRANSFER SWITCH
TRANSFORMER
DIRECT DIGITAL CONTROL PANEL
VARIABLE FREQUENCY DRIVE
30AR
20AF
NF
30AR NON-FUSED DISCONNECT SWITCH, SIZE AS NOTED
NF DENOTES NON-FUSED
COMBINATION MAGNETIC MOTOR STARTER, SIZE AS NOTED
3-POLE UNLESS OTHERWISE NOTED
30/3
3R
MOCP # OF POLES
NEMA STARTER SIZE
ENCLOSURE NEMA 1 UNLESS NOTED
FUSED DISCONNECT
AR DENOTES AMP RATING OF SWITCH
AF DENOTES AMP FUSE SIZE
SECURITY CAMERA
CEILING MOUNTED RECEPTACLE
ROUND DOWNLIGHT FIXTURE
DESCRIPTIONSYMBOL DESCRIPTIONSYMBOL
COMBINATION AUDIBLE/VISUAL NOTIFICATION DEVICE
HORN/FLASHING "FIRE" LIGHT
CD = CANDELA RATING
ROUND PENDANT FIXTURE
T
WP
S
CR
GND
J
SS
XX
ST
CAM
VFD
DDC
T
C
L
EQ
UP
DN
NEW WORK
A
2a
SQUARE DOWNLIGHT FIXTURE
LINEAR PENDANT FIXTURE
X
R
F
F
F
P
TS
FS
H
H
H
FACP
FATP
FAAP
F
X
WALL MOUNTED SMOKE DETECTOR, PHOTO-ELECTRIC TYPE
UNLESS OTHERWISE NOTED
HIGH OIL ALARM PANEL
GENERATOR ALARM ANNUNCIATOR PANEL
GAAP
HOAP
COMBINATION CARBON MONOXIDE/NITROGEN DIOXIDE SENSORCO
GROUND FLOOD LIGHT FIXTURE
EMERGENCY POWER OFF BUTTONEP
CEILING MOUNTED OCCUPANCY SENSOR SWITCH
OD
SINGLE POLE SWITCH WITH OCCUPANCY SENSOR AND DIMMER
S
S
S
EXTERIOR POLE TOP LIGHT FIXTURE,
ARROW INDICATES AIM OF DISTRIBUTION
Z
C
RK
CB
SH
T
E
S
D
N
N
SE
SA
N NURSE CALL SYSTEM CONDUIT AND WIRING
NCMS
NURSE CALL MASTER STATION
NCEC
NURSE CALL EQUIPMENT CABINET
CODE BLUE ANNUNCIATOR PANEL WALL MOUNTED
CBAP
CORRIDOR ZONE LIGHT
CORRIDOR DOME LIGHT WALL MOUNTED
37-PIN PATIENT BED CONNECTION
CODE BLUE EMERGENCY STATION
SHOWER EMERGENCY STATION
TOILET EMERGENCY STATION
EMERGENCY STATION
STAFF STATION
DUTY STATION
DUAL PATIENT STATION
SINGLE PATIENT STATION
NURSE CALL SYSTEMS
STAFF EMERGENCY STATION
STAFF EMERGENCY ANNUNCIATOR
NCRA
NURSE CALL REMOTE ALARM
NCMA NURSE CALL MASTER ALARM
12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554
©Copyright 2023
TLC No.:
www.tlc-engineers.com
119437
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg.
PROJECT TEAM:
Office of
Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
Department of Veterans Affairs
MURFREESBORO, TN
615.370.8500
615.370.8530 hfrdesign.com
214 Centerview Drive Suite 300 Brentwood, TN 37027
Phase
FULLY SPRINKLERED
C R e v it
L o c a ls \1
-E L
E C
-V A
M C
W a rd
B
R a n d re .n g u y e n
V D
W
F .r v t
/1
/2
:4
:2
A
M
06-13-2023
626A4-19-101
E-EI-00
AE RENOVATE WARD 1B
ELECTRICAL SYMBOLS LEGEND,
LIGHTING FIXTURE SCHEDULE, AND
GENERAL NOTES
AWD
HFR Project No: 2019056
100% CONSTRUCTION
DOCUMENTS
DLM
ELECTRICAL SHEET LIST
NO. SHEET NAME ISSUED
E-EI-00 ELECTRICAL SYMBOLS LEGEND, LIGHTING FIXTURE SCHEDULE, AND GENERAL NOTES Yes
E-EI-01 PARTIAL ELECTRICAL RISER DIAGRAM - DEMOLITION Yes
E-EI-02 PARTIAL ELECTRICAL RISER DIAGRAM - NEW WORK Yes
E-EI-03 ELECTRICAL PANEL SCHEDULES Yes
E-EI-04 ELECTRICAL PANEL SCHEDULES Yes
E-EI-05 ELECTRICAL DETAILS Yes
E-EI-06 ELECTRICAL DETAILS Yes
E-ED-00 3RD FLOOR - DEMOLITION PLAN - ELECTRICAL - OVERALL Yes
E-ED-01 3RD FLOOR - DEMOLITION PLAN - ELECTRICAL - PART A Yes
E-ED-02 3RD FLOOR - DEMOLITION PLAN - ELECTRICAL - PART B Yes
E-ED-03 3RD FLOOR - DEMOLITION PLAN - ELECTRICAL - PART C Yes
E-EP-01 3RD FLOOR - NEW WORK PLAN - POWER - PART A Yes
E-EP-02 3RD FLOOR - NEW WORK PLAN - POWER - PART B Yes
E-EP-03 3RD FLOOR - NEW WORK PLAN - POWER - PART C Yes
E-EP-04 3RD FLOOR ROOF - NEW WORK PLAN - POWER - PART A Yes
E-EL-01 3RD FLOOR - NEW WORK PLAN - LIGHTING - PART A Yes
E-EL-02 3RD FLOOR - NEW WORK PLAN - LIGHTING - PART B Yes
E-EL-03 3RD FLOOR - NEW WORK PLAN - LIGHTING - PART C Yes
E-EY-01 3RD FLOOR - NEW WORK PLAN - SYSTEMS - PART A Yes
E-EY-02 3RD FLOOR - NEW WORK PLAN - SYSTEMS - PART B Yes
E-EY-03 3RD FLOOR - NEW WORK PLAN - SYSTEMS - PART C Yes
Lighting Fixture Schedule
Type Description Manufacturer Model Lamp Electrical Data Type Comments
A 2'x4' LED LOW PROFILE TROFFER FIXTURE, ACRYLIC LENS, 4033 LUMEN, >80 CRI
LITHONIA
OR APPROVED EQUAL
CPX 2X4 AL08 SWW7 M2
OR APPROVED EQUAL
LED 277 V/1-28 VA
B 2'x2' LED LOW PROFILE TROFFER FIXTURE, ACRYLIC LENS, 2570 LUMEN, >80 CRI
LITHONIA
OR APPROVED EQUAL
CPX 2X2 AL07 SWW7 M4
OR APPROVED EQUAL
LED 277 V/1-19 VA
C 4' LED STRIP FIXTURE, ROUND LENSED, 80 CRI, DIMMABLE LITHONIA
OR APPROVED EQUAL
CSS L48 ALO3 MVOLT SWW3 80CRI
OR APPROVED EQUAL
LED 277 V/1-16 VA
D 6" LED DOWNLIGHT, 1110 LUMEN, DIMMABLE, 90 CRI, 3500K, MEDIUM
DISTRIBUTION
LITHONIA
OR APPROVED EQUAL
WF6 LED 27K30K35K MVOLT 90CRI MW
OR APPROVED EQUAL
LED 277 V/1-14 VA
F LED DECORATIVE WALL SCONCE, ALUMINUM CONSTRUCTION, ACRYLIC
DIFFUSER
BROWNLEE
OR APPROVED EQUAL
7328 NT H32 40K
OR APPROVED EQUAL
LED 277 V/1-32 VA
G WALL MOUNTED LED VANITY FIXTURE, 4000K WHITE, WHITE FINISH,
DIMMABLE
EUREKA
OR APPROVED EQUAL
3211C LED.16 35 277 DV SC WH
OR APPROVED EQUAL
LED 277 V/1-16 VA COORDINATE MOUNTING HEIGHT WITH ARCHITECTURAL ELEVATION
H 4' DIRECT/INDIRECT LED WALL MOUNTED LINEAR PATIENT BED LIGHT,
DIMMABLE, LOW VOLTAGE RELAY FOR PATIENT BED CONTROLLER
KENALL
OR APPROVED EQUAL
MPWUD MW 1/1 45L 40K8 DIM1 DV LVCD NLA*
OR APPROVED EQUAL
LED 277 V/1-45 VA PROVIDE FIXTURE WITH AMBER LED NIGHTLIGHT (EITHER LEFT OR RIGHT) ON
ROOM ENTRY DOOR SIDE OF BED. COORDINATE QUANTITIES OF EACH BASED
UPON ROOM ORIENTATIONS.
UC 2' LED UNDERCABINET, 788 LUMEN, DIMMABLE, WHITE FINISH JUNO
OR APPROVED EQUAL
UCES 24IN SWW6 90CRI WH M6
OR APPROVED EQUAL
LED 120 V/1-11 VA CONNECT TO NEAREST NON-DEDICATED NORMAL POWER RECEPTACLE CIRCUIT
X UNIVERSAL MOUNT LED EDGE LIT EXIT SIGN, ALUMINUM HOUSING, RED
LETTERING
EXITRONIX
OR APPROVED EQUAL
S900UM-WB-SR-R
OR APPROVED EQUAL
LED 277 V/1-4 VA COORDINATE CHEVRONS AND NUMBER OF FACES WITH FLOOR PLANS AND LIFE
SAFETY PLANS
GL 05.01 PHASING PLAN
No. Date Description
Yes
2N1Z
NOR
100A
208V
2LC1Z
CR
225A
208V
2N1Y
NOR
100A
208V
2LC1Y
CR
100A
208V
2N1X
NOR
100A
208V
2LC1X
CR
225A
208V
2LC1W
CR
208V
2L13
LS
100A
208V
L13
LS
100A
480V
2LC1WA
CR
225A
208V
C13
CR
100A
480V
2N1W
NOR
70A
208V
N13
NOR
100A
480V
N12
NOR
100A
480V
C12
CR
100A
480V
2N1S
NOR
100A
208V
2C1S
CR
225A
208V
L12
LS
100A
480V
2L12
LS
100A
208V
2LC1Z
NOR
225A
208V
2N1V
NOR
225A
208V
2N1FF
EQ
80A
208V
N14
NOR
225A
480V
Q15
EQ
225A
480V
N15
NOR
225A
480V
SEG1
CR
100A
208V
2N1M
NOR
225A
208V
2L11N
LS
100A
208V
L11N
LS
100A
480V
2LC1F
CR
100A
208V
2N1N
NOR
225A
208V
C11N
CR
100A
480V
N11N
NOR
100A
480V
2N20G1
NOR
225A
208V
2N1K
NOR
125A
208V
2N1G
NOR
225A
208V
2N1F
NOR
225A
208V
2LC1G
NOR
100A
208V
ATS-1C
CR
600A
4P
C1GM
CR
600A
480V
2LC1M
CR
225A
208V
ATS-1L
LS
260A
4P
L1GM
LS
250A
480V
2L1GM
LS
150A
208V
ATS-1Q
EQ
600A
4P
Q1GM
EQ
600A
480V
ATS-1X
EQ
600A
4P
X1GM
EQ
600A
480V
E1GM
EMER
1000A
480V
2N11
NOR
400A
208V
2N1A
NOR
800A
208V
2N1C
NOR
225A
208V
CEG
CR
225A
208V
2N1P
NOR
600A
208V
SPD1
EQ
600A
208V
2Q1
EQ
400A
208V
SEG
CR
225A
208V
2N1E
NOR
225A
208V
2N1H
NOR
225A
208V
2N1J
NOR
225A
208V
2N1
NOR
400A
208V
SB6120-0641
NOR
2000A
208V
SPDMCC
EQ
480V
MSBE
SB6120-0640
NOR
800A MB
208V
2C1GM
CR
500A
208V
N1GM
NOR
1200A
480V
N1MSB
NOR
2000A
480V
(MAIN)
N1MSB
NOR
2000A
480V
(DIST)
XFMR
1MVA
TC1GM
150kVA
TQ1GM
112.5kVA
TN1GM
750kVA
TVSS TVSS
TVSS
TVSS
TSPDTL1GM
45kVA
TVSS
2000/3
LSIG
400/3
GROUND FLOOR NORTH ELECTRICAL ROOM G17 SITE MAIN ELECTRICAL ROOM G26 ESSENTIAL SYSTEM ELECTRICAL ROOM G25 ELECTRICAL ROOM G29 ELECTRICAL SWITCHGEAR G30 GROUND FLOOR SOUTH ELECTRICAL ROOM
ELECTRICAL ROOM 237ELECTRICAL ROOM 212ELECTRICAL ROOM 273SECOND FLOOR NORTH ELECTRICAL ROOM 251
THIRD FLOOR NORTH ELECTRICAL ROOM 349 ELECTRICAL ROOM 374
ELECTRICAL ROOM 406A
FOURTH FLOOR
THIRD FLOOR
SECOND FLOOR
FIRST FLOOR
GROUND FLOOR
ATTIC
ELECTRICAL ROOM 312 ELECTRICAL ROOM 336
TO
B
U
IL
D
IN
G
1 1
30kVA
2C1AV
CR
60A
208V
2N1AV
NOR
100A
208V
2L1V
LS
70A
208V
2C1AS
CR
100A
480V
2N1AS
NOR
150A
208V
2C1T
CR
150A
208V
2N1T
NOR
150A
208V
2C1AT
CR
70A
208V
2N1AT
NOR
100A
208V
2L1T
LS
100A
208V
ELECTRICAL ROOM A270
T-N12
45kVA
T-C12
45kVA
T-L12
30kVA
ATS-Q1-4
EQ
600A
4P
Q1-4-1S
EQ
225A
480V
Q1-4-1N
EQ
225A
480V
NAME
BRANCH
###A
###V
NAME
###kVA
NAME
BRANCH
###V
RATING
TYPE
NAME
BRANCH
###A
#P
TVSSSWITCHBOARD
BRANCH KEY:
NOR: NORMAL BRANCH
LS: LIFE SAFETY
CR: CRITICAL BRANCH
EQ: EQUIPMENT BRANCH
BRANCH PANEL
TRANSFORMER AUTOMATIC TRANSFER SWITCH
ENCLOSED CIRCUIT BREAKER
RATING
DISCONNECT SWITCH
GROUND
SURGE SUPPRESSION
RISER DIAGRAM LEGEND
12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554
©Copyright 2023
TLC No.:
www.tlc-engineers.com
119437
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg.
PROJECT TEAM:
Office of
Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
Department of Veterans Affairs
MURFREESBORO, TN
615.370.8500
615.370.8530 hfrdesign.com
214 Centerview Drive Suite 300 Brentwood, TN 37027
Phase
FULLY SPRINKLERED
C R e v it
L o c a ls \1
-E L
E C
-V A
M C
W a rd
B
R a n d re .n g u y e n
V D
W
F .r v t
/1
/2
:4
:2
A
M
06-13-2023
626A4-19-101
E-EI-01
AE RENOVATE WARD 1B
PARTIAL ELECTRICAL RISER DIAGRAM -
DEMOLITION
AWD
HFR Project No: 2019056
100% CONSTRUCTION
DOCUMENTS
DLM
GENERAL NOTES:
1. ALL EXISTING ELECTRICAL EQUIPMENT INDICATED ON THIS RISER
DIAGRAM WAS TRANSCRIBED FROM RECORD DOCUMENTS
FURNISHED BY THE VETERAN’S AFFAIRS ENGINEERING
DEPARTMENT. PLEASE NOTIFY TLC IMMEDIATELY WITH ANY
DISCREPANCIES BETWEEN THE EXISTING FIELD CONDITIONS AND
THE ELECTRICAL EQUIPMENT INDICATED ON THIS DOCUMENT.
KEYED NOTES:
AREA WITHIN SCOPE OF VA PROJECT #626A4-18-105
"RENOVATE WARD 1A". REFER TO PROJECT DOCUMENTS
FOR SCOPE OF WORK. COORDINATE DEMOLITION AND RE-
FEED OF CONDUCTORS AND CONDUITS WITH NEW
CONDITIONS.
PHASE LEGEND:
EXISTING TO REMAIN
DEMOLISHED
NEW WORK
2N1Z
NOR
84 POLE
100A
208V
2C1Z
CR
84 POLE
225A
208V
2L13
LS
100A
208V
L13
LS
100A
480V
2C1W
CR
84 POLE
225A
208V
C13
CR
100A
480V
2N1W
NOR
84 POLE
100A
208V
N13
NOR
100A
480V
2N1S
NOR
100A
208V
2LC1Z
NOR
225A
208V
2N1V
NOR
225A
208V
2N1FF
EQ
80A
208V
N14
NOR
225A
480V
Q15
EQ
225A
480V
N15
NOR
225A
480V
SEG1
CR
100A
208V
2N1M
NOR
225A
208V
2L11N
LS
100A
208V
L11N
LS
100A
480V
2LC1F
CR
100A
208V
2N1N
NOR
225A
208V
C11N
CR
100A
480V
N11N
NOR
100A
480V
2N20G1
NOR
225A
208V
2N1K
NOR
125A
208V
2N1G
NOR
225A
208V
2N1F
NOR
225A
208V
2LC1G
NOR
100A
208V
ATS-1C
CR
600A
4P
C1GM
CR
600A
480V
2LC1M
CR
225A
208V
ATS-1L
LS
260A
4P
L1GM
LS
250A
480V
2L1GM
LS
150A
208V
ATS-1Q
EQ
600A
4P
Q1GM
EQ
600A
480V
ATS-1X
EQ
600A
4P
X1GM
EQ
600A
480V
E1GM
EMER
1000A
480V
2N11
NOR
400A
208V
2N1A
NOR
800A
208V
2N1C
NOR
225A
208V
CEG
CR
225A
208V
2N1P
NOR
600A
208V
SPD1
EQ
600A
208V
2Q1
EQ
400A
208V
SEG
CR
225A
208V
2N1E
NOR
225A
208V
2N1H
NOR
225A
208V
2N1J
NOR
225A
208V
2N1
NOR
400A
208V
SB6120-0641
NOR
2000A
208V
SPDMCC
EQ
480V
MSBE
SB6120-0640
NOR
800A MB
208V
2C1GM
CR
500A
208V
N1GM
NOR
1200A
480V
N1MSB
NOR
2000A
480V
(MAIN)
N1MSB
NOR
2000A
480V
(DIST)
XFMR
1MVA
TC1GM
150kVA
TQ1GM
112.5kVA
TN1GM
750kVA
TVSS TVSS
TVSS
TVSS
TSPDTL1GM
45kVA
TVSS
2000/3
LSIG
400/3
GROUND FLOOR NORTH ELECTRICAL ROOM G17 SITE MAIN ELECTRICAL ROOM G26 ESSENTIAL SYSTEM ELECTRICAL ROOM G25 ELECTRICAL ROOM G29 ELECTRICAL SWITCHGEAR G30 GROUND FLOOR SOUTH ELECTRICAL ROOM
SECOND FLOOR NORTH ELECTRICAL ROOM 251
THIRD FLOOR NORTH ELECTRICAL ROOM B344
ELECTRICAL ROOM 406A
FOURTH FLOOR
THIRD FLOOR
SECOND FLOOR
FIRST FLOOR
GROUND FLOOR
ATTIC
ELECTRICAL ROOM B326
TO
B
U
IL
D
IN
G
N12
NOR
100A
480V
C12
CR
100A
480V
2N1S
NOR
100A
208V
2C1S
CR
225A
208V
L12
LS
100A
480V
2L12
LS
100A
208V
2LC1Z
NOR
225A
208V
2N1V
NOR
225A
208V
ELECTRICAL ROOM 237
2C1AV
CR
60A
208V
2N1AV
NOR
100A
208V
2L1V
LS
70A
208V
2C1AS
CR
100A
480V
2N1AS
NOR
150A
208V
2C1T
CR
150A
208V
2N1T
NOR
150A
208V
2C1AT
CR
70A
208V
2N1AT
NOR
100A
208V
2L1T
LS
100A
208V
ELECTRICAL ROOM A270
T-N12
45kVA
T-C12
45kVA
T-L12
30kVA
2N1X
NOR
100A
208V
COMMUNICATIONS ROOM B334
TN13
75kVA
2N13
NOR
300A
208V
2C1X
CR
100A
208V
ATS-Q1-4
EQ
600A
4P
2Q1-4-1S
EQ
225A
480V
Q1-4-1N
EQ
225A
480V
3 6
#2
NAME
BRANCH
###A
###V
NAME
###kVA
NAME
BRANCH
###V
RATING
TYPE
NAME
BRANCH
###A
#P
TVSSSWITCHBOARD
BRANCH KEY:
NOR: NORMAL BRANCH
LS: LIFE SAFETY
CR: CRITICAL BRANCH
EQ: EQUIPMENT BRANCH
BRANCH PANEL
TRANSFORMER AUTOMATIC TRANSFER SWITCH
ENCLOSED CIRCUIT BREAKER
RATING
DISCONNECT SWITCH
GROUND
SURGE SUPPRESSION
RISER DIAGRAM LEGEND
12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554
©Copyright 2023
TLC No.:
www.tlc-engineers.com
119437
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg.
PROJECT TEAM:
Office of
Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
Department of Veterans Affairs
MURFREESBORO, TN
615.370.8500
615.370.8530 hfrdesign.com
214 Centerview Drive Suite 300 Brentwood, TN 37027
Phase
FULLY SPRINKLERED
C R e v it
L o c a ls \1
-E L
E C
-V A
M C
W a rd
B
R a n d re .n g u y e n
V D
W
F .r v t
/1
/2
:4
:2
A
M
06-13-2023
626A4-19-101
E-EI-02
AE RENOVATE WARD 1B
PARTIAL ELECTRICAL RISER DIAGRAM -
NEW WORK
AWD
HFR Project No: 2019056
100% CONSTRUCTION
DOCUMENTS
DLM
GENERAL NOTES:
1. ALL EXISTING ELECTRICAL EQUIPMENT INDICATED ON THIS RISER
DIAGRAM WAS TRANSCRIBED FROM RECORD DOCUMENTS
FURNISHED BY THE VETERAN’S AFFAIRS ENGINEERING
DEPARTMENT. PLEASE NOTIFY TLC IMMEDIATELY WITH ANY
DISCREPANCIES BETWEEN THE EXISTING FIELD CONDITIONS AND
THE ELECTRICAL EQUIPMENT INDICATED ON THIS DOCUMENT.
2. INSTALL 3/4"C, 1#10 GND (FOR BONDING PER NATIONAL
ELECTRICAL CODE 517.14) BETWEEN GROUND BUSES OF ANY TWO
NORMAL AND ESSENTIAL PANELS WHICH SERVE THE SAME
PATIENT CARE AREA.
FEEDER SIZES:
125A, (3) #1, #6 GND, 1-1/2" C.
300A, (4) 350 MCM, #4 GND, 3-1/2" C.
150A, (3) #1/0, #6 GND, 2" C.
100A, (4) #3, #8 GND, 1-1/2" C.
150A, (3) #1/0, #6 GND, 2" C.
60A, (4) #6, #8 GND, 1-1/4" C.
PHASE LEGEND:
EXISTING TO REMAIN
DEMOLISHED
NEW WORK2
12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554
©Copyright 2023
TLC No.:
www.tlc-engineers.com
119437
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg.
PROJECT TEAM:
Office of
Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
Department of Veterans Affairs
MURFREESBORO, TN
615.370.8500
615.370.8530 hfrdesign.com
214 Centerview Drive Suite 300 Brentwood, TN 37027
Phase
FULLY SPRINKLERED
C R e v it
L o c a ls \1
-E L
E C
-V A
M C
W a rd
B
R a n d re .n g u y e n
V D
W
F .r v t
/1
/2
:4
:3
A
M
06-13-2023
626A4-19-101
E-EI-03
AE RENOVATE WARD 1BELECTRICAL PANEL SCHEDULES
AWD
HFR Project No: 2019056
100% CONSTRUCTION
DOCUMENTS
DLM
1. CONNECT TO EXISTING SPARE CIRCUIT BREAKER.
Notes:
Total Est. Demand: 1 A
Total Conn.: 1 A
Total Est. Demand: 854 VA
Total Conn. Load: 854 VA
Lighting 854 VA 100.00% 854 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Total Amps: 1 A 1 A 1 A
Total Load: 0.2 kVA 0.3 kVA 0.3 kVA
41 Space -- 1 -- -- 1 -- Space 42
39 Space -- 1 -- -- 1 -- Space 40
37 Space -- 1 -- -- 1 -- Space 38
35 Space -- 1 -- -- 1 -- Space 36
33 Space -- 1 -- -- 1 -- Space 34
31 Space -- 1 -- -- 1 -- Space 32
29 Space -- 1 -- -- 1 -- Space 30
27 Space -- 1 -- -- 1 -- Space 28
25 Space -- 1 -- -- 1 -- Space 26
23 Space -- 1 -- -- 1 -- Space 24
21 Space -- 1 -- -- 1 -- Space 22
19 Space -- 1 -- -- 1 -- Space 20
17 Space -- 1 -- -- 1 -- Space 18
15 Space -- 1 -- -- 1 -- Space 16
13 Space -- 1 -- -- 1 -- Space 14
11 Space -- 1 -- -- 1 -- Space 12
9 Space -- 1 -- -- 1 -- Space 10
7 Space -- 1 -- -- 1 -- Space 8
1 5 Lighting - Egress Area C 20 A 1 0.3 0.0 1 20 A Spare 6
1 3 Lighting - Egress Area B 20 A 1 0.3 0.0 1 20 A Spare 4
1 1 Lighting - Egress Area A 20 A 1 0.2 0.0 1 20 A Spare 2
N O T E CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
N O T E
LOAD/PHASE (KVA)
EXISTING PANEL
Notes:
Enclosure: TYPE 1 MCB Rating:
Mounting: SURFACE Wires: 4 Mains Rating: 225 A
Supply From: L1GM Phases: 3 Main Type: MLO
Location: ELECTRICAL B344 Volts: 480/277 Wye A.I.C. Rating: 14000
Branch Panel: L13
1. CONNECT TO EXISTING SPARE CIRCUIT BREAKER.
Notes:
Total Est. Demand: 1 A
Total Conn.: 1 A
Total Est. Demand: 400 VA
Total Conn. Load: 400 VA
Other 400 VA 100.00% 400 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Total Amps: 3 A 0 A 0 A
Total Load: 0.4 kVA 0.0 kVA 0.0 kVA
41 Space -- 1 -- -- 1 -- Space 42
39 Space -- 1 -- -- 1 -- Space 40
37 Space -- 1 -- -- 1 -- Space 38
35 Space -- 1 -- -- 1 -- Space 36
33 Space -- 1 -- -- 1 -- Space 34
31 Space -- 1 -- -- 1 -- Space 32
29 Space -- 1 -- -- 1 -- Space 30
27 Space -- 1 -- -- 1 -- Space 28
25 Space -- 1 -- -- 1 -- Space 26
23 Space -- 1 -- -- 1 -- Space 24
21 Space -- 1 -- -- 1 -- Space 22
19 Space -- 1 -- -- 1 -- Space 20
17 Spare 20 A 1 0.0 0.0 1 20 A Spare 18
15 Spare 20 A 1 0.0 0.0 1 20 A Spare 16
13 Spare 20 A 1 0.0 0.0 1 20 A Spare 14
11 Spare 20 A 1 0.0 0.0 1 20 A Spare 12
9 Spare 20 A 1 0.0 0.0 1 20 A Spare 10
7 Spare 20 A 1 0.0 0.0 1 20 A Spare 8
5 Spare 20 A 1 0.0 0.0 1 20 A Spare 6
3 Spare 20 A 1 0.0 0.0 1 20 A Spare 4
1 1 Door Power 20 A 1 0.4 2
N O T E CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
N O T E
LOAD/PHASE (KVA)
EXISTING PANEL
Notes:
Enclosure: TYPE 1 MCB Rating:
Mounting: SURFACE Wires: 4 Mains Rating: 225 A
Supply From: 2L1GM Phases: 3 Main Type: MLO
Location: ELECTRICAL B344 Volts: 120/208 Wye A.I.C. Rating: 22000
Branch Panel: 2L13
1. CONNECT TO EXISTING SPARE CIRCUIT BREAKER.
Notes:
Total Est. Demand: 3 A
Total Conn.: 3 A
Total Est. Demand: 2484 VA
Total Conn. Load: 2484 VA
Lighting 2484 VA 100.00% 2484 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Total Amps: 4 A 3 A 2 A
Total Load: 1.2 kVA 0.7 kVA 0.6 kVA
41 Space -- 1 -- -- 1 -- Space 42
39 Space -- 1 -- -- 1 -- Space 40
37 Space -- 1 -- -- 1 -- Space 38
35 Spare 20 A 1 0.0 0.0 1 20 A Spare 36
33 Spare 20 A 1 0.0 0.0 1 20 A Spare 34
31 Spare 20 A 1 0.0 0.0 1 20 A Spare 32
29 Spare 20 A 1 0.0 0.0 1 20 A Spare 30
27 Spare 20 A 1 0.0 0.0 1 20 A Spare 28
25 Spare 20 A 1 0.0 0.0 1 20 A Spare 26
23 Spare 20 A 1 0.0 0.0 1 20 A Spare 24
21 Spare 20 A 1 0.0 0.0 1 20 A Spare 22
19 Spare 20 A 1 0.0 0.0 1 20 A Spare 20
17 Spare 20 A 1 0.0 0.0 1 20 A Spare 18
15 Spare 20 A 1 0.0 0.0 1 20 A Lighting Electrical Room B1-383 16 1
13 Spare 20 A 1 0.0 0.3 1 20 A Lighting - Patient Rooms Area C 14 1
11 Spare 20 A 1 0.0 0.6 1 20 A Lighting - Area C 12 1
9 Spare 20 A 1 0.0 0.0 1 20 A Lighting - Comm, Data, B1-316, B1-314 10 1
7 Spare 20 A 1 0.0 0.5 1 20 A Lighting - Area A 8 1
5 Spare 20 A 1 0.0 0.0 1 20 A Lighting Electrical Room B1-352 6 1
3 Spare 20 A 1 0.0 0.7 1 20 A Lighting - Patient Rooms Area B 4 1
1 Spare 20 A 1 0.0 0.3 1 20 A Lighting - Patient Rooms Area B 2 1
N O T E CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
N O T E
LOAD/PHASE (KVA)
EXISTING PANEL
Notes:
Enclosure: TYPE 1 MCB Rating:
Mounting: SURFACE Wires: 4 Mains Rating: 225 A
Supply From: C1GM Phases: 3 Main Type: MLO
Location: ELECTRICAL B344 Volts: 480/277 Wye A.I.C. Rating: 35000
Branch Panel: C13
Notes:
Total Est. Demand: 92 A
Receptacle 27700 VA 68.05% 18850 VA Total Conn.: 116 A
Power 8800 VA 100.00% 8800 VA Total Est. Demand: 32970 VA
Other 1400 VA 100.00% 1400 VA Total Conn. Load: 41820 VA
Motor 3920 VA 100.00% 3920 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Total Amps: 130 A 109 A 110 A
Total Load: 15.6 kVA 13.0 kVA 13.2 kVA
83 Spare 20 A 1 0.0 0.0 1 20 A Spare 84
81 Spare 20 A 1 0.0 0.0 1 20 A Spare 82
79 Spare 20 A 1 0.0 0.0 1 20 A Spare 80
77 Spare 20 A 1 0.0 0.0 1 20 A Spare 78
75 Spare 20 A 1 0.0 0.0 1 20 A Spare 76
73 NCMS - B1-317 CHARGE STATION 20 A 1 0.2 0.5 1 20 A Rec - B1-337 Automated Laundry Cart 74
71 Rec - B1-349 Bariatric Lift 20 A 1 0.2 0.2 1 20 A Rec - B1-343 Bariatric Lift 72
69 Rec - B1-349 Bed Power 20 A 1 0.2 0.2 1 20 A Rec - B1-343 Bed Power 70
67 Rec - B1-349 Computer Cart 20 A 1 0.2 0.2 1 20 A Rec - B1-343 Computer Cart 68
65 Rec - B1-349 Headwall 20 A 1 0.5 0.5 1 20 A Rec - B1-343 Headwall 66
63 Rec - B1-349 Headwall 20 A 1 0.5 0.5 1 20 A Rec - B1-343 Headwall 64
61 Rec - B1-348 Bariatric Lift 20 A 1 0.2 0.2 1 20 A Rec - B1-342 Bariatric Lift 62
59 Rec - B1-348 Bed Power 20 A 1 0.2 0.2 1 20 A Rec - B1-342 Bed Power 60
57 Rec - B1-348 Computer Cart 20 A 1 0.2 0.2 1 20 A Rec - B1-342 Computer Cart 58
55 Rec - B1-348 Headwall 20 A 1 0.5 0.5 1 20 A Rec - B1-342 Headwall 56
53 Rec - B1-348 Headwall 20 A 1 0.5 0.5 1 20 A Rec - B1-342 Headwall 54
51 Spare 20 A 1 0.0 0.2 1 20 A Rec - B1-341 Bariatric Lift 52
-- 49 -- -- -- 1.0 0.2 1 20 A Rec - B1-341 Bed Power 50
47 CU-2/AC-2 25 A 2 1.0 0.2 1 20 A Rec - B1-341 Computer Cart 48
-- 45 -- -- -- 1.0 0.5 1 20 A Rec - B1-341 Headwall 46
43 CU-1/AC-1 25 A 2 1.0 0.5 1 20 A Rec - B1-341 Headwall 44
41 Rec - B1-317 Charge Nurse 20 A 1 0.7 0.2 1 20 A Rec - B1-339 Ante Room 42
39 Rec - B1-331A Corridor, Charting 20 A 1 0.5 0.2 1 20 A Rec - B1-340 Bariatric Lift 40
37 Rec - B1-331A Corridor, Charting 20 A 1 0.5 0.2 1 20 A Rec - B1-340 Bed Power 38
35 Rec - B1-352 Electrical Room 20 A 1 0.4 0.2 1 20 A Rec - B1-340 Computer Cart 36
33 Rec - B1-351 Equip Storage 20 A 1 0.4 0.5 1 20 A Rec - B1-340 Headwall 34
31 Rec - B1-344 Team Work 20 A 1 1.1 0.5 1 20 A Rec - B1-340 Headwall 32
29 Rec - B1-344 Team Work 20 A 1 0.7 0.2 1 20 A Rec - B1-335 Bariatric Lift 30
27 Rec - B1-333 - Nourishment, Refrigerator 20 A 1 0.2 0.2 1 20 A Rec - B1-335 Bed Power 28
25 Rec - B1-333 - Nourishment, Ice Maker 20 A 1 0.2 0.2 1 20 A Rec - B1-335 Computer Cart 26
23 Rec - B1-330 Corridor, Charting 20 A 1 0.5 0.5 1 20 A Rec - B1-335 Headwall 24
21 Rec - B1-346 Nurse Station 20 A 1 0.7 0.5 1 20 A Rec - B1-335 Headwall 22
19 Rec - B1-330 Corridor, Charting 20 A 1 0.5 0.2 1 20 A Rec - B1-334 Bariatric Lift 20
-- 17 -- -- -- 2.9 0.2 1 20 A Rec - B1-334 Bed Power 18
-- 15 -- -- -- 2.9 0.2 1 20 A Rec - B1-334 Computer Cart 16
13 Power - Retherm 30 A 3 2.9 0.5 1 20 A Rec - B1-334 Headwall 14
11 Rec - B1-318 Nurse Station 20 A 1 0.9 0.5 1 20 A Rec - B1-334 Headwall 12
9 Rec - B1-318 Nurse Station 20 A 1 1.1 0.2 1 20 A Rec - B1-332 Bariatric Lift 10
7 Rec - B1-317 Charge Nurse 20 A 1 0.9 0.2 1 20 A Rec - B1-332 Bed Power 8
-- 5 -- -- -- 1.0 0.2 1 20 A Rec - B1-332 Computer Cart 6
-- 3 -- -- -- 1.4 0.5 1 20 A Rec - B1-332 Headwall 4
1 2C1X 100 A 3 2.0 0.5 1 20 A Rec - B1-332 Headwall 2
N O T E CKT Circuit Description Trip Poles
A B C
Poles Trip Circuit Description CKT
N O T E
LOAD/PHASE (KVA)
NEW PANEL, REUSE EXISTING FEEDER
Notes:
Enclosure: TYPE 1 MCB Rating:
Mounting: SURFACE Wires: 4 Mains Rating: 150 A
Supply From: 2C1GM Phases: 3 Main Type: MCB
Location: ELECTRICAL B344 Volts: 120/208 Wye A.I.C. Rating: 22000
Branch Panel: 2C1W
Notes:
Total Est. Demand: 49 A
Total Conn.: 69 A
Total Est. Demand: 17510 VA
Total Conn. Load: 25020 VA
Receptacle 25020 VA 69.98% 17510 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Total Amps: 71 A 73 A 66 A
Total Load: 8.5 kVA 8.6 kVA 7.9 kVA
83 Spare 20 A 1 0.0 0.0 1 20 A Spare 84
81 Spare 20 A 1 0.0 0.0 1 20 A Spare 82
79 Spare 20 A 1 0.0 0.0 1 20 A Spare 80
77 Spare 20 A 1 0.0 0.0 1 20 A Spare 78
75 Spare 20 A 1 0.0 0.0 1 20 A Spare 76
73 Spare 20 A 1 0.0 0.0 1 20 A Spare 74
71 Rec - B1-382 Bariatric Lift 20 A 1 0.2 0.2 1 20 A Rec - B1-380 Bariatric Lift 72
69 Rec - B1-382 Bed Power 20 A 1 0.2 0.2 1 20 A Rec - B1-380 Bed Power 70
67 Rec - B1-382 Computer Cart 20 A 1 0.2 0.2 1 20 A Rec - B1-380 Computer Cart 68
65 Rec - B1-382 Headwall 20 A 1 0.5 0.5 1 20 A Rec - B1-380 Headwall 66
63 Rec - B1-382 Headwall 20 A 1 0.5 0.5 1 20 A Rec - B1-380 Headwall 64
61 Rec - B1-381 Bariatric Lift 20 A 1 0.2 0.2 1 20 A Rec - B1-379 Bariatric Lift 62
59 Rec - B1-381 Bed Power 20 A 1 0.2 0.2 1 20 A Rec - B1-379 Bed Power 60
57 Rec - B1-381 Computer Cart 20 A 1 0.2 0.2 1 20 A Rec - B1-379 Computer Cart 58
55 Rec - B1-381 Headwall 20 A 1 0.5 0.5 1 20 A Rec - B1-379 Headwall 56
53 Rec - B1-381 Headwall 20 A 1 0.5 0.5 1 20 A Rec - B1-379 Headwall 54
51 Spare 20 A 1 0.0 0.2 1 20 A Rec - B1-378 Bariatric Lift 52
49 Spare 20 A 1 0.0 0.2 1 20 A Rec - B1-378 Bed Power 50
47 Spare 20 A 1 0.0 0.2 1 20 A Rec - B1-378 Computer Cart 48
45 Spare 20 A 1 0.0 0.5 1 20 A Rec - B1-378 Headwall 46
43 Spare 20 A 1 0.0 0.5 1 20 A Rec - B1-378 Headwall 44
41 Rec - B1-371 - Clean Linen - Auto Laundry 20 A 1 0.5 0.2 1 20 A Rec - B1-377 Ante Room 42
39 Rec - B1-315 - Meds, Dispenser 20 A 1 0.2 0.2 1 20 A Rec - B1-377 Bariatric Lift 40
37 Rec - B1-315 - Meds, Dispenser 20 A 1 0.2 0.2 1 20 A Rec - B1-377 Bed Power 38
35 Rec - B1-315 - Meds, Dispenser 20 A 1 0.2 0.2 1 20 A Rec - B1-377 Computer Cart 36
33 Rec - B1-361A Corridor, Charting 20 A 1 0.5 0.5 1 20 A Rec - B1-377 Headwall 34
31 Rec - B1-361A Corridor, Charting 20 A 1 0.5 0.5 1 20 A Rec - B1-377 Headwall 32
29 Rec - B1-383 Electrical Room 20 A 1 0.4 0.2 1 20 A Rec - B1-365 Bariatric Lift 30
27 Rec - B1-372 Team Work 20 A 1 1.1 0.2 1 20 A Rec - B1-365 Bed Power 28
25 Rec - B1-372 Team Work 20 A 1 0.7 0.2 1 20 A Rec - B1-365 Computer Cart 26
23 Rec - B1-363 - Nourishment, Refrigerator 20 A 1 0.2 0.5 1 20 A Rec - B1-365 Headwall 24
21 Rec - B1-363 - Nourishment, Ice Maker 20 A 1 0.2 0.5 1 20 A Rec - B1-365 Headwall 22
19 Rec - B1-360 Corridor, Charting 20 A 1 0.5 0.2 1 20 A Rec - B1-364 Bariatric Lift 20
17 Rec - B1-367 Nurse Station 20 A 1 0.7 0.2 1 20 A Rec - B1-364 Bed Power 18
15 Rec - B1-360 Corridor, Charting 20 A 1 0.5 0.2 1 20 A Rec - B1-364 Computer Cart 16
13 Rec - B1-315 Meds, Pyxis 20 A 1 0.2 0.5 1 20 A Rec - B1-364 Headwall 14
11 Rec - B1-315 Meds, Pyxis 20 A 1 0.2 0.5 1 20 A Rec - B1-364 Headwall 12
9 Rec - B1-315 Meds, Pyxis 20 A 1 0.2 0.2 1 20 A Rec - B1-362 Bariatric Lift 10
7 Rec - B1-313 Nurse Manager 20 A 1 1.1 0.2 1 20 A Rec - B1-362 Bed Power 8
5 Rec - B1-312 Team Room 20 A 1 0.7 0.2 1 20 A Rec - B1-362 Computer Cart 6
3 Rec - B1-312 Team Room 20 A 1 1.1 0.5 1 20 A Rec - B1-362 Headwall 4
1 Rec - B1-302 Equip Storage 20 A 1 0.4 0.5 1 20 A Rec - B1-362 Headwall 2
N O T E CKT Circuit Description Trip Poles
A B C
Poles Trip Circuit Description CKT
N O T E
LOAD/PHASE (KVA)
NEW PANEL, REUSE EXISTING FEEDER
Notes:
Enclosure: TYPE 1 MCB Rating:
Mounting: SURFACE Wires: 4 Mains Rating: 225 A
Supply From: 2C1GM Phases: 3 Main Type: MLO
Location: ELECTRICAL B326 Volts: 120/208 Wye A.I.C. Rating: 22000
Branch Panel: 2C1Z
1. CONNECT TO EXISTING SPARE CIRCUIT BREAKER.
Notes:
Receptacle 95100 VA 55.26% 52550 VA Total Est. Demand: 77 A
Power 1975 VA 100.00% 1975 VA Total Conn.: 128 A
Other 5000 VA 100.00% 5000 VA Total Est. Demand: 63867 VA
Motor 90 VA 125.00% 113 VA Total Conn. Load: 106394 VA
Lighting 4229 VA 100.00% 4229 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Total Amps: 128 A 127 A 130 A
Total Load: 35.4 kVA 35.1 kVA 35.9 kVA
41 Space -- 1 -- -- 1 -- Space 42
39 Space -- 1 -- -- 1 -- Space 40
37 Space -- 1 -- -- 1 -- Space 38
35 Space -- 1 -- -- 1 -- Space 36
33 Space -- 1 -- -- 1 -- Space 34
31 Space -- 1 -- -- 1 -- Space 32
29 Spare 20 A 1 0.0 -- 1 -- Space 30
27 Spare 20 A 1 0.0 -- 1 -- Space 28
25 Spare 20 A 1 0.0 -- 1 -- Space 26
23 Spare 20 A 1 0.0 -- 1 -- Space 24
21 Spare 20 A 1 0.0 -- 1 -- Space 22
1 19 Lighting - Patient Rooms Area C 20 A 1 0.4 -- 1 -- Space 20
1 17 Lighting - Area C 20 A 1 0.6 -- 1 -- Space 18
1 15 Lighting - Corridor Area C 20 A 1 0.5 -- 1 -- Space 16
1 13 Lighting - Comm, Data, B1-316, B1-314 20 A 1 0.0 -- 1 -- Space 14
1 11 Lighting - Area A 20 A 1 0.6 -- 1 -- Space 12
1 9 Lighting - Corridor Area A 20 A 1 0.4 -- 1 -- Space 10
1 7 Lighting Electrical Room B1-352 20 A 1 0.0 -- 1 -- Space 8
1 5 Lighting - Patient Rooms Area B 20 A 1 0.6 34.1 -- -- -- 6 --
1 3 Lighting - Patient Rooms Area B 20 A 1 0.4 33.8 -- -- -- 4 --
1 1 Lighting - Corridor Area B 20 A 1 0.5 34.3 3 20 A TN13 2
N O T E CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
N O T E
LOAD/PHASE (KVA)
EXISTING PANEL
Notes:
Enclosure: TYPE 1 MCB Rating:
Mounting: SURFACE Wires: 4 Mains Rating: 225 A
Supply From: N1GM Phases: 3 Main Type: MLO
Location: ELECTRICAL B344 Volts: 480/277 Wye A.I.C. Rating: 35000
Branch Panel: N13
12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554
©Copyright 2023
TLC No.:
www.tlc-engineers.com
119437
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg.
PROJECT TEAM:
Office of
Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
Department of Veterans Affairs
MURFREESBORO, TN
615.370.8500
615.370.8530 hfrdesign.com
214 Centerview Drive Suite 300 Brentwood, TN 37027
Phase
FULLY SPRINKLERED
C R e v it
L o c a ls \1
-E L
E C
-V A
M C
W a rd
B
R a n d re .n g u y e n
V D
W
F .r v t
/1
/2
:4
:3
A
M
06-13-2023
626A4-19-101
E-EI-04
AE RENOVATE WARD 1BELECTRICAL PANEL SCHEDULES
AWD
HFR Project No: 2019056
100% CONSTRUCTION
DOCUMENTS
DLM
Notes:
Total Est. Demand: 85 A
Total Conn.: 128 A
Receptacle 40980 VA 62.20% 25490 VA Total Est. Demand: 30465 VA
Power 1975 VA 100.00% 1975 VA Total Conn. Load: 45955 VA
Other 3000 VA 100.00% 3000 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Total Amps: 120 A 131 A 136 A
Total Load: 14.3 kVA 15.5 kVA 16.1 kVA
83 Spare 20 A 1 0.0 0.0 1 20 A Spare 84
81 Spare 20 A 1 0.0 0.0 1 20 A Spare 82
79 Spare 20 A 1 0.0 0.0 1 20 A Spare 80
77 Spare 20 A 1 0.0 0.0 1 20 A Spare 78
75 Spare 20 A 1 0.0 0.0 1 20 A Spare 76
73 Spare 20 A 1 0.0 0.0 1 20 A Spare 74
71 Rec - B1-349 Computer Cart 20 A 1 0.2 0.4 1 20 A Power - Bug Lamps 72
69 Rec - B1-349 Headwall 20 A 1 0.7 0.8 1 20 A Power - Bug Lamps 70
67 Rec - B1-349 Headwall 20 A 1 0.7 0.9 1 20 A Rec - B1-337 - Clean Linen 68
65 Rec - B1-349 20 A 1 0.7 1.8 1 20 A Power - Trap Primers 66
63 Rec - B1-348 Computer Cart 20 A 1 0.2 0.5 1 20 A Rec - B1-331A Corridor, Charting 64
61 Rec - B1-348 Headwall 20 A 1 0.7 0.5 1 20 A Rec - B1-331A Corridor, Charting 62
59 Rec - B1-348 Headwall 20 A 1 0.7 0.2 1 20 A Rec - B1-352 Electrical Room 60
57 Rec - B1-348 20 A 1 0.7 0.5 1 20 A Rec - B1-338 Clean Utility/Linen 58
55 Rec - B1-343 Computer Cart 20 A 1 0.2 1.1 1 20 A Rec - B1-344 Team Work 56
53 Rec - B1-343 Headwall 20 A 1 0.7 0.9 1 20 A Rec - B1-344 Team Work 54
51 Rec - B1-343 Headwall 20 A 1 0.7 0.4 1 20 A Rec - B1-351 Equip Storage 52
49 Rec - B1-343 20 A 1 0.7 0.2 1 20 A Rec - B1-333 - Nourishment, Refrigerator 50
47 Rec - B1-342 Computer Cart 20 A 1 0.2 0.2 1 20 A Rec - B1-333 - Nourishment, Ice Maker 48
45 Rec - B1-342 Headwall 20 A 1 0.7 0.5 1 20 A Rec - B1-333 - Nourishment 46
43 Rec - B1-342 Headwall 20 A 1 0.7 0.5 1 20 A Rec - B1-330 Corridor, Charting 44
41 Rec - B1-342 20 A 1 0.7 0.7 1 20 A Rec - B1-346 Nurse Station 42
39 Rec - B1-341 Computer Cart 20 A 1 0.2 1.4 1 20 A Rec - B1-346 Nurse Station 40
37 Rec - B1-341 Headwall 20 A 1 0.7 0.5 1 20 A Rec - B1-330 Corridor, Charting 38
35 Rec - B1-341 Headwall 20 A 1 0.7 1.6 1 20 A Rec - Corridor Area B 36
33 Rec - B1-341 20 A 1 0.7 0.3 -- -- -- 34 --
31 Rec - B1-340 Computer Cart 20 A 1 0.2 0.3 2 20 A Rec - B1-350 Laundry, Dryer 32
29 Rec - B1-340 Headwall 20 A 1 0.7 0.3 -- -- -- 30 --
27 Rec - B1-340 Headwall 20 A 1 0.7 0.3 2 20 A Rec - B1-350 Laundry, Dryer 28
25 Rec - B1-340 20 A 1 0.9 0.2 1 20 A Rec - B1-350 Laundry, Washing Machine 26
23 Rec - B1-335 Computer Cart 20 A 1 0.2 0.4 1 20 A Rec - B1-350 Laundry 24
21 Rec - B1-335 Headwall 20 A 1 0.7 0.7 1 20 A Rec - B1-324 Clean Supply 22
19 Rec - B1-335 Headwall 20 A 1 0.7 0.7 1 20 A Rec - B1-320 Serving Kitchen 20
17 Rec - B1-335 20 A 1 0.7 1.0 -- -- -- 18 --
15 Rec - B1-334 Computer Cart 20 A 1 0.2 1.0 2 20 A Power - B1-319 Dining/Day Room, Fireplace 16
13 Rec - B1-334 Headwall 20 A 1 0.7 0.5 1 20 A Rec - B1-319 Dining/Day Room 14
11 Rec - B1-334 Headwall 20 A 1 0.7 0.7 1 20 A Rec - B1-319 Dining/Day Room 12
9 Rec - B1-334 20 A 1 0.7 1.1 1 20 A Rec - B1-318 Nurse Station 10
7 Rec - B1-332 Computer Cart 20 A 1 0.2 0.9 1 20 A Rec - B1-318 Nurse Station 8
5 Rec - B1-332 Headwall 20 A 1 0.7 0.9 1 20 A Rec - B1-318 Nurse Station 6
3 Rec - B1-332 Headwall 20 A 1 0.7 0.9 1 20 A Rec - B1-317 Charge Nurse 4
1 Rec - B1-332 20 A 1 0.7 0.7 1 20 A Rec - B1-317 Charge Nurse 2
N O T E CKT Circuit Description Trip Poles
A B C
Poles Trip Circuit Description CKT
N O T E
LOAD/PHASE (KVA)
Notes:
Enclosure: TYPE 1 MCB Rating:
Mounting: SURFACE Wires: 4 Mains Rating: 150 A
Supply From: 2N13 Phases: 3 Main Type: MLO
Location: ELECTRICAL B344 Volts: 120/208 Wye A.I.C. Rating: 22000
Branch Panel: 2N1W
Notes:
Total Est. Demand: 79 A
Total Conn.: 124 A
Total Est. Demand: 28420 VA
Receptacle 42840 VA 61.67% 26420 VA Total Conn. Load: 44840 VA
Other 2000 VA 100.00% 2000 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Total Amps: 131 A 123 A 121 A
Total Load: 15.7 kVA 14.7 kVA 14.5 kVA
83 Spare 20 A 1 0.0 0.0 1 20 A Spare 84
81 Spare 20 A 1 0.0 0.0 1 20 A Spare 82
79 Spare 20 A 1 0.0 0.0 1 20 A Spare 80
77 Spare 20 A 1 0.0 0.0 1 20 A Spare 78
75 Spare 20 A 1 0.0 0.0 1 20 A Spare 76
73 Spare 20 A 1 0.0 0.4 1 20 A Rec - B1-310 Rec. Thr. Stor. 74
71 Rec - B1-382 Computer Cart 20 A 1 0.2 0.8 1 20 A Power - Bug Lamps 72
69 Rec - B1-382 Headwall 20 A 1 0.7 1.2 1 20 A Power - Trap Primers 70
67 Rec - B1-382 Headwall 20 A 1 0.7 0.5 1 20 A Rec - B1-361A Corridor, Charting 68
65 Rec - B1-382 20 A 1 0.7 0.5 1 20 A Rec - B1-361A Corridor, Charting 66
63 Rec - B1-381 Computer Cart 20 A 1 0.2 0.5 1 20 A Rec - B1-375 Clean Utility/Work 64
61 Rec - B1-381 Headwall 20 A 1 0.7 0.5 1 20 A Rec - B1-383 Electrical Room 62
59 Rec - B1-381 Headwall 20 A 1 0.7 1.1 1 20 A Rec - B1-372 Team Work 60
57 Rec - B1-381 20 A 1 0.7 0.9 1 20 A Rec - B1-372 Team Work 58
55 Rec - B1-380 Computer Cart 20 A 1 0.2 0.2 1 20 A Rec - B1-363 - Nourishment, Refrigerator 56
53 Rec - B1-380 Headwall 20 A 1 0.7 0.2 1 20 A Rec - B1-363 - Nourishment, Ice Maker 54
51 Rec - B1-380 Headwall 20 A 1 0.7 0.5 1 20 A Rec - B1-363 - Nourishment 52
49 Rec - B1-380 20 A 1 0.7 0.5 1 20 A Rec - B1-360 Corridor, Charting 50
47 Rec - B1-379 Computer Cart 20 A 1 0.2 0.7 1 20 A Rec - B1-367 Nurse Station 48
45 Rec - B1-379 Headwall 20 A 1 0.7 1.3 1 20 A Rec - B1-367 Nurse Station 46
43 Rec - B1-379 Headwall 20 A 1 0.7 0.5 1 20 A Rec - B1-360 Corridor, Charting 44
41 Rec - B1-379 20 A 1 0.7 1.6 1 20 A Rec - Corridor Area C 42
39 Rec - B1-378 Computer Cart 20 A 1 0.2 0.2 1 20 A Rec - B1-315 Meds, Pyxis 40
37 Rec - B1-378 Headwall 20 A 1 0.7 0.2 1 20 A Rec - B1-315 Meds, Pyxis 38
35 Rec - B1-378 Headwall 20 A 1 0.7 0.2 1 20 A Rec - B1-315 Meds, Pyxis 36
33 Rec - B1-378 20 A 1 0.7 0.5 1 20 A Rec - B1-315 Meds 34
31 Rec - B1-377 Computer Cart 20 A 1 0.2 1.1 1 20 A Rec - B1-313 Nurse Manager 32
29 Rec - B1-377 Headwall 20 A 1 0.7 0.5 1 20 A Rec - B1-313 Nurse Manager 30
27 Rec - B1-377 Headwall 20 A 1 0.7 1.1 1 20 A Rec - B1-312 Team Room 28
25 Rec - B1-377 20 A 1 0.9 0.9 1 20 A Rec - B1-312 Team Room 26
23 Rec - B1-365 Computer Cart 20 A 1 0.2 0.5 1 20 A Rec - B1-309 Consult 24
21 Rec - B1-365 Headwall 20 A 1 0.7 0.2 1 20 A Rec - B1-308 Family Lounge, Coffee Machine 22
19 Rec - B1-365 Headwall 20 A 1 0.7 0.7 1 20 A Rec - B1-308 Family Lounge 20
17 Rec - B1-365 20 A 1 0.7 0.2 1 20 A Rec - B1-305 Staff Lounge, Refrigerator 18
15 Rec - B1-364 Computer Cart 20 A 1 0.2 0.2 1 20 A Rec - B1-305 Staff Lounge, Microwave 16
13 Rec - B1-364 Headwall 20 A 1 0.7 1.4 1 20 A Rec - B1-305/306 Staff Lounge/Lockers 14
11 Rec - B1-364 Headwall 20 A 1 0.7 0.9 1 20 A Rec - B1-304 Inpatient Rehab 12
9 Rec - B1-364 20 A 1 0.7 0.9 1 20 A Rec - B1-303 Social Worker 10
7 Rec - B1-362 Computer Cart 20 A 1 0.2 0.4 1 20 A Rec - B1-302 Equip Storage 8
5 Rec - B1-362 Headwall 20 A 1 0.7 0.2 1 20 A Rec - Area A Vending Machine 6
3 Rec - B1-362 Headwall 20 A 1 0.7 0.2 1 20 A Rec - Area A Vending Machine 4
1 Rec - B1-362 20 A 1 0.7 1.1 1 20 A Rec - Corridor Area A 2
N O T E CKT Circuit Description Trip Poles
A B C
Poles Trip Circuit Description CKT
N O T E
LOAD/PHASE (KVA)
Notes:
Enclosure: TYPE 1 MCB Rating:
Mounting: SURFACE Wires: 4 Mains Rating: 150 A
Supply From: 2N13 Phases: 3 Main Type: MLO
Location: ELECTRICAL B326 Volts: 120/208 Wye A.I.C. Rating: 22000
Branch Panel: 2N1Z
Notes:
Total Est. Demand: 7 A
Total Conn.: 7 A
Total Est. Demand: 2680 VA
Total Conn. Load: 2680 VA
Receptacle 2680 VA 100.00% 2680 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Total Amps: 12 A 6 A 5 A
Total Load: 1.4 kVA 0.7 kVA 0.6 kVA
23 Spare 20 A 1 0.0 0.0 1 20 A Spare 24
21 Spare 20 A 1 0.0 0.0 1 20 A Spare 22
19 Spare 20 A 1 0.0 0.0 1 20 A Spare 20
-- 17 -- -- -- 0.3 0.0 1 20 A Spare 18
-- 15 -- -- -- 0.3 0.0 1 20 A Spare 16
13 DATA ROOM - RACK 1 - FIBER/PATCH 30 A 3 0.3 0.7 1 20 A DATA ROOM - CONVENIENCE RECEPTACLES 14
11 COMM ROOM - CONVENIENCE... 20 A 1 0.4 0.0 1 20 A Spare 12
9 Spare 20 A 1 0.0 0.0 1 20 A Spare 10
7 Spare 20 A 1 0.0 0.0 1 20 A Spare 8
5 Spare 20 A 1 0.0 0.0 1 20 A Spare 6
-- 3 -- -- -- 0.4 0.0 1 20 A Spare 4
1 COMM ROOM - RACK 1 - FIBER/PATCH 20 A 2 0.4 0.0 1 20 A Spare 2
N O T E CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
N O T E
LOAD/PHASE (KVA)
Notes:
Enclosure: TYPE 1 MCB Rating:
Mounting: SURFACE Wires: 4 Mains Rating: 100 A
Supply From: 2N13 Phases: 3 Main Type: MLO
Location: ELECTRICAL B334 Volts: 120/208 Wye A.I.C. Rating: 22000
Branch Panel: 2N1X
Notes:
Total Est. Demand: 12 A
Total Conn.: 12 A
Total Est. Demand: 4440 VA
Receptacle 3040 VA 100.00% 3040 VA Total Conn. Load: 4440 VA
Other 1400 VA 100.00% 1400 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Total Amps: 17 A 13 A 9 A
Total Load: 2.0 kVA 1.4 kVA 1.0 kVA
23 Spare 20 A 1 0.0 0.0 1 20 A Spare 24
21 Spare 20 A 1 0.0 0.0 1 20 A Spare 22
19 Spare 20 A 1 0.0 0.0 1 20 A Spare 20
-- 17 -- -- -- 0.3 0.0 1 20 A Spare 18
-- 15 -- -- -- 0.3 0.0 1 20 A DATA ROOM - CONV RECPT 16
13 DATA ROOM - RACK 1 - FIBER/PATCH 30 A 3 0.3 0.9 1 20 A DATA ROOM - TELCO TERMINAL 14
11 COMM ROOM - CONVENIENCE... 20 A 1 0.4 0.0 1 20 A Spare 12
9 COMM ROOM - NURSE CALL 20 A 1 0.4 0.2 1 20 A COMM ROOM - RADIO/DAS 10
7 COMM ROOM - TELEVISION 20 A 1 0.2 0.2 1 20 A COMM ROOM - INTERCOM 8
5 COMM ROOM - DDC 20 A 1 0.2 0.2 1 20 A COMM ROOM - PUBLIC ADDRESS 6
-- 3 -- -- -- 0.4 0.2 1 20 A COMM ROOM - SECURITY 4
1 COMM ROOM - RACK 1 - FIBER/PATCH 30 A 2 0.4 0.0 1 20 A Spare 2
N O T E CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
N O T E
LOAD/PHASE (KVA)
Notes:
Enclosure: TYPE 1 MCB Rating:
Mounting: SURFACE Wires: 4 Mains Rating: 100 A
Supply From: 2C1W Phases: 3 Main Type: MLO
Location: ELECTRICAL B334 Volts: 120/208 Wye A.I.C. Rating: 22000
Branch Panel: 2C1X
Notes:
Total Est. Demand: 166 A
Receptacle 95100 VA 55.26% 52550 VA Total Conn.: 284 A
Power 1975 VA 100.00% 1975 VA Total Est. Demand: 59638 VA
Other 5000 VA 100.00% 5000 VA Total Conn. Load: 102165 VA
Motor 90 VA 125.00% 113 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Total Amps: 284 A
Total Conn. Load: 102165 VA
5 Rec - B1-320 Serving Kitchen, Servery 3 100 A 30 A 8600 VA
4 EF-1 1 100 A 15 A 90 VA
3 2N1X 3 100 A 60 A 2680 VA
2 2N1Z 3 250 A 150 A 44840 VA
1 2N1W 3 250 A 150 A 45955 VA
CKT Circuit Description # of Poles Frame Size Trip Rating
Load
Remarks
Notes:
Enclosure: TYPE 1 MCB Rating: 300 A
Mounting: SURFACE Wires: 4 Mains Rating:
Supply From: TN13 Phases: 3 Mains Type: MCB
Location: ELECTRICAL B344 Volts: 120/208 Wye A.I.C. Rating: 22000
Branch Panel: 2N13
1. EXISTING LOAD
Notes:
Total Est. Demand: 0 A
Total Conn.: 0 A
To…