This solicitation is for a construction project to renovate Ward 1B at the Alvin C. York VA Medical Center in Murfreesboro, Tennessee. The solicitation number is 36C24923R0114.

The project involves renovations and upgrades to patient rooms, support spaces, and building systems on the third floor of the medical center. The scope of work includes demolishing existing finishes, fixtures, and equipment to prepare for new construction. It will upgrade electrical, mechanical, plumbing and fire protection systems. New finishes, fixtures, medical equipment and furnishings will be installed. The construction drawings provide layouts and details of proposed demolition, new construction, and equipment. The estimated project completion date is 2023.

The solicitation is designated for small business set-aside and involves the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 9. The projected award date is in 2022. Pricing will be fixed-price, lump sum. The incumbent contractor was not identified.

The key information provided includes the location and scope of construction work required, federal agencies and contracting preferences involved, estimated timelines, and basic contracting terms. The document consists of construction drawings outlining demolition and new work.

View the file

Other files

File Type Posted
36C24923R0114 0003.docx DOCX document
E-EI-01 - PARTIAL ELECTRICAL RISER DIAGRAM - DEMOLITION.pdf PDF
119437-Alvin C. York VAMC Renovate Ward 1B - Revision 1 - Electrical Narrative.pdf PDF
Government Answers to Industry Questions.pdf PDF
283100.pdf PDF
275223.pdf PDF
Bradley_GrabBar_8370-107.pdf PDF
Ward 1B - Revision 1.pdf PDF
Renovate Ward 1B Pre-Proposal Sign in Sheet - 07-06-2023.pdf PDF
E-EI-02 - PARTIAL ELECTRICAL RISER DIAGRAM - NEW WORK.pdf PDF
Bradley_GrabBar_8370-108.pdf PDF
General Decision Number TN20230187 06-30-2023 Rutherford County TN.pdf PDF
ASI 3413-25.pdf PDF
36C24923R0114 0002.docx DOCX document
GAMCO 125SwingUpTP.pdf PDF
Interior Wall Type Legend.pdf PDF
SUBCONTRACTOR INFORMATION AND CONSENT FORM.docx DOCX document
36C24923R0114 0001.docx DOCX document
MECH BINDER.pdf PDF
Ward 1B - Specs - Vol. 2.pdf PDF
GD Number TN20230187 05-12-2023.pdf PDF
GI 01-02 - CONSTRUCTION STAGING PLAN.pdf PDF
GI 03-01 - SECOND FLOOR ICRA PLAN.pdf PDF
GI 05-01 - PHASING PLANS.pdf PDF
GI 00-01 - COVER SHEET.pdf PDF
GI 01-10 - WALL TYPE DETAILS.pdf PDF
Price Schedule Project 626A4-19-101 Renovate Ward 1B.xlsx XLSX spreadsheet
GI 04-02 - LEAD PAINT AND TRANSITE PANELS.pdf PDF
36C24923R0114.docx DOCX document
General Conditions Breakout.xlsx XLSX spreadsheet
WARD 1B - ARCH BINDER.pdf PDF
GI 01-20 - ACCESSIBILITY DETAILS.pdf PDF
RFI Form.docx DOCX document
GI 04-01 - ACM DUCT WORK AND ACM PIPE INSULATION.pdf PDF
Performance Relevancy Survey Form - 626A4-19-101 Renovate Ward 1B.docx DOCX document
Ward 1B - Specs - Vol. 1.pdf PDF
VN 01-00 - PATIENT LIFT VENDOR DRAWINGS.pdf PDF
PLUMBING BINDER.pdf PDF
GI 01-01 - GENERAL DATA.pdf PDF
TECH BINDER.pdf PDF
WARD 1B - GENERAL.pdf PDF
WARD 1B - INTERIORS .pdf PDF
Calculation of Self Performed Work.docx DOCX document
GI 02-01 - THIRD FLOOR LIFE SAFETY PLAN - OVERALL.pdf PDF
AD 01-01 - THIRD FLOOR DEMOLITION PLAN - OVERALL.pdf PDF
Contractor EMR Certification Form.docx DOCX document
FP BINDER.pdf PDF
GI 03-02 - THIRD FLOOR ICRA PLAN.pdf PDF
Show all 48

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

CLEAN UTILITY

SOILED UT.

PT. ROOM

PT. ROOM

PT. ROOM

PT. ROOM

ELEC.

STAFF TLT.STAIR

PT. ISO ROOM

PT. ROOM

PT. ROOM

WORK RM

ANTE

OFFICE

RESIDENTS RM.

MECH.

PT. ROOM

PT. ROOM

STOR. ROOM MEDS

SUPPLY ROOM

ELEC.

NOURISHMENT

CHUTE

IT

COMM

CONSULT

PT. ROOM PT. ROOM

PT. ROOM

PT. ROOM

MECH

OFFICE

RESIDENTS

ROOM

STAIR

PT. ROOM

PT. ROOM

PT. ROOM

WORK ROOM

CLEAN UTILITY

SOILED UTILITY

PT. ROOM

PT. ROOM

PT. ROOM

PT. ROOM

HAC ELEC.

STAFF TLT

NURSE WK.

NURSE STATION

SOCIAL WORK

WAITING ROOM

STAIRS

CHASE

LOCKER RM.

RETHERM

CONF.

STAFF TLT.

CORRID

STAFF BREAK

EXAMPLE #1

EXAMPLE LEGEND

EXAMPLE #2

EXAMPLE #3

EXAMPLE #4

EXAMPLE #5

EXAMPLE #6

ISO ROOM

PAT. TLT.

PRIVATE ROOM

PRIVATE ROOM

PRIVATE ROOM

BARI PRIVATE

ROOM

BARIATRIC

PATIENT TOILET

PRIVATE ROOM

PRIVATE ROOM

PANTRY

SERVING

KITCHEN

DINING/DAY

ROOM

LAUNDRY CLEAN SUPPLY

RETHERMCHUTE

EQUIP STORAGE

INPATIENT

REHAB

STAFF LOUNGE

STAFF LOCKERS

CHAIR ALCOVE

FAM. LOUNGE

CONSULT

FAM/PUB. TLT.

REC.THR. STOR.

TEAM ROOM

DATA

CLEAN LINEN

NOURISH

ST. TLT.

HAC.

SOILED HOLD

ELEC.

CLEAN UTILITY

HAC

WOUND CART

STOR.SUB NS.

PRIVATE ROOM

PRIVATE ROOM

ISO ROOM

CLEAN UTILITY

PAT. TLT.

ELEC.

EQUIP STOR.

TEAM WORKCLEAN LINEN

SOILED HOLD

BARI PRIVATE

ROOM

BARI. TLT.

NOURISHMENT

PAT. TLT.

PAT. TLT.

STAFF TLT.

PRIVATE ROOM

PAT. TLT.

PAT. TLT.

PAT. TLT.

PRIVATE ROOM

PAT. TLT.

PRIVATE ROOM

PRIVATE ROOM

PRIVATE ROOM

PAT. TLT.

PAT. TLT.

PAT. TLT.

PAT. TLT.

TEAM WORK

ROOM

SUB N.S.

CHARGE NURSE

NURSE STATION

SOCIAL WORKER

DIRTY

EMPTY CYL.

STOR.

FULL CYL. STOR.

ANTE

NURSE

MANAGER

PAT. TLT.

PAT. TLT.

ANTE

MEDS

COMM

STAFF TLT.

PRIVATE ROOM PRIVATE ROOM

CORRIDOR

CORRIDOR

CORRIDOR

CORRIDOR

VENDING

PAT. TLT.

PAT. TLT.

CORRIDOR

CORRIDOR

CORRIDOR

CORRIDOR

STAIR 1

STAIR 2

STAIR 3

EXISTING RISER

ELEV.

ELEV.

CHASE

CHASE

CHASE

CHASE

THE INTENT WITH THIS PLAN IS TO SHOW

HOW THE AREAS BETWEEN THE SECOND

FLOOR AND THRID FLOOR ALIGN

12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554

©Copyright 2019

TLC No.:

www.tlc-engineers.com

118626

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Dwg.

PROJECT TEAM:

Office of

Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

Department of Veterans Affairs

KEYPLAN

MURFREESBORO, TN

615.370.8500

615.370.8530 hfrdesign.com

214 Centerview Drive Suite 300 Brentwood, TN 37027

BLDG 2

BLDG 1

BLDG 9

Phase

FULLY SPRINKLERED

C U s e rs \a tr a y lo r\ D o c u m e n ts

\M b o ro V

A W a rd b

R e n o a tr a y lo r2 X

N D

H .r v t

/1

/2

:5

:4

P

M

04-14-2023

626A4-19-101

GI 05.01

AE RENOVATE WARD 1BPHASING PLANS

Author

HFR Project No: 2019056

100% CONSTRUCTION

DOCUMENTS

1 SECOND FLOOR PLAN - PHASING PLAN

0 8' 16' 32'4'

2 03 THIRD FLOOR PLAN - PHASING PLAN

0 8' 16' 32'4'

GENERAL NOTE:

1. THE PHASING PLAN IS NOTED AS EXAMPLES TO GIVE THE CONTRACTOR AN

UNDERSTANDING OF HOW THE PHASING FOR THE PROJECT NEEDS TO BE

ADDRESSED. WHILE THEY ARE LISTED BY NUMBER THESE EXAMPLES CAN BE

CONDUCTED IN ANY SEQUENCE AS DEEMED NECESSARY FOR THE MOST EFFECIENT

PROCESS POSSIBLE.

2. IN GENERAL 5 PATIENT ROOMS AT ONE TIME ON THE FLOOR BELOW WILL BE ABLE

TO BE TEMPORARLY OUT OF COMMISSION TO WORK ON VERTICAL SERVICES, THERE

MUST BE AT LEAST 15 ACTIVE PATIENT ROOMS AT ALL TIMES.

3. ALL ROOMS THAT ARE BEING WORKED ON SHALL BE PROTECTED FROM DAMAGE

AS BEST AS POSSIBILE. MOST OF THE WORK WILL TAKE PLACE IN THE CEILING,

HOWEVER DAMAGE TO ANY OTHER PART OF THE ROOM MUST BE REPARIED.

PROTECT EXISTING CEILING TILES, TILES THAT ARE DAMAGED OR BROKEN MUST BE

REPLACED TO THE ORIGINAL STATE.

4. CAREFUL COORDINATION WITH THE FACILITY MUST TAKE PLACE TO ADDRESS ANY

SHUTDOWNS THAT COULD EFFECT AREAS OUTSIDE OF THE DESIGNATED EXAMLE

ZONE.

5. IF SUPPORT SPACE INSIDE OF A DESIGNATED EXAMPLE ZONE IS SERVING

ANOTHER EXAMPLE ZONE COORDINATE SPECIFIC TIMES WITH THE FACILITY TO GAIN

ACCESS TO THIS SPACE.

6. ICRA BARRIERS MUST BE USED TO CLOSE OFF EACH AREA THAT IS BEING WORKED

ON TO PREVENT CONSTRUCTION DEBRIS AND DUST FROM INFILTRATING OCCUPIED

SPACE. BARRIERS SHALL BE INSTALLED AND SEALED ALONG WITH STICKY MATS AND

ANY OTHER INFECTION CONTROL ITEMS. IN SOME INSTANCES ICRA BARRIERS MAY

BE REQUIRED PER ROOM.

7. WORK IN THE CONNECTING CORRIDORS, ELEVATOR LOBBY AND NURSE STATION

SHALL BE CAREFULLY COORDINATED WITH THE FACILITY AND STAFF. THE NEED TO

WORK IN THESE AREAS SHALL BE EVALUATED ON A AS NEEDED BASIS. ELEVATOR

ACCESS SHALL BE MAINTAINED AT ALL TIMES

No. Date Description jim.elder Rectangle jim.elder Typewritten Text 06-13-2023 jim.elder Rectangle jacob.kelsheimer Snapshot jacob.kelsheimer Snapshot

GENERAL NOTES

NOTE: SOME SYMBOLS SHOWN ON THIS LEGEND MAY NOT PERTAIN TO THIS PROJECT.

ELECTRICAL SYMBOL LEGEND

FIRE ALARM SYSTEM CONDUIT AND WIRING

FIRE ALARM ANNUNCIATOR PANEL - FLUSH MOUNTED

FIRE ALARM TERMINAL CABINET

FIRE ALARM CONTROL PANEL

CEILING HEAT DETECTOR 135° F UNLESS OTHERWISE INDICATED

ELECTROMAGNETIC DOOR HOLD OPEN DEVICE

WITH CONNECTION TO CLOSURE/ HOLDER,

INCLUDES DETECTOR

ELECTROMAGNETIC DOOR HOLD OPEN DEVICE

WITH CONNECTION TO CLOSURE/HOLDER

ELECTROMAGNETIC DOOR HOLD OPEN DEVICE

SPRINKLER WATERFLOW SWITCH CONNECTION

SPRINKLER TAMPER SWITCH CONNECTION

FIREMAN'S PHONE JACK

VISUAL SIGNALING UNIT, WALL MOUNTED

(NO AUDIO DEVICE)

XXCD

XXCD

COMBINATION AUDIBLE/VISUAL NOTIFICATION DEVICE

CHIME/FLASHING "FIRE" LIGHT

CD = CANDELA RATING

FIRE ALARM CONTROL RELAY

DUCT SMOKE DETECTOR

R = RETURN

S = SUPPLY

CEILING SMOKE DETECTOR, PHOTO-ELECTRIC TYPE

UNLESS OTHERWISE NOTED

E = ELEVATOR WITH RECALL CONTACTS

I = IONIZATION

MANUAL PULL STATION

MOTOR CONNECTION, NUMBER DENOTES HORSEPOWER

EMERGENCY BATTERY PACK WITH TWIN HEADS

TRACK WITH TRACK LIGHT FIXTURE - TRIANGLES

INDICATE QUANTITY OF FIXTURE HEADS

EXTERIOR POLE LIGHT FIXTURE WITH

ARMS ORIENTED AS SHOWN ON PLANS

WALL MOUNTED SCONCE FIXTURE

EXIT LIGHT FIXTURE - SHADED QUADRANTS

INDICATE FACE(S), DIRAECTIONAL ARROWS

AS SHOWN ON PLANS

WALL WASH FIXTURE

COMPLETELY SHADED DENOTES UNSWITCHED

FIXTURE ON GENERATOR BRANCH CIRCUIT

DIAGONAL SHADING DENOTES SWITCHED

FIXTURE ON GENERATOR BRANCH CIRCUIT

TROFFER FIXTURE, RECESSED OR SURFACE MOUNT

LINEAR STRIP FIXTURE

EXISTING TO REMAIN

EXISTING TO BE REMOVED

FLEXIBLE CONDUIT

CONDUIT CONTINUED

CONDUIT STUB

CONDUIT TURNING DOWN

CONDUIT TURNING UP

EQUIPMENT BRANCH CONDUIT

LIFE SAFETY BRANCH CONDUIT

CRITICAL BRANCH CONDUIT

GROUND OR GROUND ROD AS NOTED

BRANCH CIRCUIT CONDUIT EXPOSED

BRANCH CIRCUIT CONDUIT CONCEALED IN SLAB,

UNDERGROUND OR UNDER FLOOR.

BRANCH CIRCUIT CONDUIT CONCEALED ABOVE CEILING OR IN WALL.

CONDUIT SHALL INCLUDE PHASE, NEUTRAL AND GROUND CONDUCTORS

AS REQUIRED FOR CIRCUITS (UNLESS OTHERWISE NOTED).

BRANCH CIRCUIT PANELBOARD, OVER 250 VOLTS, FLUSH MOUNTED

BRANCH CIRCUIT PANELBOARD, OVER 250 VOLTS, SURFACE MOUNTED

BRANCH CIRCUIT PANELBOARD, UNDER 250 VOLTS, FLUSH MOUNTED

BRANCH CIRCUIT PANELBOARD, UNDER 250 VOLTS, SURFACE MOUNTED

SHUNT-TRIP BUTTON

FLUSH MOUNTED UNLESS OTHERWISE NOTED

NEMA 3R FOR EXTERIOR LOCATIONS

SURGE SUPRESSOR

A3 = PANELBOARD DEVICE

B3 = DISTRIBUTION BOARD DEVICE

C3 = SERVICE ENTRANCE DEVICE

JUNCTION BOX

CABLE TRAY

PLUG-IN STRIP WITH RECEPTACLES, 18" O.C. UNLESS

OTHERWISE INDICATED

GROUND BAR

PHOTOCELL, MOUNTED ON ROOF FACING NORTH

DOOR ACCESS CONTROL CARD READER

SPECIAL PURPOSE RECEPTACLE, RATING AS NOTED

SPEAKER

TICK MARKS SHOWN ON ANY DEVICE REPRESENTS

RECEPTACLE CONNECTED TO THE EMERGENCY CIRCUIT

(RED DEVICE) TYPICAL FOR ANY DEVICE IN LEGEND

ISOLATED GROUND DUPLEX RECEPTACLE (ORANGE DEVICE)

TWO DUPLEX RECEPTACLES WITH COMMON COVER

MOUNTED ABOVE COUNTER

TWO DUPLEX RECEPTACLES WITH COMMON COVER

GFCI RECEPTACLE MOUNTED ABOVE COUNTER

GFCI RECEPTACLE

WP DENOTES WEATHERPROOF COVER.

SIMPLEX RECEPTACLE

DUPLEX RECEPTACLE MOUNTED ABOVE COUNTER

FLOOR OUTLET BOX WITH TWO DUPLEX RECEPTACLES

AND ONE COMBINATION W/ VOICE/DATA OUTLET

FLOOR OUTLET BOX AND DUPLEX RECEPTACLE

WITH APPROPRIATE FLANGE

M

T

WP

OC

a

1. LIGHT SWITCHES SHALL BE MOUNTED 48 INCHES ABOVE FINISHED FLOOR TO CENTER LINE OF DEVICE, UNLESS OTHERWISE NOTED.

2. RECEPTACLES SHALL BE LOCATED 18 INCHES ABOVE FINISHED FLOOR TO CENTER LINE OF DEVICE, UNLESS OTHERWISE NOTED. ABOVE COUNTER RECEPTACLES SHALL BE MOUNTED 6" ABOVE BACK

SPLASH TO CENTERLINE OF DEVICE.

3. EQUIPMENT SHALL BE OF MATERIALS SUITABLE FOR AND RATED FOR THE ENVIRONMENT IN WHICH

THEY ARE TO BE INSTALLED.

4. THE FOLLOWING NEC REQUIREMENTS SHALL BE MET:

A. WORKING CLEARANCES FOR ELECTRICAL EQUIPMENT SHALL BE IN COMPLIANCE WITH NEC 110.

B. THE EXCLUSIVELY DEDICATED SPACE EXTENDING FROM FLOOR TO STRUCTURAL CEILING WITH

A WIDTH AND DEPTH OF THE PANELBOARD OR SWITCHBOARD MUST BE CLEAR OF ALL PIPING,

DUCTS, EQUIPMENT FOREIGN TO THE ELECTRICAL EQUIPMENT OR ARCHITECTURAL

APPURTENANCES IN ACCORDANCE WITH NEC 408.

5. WHEN ELECTRICAL BOXES ARE LOCATED IN VERTICAL FIRE RESISTIVE ASSEMBLIES, (CLASSIFIED AS FIRE/SMOKE AND SMOKE PARTITIONS), THEY SHALL BE INSTALLED WITHOUT AFFECTING THE FIRE

CLASSIFICATION. ALL OF THE FOLLOWING CONDITIONS SHALL BE MET:

A. ALL ELECTRICAL BOXES SHALL BE METALLIC.

B. BOX OPENING SHALL OCCUR ONLY ON ONE SIDE OF FRAMING SPACE.

C. BOX OPENING SHALL NOT EXCEED 16 SQUARE INCHES.

D. ALL CLEARANCES BETWEEN OUTLET BOX AND GYPSUM BOARD SHALL BE COMPLETELY FILLED

WITH JOINT COMPOUND (OR OTHER APPROVED MATERIAL).

E. PROVIDE A WALL AROUND OUTLETS LARGER THAN 16 SQUARE INCHES. THE INTEGRITY OF THE

WALL RATING SHALL BE MAINTAINED.

F. THE TOTAL AGGREGATE SURFACE AREA OF THE BOXES SHALL NOT EXCEED 100 SQUARE

INCHES PER 100 SQUARE FEET.

G. OUTLET BOXES LOCATED ON OPPOSITE SIDES OF FIRE RESISTIVE ASSEMBLIES SHALL BE

SEPARATED BY A MINIMUM HORIZONTAL DISTANCE OF 24 INCHES.

H. OUTLET BOXES SHALL BE SECURELY FASTENED TO WALL FRAMING MEMBERS.

I. THE OPENING IN THE GYPSUM BOARD FACING SHALL BE CUT NOT TO EXCEED 1/8 INCH

BETWEEN THE EDGES OF THE OUTLET BOX AND THE EDGES OF THE OPENING.

6. ALL DEVICES SHALL BE MOUNTED VERTICAL, UNLESS OTHERWISE NOTED.

7. PROVIDE AN EXTENSION TO THE EXISTING LIGHTNING PROTECTION SYSTEM ON THE BUILDING IN

COMPLIANCE WITH SPEC SECTION 264113.

8. FOR BUCK HOIST POWER REQUIREMENTS DURING CONSTRUCTION, OBTAIN 480V, 3-PHASE POWER

FROM NORMAL BRANCH PANEL IN ROOM 349, NORTH END OF BUILDING 1. INSTALL CONDUIT, WIRE, CIRCUIT BREAKER, DISCONNECTING MEANS, ETC., IN COORDINATION WITH BUCK HOIST SUPPLIER.

REMOVE ALL DEVICES, FEEDERS, AND EQUIPMENT UPON COMPLETION OF CONSTRUCTION.

PEDESTAL MOUNTED RECEPTACLE

DUPLEX RECEPTACLE

DIMMER SWITCH

MANUAL MOTOR STARTER WITH OVERLOAD HEATERS

SINGLE POLE TIMER SWITCH

SINGLE POLE SWITCH WITH WEATHERPROOF COVER

SINGLE POLE SWITCH WITH OCCUPANCY SENSOR

FOUR-WAY SWITCH

THREE-WAY SWITCH

SINGLE POLE SWITCH

(SUBSCRIPT DENOTES SWITCH LEG)

TAMPER PROOF DUPLEX RECEPTACLE

TWIST LOCK RECEPTACLE

D

WALL MOUNTED LINEAR FIXTURE

FIXTURE DESIGNATION

LOWER CASE LETTER INDICATES SWITCH LEG

CIRCUIT NUMBER

LIGHTING

DESCRIPTIONSYMBOL

FIRE ALARM/DETECTION SYSTEMBASIC MATERIALS CONT.BASIC MATERIALS

F

AUTOMATIC TRANSFER SWITCH

TRANSFORMER

DIRECT DIGITAL CONTROL PANEL

VARIABLE FREQUENCY DRIVE

30AR

20AF

NF

30AR NON-FUSED DISCONNECT SWITCH, SIZE AS NOTED

NF DENOTES NON-FUSED

COMBINATION MAGNETIC MOTOR STARTER, SIZE AS NOTED

3-POLE UNLESS OTHERWISE NOTED

30/3

3R

MOCP # OF POLES

NEMA STARTER SIZE

ENCLOSURE NEMA 1 UNLESS NOTED

FUSED DISCONNECT

AR DENOTES AMP RATING OF SWITCH

AF DENOTES AMP FUSE SIZE

SECURITY CAMERA

CEILING MOUNTED RECEPTACLE

ROUND DOWNLIGHT FIXTURE

DESCRIPTIONSYMBOL DESCRIPTIONSYMBOL

COMBINATION AUDIBLE/VISUAL NOTIFICATION DEVICE

HORN/FLASHING "FIRE" LIGHT

CD = CANDELA RATING

ROUND PENDANT FIXTURE

T

WP

S

CR

GND

J

SS

XX

ST

CAM

VFD

DDC

T

C

L

EQ

UP

DN

NEW WORK

A

2a

SQUARE DOWNLIGHT FIXTURE

LINEAR PENDANT FIXTURE

X

R

F

F

F

P

TS

FS

H

H

H

FACP

FATP

FAAP

F

X

WALL MOUNTED SMOKE DETECTOR, PHOTO-ELECTRIC TYPE

UNLESS OTHERWISE NOTED

HIGH OIL ALARM PANEL

GENERATOR ALARM ANNUNCIATOR PANEL

GAAP

HOAP

COMBINATION CARBON MONOXIDE/NITROGEN DIOXIDE SENSORCO

GROUND FLOOD LIGHT FIXTURE

EMERGENCY POWER OFF BUTTONEP

CEILING MOUNTED OCCUPANCY SENSOR SWITCH

OD

SINGLE POLE SWITCH WITH OCCUPANCY SENSOR AND DIMMER

S

S

S

EXTERIOR POLE TOP LIGHT FIXTURE,

ARROW INDICATES AIM OF DISTRIBUTION

Z

C

RK

CB

SH

T

E

S

D

N

N

SE

SA

N NURSE CALL SYSTEM CONDUIT AND WIRING

NCMS

NURSE CALL MASTER STATION

NCEC

NURSE CALL EQUIPMENT CABINET

CODE BLUE ANNUNCIATOR PANEL WALL MOUNTED

CBAP

CORRIDOR ZONE LIGHT

CORRIDOR DOME LIGHT WALL MOUNTED

37-PIN PATIENT BED CONNECTION

CODE BLUE EMERGENCY STATION

SHOWER EMERGENCY STATION

TOILET EMERGENCY STATION

EMERGENCY STATION

STAFF STATION

DUTY STATION

DUAL PATIENT STATION

SINGLE PATIENT STATION

NURSE CALL SYSTEMS

STAFF EMERGENCY STATION

STAFF EMERGENCY ANNUNCIATOR

NCRA

NURSE CALL REMOTE ALARM

NCMA NURSE CALL MASTER ALARM

12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554

©Copyright 2023

TLC No.:

www.tlc-engineers.com

119437

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Dwg.

PROJECT TEAM:

Office of

Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

Department of Veterans Affairs

MURFREESBORO, TN

615.370.8500

615.370.8530 hfrdesign.com

214 Centerview Drive Suite 300 Brentwood, TN 37027

Phase

FULLY SPRINKLERED

C R e v it

L o c a ls \1

-E L

E C

-V A

M C

W a rd

B

R a n d re .n g u y e n

V D

W

F .r v t

/1

/2

:4

:2

A

M

06-13-2023

626A4-19-101

E-EI-00

AE RENOVATE WARD 1B

ELECTRICAL SYMBOLS LEGEND,

LIGHTING FIXTURE SCHEDULE, AND

GENERAL NOTES

AWD

HFR Project No: 2019056

100% CONSTRUCTION

DOCUMENTS

DLM

ELECTRICAL SHEET LIST

NO. SHEET NAME ISSUED

E-EI-00 ELECTRICAL SYMBOLS LEGEND, LIGHTING FIXTURE SCHEDULE, AND GENERAL NOTES Yes

E-EI-01 PARTIAL ELECTRICAL RISER DIAGRAM - DEMOLITION Yes

E-EI-02 PARTIAL ELECTRICAL RISER DIAGRAM - NEW WORK Yes

E-EI-03 ELECTRICAL PANEL SCHEDULES Yes

E-EI-04 ELECTRICAL PANEL SCHEDULES Yes

E-EI-05 ELECTRICAL DETAILS Yes

E-EI-06 ELECTRICAL DETAILS Yes

E-ED-00 3RD FLOOR - DEMOLITION PLAN - ELECTRICAL - OVERALL Yes

E-ED-01 3RD FLOOR - DEMOLITION PLAN - ELECTRICAL - PART A Yes

E-ED-02 3RD FLOOR - DEMOLITION PLAN - ELECTRICAL - PART B Yes

E-ED-03 3RD FLOOR - DEMOLITION PLAN - ELECTRICAL - PART C Yes

E-EP-01 3RD FLOOR - NEW WORK PLAN - POWER - PART A Yes

E-EP-02 3RD FLOOR - NEW WORK PLAN - POWER - PART B Yes

E-EP-03 3RD FLOOR - NEW WORK PLAN - POWER - PART C Yes

E-EP-04 3RD FLOOR ROOF - NEW WORK PLAN - POWER - PART A Yes

E-EL-01 3RD FLOOR - NEW WORK PLAN - LIGHTING - PART A Yes

E-EL-02 3RD FLOOR - NEW WORK PLAN - LIGHTING - PART B Yes

E-EL-03 3RD FLOOR - NEW WORK PLAN - LIGHTING - PART C Yes

E-EY-01 3RD FLOOR - NEW WORK PLAN - SYSTEMS - PART A Yes

E-EY-02 3RD FLOOR - NEW WORK PLAN - SYSTEMS - PART B Yes

E-EY-03 3RD FLOOR - NEW WORK PLAN - SYSTEMS - PART C Yes

Lighting Fixture Schedule

Type Description Manufacturer Model Lamp Electrical Data Type Comments

A 2'x4' LED LOW PROFILE TROFFER FIXTURE, ACRYLIC LENS, 4033 LUMEN, >80 CRI

LITHONIA

OR APPROVED EQUAL

CPX 2X4 AL08 SWW7 M2

OR APPROVED EQUAL

LED 277 V/1-28 VA

B 2'x2' LED LOW PROFILE TROFFER FIXTURE, ACRYLIC LENS, 2570 LUMEN, >80 CRI

LITHONIA

OR APPROVED EQUAL

CPX 2X2 AL07 SWW7 M4

OR APPROVED EQUAL

LED 277 V/1-19 VA

C 4' LED STRIP FIXTURE, ROUND LENSED, 80 CRI, DIMMABLE LITHONIA

OR APPROVED EQUAL

CSS L48 ALO3 MVOLT SWW3 80CRI

OR APPROVED EQUAL

LED 277 V/1-16 VA

D 6" LED DOWNLIGHT, 1110 LUMEN, DIMMABLE, 90 CRI, 3500K, MEDIUM

DISTRIBUTION

LITHONIA

OR APPROVED EQUAL

WF6 LED 27K30K35K MVOLT 90CRI MW

OR APPROVED EQUAL

LED 277 V/1-14 VA

F LED DECORATIVE WALL SCONCE, ALUMINUM CONSTRUCTION, ACRYLIC

DIFFUSER

BROWNLEE

OR APPROVED EQUAL

7328 NT H32 40K

OR APPROVED EQUAL

LED 277 V/1-32 VA

G WALL MOUNTED LED VANITY FIXTURE, 4000K WHITE, WHITE FINISH,

DIMMABLE

EUREKA

OR APPROVED EQUAL

3211C LED.16 35 277 DV SC WH

OR APPROVED EQUAL

LED 277 V/1-16 VA COORDINATE MOUNTING HEIGHT WITH ARCHITECTURAL ELEVATION

H 4' DIRECT/INDIRECT LED WALL MOUNTED LINEAR PATIENT BED LIGHT,

DIMMABLE, LOW VOLTAGE RELAY FOR PATIENT BED CONTROLLER

KENALL

OR APPROVED EQUAL

MPWUD MW 1/1 45L 40K8 DIM1 DV LVCD NLA*

OR APPROVED EQUAL

LED 277 V/1-45 VA PROVIDE FIXTURE WITH AMBER LED NIGHTLIGHT (EITHER LEFT OR RIGHT) ON

ROOM ENTRY DOOR SIDE OF BED. COORDINATE QUANTITIES OF EACH BASED

UPON ROOM ORIENTATIONS.

UC 2' LED UNDERCABINET, 788 LUMEN, DIMMABLE, WHITE FINISH JUNO

OR APPROVED EQUAL

UCES 24IN SWW6 90CRI WH M6

OR APPROVED EQUAL

LED 120 V/1-11 VA CONNECT TO NEAREST NON-DEDICATED NORMAL POWER RECEPTACLE CIRCUIT

X UNIVERSAL MOUNT LED EDGE LIT EXIT SIGN, ALUMINUM HOUSING, RED

LETTERING

EXITRONIX

OR APPROVED EQUAL

S900UM-WB-SR-R

OR APPROVED EQUAL

LED 277 V/1-4 VA COORDINATE CHEVRONS AND NUMBER OF FACES WITH FLOOR PLANS AND LIFE

SAFETY PLANS

GL 05.01 PHASING PLAN

No. Date Description

Yes

2N1Z

NOR

100A

208V

2LC1Z

CR

225A

208V

2N1Y

NOR

100A

208V

2LC1Y

CR

100A

208V

2N1X

NOR

100A

208V

2LC1X

CR

225A

208V

2LC1W

CR

208V

2L13

LS

100A

208V

L13

LS

100A

480V

2LC1WA

CR

225A

208V

C13

CR

100A

480V

2N1W

NOR

70A

208V

N13

NOR

100A

480V

N12

NOR

100A

480V

C12

CR

100A

480V

2N1S

NOR

100A

208V

2C1S

CR

225A

208V

L12

LS

100A

480V

2L12

LS

100A

208V

2LC1Z

NOR

225A

208V

2N1V

NOR

225A

208V

2N1FF

EQ

80A

208V

N14

NOR

225A

480V

Q15

EQ

225A

480V

N15

NOR

225A

480V

SEG1

CR

100A

208V

2N1M

NOR

225A

208V

2L11N

LS

100A

208V

L11N

LS

100A

480V

2LC1F

CR

100A

208V

2N1N

NOR

225A

208V

C11N

CR

100A

480V

N11N

NOR

100A

480V

2N20G1

NOR

225A

208V

2N1K

NOR

125A

208V

2N1G

NOR

225A

208V

2N1F

NOR

225A

208V

2LC1G

NOR

100A

208V

ATS-1C

CR

600A

4P

C1GM

CR

600A

480V

2LC1M

CR

225A

208V

ATS-1L

LS

260A

4P

L1GM

LS

250A

480V

2L1GM

LS

150A

208V

ATS-1Q

EQ

600A

4P

Q1GM

EQ

600A

480V

ATS-1X

EQ

600A

4P

X1GM

EQ

600A

480V

E1GM

EMER

1000A

480V

2N11

NOR

400A

208V

2N1A

NOR

800A

208V

2N1C

NOR

225A

208V

CEG

CR

225A

208V

2N1P

NOR

600A

208V

SPD1

EQ

600A

208V

2Q1

EQ

400A

208V

SEG

CR

225A

208V

2N1E

NOR

225A

208V

2N1H

NOR

225A

208V

2N1J

NOR

225A

208V

2N1

NOR

400A

208V

SB6120-0641

NOR

2000A

208V

SPDMCC

EQ

480V

MSBE

SB6120-0640

NOR

800A MB

208V

2C1GM

CR

500A

208V

N1GM

NOR

1200A

480V

N1MSB

NOR

2000A

480V

(MAIN)

N1MSB

NOR

2000A

480V

(DIST)

XFMR

1MVA

TC1GM

150kVA

TQ1GM

112.5kVA

TN1GM

750kVA

TVSS TVSS

TVSS

TVSS

TSPDTL1GM

45kVA

TVSS

2000/3

LSIG

400/3

GROUND FLOOR NORTH ELECTRICAL ROOM G17 SITE MAIN ELECTRICAL ROOM G26 ESSENTIAL SYSTEM ELECTRICAL ROOM G25 ELECTRICAL ROOM G29 ELECTRICAL SWITCHGEAR G30 GROUND FLOOR SOUTH ELECTRICAL ROOM

ELECTRICAL ROOM 237ELECTRICAL ROOM 212ELECTRICAL ROOM 273SECOND FLOOR NORTH ELECTRICAL ROOM 251

THIRD FLOOR NORTH ELECTRICAL ROOM 349 ELECTRICAL ROOM 374

ELECTRICAL ROOM 406A

FOURTH FLOOR

THIRD FLOOR

SECOND FLOOR

FIRST FLOOR

GROUND FLOOR

ATTIC

ELECTRICAL ROOM 312 ELECTRICAL ROOM 336

TO

B

U

IL

D

IN

G

1 1

30kVA

2C1AV

CR

60A

208V

2N1AV

NOR

100A

208V

2L1V

LS

70A

208V

2C1AS

CR

100A

480V

2N1AS

NOR

150A

208V

2C1T

CR

150A

208V

2N1T

NOR

150A

208V

2C1AT

CR

70A

208V

2N1AT

NOR

100A

208V

2L1T

LS

100A

208V

ELECTRICAL ROOM A270

T-N12

45kVA

T-C12

45kVA

T-L12

30kVA

ATS-Q1-4

EQ

600A

4P

Q1-4-1S

EQ

225A

480V

Q1-4-1N

EQ

225A

480V

NAME

BRANCH

###A

###V

NAME

###kVA

NAME

BRANCH

###V

RATING

TYPE

NAME

BRANCH

###A

#P

TVSSSWITCHBOARD

BRANCH KEY:

NOR: NORMAL BRANCH

LS: LIFE SAFETY

CR: CRITICAL BRANCH

EQ: EQUIPMENT BRANCH

BRANCH PANEL

TRANSFORMER AUTOMATIC TRANSFER SWITCH

ENCLOSED CIRCUIT BREAKER

RATING

DISCONNECT SWITCH

GROUND

SURGE SUPPRESSION

RISER DIAGRAM LEGEND

12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554

©Copyright 2023

TLC No.:

www.tlc-engineers.com

119437

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Dwg.

PROJECT TEAM:

Office of

Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

Department of Veterans Affairs

MURFREESBORO, TN

615.370.8500

615.370.8530 hfrdesign.com

214 Centerview Drive Suite 300 Brentwood, TN 37027

Phase

FULLY SPRINKLERED

C R e v it

L o c a ls \1

-E L

E C

-V A

M C

W a rd

B

R a n d re .n g u y e n

V D

W

F .r v t

/1

/2

:4

:2

A

M

06-13-2023

626A4-19-101

E-EI-01

AE RENOVATE WARD 1B

PARTIAL ELECTRICAL RISER DIAGRAM -

DEMOLITION

AWD

HFR Project No: 2019056

100% CONSTRUCTION

DOCUMENTS

DLM

GENERAL NOTES:

1. ALL EXISTING ELECTRICAL EQUIPMENT INDICATED ON THIS RISER

DIAGRAM WAS TRANSCRIBED FROM RECORD DOCUMENTS

FURNISHED BY THE VETERAN’S AFFAIRS ENGINEERING

DEPARTMENT. PLEASE NOTIFY TLC IMMEDIATELY WITH ANY

DISCREPANCIES BETWEEN THE EXISTING FIELD CONDITIONS AND

THE ELECTRICAL EQUIPMENT INDICATED ON THIS DOCUMENT.

KEYED NOTES:

AREA WITHIN SCOPE OF VA PROJECT #626A4-18-105

"RENOVATE WARD 1A". REFER TO PROJECT DOCUMENTS

FOR SCOPE OF WORK. COORDINATE DEMOLITION AND RE-

FEED OF CONDUCTORS AND CONDUITS WITH NEW

CONDITIONS.

PHASE LEGEND:

EXISTING TO REMAIN

DEMOLISHED

NEW WORK

2N1Z

NOR

84 POLE

100A

208V

2C1Z

CR

84 POLE

225A

208V

2L13

LS

100A

208V

L13

LS

100A

480V

2C1W

CR

84 POLE

225A

208V

C13

CR

100A

480V

2N1W

NOR

84 POLE

100A

208V

N13

NOR

100A

480V

2N1S

NOR

100A

208V

2LC1Z

NOR

225A

208V

2N1V

NOR

225A

208V

2N1FF

EQ

80A

208V

N14

NOR

225A

480V

Q15

EQ

225A

480V

N15

NOR

225A

480V

SEG1

CR

100A

208V

2N1M

NOR

225A

208V

2L11N

LS

100A

208V

L11N

LS

100A

480V

2LC1F

CR

100A

208V

2N1N

NOR

225A

208V

C11N

CR

100A

480V

N11N

NOR

100A

480V

2N20G1

NOR

225A

208V

2N1K

NOR

125A

208V

2N1G

NOR

225A

208V

2N1F

NOR

225A

208V

2LC1G

NOR

100A

208V

ATS-1C

CR

600A

4P

C1GM

CR

600A

480V

2LC1M

CR

225A

208V

ATS-1L

LS

260A

4P

L1GM

LS

250A

480V

2L1GM

LS

150A

208V

ATS-1Q

EQ

600A

4P

Q1GM

EQ

600A

480V

ATS-1X

EQ

600A

4P

X1GM

EQ

600A

480V

E1GM

EMER

1000A

480V

2N11

NOR

400A

208V

2N1A

NOR

800A

208V

2N1C

NOR

225A

208V

CEG

CR

225A

208V

2N1P

NOR

600A

208V

SPD1

EQ

600A

208V

2Q1

EQ

400A

208V

SEG

CR

225A

208V

2N1E

NOR

225A

208V

2N1H

NOR

225A

208V

2N1J

NOR

225A

208V

2N1

NOR

400A

208V

SB6120-0641

NOR

2000A

208V

SPDMCC

EQ

480V

MSBE

SB6120-0640

NOR

800A MB

208V

2C1GM

CR

500A

208V

N1GM

NOR

1200A

480V

N1MSB

NOR

2000A

480V

(MAIN)

N1MSB

NOR

2000A

480V

(DIST)

XFMR

1MVA

TC1GM

150kVA

TQ1GM

112.5kVA

TN1GM

750kVA

TVSS TVSS

TVSS

TVSS

TSPDTL1GM

45kVA

TVSS

2000/3

LSIG

400/3

GROUND FLOOR NORTH ELECTRICAL ROOM G17 SITE MAIN ELECTRICAL ROOM G26 ESSENTIAL SYSTEM ELECTRICAL ROOM G25 ELECTRICAL ROOM G29 ELECTRICAL SWITCHGEAR G30 GROUND FLOOR SOUTH ELECTRICAL ROOM

SECOND FLOOR NORTH ELECTRICAL ROOM 251

THIRD FLOOR NORTH ELECTRICAL ROOM B344

ELECTRICAL ROOM 406A

FOURTH FLOOR

THIRD FLOOR

SECOND FLOOR

FIRST FLOOR

GROUND FLOOR

ATTIC

ELECTRICAL ROOM B326

TO

B

U

IL

D

IN

G

N12

NOR

100A

480V

C12

CR

100A

480V

2N1S

NOR

100A

208V

2C1S

CR

225A

208V

L12

LS

100A

480V

2L12

LS

100A

208V

2LC1Z

NOR

225A

208V

2N1V

NOR

225A

208V

ELECTRICAL ROOM 237

2C1AV

CR

60A

208V

2N1AV

NOR

100A

208V

2L1V

LS

70A

208V

2C1AS

CR

100A

480V

2N1AS

NOR

150A

208V

2C1T

CR

150A

208V

2N1T

NOR

150A

208V

2C1AT

CR

70A

208V

2N1AT

NOR

100A

208V

2L1T

LS

100A

208V

ELECTRICAL ROOM A270

T-N12

45kVA

T-C12

45kVA

T-L12

30kVA

2N1X

NOR

100A

208V

COMMUNICATIONS ROOM B334

TN13

75kVA

2N13

NOR

300A

208V

2C1X

CR

100A

208V

ATS-Q1-4

EQ

600A

4P

2Q1-4-1S

EQ

225A

480V

Q1-4-1N

EQ

225A

480V

3 6

#2

NAME

BRANCH

###A

###V

NAME

###kVA

NAME

BRANCH

###V

RATING

TYPE

NAME

BRANCH

###A

#P

TVSSSWITCHBOARD

BRANCH KEY:

NOR: NORMAL BRANCH

LS: LIFE SAFETY

CR: CRITICAL BRANCH

EQ: EQUIPMENT BRANCH

BRANCH PANEL

TRANSFORMER AUTOMATIC TRANSFER SWITCH

ENCLOSED CIRCUIT BREAKER

RATING

DISCONNECT SWITCH

GROUND

SURGE SUPPRESSION

RISER DIAGRAM LEGEND

12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554

©Copyright 2023

TLC No.:

www.tlc-engineers.com

119437

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Dwg.

PROJECT TEAM:

Office of

Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

Department of Veterans Affairs

MURFREESBORO, TN

615.370.8500

615.370.8530 hfrdesign.com

214 Centerview Drive Suite 300 Brentwood, TN 37027

Phase

FULLY SPRINKLERED

C R e v it

L o c a ls \1

-E L

E C

-V A

M C

W a rd

B

R a n d re .n g u y e n

V D

W

F .r v t

/1

/2

:4

:2

A

M

06-13-2023

626A4-19-101

E-EI-02

AE RENOVATE WARD 1B

PARTIAL ELECTRICAL RISER DIAGRAM -

NEW WORK

AWD

HFR Project No: 2019056

100% CONSTRUCTION

DOCUMENTS

DLM

GENERAL NOTES:

1. ALL EXISTING ELECTRICAL EQUIPMENT INDICATED ON THIS RISER

DIAGRAM WAS TRANSCRIBED FROM RECORD DOCUMENTS

FURNISHED BY THE VETERAN’S AFFAIRS ENGINEERING

DEPARTMENT. PLEASE NOTIFY TLC IMMEDIATELY WITH ANY

DISCREPANCIES BETWEEN THE EXISTING FIELD CONDITIONS AND

THE ELECTRICAL EQUIPMENT INDICATED ON THIS DOCUMENT.

2. INSTALL 3/4"C, 1#10 GND (FOR BONDING PER NATIONAL

ELECTRICAL CODE 517.14) BETWEEN GROUND BUSES OF ANY TWO

NORMAL AND ESSENTIAL PANELS WHICH SERVE THE SAME

PATIENT CARE AREA.

FEEDER SIZES:

125A, (3) #1, #6 GND, 1-1/2" C.

300A, (4) 350 MCM, #4 GND, 3-1/2" C.

150A, (3) #1/0, #6 GND, 2" C.

100A, (4) #3, #8 GND, 1-1/2" C.

150A, (3) #1/0, #6 GND, 2" C.

60A, (4) #6, #8 GND, 1-1/4" C.

PHASE LEGEND:

EXISTING TO REMAIN

DEMOLISHED

NEW WORK2

12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554

©Copyright 2023

TLC No.:

www.tlc-engineers.com

119437

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Dwg.

PROJECT TEAM:

Office of

Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

Department of Veterans Affairs

MURFREESBORO, TN

615.370.8500

615.370.8530 hfrdesign.com

214 Centerview Drive Suite 300 Brentwood, TN 37027

Phase

FULLY SPRINKLERED

C R e v it

L o c a ls \1

-E L

E C

-V A

M C

W a rd

B

R a n d re .n g u y e n

V D

W

F .r v t

/1

/2

:4

:3

A

M

06-13-2023

626A4-19-101

E-EI-03

AE RENOVATE WARD 1BELECTRICAL PANEL SCHEDULES

AWD

HFR Project No: 2019056

100% CONSTRUCTION

DOCUMENTS

DLM

1. CONNECT TO EXISTING SPARE CIRCUIT BREAKER.

Notes:

Total Est. Demand: 1 A

Total Conn.: 1 A

Total Est. Demand: 854 VA

Total Conn. Load: 854 VA

Lighting 854 VA 100.00% 854 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Total Amps: 1 A 1 A 1 A

Total Load: 0.2 kVA 0.3 kVA 0.3 kVA

41 Space -- 1 -- -- 1 -- Space 42

39 Space -- 1 -- -- 1 -- Space 40

37 Space -- 1 -- -- 1 -- Space 38

35 Space -- 1 -- -- 1 -- Space 36

33 Space -- 1 -- -- 1 -- Space 34

31 Space -- 1 -- -- 1 -- Space 32

29 Space -- 1 -- -- 1 -- Space 30

27 Space -- 1 -- -- 1 -- Space 28

25 Space -- 1 -- -- 1 -- Space 26

23 Space -- 1 -- -- 1 -- Space 24

21 Space -- 1 -- -- 1 -- Space 22

19 Space -- 1 -- -- 1 -- Space 20

17 Space -- 1 -- -- 1 -- Space 18

15 Space -- 1 -- -- 1 -- Space 16

13 Space -- 1 -- -- 1 -- Space 14

11 Space -- 1 -- -- 1 -- Space 12

9 Space -- 1 -- -- 1 -- Space 10

7 Space -- 1 -- -- 1 -- Space 8

1 5 Lighting - Egress Area C 20 A 1 0.3 0.0 1 20 A Spare 6

1 3 Lighting - Egress Area B 20 A 1 0.3 0.0 1 20 A Spare 4

1 1 Lighting - Egress Area A 20 A 1 0.2 0.0 1 20 A Spare 2

N O T E CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

N O T E

LOAD/PHASE (KVA)

EXISTING PANEL

Notes:

Enclosure: TYPE 1 MCB Rating:

Mounting: SURFACE Wires: 4 Mains Rating: 225 A

Supply From: L1GM Phases: 3 Main Type: MLO

Location: ELECTRICAL B344 Volts: 480/277 Wye A.I.C. Rating: 14000

Branch Panel: L13

1. CONNECT TO EXISTING SPARE CIRCUIT BREAKER.

Notes:

Total Est. Demand: 1 A

Total Conn.: 1 A

Total Est. Demand: 400 VA

Total Conn. Load: 400 VA

Other 400 VA 100.00% 400 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Total Amps: 3 A 0 A 0 A

Total Load: 0.4 kVA 0.0 kVA 0.0 kVA

41 Space -- 1 -- -- 1 -- Space 42

39 Space -- 1 -- -- 1 -- Space 40

37 Space -- 1 -- -- 1 -- Space 38

35 Space -- 1 -- -- 1 -- Space 36

33 Space -- 1 -- -- 1 -- Space 34

31 Space -- 1 -- -- 1 -- Space 32

29 Space -- 1 -- -- 1 -- Space 30

27 Space -- 1 -- -- 1 -- Space 28

25 Space -- 1 -- -- 1 -- Space 26

23 Space -- 1 -- -- 1 -- Space 24

21 Space -- 1 -- -- 1 -- Space 22

19 Space -- 1 -- -- 1 -- Space 20

17 Spare 20 A 1 0.0 0.0 1 20 A Spare 18

15 Spare 20 A 1 0.0 0.0 1 20 A Spare 16

13 Spare 20 A 1 0.0 0.0 1 20 A Spare 14

11 Spare 20 A 1 0.0 0.0 1 20 A Spare 12

9 Spare 20 A 1 0.0 0.0 1 20 A Spare 10

7 Spare 20 A 1 0.0 0.0 1 20 A Spare 8

5 Spare 20 A 1 0.0 0.0 1 20 A Spare 6

3 Spare 20 A 1 0.0 0.0 1 20 A Spare 4

1 1 Door Power 20 A 1 0.4 2

N O T E CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

N O T E

LOAD/PHASE (KVA)

EXISTING PANEL

Notes:

Enclosure: TYPE 1 MCB Rating:

Mounting: SURFACE Wires: 4 Mains Rating: 225 A

Supply From: 2L1GM Phases: 3 Main Type: MLO

Location: ELECTRICAL B344 Volts: 120/208 Wye A.I.C. Rating: 22000

Branch Panel: 2L13

1. CONNECT TO EXISTING SPARE CIRCUIT BREAKER.

Notes:

Total Est. Demand: 3 A

Total Conn.: 3 A

Total Est. Demand: 2484 VA

Total Conn. Load: 2484 VA

Lighting 2484 VA 100.00% 2484 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Total Amps: 4 A 3 A 2 A

Total Load: 1.2 kVA 0.7 kVA 0.6 kVA

41 Space -- 1 -- -- 1 -- Space 42

39 Space -- 1 -- -- 1 -- Space 40

37 Space -- 1 -- -- 1 -- Space 38

35 Spare 20 A 1 0.0 0.0 1 20 A Spare 36

33 Spare 20 A 1 0.0 0.0 1 20 A Spare 34

31 Spare 20 A 1 0.0 0.0 1 20 A Spare 32

29 Spare 20 A 1 0.0 0.0 1 20 A Spare 30

27 Spare 20 A 1 0.0 0.0 1 20 A Spare 28

25 Spare 20 A 1 0.0 0.0 1 20 A Spare 26

23 Spare 20 A 1 0.0 0.0 1 20 A Spare 24

21 Spare 20 A 1 0.0 0.0 1 20 A Spare 22

19 Spare 20 A 1 0.0 0.0 1 20 A Spare 20

17 Spare 20 A 1 0.0 0.0 1 20 A Spare 18

15 Spare 20 A 1 0.0 0.0 1 20 A Lighting Electrical Room B1-383 16 1

13 Spare 20 A 1 0.0 0.3 1 20 A Lighting - Patient Rooms Area C 14 1

11 Spare 20 A 1 0.0 0.6 1 20 A Lighting - Area C 12 1

9 Spare 20 A 1 0.0 0.0 1 20 A Lighting - Comm, Data, B1-316, B1-314 10 1

7 Spare 20 A 1 0.0 0.5 1 20 A Lighting - Area A 8 1

5 Spare 20 A 1 0.0 0.0 1 20 A Lighting Electrical Room B1-352 6 1

3 Spare 20 A 1 0.0 0.7 1 20 A Lighting - Patient Rooms Area B 4 1

1 Spare 20 A 1 0.0 0.3 1 20 A Lighting - Patient Rooms Area B 2 1

N O T E CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

N O T E

LOAD/PHASE (KVA)

EXISTING PANEL

Notes:

Enclosure: TYPE 1 MCB Rating:

Mounting: SURFACE Wires: 4 Mains Rating: 225 A

Supply From: C1GM Phases: 3 Main Type: MLO

Location: ELECTRICAL B344 Volts: 480/277 Wye A.I.C. Rating: 35000

Branch Panel: C13

Notes:

Total Est. Demand: 92 A

Receptacle 27700 VA 68.05% 18850 VA Total Conn.: 116 A

Power 8800 VA 100.00% 8800 VA Total Est. Demand: 32970 VA

Other 1400 VA 100.00% 1400 VA Total Conn. Load: 41820 VA

Motor 3920 VA 100.00% 3920 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Total Amps: 130 A 109 A 110 A

Total Load: 15.6 kVA 13.0 kVA 13.2 kVA

83 Spare 20 A 1 0.0 0.0 1 20 A Spare 84

81 Spare 20 A 1 0.0 0.0 1 20 A Spare 82

79 Spare 20 A 1 0.0 0.0 1 20 A Spare 80

77 Spare 20 A 1 0.0 0.0 1 20 A Spare 78

75 Spare 20 A 1 0.0 0.0 1 20 A Spare 76

73 NCMS - B1-317 CHARGE STATION 20 A 1 0.2 0.5 1 20 A Rec - B1-337 Automated Laundry Cart 74

71 Rec - B1-349 Bariatric Lift 20 A 1 0.2 0.2 1 20 A Rec - B1-343 Bariatric Lift 72

69 Rec - B1-349 Bed Power 20 A 1 0.2 0.2 1 20 A Rec - B1-343 Bed Power 70

67 Rec - B1-349 Computer Cart 20 A 1 0.2 0.2 1 20 A Rec - B1-343 Computer Cart 68

65 Rec - B1-349 Headwall 20 A 1 0.5 0.5 1 20 A Rec - B1-343 Headwall 66

63 Rec - B1-349 Headwall 20 A 1 0.5 0.5 1 20 A Rec - B1-343 Headwall 64

61 Rec - B1-348 Bariatric Lift 20 A 1 0.2 0.2 1 20 A Rec - B1-342 Bariatric Lift 62

59 Rec - B1-348 Bed Power 20 A 1 0.2 0.2 1 20 A Rec - B1-342 Bed Power 60

57 Rec - B1-348 Computer Cart 20 A 1 0.2 0.2 1 20 A Rec - B1-342 Computer Cart 58

55 Rec - B1-348 Headwall 20 A 1 0.5 0.5 1 20 A Rec - B1-342 Headwall 56

53 Rec - B1-348 Headwall 20 A 1 0.5 0.5 1 20 A Rec - B1-342 Headwall 54

51 Spare 20 A 1 0.0 0.2 1 20 A Rec - B1-341 Bariatric Lift 52

-- 49 -- -- -- 1.0 0.2 1 20 A Rec - B1-341 Bed Power 50

47 CU-2/AC-2 25 A 2 1.0 0.2 1 20 A Rec - B1-341 Computer Cart 48

-- 45 -- -- -- 1.0 0.5 1 20 A Rec - B1-341 Headwall 46

43 CU-1/AC-1 25 A 2 1.0 0.5 1 20 A Rec - B1-341 Headwall 44

41 Rec - B1-317 Charge Nurse 20 A 1 0.7 0.2 1 20 A Rec - B1-339 Ante Room 42

39 Rec - B1-331A Corridor, Charting 20 A 1 0.5 0.2 1 20 A Rec - B1-340 Bariatric Lift 40

37 Rec - B1-331A Corridor, Charting 20 A 1 0.5 0.2 1 20 A Rec - B1-340 Bed Power 38

35 Rec - B1-352 Electrical Room 20 A 1 0.4 0.2 1 20 A Rec - B1-340 Computer Cart 36

33 Rec - B1-351 Equip Storage 20 A 1 0.4 0.5 1 20 A Rec - B1-340 Headwall 34

31 Rec - B1-344 Team Work 20 A 1 1.1 0.5 1 20 A Rec - B1-340 Headwall 32

29 Rec - B1-344 Team Work 20 A 1 0.7 0.2 1 20 A Rec - B1-335 Bariatric Lift 30

27 Rec - B1-333 - Nourishment, Refrigerator 20 A 1 0.2 0.2 1 20 A Rec - B1-335 Bed Power 28

25 Rec - B1-333 - Nourishment, Ice Maker 20 A 1 0.2 0.2 1 20 A Rec - B1-335 Computer Cart 26

23 Rec - B1-330 Corridor, Charting 20 A 1 0.5 0.5 1 20 A Rec - B1-335 Headwall 24

21 Rec - B1-346 Nurse Station 20 A 1 0.7 0.5 1 20 A Rec - B1-335 Headwall 22

19 Rec - B1-330 Corridor, Charting 20 A 1 0.5 0.2 1 20 A Rec - B1-334 Bariatric Lift 20

-- 17 -- -- -- 2.9 0.2 1 20 A Rec - B1-334 Bed Power 18

-- 15 -- -- -- 2.9 0.2 1 20 A Rec - B1-334 Computer Cart 16

13 Power - Retherm 30 A 3 2.9 0.5 1 20 A Rec - B1-334 Headwall 14

11 Rec - B1-318 Nurse Station 20 A 1 0.9 0.5 1 20 A Rec - B1-334 Headwall 12

9 Rec - B1-318 Nurse Station 20 A 1 1.1 0.2 1 20 A Rec - B1-332 Bariatric Lift 10

7 Rec - B1-317 Charge Nurse 20 A 1 0.9 0.2 1 20 A Rec - B1-332 Bed Power 8

-- 5 -- -- -- 1.0 0.2 1 20 A Rec - B1-332 Computer Cart 6

-- 3 -- -- -- 1.4 0.5 1 20 A Rec - B1-332 Headwall 4

1 2C1X 100 A 3 2.0 0.5 1 20 A Rec - B1-332 Headwall 2

N O T E CKT Circuit Description Trip Poles

A B C

Poles Trip Circuit Description CKT

N O T E

LOAD/PHASE (KVA)

NEW PANEL, REUSE EXISTING FEEDER

Notes:

Enclosure: TYPE 1 MCB Rating:

Mounting: SURFACE Wires: 4 Mains Rating: 150 A

Supply From: 2C1GM Phases: 3 Main Type: MCB

Location: ELECTRICAL B344 Volts: 120/208 Wye A.I.C. Rating: 22000

Branch Panel: 2C1W

Notes:

Total Est. Demand: 49 A

Total Conn.: 69 A

Total Est. Demand: 17510 VA

Total Conn. Load: 25020 VA

Receptacle 25020 VA 69.98% 17510 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Total Amps: 71 A 73 A 66 A

Total Load: 8.5 kVA 8.6 kVA 7.9 kVA

83 Spare 20 A 1 0.0 0.0 1 20 A Spare 84

81 Spare 20 A 1 0.0 0.0 1 20 A Spare 82

79 Spare 20 A 1 0.0 0.0 1 20 A Spare 80

77 Spare 20 A 1 0.0 0.0 1 20 A Spare 78

75 Spare 20 A 1 0.0 0.0 1 20 A Spare 76

73 Spare 20 A 1 0.0 0.0 1 20 A Spare 74

71 Rec - B1-382 Bariatric Lift 20 A 1 0.2 0.2 1 20 A Rec - B1-380 Bariatric Lift 72

69 Rec - B1-382 Bed Power 20 A 1 0.2 0.2 1 20 A Rec - B1-380 Bed Power 70

67 Rec - B1-382 Computer Cart 20 A 1 0.2 0.2 1 20 A Rec - B1-380 Computer Cart 68

65 Rec - B1-382 Headwall 20 A 1 0.5 0.5 1 20 A Rec - B1-380 Headwall 66

63 Rec - B1-382 Headwall 20 A 1 0.5 0.5 1 20 A Rec - B1-380 Headwall 64

61 Rec - B1-381 Bariatric Lift 20 A 1 0.2 0.2 1 20 A Rec - B1-379 Bariatric Lift 62

59 Rec - B1-381 Bed Power 20 A 1 0.2 0.2 1 20 A Rec - B1-379 Bed Power 60

57 Rec - B1-381 Computer Cart 20 A 1 0.2 0.2 1 20 A Rec - B1-379 Computer Cart 58

55 Rec - B1-381 Headwall 20 A 1 0.5 0.5 1 20 A Rec - B1-379 Headwall 56

53 Rec - B1-381 Headwall 20 A 1 0.5 0.5 1 20 A Rec - B1-379 Headwall 54

51 Spare 20 A 1 0.0 0.2 1 20 A Rec - B1-378 Bariatric Lift 52

49 Spare 20 A 1 0.0 0.2 1 20 A Rec - B1-378 Bed Power 50

47 Spare 20 A 1 0.0 0.2 1 20 A Rec - B1-378 Computer Cart 48

45 Spare 20 A 1 0.0 0.5 1 20 A Rec - B1-378 Headwall 46

43 Spare 20 A 1 0.0 0.5 1 20 A Rec - B1-378 Headwall 44

41 Rec - B1-371 - Clean Linen - Auto Laundry 20 A 1 0.5 0.2 1 20 A Rec - B1-377 Ante Room 42

39 Rec - B1-315 - Meds, Dispenser 20 A 1 0.2 0.2 1 20 A Rec - B1-377 Bariatric Lift 40

37 Rec - B1-315 - Meds, Dispenser 20 A 1 0.2 0.2 1 20 A Rec - B1-377 Bed Power 38

35 Rec - B1-315 - Meds, Dispenser 20 A 1 0.2 0.2 1 20 A Rec - B1-377 Computer Cart 36

33 Rec - B1-361A Corridor, Charting 20 A 1 0.5 0.5 1 20 A Rec - B1-377 Headwall 34

31 Rec - B1-361A Corridor, Charting 20 A 1 0.5 0.5 1 20 A Rec - B1-377 Headwall 32

29 Rec - B1-383 Electrical Room 20 A 1 0.4 0.2 1 20 A Rec - B1-365 Bariatric Lift 30

27 Rec - B1-372 Team Work 20 A 1 1.1 0.2 1 20 A Rec - B1-365 Bed Power 28

25 Rec - B1-372 Team Work 20 A 1 0.7 0.2 1 20 A Rec - B1-365 Computer Cart 26

23 Rec - B1-363 - Nourishment, Refrigerator 20 A 1 0.2 0.5 1 20 A Rec - B1-365 Headwall 24

21 Rec - B1-363 - Nourishment, Ice Maker 20 A 1 0.2 0.5 1 20 A Rec - B1-365 Headwall 22

19 Rec - B1-360 Corridor, Charting 20 A 1 0.5 0.2 1 20 A Rec - B1-364 Bariatric Lift 20

17 Rec - B1-367 Nurse Station 20 A 1 0.7 0.2 1 20 A Rec - B1-364 Bed Power 18

15 Rec - B1-360 Corridor, Charting 20 A 1 0.5 0.2 1 20 A Rec - B1-364 Computer Cart 16

13 Rec - B1-315 Meds, Pyxis 20 A 1 0.2 0.5 1 20 A Rec - B1-364 Headwall 14

11 Rec - B1-315 Meds, Pyxis 20 A 1 0.2 0.5 1 20 A Rec - B1-364 Headwall 12

9 Rec - B1-315 Meds, Pyxis 20 A 1 0.2 0.2 1 20 A Rec - B1-362 Bariatric Lift 10

7 Rec - B1-313 Nurse Manager 20 A 1 1.1 0.2 1 20 A Rec - B1-362 Bed Power 8

5 Rec - B1-312 Team Room 20 A 1 0.7 0.2 1 20 A Rec - B1-362 Computer Cart 6

3 Rec - B1-312 Team Room 20 A 1 1.1 0.5 1 20 A Rec - B1-362 Headwall 4

1 Rec - B1-302 Equip Storage 20 A 1 0.4 0.5 1 20 A Rec - B1-362 Headwall 2

N O T E CKT Circuit Description Trip Poles

A B C

Poles Trip Circuit Description CKT

N O T E

LOAD/PHASE (KVA)

NEW PANEL, REUSE EXISTING FEEDER

Notes:

Enclosure: TYPE 1 MCB Rating:

Mounting: SURFACE Wires: 4 Mains Rating: 225 A

Supply From: 2C1GM Phases: 3 Main Type: MLO

Location: ELECTRICAL B326 Volts: 120/208 Wye A.I.C. Rating: 22000

Branch Panel: 2C1Z

1. CONNECT TO EXISTING SPARE CIRCUIT BREAKER.

Notes:

Receptacle 95100 VA 55.26% 52550 VA Total Est. Demand: 77 A

Power 1975 VA 100.00% 1975 VA Total Conn.: 128 A

Other 5000 VA 100.00% 5000 VA Total Est. Demand: 63867 VA

Motor 90 VA 125.00% 113 VA Total Conn. Load: 106394 VA

Lighting 4229 VA 100.00% 4229 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Total Amps: 128 A 127 A 130 A

Total Load: 35.4 kVA 35.1 kVA 35.9 kVA

41 Space -- 1 -- -- 1 -- Space 42

39 Space -- 1 -- -- 1 -- Space 40

37 Space -- 1 -- -- 1 -- Space 38

35 Space -- 1 -- -- 1 -- Space 36

33 Space -- 1 -- -- 1 -- Space 34

31 Space -- 1 -- -- 1 -- Space 32

29 Spare 20 A 1 0.0 -- 1 -- Space 30

27 Spare 20 A 1 0.0 -- 1 -- Space 28

25 Spare 20 A 1 0.0 -- 1 -- Space 26

23 Spare 20 A 1 0.0 -- 1 -- Space 24

21 Spare 20 A 1 0.0 -- 1 -- Space 22

1 19 Lighting - Patient Rooms Area C 20 A 1 0.4 -- 1 -- Space 20

1 17 Lighting - Area C 20 A 1 0.6 -- 1 -- Space 18

1 15 Lighting - Corridor Area C 20 A 1 0.5 -- 1 -- Space 16

1 13 Lighting - Comm, Data, B1-316, B1-314 20 A 1 0.0 -- 1 -- Space 14

1 11 Lighting - Area A 20 A 1 0.6 -- 1 -- Space 12

1 9 Lighting - Corridor Area A 20 A 1 0.4 -- 1 -- Space 10

1 7 Lighting Electrical Room B1-352 20 A 1 0.0 -- 1 -- Space 8

1 5 Lighting - Patient Rooms Area B 20 A 1 0.6 34.1 -- -- -- 6 --

1 3 Lighting - Patient Rooms Area B 20 A 1 0.4 33.8 -- -- -- 4 --

1 1 Lighting - Corridor Area B 20 A 1 0.5 34.3 3 20 A TN13 2

N O T E CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

N O T E

LOAD/PHASE (KVA)

EXISTING PANEL

Notes:

Enclosure: TYPE 1 MCB Rating:

Mounting: SURFACE Wires: 4 Mains Rating: 225 A

Supply From: N1GM Phases: 3 Main Type: MLO

Location: ELECTRICAL B344 Volts: 480/277 Wye A.I.C. Rating: 35000

Branch Panel: N13

12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554

©Copyright 2023

TLC No.:

www.tlc-engineers.com

119437

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Dwg.

PROJECT TEAM:

Office of

Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

Department of Veterans Affairs

MURFREESBORO, TN

615.370.8500

615.370.8530 hfrdesign.com

214 Centerview Drive Suite 300 Brentwood, TN 37027

Phase

FULLY SPRINKLERED

C R e v it

L o c a ls \1

-E L

E C

-V A

M C

W a rd

B

R a n d re .n g u y e n

V D

W

F .r v t

/1

/2

:4

:3

A

M

06-13-2023

626A4-19-101

E-EI-04

AE RENOVATE WARD 1BELECTRICAL PANEL SCHEDULES

AWD

HFR Project No: 2019056

100% CONSTRUCTION

DOCUMENTS

DLM

Notes:

Total Est. Demand: 85 A

Total Conn.: 128 A

Receptacle 40980 VA 62.20% 25490 VA Total Est. Demand: 30465 VA

Power 1975 VA 100.00% 1975 VA Total Conn. Load: 45955 VA

Other 3000 VA 100.00% 3000 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Total Amps: 120 A 131 A 136 A

Total Load: 14.3 kVA 15.5 kVA 16.1 kVA

83 Spare 20 A 1 0.0 0.0 1 20 A Spare 84

81 Spare 20 A 1 0.0 0.0 1 20 A Spare 82

79 Spare 20 A 1 0.0 0.0 1 20 A Spare 80

77 Spare 20 A 1 0.0 0.0 1 20 A Spare 78

75 Spare 20 A 1 0.0 0.0 1 20 A Spare 76

73 Spare 20 A 1 0.0 0.0 1 20 A Spare 74

71 Rec - B1-349 Computer Cart 20 A 1 0.2 0.4 1 20 A Power - Bug Lamps 72

69 Rec - B1-349 Headwall 20 A 1 0.7 0.8 1 20 A Power - Bug Lamps 70

67 Rec - B1-349 Headwall 20 A 1 0.7 0.9 1 20 A Rec - B1-337 - Clean Linen 68

65 Rec - B1-349 20 A 1 0.7 1.8 1 20 A Power - Trap Primers 66

63 Rec - B1-348 Computer Cart 20 A 1 0.2 0.5 1 20 A Rec - B1-331A Corridor, Charting 64

61 Rec - B1-348 Headwall 20 A 1 0.7 0.5 1 20 A Rec - B1-331A Corridor, Charting 62

59 Rec - B1-348 Headwall 20 A 1 0.7 0.2 1 20 A Rec - B1-352 Electrical Room 60

57 Rec - B1-348 20 A 1 0.7 0.5 1 20 A Rec - B1-338 Clean Utility/Linen 58

55 Rec - B1-343 Computer Cart 20 A 1 0.2 1.1 1 20 A Rec - B1-344 Team Work 56

53 Rec - B1-343 Headwall 20 A 1 0.7 0.9 1 20 A Rec - B1-344 Team Work 54

51 Rec - B1-343 Headwall 20 A 1 0.7 0.4 1 20 A Rec - B1-351 Equip Storage 52

49 Rec - B1-343 20 A 1 0.7 0.2 1 20 A Rec - B1-333 - Nourishment, Refrigerator 50

47 Rec - B1-342 Computer Cart 20 A 1 0.2 0.2 1 20 A Rec - B1-333 - Nourishment, Ice Maker 48

45 Rec - B1-342 Headwall 20 A 1 0.7 0.5 1 20 A Rec - B1-333 - Nourishment 46

43 Rec - B1-342 Headwall 20 A 1 0.7 0.5 1 20 A Rec - B1-330 Corridor, Charting 44

41 Rec - B1-342 20 A 1 0.7 0.7 1 20 A Rec - B1-346 Nurse Station 42

39 Rec - B1-341 Computer Cart 20 A 1 0.2 1.4 1 20 A Rec - B1-346 Nurse Station 40

37 Rec - B1-341 Headwall 20 A 1 0.7 0.5 1 20 A Rec - B1-330 Corridor, Charting 38

35 Rec - B1-341 Headwall 20 A 1 0.7 1.6 1 20 A Rec - Corridor Area B 36

33 Rec - B1-341 20 A 1 0.7 0.3 -- -- -- 34 --

31 Rec - B1-340 Computer Cart 20 A 1 0.2 0.3 2 20 A Rec - B1-350 Laundry, Dryer 32

29 Rec - B1-340 Headwall 20 A 1 0.7 0.3 -- -- -- 30 --

27 Rec - B1-340 Headwall 20 A 1 0.7 0.3 2 20 A Rec - B1-350 Laundry, Dryer 28

25 Rec - B1-340 20 A 1 0.9 0.2 1 20 A Rec - B1-350 Laundry, Washing Machine 26

23 Rec - B1-335 Computer Cart 20 A 1 0.2 0.4 1 20 A Rec - B1-350 Laundry 24

21 Rec - B1-335 Headwall 20 A 1 0.7 0.7 1 20 A Rec - B1-324 Clean Supply 22

19 Rec - B1-335 Headwall 20 A 1 0.7 0.7 1 20 A Rec - B1-320 Serving Kitchen 20

17 Rec - B1-335 20 A 1 0.7 1.0 -- -- -- 18 --

15 Rec - B1-334 Computer Cart 20 A 1 0.2 1.0 2 20 A Power - B1-319 Dining/Day Room, Fireplace 16

13 Rec - B1-334 Headwall 20 A 1 0.7 0.5 1 20 A Rec - B1-319 Dining/Day Room 14

11 Rec - B1-334 Headwall 20 A 1 0.7 0.7 1 20 A Rec - B1-319 Dining/Day Room 12

9 Rec - B1-334 20 A 1 0.7 1.1 1 20 A Rec - B1-318 Nurse Station 10

7 Rec - B1-332 Computer Cart 20 A 1 0.2 0.9 1 20 A Rec - B1-318 Nurse Station 8

5 Rec - B1-332 Headwall 20 A 1 0.7 0.9 1 20 A Rec - B1-318 Nurse Station 6

3 Rec - B1-332 Headwall 20 A 1 0.7 0.9 1 20 A Rec - B1-317 Charge Nurse 4

1 Rec - B1-332 20 A 1 0.7 0.7 1 20 A Rec - B1-317 Charge Nurse 2

N O T E CKT Circuit Description Trip Poles

A B C

Poles Trip Circuit Description CKT

N O T E

LOAD/PHASE (KVA)

Notes:

Enclosure: TYPE 1 MCB Rating:

Mounting: SURFACE Wires: 4 Mains Rating: 150 A

Supply From: 2N13 Phases: 3 Main Type: MLO

Location: ELECTRICAL B344 Volts: 120/208 Wye A.I.C. Rating: 22000

Branch Panel: 2N1W

Notes:

Total Est. Demand: 79 A

Total Conn.: 124 A

Total Est. Demand: 28420 VA

Receptacle 42840 VA 61.67% 26420 VA Total Conn. Load: 44840 VA

Other 2000 VA 100.00% 2000 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Total Amps: 131 A 123 A 121 A

Total Load: 15.7 kVA 14.7 kVA 14.5 kVA

83 Spare 20 A 1 0.0 0.0 1 20 A Spare 84

81 Spare 20 A 1 0.0 0.0 1 20 A Spare 82

79 Spare 20 A 1 0.0 0.0 1 20 A Spare 80

77 Spare 20 A 1 0.0 0.0 1 20 A Spare 78

75 Spare 20 A 1 0.0 0.0 1 20 A Spare 76

73 Spare 20 A 1 0.0 0.4 1 20 A Rec - B1-310 Rec. Thr. Stor. 74

71 Rec - B1-382 Computer Cart 20 A 1 0.2 0.8 1 20 A Power - Bug Lamps 72

69 Rec - B1-382 Headwall 20 A 1 0.7 1.2 1 20 A Power - Trap Primers 70

67 Rec - B1-382 Headwall 20 A 1 0.7 0.5 1 20 A Rec - B1-361A Corridor, Charting 68

65 Rec - B1-382 20 A 1 0.7 0.5 1 20 A Rec - B1-361A Corridor, Charting 66

63 Rec - B1-381 Computer Cart 20 A 1 0.2 0.5 1 20 A Rec - B1-375 Clean Utility/Work 64

61 Rec - B1-381 Headwall 20 A 1 0.7 0.5 1 20 A Rec - B1-383 Electrical Room 62

59 Rec - B1-381 Headwall 20 A 1 0.7 1.1 1 20 A Rec - B1-372 Team Work 60

57 Rec - B1-381 20 A 1 0.7 0.9 1 20 A Rec - B1-372 Team Work 58

55 Rec - B1-380 Computer Cart 20 A 1 0.2 0.2 1 20 A Rec - B1-363 - Nourishment, Refrigerator 56

53 Rec - B1-380 Headwall 20 A 1 0.7 0.2 1 20 A Rec - B1-363 - Nourishment, Ice Maker 54

51 Rec - B1-380 Headwall 20 A 1 0.7 0.5 1 20 A Rec - B1-363 - Nourishment 52

49 Rec - B1-380 20 A 1 0.7 0.5 1 20 A Rec - B1-360 Corridor, Charting 50

47 Rec - B1-379 Computer Cart 20 A 1 0.2 0.7 1 20 A Rec - B1-367 Nurse Station 48

45 Rec - B1-379 Headwall 20 A 1 0.7 1.3 1 20 A Rec - B1-367 Nurse Station 46

43 Rec - B1-379 Headwall 20 A 1 0.7 0.5 1 20 A Rec - B1-360 Corridor, Charting 44

41 Rec - B1-379 20 A 1 0.7 1.6 1 20 A Rec - Corridor Area C 42

39 Rec - B1-378 Computer Cart 20 A 1 0.2 0.2 1 20 A Rec - B1-315 Meds, Pyxis 40

37 Rec - B1-378 Headwall 20 A 1 0.7 0.2 1 20 A Rec - B1-315 Meds, Pyxis 38

35 Rec - B1-378 Headwall 20 A 1 0.7 0.2 1 20 A Rec - B1-315 Meds, Pyxis 36

33 Rec - B1-378 20 A 1 0.7 0.5 1 20 A Rec - B1-315 Meds 34

31 Rec - B1-377 Computer Cart 20 A 1 0.2 1.1 1 20 A Rec - B1-313 Nurse Manager 32

29 Rec - B1-377 Headwall 20 A 1 0.7 0.5 1 20 A Rec - B1-313 Nurse Manager 30

27 Rec - B1-377 Headwall 20 A 1 0.7 1.1 1 20 A Rec - B1-312 Team Room 28

25 Rec - B1-377 20 A 1 0.9 0.9 1 20 A Rec - B1-312 Team Room 26

23 Rec - B1-365 Computer Cart 20 A 1 0.2 0.5 1 20 A Rec - B1-309 Consult 24

21 Rec - B1-365 Headwall 20 A 1 0.7 0.2 1 20 A Rec - B1-308 Family Lounge, Coffee Machine 22

19 Rec - B1-365 Headwall 20 A 1 0.7 0.7 1 20 A Rec - B1-308 Family Lounge 20

17 Rec - B1-365 20 A 1 0.7 0.2 1 20 A Rec - B1-305 Staff Lounge, Refrigerator 18

15 Rec - B1-364 Computer Cart 20 A 1 0.2 0.2 1 20 A Rec - B1-305 Staff Lounge, Microwave 16

13 Rec - B1-364 Headwall 20 A 1 0.7 1.4 1 20 A Rec - B1-305/306 Staff Lounge/Lockers 14

11 Rec - B1-364 Headwall 20 A 1 0.7 0.9 1 20 A Rec - B1-304 Inpatient Rehab 12

9 Rec - B1-364 20 A 1 0.7 0.9 1 20 A Rec - B1-303 Social Worker 10

7 Rec - B1-362 Computer Cart 20 A 1 0.2 0.4 1 20 A Rec - B1-302 Equip Storage 8

5 Rec - B1-362 Headwall 20 A 1 0.7 0.2 1 20 A Rec - Area A Vending Machine 6

3 Rec - B1-362 Headwall 20 A 1 0.7 0.2 1 20 A Rec - Area A Vending Machine 4

1 Rec - B1-362 20 A 1 0.7 1.1 1 20 A Rec - Corridor Area A 2

N O T E CKT Circuit Description Trip Poles

A B C

Poles Trip Circuit Description CKT

N O T E

LOAD/PHASE (KVA)

Notes:

Enclosure: TYPE 1 MCB Rating:

Mounting: SURFACE Wires: 4 Mains Rating: 150 A

Supply From: 2N13 Phases: 3 Main Type: MLO

Location: ELECTRICAL B326 Volts: 120/208 Wye A.I.C. Rating: 22000

Branch Panel: 2N1Z

Notes:

Total Est. Demand: 7 A

Total Conn.: 7 A

Total Est. Demand: 2680 VA

Total Conn. Load: 2680 VA

Receptacle 2680 VA 100.00% 2680 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Total Amps: 12 A 6 A 5 A

Total Load: 1.4 kVA 0.7 kVA 0.6 kVA

23 Spare 20 A 1 0.0 0.0 1 20 A Spare 24

21 Spare 20 A 1 0.0 0.0 1 20 A Spare 22

19 Spare 20 A 1 0.0 0.0 1 20 A Spare 20

-- 17 -- -- -- 0.3 0.0 1 20 A Spare 18

-- 15 -- -- -- 0.3 0.0 1 20 A Spare 16

13 DATA ROOM - RACK 1 - FIBER/PATCH 30 A 3 0.3 0.7 1 20 A DATA ROOM - CONVENIENCE RECEPTACLES 14

11 COMM ROOM - CONVENIENCE... 20 A 1 0.4 0.0 1 20 A Spare 12

9 Spare 20 A 1 0.0 0.0 1 20 A Spare 10

7 Spare 20 A 1 0.0 0.0 1 20 A Spare 8

5 Spare 20 A 1 0.0 0.0 1 20 A Spare 6

-- 3 -- -- -- 0.4 0.0 1 20 A Spare 4

1 COMM ROOM - RACK 1 - FIBER/PATCH 20 A 2 0.4 0.0 1 20 A Spare 2

N O T E CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

N O T E

LOAD/PHASE (KVA)

Notes:

Enclosure: TYPE 1 MCB Rating:

Mounting: SURFACE Wires: 4 Mains Rating: 100 A

Supply From: 2N13 Phases: 3 Main Type: MLO

Location: ELECTRICAL B334 Volts: 120/208 Wye A.I.C. Rating: 22000

Branch Panel: 2N1X

Notes:

Total Est. Demand: 12 A

Total Conn.: 12 A

Total Est. Demand: 4440 VA

Receptacle 3040 VA 100.00% 3040 VA Total Conn. Load: 4440 VA

Other 1400 VA 100.00% 1400 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Total Amps: 17 A 13 A 9 A

Total Load: 2.0 kVA 1.4 kVA 1.0 kVA

23 Spare 20 A 1 0.0 0.0 1 20 A Spare 24

21 Spare 20 A 1 0.0 0.0 1 20 A Spare 22

19 Spare 20 A 1 0.0 0.0 1 20 A Spare 20

-- 17 -- -- -- 0.3 0.0 1 20 A Spare 18

-- 15 -- -- -- 0.3 0.0 1 20 A DATA ROOM - CONV RECPT 16

13 DATA ROOM - RACK 1 - FIBER/PATCH 30 A 3 0.3 0.9 1 20 A DATA ROOM - TELCO TERMINAL 14

11 COMM ROOM - CONVENIENCE... 20 A 1 0.4 0.0 1 20 A Spare 12

9 COMM ROOM - NURSE CALL 20 A 1 0.4 0.2 1 20 A COMM ROOM - RADIO/DAS 10

7 COMM ROOM - TELEVISION 20 A 1 0.2 0.2 1 20 A COMM ROOM - INTERCOM 8

5 COMM ROOM - DDC 20 A 1 0.2 0.2 1 20 A COMM ROOM - PUBLIC ADDRESS 6

-- 3 -- -- -- 0.4 0.2 1 20 A COMM ROOM - SECURITY 4

1 COMM ROOM - RACK 1 - FIBER/PATCH 30 A 2 0.4 0.0 1 20 A Spare 2

N O T E CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

N O T E

LOAD/PHASE (KVA)

Notes:

Enclosure: TYPE 1 MCB Rating:

Mounting: SURFACE Wires: 4 Mains Rating: 100 A

Supply From: 2C1W Phases: 3 Main Type: MLO

Location: ELECTRICAL B334 Volts: 120/208 Wye A.I.C. Rating: 22000

Branch Panel: 2C1X

Notes:

Total Est. Demand: 166 A

Receptacle 95100 VA 55.26% 52550 VA Total Conn.: 284 A

Power 1975 VA 100.00% 1975 VA Total Est. Demand: 59638 VA

Other 5000 VA 100.00% 5000 VA Total Conn. Load: 102165 VA

Motor 90 VA 125.00% 113 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Total Amps: 284 A

Total Conn. Load: 102165 VA

5 Rec - B1-320 Serving Kitchen, Servery 3 100 A 30 A 8600 VA

4 EF-1 1 100 A 15 A 90 VA

3 2N1X 3 100 A 60 A 2680 VA

2 2N1Z 3 250 A 150 A 44840 VA

1 2N1W 3 250 A 150 A 45955 VA

CKT Circuit Description # of Poles Frame Size Trip Rating

Load

Remarks

Notes:

Enclosure: TYPE 1 MCB Rating: 300 A

Mounting: SURFACE Wires: 4 Mains Rating:

Supply From: TN13 Phases: 3 Mains Type: MCB

Location: ELECTRICAL B344 Volts: 120/208 Wye A.I.C. Rating: 22000

Branch Panel: 2N13

1. EXISTING LOAD

Notes:

Total Est. Demand: 0 A

Total Conn.: 0 A

To…

This is the start of the file's text. The full file is on GovTribe.

File details come from the government source that posted it. Updated .