About this file

This solicitation is for renovations to Ward 1B at the Alvin C. York VA Medical Center in Murfreesboro, Tennessee. The solicitation number is 36C24923R0114 and was issued by the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 9. Renovations include updating patient rooms, corridors, support spaces, and building systems on the third floor to improve patient care and comply with codes and standards. The work also involves phasing plans to minimize disruption during construction. The deadline for responses is not provided in the document.

View the file

Other files

File Type Posted
36C24923R0114 0003.docx DOCX document
E-EI-01 - PARTIAL ELECTRICAL RISER DIAGRAM - DEMOLITION.pdf PDF
119437-Alvin C. York VAMC Renovate Ward 1B - Revision 1 - Electrical Narrative.pdf PDF
Government Answers to Industry Questions.pdf PDF
283100.pdf PDF
275223.pdf PDF
Bradley_GrabBar_8370-107.pdf PDF
Ward 1B - Revision 1.pdf PDF
Renovate Ward 1B Pre-Proposal Sign in Sheet - 07-06-2023.pdf PDF
E-EI-02 - PARTIAL ELECTRICAL RISER DIAGRAM - NEW WORK.pdf PDF
Bradley_GrabBar_8370-108.pdf PDF
General Decision Number TN20230187 06-30-2023 Rutherford County TN.pdf PDF
ASI 3413-25.pdf PDF
36C24923R0114 0002.docx DOCX document
GAMCO 125SwingUpTP.pdf PDF
Interior Wall Type Legend.pdf PDF
SUBCONTRACTOR INFORMATION AND CONSENT FORM.docx DOCX document
36C24923R0114 0001.docx DOCX document
MECH BINDER.pdf PDF
Ward 1B - Specs - Vol. 2.pdf PDF
GD Number TN20230187 05-12-2023.pdf PDF
GI 01-02 - CONSTRUCTION STAGING PLAN.pdf PDF
GI 03-01 - SECOND FLOOR ICRA PLAN.pdf PDF
GI 05-01 - PHASING PLANS.pdf PDF
GI 00-01 - COVER SHEET.pdf PDF
GI 01-10 - WALL TYPE DETAILS.pdf PDF
Price Schedule Project 626A4-19-101 Renovate Ward 1B.xlsx XLSX spreadsheet
GI 04-02 - LEAD PAINT AND TRANSITE PANELS.pdf PDF
36C24923R0114.docx DOCX document
General Conditions Breakout.xlsx XLSX spreadsheet
WARD 1B - ARCH BINDER.pdf PDF
GI 01-20 - ACCESSIBILITY DETAILS.pdf PDF
RFI Form.docx DOCX document
GI 04-01 - ACM DUCT WORK AND ACM PIPE INSULATION.pdf PDF
Performance Relevancy Survey Form - 626A4-19-101 Renovate Ward 1B.docx DOCX document
Ward 1B - Specs - Vol. 1.pdf PDF
VN 01-00 - PATIENT LIFT VENDOR DRAWINGS.pdf PDF
ELECTRICAL BINDER.pdf PDF
PLUMBING BINDER.pdf PDF
GI 01-01 - GENERAL DATA.pdf PDF
WARD 1B - GENERAL.pdf PDF
WARD 1B - INTERIORS .pdf PDF
Calculation of Self Performed Work.docx DOCX document
GI 02-01 - THIRD FLOOR LIFE SAFETY PLAN - OVERALL.pdf PDF
AD 01-01 - THIRD FLOOR DEMOLITION PLAN - OVERALL.pdf PDF
Contractor EMR Certification Form.docx DOCX document
FP BINDER.pdf PDF
GI 03-02 - THIRD FLOOR ICRA PLAN.pdf PDF
Show all 48

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

CLEAN UTILITY

SOILED UT.

PT. ROOM

PT. ROOM

PT. ROOM

PT. ROOM

ELEC.

STAFF TLT.STAIR

PT. ISO ROOM

PT. ROOM

PT. ROOM

WORK RM

ANTE

OFFICE

RESIDENTS RM.

MECH.

PT. ROOM

PT. ROOM

STOR. ROOM MEDS

SUPPLY ROOM

ELEC.

NOURISHMENT

CHUTE

IT

COMM

CONSULT

PT. ROOM PT. ROOM

PT. ROOM

PT. ROOM

MECH

OFFICE

RESIDENTS

ROOM

STAIR

PT. ROOM

PT. ROOM

PT. ROOM

WORK ROOM

CLEAN UTILITY

SOILED UTILITY

PT. ROOM

PT. ROOM

PT. ROOM

PT. ROOM

HAC ELEC.

STAFF TLT

NURSE WK.

NURSE STATION

SOCIAL WORK

WAITING ROOM

STAIRS

CHASE

LOCKER RM.

RETHERM

CONF.

STAFF TLT.

CORRID

STAFF BREAK

EXAMPLE #1

EXAMPLE LEGEND

EXAMPLE #2

EXAMPLE #3

EXAMPLE #4

EXAMPLE #5

EXAMPLE #6

ISO ROOM

PAT. TLT.

PRIVATE ROOM

PRIVATE ROOM

PRIVATE ROOM

BARI PRIVATE

ROOM

BARIATRIC

PATIENT TOILET

PRIVATE ROOM

PRIVATE ROOM

PANTRY

SERVING

KITCHEN

DINING/DAY

ROOM

LAUNDRY CLEAN SUPPLY

RETHERMCHUTE

EQUIP STORAGE

INPATIENT

REHAB

STAFF LOUNGE

STAFF LOCKERS

CHAIR ALCOVE

FAM. LOUNGE

CONSULT

FAM/PUB. TLT.

REC.THR. STOR.

TEAM ROOM

DATA

CLEAN LINEN

NOURISH

ST. TLT.

HAC.

SOILED HOLD

ELEC.

CLEAN UTILITY

HAC

WOUND CART

STOR.SUB NS.

PRIVATE ROOM

PRIVATE ROOM

ISO ROOM

CLEAN UTILITY

PAT. TLT.

ELEC.

EQUIP STOR.

TEAM WORKCLEAN LINEN

SOILED HOLD

BARI PRIVATE

ROOM

BARI. TLT.

NOURISHMENT

PAT. TLT.

PAT. TLT.

STAFF TLT.

PRIVATE ROOM

PAT. TLT.

PAT. TLT.

PAT. TLT.

PRIVATE ROOM

PAT. TLT.

PRIVATE ROOM

PRIVATE ROOM

PRIVATE ROOM

PAT. TLT.

PAT. TLT.

PAT. TLT.

PAT. TLT.

TEAM WORK

ROOM

SUB N.S.

CHARGE NURSE

NURSE STATION

SOCIAL WORKER

DIRTY

EMPTY CYL.

STOR.

FULL CYL. STOR.

ANTE

NURSE

MANAGER

PAT. TLT.

PAT. TLT.

ANTE

MEDS

COMM

STAFF TLT.

PRIVATE ROOM PRIVATE ROOM

CORRIDOR

CORRIDOR

CORRIDOR

CORRIDOR

VENDING

PAT. TLT.

PAT. TLT.

CORRIDOR

CORRIDOR

CORRIDOR

CORRIDOR

STAIR 1

STAIR 2

STAIR 3

EXISTING RISER

ELEV.

ELEV.

CHASE

CHASE

CHASE

CHASE

THE INTENT WITH THIS PLAN IS TO SHOW

HOW THE AREAS BETWEEN THE SECOND

FLOOR AND THRID FLOOR ALIGN

12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554

©Copyright 2019

TLC No.:

www.tlc-engineers.com

118626

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Dwg.

PROJECT TEAM:

Office of

Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

Department of Veterans Affairs

KEYPLAN

MURFREESBORO, TN

615.370.8500

615.370.8530 hfrdesign.com

214 Centerview Drive Suite 300 Brentwood, TN 37027

BLDG 2

BLDG 1

BLDG 9

Phase

FULLY SPRINKLERED

C U s e rs \a tr a y lo r\ D o c u m e n ts

\M b o ro V

A W a rd b

R e n o a tr a y lo r2 X

N D

H .r v t

/1

/2

:5

:4

P

M

04-14-2023

626A4-19-101

GI 05.01

AE RENOVATE WARD 1BPHASING PLANS

Author

HFR Project No: 2019056

100% CONSTRUCTION

DOCUMENTS

1 SECOND FLOOR PLAN - PHASING PLAN

0 8' 16' 32'4'

2 03 THIRD FLOOR PLAN - PHASING PLAN

0 8' 16' 32'4'

GENERAL NOTE:

1. THE PHASING PLAN IS NOTED AS EXAMPLES TO GIVE THE CONTRACTOR AN

UNDERSTANDING OF HOW THE PHASING FOR THE PROJECT NEEDS TO BE

ADDRESSED. WHILE THEY ARE LISTED BY NUMBER THESE EXAMPLES CAN BE

CONDUCTED IN ANY SEQUENCE AS DEEMED NECESSARY FOR THE MOST EFFECIENT

PROCESS POSSIBLE.

2. IN GENERAL 5 PATIENT ROOMS AT ONE TIME ON THE FLOOR BELOW WILL BE ABLE

TO BE TEMPORARLY OUT OF COMMISSION TO WORK ON VERTICAL SERVICES, THERE

MUST BE AT LEAST 15 ACTIVE PATIENT ROOMS AT ALL TIMES.

3. ALL ROOMS THAT ARE BEING WORKED ON SHALL BE PROTECTED FROM DAMAGE

AS BEST AS POSSIBILE. MOST OF THE WORK WILL TAKE PLACE IN THE CEILING,

HOWEVER DAMAGE TO ANY OTHER PART OF THE ROOM MUST BE REPARIED.

PROTECT EXISTING CEILING TILES, TILES THAT ARE DAMAGED OR BROKEN MUST BE

REPLACED TO THE ORIGINAL STATE.

4. CAREFUL COORDINATION WITH THE FACILITY MUST TAKE PLACE TO ADDRESS ANY

SHUTDOWNS THAT COULD EFFECT AREAS OUTSIDE OF THE DESIGNATED EXAMLE

ZONE.

5. IF SUPPORT SPACE INSIDE OF A DESIGNATED EXAMPLE ZONE IS SERVING

ANOTHER EXAMPLE ZONE COORDINATE SPECIFIC TIMES WITH THE FACILITY TO GAIN

ACCESS TO THIS SPACE.

6. ICRA BARRIERS MUST BE USED TO CLOSE OFF EACH AREA THAT IS BEING WORKED

ON TO PREVENT CONSTRUCTION DEBRIS AND DUST FROM INFILTRATING OCCUPIED

SPACE. BARRIERS SHALL BE INSTALLED AND SEALED ALONG WITH STICKY MATS AND

ANY OTHER INFECTION CONTROL ITEMS. IN SOME INSTANCES ICRA BARRIERS MAY

BE REQUIRED PER ROOM.

7. WORK IN THE CONNECTING CORRIDORS, ELEVATOR LOBBY AND NURSE STATION

SHALL BE CAREFULLY COORDINATED WITH THE FACILITY AND STAFF. THE NEED TO

WORK IN THESE AREAS SHALL BE EVALUATED ON A AS NEEDED BASIS. ELEVATOR

ACCESS SHALL BE MAINTAINED AT ALL TIMES

No. Date Description jim.elder Rectangle jim.elder Typewritten Text 06-13-2023 jim.elder Rectangle jacob.kelsheimer Snapshot jacob.kelsheimer Snapshot

12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554

©Copyright 2023

TLC No.:

www.tlc-engineers.com

119437

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Dwg.

PROJECT TEAM:

Office of

Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

Department of Veterans Affairs

MURFREESBORO, TN

615.370.8500

615.370.8530 hfrdesign.com

214 Centerview Drive Suite 300 Brentwood, TN 37027

Phase

FULLY SPRINKLERED

C R e v it

L o c a ls \1

-T E

C H

-V A

M C

W a rd

B

R ja c o b .k e ls h e im e r.

rv t

/1

/2

:4

:4

A

M

06-13-2023

626A4-19-101

T-TJ-00

AE RENOVATE WARD 1BGENERAL TECHNOLOGY INFORMATION

JAK

HFR Project No: 2019056

100% CONSTRUCTION

DOCUMENTS

DESCRIPTIONSYMBOLDESCRIPTIONSYMBOLDESCRIPTIONSYMBOL DESCRIPTIONSYMBOL

NOTE: SOME SYMBOLS SHOWN ON THIS LEGEND MAY NOT PERTAIN TO THIS PROJECT.

DESCRIPTIONSYMBOL

X

T

2.5

DELAYED EGRESSDE

AUDIO/VIDEO SYSTEM

REQUEST TO EXIT MOTION SENSOR

GLASS BREAK SENSOR

360° MOTION DETECTOR

PAN/TILT/ZOOM CCTV CAMERA,,

PROVIDE CAT6A CABLE,

FACEPLATE, AND DOUBLE GANG

JUNCTION BOX AND CONDUIT

SECURITY PANEL

DOOR POSITION SWITCH

BALANCED MAGNETIC SWITCH

ELECTRIC LATCH

ELECTRIC MORTISE/TRIM LOCK

ELECTRIC STRIKE

MAGNETIC LOCK

POWER OVER ETHERNET

CARDREADER/LOCK COMBO

REMOTE DOOR RELEASE BUTTON

ASSISTANCE STATION

DURESS BUTTON MOUNTED

UNDERSIDE OF

COUNTER

CCTV MONITOR

PHOTO ELECTRIC BEAM

INTERCOM MASTER STATION

DIRECTIONAL MOTION DETECTOR

FIXED CCTV CAMERA, PROVIDE

CAT6A CABLE, FACEPLATE, AND

DOUBLE GANG JUNCTION BOX AND

CONDUIT

P

BASIC MATERIALS

J

J

TECHNOLOGY SYSTEMS SYMBOL LEGEND

J

SECURITY SYSTEM

LADDER TRAY FOR HORIZONTAL

CABLING.

PENETRATION CONDUIT

SLEEVE WITH

BUSHINGS.

GENERAL NOTES

EXISTING TO BE REMOVED

EXISTING TO REMAIN

EXISTING AFFECTED BY THIS

PROJECT

FUTURE

SLEEVE TURNING DOWN

SLEEVE TURNING UP

GROUND OR GROUND ROD AS

NOTED

FLEXIBLE CONDUIT

CONDUIT CONTINUED

CONDUIT STUB

CONDUIT TURNING DOWN

CONDUIT TURNING UP

CONDUIT CONCEALED IN SLAB,

UNDERGROUND OR UNDER

FLOOR

CONDUIT EXPOSED

CONDUIT CONCEALED

PEDESTAL MOUNTED JUNCTION BOX

FLOOR MOUNTED JUNCTION BOX

JUNCTION BOX

VOICE & DATA SYSTEM

BROADBAND TELEVISION SYSTEM

6 PORT TAP

8 PORT TAP

TERMINATION TAP

4 PORT TAP

2 PORT TAP

3 WAY SPLITTER

2 WAY SPLITTER

4 WAY SPLITTER

AMPLIFIER

DIRECTIONAL COUPLER

BIOMETRIC READER

INTRUSION ALARM KEYPAD

HIRSH SCRAMBLE KEYPAD

KEYPAD

CARD READER

LOCAL HORN STROBE ALARMSA

COMBINED CARD READER/KEYPAD

GENERAL SYSTEM NOTES

1. PRODUCTS SHALL BE OF MATERIALS THAT ARE SUITABLE FOR THE

ENVIRONMENT IN WHICH THEY ARE TO BE INSTALLED.

2. WORKING CLEARANCES AROUND ELECTRICAL EQUIPMENT SHALL BE

MAINTAINED IN COMPLIANCE WITH THE NATIONAL ELECTRICAL CODE ARTICLE

110, COORDINATE EQUIPMENT INSTALLATION TO MAINTAIN REQUIRED

CLEARANCES.

3. IF AN OUTLET BOX IS REQUIRED TO BE LOCATED IN AN ASSEMBLY OR PARTITION

RATED AS "FIRE/SMOKE" OR "SMOKE" OR IDENTIFIED AS EITHER "FIRE/SMOKE"

OR "SMOKE", THEN ALL OF THE FOLLOWING CONDITIONS SHALL BE MET:

THE OUTLET BOX OPENINGS SHALL OCCUR ONLY ON ONE SIDE OF THE

FRAMING SPACE.

THE OUTLET BOX SHALL BE METALLIC.

THE OUTLET BOX OPENINGS SHALL NOT EXCEED 16 SQUARE INCHES.

ALL CLEARANCES BETWEEN THE OUTLET BOX AND THE WALL BOARD

MATERIAL SHALL BE COMPLETELY SEALED WITH APPROVED MATERIALS IN

ACCORDANCE WITH THE APPLICABLE CODES AND STANDARDS FOR THE

PROJECT.

PROVIDE A SUPPLEMENTAL BARRIER AROUND OUTLETS LARGER THAN 16

INCHES SO THAT THE ORIGINAL RATING OF THE PENETRATION IS

MAINTAINED.

THE TOTAL AGGREGATE SURFACE AREA OF THE OUTLET BOX SHALL

NOT EXCEED 100 SQUARE INCHES PER 100 SQUARE FEET.

THE OUTLET BOX SHALL BE SEPARATED FROM OPENINGS ON THE

OPPOSITE SIDE OF THE RATED PARTITION BY A MINIMUM

HORIZONTAL DISTANCE OF 24 INCHES.

THE OUTLET BOX SHALL BE SECURELY FASTENED TO A PARTITION

FRAMING MEMBER BY MEANS OF AN APPROVED ATTACHMENT

METHOD.

OPENINGS CUT INTO THE WALL BOARD MATERIAL SHALL NOT

EXCEED 1/8 INCH BETWEEN THE EDGES OF THE OUTLET BOX

AND THE EDGES OF THE OPENING.

A.

B.

C.

D.

E.

F.

G.

H.

I.

LOCATIONS OF EQUIPMENT SHOWN ON THE DRAWINGS ARE

APPROXIMATE, COORDINATE EXACT EQUIPMENT LOCATION AND

CONNECTION REQUIREMENTS WITH THE APPROPRIATE TRADE PRIOR TO

INSTALLATION.

FOR EXACT LOCATION OF CEILING MOUNTED EQUIPMENT REFER TO THE

ARCHITECTURAL REFLECTED CEILING PLAN. LOCATIONS OF EQUIPMENT

NOT INCLUDED ON THE REFLECTED CEILING PLAN SHALL BE COORDINATED

WITH THOSE ITEMS SHOWN. COORDINATION OF CEILING MOUNTED

EQUIPMENT SHALL BE PRIOR TO ANY ROUGH-IN. NOTIFY ENGINEER OF ANY

DISCREPANCY.

PROVIDE FINAL CONNECTIONS TO VA PROVIDED EQUIPMENT WHERE

INDICATED ON THE PLAN DRAWINGS.

PRIOR TO ROUGH-IN AND INSTALLATION OF ANY FLOOR MOUNTED

DEVICE, VERIFY LOCATION WITH THE COR.

VERIFY AND COORDINATE THE LOCATION OF REQUIRED OUTLETS

WITH OTHER TRADE DRAWINGS AND VA PROVIDED EQUIPMENT.

EACH TELEVISION OUTLET LOCATION SHOWN, SHALL HAVE A DOUBLE GANG

OUTLET BOX WITH A SINGLE GANG PLASTER RING AND (1) 1" CONDUIT

STUBBED UP TO AN ACCESSIBLE LOCATION ABOVE THE FINISHED CEILING OR

TO AN ACCESSIBLE CABLE TRAY WHERE PROVIDED.

THE DESIGNATION ''N.I.C.'' SHALL DENOTE ITEMS, WHICH ARE ''NOT IN CONTRACT''.

THE DESIGNATION ''U.S.C.'' SHALL DENOTE ITEMS, WHICH ARE ''UNDER SEPARATE

CONTRACT''.

THE DESIGNATION ''F.B.O.'' SHALL DENOTE ITEMS, WHICH ARE ''FURNISHED BY

OTHERS''.

THE DESIGNATION ''O.F.E.'' SHALL DENOTE ITEMS, WHICH ARE ''OWNER

FURNISHED EQUIPMENT''.

ALL RACEWAY SYSTEMS SHOWN TO SUPPORT THE INSTALLATION OF THE

DIVISION 27 EQUIPMENT SHALL BE PROVIDED BY THE ELECTRICAL INSTALLER.

PROVIDE COORDINATION FOR THE INSTALLATION OF THIS BE PROVIDED BY THE

ELECTRICAL INSTALLER.

THE SYMBOL LEGENDS SHOWN ON THIS SHEET ARE ALL INCLUSIVE,

SYMBOLS INCLUDED IN THE LEGENDS MAY OR MAY NOT BE USED IN

THESE PROJECT DRAWINGS.

4.

5.

6.

7.

8.

9.

10.

11.

12.

13.

EACH VOICE/DATA OUTLET LOCATION SHOWN, SHALL HAVE A DOUBLE GANG

OUTLET BOX WITH A SINGLE GANG PLASTER RING AND (1) 1" CONDUIT STUBBED UP

TO AN ACCESSIBLE LOCATION ABOVE THE FINISHED CEILING, TO AN ACCESSIBLE

CABLE TRAY WHERE PROVIDED OR HOMERUN IN SLAB TO NEAREST

COMMUNICATIONS ROOM. WORK BY ELECTRICAL INSTALLER PER

SPECIFICATIONS.

EACH FLOOR MOUNTED VOICE/DATA OUTLET SHALL HAVE A SINGLE GANG SPACE

WITHIN THE FLOOR BOX AND (1) 1" CONDUIT CONCEALED IN SLAB STUBBED UP TO

AN ACCESSIBLE LOCATION ABOVE THE FINISHED CEILING OR TO AN ACCESSIBLE

CABLE TRAY WHERE PROVIDED. WORK BY ELECTRICAL INSTALLER PER

SPECIFICATIONS.

ALL BONDING AND GROUNDING ELEMENTS UTILIZED FOR STRUCTURED CABLING

SYSTEM SHALL BE IN COMPLIANCE WITH SPECIFICATIONS.

PROVIDE ALL SLEEVES AS REQUIRED FOR ALL LOW VOLTAGE CABLE

PATHWAYS. RESTORE THE FIRE RATING OF THE SURFACE.

AUDIO VISUAL INPUT/OUTPUT - WALL MOUNTED

WITH ADJACENT DEDICATED DUPLEX

RECEPTACLE BY

X = TYPE (A, B, C, ETC.) SEE DETAILS FOR

ADDITIONAL INFORMATION

PODIUM

X x

Y

X x Y x

SX

SX

OVERHEAD PROJECTOR WITH

SCREEN, SCREEN SIZE SHOWN ON

PLANS

OVERHEAD PROJECTOR -

CEILING MOUNTED

X - DENOTES TYPE

PULLDOWN PROJECTION SCREEN, SIZE

SPECIFIED ON PLANS

OVERHEAD PROJECTION SCREEN MOTOR

WALL SWITCH FOR MOTORIZED SCREEN

CEILING MOUNTED SPEAKER

x DENOTES TYPE y DENOTES ZONE

TELECOMMUNICATIONS EQUIPMENT ROOMTER:

TR: TELECOMMUNICATIONS ROOM

TELECOMMUNICATIONS ENTRANCE FACILITYTEF:

NOTES:

INSTALLER TO REMOVE ALL EXISTING LOW VOLTAGE CABLES NOT TO BE

REUSED. E.G. ALL EXISTING UTP 4 PAIR CABLES. NO ABANDONED CABLES

SHALL BE LEFT IN THE BUILDING.

MOUNTING 2" ABOVE COUNTER OR BACK SPLASH

C

1. VOICE/DATA JACKS:

EACH RJ45 JACK FOR VOICE/DATA SHALL BE

CONNECTED TO A DEDICATED UTP 4 PR CABLE.

COMMUNICATIONS "INFORMATION OUTLET" MOUNTED AT

RECEPTACLE HEIGHT UNLESS OTHERWISE NOTED. MODULE

AND FACEPLATE DESCRIPTIONS ON DETAIL SHEETS

NNX

X = MOUNTING (F)LUSH, (S)URFACE, (M)ODULAR FURNITURE

ADAPTER (P)OLE, (R)ACEWAY, (D)OUBLE GANG FLUSH, (PD)

PEDESTAL

N = # OF VOICE/DATA JACKS

WALL TELEPHONE OUTLET FOR HOUSE PHONE.

MOUNTED AT 52" ABOVE FINISHED FLOOR TO TOP.

WIRELESS ACCESS POINT OUTLET. ACCESS POINT BY

OWNER.

X = MOUNTING (F)LUSH, (S)URFACE, (C)EILING.

N = # OF DATA JACKS. MAXIMUM CABLE LENGTH 262 FT

N

N = # OF COAX CONNECTORS "F" TYPE CONNECTOR

N = # OF FIBER OPTIC CONNECTORS. SC, ST, LC

REX OR ADA DOOR OPEN BUTTON

AUDIO/VIDEO CAMERAAV

ASSOCIATED DOOR DETAIL REFERENCE

INGROUND PULL BOX

MON

PERSONAL COMPUTER WORKSTATION

SPECIAL NOTES:

W F1

WALL MOUNTED OUTLET FOR ADA ACCESSABLE PAY

PHONE. MOUNTED AT 44" ABOVE FINISHED FLOOR

WAP

XON

WALL TELEPHONE OUTLET FOR TELEPHONE IN ELEVATOR

MACHINE ROOM. (S)URFACE MOUNTED AT 52" ABOVE

FINISHED FLOOR.

W

ADA

S1

ELV

COMBINED VOICE/DATA, AUDIO/VIDEO AND POWER OUTLETS IN

FLOOR BOX. POWER RECEPTACLE IS SHOWN FOR

REFERENCE ONLY. CONDUIT, BOX AND POWER RECEPTACLE

PROVIDED BY

X = A, B, C... FLOOR BOX TYPE. N'S ARE DESCRIBED ABOVE.

TB

TABLE TOP POP-UP WITH VOICE/DATA, AUDIO/VIDEO AND

POWER INTERFACE.

X = A, B, C... FLOOR BOX TYPE. N'S ARE DESCRIBED ABOVE.

POKE THRU WITH COMBINED VOICE/DATA,

AUDIO/VIDEO AND POWER.

X = A, B, C... FLOOR BOX TYPE. N'S ARE DESCRIBED

ABOVE.

P

3/4" PLYWOOD BACKBOARD. BY

IDF - 2 POST RACK

IDF - 4 POST RACK

TELECOMM PANEL

1.

ALL CABLE TRAY, CONDUITS AND BOXES SHOWN ARE IN CONTRACT BY THE

ELECTRICAL INSTALLER. J-HOOKS AND LADDER RACKS BY SCS INSTALLER.

2.

STRUCTURED CABLING SYSTEM BY CABLING INSTALLER.

3.

ALL DOUBLE DOORS ARE TO RECEIVE (1)

DOOR POSITION SWITCH ON EACH

DOOR LEAF AND SHALL REPORT AS ONE

ALARM POINT.

1.

2.

FIBER CCTV LOCATION WHICH EXCEEDS 3000 FEET SHALL BE EQUIPPED WITH 2

FIBER CONNECTIONS 1 VIDEO, 1 DATA

3.

A. THE MAXIMUM PULLING TENSION SHALL NOT EXCEED 25 POUNDS TO

AVOID STRETCHING THE CONDUCTORS.

THE MINIMUM BENDING RADIUS OF THE CABLE SHALL NOT BE

LESS THAN 4X THE OUTSIDE DIAMETER OF THE CABLE.

B.

THE CABLE SHALL BE INSTALLED WITHOUT KINKS OR TWISTS AND THE

APPLICATION OF CABLE TIES SHALL NOT DEFORM THE CABLE BUNDLE.

C.

D. STRIP BACK ONLY AS MUCH CABLE JACKET AS IS REQUIRED TO

TERMINATE THE CABLE. CABLE PAIRS SHALL NOT BE UNTWISTED

MORE THAN 1/2 INCH.

4.

5.

6.

7.

ALL 120V POWER WIRING SHALL BE INSTALLED IN A SEPARATE CONDUIT.

ALL POWER CIRCUITS, 120VAC AND 24VAC, SHALL INCLUDE AN EQUIPMENT

GROUNDING CONDUCTOR WHICH IS EQUAL IN SIZE TO THE PHASE AND

NEUTRAL CONDUCTORS.

ALL CONDUIT ABOVE GRADE SHALL BE METALLIC, ALL CONDUIT BELOW GRADE

SHALL BE PVC UNLESS OTHERWISE NOTED ON DRAWINGS.

ALL CARD READERS AND KEYPADS DEDICATED FOR ELEVATOR FLOOR

SELECTION CONTROL ARE SHOWN INSIDE THE ELEVATOR CAB ON THE

LOWEST LEVEL FLOOR PLAN TO WHICH THE ELEVATOR

TRAVELS.

ALL CONDUIT, WIRING, AND ASSOCIATED BACK BOXES SHALL BE FULLY

CONCEALED WITHIN WALLS, FLOORS, AND CEILINGS.

INSTALLATION OF UTP CABLE SHALL BE IN ACCORDANCE WITH

EIA/TIA GUIDELINES. CABLE INSTALLATION AND TERMINATIONS THAT

DO NOT COMPLY SHALL BE REPLACED BY THE INSTALLER.

8.

INSTALLATION OF FIBER OPTIC CABLES SHALL BE IN ACCORDANCE

WITH EIA/TIA GUIDELINES. CABLE INSTALLATION AND TERMINATIONS

THAT DO NOT COMPLY SHALL BE REPLACED BY THE INSTALLER.

9.

A. THE BEND RADIUS FOR INTRABUILDING 2 AND 4-FIBER

HORIZONTAL OPTICAL FIBER CABLE SHALL NOT BE LESS THAN 1

INCH UNDER NO-LOAD CONDITIONS. WHEN UNDER A MAXIMUM

TENSILE LOAD OF 50 LBF, THE BEND RADIUS SHALL NOT BE LESS

THAN 2 INCHES.

B. THE BEND RADIUS FOR INTRABUILDING OPTICAL FIBER BACKBONE

SHALL NOT BE LESS THAN THAT RECOMMENDED BY THE

MANUFACTURER IF NO RECOMMENDATION IS KNOWN, THEN THE

APPLIED BEND RADIUS SHALL NOT BE LESS THAN 10 TIMES THE

CABLE OUTSIDE DIAMETER

UNDER NO-LOAD CONDITIONS AND NOT LESS THAN 15 TIMES THE

CABLE OUTSIDE DIAMETER WHEN THE CABLE IS UNDER TENSILE

LOAD.THE BEND RADIUS FOR INTER BUILDING (OSP) OPTICAL FIBER BACKBONE

SHALL NOT BE LESS THAN THAT RECOMMENDED BY THE MANUFACTURER

IF NO RECOMMENDATION IS KNOWN, THEN THE APPLIED BEND RADIUS

SHALL NOT BE LESS THAN 10 TIMES THE CABLE OUTSIDE DIAMETER NO-

LOAD CONDITIONS AND NOT LESS THAN 20 TIMES THE CABLE OUTSIDE

DIAMETER WHEN THE CABLE IS UNDER A TENSILE LOAD UP TO THE RATING

OF THE CABLE, USUALLY 600 LBF.

C.

10. COORDINATE LOCATION OF ALL FIRE RATED PENETRATIONS PRIOR TO

PROCEEDING WITH INSTALLATION. ALL PENETRATIONS THROUGH FIRE

RATED BARRIERS SHALL BE COMPLETELY SEALED WITH APPROPRIATE

FIRE STOP MATERIAL IN ACCORDANCE WITH NFPA AND FIRE AUTHORITY

HAVING

JURISDICTION.

ALL CABLES SHALL BE SUITABLE TO THE ENVIRONMENT TO WHERE THEY WILL

BE INSTALLED.

NOTES:

ALL RACEWAYS AND BOXES SHOWN ARE IN CONTRACT

BY THE ELECTRICAL INSTALLER.

1.

AUDIO/VIDEO DEVICES AND EQUIPMENT BY THE

AUDIO/VIDEO INSTALLER.

2.

NOTES:

INSTALLER TO REMOVE ALL EXISTING SECURITY

CABLES AND EQUIPMENT NOT TO BE REUSED.

ALL EXISTING EQUIPMENT WILL BE RETURNED

TO THE OWNER.

1. ALL RACEWAYS AND BOXES SHOWN ARE IN

CONTRACT BY THE ELECTRICAL INSTALLER.

2. SECURITY DEVICES AND EQUIPMENT BY

SECURITY INSTALLER.

3.

CEILING MOUNTED DOCUMENT CAMERA

X = A, B, C... INTERFACE TYPE.

X

ASSISTED LISTENING TRANSMITTER

TOUCH SCREEN AUDIO/VIDEO CONTROL

WALL MOUNTED TOUCH SCREEN AUDIO/VIDEO

CONTROL

Y

WALL MOUNTED SPEAKER

x DENOTES TYPE y DENOTES ZONE

NO ZONE DENOTES LOCAL AUDIO/VIDEO SYSTEM

Y

SPEAKER - DEMOLITION PLAN

VOLUME CONTROL. PROVIDE 3/4" CONDUIT

STUB-UP ABOVE CEILING AND SINGLE

STANDARD ELECTRICAL BOX

AT 52" ABOVE FINISHED FLOOR

CEILING MOUNTED MICROPHONE OUTLET

x DENOTES TYPE y DENOTES ZONE

MX

Y

MX WALL MOUNTED MICROPHONE

x DENOTES TYPE y DENOTES ZONE

NO ZONE DENOTES LOCAL AUDIO/VIDEO SYSTEM

Y

MICROPHONE - DEMOLITION PLAN

SATELLITE DISHSD

CALL STATION

SEE PODIUM DETAILS

CS

IK

AS

DURESS BUTTON WALL MOUNTED

X x Y MOTORIZED PROJECTION SCREEN, SIZE

SPECIFIED ON PLANS

XNNN

XNNN

XNNN

D

MX SURFACE MOUNTED MICROPHONE

x DENOTES TYPE y DENOTES ZONE

NO ZONE DENOTES LOCAL AUDIO/VIDEO SYSTEM

Y

ALL INDOOR CONDUITS N0 LARGER THAN 1" SHOWN ON THE GROUND FLOOR

SHALL BE INSTALLED EMBEDDED IN THE SLAB. CONDUITS SHALL BE KEPT DRY

AND CLEAN PRIOR TO PULLING CABLES.

ANYTHING NOT DESIGNATED AS ROUGH-IN AND SUPPORT RESPONSIBILITY

ON THESE DRAWINGS IS IN THE SYSTEM INSTALLER SCOPE OF WORK.

INTERCOM & PAGING SYSTEM

SX

SX

CEILING MOUNTED SPEAKER

x DENOTES TYPE y DENOTES ZONE

Y

WALL MOUNTED SPEAKER

x DENOTES TYPE y DENOTES ZONE

NO ZONE DENOTES LOCAL AUDIO/VIDEO SYSTEM

Y

ADMINISTRATIVE PHONEAP

HANDSETHS

11. ALL DELAYED EGRESS LOCKS AND MAGNETIC LOCKS, SHALL

RECEIVE A FIRE ALARM RELAY TO RELEASE THE DOOR UPON ALARM

AS REQUIRED BY CODE.

SEE DETAIL SHEETS FOR DEVICE MOUNTING REQUIREMENTS AND ADDITIONAL

INFORMATION.

THE DESIGNATION "D.H.C." SHALL DENOTE "DOOR HARDWARE INSTALLER".14.

IN ELECTRICAL AND MECHANICAL ROOMS, CONDUIT FOR LOW VOLTAGE

OUTLETS SHALL BE EXTENDED TO ACCESSIBLE CEILING OUTSIDE OF THE ROOM.

X

DETENTION LOCKDL

DOOR INTERLOCKDI

INTERCOM SUBSTATION

SPEAKER PHONE

16.

17.

18.

19.

20.

21.

22.

23.

24.

25.

26.

THE DESIGNATION "O.F.C.I." SHALL DENOTE ITEMS WHICH ARE FURNISHED

BY THE OWNER AND INSTALLED BY THE CONTRACTOR.

15.

M

S

DPS

BMS

CR

KP

CK

HS

BR

EL

EM

ES

ML

PE

IS

SP

D

MI

M

G

R

PC

S

AV

ALT

TS

TS

VC

DIVISION 27

DIVISION 27

DIVISION 26.

DETENTION DOOR INTERLOCKI

DIVISION 28

CABLE TRAY FOR HORIZONTAL

CABLING.

DIVISION 26

DIVISION 27

DIVISION 27

DIVISION 27

DIVISION 26

N

XX"

N = FACEPLATE CONNECTIVITY AND MOUNTING

TYPE, SEE DETAILS FOR INFORMATION

(TYPE 1,2,3, ETC.)

MONITOR SIZE IF APPLICABLE, SEE DETAILS

FOR INFORMATION

TV

AUDIO VISUAL INPUT/OUTPUT -SURFACE OR

FLOOR BOX MOUNTED WITH ADJACENT

DEDICATED DUPLEX RECEPTACLE BY

X = TYPE (A, B, C, ETC.) SEE DETAILS FOR

ADDITIONAL INFORMATION

X

AV

DIVISION 26

TELEVISION/MONITOR OUTLET, SEE DETAILS

FOR MOUNTING HEIGHT

SECURITY CAMERA EXTERIOR POLECP

PRESS CONNECTION PANEL, SEE DETAILS FOR

ADDITIONAL INFORMATION

PR

SECURITY SYSTEM NOTES

INDICATES WALL MOUNT

INDICATES WALL MOUNT

SECURITY CAMERA NETWORK OUTLET. COORDINATE

EXACT LOCATION OF OUTLET WITH OWNER PRIOR TO

ROUGH IN.

N = # OF DATA JACKS. MAXIMUM CABLE LENGTH 262 FT

CN

360 DEGREE CAMERA

MON

CMON

PAITENT MONITORING OUTLET - (1) CAT6

CENTRAL MONITOR OUTLET - (4) CAT6

CAT6

CAT6

CAT6

TECHNOLOGY DRAWING INDEX

SHEET DESCRIPTION ISSUED

T-TJ-00 GENERAL TECHNOLOGY INFORMATION Yes

T-TD-01 PARTIAL THIRD FLOOR PLAN - PART A - TECHNOLOGY DEMO Yes

T-TD-02 PARTIAL THIRD FLOOR PLAN - PART B - TECHNOLOGY DEMO Yes

T-TD-03 PARTIAL THIRD FLOOR PLAN - PART C - TECHNOLOGY DEMO Yes

T-TJ-01 PARTIAL THIRD FLOOR PLAN - PART A - TECHNOLOGY NEW WORK Yes

T-TJ-02 PARTIAL THIRD FLOOR PLAN - PART B - TECHNOLOGY NEW WORK Yes

T-TJ-03 PARTIAL THIRD FLOOR PLAN - PART C - TECHNOLOGY NEW WORK Yes

T-TJ-04 TECHNOLOGY - ENLARGED ROOMS Yes

T-TJ-06 TECHNOLOGY - DETAILS Yes

T-TJ-07 TECHNOLOGY - DETAILS Yes

T-TJ-08 TECHNOLOGY - RISER Yes

GI 05-01 PHASING PLANS Yes

No. Date Description

X3 X3

X4

X9

X10

X11

X12

X13

X14

XH XI XJ

XK

XL XM XN XO

XP

XQ XR XS

X6.1

X7.1

X12.1

X12.2 X12.3

X8

X5

X6

X7

M A

T C

H L

IN

E

P A

R T

A

M A

T C

H L

IN

E

P A

R T

A

M A

T C

H L

IN

E

P A

R T

B

M A

T C

H L

IN

E

P A

R T

B

M A

T C

H L

IN

E

P A

R T

C

M A

T C

H L

IN

E

P A

R T

A

M A

T C

H L

IN

E

P A

R T

C

M A

T C

H L

IN

E

P A

R T

A

EXISTING PA

EXISTING CATV

EXISTING RISERS TO REMAIN

EXISTING FIBER, CATV AND PA RISER TO BE REROUTED

TO NEW DATA ROOM AND NEW COMM ROOM.

EXISTING TELE 308

EXISTING TELE 343

EXISTING PA TO BE ROUTED THROUGH TELE

CHASE 308 AS PART OF WARD 1A PROJECT.

CATV CABLE AND FIBER RISERS FOR THE 4TH FLOOR ARE TO BE

REROUTED UP EXISTING RISER B1-308 AS PART OF WARD 1A PROJECT.

12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554

©Copyright 2023

TLC No.:

www.tlc-engineers.com

119437

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Dwg.

PROJECT TEAM:

Office of

Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

Department of Veterans Affairs

KEYPLAN

MURFREESBORO, TN

615.370.8500

615.370.8530 hfrdesign.com

214 Centerview Drive Suite 300 Brentwood, TN 37027

BLDG 2

BLDG 1

BLDG 9

Phase

FULLY SPRINKLERED

C R e v it

L o c a ls \1

-T E

C H

-V A

M C

W a rd

B

R ja c o b .k e ls h e im e r.

rv t

/1

/2

:3

:1

A

M

06-13-2023

626A4-19-101

T-TD-01

AE RENOVATE WARD 1B

PARTIAL THIRD FLOOR PLAN - PART A -

TECHNOLOGY DEMO

JAK

HFR Project No: 2019056

100% CONSTRUCTION

DOCUMENTS

3/16" = 1'-0"

1 PARTIAL THIRD FLOOR PLAN - PART A - DEMO

DEMOLITION GENERAL NOTES:

1. CONTRACTOR TO REMOVE EXISTING CEILING MOUNTED AV EQUIPMENT AND TURN OVER TO VA.

2. REMOVE AND TURN OVER TO VA ALL EXISTING WIRELESS ACCESS POINTS AND PUBLIC ADDRESS SPEAKERS.

3. REMOVE ALL EXISTING DATA CABLING.

4. REMOVE AND TURN OVER TO VA ALL NURSE CALL HEAD END EQUIPMENT.

X1X1

X2 X2

X3 X3

X4

X9

X10

X11

X0 X0

XB XC XD XE XF XG XH XI XJ

XK

X6.1

X7.1

X12.2 X12.3

X8

XA

X5

X6

X7

M A

T C

H L

IN

E

P A

R T

A

M A

T C

H L

IN

E

P A

R T

B

DEMO EXISTING TELCO TERM

EXISTING TELCO RISER TO BE REROUTED

THROUGH ELECTRICAL ROOM B1-352.

EXISTING TELE 350

CATV CABLE RISERS FOR THE 4TH FLOOR ARE TO BE REROUTED

UP EXISTING RISER B1-308 AS PART OF WARD 1A PROJECT.

12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554

©Copyright 2023

TLC No.:

www.tlc-engineers.com

119437

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Dwg.

PROJECT TEAM:

Office of

Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

Department of Veterans Affairs

KEYPLAN

MURFREESBORO, TN

615.370.8500

615.370.8530 hfrdesign.com

214 Centerview Drive Suite 300 Brentwood, TN 37027

BLDG 2

BLDG 1

BLDG 9

Phase

FULLY SPRINKLERED

C R e v it

L o c a ls \1

-T E

C H

-V A

M C

W a rd

B

R ja c o b .k e ls h e im e r.

rv t

/1

/2

:3

:1

A

M

06-13-2023

626A4-19-101

T-TD-02

AE RENOVATE WARD 1B

PARTIAL THIRD FLOOR PLAN - PART B -

TECHNOLOGY DEMO

JAK

HFR Project No: 2019056

100% CONSTRUCTION

DOCUMENTS

3/16" = 1'-0"

1 PARTIAL THIRD FLOOR PLAN - PART B - DEMO

DEMOLITION GENERAL NOTES:

1. CONTRACTOR TO REMOVE EXISTING CEILING MOUNTED AV EQUIPMENT AND TURN OVER TO VA.

2. REMOVE AND TURN OVER TO VA ALL EXISTING WIRELESS ACCESS POINTS AND PUBLIC ADDRESS SPEAKERS.

3. REMOVE ALL EXISTING DATA CABLING.

X1X1

X2 X2

X3 X3

X4

X9

X10

X11

X0 X0

XQ XR XS XT XU XV XW XX XY

X6.1

X7.1

X12.2

XZ

X8

X5

X6

X7

M A

T C

H L

IN

E

P A

R T

C

M A

T C

H L

IN

E

P A

R T

A

DEMO EXISTING

NURSE CALL

EXISTING

TELE 335

12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554

©Copyright 2023

TLC No.:

www.tlc-engineers.com

119437

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Dwg.

PROJECT TEAM:

Office of

Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

Department of Veterans Affairs

KEYPLAN

MURFREESBORO, TN

615.370.8500

615.370.8530 hfrdesign.com

214 Centerview Drive Suite 300 Brentwood, TN 37027

BLDG 2

BLDG 1

BLDG 9

Phase

FULLY SPRINKLERED

C R e v it

L o c a ls \1

-T E

C H

-V A

M C

W a rd

B

R ja c o b .k e ls h e im e r.

rv t

/1

/2

:3

:2

A

M

06-13-2023

626A4-19-101

T-TD-03

AE RENOVATE WARD 1B

PARTIAL THIRD FLOOR PLAN - PART C -

TECHNOLOGY DEMO

JAK

HFR Project No: 2019056

100% CONSTRUCTION

DOCUMENTS

3/16" = 1'-0"

1 PARTIAL THIRD FLOOR PLAN - PART C - DEMO

DEMOLITION GENERAL NOTES:

1. CONTRACTOR TO REMOVE EXISTING CEILING MOUNTED AV EQUIPMENT AND TURN OVER TO VA.

2. REMOVE AND TURN OVER TO VA ALL EXISTING WIRELESS ACCESS POINTS AND PUBLIC ADDRESS SPEAKERS.

3. REMOVE ALL EXISTING DATA CABLING.

CR CR

C R

R R

R

T V

T V

T V

T V

S1

S1

S1

S1

S1

S1 S1

S1

S1

S1

S1

S1 S1

S1

S1

S1

S1

ES ES

ES

DPS

D P

S

D P

S

S1

S1

T V

CR

ES

D P

S

R

X3 X3

X4 X4

X9 X9X11

X12

X13

X14

XH XI XJ

XK

XL XM XN XO

XP

XQ XR XS

X6.1 X6.1

X7.1 X7.1

X12.1

X12.2

X12.3

X8 X8

X5 X5

X6 X6

X7 X7

PANTRY

B338A

SERVING KITCHEN

B338

DINING/DAY ROOM

B337

RETHERM

B361

LAUNDRY

B359 CLEAN SUPPLY

B363

CHUTE

B360

NURSE STATION

B336

EQUIP STORAGE

B301

INPATIENT REHAB

B303

STAFF LOUNGE

B304

STAFF LOCKERS

B304B

CHAIR ALCOVE

B305

FAM. LOUNGE

B307

CONSULT

B310

FAM/PUB. TLT.

B308

REC.THR. STOR.

B309

TEAM ROOM

B332

DATA

B335

PAT. TLT.

B331A

PRIVATE ROOM

B331

CHARGE NURSE

B336A

SOCIAL WORKER

B302

DIRTY

B362

NURSE MANAGER

B333

MEDS

B336B

COMM

B334

STAFF TLT.

B304A

CORRIDOR

B300

CORRIDOR

B370

VENDING

B300A

EXISTING RISER

B370A

ELEV.

ELEV.

STAIR 1

STAIR 1

B306

WAP

S 2

WAP

S 2

WAP

S 2

WAP

S 2

J-HOOK PATHWAY

J-HOOK PATHWAY

C F 2

F 1

F 3

F 3

F 1

F 1

F 1

W F 1

W F 1

F 2

F 2

F 2 F 2

F 2

F 2

?W F 1

F 4 F 4 F 4F 4

F 4 F 4

F 4 F 4

F 2

F 2

F 2

F 2

360 DEGREE CAMERAS

360 DEGREE CAMERA

F 4

F 2

F 1

F 2

F 2

F 2 F 2

@ 66" A.F.F. CENTERED BEHIND DISPLAY.

SEE DETAIL 5 ON SHEET T-TJ-07

@ 66" A.F.F. CENTERED

BEHIND DISPLAY. SEE

DETAIL 5 ON SHEET T-TJ-07

@ 74" A.F.F. CENTERED BEHIND DISPLAY.

SEE DETAIL 5 ON SHEET T-TJ-07

4" HILTI SLEEVES

AS REQUIRED

J-HOOK PATHWAY

J-HOOK PATHWAY

?WAP

S 2

?WAP

S 2

?WAP

S 2

?WAP

S 2

F 2

F 2 F 2

F 4 F 4

F 1

F 1

F 2

F 1 F 1 1 1

J-HOOK PATHWAY

J-HOOK PATHWAY

F 1

DATA FOR OWNER

PROVIDED LEAF

SYSTEM +80" A.F.F.

12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554

©Copyright 2023

TLC No.:

www.tlc-engineers.com

119437

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Dwg.

PROJECT TEAM:

Office of

Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

Department of Veterans Affairs

KEYPLAN

MURFREESBORO, TN

615.370.8500

615.370.8530 hfrdesign.com

214 Centerview Drive Suite 300 Brentwood, TN 37027

BLDG 2

BLDG 1

BLDG 9

Phase

FULLY SPRINKLERED

C R e v it

L o c a ls \1

-T E

C H

-V A

M C

W a rd

B

R ja c o b .k e ls h e im e r.

rv t

/1

/2

:3

:2

A

M

06-13-2023

626A4-19-101

T-TJ-01

AE RENOVATE WARD 1B

PARTIAL THIRD FLOOR PLAN - PART A -

TECHNOLOGY NEW WORK

JAK

HFR Project No: 2019056

100% CONSTRUCTION

DOCUMENTS

3/16" = 1'-0"

1 PARTIAL THIRD FLOOR PLAN - PART A

TECHNOLOGY KEYED NOTES

DATA OUTLET FOR REESE MONITORING SYSTEM TO BE LOCATED ABOVE DOOR

AND CABLED BACK TO NEAREST DATA ROOM. COORDINATE LOCATION OF

TERMINATION IN DATA ROOM WITH OWNER IT.

T V

S1 S1

S1

S1S1

S1

S1S1

S1

S1

S1

S1

S1

S1

T

VT

V

T V

T V

TV

TV

TV

TV

PRIVATE ROOM

B349

PRIVATE ROOM

B348

ISO ROOM

B347

CLEAN UTILITY

B346

ELEC.

B344

EQUIP STOR.

B343

CLEAN LINEN

B351

SOILED HOLD

B352

BARI PRIVATE

ROOM

B355

BARI. TLT.

B355A

NOURISHMENT

B356

SUB NS.

B358

HAC

B357

STAFF TLT.

B358A

PANTRY

B338A

SERVING

KITCHEN

B338

DINING/DAY

ROOM

B337

RETHERM

B361

LAUNDRY

B359

CLEAN SUPPLY

B363

CHUTE

B360

X1X1

X2 X2

X3 X3

X4

X9

X10 X10

X11

X0 X0

XB XC XD XE XF XG XH XI XJ

XK

X6.1

X7.1

X12.2

X12.3

X8

XA

X5

X6

X7

CORRIDOR

B374

CORRIDOR

B375

TEAM WORK

B341

DIRTY

B362

ANTE

B347A

PRIVATE ROOM

B354

PRIVATE ROOM

B353

PAT. TLT.

B354A

PAT. TLT.

B353A

PRIVATE ROOM

B339

PRIVATE ROOM

B340

D N

PRIVATE ROOM

B350

PAT. TLT.

B349A

PAT. TLT.

B340A PAT. TLT.

B339A

PAT. TLT.

B350A

PAT. TLT.

B348A

PAT. TLT.

B347B

CORRIDOR

B376

STAIR 2

CHASE

B338B

3'-0"

STAIR 2

B345

MON

J-HOOK PATHWAY

J-HOOK PATHWAY

WAP

S 2

WAP

S 2

WAP

S 2

WAP

S 2

WAP

S 2

F 2

F 2

F 1

F 2

F 2F 2

F 2

F 2

F 2

F 2 F 2

F 2

F 2 F 4F 4

F 2

F 4

F 4

F 4 F 4

W F 1

360 DEGREE CAMERA

360 DEGREE CAMERA

360 DEGREE CAMERA

F 2

F 2

MON

F 2

MONMON

MON

F 2

F 2

F 2

F 2 F 2

F 2F 2

F 2 F 2

MON

F 2

F 2F 2

MON

F 2

F 2F 2

MON

F 2

F 2F 2

F 2 F 2MON

F 2

F 1

F 1

F 1

F 1

F 1F 1 F 1 F 1

COORDINATE EXACT MOUNTING HEIGHT

OF ALL DEVICES IN PATIENT ROOMS

WITH ARCHITECTURAL DRAWINGS.

(TYP.)

J-HOOK PATHWAY

?WAP

S 2

?WAP

S 2

?WAP

S 2

?WAP

S 2

?WAP

S 2

?WAP

S 2

F 1

F 1F 1

F 1 2

F 1

DATA FOR OWNER

PROVIDED LEAF

SYSTEM +80" A.F.F.

F 1

DATA FOR OWNER

PROVIDED LEAF

SYSTEM +80" A.F.F.

F 1

12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554

©Copyright 2023

TLC No.:

www.tlc-engineers.com

119437

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Dwg.

PROJECT TEAM:

Office of

Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

Department of Veterans Affairs

KEYPLAN

MURFREESBORO, TN

615.370.8500

615.370.8530 hfrdesign.com

214 Centerview Drive Suite 300 Brentwood, TN 37027

BLDG 2

BLDG 1

BLDG 9

Phase

FULLY SPRINKLERED

C R e v it

L o c a ls \1

-T E

C H

-V A

M C

W a rd

B

R ja c o b .k e ls h e im e r.

rv t

/1

/2

:3

:2

A

M

06-13-2023

626A4-19-101

T-TJ-02

AE RENOVATE WARD 1B

PARTIAL THIRD FLOOR PLAN - PART B -

TECHNOLOGY NEW WORK

JAK

HFR Project No: 2019056

100% CONSTRUCTION

DOCUMENTS

3/16" = 1'-0"

1 PARTIAL THIRD FLOOR PLAN - PART B

TECHNOLOGY KEYED NOTES

DATA OUTLET FOR OWNER PROVIDED REESE MONITORING SYSTEM TO BE LOCATED

ABOVE DOOR AND CABLED BACK TO NEAREST DATA ROOM. COORDINATE LOCATION

OF TERMINATION IN DATA ROOM WITH OWNER IT.

DATA OUTLET FOR ALEX DISPENSER UNIT SYSTEM AT 81" A.F.F. TO THE BOTTOM.

COORDINATE EXACT LOCATION WITH ARCHITECTURAL DRAWINGS PRIOR TO ROUGH IN.

COORDINATE EXACT LOCATION OF DATA OUTLETS ON HEADWALL & FOOTWALL WITH

ARCHITECTURAL DRAWINGS PRIOR TO ROUGH IN.

S1

S1

S1

S1 S1

S1

S1 S1

S1

S1

S1

S1

S1

T V

T V

T V

T V

T V

TV

TV

TV

TV

TEAM ROOM

B332

REC.THR. STOR.

B309

CONSULT

B310

FAM/PUB. TLT.

B308

PRIVATE ROOM

B331

PAT. TLT.

B331A

PAT. TLT.

B330A

PRIVATE ROOM

B330

TEAM WORK

ROOM

B329

WOUND CART

STOR.

B311B

ST. TLT.

B311A

CLEAN LINEN

B318

BARI PRIVATE

ROOM

B313

BARIATRIC

PATIENT TOILET

B313A

NOURISH

B312

CLEAN UTILITY

B320

ELEC.

B326

SOILED HOLD

B327

HAC.

B325

ISO ROOM

B321

PAT. TLT.

B322A

SUB N.S.

B311

X1X1

X2 X2

X3 X3

X4

X9

X10

X0 X0

XQ XR XS XT XU XV XW XX XY XZ

X8

X5

X6

X7

NURSE

MANAGER

B333

PAT. TLT.

B321B

PRIVATE ROOM

B322

EMPTY CYL.

STOR.

B317

FULL CYL. STOR.

B316

PAT. TLT.

B315A PAT. TLT.

B314A

ANTE

B321A

CORRIDOR

B371

CORRIDOR

B372

CORRIDOR

B373

PRIVATE ROOM

B314

PRIVATE ROOM

B315

PRIVATE ROOM

B324

PRIVATE ROOM

B323

PAT. TLT.

B323A

PAT. TLT.

B324A

STAIR 3

STAIR 3

B319

CHASE

B328

J-HOOK PATHWAY

J-HOOK PATHWAY

WAP

S 2

WAP

S 2

WAP

S 2

WAP

S 2

F 2

F 2

F 2F 2

F 2

F 2

F 2

F 2F 2 F 4

F 2

F 2

F 2

F 2

F 2

F 4

F 4

F 4

360 DEGREE CAMERA

360 DEGREE CAMERA

360 DEGREE CAMERA

F 2

F 2

F 2

MON

F 1

MON

F 2

F 2

F 2

F 2

MON

F 2

F 2

MON

F 2

F 2 F 2

F 2

MON

F 2

F 2

MONF 2 F 2

F 2 MON F 2

F 2 F 2MON

F 2F 2 MON

F 1

F 1

F 1

F 1

F 1

F 1F 1 F 1

F 2

F 2

F 2

F 2

F 2 F 2 F 2

F 2

COORDINATE EXACT MOUNTING HEIGHT OF ALL DEVICES

IN PATIENT ROOMS WITH ARCHITECTURAL DRAWINGS.

(TYP.)

J-HOOK PATHWAY

J-HOOK PATHWAY

?WAP

S 2

?WAP

S 2

?WAP

S 2

?WAP

S 2

?WAP

S 2

?WAP

S 2

?WAP

S 2

F 4 F 4

F 1

F 1

F 1

DATA FOR OWNER

PROVIDED LEAF

SYSTEM +80" A.F.F.

F 1

F 1

DATA FOR OWNER

PROVIDED LEAF

SYSTEM +80" A.F.F.

F 1

12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554

©Copyright 2023

TLC No.:

www.tlc-engineers.com

119437

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Dwg.

PROJECT TEAM:

Office of

Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

Department of Veterans Affairs

KEYPLAN

MURFREESBORO, TN

615.370.8500

615.370.8530 hfrdesign.com

214 Centerview Drive Suite 300 Brentwood, TN 37027

BLDG 2

BLDG 1

BLDG 9

Phase

FULLY SPRINKLERED

C R e v it

L o c a ls \1

-T E

C H

-V A

M C

W a rd

B

R ja c o b .k e ls h e im e r.

rv t

/1

/2

:3

:2

A

M

06-13-2023

626A4-19-101

T-TJ-03

AE RENOVATE WARD 1B

PARTIAL THIRD FLOOR PLAN - PART C -

TECHNOLOGY NEW WORK

JAK

HFR Project No: 2019056

100% CONSTRUCTION

DOCUMENTS

3/16" = 1'-0"

1 PARTIAL THIRD FLOOR PLAN - PART C

TECHNOLOGY KEYED NOTES

DATA OUTLET FOR OWNER PROVIDED REESE MONITORING SYSTEM TO BE LOCATED

ABOVE DOOR AND CABLED BACK TO NEAREST DATA ROOM. COORDINATE LOCATION

OF TERMINATION IN DATA ROOM WITH OWNER IT.

DATA OUTLET FOR ALEX DISPENSER UNIT SYSTEM AT 81" A.F.F. TO THE BOTTOM.

COORDINATE EXACT LOCATION WITH ARCHITECTURAL DRAWINGS PRIOR TO ROUGH IN.

COORDINATE EXACT LOCATION OF DATA OUTLETS ON HEADWALL & FOOTWALL WITH

ARCHITECTURAL DRAWINGS PRIOR TO ROUGH IN.

ELEC PANEL

TELEVISION AMP & TAPS. CONNECT TO

HEAD END LOCATED IN EXISTING COMM

ROOM 106 ON FIRST FLOOR - BUILDING 1

DDC

R A

D

IO

/D A

S

INTERCOM ABOVE PA

PUBLIC ADDRESS BELOW INTERCOM.

CONNECT TO HEAD END LOCATED IN EXISTING

COMM ROOM 106 ON FIRST FLOOR - BUILDING 1

SECURITY

NURSE CALL

GROUND

BUS BAR

4" HILTI SLEEVES

PLYWOOD BACKBOARD

COMM

B334

77 SF

2-POST

RACK

2-POST

RACK

4" HILTI SLEEVES

DATA OUTLET ABOVE DOOR FOR OWNER

PROVIDED REESE MONITORING SYSTEM

DATA

B335

GROUND BUS BAR

PLYWOOD BACKBOARD

TELECO TERM. FIBER AND

COPPER TERMINATIONS.

CONNECT TO BUILDING MDF

4" HILTI SLEEVES

4" HILTI SLEEVES

DATA OUTLET ABOVE DOOR FOR OWNER

PROVIDED REESE MONITORING SYSTEM

FIXED CAMERA, PAN /

TILT / ZOOM, PASSIVE

INFRARED CAMERA -

DUAL TECHNOLOGY

45RU, 30"D x 7'H x 23.75"W

NETWORK EQUIPMENT

RACK. MIGHTY MO 20

CABLE MANAGEMENT RACK

WITH WHITE FINISH OR

APPROVED EQUAL.

6" WIDE VERTICAL CABLE

MANAGEMENT. WHITE

MM20 VERTICAL CABLE

MANAGEMENT "CAGE" OR

APPROVED EQUAL

PLYWOOD BACKBOARD

LADDER RACK

F1 DATA FOR REESE

MONITORING SYSTEM

NURSE CALL

PLYWOOD BACKBOARD

LADDER RACK

TELEVISION

INTERCOM

PUBLIC ADDRESS

DDC

SECURITY

SECURITY

PLYWOOD BACKBOARD

LADDER RACK

ELEC

PLYWOOD BACKBOARD

LADDER RACK

GROUND

BUS BAR

RADIO OR DAS

LADDER RACK

PLYWOOD BACKBOARD

F1 DATA FOR REESE

MONITORING SYSTEM

4" HILTI SLEEVES

LADDER RACK

PLYWOOD BACKBOARD

LADDER RACK

PLYWOOD

BACKBOARD

4" HILTI SLEEVES

TELECOM

LADDER RACK

PLYWOOD BACKBOARD

GROUND

BUS BAR

COMM

B334

77 SF

DATA

B335

WIRE MESH CABLE TRAY - MINIMUM SIZE

OF 4" X 12" WITH SECOND LEVEL OF

FIBER CHANNEL PATHWAY (4" x 4")

24"

12"

12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554

©Copyright 2023

TLC No.:

www.tlc-engineers.com

119437

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Dwg.

PROJECT TEAM:

Office of

Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

Department of Veterans Affairs

MURFREESBORO, TN

615.370.8500

615.370.8530 hfrdesign.com

214 Centerview Drive Suite 300 Brentwood, TN 37027

Phase

FULLY SPRINKLERED

C R e v it

L o c a ls \1

-T E

C H

-V A

M C

W a rd

B

R ja c o b .k e ls h e im e r.

rv t

/1

/2

:3

:3

A

M

06-13-2023

626A4-19-101

T-TJ-04

AE RENOVATE WARD 1BTECHNOLOGY - ENLARGED ROOMS

JAK

HFR Project No: 2019056

100% CONSTRUCTION

DOCUMENTS

3/8" = 1'-0"

1 ENLARGED COMM ROOM

3/8" = 1'-0"

2 ENLARGED DATA ROOM

COMM ROOM ELECTRICAL DESIGN BASIS

Circuit Volts Amps Type TYP Load Description

1 220V 30A EMER 50% RACK 1 - FIBER / PATCH

2 120V 20A EMER 50% RACK 2 - BIOMED

3 120V 20A EMER 50% SECURITY

5 120V 20A EMER 50% INTERCOM

6 120V 20A EMER 50% PUBLIC ADDRESS

7 120V 20A EMER 50% NURSE CALL

8 120V 20A EMER 25% RADIO / DAS

9 120V 20A EMER 25% TELEVISION

10 120V 20A ROUTINE 25% CONVIENCE OUTLETS

DATA ROOM ELECTRICAL DESIGN BASIS

Circuit Volts. Amps. Type. TYP. Load Description.

1 220V 30A EMER 50% RACK 1 - FIBER / PATCH

2 120V 20A EMER 50% TELCO TERM.

3 120V 20A ROUTINE 25% CONVIENCE OUTLETS

3/8" = 1'-0"

3 COMM NORTH ELEVATION

3/8" = 1'-0"

4 COMM SOUTH ELEVATION

3/8" = 1'-0"

5 COMM EAST ELEVATION

3/8" = 1'-0"

6 COMM WEST ELEVATION

3/8" = 1'-0"

7 DATA NORTH ELEVATION

3/8" = 1'-0"

8 DATA SOUTH ELEVATION

3/8" = 1'-0"

9 DATA EAST ELEVATION

3/8" = 1'-0"

10 DATA WEST ELEVATION

3/8" = 1'-0"

11 ENLARGED COMM ROOM LADDER RACK

3/8" = 1'-0"

12 ENLARGED DATA ROOM LADDER RACK

1. CAMERA SHALL BE SUPPORTED FROM THE

CEILING GRID SYSTEM, NOT THE CEILING TILE.

PROVIDE MOUNTING HARDWARE AS REQUIRED.

NOTES:

SUPPORT BOX

WALL MOUNTED BOX

WITH CAT6

CONNECTION

MODULE.

CAT6 UTP,

4 PAIR

CABLE

LAY IN CEILING TILE

CEILING TEE'S

GRID SUPPORT PROVIDED

BY SCS CONTRACTOR

CEILING TILE WIRE

CONCRETE

DECK ABOVE

WIRE SHALL BE SUPPORTED

FROM LOOP SUPPORTS

SECURE SECONDARY

SUPPORT CABLE FROM

BUILDING STRUCTURE

SECONDARY SUPPORT TAB

3/4" CONDUIT

2 GANG BACK BOX

FIN. FL.

COORDINATE WITH

MOUNTING BRACKET

RG6 COAX

CAT 6A F-TYPE ADAPTER

SINGLE GANG FACE PLATE FOR (2) MODULES

TV

2) RANDOMLY INSTALL J-HOOKS AT 3', 4' AND 5'

APART.

TREE SYSTEM IS FOR MAIN CORRIDOR PATHWAYS.

DOUBLE AND SINGLE TREES MAYBE USED IN

ROOMS. CABLE J-HOOK SYSTEM CAN BE SECURED

TO METAL STUDS, WHERE PERMISSIBLE.

NOTES:

CADDY CABLE J-HOOKS

CONCRETE ANCHOR ROOF DECK

BAR JOIST CLAMP

1)

CEILING

M

IN

M

A X

STRUCTURED CABLING

SECURITY,

CCTV, MISC.

NURSE CALL, PUBLIC

ADDRESS, CATV

PROVIDE DOUBLE-GANG BOX

WITH SINGLE GANG MUD RING

FOR READER. SEE FLOOR PLAN

FOR SPECIFIC TYPE AND PLACEMENT.

PROVIDE DOUBLE-GANG BOX

WITH SINGLE GANG MUD RING

FOR READER. SEE FLOOR PLAN

FOR SPECIFIC TYPE AND

PLACEMENT.

44" A.F.F.

6"

44" A.F.F.

6"

ELECTRIC STRIKE AND

ACCOMMODATING

HARDWARE

FINISHED CEILING FINISHED CEILING

MAGNETIC DOOR CONTACT

SWITCH EMBEDDED IN

DOOR & DOOR FRAME

FINISHED FLOOR

DOOR HARDWARE SHOWN FOR GRAPHICAL ILLISTRATION ONLY, REFERENCE DIVISION 8 HARDWARE

SCHEDULE AS NEEDED FOR ACTUAL HARDWARE SET.

3.

ALL CONDUIT SHALL BE 3/4" UNLESS OTHERWISE NOTED.2.

1.NOTES: CABLE TYPE AND SIZE MUST COMPLY WITH ALL ESTABLISHED REQUIREMENTS AND APPLICABLE CODES.

4" x 4" SQUARE J-BOX.

CABLE FOR COMMUNICATION

AND LOW VOLTAGE POWER

1" CONDUIT TO ACCESSIBLE CEILING

SPACE

UNSECURE SIDE SECURE SIDE

POWER

SUPPLY

PROVIDE

DOUBLE-GANG BOX

WITH SINGLE GANG

MUD RING

FOR READER. SEE

FLOOR PLAN

FOR SPECIFIC TYPE

AND PLACEMENT.

44" A.F.F.

6"

4" x 4" SQUARE J-BOX.

MAGNETIC DOOR

CONTACT

SWITCH EMBEDDED IN

DOOR & DOOR FRAME

ELECTRIC STRIKE

AND

ACCOMMODATING

HARDWARE

FINISHED FLOOR

FINISHED CEILING

DOOR HARDWARE SHOWN FOR GRAPHICAL ILLISTRATION ONLY, REFERENCE DIVISION 8 HARDWARE

SCHEDULE AS NEEDED FOR ACTUAL HARDWARE SET.

3.

ALL CONDUIT SHALL BE 3/4" UNLESS OTHERWISE NOTED.2.

1.NOTES: CABLE TYPE AND SIZE MUST COMPLY WITH ALL ESTABLISHED REQUIREMENTS AND APPLICABLE CODES.

CABLE FOR COMMUNICATION

AND LOW VOLTAGE POWER

1" CONDUIT TO ACCESSIBLE CEILING

SPACE

ELECTRIFIED HINGE

(PROVIDED BY DOOR

HARDWARE

INSTALLER)

2" x 4" J-BOX FLUSH MOUNTED

FOR EGRESS MOTION SENSOR.

ROOM #

PORT #

TR # - PP #

TELEPHONE WALL PLATE

(1) UTP 4 PAIR

CAT6A CABLE TO TR.

W F1

12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554

©Copyright 2023

TLC No.:

www.tlc-engineers.com

119437

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Dwg.

PROJECT TEAM:

Office of

Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

Department of Veterans Affairs

MURFREESBORO, TN

615.370.8500

615.370.8530 hfrdesign.com

214 Centerview Drive Suite 300 Brentwood, TN 37027

Phase

FULLY SPRINKLERED

C R e v it

L o c a ls \1

-T E

C H

-V A

M C

W a rd

B

R ja c o b .k e ls h e im e r.

rv t

/1

/2

:3

:3

A

M

06-13-2023

626A4-19-101

T-TJ-06

AE RENOVATE WARD 1BTECHNOLOGY - DETAILS

JAK

HFR Project No: 2019056

100% CONSTRUCTION

DOCUMENTS

No Scale

CCTV CAMERA INSTALLATION1 1

No Scale

TV OUTLET 2

No Scale

CABLE HANGER (MULTI J-HOOK) 3No Scale 5

SECURITY SINGLE DOOR - ELECTRIC STRIKE WITH CARD READERS

No Scale 6

SECURITY DOUBLE DOOR - ELECTRIC STRIKE WITH CARD READER AND REX

No Scale

WALL PHONE OUTLET - W/FI 4

LABEL

1 1/2" EMT CONDUIT

STUBBED TO THE

NEAREST J-HOOK

AND GROMMET

BLDG # - SECTION # - FLOOR # - JACKID #

F4

CAT6 DATA CABLE

CAT6 DATA CABLE

CAT6 VOICE CABLE

CAT6 DATA CABLE

BLUE FOR DATA

BLUE FOR DATA

BLUE FOR DATA

BLUE FOR PHONE/FAX

CAT6A DATA CABLE WITH BLUE KEYSTONE

CAT6A DATA CABLE WITH BLUE KEYSTONE

CAT6A VOICE CABLE WITH WHITE KEYSTONE

CAT6A DATA CABLE WITH BLUE KEYSTONE

MAX

5'

(2) CAT6 UTP TO COMM/DATA ROOM

NOTE:

WIRELESS ACCESS POINT AND

ANTENNA NOT IN CONTRACT.

WAP

S2

J-HOOK

ACCESSIBLE CEILING

COIL 15' SERVICE LOOP IN CEILING.

DETAIL NOTE:

COIL CABLE IN CEILING

GROUND BUS BAR

STANDOFF

RACKET

CPI 10622-000

INSULATOR

CPI 10622-012 OR EQUAL

ISOMETRIC ELEVATION

PROVIDE # 6 COPPER CABLE 2-HOLE

LUG CLAMP FOR CABLE

CONNECTION. (TYP)

PROVIDE GROUNDING

CONDUCTOR TO

BUILDINGS

STEEL PER NEC 250.66

PROVIDE GROUNDING CONDUCTOR TO

MAIN SERVICE GROUND POINT PER NEC

250.66

4"

FRONT VIEW

INSULATOR (TYPICAL)

CPI 10622-012 OR EQUAL

12"

PROVIDED BY ELECTRICAL INSTALLER.

2-HOLE LUG (TYP.)

INSULATOR MOUNTING BRACKET

(TYP.) CPI 10622-000

PROVIDE WHITE CORE BAKELITE NAMEPLATE

FASTENED TO A WALL/SURFACE BELOW

BUSBAR AT EACH FLOOR, WITH DESIGNATION

ENGRAVED THEREON IN 1/2" HIGH LETTERS.

TGB-XXX

GENERAL NOTES:

ALL HARDWARE (BOLTS, NUTS,

WASHERS, ETC.) SHALL BE SOLID

COPPER OR BRONZE. COPPER

PLATING SHALL NOT BE ACCEPTABLE.

BUSBAR SHALL BE 1/4" THICK

(MINIMUM).

INCREASE LENGTH OF BUSBAR, FOR

NUMBER OF CONNECTIONS, AS

REQUIRED

TO MAINTAIN CORRECT SPACING

BETWEEN LUGS.

1.

2.

3.

TV / MONITOR

1" CONDUIT TO ACCESSIBLE CEILING

A/V AND DATA JUNCTION

COORDINATE EXACT HEIGHT

WITH ARCHITECTURAL

PLANS AND SECTIONS

PRIOR TO ROUGH-IN.

FINISHED FLOOR

LABEL

1 1/2" EMT CONDUIT

STUBBED TO THE

NEAREST J-HOOK

AND GROMMET

BLDG # - SECTION # - FLOOR # - JACKID #

MON

CAT6 DATA CABLE

CAT6 DATA CABLE

CAT6 DATA CABLE

CAT6 DATA CABLE

ORANGE FOR DATA

ORANGE FOR DATA

ORANGE FOR DATA

ORANGE FOR DATA

CAT6A DATA CABLE WITH ORANGE KEYSTONE

CAT6A DATA CABLE WITH ORANGE KEYSTONE

CAT6A VOICE CABLE WITH ORANGE KEYSTONE

CAT6A DATA CABLE WITH ORANGE KEYSTONE

CMON

12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554

©Copyright 2023

TLC No.:

www.tlc-engineers.com

119437

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Dwg.

PROJECT TEAM:

Office of

Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

Department of Veterans Affairs

MURFREESBORO, TN

615.370.8500

615.370.8530 hfrdesign.com

214 Centerview Drive Suite 300 Brentwood, TN 37027

Phase

FULLY SPRINKLERED

C R e v it

L o c a ls \1

-T E

C H

-V A

M C

W a rd

B

R ja c o b .k e ls h e im e r.

rv t

/1

/2

:3

:3

A

M

06-13-2023

626A4-19-101

T-TJ-07

AE RENOVATE WARD 1BTECHNOLOGY - DETAILS

JAK

HFR Project No: 2019056

100% CONSTRUCTION

DOCUMENTS

No Scale

WALL MOUNTED OUTLET - FOUR PORT FACEPLATE 1

No Scale

WIRELESS ACCESS POINT (COILED IN CEILING) 2

No Scale

GROUND BUSBAR (TYPICAL FOR ALL TR'S) 3

No Scale

TV DETAIL 4

No Scale

WALL MOUNTED OUTLET - MON / CMON 5

FIRST FLOOR

SECOND FLOOR

EXISTING MDF

BUILDING 1

ROOM 129C

THIRD FLOOR

COMM

B1-314

DATA

B1-316

BUILDING 1

ROOM G44A

(12) STRANDS OF SINGLE MODE FIBER,

(24) STRANDS OF MULTI MODE FIBER

(12) STRANDS OF SINGLE MODE FIBER,

(24) STRANDS OF MULTI MODE FIBER,

50 PAIR COPPER

(12) STRANDS OF SINGLE MODE FIBER,

(24) STRANDS OF MULTI MODE FIBER,

50 PAIR COPPER

EXISTING RISER ROOM

12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554

©Copyright 2023

TLC No.:

www.tlc-engineers.com

119437

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Dwg.

PROJECT TEAM:

Office of

Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

Department of Veterans Affairs

MURFREESBORO, TN

615.370.8500

615.370.8530 hfrdesign.com

214 Centerview Drive Suite 300 Brentwood, TN 37027

Phase

FULLY SPRINKLERED

C R e v it

L o c a ls \1

-T E

C H

-V A

M C

W a rd

B

R ja c o b .k e ls h e im e r.

rv t

/1

/2

:3

:3

A

M

06-13-2023

626A4-19-101

T-TJ-08

AE RENOVATE WARD 1BTECHNOLOGY - RISER

JAK

HFR Project No: 2019056

100% CONSTRUCTION

DOCUMENTS

3" = 1'-0"

RISER

GI 05-01 - PHASING PLANS
T-TJ-00 - GENERAL TECHNOLOGY INFORMATION
T-TD-01 - PARTIAL THIRD FLOOR PLAN - PART A - TECHNOLOGY DEMO
T-TD-02 - PARTIAL THIRD FLOOR PLAN - PART B - TECHNOLOGY DEMO
T-TD-03 - PARTIAL THIRD FLOOR PLAN - PART C - TECHNOLOGY DEMO
T-TJ-01 - PARTIAL THIRD FLOOR PLAN - PART A - TECHNOLOGY NEW WORK
T-TJ-02 - PARTIAL THIRD FLOOR PLAN - PART B - TECHNOLOGY NEW WORK
T-TJ-03 - PARTIAL THIRD FLOOR PLAN - PART C - TECHNOLOGY NEW WORK
T-TJ-04 - TECHNOLOGY - ENLARGED ROOMS
T-TJ-06 - TECHNOLOGY - DETAILS
T-TJ-07 - TECHNOLOGY - DETAILS
T-TJ-08 - TECHNOLOGY - RISER

File details come from the government source that posted it. Updated .