- Z2DA--626A4-19-101 - Renovate Ward 1B at the Alvin C. York VA Medical Center, Murfreesboro, TN 37129
- Solicitation number
- 36C24923R0114
About this file
This package includes construction documents and specifications for the renovation of Ward 1B at the Alvin C. York VA Medical Center in Murfreesboro, Tennessee. The project involves upgrading fire protection systems on the third floor to include new sprinkler piping, heads, cabinets and related components. Work will be conducted in phases to maintain protection for occupied areas. Bidders are advised to carefully review drawings and notes detailing demolition of existing piping and installation of new systems. The solicitation provides relevant details including the requirement for a Tennessee-registered sprinkler contractor, coordination responsibilities, and design criteria.
View the file
Other files
Show all 48
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
CLEAN UTILITY
SOILED UT.
PT. ROOM
PT. ROOM
PT. ROOM
PT. ROOM
ELEC.
STAFF TLT.STAIR
PT. ISO ROOM
PT. ROOM
PT. ROOM
WORK RM
ANTE
OFFICE
RESIDENTS RM.
MECH.
PT. ROOM
PT. ROOM
STOR. ROOM MEDS
SUPPLY ROOM
ELEC.
NOURISHMENT
CHUTE
IT
COMM
CONSULT
PT. ROOM PT. ROOM
PT. ROOM
PT. ROOM
MECH
OFFICE
RESIDENTS
ROOM
STAIR
PT. ROOM
PT. ROOM
PT. ROOM
WORK ROOM
CLEAN UTILITY
SOILED UTILITY
PT. ROOM
PT. ROOM
PT. ROOM
PT. ROOM
HAC ELEC.
STAFF TLT
NURSE WK.
NURSE STATION
SOCIAL WORK
WAITING ROOM
STAIRS
CHASE
LOCKER RM.
RETHERM
CONF.
STAFF TLT.
CORRID
STAFF BREAK
EXAMPLE #1
EXAMPLE LEGEND
EXAMPLE #2
EXAMPLE #3
EXAMPLE #4
EXAMPLE #5
EXAMPLE #6
ISO ROOM
PAT. TLT.
PRIVATE ROOM
PRIVATE ROOM
PRIVATE ROOM
BARI PRIVATE
ROOM
BARIATRIC
PATIENT TOILET
PRIVATE ROOM
PRIVATE ROOM
PANTRY
SERVING
KITCHEN
DINING/DAY
ROOM
LAUNDRY CLEAN SUPPLY
RETHERMCHUTE
EQUIP STORAGE
INPATIENT
REHAB
STAFF LOUNGE
STAFF LOCKERS
CHAIR ALCOVE
FAM. LOUNGE
CONSULT
FAM/PUB. TLT.
REC.THR. STOR.
TEAM ROOM
DATA
CLEAN LINEN
NOURISH
ST. TLT.
HAC.
SOILED HOLD
ELEC.
CLEAN UTILITY
HAC
WOUND CART
STOR.SUB NS.
PRIVATE ROOM
PRIVATE ROOM
ISO ROOM
CLEAN UTILITY
PAT. TLT.
ELEC.
EQUIP STOR.
TEAM WORKCLEAN LINEN
SOILED HOLD
BARI PRIVATE
ROOM
BARI. TLT.
NOURISHMENT
PAT. TLT.
PAT. TLT.
STAFF TLT.
PRIVATE ROOM
PAT. TLT.
PAT. TLT.
PAT. TLT.
PRIVATE ROOM
PAT. TLT.
PRIVATE ROOM
PRIVATE ROOM
PRIVATE ROOM
PAT. TLT.
PAT. TLT.
PAT. TLT.
PAT. TLT.
TEAM WORK
ROOM
SUB N.S.
CHARGE NURSE
NURSE STATION
SOCIAL WORKER
DIRTY
EMPTY CYL.
STOR.
FULL CYL. STOR.
ANTE
NURSE
MANAGER
PAT. TLT.
PAT. TLT.
ANTE
MEDS
COMM
STAFF TLT.
PRIVATE ROOM PRIVATE ROOM
CORRIDOR
CORRIDOR
CORRIDOR
CORRIDOR
VENDING
PAT. TLT.
PAT. TLT.
CORRIDOR
CORRIDOR
CORRIDOR
CORRIDOR
STAIR 1
STAIR 2
STAIR 3
EXISTING RISER
ELEV.
ELEV.
CHASE
CHASE
CHASE
CHASE
THE INTENT WITH THIS PLAN IS TO SHOW
HOW THE AREAS BETWEEN THE SECOND
FLOOR AND THRID FLOOR ALIGN
12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554
©Copyright 2019
TLC No.:
www.tlc-engineers.com
118626
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg.
PROJECT TEAM:
Office of
Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
Department of Veterans Affairs
KEYPLAN
MURFREESBORO, TN
615.370.8500
615.370.8530 hfrdesign.com
214 Centerview Drive Suite 300 Brentwood, TN 37027
BLDG 2
BLDG 1
BLDG 9
Phase
FULLY SPRINKLERED
C U s e rs \a tr a y lo r\ D o c u m e n ts
\M b o ro V
A W a rd b
R e n o a tr a y lo r2 X
N D
H .r v t
/1
/2
:5
:4
P
M
04-14-2023
626A4-19-101
GI 05.01
AE RENOVATE WARD 1BPHASING PLANS
Author
HFR Project No: 2019056
100% CONSTRUCTION
DOCUMENTS
1 SECOND FLOOR PLAN - PHASING PLAN
0 8' 16' 32'4'
2 03 THIRD FLOOR PLAN - PHASING PLAN
0 8' 16' 32'4'
GENERAL NOTE:
1. THE PHASING PLAN IS NOTED AS EXAMPLES TO GIVE THE CONTRACTOR AN
UNDERSTANDING OF HOW THE PHASING FOR THE PROJECT NEEDS TO BE
ADDRESSED. WHILE THEY ARE LISTED BY NUMBER THESE EXAMPLES CAN BE
CONDUCTED IN ANY SEQUENCE AS DEEMED NECESSARY FOR THE MOST EFFECIENT
PROCESS POSSIBLE.
2. IN GENERAL 5 PATIENT ROOMS AT ONE TIME ON THE FLOOR BELOW WILL BE ABLE
TO BE TEMPORARLY OUT OF COMMISSION TO WORK ON VERTICAL SERVICES, THERE
MUST BE AT LEAST 15 ACTIVE PATIENT ROOMS AT ALL TIMES.
3. ALL ROOMS THAT ARE BEING WORKED ON SHALL BE PROTECTED FROM DAMAGE
AS BEST AS POSSIBILE. MOST OF THE WORK WILL TAKE PLACE IN THE CEILING,
HOWEVER DAMAGE TO ANY OTHER PART OF THE ROOM MUST BE REPARIED.
PROTECT EXISTING CEILING TILES, TILES THAT ARE DAMAGED OR BROKEN MUST BE
REPLACED TO THE ORIGINAL STATE.
4. CAREFUL COORDINATION WITH THE FACILITY MUST TAKE PLACE TO ADDRESS ANY
SHUTDOWNS THAT COULD EFFECT AREAS OUTSIDE OF THE DESIGNATED EXAMLE
ZONE.
5. IF SUPPORT SPACE INSIDE OF A DESIGNATED EXAMPLE ZONE IS SERVING
ANOTHER EXAMPLE ZONE COORDINATE SPECIFIC TIMES WITH THE FACILITY TO GAIN
ACCESS TO THIS SPACE.
6. ICRA BARRIERS MUST BE USED TO CLOSE OFF EACH AREA THAT IS BEING WORKED
ON TO PREVENT CONSTRUCTION DEBRIS AND DUST FROM INFILTRATING OCCUPIED
SPACE. BARRIERS SHALL BE INSTALLED AND SEALED ALONG WITH STICKY MATS AND
ANY OTHER INFECTION CONTROL ITEMS. IN SOME INSTANCES ICRA BARRIERS MAY
BE REQUIRED PER ROOM.
7. WORK IN THE CONNECTING CORRIDORS, ELEVATOR LOBBY AND NURSE STATION
SHALL BE CAREFULLY COORDINATED WITH THE FACILITY AND STAFF. THE NEED TO
WORK IN THESE AREAS SHALL BE EVALUATED ON A AS NEEDED BASIS. ELEVATOR
ACCESS SHALL BE MAINTAINED AT ALL TIMES
No. Date Description jim.elder Rectangle jim.elder Typewritten Text 06-13-2023 jim.elder Rectangle jim.elder Snapshot jim.elder Rectangle jim.elder Snapshot
NOT TO SCALE
METAL PIPE THROUGH GYPSUM WALL ASSEMBLY (1-HR.)
INSTALL PER UL SYSTEM W-L-1054
USE HILTI FS-ONE MAX FIRESTOP SEALANT
METAL PIPE
TYPE MAX. DIA.
STEEL PIPE (SCH. 10
OR HEAVIER)
30"
CAST IRON PIPE 30"
COPPER PIPE 6"
STEEL CONDUIT 6"
EMT 4"
2 1/2"
2 1/2"
3-0
NOT TO SCALE
METAL PIPE THROUGH GYPSUM WALL ASSEMBLY (2-HR.)
INSTALL PER UL SYSTEM W-L-1054
USE HILTI FS-ONE MAX FIRESTOP SEALANT
METAL PIPE
TYPE MAX. DIA.
STEEL PIPE (SCH. 10
OR HEAVIER)
30"
CAST IRON PIPE 30"
COPPER PIPE 6"
STEEL CONDUIT 6"
EMT 4"
Notes:
1. Refer to the following specifications for firestopping.
a. 07 84 00 Firestopping
b. 07 84 13 Penetration Firestopping
c. 22 00 00 Plumbing
d. 23 00 00 HVAC
e. 26 00 00 Electrical
f. 27 06 37 Communication
For Quality Control requirements, refer to the Quality Control portion of the specification.
2. Details shown are typical details, containing general information only. Always refer to the full UL system detail for complete system requirements. If field conditions do not match requirements of details, approved alternate details shall be utilized. Design requirements, field conditions and dimensions need to be verified for compliance with the details, including but not limited to the following:
* Fire Rating (F-Rating)
* Temperature Rating (T-Rating)
* Leakage Rating (L-Rating)
* Water Rating (W-Rating)
* Annular Space
* Percent Fill
* Movement
* Type and thickness of fire-rated construction.
3. If alternate details matching the field conditions are not available, manufacturer's engineering judgment drawings are acceptable.
Contact Hilti Inc. for alternative systems or Engineering
Judgment (800-879-8000) Drawings shall follow the International Firestop Council (IFC) Guidelines for Evaluating Firestop
Systems Engineering Judgments.
4. References:
* 2013 Underwriter's Laboratories Fire Resistance Directory, Volumes 1 & 2
* NFPA 101 Life Safety Code
* NFPA 70 - National Electric Code
* All governing local and regional building codes
5. Firestop System installation must meet requirements of ASTM
E-814 (UL 1479) tested assemblies that provide a fire rating equal to that of construction being penetrated.
6. All rated through-penetration assemblies shall be prominently labeled with a Hilti Firestop Label equipped with a QR code with the following information:
*Warning! - Do Not Disturb
*Through Penetration Firestop System
* UL System # * Product(s) used
* Hourly Rating (F-Rating)
* Installation Date
*Contractor's Name
7. For outlet boxes requiring protection, use only Wall Opening
Protective Materials, category CLIV as classified by Underwriter's
Laboratories, Fire Resistance Directory (Volume 1.)
MIN.RADIUS = 7"
MAX NUMBER OF BENDS = 2
SHEET METAL SCREW
DROP CEILING TILE
CEILING COVER PLATE
SPRINKLER HEAD
END BRACKET ASSEMBLY
SQUARE BAR
CENTER BRACKET ASSEMBLYREDUCING OUTLET
NUT
COLLAR
STAINLESS STEEL FLEXIBLE
BRAIDED HOSE
COLLAR
ISOLATION RING
NUT
INLET NIPPLE
MAX LENGTH OF PIPE = 48"
FIRE PROTECTION DRAWING INDEX
FIRE PROTECTION LEGEND
FIRE PROTECTION DESIGN CRITERIA
FIRE PROTECTION FLOW TEST DATA
THERE IS NO FIRE PUMP AT THIS FACILITY.
NOTE: SOME SYMBOLS SHOWN ON THIS LEGEND MAY NOT PERTAIN TO THIS PROJECT
SYMBOL DESCRIPTION
- CONTROL VALVE w/TAMPER SWITCH
- HYDRAULIC REFERENCE NODE
- EXISTING SPRINKLER PIPING
- FIRE VALVE CABINET
- REVISION REFERENCE
OR
- CONNECT TO
- DEMO TO
- DEMOLISHED SPRINKLER PIPING
- NEW SPRINKLER PIPING
- U/G GATE VALVE
# - KEYNOTE
- HYDRAULIC REMOTE AREA
- CONTROL VALVE W/ TAMPER SWITCH
- PIPE SIZE
- 2-1/2" FIRE DEPARTMENT VALVE W/ CAP AND CHAIN
- PIPE SIZE AND LENGTH
1. FIRE PROTECTION DESIGN SHALL COMPLY THE VA FIRE PROTECTION DESIGN MANUAL; SEVENTH
EDITION 2015, AND ALL APPLICABLE LOCAL CODES.
2. V.A. IS THE ONLY AHJ. SEE V.A. FIRE PROTECTION DESIGN MANUAL.
3. THE FIRE PROTECTION SYSTEMS SHOWN REPRESENT THE DESIGN INTENT OF THE ENGINEER, IN
ACCORDANCE WITH ALL APPLICABLE LOCAL CODES. IT IS THE RESPONSIBILITY OF THE
CONTRACTOR TO COORDINATE INSTALLATION WITH ALL OTHER TRADES. SUBMIT COMPLETE
SPRINKLER SYSTEM LAYOUT DRAWINGS WITH ANY ADDITIONAL OFFSETS, SPRINKLERS OR SYSTEM
COMPONENTS AS REQUIRED FOR A COMPLETE AND OPERABLE SYSTEM AND TO AVOID CONFLICTS
WITH OTHER TRADES.
4. SPRINKLER SHOP DRAWINGS AND MATERIAL CUT SHEETS SHALL BE SUBMITTED TO THE
ARCHITECT AND LOCAL FIRE MARSHAL FOR APPROVAL PRIOR TO ANY INSTALLATION.
5. PIPE ROUTING SHOWN IS SCHEMATIC ONLY. PROVIDE ALL ADDITIONAL OFFSETS REQUIRED FOR
PROPER INSTALLATION AND COORDINATION WITH OTHER TRADES.
6. INSTALL PIPING IN AREAS WITH EXPOSED STRUCTURE AS HIGH AS POSSIBLE TO ALLOW THE
OWNER MAXIMUM USE OF THE SPACE.
7. REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR CEILING DESCRIPTIONS AND HEIGHTS.
8. COORDINATE SPRINKLERS WITH ALL DIFFUSERS, SPEAKERS, LIGHTING FIXTURES AND LISTING OF
THE SPRINKLER.
9. CENTER SPRINKLERS IN THE CENTER OF CEILING TILE. PROVIDE ARMOVER OR SWING JOINT AS
REQUIRED.
10. SPRINKLERS IN AREAS WITH EXPOSED STRUCTURE (OBSTRUCTED CONSTRUCTION) SHALL BE
INSTALLED WITH DEFLECTOR 1" BELOW THE BOTTOM OF THE BEAM (MAXIMUM 22" BELOW ROOF
DECK). EXPOSED BAR JOISTS THAT HAVE SPRAY-ON FIRE PROOFING THAT MAKES THE JOIST SOLID
SHALL BE TREATED LIKE A BEAM WITH THE SPRINKLERS 1" BELOW THE BOTTOM OF THE FIRE
PROOFING.
11. SLEEVE AND/OR FIRESTOP ALL PENETRATIONS THROUGH RATED WALLS, CEILINGS, AND FLOORS WITH U/L LISTED ASSEMBLIES. PROVIDE FIRESTOP ASSEMBLIES EQUAL TO OR EXCEEDING THE
RATING OF THE WALL, CEILING OR FLOOR. SEE ARCHITECTURAL DRAWINGS FOR RATINGS.
12. FURNISH ACCESS PANELS TO ALL VALVES ABOVE NON-ACCESSIBLE CEILINGS AND CHASES, FOR
INSTALLATION BY GENERAL CONTRACTOR.
13. PROVIDE A PERMANENTLY ATTACHED NAME TAG TO THE RISER STATING THE REQUIRED DESIGN
CRITERIA FOR EACH HYDRAULICALLY-DESIGNED SYSTEM.
14. PROVIDE SPRINKLERS UNDERNEATH ALL EXPOSED DUCTWORK WHICH IS OVER 48" WIDE AND
SPACE HEADS AROUND ALL OBSTRUCTIONS IN ACCORDANCE WITH VA FIRE PROTECTION DESIGN
MANUAL 2015 EDITION. HEADS UNDER DUCTS ARE NOT INDICATED ON THE DRAWINGS BUT ARE
REQUIRED. PROVIDE IN ACCORDANCE WITH VA FIRE PROTECTION DESIGN MANUAL 2015 EDITION.
COORDINATE SPRINKLER LOCATIONS UNDER DUCTWORK AND AROUND OBSTRUCTIONS WITH
FINAL INSTALLED LOCATIONS.
15. PROVIDE SPRINKLER GUARDS ON ALL HEADS IN ELECTRIC ROOMS, TELEPHONE ROOMS, ELEVATOR
ROOMS, ELEVATOR SHAFTS, STORAGE ROOMS, UTILITY ROOMS AND ON ANY HEADS LESS THAN
7'-0" ABOVE THE FLOOR.
16. PROVIDE HANGERS ON END HEADS IN PENDANT POSITION WITHIN 12" OF END OF LINE, IN
ACCORDANCE WITH VA FIRE PROTECTION DESIGN MANUAL 2015 EDITION, WHEN SYSTEM
PRESSURE EXCEEDS 100 PSI.
17. COORDINATE PIPING WITH ALL ELECTRICAL EQUIPMENT (PANELS, TRANSFORMERS, ETC.) PRIOR TO
ANY INSTALLATION. DO NOT ROUTE ANY PIPING OVER ANY ELECTRICAL PANELS UNDER ANY
CIRCUMSTANCES. REROUTE ANY PIPING RUN OVER ELECTRICAL EQUIPMENT.
18. ALL DRAIN SYSTEM PIPING AND FITTINGS SHALL BE GALVANIZED BOTH INSIDE AND OUTSIDE.
19. PROVIDE TAMPER SWITCHES ON ALL CONTROL VALVES.
20. SLOPE ALL PIPING TO THE SYSTEM MAIN DRAIN AS REQUIRED TO INSURE PROPER DRAINAGE.
INSTALL ADDITIONAL DRAINS AND PLUGS WHERE REQUIRED TO COMPLY WITH THE ABOVE
REFERENCED CODES.
21. PROVIDE ROLL GROOVED OR CUT GROOVED COUPLINGS AND FITTINGS FROM A SINGLE
MANUFACTURER.
22. THIS BUILDINGS STRUCTURAL SYSTEM HAS BEEN DESIGNED TO SUPPORT THE ADDITIONAL
WEIGHT ASSOCIATED WITH THE SPRINKLER SYSTEM.
23. PAINT ALL SPRINKLER PIPING INSTALLED BELOW THE CEILINGS AND IN EXPOSED LOCATIONS.
CLEAN, PRIME AND PAINT ALL EXPOSED PIPING RED, UNLESS OTHERWISE NOTED. COORDINATE
ALL COLORS WITH THE ARCHITECT.
24. COORDINATE HANGER LOCATIONS WITH THE BUILDING STRUCTURE. SUPPORT PIPING IN
ACCORDANCE WITH VA FIRE PROTECTION DESIGN MANUAL 2015 EDITION. PROVIDE ALL
MISCELLANEOUS STEEL FRAMING AS REQUIRED TO SUPPORT PIPING. PROVIDE GALVANIZED OR
COATED HANGERS AND RODS.
25. THE OWNER AND ARCHITECT/ENGINEER SHALL BE NOTIFIED IN WRITING AT LEAST 10 DAYS PRIOR
TO ANY FIRE PROTECTION SYSTEM SHUTDOWNS. FIRE PROTECTION CONTRACTOR SHALL BE
RESPONSIBLE FOR A FIRE WATCH ON THE BUILDING WHILE THE SYSTEM IS DOWN.
26. TENNESSEE SPRINKLER CONTRACTOR TO PROVIDE SPRINKLER CALCS ON THE DRAWINGS.
27. SPRINKLER CONTRACTOR TO MOUNT INFORMATION PLATES ON SPRINKLER SYSTEMS WITH CALCS
ON THE PLATES.
28. PROVIDE FIRELOOP (FLEX) EXPANSION JOINT FOR FIRE SPRINKLER SYSTEM. UL LISTED AND FM
APPROVED. METRAFLEX OR EQUAL.
GENERAL NOTES
HANGER - STEEL
No Scale
PIPE HANGER RING
(UL LISTED OR FM APPROVED)
ALL THREAD ROD
TOP BEAM CLAMP
(UL LISTED OR FM APPROVED)
RETURN BEND
No Scale
SPRINKLER HEAD
1" DROP
1" 90° ELL
1" 90° ELL
BRANCH LINE
1x1/2 REDUCER
CEILING
LIGHT HAZARD
WET PIPE
.10 GPM/SQ. FT.
1,500 SQ. FT.
1/2"
30 MIN.
225 SQ. FT.
100 GPM
OCCUPANCY CLASSIFICATION:
SYSTEM TYPE:
DESIGN DENSITY:
HYDRAULIC REMOTE AREA:
SPRINKLER ORIFICE SIZE:
DURATION OF SUPPLY:
MAXIMUM COVERAGE/SPRINKLER HEAD:
HOSE STREAM ALLOWANCE:
ENTIRE BUILDING (EXCEPT AS NOTED):
FIRE SPRINKLER:
WATER SUPPLY DATA:
THE CONTRACTOR SHALL PREPARE SYSTEM LAYOUT DRAWINGS PER VA FIRE PROTECTION
DESIGN MANUAL 2015 EDITION. THE CONTRACTOR SHALL PERFORM HYDRAULIC CALCULATIONS.
CONTRACTOR'S SPRINKLER SYSTEM LAYOUT (SHOP DRAWINGS), HYDRAULIC CALCULATIONS
AND MATERIAL DATA SHALL BE SUBMITTED TO THE ARCHITECT/ENGINEER AND AUTHORITY
HAVING JURISDICTION FOR APPROVAL PRIOR TO SYSTEM INSTALLATION.
THE CONTRACTOR SHALL PERFORM HYDRANT-FLOW TEST TO VERIFY WATER PRESSURE
REQUIRED FOR HYDRAULIC CALCULATIONS.
UNLESS OTHERWISE NOTED ALL STORAGE ROOMS:
DESIGN CRITERIA:
DESIGN OF THE FIRE SUPPRESSION SYSTEM ON THIS PROJECT. THE
FOLLOWING PUBLICATIONS SHALL BE USED AS A REFERENCE.
1. VA FIRE PROTECTION MANUAL, 2015 EDITION.
ORDINARY HAZARD GROUP II
WET PIPE
0.2 GPM/SQ. FT.
1,500 SQ. FT.
1/2"
60-90 MIN.
130 SQ. FT.
250 GPM
OCCUPANCY CLASSIFICATION:
SYSTEM TYPE:
DESIGN DENSITY:
HYDRAULIC REMOTE AREA:
SPRINKLER ORIFICE SIZE:
DURATION OF SUPPLY:
MAXIMUM COVERAGE/SPRINKLER HEAD:
HOSE STREAM ALLOWANCE:
STANDPIPE DESIGN CRITERIA:
HYDRAULIC DESIGN CRITERIA: EXISTING
HYDRAULIC CALCULATIONS AND PIPE SIZES FOR EACH STANDPIPE SHALL BE BASED ON
PROVIDING 250 GPM AT THE HYDRAULICALLY MOST REMOTE TWO HOSE CONNECTIONS ON
THE MOST REMOTE STANDPIPE AND 250 GPM FROM THE MOST REMOTE HOSE CONNECTION
ON EACH ADDITIONAL STANDPIPE AT A MINIMUM RESIDUAL PRESSURE OF 100 PSI AT THE
HOSE VALVE OUTLET.
STANDPIPE HYDRAULIC DESIGN CRITERIA:
SPRINKLER LEGEND
SWING JOINT
No Scale
1" DROP
1" 90° ELL
1" NIPPLE
BRANCH LINE
1" 90° ELL
REDUCER
CEILING
SPRINKLER HEAD
UNLESS OTHERWISE NOTED ALL MECHANICAL AND ELECTRICAL ROOMS:
ORDINARY HAZARD GROUP I
WET PIPE
.15 GPM/SQ. FT.
1,500 SQ. FT.
1/2"
60-90 MIN.
130 SQ. FT.
250 GPM
OCCUPANCY CLASSIFICATION:
SYSTEM TYPE:
DESIGN DENSITY:
HYDRAULIC REMOTE AREA:
SPRINKLER ORIFICE SIZE:
DURATION OF SUPPLY:
MAXIMUM COVERAGE/SPRINKLER HEAD:
HOSE STREAM ALLOWANCE:
FLEX PIPE TO SPRINKLER
No Scale
FLEXIBLE HOSE SHALL BE INSTALLED IN ACCORDANCE WITH REQUIREMENTS OF THE LISTING INCLUDING INSTALLATION INSTRUCTIONS SEE VA GUIDELINES. ADD A NOTE THAT THE SPRINKLER CONTRACTOR SHALL HAVE THE LISTING DOCUMENTATION AND INSTALLATION INSTRUCTIONS.
SUSPENDED CEILINGS SHALL BE CERTIFIED AS
MEETING ASTM C 635 SPECIFICATION AND ASTM
C 636 STANDARD PRACTICE FOR INSTALLATION.
SEE VA GUIDELINES. ADD A NOTE THAT THE
CEILING INSTALLING CONTRACTOR SHALL
PROVIDE A SIGNED STATEMENT CONFIRMING
THE LAY-IN CEILING SYSTEMS COMPLY WITH
ASTM C 635 AND ASTM C 636.
FLEXIBLE HOSE EXCEEDING 6 FEET IN
LENGTH SERVING SPRINKLERS IN
SUSPENDED CEILINGS SHALL HAVE
HANGER ATTACHED TO THE STRUCTURE
TO LIMIT THE MAXIMUM UNSUPPORTED
LENGTH TO 6 FEET. SEE VA GUIDELINES.
FIRE SPRINKLER LEGEND
SYMBOL ORF.
1/2"
1/2"
TEMP.
155 DEG.
155 DEG.
RESPONSE
QUICK
QUICK
K-FACTOR
5.6
5.6 OR 8.0
FINISH
BRASS
BRASS
MODEL STYLE PLATE
WHITE
WHITE
MFG
RELIABLE
RELIABLERECESSED
UPRIGHTF1-FR
DESIGN NOTES:
1. PROVIDE F1FR SPRINKLERS WITH 175 DEG. F. TEMPERATURE RATING IN ALL MECHANICAL
AND ELECTRICAL ROOMS
2. RELIABLE IS BASIS OF DESIGN, APPROVED EQUALS ARE ALLOWED.
3. PROVIDE EXTENDED COVERAGE SPRINKLERS AS NEEDED.
1/2" 155 DEG. QUICK 5.6 BRASS RELIABLESIDEWALL
12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554
©Copyright 2023
TLC No.:
www.tlc-engineers.com
119437
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg.
PROJECT TEAM:
Office of
Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
Department of Veterans Affairs
MURFREESBORO, TN
615.370.8500
615.370.8530 hfrdesign.com
214 Centerview Drive Suite 300 Brentwood, TN 37027
Phase
FULLY SPRINKLERED
C R e v it
L o c a ls \1
-A lv in
C .Y o rk
P L
U M
B R
D a n n y .t h o m a s tl c -e n g
.c o m .r v t
/1
/2
:3
:5
A
M
06-13-2023
626A4-19-101
F-FI-01
AE RENOVATE WARD 1B
FIRE PROTECTION LEGENDS, DETAILS &
NOTES
DRT
HFR Project No: 2019056
100% CONSTRUCTION
DOCUMENTS
Sheet Number Sheet Name
F-FI-01 FIRE PROTECTION LEGENDS, DETAILS & NOTES
F-FD-01 PARTIAL THIRD FLOOR - PART A - FIRE PROTECTION - DEMO
F-FD-02 PARTIAL THIRD FLOOR - PART B - FIRE PROTECTION - DEMO
F-FD-03 PARTIAL THIRD FLOOR - PART C - FIRE PROTECTION - DEMO
F-FX-01 PARTIAL THIRD FLOOR - PART A - FIRE PROTECTION - NEW WORK
F-FX-02 PARTIAL THIRD FLOOR - PART B - FIRE PROTECTION - NEW WORK
F-FX-03 PARTIAL THIRD FLOOR - PART C - FIRE PROTECTION - NEW WORK
GI-05.01 PHASING PLANS
No. Date Description
1 06/20/2019 ADDENDUM 01
X3 X3
X4
X9
X10
X11
X12
X13
X14
XI XJ
XK
XL XM XN XO
XP
XQ XR
X6.1
X7.1
X12.1
X12.2 X12.3
X8
X5
X6
X7
EXISTING FIRE
STANDPIPE TO
REMAIN.
DEMO AND REMOVE EXISTING
FIRE PROTECTION PIPING UP
TO ZONE CONTROL ASSEMBLY.
REMOVE ALL
EXISTING
SPRINKLER
HEADS
REMOVE ALL
EXISTING
SPRINKLER
HEADS
REMOVE ALL
EXISTING
SPRINKLER
HEADS
REMOVE EXISTING
FDV CABINET AND
PIPING.
12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554
©Copyright 2023
TLC No.:
www.tlc-engineers.com
119437
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg.
PROJECT TEAM:
Office of
Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
Department of Veterans Affairs
KEYPLAN
MURFREESBORO, TN
615.370.8500
615.370.8530 hfrdesign.com
214 Centerview Drive Suite 300 Brentwood, TN 37027
BLDG 2
BLDG 1
BLDG 9
Phase
FULLY SPRINKLERED
C R e v it
L o c a ls \1
-A lv in
C .Y o rk
P L
U M
B R
D a n n y .t h o m a s tl c -e n g
.c o m .r v t
/1
/2
:3
:5
A
M
06-13-2023
626A4-19-101
F-FD-01
AE RENOVATE WARD 1B
PARTIAL THIRD FLOOR - PART A - FIRE
PROTECTION - DEMO
DRT
HFR Project No: 2019056
100% CONSTRUCTION
DOCUMENTS
3/16" = 1'-0"
1 PARTIAL THIRD FLOOR PART A - FIRE PROTECTION - DEMO
0 2' 4' 8'1'
FIRE PROTECTION GENERAL NOTES
1. FIRE PROTECTION DRAWINGS ARE CONCEPTUAL, FOR
GENERAL INFORMATION ONLY AND NOT AN EXACT
INDICATOR OF PIPE AND SPRINKLER HEAD LOCATIONS.
2. REMOVE EXISTING FIRE EXTINGUISHERS AND RETURN
TO VA FOR STORAGE.
3. REMOVE EXISTING FIRE VALVE CABINETS AND PIPING.
4. EXISTING SPRINKLER PIPING IS LOCATED INCHES
ABOVE CEILING GRID/TILES.
THE EXISTING FIRE PROTECTION SYSTEM SHALL REMAIN ACTIVE DURING THE CONSTRUCTION
AND INSTALLATION OF THE NEW FIRE SPRINKLER SYSTEM. ONCE THE NEW SYSTEM IS
INSTALLED, CONNECTED TO THE WATER SOURCE, IS TESTED AND ACCEPTED BY THE AHJ THE
EXISTING SYSTEM CAN BE DEMOLISHED. THE BUILDING SHALL NOT BE WITH OUT FIRE
SPRINKLER PROTECTION AT ANY TIME DURING CONSTRUCTION EXCEPT FOR THE TIME OF
CONNECTING THE NEW SYSTEM AND DISCONNECTING THE EXISTING SYSTEM. PROVIDE 72
HOUR NOTICE TO THE OWNER PRIOR TO SYSTEM SHUT DOWNS. COORDINATION WITH THE
OWNER PRIOR TO SHUT DOWN OF THE EXISTING FIRE SPRINKLER SYSTEM IS REQUIRED TO
IMPLEMENT OTHER MEANS OF FIRE SAFETY FOR THE BUILDING.
TEMPORARY FIRE PROTECTION:
PROVIDE TEMPORARY HEAT DETECTORS, CONNECTED TO EXISTING FIRE ALARM SYSTEM TO
NOTIFY SYSTEM IN THE EVENT OF A FIRE IN SPACES UNDER CONSTRUCTION. HEAT
DETECTORS SHALL PROVIDE COMPLETE COVERAGE OF THE AREA UNDER CONSTRUCTION.
QUANTITIES AND SPACING SHALL NOT EXCEED MANUFACTURER’S RECOMMENDATIONS FOR
THE DETECTORS USED. PROVIDE A MINIMUM OF ONE (1) HEAT DETECTOR IN EVERY SPACE IN
THE AREA OF CONSTRUCTION FOR EVERY 900 SQUARE FEET (MAXIMUM). HEAT DETECTORS
SHALL REMAIN ACTIVE AND IN PLACE UNTIL REPLACEMENT FIRE ALARM SYSTEM IS FULLY-
FUNCTIONAL AND COVERAGE IS PROVIDED.
FIRE SPRINKLER CONSTRUCTION CONSIDERATIONS
X1X1
X2 X2
X3 X3
X4
X9
X10
X11
X0 X0
XB XC XD XE XF XG XH XI XJ
XK
X6.1
X7.1
X12.2 X12.3
X8
XA
X5
X6
X7
EXISTING FIRE
STANDPIPE TO
REMAIN.
DEMO AND REMOVE EXISTING
FIRE PROTECTION PIPING UP
TO ZONE VALVE ASSEMBLY.
REMOVE ALL
EXISTING
SPRINKLER
HEADS
REMOVE ALL
EXISTING
SPRINKLER
HEADS
REMOVE ALL
EXISTING
SPRINKLER
HEADS
REMOVE EXISTING
FDV CABINET AND PIPING
12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554
©Copyright 2023
TLC No.:
www.tlc-engineers.com
119437
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg.
PROJECT TEAM:
Office of
Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
Department of Veterans Affairs
KEYPLAN
MURFREESBORO, TN
615.370.8500
615.370.8530 hfrdesign.com
214 Centerview Drive Suite 300 Brentwood, TN 37027
BLDG 2
BLDG 1
BLDG 9
Phase
FULLY SPRINKLERED
C R e v it
L o c a ls \1
-A lv in
C .Y o rk
P L
U M
B R
D a n n y .t h o m a s tl c -e n g
.c o m .r v t
/1
/2
:3
:5
A
M
06-13-2023
626A4-19-101
F-FD-02
AE RENOVATE WARD 1B
PARTIAL THIRD FLOOR - PART B - FIRE
PROTECTION - DEMO
DRT
HFR Project No: 2019056
100% CONSTRUCTION
DOCUMENTS
0 2' 4' 8'1'
3/16" = 1'-0"
1 PARTIAL THIRD FLOOR PART B - FIRE PROTECTION - DEMO
FIRE PROTECTION GENERAL NOTES
1. FIRE PROTECTION DRAWINGS ARE CONCEPTUAL, FOR
GENERAL INFORMATION ONLY AND NOT AN EXACT
INDICATOR OF PIPE AND SPRINKLER HEAD LOCATIONS.
2. REMOVE EXISTING FIRE EXTINGUISHERS AND RETURN
TO VA FOR STORAGE.
3. REMOVE EXISTING FIRE VALVE CABINETS AND PIPING.
4. EXISTING SPRINKLER PIPING IS LOCATED INCHES
ABOVE CEILING GRID/TILES.
THE EXISTING FIRE PROTECTION SYSTEM SHALL REMAIN ACTIVE DURING THE CONSTRUCTION
AND INSTALLATION OF THE NEW FIRE SPRINKLER SYSTEM. ONCE THE NEW SYSTEM IS
INSTALLED, CONNECTED TO THE WATER SOURCE, IS TESTED AND ACCEPTED BY THE AHJ THE
EXISTING SYSTEM CAN BE DEMOLISHED. THE BUILDING SHALL NOT BE WITH OUT FIRE
SPRINKLER PROTECTION AT ANY TIME DURING CONSTRUCTION EXCEPT FOR THE TIME OF
CONNECTING THE NEW SYSTEM AND DISCONNECTING THE EXISTING SYSTEM. PROVIDE 72
HOUR NOTICE TO THE OWNER PRIOR TO SYSTEM SHUT DOWNS. COORDINATION WITH THE
OWNER PRIOR TO SHUT DOWN OF THE EXISTING FIRE SPRINKLER SYSTEM IS REQUIRED TO
IMPLEMENT OTHER MEANS OF FIRE SAFETY FOR THE BUILDING.
TEMPORARY FIRE PROTECTION:
PROVIDE TEMPORARY HEAT DETECTORS, CONNECTED TO EXISTING FIRE ALARM SYSTEM TO
NOTIFY SYSTEM IN THE EVENT OF A FIRE IN SPACES UNDER CONSTRUCTION. HEAT
DETECTORS SHALL PROVIDE COMPLETE COVERAGE OF THE AREA UNDER CONSTRUCTION.
QUANTITIES AND SPACING SHALL NOT EXCEED MANUFACTURER’S RECOMMENDATIONS FOR
THE DETECTORS USED. PROVIDE A MINIMUM OF ONE (1) HEAT DETECTOR IN EVERY SPACE IN
THE AREA OF CONSTRUCTION FOR EVERY 900 SQUARE FEET (MAXIMUM). HEAT DETECTORS
SHALL REMAIN ACTIVE AND IN PLACE UNTIL REPLACEMENT FIRE ALARM SYSTEM IS FULLY-
FUNCTIONAL AND COVERAGE IS PROVIDED.
X1X1
X2 X2
X3 X3
X4
X9
X10
X0 X0
XS XT XU XV XW XX XY
X6.1
X7.1
XZ
X8
X5
X6
X7
EXISTING FIRE
STANDPIPE TO
REMAIN.
DEMO AND REMOVE EXISTING
FIRE PROTECTION PIPING UP
TO ZONE VALVE ASSEMBLY.
REMOVE ALL
EXISTING
SPRINKLER
HEADS
REMOVE ALL
EXISTING
SPRINKLER
HEADS
REMOVE ALL
EXISTING
SPRINKLER
HEADS
REMOVE EXISTING
FDV CABINET AND
PIPING.
12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554
©Copyright 2023
TLC No.:
www.tlc-engineers.com
119437
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg.
PROJECT TEAM:
Office of
Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
Department of Veterans Affairs
KEYPLAN
MURFREESBORO, TN
615.370.8500
615.370.8530 hfrdesign.com
214 Centerview Drive Suite 300 Brentwood, TN 37027
BLDG 2
BLDG 1
BLDG 9
Phase
FULLY SPRINKLERED
C R e v it
L o c a ls \1
-A lv in
C .Y o rk
P L
U M
B R
D a n n y .t h o m a s tl c -e n g
.c o m .r v t
/1
/2
:3
:5
A
M
06-13-2023
626A4-19-101
F-FD-03
AE RENOVATE WARD 1B
PARTIAL THIRD FLOOR - PART C - FIRE
PROTECTION - DEMO
DRT
HFR Project No: 2019056
100% CONSTRUCTION
DOCUMENTS
0 2' 4' 8'1'
3/16" = 1'-0"
1 PARTIAL THIRD FLOOR PART C - FIRE PROTECTION - DEMO
FIRE PROTECTION GENERAL NOTES
1. FIRE PROTECTION DRAWINGS ARE CONCEPTUAL, FOR
GENERAL INFORMATION ONLY AND NOT AN EXACT
INDICATOR OF PIPE AND SPRINKLER HEAD LOCATIONS.
2. REMOVE EXISTING FIRE EXTINGUISHERS AND RETURN
TO VA FOR STORAGE.
3. REMOVE EXISTING FIRE VALVE CABINETS AND PIPING.
4. EXISTING SPRINKLER PIPING IS LOCATED INCHES
ABOVE CEILING GRID/TILES.
THE EXISTING FIRE PROTECTION SYSTEM SHALL REMAIN ACTIVE DURING THE CONSTRUCTION
AND INSTALLATION OF THE NEW FIRE SPRINKLER SYSTEM. ONCE THE NEW SYSTEM IS
INSTALLED, CONNECTED TO THE WATER SOURCE, IS TESTED AND ACCEPTED BY THE AHJ THE
EXISTING SYSTEM CAN BE DEMOLISHED. THE BUILDING SHALL NOT BE WITH OUT FIRE
SPRINKLER PROTECTION AT ANY TIME DURING CONSTRUCTION EXCEPT FOR THE TIME OF
CONNECTING THE NEW SYSTEM AND DISCONNECTING THE EXISTING SYSTEM. PROVIDE 72
HOUR NOTICE TO THE OWNER PRIOR TO SYSTEM SHUT DOWNS. COORDINATION WITH THE
OWNER PRIOR TO SHUT DOWN OF THE EXISTING FIRE SPRINKLER SYSTEM IS REQUIRED TO
IMPLEMENT OTHER MEANS OF FIRE SAFETY FOR THE BUILDING.
TEMPORARY FIRE PROTECTION:
PROVIDE TEMPORARY HEAT DETECTORS, CONNECTED TO EXISTING FIRE ALARM SYSTEM TO
NOTIFY SYSTEM IN THE EVENT OF A FIRE IN SPACES UNDER CONSTRUCTION. HEAT
DETECTORS SHALL PROVIDE COMPLETE COVERAGE OF THE AREA UNDER CONSTRUCTION.
QUANTITIES AND SPACING SHALL NOT EXCEED MANUFACTURER’S RECOMMENDATIONS FOR
THE DETECTORS USED. PROVIDE A MINIMUM OF ONE (1) HEAT DETECTOR IN EVERY SPACE IN
THE AREA OF CONSTRUCTION FOR EVERY 900 SQUARE FEET (MAXIMUM). HEAT DETECTORS
SHALL REMAIN ACTIVE AND IN PLACE UNTIL REPLACEMENT FIRE ALARM SYSTEM IS FULLY-
FUNCTIONAL AND COVERAGE IS PROVIDED.
C Z
C Z
Z Z
Z Z
DD
D
D
D
D
D
CORRIDOR
B370
CORRIDOR
B300
CORRIDOR
B300
CHAIR ALCOVE
B305
STAFF LOCKERS
B304B
STAFF LOUNGE
B304
STAFF TLT.
B304A
INPATIENT
REHAB
B303
SOCIAL WORKER
B302
EQUIP STORAGE
B301
CLEAN SUPPLY
B363
LAUNDRY
B359
RETHERM
B361
DIRTY
B362
DINING/DAY
ROOM
B337
PANTRY
B338A
NURSE STATION
B336
CHARGE NURSE
B336A
MEDS
B336B
DATA
B335
COMM
B334
NURSE
MANAGER
B333
TEAM ROOM
B332
FAM/PUB. TLT.
B308
REC.THR. STOR.
B309
CONSULT
B310
FAM. LOUNGE
B307
PRIVATE ROOM
B331
PAT. TLT.
B331A
SERVING
KITCHEN
B338
PRIVATE ROOM
B339
EXISTING FIRE
STANDPIPE &
CONTROL ASSEMBLY
TO REMAIN.
EXISTING
CHUTE
SMOKE COMPARTMENT
& SPRINKLER ZONE
BOUNDARY
SMOKE COMPARTMENT
& SPRINKLER ZONE
BOUNDARY
ORDINARY HAZARD
GROUP I
ORDINARY HAZARD
GROUP II
ORDINARY HAZARD
GROUP I
ORDINARY HAZARD
GROUP II
ORDINARY HAZARD
GROUP II
ORDINARY HAZARD
GROUP II
ORDINARY HAZARD
GROUP II
ORDINARY HAZARD
GROUP II
NOTES:
1. INSTALLATION OF ALL SPRINKLER SYSTEM PIPING MUST BE PERFORMED
BY A TENNESSEE REGISTERED SPRINKLER CONTRACTOR. PIPE SIZING, FDC LOCATIONS
AND CALCULATIONS TO BE PROVIDED ON SPRINKLER CONTRACTOR SHOP DRAWINGS.
2. SPRINKLER CONTRACTOR TO COORDINATE WITH STRUCTURAL, ELECTRICAL,
TECHNOLOGY AND MECHANICAL.
3. PROVIDE FIRELOOP (FLEX) EXPANSION JOINT FOR FIRE SPRINKLER SYSTEM. UL
LISTED AND FM APPROVED.
4. COORDINATE SPRINKLER HEAD LOCATIONS IN PATIENTS ROOMS WITH LIFT
RECESSED TRACK IN CEILING. CONTRACTOR IS RESPONSIBLE FOR INSTALLATION AND
COORDINATION.
COORDINATE WITH
LIFT RECESSED TRACK
IN CEILING.
12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554
©Copyright 2023
TLC No.:
www.tlc-engineers.com
119437
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg.
PROJECT TEAM:
Office of
Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
Department of Veterans Affairs
KEYPLAN
MURFREESBORO, TN
615.370.8500
615.370.8530 hfrdesign.com
214 Centerview Drive Suite 300 Brentwood, TN 37027
BLDG 2
BLDG 1
BLDG 9
Phase
FULLY SPRINKLERED
C R e v it
L o c a ls \1
-A lv in
C .Y o rk
P L
U M
B R
D a n n y .t h o m a s tl c -e n g
.c o m .r v t
/1
/2
:3
:0
A
M
06-13-2023
626A4-19-101
F-FX-01
AE RENOVATE WARD 1B
PARTIAL THIRD FLOOR - PART A - FIRE
PROTECTION - NEW WORK
DRT
HFR Project No: 2019056
100% CONSTRUCTION
DOCUMENTS
0 2' 4' 8'1'
3/16" = 1'-0"
1 PARTIAL THIRD FLOOR PART A FIRE PROTECTION - NEW WORK
EN
B
T
S H
C C
C
C
CCC C
C
ZZ
Z
Z
Z
Z
EN
C B
SH
T
N
N E
E
C B
C B
S H
SH
T
T
CBCB
E N
E N
T T
S H
SH
CB
N E
T
S H
S H
T
T
CB
CB
N E E
N
Z
D
D
D
D
F
F
S
S
S
S
S
F
F F
F
F
F
RK
RK
RK
RK
R K
R K
R K
R
KR
K
F
S
S S S S S
S
S
S
S
F
F
F
F
F
F
F
F
BARI. TLT.
B355A
BARI PRIVATE
ROOM
B355
PRIVATE ROOM
B354
PRIVATE ROOM
B353
PAT. TLT.
B353A
PAT. TLT.
B354A
NOURISHMENT
B356
CORRIDOR
B374
LAUNDRY
B359
RETHERM
B361
DIRTY
B362
DINING/DAY
ROOM
B337
PANTRY
B338A
TEAM WORK
B341
CLEAN LINEN
B351
SOILED HOLD
B352
CLEAN UTILITY
B346
ISO ROOM
B347
PRIVATE ROOM
B348
PRIVATE ROOM
B349
ANTE
B347A
ELEC.
B344
EQUIP STOR.
B343
STAFF TLT.
B358A
SUB NS.
B358HAC
B357
SERVING
KITCHEN
B338
PRIVATE ROOM
B340
PRIVATE ROOM
B339
PAT. TLT.
B339A
PAT. TLT.
B340A
PAT. TLT.
B348A
PAT. TLT.
B347B
PRIVATE ROOM
B350
PAT. TLT.
B350A
PAT. TLT.
B349A
CORRIDOR
B376
EXISTING FIRE
STANDPIPE &
CONTROL ASSEMBLY
TO REMAIN.
SMOKE COMPARTMENT
& SPRINKLER ZONE
BOUNDARY
PROVIDE SPRINKLER
COVERAGE FOR
CLOUDS.
ORDINARY HAZARD
GROUP I
ORDINARY HAZARD
GROUP II
ORDINARY HAZARD
GROUP II
ORDINARY HAZARD
GROUP II
ORDINARY HAZARD
GROUP II
ORDINARY HAZARD
GROUP II
NOTES:
1. INSTALLATION OF ALL SPRINKLER SYSTEM PIPING MUST BE PERFORMED
BY A TENNESSEE REGISTERED SPRINKLER CONTRACTOR. PIPE SIZING, FDC LOCATIONS
AND CALCULATIONS TO BE PROVIDED ON SPRINKLER CONTRACTOR SHOP DRAWINGS.
2. SPRINKLER CONTRACTOR TO COORDINATE WITH STRUCTURAL, ELECTRICAL,
TECHNOLOGY AND MECHANICAL.
3. PROVIDE FIRELOOP (FLEX) EXPANSION JOINT FOR FIRE SPRINKLER SYSTEM. UL
LISTED AND FM APPROVED.
4. COORDINATE SPRINKLER HEAD LOCATIONS IN PATIENTS ROOMS WITH LIFT
RECESSED TRACK IN CEILING. CONTRACTOR IS RESPONSIBLE FOR INSTALLATION AND
COORDINATION.
COORDINATE WITH
LIFT RECESSED TRACK
IN CEILING. (TYPICAL)
COORDINATE WITH
LIFT RECESSED TRACK
IN CEILING. (TYPICAL)
COORDINATE WITH
LIFT TRACK IN CEILING.
(TYPICAL)
COORDINATE WITH
LIFT TRACK IN CEILING.
(TYPICAL)
12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554
©Copyright 2023
TLC No.:
www.tlc-engineers.com
119437
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg.
PROJECT TEAM:
Office of
Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
Department of Veterans Affairs
KEYPLAN
MURFREESBORO, TN
615.370.8500
615.370.8530 hfrdesign.com
214 Centerview Drive Suite 300 Brentwood, TN 37027
BLDG 2
BLDG 1
BLDG 9
Phase
FULLY SPRINKLERED
C R e v it
L o c a ls \1
-A lv in
C .Y o rk
P L
U M
B R
D a n n y .t h o m a s tl c -e n g
.c o m .r v t
/1
/2
:3
:1
A
M
06-13-2023
626A4-19-101
F-FX-02
AE RENOVATE WARD 1B
PARTIAL THIRD FLOOR - PART B - FIRE
PROTECTION - NEW WORK
DRT
HFR Project No: 2019056
100% CONSTRUCTION
DOCUMENTS
0 2' 4' 8'1'
3/16" = 1'-0"
1 PARTIAL THIRD FLOOR PART B - FIRE PROTECTION - NEW WORK
E N
B
T
S H
C C
C
C
C C CCC
Z Z
Z
Z
Z
Z
E N
C B
SH
T
N
NE
E
C B
C B
S H
SH
T
T
CB CB
E N
E N
TT
S H
SH
CB
N E
T
S H
SH
S H
T
T
CB
CB
N
EE
N
Z
D
D
D
D
D
F
F
S S
S
S
S
F
F
F F
F
R K
R K R
KR
K
R K
RK
RK
RK
RK
F
S
S
S
S
S S S
SS
F
F
F
FF
F
TEAM ROOM
B332
PRIVATE ROOM
B331
PRIVATE ROOM
B330
PAT. TLT.
B330A
PAT. TLT.
B331A
TEAM WORK
ROOM
B329
WOUND CART
STOR.
B311B
SUB N.S.
B311
ST. TLT.
B311A
EMPTY CYL.
STOR.
B317
CLEAN LINEN
B318
PRIVATE ROOM
B315
PRIVATE ROOM
B314
BARI PRIVATE
ROOM
B313
BARIATRIC
PATIENT TOILET
B313A
NOURISH
B312
PAT. TLT.
B314A
PAT. TLT.
B315A
SOILED HOLD
B327
HAC.
B325
ELEC.
B326
CLEAN UTILITY
B320
ISO ROOM
B321
PRIVATE ROOM
B322
PAT. TLT.
B322A
PAT. TLT.
B321B
ANTE
B321A
PRIVATE ROOM
B323
PRIVATE ROOM
B324
PAT. TLT.
B324A
PAT. TLT.
B323A
CORRIDOR
B373
EXSITING FIRE
STANDPIPE &
CONTROL ASSEMBLY
TO REMAIN.
PROVIDE SPRINKLER
COVERAGE FOR
CLOUDS.
NOTES:
1. INSTALLATION OF ALL SPRINKLER SYSTEM PIPING MUST BE PERFORMED
BY A TENNESSEE REGISTERED SPRINKLER CONTRACTOR. PIPE SIZING, FDC LOCATIONS
AND CALCULATIONS TO BE PROVIDED ON SPRINKLER CONTRACTOR SHOP DRAWINGS.
2. SPRINKLER CONTRACTOR TO COORDINATE WITH STRUCTURAL, ELECTRICAL,
TECHNOLOGY AND MECHANICAL.
3. PROVIDE FIRELOOP (FLEX) EXPANSION JOINT FOR FIRE SPRINKLER SYSTEM. UL
LISTED AND FM APPROVED.
4. COORDINATE SPRINKLER HEAD LOCATIONS IN PATIENTS ROOMS WITH LIFT
RECESSED TRACK IN CEILING. CONTRACTOR IS RESPONSIBLE FOR INSTALLATION AND
COORDINATION.
SMOKE COMPARTMENT
& SPRINKLER ZONE
BOUNDARY.
ORDINARY HAZARD
GROUP II
ORDINARY HAZARD
GROUP II
ORDINARY HAZARD
GROUP I
ORDINARY HAZARD
GROUP II
ORDINARY HAZARD
GROUP II
COORDINATE WITH LIFT
RECESSED TRACK IN
CEILING. (TYPICAL)
COORDINATE WITH LIFT
RECESSED TRACK IN
CEILING. (TYPICAL)
12 Cadillac Dr., Suite 150 Brentwood, TN 37027 P 615.297.4554
©Copyright 2023
TLC No.:
www.tlc-engineers.com
119437
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg.
PROJECT TEAM:
Office of
Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
Department of Veterans Affairs
KEYPLAN
MURFREESBORO, TN
615.370.8500
615.370.8530 hfrdesign.com
214 Centerview Drive Suite 300 Brentwood, TN 37027
BLDG 2
BLDG 1
BLDG 9
Phase
FULLY SPRINKLERED
C R e v it
L o c a ls \1
-A lv in
C .Y o rk
P L
U M
B R
D a n n y .t h o m a s tl c -e n g
.c o m .r v t
/1
/2
:3
:1
A
M
06-13-2023
626A4-19-101
F-FX-03
AE RENOVATE WARD 1B
PARTIAL THIRD FLOOR - PART C - FIRE
PROTECTION - NEW WORK
DRT
HFR Project No: 2019056
100% CONSTRUCTION
DOCUMENTS
0 2' 4' 8'1'
3/16" = 1'-0"
1 PARTIAL THIRD FLOOR PART C - FIRE PROTECTION - NEW WORK
1 06/20/2019 ADDENDUM 01
| GI 05-01 - PHASING PLANS |
| F-FI-01 - FIRE PROTECTION LEGENDS, DETAILS & NOTES |
| F-FD-01 - PARTIAL THIRD FLOOR - PART A - FIRE PROTECTION - DEMO |
| F-FD-02 - PARTIAL THIRD FLOOR - PART B - FIRE PROTECTION - DEMO |
| F-FD-03 - PARTIAL THIRD FLOOR - PART C - FIRE PROTECTION - DEMO |
| F-FX-01 - PARTIAL THIRD FLOOR - PART A - FIRE PROTECTION - NEW WORK |
| F-FX-02 - PARTIAL THIRD FLOOR - PART B - FIRE PROTECTION - NEW WORK |
| F-FX-03 - PARTIAL THIRD FLOOR - PART C - FIRE PROTECTION - NEW WORK |