R-P693_Drawings_Final_Vol14.7_20241007.pdf
PDF 13 MB Posted
- Solicitation number
- N6274225R1301
About this file
This is a volume of drawings (Volume 14.7) related to solicitation N6274225R1301 for the construction of a Guam Defense Radar System Command Center and associated facilities at Joint Region Marianas, Guam. While the file itself contains technical drawings, the associated solicitation provides details for a $250-500M design-bid-build project that includes construction of a command center, power generation facility, switchgear building, fuel storage facility, and entry control facility.
The project requires Risk Category IV construction with specific seismic requirements including base isolation, and includes specialized elements such as a 150-foot galvanized steel antenna tower, security infrastructure for SSL-C and IESS systems, and complex control system integration. The contract includes five pre-priced options related to generators, fuel tanks, and UPS systems. The completion period is 1,323 calendar days, with proposals due by October 30, 2024. The solicitation is unrestricted under NAICS 236220, with technical evaluation factors including Experience, Small Business Utilization, Safety, Management Plan, and Past Performance. A pre-proposal site visit is scheduled for December 11, 2024, with required base access forms due by November 14, 2024.
View the file
Other files
Show 40 more
Latest 50 of 63 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
07-OCT-2024
Approved By
CAPT Troy Brown, JRM J4 via email
9/24/2024
10/17/2024
07-OCT-2024
CAPT Troy Brown, JRM J4 via email
CAPT Troy Brown, JRM J4 via email via email via email via email via email via email via email via email
16 GAUGE, 316L STAINLESS STEEL
SHEET METAL WALL SLEEVE
COMPLETE WITH FORMED FLANGE
FOR CONNECTING ISOLATION
DAMPER.
LOUVER (SEE
ARCHITECTURAL SET)
DUCT SIZE AS TAGGED
ISOLATION DAMPER WHERE INDICATED
TRANSITION AS REQUIRED
MINIMUM 1" RETURN BRAKE ON WALL SLEEVE FLANGE
ALTERNATIVE ACTUATOR POSITION IF
JACKSHAFT IS REQUIRED FOR DAMPER.
EXTERIOR WALL
FLEX CONN. (TYP)
MOUNTING BRACKETS
REFER TO STRUCTURAL SET FOR
DETAILS OF SUPPORTS MOTOR MOUNT IF
BELT-DRIVE
DUCT MOUNT FAN
DUCT
AIRFLOW
HIGH PRESSURE SENSING
TUBE IN AIRSTREAM
LOW PRESSURE SENSING
TUBE IN AIRSTREAMDIFFERENTIAL
PRESSURE AIR
PROVING SWITCH 1/4" PRESSURE TUBING (TYP)
* FAN STATUS VIA DIFFERENTIAL PRESSURE AIR PROVING SWITCH
A. FOR GENERAL NOTES, LEGENDS, AND ABBREVIATIONS SEE
SHEETS 14GI-M-001 THROUGH 14GI-M-008.
OUTSIDEINSIDE
ISOLATION DAMPER PER PLAN DRAWING
END CAP
HORIZONTAL DUCT. SEE
PLAN FOR DIMENSION
LOUVER
OUTSIDE WALL
45 DEGREE TAP INTO
HORIZONTAL DUCT
VERTICAL DUCT. MATCH FAN
OUTLET DIMENSION.
FLEXIBLE CONNECTION
PROVIDE MOTOR SLIDE BASE
ELECTRICAL CONNECTION
FAN SHEAVE
STRUCTURAL STEEL ANGLE FRAME
INTEGRAL FROM FACTORY WITH ARR. 3F
EXTENSION FOR MOTOR MOUNT. PROVIDE
FACTORY STANDARD PAINT COAT.
CENTRIFUGAL SCROLL
FAN PER PLANS AND
SCHEDULE
SEISMIC SPRING ISOLATORS
PILLOW BLOCK
BEARINGS BOTH SIDES
AIRFLOW
V-BELT (PROVIDE OSHA BELT GUARD)
MOTOR SHEAVE
REFER TO
STRUCTURAL SET FOR
DETAILS OF SUPPORTS
SUPPLY AIR FREE
DISCHARGE TO
SPACE
ELEVATION VIEW
DISCONNECT SWITCH
HOT GAS REHEAT COIL
DX COOLING COIL
FINAL FILTER
PRE-FILTER
ISOLATION DAMPER
CONDENSATE DRAIN CONNECTION
DUCTED INLET
OA
DUCT
FLEX CONNECTION
DIRECT-DRIVE SUPPLY FAN
21" MIN
CONDENSATE DRAIN
CONNECTION
PROVIDE STRUCTURAL
RAIL OR FORMED METAL
CURB DESIGNED TO MEET
THE SEISMIC LOADING
CRITERIA (SEE NOTE 1).
HOUSEKEEPING PAD
FLOOR
AHU
(2)
(2)
1. AS REQUIRED TO ACHIEVE THE INDICATED CONDENSATE DRAIN CONNECTION HEIGHT.
2. ATTACHMENT METHOD AS REQUIRED TO MEET SEISMIC LOADING CRITERIA.
NOTES:
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P
AR
TM
E
N T
O F
TH
E
N A
VY
N
A
VA
L
FA
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
SY
S
TE
M
S C
O M
M A
N D
DRAWFORM REVISION: 25 AUGUST 2020
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
NA
VF
AC
P
AC
IF
IC
M
A K
AL
AP
A , H
A W
AI
I
AS NOTED
PR
O
JE
C
T
SI
TE
C
O M
M
AN
D C
EN
TE
R
N
AV
FA
C
P
AC
IF
IC
1812861
KYM
JC
Jacobs/B&V, A Joint Venture (Federal Services) 1003 Bishop Street Suite 1340 Honolulu, HI 96813
A/E Task Order No. N6274223F0324
AN
DE
RS
EN
A
IR
F O
RC
E
BA
SE
LJE
AWK/DMK
9/
/2
9:
:1
PM
P6
_1
_1 4P
P_ M
_d et ac he d.
rv t
14PP-M-501
PO
W
ER
P
LA
NT
ME
CH
AN
IC
AL
D
ET
AI
LS
MAM
17324526
MGP THF
G
UA
M
PP
-M -5
FINAL DESIGN SUBMITTAL
SCALE: NTSC1 EXTERIOR WALL DUCT PENETRATION DETAIL
SCALE: NTSA1 EXHAUST FAN SUPPORT DETAIL - INLINE
14CC-A-101
SITE #
BUILDING ID DISCIPLINE
CONSECUTIVE NUMBERS
SITE #
SITE 01
SITE 02
SITE 14
BUILDING ID
AC - ACCESS CONTROL POINT
CC - COMMAND CENTER
FP - FIRE PUMP BUILDING
GI - GENERAL
PP - POWER PLANT
SF - SECURITY FORCE
ST - SITE
GENERAL SHEET NOTES
SHEET NAMING CONVENTION
SCALE: NTSB3 CLEAN AGENT EXHAUST FAN DETAIL
SCALE: NTSB1 MAKEUP AIR UNIT DETAIL
SCALE: NTSA3 AHU CONDENSATE DRAIN HEIGHT DETAIL
SY
M
DE
SC
RI
PT
IO
N
DA
TE
AP
PR
14GI-M-001
14GI-M-008
Approved By
CAPT Troy Brown, JRM J4 via email
DUCT
SHEET METAL AS
SPECIFIED FOR
DUCTWORK
SHEET METAL
SCREW
1-1/2" POCKET
SLIP
ALTERNATE POSITION OF BOLT
1" FLANGE AND HEM
BOLT ON 4" CENTERS
1"x1/8" BAND IRON
FLANGED
CONNECTION
ON FAN SIDE
WASHER
FLEXIBLE MATERIAL
AS SPECIFIED
2" MIN TO 4" MAX
INSTALLED. 6" WITH
MATERIAL TAUT
NOTE:
1. EXAMPLE ABOVE IS FOR TWO DIFFERENT PRESSURE CLASSES. FOLLOW APPROPRIATE SEALING REQUIREMENTS PER STANDARDS.
MAIN DUCT
MAIN DUCT
1" MIN ON TOP
AND BOTTOM
1/4" BRANCH DUCT
WIDTH, BUT MIN 4"
ADJUSTABLE
ELBOW RINGS
EQUAL TO REQUIRED
BRANCH DUCT DIA
SEAL ALL
AROUND
1" MIN ON TOP AND BOTTOM
SUPPLY
AIRFLOW
SEAL ALL
AROUND
30°
BALANCING DAMPER WHERE INDICATED
ON DRAWINGS. MINIMUM OF 1 DUCT
DIAMETER FROM MAIN DUCT.
-45°
PANEL IS DUCT GAGE (MIN) WITH SCREWS
AT 7 7/8" MAX SPACING.
S = SIDE OPPOSITE HINGES, T = TOP, B = BOTTOM
NO. HINGES
DOOR SIZE
2-S 2-S
NO. LOCKS
1-S
FRAME 1 HINGE POS. 1
ACCESS PANEL
DUCT
LOCK TYPE 1
VIEW PORT IF SPECIFIED
BUTT HINGE 25x25, OR PIANO HINGE
SASH LOCK
500 PA STATIC AND LESS
(INCHES)
11 13/16" x 11 13/16" 15 3/4" x 19 11/16" 23 5/8" x 23 5/8"
" M
AX
IM
U M
THERMOSTAT
TYP FOR ALL
THERMOSTATS
INSTALLED
CEILING
NOTE: THERMOSTAT PLACEMENT NOT HIGHER
THAN 48" AT OPERABLE PORTION OF DEVICE.
A. FOR GENERAL NOTES, LEGENDS, AND ABBREVIATIONS SEE
SHEETS 14GI-M-001 THROUGH 14GI-M-008.
BOTTOM OF 10" PIPE
CLOSED END WITH 2"ø
DRAIN HOLE
WELD 2" DRAIN PIPE
STD. TEE OPEN THIS SIDE
WELD 2" DRAIN PIPE TO 10"
EXHAUST PIPE. 3 INCH
FILLET MINIMUM.
CONNECT 10"ø 316L SS
EXHAUST DUCT TO 10"
316L SS SCHEDULE 40S
PIPE VIA BUTT JOINT
CLAMP OR OTHER
EFFECTIVE MEANS
DUCT TRANSITION AS
NEEDED
10"ø EXHAUST DUCT
316L STAINLESS STEEL
SCH.40S TYP.
ISOLATION DAMPER
REFER TO ARCHITECTURAL
DRAWINGS FOR INFORMATION
ON PENETRATION SEAL
316L STAINLESS SLEEVE
EXHAUST DUCT
316L STAINLESS STEEL
SCH.40S PIPE TYP.
STRUCTURAL BRACING
BUILDING OUTSIDE WALL
ROOF GUTTER
ROOF
WELDED FITTINGS (TYP)
OPEN
10"X6" CONCENTRIC
REDUCER
6'
0"
TOP OF STACK
ROOF LINE
PLAN LOOKING NORTH
STD. SHORT RADIUS
ELBOW TYP.
CLOSED END OF 2" PIPE
WELDED FITTINGS (TYP)
WELDED FITTINGS (TYP)
LOOKING EAST
BUILDING OUTSIDE WALL
STD. SHORT RADIUS
316L STAINLESS STEEL SCH.40S
PIPE TYP.
316L STAINLESS SLEEVE
EXHAUST STACK
STRIAGHT UP
1'
8"
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P
AR
TM
E
N T
O F
TH
E
N A
VY
N
A
VA
L
FA
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
SY
S
TE
M
S C
O M
M A
N D
DRAWFORM REVISION: 25 AUGUST 2020
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
NA
VF
AC
P
AC
IF
IC
M
A K
AL
AP
A , H
A W
AI
I
AS NOTED
PR
O
JE
C
T
SI
TE
C
O M
M
AN
D C
EN
TE
R
N
AV
FA
C
P
AC
IF
IC
1812861
KYM
JC
Jacobs/B&V, A Joint Venture (Federal Services) 1003 Bishop Street Suite 1340 Honolulu, HI 96813
A/E Task Order No. N6274223F0324
AN
DE
RS
EN
A
IR
F O
RC
E
BA
SE
LJE
AWK/DMK
/2
/2
9:
:4
AM
P6
_1
_1 4P
P_ M
_d et ac he d.
rv t
14PP-M-502
PO
W
ER
P
LA
NT
ME
CH
AN
IC
AL
D
ET
AI
LS
MAM
17324527
MGP THF
G
UA
M
PP
-M -5
FINAL DESIGN SUBMITTAL
SCALE: NTSB1 FLEXIBLE CONNECTION - RECTANGULAR
SCALE: NTSC1 DUCTWORK BRANCH TAKEOFF FITTING DETAIL
SCALE: NTSA1 DUCT ACCESS DOOR DETAIL
SCALE: NTSA3 THERMOSTAT ELEVATION DETAIL
14CC-A-101
SITE #
BUILDING ID DISCIPLINE
CONSECUTIVE NUMBERS
SITE #
SITE 01
SITE 02
SITE 14
BUILDING ID
AC - ACCESS CONTROL POINT
CC - COMMAND CENTER
FP - FIRE PUMP BUILDING
GI - GENERAL
PP - POWER PLANT
SF - SECURITY FORCE
ST - SITE
GENERAL SHEET NOTES
SHEET NAMING CONVENTION
SCALE: NTSB3 EXTERIOR BATTERY EXHAUST STACK DETAIL
SY
M
DE
SC
RI
PT
IO
N
DA
TE
AP
PR
Approved By
CAPT Troy Brown, JRM J4 via email
FOR
FOS
OSHA TANK ACCESS LADDER AND PLATFORM
SEE SPECIFICATION 33 56 10.00 14
FOR DETAILS
FOR BULK STORAGE TANK EQUIPMENT PAD
ELEVATION SEE STRUCTURAL DRAWINGS
PIPE SUPPORT
DOUBLE WALLED BALLISTIC
RATED FUEL OIL TANK
ACCESS MANWAY 24" DIAMETER
1/2"
3/8"
UNION PSV
(SEE NOTE 1)
FOS, FOR
(SEE NOTE 1)
DIRECTION OF RELIEF
TO STORAGE TANKS BALL OR PLUG VALVE
(AS INDICATED)
NOTES:
1. VALVE MUST HAVE REMOVABLE HANDLE.
NO NO
SET @
25 PSIG
6" 6"
A. FOR GENERAL NOTES, LEGENDS, AND ABBREVIATIONS SEE
SHEETS 14GI-M-001 THROUGH 14GI-M-008.
SLEEVE
ACCESS PLATE
BRANCHING CONNECTOR
ACCESS PORT CAP
CONCRETE SLAB
SAND UNDERGROUND DOUBLE
WALL FUEL PIPE
6" ACCESS PIPE
RECOMMENDED
LEAK DETECTION
CABLE (FUEL)
AP
PR
OX
3'
-1 1"
FOS FOS
NOTES:
1. ALL PIPING TO BE LINE SIZE
DUAL STAGE DIESEL
FUEL FILTER
FILTER REMOVABLE
ACCESS (TYP)
VARIABLE LENGTH COLUMN PIPE
CHECK VALVE
BYPASS RELIEF VALVE
PUMP MOTOR ASSEMBLY
CONNECTION KIT
PUMP/MOTOR
MOTOR OPERATED VALVE
THERMAL RELIEF VALVE
POWER WIRING
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P
AR
TM
E
N T
O F
TH
E
N A
VY
N
A
VA
L
FA
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
SY
S
TE
M
S C
O M
M A
N D
DRAWFORM REVISION: 25 AUGUST 2020
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
NA
VF
AC
P
AC
IF
IC
M
A K
AL
AP
A , H
A W
AI
I
AS NOTED
PR
O
JE
C
T
SI
TE
C
O M
M
AN
D C
EN
TE
R
N
AV
FA
C
P
AC
IF
IC
1812861
KYM
JC
Jacobs/B&V, A Joint Venture (Federal Services) 1003 Bishop Street Suite 1340 Honolulu, HI 96813
A/E Task Order No. N6274223F0324
AN
DE
RS
EN
A
IR
F O
RC
E
BA
SE
LJE
AWK/DMK
9/
/2
9:
:2
PM
P6
_1
_1 4P
P_ M
_d et ac he d.
rv t
14PP-M-503
PO
W
ER
P
LA
NT
ME
CH
AN
IC
AL
D
ET
AI
LS
MAM
17324528
BJE THF
G
UA
M
PP
-M -5
FINAL DESIGN SUBMITTAL
013SCALE: NTSA1 FUEL OIL BULK TANK DETAIL
SCALE: NTSD3 THERMAL RELIEF PIPING
14CC-A-101
SITE #
BUILDING ID DISCIPLINE
CONSECUTIVE NUMBERS
SITE #
SITE 01
SITE 02
SITE 14
BUILDING ID
AC - ACCESS CONTROL POINT
CC - COMMAND CENTER
FP - FIRE PUMP BUILDING
GI - GENERAL
PP - POWER PLANT
SF - SECURITY FORCE
ST - SITE
GENERAL SHEET NOTES
SHEET KEYNOTES
SHEET NAMING CONVENTION
01. BELOW GRADE PIPING MUST BE DOUBLEWALL PIPE WITH
OUTER PIPE THROUGH STUB UPS. DOUBLE WALL PIPE
INCLUDES LEAK DETECTION CABLE.
SCALE: NTSA3 ACCESS PORT DETAIL
SCALE: NTSC3 FUEL FILTER
SCALE: NTSC1 FUEL OIL SUBMERSIBLE PUMP DETAIL
SY
M
DE
SC
RI
PT
IO
N
DA
TE
AP
PR
14GI-M-001
14GI-M-008
Approved By
CAPT Troy Brown, JRM J4 via email
PROVIDE TRANSITION FROM
TERMINAL TO DUCTWORK
VAV OR CV
TERMINAL
PROVIDE A MINIMUM OF FOUR DUCT
DIAMETERS OF STRAIGHT DUCT
PROVIDE BALANCING DAMPER
AT EACH FLOOR TAKE-OFF
SU
PP
LY
D
UC
T
MA
IN
LINEAR SLOT, LINEAR BAR
OR FLOW BAR DIFFUSER
SUPPLY DUCT RISER
EQUAL LENGTH
BRANCH DUCTS TO
SUPPLY AIR OUTLETS
SUPPLY DUCT BRANCH
RIGID DUCTFLEX DUCT
(5'-0" MAX)
SUPPLY
GRILLE/
REGISTER
SIZE BY CFM
PROPORTION
NOTES:
1. REFER TO HVAC FLOOR PLANS FOR DUCT SIZES.
2. REFER TO SCHEDULES FOR GRILLES, REGISTERS, DIFFUSERS AND TERMINAL SIZES AND TYPES.
3. PROVIDE A MANUAL TYPE BALANCING DAMPER FOR EACH SUPPLY OUTLET, RETURN INLET, AND EXHAUST INLET.
4. ALL DUCT RUNOUTS TO DIFFUSERS MUST BE THE SAME SIZE AS DIFFUSER NECK SIZE, UNLESS OTHERWISE NOTED.
5. FLEX DUCT WILL NOT BE ALLOWED ON RETURN OR EXHAUST DUCTWORK SYSTEMS.
6. PROVIDE 12" AIR CUSHION AT THE END OF EACH SUPPLY MAIN AND BRANCH DUCT.
7. INDIVIDUAL BRANCH BALANCING DAMPERS NOT REQUIRED FOR SUPPLY OR EXHAUST REGISTERS.
CEILING
DIFFUSER
SUPPLY DUCT BRANCH
SU
PP
LY
D
UC
T
MA
IN
RETURN DUCT RISER
RE
TU
RN
D
UC
T
MA
IN
RETURN
DUCT BRANCH
RETURN
GRILLE
CEILING
GRILLE
OPEN ENDED
RETURN AIR
BRANCH DUCT
PROVIDE 1-1/2 RADIUS ELBOWS
FOR ALL DUCTWORK SYSTEMS
WHEREVER SPACE ALLOWS
PROVIDE 90° ELBOWS
W/ TURNING VANES IF
RADIUS ELBOWS WILL
NOT FIT
EXHAUST
REGISTER
EX
HA
US
T
DU
CT
M
AI
N
EXHAUST
DUCT BRANCH
EXHAUST DUCT RISER
30° MIN
SUPPLY
AIR FLOW
DUCT TO MATCH REGISTER FLANGE
OUTSIDE DIMENSIONS
REGISTER
PLAN VIEW
RETURN OR EXHAUST
AIR FLOW
6" M
IN
BALANCING DAMPER
A. FOR GENERAL NOTES, LEGENDS, AND ABBREVIATIONS SEE
SHEETS 14GI-M-001 THROUGH 14GI-M-008.
NOTES:
1. FOLLOW DAMPER MANUFACTURER'S INSTRUCTIONS, INCLUDING FASTENER OPTIONS AND GAUGES FOR SLEEVE AND PERIMETER ANGLES. COORDINATE MANUFACTURER'S INSTALLATION INSTRUCTIONS WITH STRUCTURAL WALL
PENETRATION OPENINGS.
2. ACCESS DOORS: SIZE AND LOCATION TO PERMIT SERVICING EACH FUSIBLE LINK OR LINKS. PROVIDE 24"x24" ACCESS DOORS MINIMUM OR DUCT WIDTH MINUS 2"x24" WHICHEVER IS LARGER.
DUCTWORK AS
REQUIRED ON
PLANS
INSULATION AS
REQUIRED
MULTI-BLADE FIRE
DAMPER W/ V STYLE
BLADES
BEAD OF ACOUSTIC/
FIRE-RATED SEALANT
(MAY BE ON EITHER
SIDE OF DAMPER
FRAME)
FIRE BARRIER
PARTITION OR
CHASE (WALL
MATERIAL WILL
VARY, REFER TO
STRUCTURAL AND
ARCH DRAWINGS)
BEAD OF ACOUSTIC/
FIRE-RATED SEALANT
AROUND EDGES
1/2" CLEARANCE MIN TOP
AND SIDES FOR VERTICAL
INSTALLATION, AND 1/2"
CLEARANCE MIN ALL
AROUND FOR
HORIZONTAL
INSTALLATIONS (1/8" PER
FOOT OF DUCT
DIMENSION)
1/8" NEOPRENE
GASKET (ALL
AROUND)
ACCESS DOOR
(NOTE 2)
MINIMUM EDGE DISTANCE =
5 ANCHOR DIAMETERS
INSULATE WITH
VAPOR BARRIER
UNION
DRAIN PAN
CAP
CALCULATION PROCESS
WHERE X = TSP
UNIT TYPE A B
DRAW
THRU
BLOW
THRU
2" PLUS X X
1" MINIMUM 2X
FLOOR
PITCH AT LEAST 1/8" PER FOOT DOWN
TOWARDS FLOOR DRAIN, COVER END
WITH WIRE SCREEN
TERMINATE AT
FLOOR DRAIN
WITH AIR BREAK
PIPE SUPPORT
A B
NOTES:
1. PIPE SIZES AS INDICATED ON PLANS WHERE NOT SHOWN, SIZE MUST BE FULL SIZE OF DRAIN TAP ON
AHU OR 1-1/4" MINIMUM.
2. COORDINATE PAD OR CURB HEIGHT WITH TAP SIZE.
3. SEE SPECIFICATIONS FOR INSULATION REQUIREMENT.
4. ROUTE CONDENSATE DRAIN LINES TO THE NEAREST FLOOR DRAIN AND TERMINATE 6" ABOVE THE
FLOOR DRAIN.
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P
AR
TM
E
N T
O F
TH
E
N A
VY
N
A
VA
L
FA
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
SY
S
TE
M
S C
O M
M A
N D
DRAWFORM REVISION: 25 AUGUST 2020
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
NA
VF
AC
P
AC
IF
IC
M
A K
AL
AP
A , H
A W
AI
I
AS NOTED
PR
O
JE
C
T
SI
TE
C
O M
M
AN
D C
EN
TE
R
N
AV
FA
C
P
AC
IF
IC
1812861
KYM
JC
Jacobs/B&V, A Joint Venture (Federal Services) 1003 Bishop Street Suite 1340 Honolulu, HI 96813
A/E Task Order No. N6274223F0324
AN
DE
RS
EN
A
IR
F O
RC
E
BA
SE
LJE
AWK/DMK
9/
/2
9:
:2
PM
P6
_1
_1 4P
P_ M
_d et ac he d.
rv t
14PP-M-504
PO
W
ER
P
LA
NT
ME
CH
AN
IC
AL
D
ET
AI
LS
MAM
17324529
MGP THF
G
UA
M
PP
-M -5
FINAL DESIGN SUBMITTAL
SCALE: NTSA3 DUCTWORK INSTALLATION DIAGRAM
SCALE: NTSC3 REGISTER DETAIL - DUCT MOUNTED
14CC-A-101
SITE #
BUILDING ID DISCIPLINE
CONSECUTIVE NUMBERS
SITE #
SITE 01
SITE 02
SITE 14
BUILDING ID
AC - ACCESS CONTROL POINT
CC - COMMAND CENTER
FP - FIRE PUMP BUILDING
GI - GENERAL
PP - POWER PLANT
SF - SECURITY FORCE
ST - SITE
GENERAL SHEET NOTES
SHEET NAMING CONVENTION
SCALE: NTSA1 DAMPER DETAIL - MULTI-BLADE V-STYLE FIRE
SCALE: NTSC1 COIL DRAIN TRAP DETAIL
SY
M
DE
SC
RI
PT
IO
N
DA
TE
AP
PR
14GI-M-001
14GI-M-008
Approved By
CAPT Troy Brown, JRM J4 via email
CFM
SA
CFM
RA
AHU-14PP41101
CFM
SA
CFM
RA
300 CFM EA
300 CFM
EA
300 CFM
EA
300 CFM EA
AHU-14PP41102
CFM
TA
EF-14PP41102
EF-14PP41101
FCU-14PP41102FCU-14PP41101
MOD-14PP41101
MOD-14PP41102
200 CFM
EXFL
MOD-14PP41112
EF-14PP41104
2880 CFM
EF-14PP41103
MOD-14PP41110
2660 CFM
MOD-14PP41113
MOD-14PP41111
500/
CFM
500/
CFM
MOD-14PP41107 MOD-14PP41105
MOD-14PP41109
ROOM 104
ROOM 103 ROOM 102
ROOM 1012880 CFM
01 300
CFM
TA
200 CFM
EXFL
500 CFM
2660 CFM
MOD-14PP41104
MOD-14PP41103
03 03
MAU-14PP41102
500 CFM
MAU-14PP41101300
CFM TA
CFM TA
MOD-14PP41106
A. FOR GENERAL NOTES, LEGENDS, AND ABBREVIATIONS SEE
SHEETS 14GI-M-001 THROUGH 14GI-M-008.
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P
AR
TM
E
N T
O F
TH
E
N A
VY
N
A
VA
L
FA
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
SY
S
TE
M
S C
O M
M A
N D
DRAWFORM REVISION: 25 AUGUST 2020
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
NA
VF
AC
P
AC
IF
IC
M
A K
AL
AP
A , H
A W
AI
I
AS NOTED
PR
O
JE
C
T
SI
TE
C
O M
M
AN
D C
EN
TE
R
N
AV
FA
C
P
AC
IF
IC
1812861
KYM
JC
Jacobs/B&V, A Joint Venture (Federal Services) 1003 Bishop Street Suite 1340 Honolulu, HI 96813
A/E Task Order No. N6274223F0324
AN
DE
RS
EN
A
IR
F O
RC
E
BA
SE
LJE
AWK/DMK
9/
/2
9:
:5
PM
P6
_1
_1 4P
P_ M
_d et ac he d.
rv t
14PP-M-601
PO
W
ER
P
LA
NT
ME
CH
AN
IC
AL
S
CH
EM
AT
IC
S
MAM
17324530
MGP THF
G
UA
M
PP
-M -6
FINAL DESIGN SUBMITTAL
SCALE: NTSA1 AIRFLOW DIAGRAM
14CC-A-101
SITE #
BUILDING ID DISCIPLINE
CONSECUTIVE NUMBERS
SITE #
SITE 01
SITE 02
SITE 14
BUILDING ID
AC - ACCESS CONTROL POINT
CC - COMMAND CENTER
FP - FIRE PUMP BUILDING
GI - GENERAL
PP - POWER PLANT
SF - SECURITY FORCE
ST - SITE
GENERAL SHEET NOTES
SHEET KEYNOTES
SHEET NAMING CONVENTION
01. AIRFLOW IS ONLY DURING THE REMOVAL OF CLEAN AGENT
FIRE SUPPRESSANT AFTER IT HAS BEEN DEPLOYED AND
EXTINGUISHED A FIRE IN THE SPACE.
02. AIRFLOWS IN DIFFERENT OPERATIONS. FIRST AIRFLOW IS
NORMAL. SECOND AIRFLOW IS DURING REMOVAL OF CLEAN
AGENT (SEE NOTE 01).
03. MANUAL ISOLATION DAMPER WITH ALUMINUM PARALLEL
AIRFOIL BLADES AND LOW-LEAK SEAL.
04. TRANSFER AIR PATH EITHER DIRECTION.
SY
M
DE
SC
RI
PT
IO
N
DA
TE
AP
PR
14GI-M-001
14GI-M-008
Approved By
CAPT Troy Brown, JRM J4 via email
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M M
M
M
M
M
M
M
M
FBT-14PP03101
FUEL OFFLOADING
STATION
WALK-IN GENERATOR
ENCLOSURE (TYP)
FUEL BELLY TANK (TYP).
REFER TO 14PP-M-802 FOR
FURTHER DETAIL
DG-14PP61114
DG-14PP61113
DG-14PP61112
DG-14PP61111
FBT-14PP03102
FOP-14PP03102
FUEL POLISHER (TYP).
REFER TO 14PP-M-805 FOR
FURTHER DETAIL
FUEL BULK TANK (TYP).
REFER TO 14PP-M-801 FOR
FURTHER DETAIL
FOR
FOS
FOR
FOS
FOR
FOS
FOR
FOS
1-1/4" FOS
1-1/4" FOR
1-1/4" FOS
1-1/4" FOR
1-1/4" FOS
1-1/4" FOR
1-1/2" FOS
2" FOR2" FOR
1-1/2" FOS
2" FOR
1-1/2" FOS
2" FOR
1-1/4" FOS
1-1/4" FOR
6" FOF
6" FOF
6" FOF
FF-14PP03102
FF-14PP03101
1-1/4" FOS
1-1/4" FOR
1-1/4" FOS
1-1/4" FOR
2" F
OR
1- 1/2
" F
OS
1- 1/2
" F
OS
2" F
OR
MOV-14PP03102A
MOV-14PP03101A
MOV-14PP03103
MOV-14PP03105
MOV-14PP03104
MOV-14PP03106
MOV-14PP03107A
MOV-14PP03109A
MOV-14PP03111A
MOV-14PP03113A
FOP-14PP03101
MOV-14PP03115
MOV-14PP03116
MOV-14PP03117
MOV-14PP03118
FOP-14PP03101B
FOP-14PP03101A
FOP-14PP03102B
FOP-14PP03102A
FOP-14PP03103A
FOP-14PP03103B
FOP-14PP03104A
FOP-14PP03104B
FOP-14PP03105A
FOP-14PP03105B
FOP-14PP03106A
FOP-14PP03106B
SEE 14PP-M-803 FOR
FURTHER DETAIL
WASTE TANK
WASTE TANK
FUTURE FBT(S)
FUEL FILTRATION CABINET SEE C3/14PP-M-503
FOP-14PP03107
FBT-14PP03103
FOP-14PP03108A
FOP-14PP03108B
MOV-14PP03119A
MOV-14PP03121
MOV-14PP03120
MOV-14PP03122
1- 1/2
" F
OS
1- 1/2
" F
OR
1- 1/2
" F
OS
OPTION ITEM #101
OPTION ITEM #303
OPTION ITEM #202
OPTION ITEM #101
6" FOF FUTURE
CONNECTION
1-1/2" FOS FUTURE
CONNECTION
2" FOR FUTURE
CONNECTION
2" F
OR
MOV-14PP03123
MOV-14PP03124A
MOV-14PP03124B
(15 GPM)
(15 GPM)
(15 GPM)
(15 GPM)
(24 GPM)
(24 GPM)
(300 GPM)
(24 GPM)
MOV-14PP03102B
MOV-14PP03101B
MOV-14PP03119B
ICC 500 FUEL STORAGE TANK
REFER TO 14PP-M-809 FOR
FURTHER DETAIL
MOV-14PP03107B
MOV-14PP03109B
MOV-14PP03111B
MOV-14PP03113B
BPCV
[300 GPM]
[300 GPM]
[12 GPM]
[15 GPM]
[12 GPM]
[15 GPM]
[12 GPM]
[15 GPM]
[12 GPM]
[15 GPM]
[24 GPM]
[24 GPM]
[30 GPM]
[24 GPM]
[12 GPM]
[12 GPM]
[12 GPM]
[12 GPM] [24 GPM]
[30 GPM]
[24 GPM]
[30 GPM]
A. FOR GENERAL NOTES, LEGENDS, AND ABBREVIATIONS SEE
SHEETS 14GI-M-001 THROUGH 14GI-M-008.
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P
AR
TM
E
N T
O F
TH
E
N A
VY
N
A
VA
L
FA
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
SY
S
TE
M
S C
O M
M A
N D
DRAWFORM REVISION: 25 AUGUST 2020
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
NA
VF
AC
P
AC
IF
IC
M
A K
AL
AP
A , H
A W
AI
I
AS NOTED
PR
O
JE
C
T
SI
TE
C
O M
M
AN
D C
EN
TE
R
N
AV
FA
C
P
AC
IF
IC
1812861
KYM
JC
Jacobs/B&V, A Joint Venture (Federal Services) 1003 Bishop Street Suite 1340 Honolulu, HI 96813
A/E Task Order No. N6274223F0324
AN
DE
RS
EN
A
IR
F O
RC
E
BA
SE
LJE
AWK/DMK
9/
/2
9:
:4
PM
P6
_1
_1 4P
P_ M
_d et ac he d.
rv t
14PP-M-611
PO
W
ER
P
LA
NT
ME
CH
AN
IC
AL
S
CH
EM
AT
IC
S
MAM
17324531
BJE THF
G
UA
M
PP
-M -6
FINAL DESIGN SUBMITTAL
SCALE: NTSA1 FUEL OIL FLOW DIAGRAM
14CC-A-101
SITE #
BUILDING ID DISCIPLINE
CONSECUTIVE NUMBERS
SITE #
SITE 01
SITE 02
SITE 14
BUILDING ID
AC - ACCESS CONTROL POINT
CC - COMMAND CENTER
FP - FIRE PUMP BUILDING
GI - GENERAL
PP - POWER PLANT
SF - SECURITY FORCE
ST - SITE
GENERAL SHEET NOTES
SHEET KEYNOTES
SHEET NAMING CONVENTION
01. THE FOLLOWING MECHANICAL ITEMS INCLUDE THE SCOPE
ASSOCIATED WITH OPTION ITEM #1 (APPLICABLE TO
MECHANICAL ITEMS WITHIN THE DASHED BOUNDARY ON
THIS DRAWING ONLY AND ASSOCIATED CONTROLS POINTS):
- PROVIDE BELLY OR DAY TANKS PUMPS FOP-14PP03105A
AND FOP-14PP03105B AND ASSOCIATED VALVE
MOV-14PP03111.
-PROVIDE FUEL OIL BULK TANK FBT-14PP03102, ASSOCIATED
VALVES MOV-14PP03117, MOV-14PP03118, MOV-14PP03104,
MOV-14PP03106, MOV-14PP03102 AND ASSOCIATED FUEL
POLISHER FP-14PP03102.
02. THE FOLLOWING MECHANICAL ITEMS INCLUDE THE SCOPE
ASSOCIATED WITH OPTION ITEM #2 (APPLICABLE TO
MECHANICAL ITEMS WITHIN THE DASHED BOUNDARY ON
THIS DRAWING ONLY AND ASSOCIATED CONTROLS POINT):
- PROVIDE BELLY OR DAY TANKS PUMPS FOP-14PP03104A
AND FOP-14PP03104B AND ASSOCIATED VALVE
MOV-14PP03109.
03. THE FOLLOWING MECHANICAL ITEMS INCLUDE THE SCOPE
ASSOCIATED WITH OPTION ITEM #3 (APPLICABLE TO
MECHANICAL ITEMS WITHIN THE DASHED BOUNDARY ON
THIS DRAWING ONLY AND ASSOCIATED CONTROLS POINTS):
- PROVIDE BELLY OR DAY TANKS PUMPS FOP-14PP03103A
AND FOP-14PP03103B AND ASSOCIATED VALVE
MOV-14PP03107.
SY
M
DE
SC
RI
PT
IO
N
DA
TE
AP
PR
14GI-M-001
14GI-M-008
/14PP-M-503(
14PP-M-801
14PP-M-802
14PP-M-803
14PP-M-805
14PP-M-809
Approved By
CAPT Troy Brown, JRM J4 via email
A. FOR GENERAL NOTES, LEGENDS, AND ABBREVIATIONS SEE
SHEETS 14GI-M-001 THROUGH 14GI-M-008.
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P
AR
TM
E
N T
O F
TH
E
N A
VY
N
A
VA
L
FA
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
SY
S
TE
M
S C
O M
M A
N D
DRAWFORM REVISION: 25 AUGUST 2020
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
NA
VF
AC
P
AC
IF
IC
M
A K
AL
AP
A , H
A W
AI
I
AS NOTED
PR
O
JE
C
T
SI
TE
C
O M
M
AN
D C
EN
TE
R
N
AV
FA
C
P
AC
IF
IC
1812861
KYM
JC
Jacobs/B&V, A Joint Venture (Federal Services) 1003 Bishop Street Suite 1340 Honolulu, HI 96813
A/E Task Order No. N6274223F0324
AN
DE
RS
EN
A
IR
F O
RC
E
BA
SE
LJE
AWK/DMK
9/
/2
9:
:2
PM
P6
_1
_1 4P
P_ M
_d et ac he d.
rv t
14PP-M-701
PO
W
ER
P
LA
NT
ME
CH
AN
IC
AL
S
CH
ED
UL
ES
MAM
17324532
MGP THF
G
UA
M
PP
-M -7
FINAL DESIGN SUBMITTAL
3. WALL MOUNT UNIT.
2. POWERED FROM OUTDOOR UNIT. PROVIDE WIRING IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS.
1. PERFORMANCE INDICATED IS FOR OPERATION WITH THE ASSOCIATED OUTDOOR UNIT USING REFRIGERANT TYPE SCHEDULED FOR THAT UNIT.
REMARKS:
FCU-14PP41102 ROOM 101 ACCU-14PP41102 400 77 64.1 55 54 10.1 12 NOTE 2 36 X 10 X 12 100 1-3 FCU-14PP41101 ROOM 104 ACCU-14PP41101 400 77 64.1 55 54 10.1 12 NOTE 2 36 X 10 X 12 100 1-3
DB
(°F)
WB
(°F)
DB
(°F)
WB
(°F)
ENTERING LEAVING
SENSIBLE
OUTPUT
(MBH)
TOTAL
OUTPUT
(MBH)
EQUIPMENT TAG LOCATION ASSOCIATED
OUTDOOR UNIT
AIRFLOW
(CFM)
DX COOLING COIL
ELECTRICAL
DATA
MAX
DIMENSIONS
(L x W x H)
MAX
WEIGHT
(LB)
REMARKS
FAN COIL UNIT SCHEDULE
5. PROVIDE VFD.
4. PROVIDE ACROSS-THE-LINE STARTER.
3. MAXIMUM FAN SPEED 1800 RPM.
2. AMCA ARR. 3 CONFIGURATION WITH OSHA BELT GUARD, AND INLET SCREEN.
1. PROVIDE AMCA TYPE B SPARK RESISTANT CONSTRUCTION.
REMARKS:
EF-14PP41104 ROOM 103 DWDI, FLOOR MOUNTED, UP DISCHARGE BELT 2,880 1.0 3 460/3/60 260 2-4 EF-14PP41103 ROOM 102 DWDI, FLOOR MOUNTED, UP DISCHARGE BELT 2,660 1.0 3 460/3/60 260 2-4 EF-14PP41102 ROOM 101 INLINE CENTRIFUGAL, DUCT MOUNTED BELT 300 0.5 1/4 115/1/60 100 1, 5 EF-14PP41101 ROOM 104 INLINE CENTRIFUGAL, DUCT MOUNTED BELT 300 0.5 1/4 115/1/60 100 1, 5
HP V / PH / HZ
EQUIPMENT TAG SERVING FAN TYPE DRIVE TYPE FAN ESP
(IN WC)
MOTOR
MAX WEIGHT
(LBS) REMARKS
EXHAUST FAN SCHEDULE
6. TURN DOWN TO 30 PERCENT OR LOWER OF DESIGN CAPACITY.
5. PROVIDE FIELD CONNECTION FOR POWER WIRING TO THE ASSOCIATED INDOOR UNIT.
4. ADD MARINE RATED COATING FOR OUTDOOR UNIT
3. OUTDOOR UNIT/FLOOR MOUNTED
2. PROVIDE SINGLE POINT POWER CONNECTION.
1. AS REQUIRED TO ACHIEVE THE SCHEDULED INDOOR UNIT COOLING COIL PERFORMANCE WHEN CONNECTED AS A SPLIT SYSTEM.
REMARKS:
ACCU-14PP41106 MAU-14PP41102 NOTE 1 95 460/3/60 9 15 R-454B 63"x32"x60" 500 1-4, 6 ACCU-14PP41105 MAU-14PP41101 NOTE 1 95 460/3/60 9 15 R-454B 63"x32"x60" 500 1-4, 6 ACCU-14PP41104 AHU-14PP41102 NOTE 1 95 460/3/60 31.6 40 R-454B 99x58x56" 1,900 1-4, 6 ACCU-14PP41103 AHU-14PP41101 NOTE 1 95 460/3/60 31.6 40 R-454B 99x58x56" 1,900 1-4, 6 ACCU-14PP41102 FCU-14PP41102 NOTE 1 95 208/1/60 11 20 R-454B 31x12x25" 200 1-5 ACCU-14PP41101 FCU-14PP41101 NOTE 1 95 208/1/60 11 20 R-454B 31x12x25" 200 1-5
CAPACITY
HIGH
AMBIENT
DB (°F)
V/PH/HZ MCA MOCP
EQUIPMENT TAG ASSOCIATED
INDOOR UNIT
RATED COOLING PERFORMANCE ELECTRICAL DATA
REFRIGERAN
T TYPE
MAX
DIMENSIONS
(L x W x H)
MAX
WEIGHT
(LB)
REMARKS
AIR-COOLED CONDENSING UNIT SCHEDULE
14CC-A-101
SITE #
BUILDING ID DISCIPLINE
CONSECUTIVE NUMBERS
SITE #
SITE 01
SITE 02
SITE 14
BUILDING ID
AC - ACCESS CONTROL POINT
CC - COMMAND CENTER
FP - FIRE PUMP BUILDING
GI - GENERAL
PP - POWER PLANT
SF - SECURITY FORCE
ST - SITE
GENERAL SHEET NOTES
SHEET NAMING CONVENTION
5. PROVIDE CURB OR STRUCTURAL RAILS TO FACILITATE NECESSARY CONDENSATE DRAIN HEIGHT ABOVE FINISHED FLOOR.
4. PROVIDE UNIT MOUNTED VARIABLE FREQUENCY DRIVE.
3. VERTICAL, UP DISCHARGE AIR HANDLER CONFIGURATION.
2. PROVIDE SINGLE POINT POWER CONNECTION.
1. PERFORMANCE INDICATED IS FOR OPERATION WITH THE ASSOCIATED OUTDOOR UNIT AND USING REFRIGERANT TYPE SCHEDULED FOR THAT UNIT.
REMARKS:
AHU-14PP41102 ROOM 102 NOTE 3 2,500 1.5 ACCU-14PP41104 64.4 88.9 77.0 64.1 53 9.5 20 460/3/60 2" PLEAT 8 1500 78x54x72 1-5 AHU-14PP41101 ROOM 103 NOTE 3 2,500 1.5 ACCU-14PP41103 64.4 88.9 77.0 64.1 53 9.5 20 460/3/60 2" PLEAT 8 1500 78x54x72 1-5
CFM ESP
(IN WG)
ENT.DB
(°F)
ENT.WB
(°F) TYPE MERV
ASSOCIATED
OUTDOOR UNIT
NET SENSIBLE
CAPACITY
(MBH)
NET TOTAL
CAPACITY
(MBH)
ENTERING
LVG.DB
(°F) FLA MOCP V / PH / HZ
EQUIPMENT TAG LOCATION ORIENTATION
FAN
DX COOLING COIL ELECTRICAL DATA
FILTER MAX
WEIGHT
(LB)
MAX
DIMENSIONS
(INDOOR UNIT)
(L x W x H)
REMARKS
AIR HANDLING UNIT SCHEDULE
SY
M
DE
SC
RI
PT
IO
N
DA
TE
AP
PR
14GI-M-001
14GI-M-008
Approved By
CAPT Troy Brown, JRM J4 via email
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P
AR
TM
E
N T
O F
TH
E
N A
VY
N
A
VA
L
FA
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
SY
S
TE
M
S C
O M
M A
N D
DRAWFORM REVISION: 25 AUGUST 2020
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
NA
VF
AC
P
AC
IF
IC
M
A K
AL
AP
A , H
A W
AI
I
AS NOTED
PR
O
JE
C
T
SI
TE
C
O M
M
AN
D C
EN
TE
R
N
AV
FA
C
P
AC
IF
IC
1812861
KYM
JC
Jacobs/B&V, A Joint Venture (Federal Services) 1003 Bishop Street Suite 1340 Honolulu, HI 96813
A/E Task Order No. N6274223F0324
AN
DE
RS
EN
A
IR
F O
RC
E
BA
SE
LJE
AWK/DMK
9/
/2
9:
:2
PM
P6
_1
_1 4P
P_ M
_d et ac he d.
rv t
14PP-M-702
PO
W
ER
P
LA
NT
ME
CH
AN
IC
AL
S
CH
ED
UL
ES
MAM
17324533
BJE THF
G
UA
M
PP
-M -7
FINAL DESIGN SUBMITTAL
14CC-A-101
SITE #
BUILDING ID DISCIPLINE
CONSECUTIVE NUMBERS
SITE #
SITE 01
SITE 02
SITE 14
BUILDING ID
AC - ACCESS CONTROL POINT
CC - COMMAND CENTER
FP - FIRE PUMP BUILDING
GI - GENERAL
PP - POWER PLANT
SF - SECURITY FORCE
ST - SITE
GENERAL SHEET NOTES
SHEET KEYNOTES
SHEET NAMING CONVENTION
2. SELECT OPEN/CLOSE CONTROL VALVE TO HAVE A MAXIMUM OPERATING DIFFERENTIAL PRESSURE OF 45 PSI.
1. COORDINATE POWER AND CONTROLS CONNECTIONS WITH ELECTRICAL AND CONTROLS CONTRACTOR.
REMARKS:
MOV-14PP03124B FUEL OIL SUPPLY FROM ICC500 TANK (FBT-14PP03103) 1 1/2 24 15 NO. 2 FUEL OIL AMBIENT 2-WAY OPEN 12 VAC - 1, 2 MOV-14PP03124A FUEL OIL SUPPLY FROM ICC500 TANK (FBT-14PP03103) 1 1/2 24 15 NO. 2 FUEL OIL AMBIENT 2-WAY OPEN 12 VAC - 1, 2 MOV-14PP03123 FUEL OIL RETURN TO ICC500 TANK (FBT-14PP03103) 2 30 15 NO. 2 FUEL OIL AMBIENT 2-WAY OPEN 12 VAC - 1, 2 MOV-14PP03122 FUEL OIL RETURN TO FBT-14PP03102 &14PP03101 2 30 15 NO. 2 FUEL OIL AMBIENT 2-WAY OPEN 12 VAC - 1, 2 MOV-14PP03121 FUEL OIL RETURN FROM ICC500 TANK (FBT-14PP03103) 1 1/2 24 15 NO. 2 FUEL OIL AMBIENT 2-WAY OPEN 12 VAC - 1, 2 MOV-14PP03120 FUEL OIL SUPPLY TO GENERATORS 1 1/2 24 15 NO. 2 FUEL OIL AMBIENT 2-WAY OPEN 12 VAC - 1, 2
MOV-14PP03119B FUEL OIL TO FBT-14PP03103 1 1/2 24 15 NO. 2 FUEL OIL AMBIENT 2-WAY OPEN 12 VAC - 1, 2 MOV-14PP03119A FUEL OIL TO ICC500 TANK (FBT-14PP03103) 1 1/2 24 15 NO. 2 FUEL OIL AMBIENT 2-WAY OPEN 12 VAC - 1, 2 MOV-14PP03118 FUEL OIL FROM FOP-14PP03102 1 1/4 12 15 NO. 2 FUEL OIL AMBIENT 2-WAY OPEN 12 VAC 1 1, 2 MOV-14PP03117 FUEL OIL TO FOP-14PP03102 1 1/4 12 15 NO. 2 FUEL OIL AMBIENT 2-WAY OPEN 12 VAC 1 1, 2 MOV-14PP03116 FUEL OIL TO FOP-14PP03101 1 1/4 12 15 NO. 2 FUEL OIL AMBIENT 2-WAY OPEN 12 VAC - 1, 2 MOV-14PP03115 FUEL OIL FROM FOP-14PP03101 1 1/4 12 15 NO. 2 FUEL OIL AMBIENT 2-WAY OPEN 12 VAC - 1, 2
MOV-14PP03113B FUEL OIL SUPPLY TO DG-14PP61111 1 1/4 12 15 NO. 2 FUEL OIL AMBIENT 2-WAY OPEN 12 VAC - 1, 2 MOV-14PP03113A FUEL OIL SUPPLY TO DG-14PP61111 1 1/4 12 15 NO. 2 FUEL OIL AMBIENT 2-WAY OPEN 12 VAC - 1, 2 MOV-14PP03111B FUEL OIL SUPPLY TO DG-14PP61112 1 1/4 12 15 NO. 2 FUEL OIL AMBIENT 2-WAY OPEN 12 VAC 1 1, 2 MOV-14PP03111A FUEL OIL SUPPLY TO DG-14PP61112 1 1/4 12 15 NO. 2 FUEL OIL AMBIENT 2-WAY OPEN 12 VAC 1 1, 2 MOV-14PP03109B FUEL OIL SUPPLY TO DG-14PP61113 1 1/4 12 15 NO. 2 FUEL OIL AMBIENT 2-WAY OPEN 12 VAC 2 1, 2 MOV-14PP03109A FUEL OIL SUPPLY TO DG-14PP61113 1 1/4 12 15 NO. 2 FUEL OIL AMBIENT 2-WAY OPEN 12 VAC 2 1, 2 MOV-14PP03107B FUEL OIL SUPPLY TO DG-14PP61114 1 1/4 12 15 NO. 2 FUEL OIL AMBIENT 2-WAY OPEN 12 VAC 3 1, 2 MOV-14PP03107A FUEL OIL SUPPLY TO DG-14PP61114 1 1/4 12 15 NO. 2 FUEL OIL AMBIENT 2-WAY OPEN 12 VAC 3 1, 2 MOV-14PP03106 FUEL OIL RETURN TO FBT-14PP03102 2 30 15 NO. 2 FUEL OIL AMBIENT 2-WAY OPEN 12 VAC 1 1, 2 MOV-14PP03105 FUEL OIL RETURN TO FBT-14PP03101 2 30 15 NO. 2 FUEL OIL AMBIENT 2-WAY OPEN 12 VAC - 1, 2 MOV-14PP03104 FUEL OIL SUPPLY FROM FBT-14PP03102 1 1/2 24 15 NO. 2 FUEL OIL AMBIENT 2-WAY OPEN 12 VAC 1 1, 2 MOV-14PP03103 FUEL OIL SUPPLY FROM FBT-14PP03101 1 1/2 24 15 NO. 2 FUEL OIL AMBIENT 2-WAY OPEN 12 VAC - 1, 2
MOV-14PP03102B FUEL UNLOADING TO FBT-14PP03102 6 300 15 NO. 2 FUEL OIL AMBIENT 2-WAY OPEN 12 VAC 1 1, 2 MOV-14PP03102A FUEL UNLOADING TO FBT-14PP03102 6 300 15 NO. 2 FUEL OIL AMBIENT 2-WAY OPEN 12 VAC 1 1, 2 MOV-14PP03101B FUEL UNLOADING TO FBT-14PP03101 6 300 15 NO. 2 FUEL OIL AMBIENT 2-WAY OPEN 12 VAC - 1, 2 MOV-14PP03101A FUEL UNLOADING TO FBT-14PP03101 6 300 15 NO. 2 FUEL OIL AMBIENT 2-WAY OPEN 12 VAC - 1, 2
VALVE TAG UNIT SERVED VALVE SIZE (IN) DESIGN FLOW RATE
(GPM) MAX DP (FT HD) FLUID TYPE FLUID TEMP (°F) ACTION FAIL POSITION ELECTRICAL
BID OPTION NUMBER
(SEE SHEET
KEYNOTES)
REMARKS
MOTOR OPERATED VALVE SCHEDULE
01. THE FOLLOWING MECHANICAL ITEMS INCLUDE THE SCOPE
ASSOCIATED WITH OPTION ITEM #1 (APPLICABLE TO
MECHANICAL ITEMS WITHIN THE DASHED BOUNDARY ON
THIS DRAWING ONLY AND ASSOCIATED CONTROLS POINTS):
- PROVIDE BELLY OR DAY TANKS PUMPS FOP-14PP03105A
AND FOP-14PP03105B AND ASSOCIATED VALVE
MOV-14PP03111.
-PROVIDE FUEL OIL BULK TANK FBT-14PP03102, ASSOCIATED
VALVES MOV-14PP03117, MOV-14PP03118, MOV-14PP03104,
MOV-14PP03106, MOV-14PP03102 AND ASSOCIATED FUEL
POLISHER FP-14PP03102.
02. THE FOLLOWING MECHANICAL ITEMS INCLUDE THE SCOPE
ASSOCIATED WITH OPTION ITEM #2 (APPLICABLE TO
MECHANICAL ITEMS WITHIN THE DASHED BOUNDARY ON
THIS DRAWING ONLY AND ASSOCIATED CONTROLS POINT):
- PROVIDE BELLY OR DAY TANKS PUMPS FOP-14PP03104A
AND FOP-14PP03104B AND ASSOCIATED VALVE
MOV-14PP03109.
03. THE FOLLOWING MECHANICAL ITEMS INCLUDE THE SCOPE
ASSOCIATED WITH OPTION ITEM #3 (APPLICABLE TO
MECHANICAL ITEMS WITHIN THE DASHED BOUNDARY ON
THIS DRAWING ONLY AND ASSOCIATED CONTROLS POINTS):
- PROVIDE BELLY OR DAY TANKS PUMPS FOP-14PP03103A
AND FOP-14PP03103B AND ASSOCIATED VALVE
MOV-14PP03107.
SY
M
DE
SC
RI
PT
IO
N
DA
TE
AP
PR
14GI-M-001
14GI-M-008
Approved By
CAPT Troy Brown, JRM J4 via email
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P
AR
TM
E
N T
O F
TH
E
N A
VY
N
A
VA
L
FA
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
SY
S
TE
M
S C
O M
M A
N D
DRAWFORM REVISION: 25 AUGUST 2020
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
NA
VF
AC
P
AC
IF
IC
M
A K
AL
AP
A , H
A W
AI
I
AS NOTED
PR
O
JE
C
T
SI
TE
C
O M
M
AN
D C
EN
TE
R
N
AV
FA
C
P
AC
IF
IC
1812861
KYM
JC
Jacobs/B&V, A Joint Venture (Federal Services) 1003 Bishop Street Suite 1340 Honolulu, HI 96813
A/E Task Order No. N6274223F0324
AN
DE
RS
EN
A
IR
F O
RC
E
BA
SE
LJE
AWK/DMK
9/
/2
9:
:3
PM
P6
_1
_1 4P
P_ M
_d et ac he d.
rv t
14PP-M-703
PO
W
ER
P
LA
NT
ME
CH
AN
IC
AL
S
CH
ED
UL
ES
MAM
17324534
BJE THF
G
UA
M
PP
-M -7
FINAL DESIGN SUBMITTAL
3. PROVIDE WASTE TANK SIZE DETERMINED BY MANYFACTURER.
2. GEAR PUMP WITH INTERNAL PRESSURE RELIEF.
1. PACKAGED CONTROLS, FILTERS, AND COALESCER INCLUDED.
REMARKS:
FP-14PP03102 AT FUEL TANKS PACKAGED NO. 2 16 AMBIENT 50 1.5 1725 208 / 1 1 1, 2, 3 FP-14PP03101 AT FUEL TANKS PACKAGED NO. 2 16 AMBIENT 50 1.5 1725 208 / 1 - 1, 2, 3
HP RPM V / PH
EQUIPMENT TAG LOCATION TYPE FUEL OIL TYPE FLOW
(GPM)
TEMP
(°F)
HEAD
(PSI)
MOTOR DATA BID OPTION
NUMBER
(SEE SHEET
KEYNOTES)
REMARKS
FUEL POLISHER
4. FUEL UNLOADING PAD DETAILS ON SHEET 14ST-C-517
3. SEE C1/14PP-M-503 FOR FURTHER DETAIL
2. DETAILED PUMP DESIGN AND SELECTION SHALL BE BY GENERATOR MANUFACTURER. PUMPS SHALL BE SIZED AND PROVIDED BY MANUFACTURER.
1. INCLUDED WITH GENERATOR ENCLOSURE.
REMARKS:
FOP-14PP03108B ICC500 FUEL TANK FUEL OIL SUPPLY/BULK
RECIRCULATION SUBMERSIBLE TURBINE NO. 2 24 43 3/4 1800 208 / 1 - 3
FOP-14PP03108A ICC500 FUEL TANK FUEL OIL SUPPLY/BULK
RECIRCULATION SUBMERSIBLE TURBINE NO. 2 24 43 3/4 1800 208 / 1 - 3
FOP-14PP03107 FUEL UNLOADING
STATION FUEL UNLOADING STATION CENTRIFUGAL SELF
PRIMING NO. 2 300 102 20 1800 460 / 3 - -
FOP-14PP03106B BELLY TANK BELLY TANK RETURN POSITIVE DISPLACEMENT NO. 2 15 43 3/4 1800 208 / 1 - 1, 2
FOP-14PP03106A BELLY TANK BELLY TANK RETURN POSITIVE DISPLACEMENT NO. 2 15 43 3/4 1800 208 / 1 - 1, 2
FOP-14PP03105B BELLY TANK BELLY TANK RETURN POSITIVE DISPLACEMENT NO. 2 15 43 3/4 1800 208 / 1 1 1, 2
FOP-14PP03105A BELLY TANK BELLY TANK RETURN POSITIVE DISPLACEMENT NO. 2 15 43 3/4 1800 208 / 1 1 1, 2
FOP-14PP03104B BELLY TANK BELLY TANK RETURN POSITIVE DISPLACEMENT NO. 2 15 43 3/4 1800 208 / 1 2 1, 2
FOP-14PP03104A BELLY TANK BELLY TANK RETURN POSITIVE DISPLACEMENT NO. 2 15 43 3/4 1800 208 / 1 2 1, 2
FOP-14PP03103B BELLY TANK BELLY TANK RETURN POSITIVE DISPLACEMENT NO. 2 15 43 3/4 1800 208 / 1 3 1, 2
FOP-14PP03103A BELLY TANK BELLY TANK RETURN POSITIVE DISPLACEMENT NO. 2 15 43 3/4 1800 208 / 1 3 1, 2
FOP-14PP03102B BULK FUEL TANK FUEL OIL SUPPLY SUBMERSIBLE TURBINE NO. 2 24 43 3/4 1800 208 / 1 - 3 FOP-14PP03102A BULK FUEL TANK FUEL OIL SUPPLY SUBMERSIBLE TURBINE NO. 2 24 43 3/4 1800 208 / 1 - 3 FOP-14PP03101B BULK FUEL TANK FUEL OIL SUPPLY SUBMERSIBLE TURBINE NO. 2 24 43 3/4 1800 208 / 1 - 3 FOP-14PP03101A BULK FUEL TANK FUEL OIL SUPPLY SUBMERSIBLE TURBINE NO. 2 24 43 3/4 1800 208 / 1 - 3
HP RPM VOLTS / PHEQUIPMENT TAG LOCATION SERVICE PUMP TYPE FUEL OIL
TYPE
FLOW
(GPM)
HEAD
(FT)
MOTOR DATA BID OPTION
NUMBER
(SEE SHEET
KEYNOTES)
REMARKS
FUEL OIL PUMPS
14CC-A-101
SITE #
BUILDING ID DISCIPLINE
CONSECUTIVE NUMBERS
SITE #
SITE 01
SITE 02
SITE 14
BUILDING ID
AC - ACCESS CONTROL POINT
CC - COMMAND CENTER
FP - FIRE PUMP BUILDING
GI - GENERAL
PP - POWER PLANT
SF - SECURITY FORCE
ST - SITE
GENERAL SHEET NOTES
SHEET KEYNOTES
SHEET NAMING CONVENTION
3. PROVIDE WITH WEATHER RESISTANT COATING CAPABLE OF WITHSTANDING A MINIMUM OF 10,000 HOUR SALT SPRAY.
2. TANK CONTROLLER VOLTAGE: 208/1/60.
1. UNIT TO BE UL142 AND UL 2085 RATED. PROVIDE BALLISTIC TESTING BY MANUFACTURER AND SUBMIT CERTIFICATE WITH PRODUCT DATA.
REMARKS:
FBT-14PP03103 FUEL (NO. 2 DIESEL) DOUBLE WALL / HORIZ. CYLINDRICAL STORAGE TANK ICC 500 5,000 4,000 CARBON STEEL 1 ATM 167 X 102 DIA 66,000 - 1-3
FBT-14PP03102 FUEL (NO. 2 DIESEL) DOUBLE WALL / HORIZ. CYLINDRICAL STORAGE TANK 30,000 28,500 CARBON STEEL 1 ATM 635 X 138 DIA 66,000 1 1-3
FBT-14PP03101 FUEL (NO. 2 DIESEL) DOUBLE WALL / HORIZ. CYLINDRICAL STORAGE TANK 30,000 28,500 CARBON STEEL 1 ATM 635 X 138 DIA 66,000 - 1-3
EQUIPMENT TAG FLUID TANK TYPE / CONFIG. GROSS CAPACITY
(GALLONS)
USABLE CAPACITY
(GALLONS) MATERIAL DESIGN
PRESSURE
MAXIMUM
DIMENSIONS
(L x DIA.) (IN)
MAX DRY
WEIGHT (LBS)
BID OPTION
NUMBER
(SEE SHEET
KEYNOTES)
REMARKS
FUEL OIL TANK SCHEDULE
1. SEE 14PP-M-503/C3 FOR DETAIL
REMARKS:
FF-14PP03102 GEN YARD PACKAGED NO. 2 24 1.2 1
FF-14PP03101 GEN YARD PACKAGED NO. 2 24 1.2 1
EQUIPMENT TAG LOCATION TYPE FUEL OIL TYPE FLOW
(GPM)
PRESSURE
DROP (FT) REMARKS
FUEL FILTER
01. THE FOLLOWING MECHANICAL ITEMS INCLUDE THE SCOPE
ASSOCIATED WITH OPTION ITEM #1 (APPLICABLE TO
MECHANICAL ITEMS WITHIN THE DASHED BOUNDARY ON
THIS DRAWING ONLY AND ASSOCIATED CONTROLS POINTS):
- PROVIDE BELLY OR DAY TANKS PUMPS FOP-14PP03105A
AND FOP-14PP03105B AND ASSOCIATED VALVE
MOV-14PP03111.
-PROVIDE FUEL OIL BULK TANK FBT-14PP03102, ASSOCIATED
VALVES MOV-14PP03117, MOV-14PP03118, MOV-14PP03104,
MOV-14PP03106, MOV-14PP03102 AND ASSOCIATED FUEL
POLISHER FP-14PP03102.
02. THE FOLLOWING MECHANICAL ITEMS INCLUDE THE SCOPE
ASSOCIATED WITH OPTION ITEM #2 (APPLICABLE TO
MECHANICAL ITEMS WITHIN THE DASHED BOUNDARY ON
THIS DRAWING ONLY AND ASSOCIATED CONTROLS POINT):
- PROVIDE BELLY OR DAY TANKS PUMPS FOP-14PP03104A
AND FOP-14PP03104B AND ASSOCIATED VALVE
MOV-14PP03109.
03. THE FOLLOWING MECHANICAL ITEMS INCLUDE THE SCOPE
ASSOCIATED WITH OPTION ITEM #3 (APPLICABLE TO
MECHANICAL ITEMS WITHIN THE DASHED BOUNDARY ON
THIS DRAWING ONLY AND ASSOCIATED CONTROLS POINTS):
- PROVIDE BELLY OR DAY TANKS PUMPS FOP-14PP03103A
AND FOP-14PP03103B AND ASSOCIATED VALVE
MOV-14PP03107.
SY
M
DE
SC
RI
PT
IO
N
DA
TE
AP
PR
14GI-M-001
14GI-M-008
/14PP-M-503
14PP-M-503/
Approved By
CAPT Troy Brown, JRM J4 via email
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P
AR
TM
E
N T
O F
TH
E
N A
VY
N
A
VA
L
FA
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
SY
S
TE
M
S C
O M
M A
N D
DRAWFORM REVISION: 25 AUGUST 2020
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
NA
VF
AC
P
AC
IF
IC
M
A K
AL
AP
A , H
A W
AI
I
AS NOTED
PR
O
JE
C
T
SI
TE
C
O M
M
AN
D C
EN
TE
R
N
AV
FA
C
P
AC
IF
IC
1812861
KYM
JC
Jacobs/B&V, A Joint Venture (Federal Services) 1003 Bishop Street Suite 1340 Honolulu, HI 96813
A/E Task Order No. N6274223F0324
AN
DE
RS
EN
A
IR
F O
RC
E
BA
SE
LJE
AWK/DMK
9/
/2
9:
:5
PM
P6
_1
_1 4P
P_ M
_d et ac he d.
rv t
14PP-M-704
PO
W
ER
P
LA
NT
ME
CH
AN
IC
AL
S
CH
ED
UL
ES
MAM
17324535
MGP THF
G
UA
M
PP
-M -7
FINAL DESIGN SUBMITTAL
14CC-A-101
SITE #
BUILDING ID DISCIPLINE
CONSECUTIVE NUMBERS
SITE #
SITE 01
SITE 02
SITE 14
BUILDING ID
AC - ACCESS CONTROL POINT
CC - COMMAND CENTER
FP - FIRE PUMP BUILDING
GI - GENERAL
PP - POWER PLANT
SF - SECURITY FORCE
ST - SITE
GENERAL SHEET NOTES
SHEET NAMING CONVENTION
F. "CA-EXH-B" - CLEAN AGENT EXHAUST FROM ROOM B.
E. "CA-EXH-A" - CLEAN AGENT EXHAUST FROM ROOM A.
D. "CA-ISO-B" - CLEAN AGENT ISOLATION FOR ROOM B.
C. "CA-ISO-A" - CLEAN AGENT ISOLATION FOR ROOM A.
B. "UCC-ISO-AB" - UCC OVERRIDE TO ISOLATION ROOM A FROM ROOM B.
A. "DEFAULT" - DEFAULT SYSTEM OPERATION.
OPERATION MODES
4. MODULATING OPERATION AS DESCRIBED IN THE ASSOCIATED AHU SEQUENCE OF OPERATION.
3. MATERIAL REFERS TO BLADES AND FRAME. SHAFT AND LINKAGES SHALL BE STAINLESS STEEL IN ALL INSTANCES.
2. PROVIDE DAMPER SIZES CORRESPONDING TO THE CONNECTED DUCTWORK AS SHOWN ON THE PLAN DRAWINGS.
1. REFER TO PLANS AND SCHEMATICS FOR DAMPER LOCATION.
REMARKS
MOD-14PP41113 ISOLATION ROOM 103 MAKE-UP AIR PARALLEL V-GROOVE LOW-LEAK STAINLESS STEEL TWO-POSITION 24 / 1 / 60 CLOSED F A,B,C,D,E 1-3 MOD-14PP41112 ISOLATION ROOM 103 CLEAN AGENT EA PARALLEL V-GROOVE LOW-LEAK STAINLESS STEEL TWO-POSITION 24 / 1 / 60 CLOSED F A,B,C,D,E 1-3 MOD-14PP41111 ISOLATION ROOM 102 MAKE-UP AIR PARALLEL V-GROOVE LOW-LEAK STAINLESS STEEL TWO-POSITION 24 / 1 / 60 CLOSED E A,B,C,D,F 1-3 MOD-14PP41110 ISOLATION ROOM 102 CLEAN AGENT EA PARALLEL V-GROOVE LOW-LEAK STAINLESS STEEL TWO-POSITION 24 / 1 / 60 CLOSED E A,B,C,D,F 1-3 MOD-14PP41109 ISOLATION ROOM 102 SUPPLY AIR PARALLEL AIRFOIL STANDARD ALUMINUM TWO-POSITION 24 / 1 / 60 CLOSED A B,C,D,E,F 1-3 MOD-14PP41107 VAV CONTROL ROOM 103 SUPPLY AIR OPPOSED AIRFOIL STANDARD ALUMINUM MODULATING 24 / 1 / 60 OPEN N/A N/A 1-4 MOD-14PP41106 ISOLATION ROOM 103 TRANSFER AIR PARALLEL AIRFOIL LOW-LEAK ALUMINUM TWO-POSITION 24 / 1 / 60 CLOSED A B,C,D,E,F 1-3 MOD-14PP41105 VAV CONTROL ROOM 102 SUPPLY AIR OPPOSED AIRFOIL STANDARD ALUMINUM MODULATING 24 / 1 / 60 OPEN N/A N/A 1-4 MOD-14PP41104 ISOLATION ROOM 102 MAKE-UP AIR PARALLEL AIRFOIL LOW-LEAK STAINLESS STEEL TWO-POSITION 24 / 1 / 60 OPEN A C, E 1-3 MOD-14PP41103 ISOLATION ROOM 103 MAKE-UP AIR PARALLEL AIRFOIL LOW-LEAK STAINLESS STEEL TWO-POSITION 24 / 1 / 60 OPEN A D, F 1-3 MOD-14PP41102 ISOLATION ROOM 104 EXHAUST AIR PARALLEL AIRFOIL LOW-LEAK STAINLESS STEEL TWO-POSITION 24 / 1 / 60 CLOSED A D, F 1-3 MOD-14PP41101 ISOLATION ROOM 101 EXHAUST AIR PARALLEL AIRFOIL LOW-LEAK STAINLESS STEEL TWO-POSITION 24 / 1 / 60 CLOSED A C, E 1-3
ROOM/SYSTEM
ASSOC.
AIR
STREAM CONFIG. TYPE SEAL CONTROL TYPE V / PH / HZ FAIL OPEN CLOSED
EQUIPMENT TAG APPLICATION
SERVICE BLADE INFORMATION
MATERIAL
(NOTE 3)
ACTUATOR OPERATION MODES
REMARKS
MOTOR OPERATED DAMPER SCHEDULE
6. PERFORMANCE INDICATED IS FOR OPERATION WITH THE ASSOCIATED OUTDOOR UNIT, AND USING REFRIGERANT TYPE SCHEDULED FOR THAT UNIT.
5. COOLING COIL MUST HAVE 6 ROWS MINIMUM; MAXIMUM 8 FINS PER INCH.
4. DOUBLE WALL CASING WITH 316L STAINLESS STEEL INTERIOR LINER.
3. INCLUDE AN ADDITIONAL 0.5" DIRT ALLOWANCE FOR THE UNIT FILTER BANK.
2. HORIZONTAL, SUSPENDED FROM ROOF STRUCTURE, DUCTED INLET, FREE OUTLET.
1. PROVIDE SINGLE POINT POWER CONNECTION.
REMARKS:
MAU-14PP41102 500 0.5 ACCU-14PP41106 13.2 / 40.7 82.3 79.9 57.8 10.3 57.8 77 2 15 460/3/60 2" PLEAT 11 2" PLEAT 13 675 60"x45"x26" 1-6 MAU-14PP41101 500 0.5 ACCU-14PP41105 13.2 / 40.7 82.3 79.9 57.8 10.3 57.8 77 2 15 460/3/60 2" PLEAT 11 2" PLEAT 13 675 60"x45"x26" 1-6
CFM ESP
(IN WG)
DB
(°F)
WB
(°F) TYPE MERV TYPE MERV
CAPACITY
SENS/TOT
(MBH)
ENTERING LVG.
DB
(°F)
CAPACITY
(MBH)
ENT.
DB
(°F)
LVG.
DB
(°F)
MCA MOCP V / PH /
HZ
PRE-FILTER FINAL FILTEREQUIPMENT
TAG
FAN ASSOCIATED
OUTDOOR UNIT
DX COOLING COIL HOT GAS REHEAT COIL ELECTRICAL DATA FILTER
MAX
WEIGHT
(LBS)
MAX
DIMENSIONS
(INDOOR
UNIT)
(L x W x H)
REMARKS
MAKEUP AIR UNIT SCHEDULE
2. MODULE SIZE SHALL BE TYPICAL TO ALIGN WITH THE CORRESPONDING DUCT SIZE.
1. GRILLE IS INSTALLED ON THE END OF A DUCT. MATCH THE SIZE OF DUCT SHOWN ON THE PLAN DRAWINGS.
REMARKS:
TG-1 TRANSFER GRILLE WITH 3/4" BLADE SPACING, 35 DEGREE
DEFLECTION AND BLADE PARALLEL TO LONG DIMENSION NOTE 2 NOTE 1 SEE PLANS ALUMINUM WHITE DUCT 45 0.15 1, 2
RG-1 RETURN GRILLE WITH 3/4" BLADE SPACING, 35 DEGREE
DEFLECTION AND BLADE PARALLEL TO LONG DIMENSION NOTE 2 NOTE 1 SEE PLANS ALUMINUM WHITE DUCT 45 0.15 1, 2
SG-1 DOUBLE DEFLECTION SUPPLY GRILLE WITH 3/4" BLADE
SPACING. FRONT BLADES PARALLEL TO LONG DIMENSION NOTE 2 NOTE 1 SEE PLANS ALUMINUM WHITE DUCT 45 0.30 1, 2
MAX N.C. MAX APD
(IN WC)
EQUIPMENT TAG DESCRIPTION MODULE SIZE
(INCHES)
INLET CONNECTION
SIZE (IN)
FLOW RANGE
(CFM) MATERIAL FINISH MOUNTING
PERFORMANCE
REMARKS
DIFFUSER, REGISTER, & GRILLE SCHEDULE
SY
M
DE
SC
RI
PT
IO
N
DA
TE
AP
PR
14GI-M-001
14GI-M-008
Approved By
CAPT Troy Brown, JRM J4 via email
BT-YD
FILL-V-C
FILL-V-S
L-LL
L-L
L-H
L-HH
FOS-F
FOR-F
FPA-S
FPA-SS
FPB-S
FPB-SS
BT-T
BT-ST
BT-L
FPA-C FPB-C
FFP-O
FRV-S
FRV-C
M
FSV-S
FSV-C
M
FSP-O
FRP-O
EMR-BUT
M
FILL-V-C
FILL-V-S
SEQUENCE OF OPERATION: BULK FUEL TANK
PROVIDE EACH BULK STORAGE TANK WITH A FUEL LEVEL ALARM SYSTEM LOCATED AT THE LOCAL FUEL CONTROL PANEL.
INDICATOR LIGHTS FOR "LOW LEVEL" AND "LOW-LOW LEVEL" MUST ILLUMINATE WHEN LEVEL FALLS BELOW EACH RESPECTIVE SETPOINT.
INDICATOR LIGHTS FOR "HIGH LEVEL" AND "HIGH-HIGH LEVEL" MUST ILLUMINATE WHEN LEVEL RISES ABOVE EACH RESPECTIVE SETPOINT.
ANNUNCIATE ALARM WHEN LEVEL FALLS BELOW THE "LOW-LOW LEVEL" SETPOINT.
LEAK DETECTION: ANNUNCIATE ALARM AT THE CONTROL NETWORK FRONT-END WHENEVER FUEL IS DETECTED INSIDE THE BULK TANK INTERSTITIAL SPACE.
FUEL OIL FORWARDING TO DAY TANKS: TWO SUBMERSIBLE PUMPS (1 RUN; 1 STANDBY) CYCLE AS REQUIRED TO MAINTAIN THE LEVEL SETPOINT OF ALL DAY TANKS. THE PUMPS MUST ADDITIONALLY BE AUTOMATICALLY COORDINATED WITH THOSE OF ALL OTHER BULK FUEL TANKS AT THE SITE TO MAINTAIN A CONSISTENT FILL LEVEL ACROSS ALL BULK TANKS AT A GIVEN TIME. UPON A CALL FOR FUEL OIL SUPPLY FROM A DESIGNATED BULK TANK THE ASSOCIATED FUEL SUPPLY TO BELLY TANK VALVE SHALL BE OPENED. ONCE THE VALVE STATUS IS CONFIRMED OPEN, THE PUMP SHALL START. THE PUMP VFD SHALL BE RAMPED UP TO THE SPEED SET DURING COMMISSIONING, THAT PRODUCES THE FLOW SCHEDULED IN THE FUEL OIL PUMP SCHEDULE.DESIGNATION OF "RUN" AND "STANDBY" MUST AUTOMATICALLY ROTATE WITH EACH RUN CYCLE. THE STANDBY PUMP MUST AUTOMATICALLY ENGAGE UPON FAILURE TO PROVE FLOW AFTER 1 MINUTE (ADJ) FOLLOWING A COMMAND FOR FUEL FORWARDING FROM THE TANK. THIS MUST BE ACCOMPANIED BY A PUMP FAILURE ALARM ANNUNCIATED AT THE CONTROL NETWORK FRONT-END.
IF THE FUEL LEVEL IN THE BULK TANK EXCEEDS THE HIGH-HIGH LEVEL (L-HH) AN AUDIBLE AND VISUAL ALARM MUST BE INITIATED, THE MECHANICAL OVERFLOW PREVENTION VALVE MUST CLOSE, BOTH NORMALLY OPEN (MOV-A(NO)) AND NORMALLY CLOSED (MOV-B(NC)) VALVES MUST CLOSE UNTIL THE FUEL LEVEL
DROPS TO THE HIGH-LEVEL (L-H)
BACKPRESSURE CONTROL VALVE MAINTAINS CONSTANT PRESSURE IN THE FOS ALLOWING EXCESS FUEL TO RETURN BACK TO BULK TANK(S)REGARDLESS OF HOW MANY DAY TANKS ARE CALLING FOR FUEL.
SEE 02PP-M-611 FOR BPCV LOCATION.
TANK OUTER SHELL
TANK INNER SHELL
TANK INTERSTITIAL
FROM FUEL UNLOADING
14PP-M-803
FROM FUEL POLISHING
14PP-M-805
TO FUEL POLISHING
14PP-M-805
MOV-"B"
(NC)
PRESSURE
RELIEF VALVE
SET AT 50 PSI
EM
ER
GE
NC
Y
VE
NT
EM
ER
GE
NC
Y
CO
NT
AI
NM
EN
T
VE
NT
2" A
TM
OS
PH
ER
IC
V
EN
T
W
IT
H
IN
SE
T
SC
RE
EN
IN
SP
EC
TI
ON
LO
CA
L F
ILL
TO BELLY TANK
14PP-M-802
FROM BELLY TANK
14PP-M-802
FOR
FOS
EMERGENCY STOP BUTTON
(LOCATED ADJACENT TO BULK FUEL TANKS)
MOV (SEE 14PP-M-611 FOR
TAG NUMBERS)
MOV-"A"
(NO)
MOV (SEE 14PP-M-611 FOR
TAG NUMBERS)
OVERFILL
PREVENTION
DEVICE BA
MANUAL DRAIN
A. FOR GENERAL NOTES, LEGENDS, AND ABBREVIATIONS SEE
SHEETS 14GI-M-001 THROUGH 14GI-M-008.
AO: FBT-14PP03101 LEVEL
AO: FBT-14PP03102 LEVEL
BO: FUEL OIL TRANSFER
PUMP ON
AO: FBT-14PP03101 LEVEL
AO: FBT-14PP03102 LEVEL
BO: FUEL OIL TRANSFER
PUMP ON
FUEL OIL LEVEL INDICATING
AND ALARM PANEL LOCATED
NEAR FUEL BULK TANKS
(PROVIDE 2 EA PANELS:
PANEL A AND PANEL B-
PANEL B IS FULLY
REDUNDANT)
LAHH
LAH
90%
95%
PCMS-A PCMS-B
ALARM HORN
HS
SILENCE
FBT-14PP03101
LI YI
TRANSFER PUMP
FOP-14PP03101A ON
TRANSFER PUMP
FOP-14PP03101B ON
TRANSFER PUMP
FOP-14PP03102A ON
TRANSFER PUMP
FOP-14PP03102B ON
YI
YIYI
FFA
FRA
FUEL RETURN LEAK
FUEL FILL LEAK
FSA
FUEL SUPPLY LEAK
TO FUEL OFFLOADING AND
ALARM INDICATING PANEL
LOCATED NEAR PACKAGED
OFFLOADING SKID
LAHH
LAH
90%
95%
FBT-14PP03102
LI
FBCP-14PP0301A & FBCP-14PP03101
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P
AR
TM
E
N T
O F
TH
E
N A
VY
N
A
VA
L
FA
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
SY
S
TE
M
S C
O M
M A
N D
DRAWFORM REVISION: 25 AUGUST 2020
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
NA
VF
AC
P
AC
IF
IC
M
A K
AL
AP
A , H
A W
AI
I
AS NOTED
PR
O
JE
C
T
SI
TE
C
O M
M
AN
D C
EN
TE
R
N
AV
FA
C
P
AC
IF
IC
1812861
KYM
JC
Jacobs/B&V, A Joint Venture (Federal Services) 1003 Bishop Street Suite 1340 Honolulu, HI 96813
A/E Task Order No. N6274223F0324
AN
DE
RS
EN
A
IR
F O
RC
E
BA
SE
LJE
AWK/DMK
9/
/2
9:
:0
PM
P6
_1
_1 4P
P_ M
_d et ac he d.
rv t
14PP-M-801
PO
W
ER
P
LA
NT
ME
CH
AN
IC
AL
C
ON
TR
OL
S
MAM
17324536
BJE THF
G
UA
M
PP
-M -8
FINAL DESIGN SUBMITTAL
SCALE: NTSA1 MECHANICAL CONTROLS - FUEL BULK STORAGE TANK
1) SEE EI-900 SERIES SHEETS FOR SPECIFIC EQUIPMENT I/O POINTS.
NOTES:
BT-L BULK TANK LEVEL SENSOR 0-100% <__>
OTHER POINTS BT-T BULK TANK TEMPERATURE SENSOR <___> <___> F AI
FILL-V-B-C FILL MOTOR OPERATED VALVE COMMAND (MOV-B) OPEN/CLOSE BO
FILL-V-B-S FILL MOTOR OPERATED VALVE STATUS (MOV-B) OPEN/CLOSE BI
FILL-V-A-C FILL MOTOR OPERATED VALVE COMMAND (MOV-A) OPEN/CLOSE BO
FILL-V-A-S FILL MOTOR OPERATED VALVE STATUS (MOV-A) OPEN/CLOSE BI
L-L BULK TANK LEVEL SENSOR LOW LEVEL 20% ALM/NORMAL
L-H BULK TANK LEVEL SENSOR HIGH LEVEL 95% ALM/NORMAL
FRV-C FUEL RETURN FROM BELLY TANK VALVE COMMAND OPEN/CLOSE BO
FRV-S FUEL RETURN FROM BELLY TANK VALVE STATUS OPEN/CLOSE BI
FSV-C FUEL SUPPLY TO BELLY TANK VALVE COMMAND OPEN/CLOSE BO
FSV-S FUEL SUPPLY TO BELLY TANK VALVE STATUS OPEN/CLOSE BI
FPB-C BULK TANK PUMP SPEED COMMAND 0-100% <___> GPM AO
FPA-C BULK TANK PUMP SPEED COMMAND 0-100% <___> GPM AO
FPB-SS BULK TANK FUEL OIL SUPPLY PUMP B START/STOP ON/OFF BO
FPB-SS BULK TANK FUEL OIL SUPPLY PUMP B START/STOP ON/OFF BO
START / STOP
FPA-SS BULK TANK FUEL OIL SUPPLY PUMP A START/STOP ON/OFF BO
EMR-BUT EMERGENCY STOP BUTTON (SEE NOTE) ON/OFF BI
RST-BUT SYSTEM RESET BUTTON (FOR SAFETIES) ~ <__>
FPB-S BULK TANK FUEL OIL SUPPLY PUMP B STATUS ON/OFF BI
FPA-S BULK TANK FUEL OIL SUPPLY PUMP A STATUS ON/OFF BI
BT-ST BULK TANK SUPPLY TEMPERATURE <___> <___> F AI
BT-T-H BULK TANK TEMPERATURE SENSOR HIGH LIMIT <115 DEG F> ALM/NORMAL BI
L-LL BULK TANK LEVEL SENSOR LOW LOW LEVEL 15% ALM/NORMAL BI
L-HH BULK TANK LEVEL SENSOR HIGH HIGH LEVEL 98% ALM/NORMAL BI
FFP-O FUEL FILL CONTAINMENT PIPE OIL LEAK ALM/NORMAL BI
FRP-O FUEL RETURN CONTAINMENT PIPE OIL LEAK ALM/NORMAL BI
FSP-O FUEL SUPPLY CONTAINMENT PIPE OIL LEAK ALM/NORMAL BI
BT-YD INTERSTITIAL LEAK DETECTION SENSOR BULK TANK ALM/NORMAL BI
FOR-F BULK TANK RETURN PROOF OF FUEL FLOW ALM/NORMAL BI
PROOFS
SAFETIES
FOS-F SUPPLY PROOF OF FUEL FLOW ALM/NORMAL BI
FUNCTION NAME DESCRIPTION SETTING RANGE I/O TYPE
FUEL BULK TANK
14CC-A-101
SITE #
BUILDING ID DISCIPLINE
CONSECUTIVE NUMBERS
SITE #
SITE 01
SITE 02
SITE 14
BUILDING ID
AC - ACCESS CONTROL POINT
CC - COMMAND CENTER
FP - FIRE PUMP BUILDING
GI - GENERAL
PP - POWER PLANT
SF - SECURITY FORCE
ST - SITE
GENERAL SHEET NOTES
SHEET NAMING CONVENTION
CONTROLLER A (1 OF 2)
PROVIDE FULLY REDUNDANT
CONTROLLER B
SY
M
DE
SC
RI
PT
IO
N
DA
TE
AP
PR
14GI-M-001
14GI-M-008
14PP-M-611
14PP-M-611
14PP-M-802
14PP-M-802
14PP-M-803
14PP-M-805
14PP-M-805
Approved By
CAPT Troy Brown, JRM J4 via email
BTNK-YD
BTNK-T
BTNK-L-LL
BTNK-L-L
BTNK-L-H
BTNK-L-HH
BTNK-L
FOS-S
FOS-S
FOR-P1-C
FOR-P1-S
FOR-P1-SS
BTNK-FS-FBTNK-FO-FT
BTNK-FR-F
BTNK-ST
FOR-P2-SS
FOR-P2-S
FOR-P2-C
FOS-C
FOS-C
SEQUENCE OF OPERATION: GENERATOR BELLY TANK
PROVIDE EACH BELLY TANK WITH A FUEL LEVEL ALARM SYSTEM LOCATED AT THE LOCAL FUEL CONTROL PANEL.
INDICATOR LIGHTS FOR "LOW LEVEL" AND "LOW-LOW LEVEL" MUST ILLUMINATE WHEN LEVEL FALLS BELOW EACH RESPECTIVE SETPOINT.
INDICATOR LIGHTS FOR "HIGH LEVEL" AND "HIGH-HIGH LEVEL" MUST ILLUMINATE WHEN LEVEL RISES ABOVE EACH RESPECTIVE SETPOINT.
ANNUNCIATE ALARM WHEN LEVEL FALLS BELOW THE "LOW-LOW LEVEL" SETPOINT.
LEAK DETECTION: ANNUNCIATE ALARM AT THE CONTROL NETWORK FRONT-END WHENEVER FUEL IS DETECTED INSIDE THE BELLY TANK INTERSTITIAL SPACE.
FUEL OIL COOLERS MUST BE PROVIDED ON THE FUEL OIL RETURN LINE BETWEEN THE DIESEL ENGINE AND ITS RESPECTIVE BELLY TANK. A TEMPERATURE SWITCH PROVIDED ON THE FUEL OIL RETURN LINE. WHEN THE TEMPERATURE SWITCH SENSES A FUEL RETURN TEMPERATURE OF 115 DEG F (ADJ) OR HIGHER, THE FUEL COOLER MUST BE ENABLED. WHEN THE FUEL RETURN TEMPERATURE DROPS BELOW 105 DEG F THE FUEL COOLER MUST BE DISABLED.
WHEN THE BELLY TANK LEVEL REACHES THE LOW-LEVEL LIMIT (BTNK-L-L), THE NORMALLY CLOSED SOLENOID VALVE MOV-B(NC) IS ENERGIZED TO OPEN AND THE PRIMARY FORWARDING PUMPS AT THE BULK TANKS START. WHEN THE BELLY TANK HIGH LEVEL LIMIT (BTNK-L-H) IS REACHED THE NORMALLY CLOSED SOLENOID VALVE MUST BE DE-ENERGIZED TO CLOSE.
IF THE FUEL LEVEL IN THE BELLY TANK EXCEEDS THE HIGH-HIGH LEVEL (BTNK-L-HH) AN AUDIBLE AND VISUAL ALARM MUST BE INITIATED, THE MECHANICAL OVERFLOW PREVENTION VALVE MUST CLOSE, BOTH NORMALLY OPEN (MOV-A(NO)) AND NORMALLY CLOSED (MOV-B(NC)) SOLENOID VALVES MUST CLOSE, THE BULK TANK ISOLATION VALVES ON RETURN LINE MUST PROVE OPEN, AND THE ASSOCIATED PRIMARY RETURN PUMP STARTS UNTIL THE FUEL LEVEL DROPS TO THE HIGH-LEVEL (BTNK-L-H).
IF THE FUEL LEVEL IN THE TANK DROPS BELOW THE LOW-LOW LEVEL (BTNK-L-LL) AN AUDIBLE AND VISUAL ALARM IS INITIATED AND MUST INHIBIT THE RETURN PUMP OPERATION.
FUEL COOLER
FOS
FOR
FOS
FOR
AUTOMATIC
CLOSURE FUSIBLE
LINK FIRE RATED
VALVE (TYPICAL)
BELLY TANK OUTER
SHELL
BELLY TANK INNER
SHELL
BELLY TANK
INTERSTITIAL
FROM GENSETS
14PP-M-611
TO GENSETS
14PP-M-611
TO BULK TANKS
14PP-M-801
FROM BULK TANKS
14PP-M-801
MOV-A(NO)
MOV-B(NC)
MA
NU
AL
F
ILL
P
OI
NT
EM
ER
GE
NC
Y
VE
NT
OVERFILL
PREVENTION
DEVICE
EM
ER
GE
NC
Y
CO
NT
AI
NM
EN
T
VE
NT
2" A
TM
OS
PH
ER
IC
V
EN
T
W
IT
H
IN
SE
CT
S
CR
EE
N
MANUAL DRAIN
"PUMP RELIEF MAY BE INTERNAL
TO PUMP OR SEPARATE"
AUTOMATIC
CLOSURE FUSIBLE
LINK FIRE RATED
VALVE (TYPICAL)
MANUAL FCV
A. FOR GENERAL NOTES, LEGENDS, AND ABBREVIATIONS SEE
SHEETS 14GI-M-001 THROUGH 14GI-M-008.
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P
AR
TM
E
N T
O F
TH
E
N A
VY
N
A
VA
L
FA
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
SY
S
TE
M
S C
O M
M A
N D
DRAWFORM REVISION: 25 AUGUST 2020
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
NA
VF
AC
P
AC
IF
IC
M
A K
AL
AP
A , H
A W
AI
I
AS NOTED
PR
O
JE
C
T
SI
TE
C
O M
M
AN
D C
EN
TE
R
N
AV
FA
C
P
AC
IF
IC
1812861
KYM
JC
Jacobs/B&V, A Joint Venture…
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .