R-P693_Drawings_Final_Vol14.4_20241007.pdf
PDF 17 MB Posted
- Solicitation number
- N6274225R1301
About this file
This drawings file (R-P693_Drawings_Final_Vol14.4_20241007.pdf) is associated with a design-bid-build construction project for a Guam Defense Radar System Command Center in Joint Region Marianas, Guam. The project, solicited under N6274225R1301, includes construction of a command center, power generation facility, switchgear building, fuel storage facility, and entry control facility with an estimated value between $250-500 million.
The project requires specialized construction elements including seismic isolation bearings, a 150-foot galvanized steel antenna tower, security infrastructure for SSL-C and IESS systems, and complex concrete construction meeting ICC-500 Storm Shelter requirements. The contract includes five pre-priced options related to generators, fuel tanks, UPS systems, and B-side systems equipment. The RFP will be available on October 30, 2024, with a pre-proposal site visit scheduled for December 11, 2024. The contract has a 1,323-day completion period and is being procured on an unrestricted basis by NAVFAC Pacific using a best-value trade-off approach under NAICS code 236220.
View the file
Other files
Show 40 more
Latest 50 of 63 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
07-OCT-2024
Approved By
CAPT Troy Brown, JRM J4 via email
9/24/2024
10/17/2024
07-OCT-2024
CAPT Troy Brown, JRM J4 via email
10/04/2024
CAPT Troy Brown, JRM J4 via email
NORM ALT
Approved By
CAPT Troy Brown, JRM J4 via email
CAPT Troy Brown, JRM J4 via email
CAPT Troy Brown, JRM J4 via email
CAPT Troy Brown, JRM J4 via email
ST
A T
E OF
M I SSOU
R I
P R O
FE S SION A L E N
GI
N E E R
NUMBER
028892
RANDALL
SCOTT
KENT
10-4-2024
Approved By
CAPT Troy Brown, JRM J4 via email
10/04/202410111111111111111 /0000000000000000004/202020202022202020202020202020020020202022 242424242424244242424422422424242424244224441000000/0/0/0//0/0/000000000/0//0//00/004/4/444/4444/4//4//4/////4/4///20222020220202202202200202000000020202022220000024222
CAPT Troy Brown, JRM J4 via email
A. SEE SHEET 14GI-E-001 THROUGH 14GI-E-007 FOR GENERAL NOTES, ABBREVIATIONS, AND
LEGENDS.
14GI-E-001 14GI-E-007
10/04/2024
Approved By
CAPT Troy Brown, JRM J4 via email
LP-14CC61102
ELP-14CC61102XFMR-14CC61104
XFMR-14CC61103
XFMR-14CC61103A
XFMR-14CC61103B
XFMR-14CC61111
R14CC-4527B
R14CC-1014
R14CC-1017
R14CC-1005
R14CC-4527A
R14CC-1009
PP-14CC61111
UPP-14CC61102A
UPP-14CC61102B
DP-14CC61108
LC-102
PP-14CC61102
R14CC-1021
R14CC-4511R14CC-4512R14CC-4513
A. SEE SHEET 14GI-E-001 THROUGH 14GI-E-007 FOR GENERAL NOTES, ABBREVIATIONS, AND
LEGENDS.
B. SEE ONE LINE DIAGRAMS ON SHEETS 14CC-EP601 THROUGH 14CC-EP611 FOR MORE
INFORMATION.
C. SEE CIRCUIT SCHEDULES ON SHEETS 14CC-EP751 THROUGH 14CC-EP754 AND RACEWAY
SCHEDULES ON 14CC-EP771 THROUGH 14CC-EP774.
D. EQUIPMENT TAGS SHOWN ON PLANS ARE SHORTENED FOR SPACING AND LEGIBILITY AS
FOLLOWS: (PANEL TYPE)-14CC61(PANEL TAG NUMBER) IS SHORTENED TO (PANEL TYPE)-
(PANEL TAG NUMBER). EXAMPLE: EQUIPMENT TAG PP-14CC61102:10 IS SHOWN ON PLANS AS
PP-102.
E. CONDUIT PENETRATIONS AND ROUTING MAY DIFFER TO WHAT IS SHOWN ON PLAN BASED ON
EQUIPMENT SELECTION AND FIELD CONDITIONS. COORDINATE FINAL CONDUIT PENETRATIONS
WITH FINAL EQUIPMENT SELECTED.
14GI-E-001 14GI-E-007
14CC-EP601 14CC-EP611
14CC-EP771 14CC-EP774
14CC-EP751 14CC-EP754
10/04/2024
Approved By
CAPT Troy Brown, JRM J4 via email
PP-104
UPP-103
UPP-102
UPP-101
UPP-104
UPP-110
UPP-105
R14CC-1021
R14CC-4511 R14CC-4512
R14CC-4522
R14CC-4513
A. SEE SHEET 14GI-E-001 THROUGH 14GI-E-007 FOR GENERAL NOTES, ABBREVIATIONS, AND
LEGENDS.
B. SEE ONE LINE DIAGRAMS ON SHEETS 14CC-EP601 THROUGH 14CC-EP611 FOR MORE
INFORMATION.
C. SEE CIRCUIT SCHEDULES ON SHEETS 14CC-EP751 THROUGH 14CC-EP754 AND RACEWAY
SCHEDULES ON 14CC-EP771 THROUGH 14CC-EP774.
D. EQUIPMENT TAGS SHOWN ON PLANS ARE SHORTENED FOR SPACING AND LEGIBILITY AS
FOLLOWS: (PANEL TYPE)-14CC61(PANEL TAG NUMBER) IS SHORTENED TO (PANEL TYPE)-
(PANEL TAG NUMBER). EXAMPLE: EQUIPMENT TAG PP-14CC61102:10 IS SHOWN ON PLANS AS
PP-102.
E. CONDUIT PENETRATIONS AND ROUTING MAY DIFFER TO WHAT IS SHOWN ON PLAN BASED ON
EQUIPMENT SELECTION AND FIELD CONDITIONS. COORDINATE FINAL CONDUIT PENETRATIONS
WITH FINAL EQUIPMENT SELECTED.
14GI-E-001 14GI-E-007
14CC-EP601 14CC-EP611
14CC-EP771 14CC-EP774
14CC-EP751 14CC-EP754
10/04/2024
Approved By
CAPT Troy Brown, JRM J4 via email
SEE SHEET 14ST-ES105 FOR CONTINUATION SEE SHEET 14ST-ES105 FOR CONTINUATION
USWBD-14CC61101B
LVS-14CC61101B LVS-14CC61101A
UDP-14CC61101
DP-14CC61102
XFMR-14CC61101B XFMR-14CC61101A
ABT-14CC61108 ABT-14CC61107
CH-14CC41101
R14CC-4527B
R14CC-1014
R14CC-1017
R14CC-1005
R14CC-4527A
R14CC-1009 P14CC-1021
R14CC-4513
R14CC-4512
R14CC-4515
ELP-14CC61101
R14CC-1010
ABT-14CC61103
ABT-14CC61104
UMBC-14CC61101B 1200kW MAINT
BYP
R14CC-4511
01. 4' WIDE X 6" DEEP ALUMINUM CABLE TRAY
02. 6' X 4' X 2' NEMA 4X SS PULL BOX.
03. 4-INCH FLEXIBLE LIQUIDTIGHT ALUMINUM METALLIC CONDUIT WITH MV FEEDER TO
TRANSFORMER.
04. PROVIDE 120V 20A POWER CONNECTION FOR SECURITY DIB BOX.
A. SEE SHEET 14GI-E-001 THROUGH 14GI-E-007 FOR GENERAL NOTES, ABBREVIATIONS, AND
LEGENDS.
B. SEE ONE LINE DIAGRAMS ON SHEETS 14CC-EP601 THROUGH 14CC-EP611 FOR MORE
INFORMATION.
C. SEE CIRCUIT SCHEDULES ON SHEETS 14CC-EP751 THROUGH 14CC-EP754 AND RACEWAY
SCHEDULES ON 14CC-EP771 THROUGH 14CC-EP774.
D. EQUIPMENT TAGS SHOWN ON PLANS ARE SHORTENED FOR SPACING AND LEGIBILITY AS
FOLLOWS: (PANEL TYPE)-14CC61(PANEL TAG NUMBER) IS SHORTENED TO (PANEL TYPE)-
(PANEL TAG NUMBER). EXAMPLE: EQUIPMENT TAG PP-14CC61102:10 IS SHOWN ON PLANS AS
PP-102.
E. CONDUIT PENETRATIONS AND ROUTING MAY DIFFER TO WHAT IS SHOWN ON PLAN BASED ON
EQUIPMENT SELECTION AND FIELD CONDITIONS. COORDINATE FINAL CONDUIT PENETRATIONS
WITH FINAL EQUIPMENT SELECTED.
14GI-E-001 14GI-E-007
14CC-EP601 14CC-EP611
14CC-EP771 14CC-EP774
14CC-EP751 14CC-EP754
10/04/2024
Approved By
CAPT Troy Brown, JRM J4 via email
CH-14CC41104 CH-14CC41103 CH-14CC41102
UDP-14CC61103
R14CC-4522
R14CC-1010
R14CC-4523
SWBD-14CC61103A
SWBD-14CC61103B
A. SEE SHEET 14GI-E-001 THROUGH 14GI-E-007 FOR GENERAL NOTES, ABBREVIATIONS, AND
LEGENDS.
B. SEE ONE LINE DIAGRAMS ON SHEETS 14CC-EP601 THROUGH 14CC-EP611 FOR MORE
INFORMATION.
C. SEE CIRCUIT SCHEDULES ON SHEETS 14CC-EP751 THROUGH 14CC-EP754 AND RACEWAY
SCHEDULES ON 14CC-EP771 THROUGH 14CC-EP774.
D. EQUIPMENT TAGS SHOWN ON PLANS ARE SHORTENED FOR SPACING AND LEGIBILITY AS
FOLLOWS: (PANEL TYPE)-14CC61(PANEL TAG NUMBER) IS SHORTENED TO (PANEL TYPE)-
(PANEL TAG NUMBER). EXAMPLE: EQUIPMENT TAG PP-14CC61102:10 IS SHOWN ON PLANS AS
PP-102.
E. CONDUIT PENETRATIONS AND ROUTING MAY DIFFER TO WHAT IS SHOWN ON PLAN BASED ON
EQUIPMENT SELECTION AND FIELD CONDITIONS. COORDINATE FINAL CONDUIT PENETRATIONS
WITH FINAL EQUIPMENT SELECTED.
14GI-E-001 14GI-E-007
14CC-EP601 14CC-EP611
14CC-EP771 14CC-EP774
14CC-EP751 14CC-EP754
10/04/2024
Approved By
CAPT Troy Brown, JRM J4 via email
CH-14CC41101 CH-14CC41102 CH-14CC41103 CH-14CC41104
LEGENDS.
B. SEE SHEETS 14CC-EP112 THROUGH 14CC-EP115 FOR LOCATION OF FLOOR BOXES AND WIRING
DEVICES.
C. SEE SHEETS 14CC-T-T111 THROUGH 14CC-T-115 FOR ROUTING OF UNDER FLOOR
TELECOMMUNICATIONS PATHWAYS.
D. SEE SHEET 14CC-EP503 FOR APPLICABLE DETAILS AND SCHEDULES.
E. PROVIDE ALL HARDWARE ACCESSORIES, WHICH MAY INCLUDE, BUT ARE NOT LIMITED TO,
FITTINGS, SUPPORTS, DROPOUTS, SPLICE AND END PLATES, ETC. AS REQUIRED FOR A
COMPLETE CABLE TRAY SYSTEM INSTALLATION.
F. PROVIDE FLEXIBLE METAL CONDUIT TO ENCLOSE TC CABLE FOR FINAL CONNECTION TO
FLOOR BOX. FLEXIBLE RACEWAY MUST NOT EXCEED 3 FEET IN LENGTH.
14GI-E-001 14GI-E-007
14CC-EP112 14CC-EP115
14CC-EP503
10/04/2024
Approved By
CAPT Troy Brown, JRM J4 via email
XFMR-14CC61111
XFMR-14CC61103
XFMR-14CC61104
REU-A205
(TYP.)
XFMR-14CC61103B
XFMR-14CC61103A
TYP.
TYP.
A. SEE SHEET 14GI-E-001 THROUGH 14GI-E-007 FOR GENERAL NOTES, ABBREVIATIONS, AND
LEGENDS.
B. SEE SHEETS 14CC-EP112 THROUGH 14CC-EP115 FOR LOCATION OF FLOOR BOXES AND WIRING
DEVICES.
C. SEE SHEETS 14CC-T-111 THROUGH 14CC-T-115 FOR ROUTING OF UNDER FLOOR
TELECOMMUNICATIONS PATHWAYS.
D. SEE SHEETS 14CC-EP503 AND 14CC-EP504 FOR APPLICABLE CABLE TRAY DETAILS AND
SCHEDULES.
E. PROVIDE ALL HARDWARE ACCESSORIES, WHICH MAY INCLUDE, BUT ARE NOT LIMITED TO,
FITTINGS, SUPPORTS, DROPOUTS, SPLICE AND END PLATES, ETC. AS REQUIRED FOR A
COMPLETE CABLE TRAY SYSTEM INSTALLATION.
F. PROVIDE FLEXIBLE METAL CONDUIT TO ENCLOSE TC CABLE FOR FINAL CONNECTION TO
FLOOR BOX. FLEXIBLE RACEWAY MUST NOT EXCEED 3 FEET IN LENGTH.
01. PROVIDE STRAIGHT SECTION OF CABLE TRAY.
02. PROVIDE ELBOW JUNCTION CABLE TRAY FITTING.
03. PROVIDE TEE JUNCTION CABLE TRAY FITTING.
04. PROVIDE FOUR-WAY JUNCTION CABLE TRAY FITTING.
14GI-E-001 14GI-E-007
14CC-EP112 14CC-EP115
14CC-EP503 14CC-EP504
10/04/2024
Approved By
CAPT Troy Brown, JRM J4 via email
REU-L201REU-L202REU-A303
REU-A208REU-A209REU-A304
REU-A206REU-A207REU-A302
REU-A213REU-A214REU-A308
REU-A215REU-A216REU-A305
REU-A211REU-A212REU-A306
SPARE REUSPARE REUSPARE REU
REU-A201
REU-A202REU-A204
REU-A203
REU-A217
UCC
CCSOS
UPP-14CC61110
UPP-14CC61105
(TYP.)
UCC
(TYP)
A. SEE SHEET 14GI-E-001 THROUGH 14GI-E-007 FOR GENERAL NOTES, ABBREVIATIONS, AND
LEGENDS.
B. SEE SHEETS 14CC-EP112 THROUGH 14CC-EP115 FOR LOCATION OF FLOOR BOXES AND WIRING
DEVICES.
C. SEE SHEETS 14CC-T-111 THROUGH 14CC-T-115 FOR ROUTING OF UNDER FLOOR
TELECOMMUNICATIONS PATHWAYS.
D. SEE SHEETS 14CC-EP503 AND 14CC-EP504 FOR APPLICABLE CABLE TRAY DETAILS AND
SCHEDULES.
E. PROVIDE ALL HARDWARE ACCESSORIES, WHICH MAY INCLUDE, BUT ARE NOT LIMITED TO,
FITTINGS, SUPPORTS, DROPOUTS, SPLICE AND END PLATES, ETC. AS REQUIRED FOR A
COMPLETE CABLE TRAY SYSTEM INSTALLATION.
F. PROVIDE FLEXIBLE METAL CONDUIT TO ENCLOSE TC CABLE FOR FINAL CONNECTION TO
FLOOR BOX. FLEXIBLE RACEWAY MUST NOT EXCEED 3 FEET IN LENGTH.
01. PROVIDE STRAIGHT SECTION OF CABLE TRAY.
02. PROVIDE ELBOW JUNCTION CABLE TRAY FITTING.
03. PROVIDE TEE JUNCTION CABLE TRAY FITTING.
04. PROVIDE FOUR-WAY JUNCTION CABLE TRAY FITTING.
14GI-E-001 14GI-E-007
14CC-EP112 14CC-EP115
14CC-EP503 14CC-EP504
10/04/2024
Approved By
CAPT Troy Brown, JRM J4 via email
XFMR-14CC61101AXFMR-14CC61101B
SABT-14CC61102
(TYP.)
TYP.
TYP.
R14CC-4517A
R14CC-4515BR14CC-4521A
R14CC-4527A
R14CC-4516B
A. SEE SHEET 14GI-E-001 THROUGH 14GI-E-007 FOR GENERAL NOTES, ABBREVIATIONS, AND
LEGENDS.
B. SEE SHEETS 14CC-EP112 THROUGH 14CC-EP115 FOR LOCATION OF FLOOR BOXES AND WIRING
DEVICES.
C. SEE SHEETS 14CC-T-111 THROUGH 14CC-T-115 FOR ROUTING OF UNDER FLOOR
TELECOMMUNICATIONS PATHWAYS.
D. SEE SHEETS 14CC-EP503 AND 14CC-EP504 FOR APPLICABLE CABLE TRAY DETAILS AND
SCHEDULES.
E. PROVIDE ALL HARDWARE ACCESSORIES, WHICH MAY INCLUDE, BUT ARE NOT LIMITED TO,
FITTINGS, SUPPORTS, DROPOUTS, SPLICE AND END PLATES, ETC. AS REQUIRED FOR A
COMPLETE CABLE TRAY SYSTEM INSTALLATION.
F. PROVIDE FLEXIBLE METAL CONDUIT TO ENCLOSE TC CABLE FOR FINAL CONNECTION TO
FLOOR BOX. FLEXIBLE RACEWAY MUST NOT EXCEED 3 FEET IN LENGTH.
01. PROVIDE STRAIGHT SECTION OF CABLE TRAY.
02. PROVIDE ELBOW JUNCTION CABLE TRAY FITTING.
03. PROVIDE TEE JUNCTION CABLE TRAY FITTING.
14GI-E-001 14GI-E-007
14CC-EP112 14CC-EP115
14CC-EP503 14CC-EP504
10/04/2024
Approved By
CAPT Troy Brown, JRM J4 via email
REU-A301REU-A210REU-A307
XFMR-14CC61110XFMR-14CC61109
SABT-14CC61104
SABT-14CC61103
XFMR-14CC61108DP-14CC61107B DP-14CC61107A
UPP-14CC61107 UPP-14CC61109
UDP-14CC61103
UDP-14CC61102
(TYP.)
TYP.
TYP.
A. SEE SHEET 14GI-E-001 THROUGH 14GI-E-007 FOR GENERAL NOTES, ABBREVIATIONS, AND
LEGENDS.
B. SEE SHEETS 14CC-EP112 THROUGH 14CC-EP115 FOR LOCATION OF FLOOR BOXES AND WIRING
DEVICES.
C. SEE SHEETS 14CC-T-111 THROUGH 14CC-T-115 FOR ROUTING OF UNDER FLOOR
TELECOMMUNICATIONS PATHWAYS.
D. SEE SHEETS 14CC-EP503 AND 14CC-EP504 FOR APPLICABLE DETAILS AND SCHEDULES.
E. PROVIDE ALL HARDWARE ACCESSORIES, WHICH MAY INCLUDE, BUT ARE NOT LIMITED TO,
FITTINGS, SUPPORTS, DROPOUTS, SPLICE AND END PLATES, ETC. AS REQUIRED FOR A
COMPLETE CABLE TRAY SYSTEM INSTALLATION.
F. PROVIDE FLEXIBLE METAL CONDUIT TO ENCLOSE TC CABLE FOR FINAL CONNECTION TO
FLOOR BOX. FLEXIBLE RACEWAY MUST NOT EXCEED 3 FEET IN LENGTH.
01. PROVIDE STRAIGHT SECTION OF CABLE TRAY.
02. PROVIDE ELBOW JUNCTION CABLE TRAY FITTING.
03. PROVIDE TEE JUNCTION CABLE TRAY FITTING.
14GI-E-001 14GI-E-007
14CC-EP112 14CC-EP115
14CC-EP503 14CC-EP504
10/04/2024
Approved By
CAPT Troy Brown, JRM J4 via email
OPTION ITEM #4
OPTION ITEM #2
A. SEE SHEET 14GI-E-001 THROUGH 14GI-E-007 FOR GENERAL NOTES, ABBREVIATIONS, AND
LEGENDS.
B. REFER TO SHEET 14CC-EP405 AND 14CC-EP406 FOR OPTION ITEMS SCOPE OF WORK.
14GI-E-001 14GI-E-007
14CC-EP405 14CC-EP406
10/04/2024
Approved By
CAPT Troy Brown, JRM J4 via email
WP
VAV-14CC41104
VAV-14CC41101
VAV-14CC41103
GFCI
VAV-14CC41105
VAV-14CC41106
GFCI
GFCI
GFCI
GFCI
VAV-14CC41102
PP-102:16 PP-102:16
PP-103:10
PP-102:16
PP-102:16
PP-102:19 PP-102:19
PP-103:8
PP-102:19
PP-102:19
PP-102:24 PP-102:24
PP-111:8
PP-103:1PP-102:24
PP-102:24
PP-102:31
PP-102:31 PP-102:31
PP-103:9
PP-102:15
PP-102:15
PP-103:9
PP-103:9
PP-103:9PP-102:31
PP-103:9 PP-103:9
PP-102:12
PP-102:8
PP-102:8
PP-102:8
PP-102:8PP-102:8
PP-102:12
PP-102:12
PP-102:12 PP-102:27PP-102:27
PP-102:27
PP-102:27
PP-102:25
PP-102:27
PP-102:25
PP-111:4
PP-103:11
PP-102:28
PP-102:18
PP-102:28
PP-103:12
PP-102:28
PP-102:18
PP-102:18
PP-102:18
PP-103:11
PP-103:11 PP-103:11
PP-103:11
PP-102:22
PP-102:22
PP-102:22
PP-111:5
PP-102:22
PP-102:22
PP-103:13
PP-103:18
PP-103:15
PP-103:16
PP-103:11
PP-103:3
PP-103:14
PP-103:11
PP-102:23
PP-102:23
PP-102:23
PP-102:23
PP-102:5
PP-102:5
PP-102:5
PP-102:5PP-102:5 PP-102:9 PP-102:9
PP-102:9
PP-102:9
PP-102:9
PP-102:9
PP-111:3
PP-102:23
PP-102:16
PP-102:22
PP-111:10
SPECIAL USE SPACE BOUNDARY
S
S
S S S
S
S
SS
SS S
S
S
PP-111:9
S
S S
S
S S
SS
S S
SS
PP-103:17
S S
S
S
S
S S
S
S S
S SS
S
S
S
S S
S
S
S
S S
S
S
S
S
PP-103:6
PP-103:19
PP-103:21 PP-103:21 PP-103:21
PP-103:23 PP-103:23 PP-103:23
PP-102:31
S
DP-108:2,4,6
PP-102:28
PP-102:28
S
S
PP-102:2PP-102:2
S
PP-102:31S
PP-102:27
WP/GFCI
WS-118-01 WS-118-02 WS-118-03
WS-118-06WS-118-05WS-118-04
PP-103:25
TP-14CC12101
UPP-105:6
UPP-105:6
UPP-105:4
UPP-105:4
UPP-105:4
A. SEE SHEET 14GI-E-001 THROUGH 14GI-E-007 FOR GENERAL NOTES, ABBREVIATIONS, AND
LEGENDS.
B. CIRCUITING TAGS SHOWN ON PLANS ARE SHORTENED FOR SPACING AND LEGIBILITY AS
FOLLOWS: (PANEL TYPE)-14CC61(PANEL TAG NUMBER):(CIRCUIT NUMBER) IS SHORTENED TO
(PANEL TYPE)-(PANEL TAG NUMBER):(CIRCUIT NUMBER). EXAMPLE: CIRCUIT TAG
PP-14CC61102:10 IS SHOWN ON PLANS AS PP-102:10.
C. RECEPTACLE AND ASSOCIATED RACEWAY MUST BE SURFACE MOUNTED ALONG THE
BOUNDARY OF THE RF SHIELD IN THE SPECIAL USE SPACE (SUS). PENETRATION OF RF SHIELD
IS NOT PERMITTED AT THIS LOCATION.
D. ELECTRICAL DEVICES AND RACEWAY ALONG THE PERIMETER ARE TO BE SURFACE-MOUNTED
FOR INSPECTION PURPOSES AND TO AVOID DAMAGE OF THE RF-SHIELD.
E. UTILITIES SERVICING AREAS OTHER THAN THE SUS SPACE MUST NOT TRANSIT THE SUS SPACE
VOLUME UNLESS MITIGATED WITH AO APPROVAL.
F. REFER TO INTERIOR PLANS FOR EXACT WORKSTATION FLOOR BOX LOCATIONS.
01. PROVIDE 120V 20A POWER CONNECTION FOR SECURITY DIB BOX.
02. PROVIDE 120V 20A POWER CONNECTION FOR TRAP PRIMER. REFER TO MECHANICAL
PLANS FOR EXACT LOCATION.
14GI-E-001 14GI-E-007
10/04/2024
Approved By
CAPT Troy Brown, JRM J4 via email
VAV-14CC41110
VAV-14CC41111
VAV-14CC41109
GFCI
GFCI
GFCI
GFCI
GFCI
GFCI
PP-102:27 PP-102:30 PP-102:30
PP-111:16,18,20PP-103:7
PP-102:30
PP-102:30
PP-102:30
PP-102:30
PP-102:25PP-102:25
PP-102:25
PP-103:2
PP-102:25
PP-102:21
PP-102:10 PP-102:10
PP-102:21
PP-102:10
PP-102:17
PP-102:17
PP-102:21
PP-102:17
PP-102:6
PP-102:6
UPP-102:10
PP-102:6 UPP-102:10
UPP-102:14
UPP-102:2
UPP-102:2
UPP-102:9
UPP-102:9
PP-111:7
UPP-102:9
UPP-102:2
UPP-102:1PP-102:21
PP-102:14
PP-102:11
PP-102:11
PP-102:11
PP-102:14
PP-102:14
PP-102:14
PP-102:4
PP-102:4
PP-102:20
PP-111:6
PP-104:7
PP-111:15
PP-104:6
PP-102:21
PP-102:6
PP-111:19
UPP-105:7
UPP-102:8
UPP-102:12
S
S
S
S
PP-102:7
S
S
S
S
SS
S
VAV-14CC41114B
VAV-14CC41114C
S
GFCI
GFCI
PP-102:10
PP-102:17
S S
S
PP-102:4
PP-102:4
PP-102:4
S S
S
PP-102:7 PP-102:7
PP-102:7
S
S
S
S
S
PP-102:20
PP-102:20
PP-102:26
PP-102:26
PP-102:26
PP-103:4
PP-103:5
PP-102:1
GFCI
PP-111:28,30,32
UCC
UCC
CCSOS
EF-14CC41101
PP-102:2PP-102:2PP-102:2
PP-104:18
WP/GFCI
WP/GFCI
UPP-102:4
UPP-102:5
(TYP.)
REU-A217
WS-105-01 WS-105-02 WS-105-03
WS-105-04
WS-105-05
WS-106-01
WS-106-02
WS-106-03
WS-106-04
WS-106-05
WS-106-06
UPP-102:33
UPP-102:34
UPP-102:35
EF-14CC41107
PP-111:12
PP-103:26
TP-14CC12102
UPP-105:7
UPP-105:6
UPP-105:9
VFD PP-111:33,35
UPP-105:15
A. SEE SHEET 14GI-E-001 THROUGH 14GI-E-007 FOR GENERAL NOTES, ABBREVIATIONS, AND
LEGENDS.
B. CIRCUITING TAGS SHOWN ON PLANS ARE SHORTENED FOR SPACING AND LEGIBILITY AS
FOLLOWS: (PANEL TYPE)-14CC61(PANEL TAG NUMBER):(CIRCUIT NUMBER) IS SHORTENED TO
(PANEL TYPE)-(PANEL TAG NUMBER):(CIRCUIT NUMBER). EXAMPLE: CIRCUIT TAG
PP-14CC61102:10 IS SHOWN ON PLANS AS PP-102:10.
C. REFER TO INTERIOR PLANS FOR EXACT WORKSTATION FLOOR BOX LOCATIONS.
01. PROVIDE CONNECTION FOR PERIMETER LIGHTING LUMINAIRES TO SECURITY
CONTACTOR PANEL. SEE DETAIL A1 ON SHEET 14ST-EL501 FOR FURTHER INFORMATION.
02. PROVIDE 120V 1PH POWER CONNECTION FOR SECURITY DIB BOX.
03. JUNCTION BOX FOR ADA DOOR SWITCH. REFER TO ARCHITECTURAL DOOR HARDWARE
SPECIFICATION 08 71 00.00 14 FOR ADA SWITCH REQUIREMENTS. PROVIDE DOOR
SWITCH CONTROL CIRCUITS FROM EACH SWITCH BOX TO THE DOOR OPERATOR PER
MANUFACTURER'S REQUIREMENTS.
04. PROVIDE 120V 1PH POWER CONNECTION FOR TRAP PRIMER. REFER TO MECHANICAL
PLANS FOR EXACT LOCATION.
05. PROVIDE 120V 1PH POWER CONNECTION FOR LAND MOBILE RADIO. REFER TO TELECOM
PLANS FOR EXACT LOCATION.
TYP.
14GI-E-001 14GI-E-007
10/04/2024
Approved By
CAPT Troy Brown, JRM J4 via email
PP-104:22
PP-104:22 PP-104:22
PP-104:22
SPECIAL USE SPACE BOUNDARY
CAV-14CC41123 PP-110:9
XFMR-14CC61101AXFMR-14CC61101B
OPTION ITEM #5
OPTION ITEM #4
WP/GFCI
UPP-105:10
UPP-105:13
A. SEE SHEET 14GI-E-001 THROUGH 14GI-E-007 FOR GENERAL NOTES, ABBREVIATIONS, AND
LEGENDS.
B. CIRCUITING TAGS SHOWN ON PLANS ARE SHORTENED FOR SPACING AND LEGIBILITY AS
FOLLOWS: (PANEL TYPE)-14CC61(PANEL TAG NUMBER):(CIRCUIT NUMBER) IS SHORTENED TO
(PANEL TYPE)-(PANEL TAG NUMBER):(CIRCUIT NUMBER). EXAMPLE: CIRCUIT TAG
PP-14CC61102:10 IS SHOWN ON PLANS AS PP-102:10.
C. RECEPTACLE AND ASSOCIATED RACEWAY MUST BE SURFACE MOUNTED ALONG THE
BOUNDARY OF THE RF SHIELD IN THE SPECIAL USE SPACE (SUS). PENETRATION OF RF SHIELD
IS NOT PERMITTED AT THIS LOCATION.
D. ELECTRICAL DEVICES AND RACEWAY ALONG THE PERIMETER ARE TO BE SURFACE-MOUNTED
FOR INSPECTION PURPOSES AND TO AVOID DAMAGE OF THE RF-SHIELD.
E. UTILITIES SERVICING AREAS OTHER THAN THE SUS SPACE MUST NOT TRANSIT THE SUS
VOLUME UNLESS MITIGATED WITH AO APPROVAL.
F. ELECTRICAL UTILITIES MUST ENTER THE SUS SPACE VOLUME AT A SINGLE POINT.
G. ALL METALLIC CONDUIT PENETRATIONS AT THE SECURE BOUNDARY PERIMETER MUST BE
SEALED WITH AN ACOUSTICAL FOAM OR SEALANT FINISH TO MITIGATE ACOUSTIC EMANATION
IN ACCORDANCE WITH ICD-705.
01. PROVIDE 120V 1PH POWER CONNECTION FOR SECURITY DIB BOX.
02. OPTION ITEM #5:
REFER TO SHEETS 14CC-EP605 FOR FOR OPTION ITEM #5 SCOPE OF WORK.
03. OPTION ITEM #4:
REFER TO SHEETS 14CC-EP405 FOR FOR OPTION ITEM #4 SCOPE OF WORK
14GI-E-001 14GI-E-007
14CC-EP405
14CC-EP605
10/04/2024
Approved By
CAPT Troy Brown, JRM J4 via email
WP/GFCI
PP-110:5
PP-104:22
PP-104:23
PP-104:23
PP-104:23
PP-104:23
PP-104:6 PP-104:6PP-104:7
PP-104:6
VAV-14CC41116
VAV-14CC41117 VAV-14CC41114D
PP-110:10
PP-110:14
PP-110:12
S
S
S
S
S
S
PP-104:6
S
UPP-105:9
UPP-105:9
UPP-105:8
A. SEE SHEET 14GI-E-001 THROUGH 14GI-E-007 FOR GENERAL NOTES, ABBREVIATIONS, AND
LEGENDS.
B. CIRCUITING TAGS SHOWN ON PLANS ARE SHORTENED FOR SPACING AND LEGIBILITY AS
FOLLOWS: (PANEL TYPE)-14CC61(PANEL TAG NUMBER):(CIRCUIT NUMBER) IS SHORTENED TO
(PANEL TYPE)-(PANEL TAG NUMBER):(CIRCUIT NUMBER). EXAMPLE: CIRCUIT TAG
PP-14CC61102:10 IS SHOWN ON PLANS AS PP-102:10.
14GI-E-001 14GI-E-007
10/04/2024
Approved By
CAPT Troy Brown, JRM J4 via email
DP-106B
LEGENDS.
14GI-E-001 14GI-E-007
10/04/2024
Approved By
CAPT Troy Brown, JRM J4 via email
UPP-103B
UPP-103A
XFMR-14CC61103B
XFMR-14CC61111
XFMR-14CC61103
XFMR-14CC61103A
XFMR-14CC61104 LP-102
PP-102
PP-111
UPP-102A
ELP-102
UPP-102B
DP-108
R14CC-1016
R14CC-1019
PP-103
R14CC-1033
R14CC-1032
LC-102
R14CC-4529A
R14CC-4529B
UPP-101B
UPP-101A
R14CC-4530B
R14CC-4530A
A. SEE SHEET 14GI-E-001 THROUGH 14GI-E-007 FOR GENERAL NOTES, ABBREVIATIONS, AND
LEGENDS.
B. SEE SHEETS 14CC-EP112 THROUGH 14CC-EP115 FOR LOCATION OF FLOOR BOXES AND WIRING
DEVICES.
C. SEE SHEETS 14CC-T-111 THROUGH 14CC-T-115 FOR ROUTING OF UNDER FLOOR
TELECOMMUNICATIONS PATHWAYS.
D. SEE SHEETS 14CC-EP503 AND 14CC-EP504 FOR APPLICABLE DETAILS AND SCHEDULES.
E. PROVIDE ALL HARDWARE ACCESSORIES, WHICH MAY INCLUDE, BUT ARE NOT LIMITED TO,
FITTINGS, SUPPORTS, DROPOUTS, SPLICE AND END PLATES, ETC. AS REQUIRED FOR A
COMPLETE CABLE TRAY SYSTEM INSTALLATION.
F. PROVIDE FLEXIBLE METAL CONDUIT TO ENCLOSE TC CABLE FOR FINAL CONNECTION TO
FLOOR BOX. FLEXIBLE RACEWAY MUST NOT EXCEED 3 FEET IN LENGTH.
14GI-E-001 14GI-E-007
14CC-EP112 14CC-EP115
14CC-EP503 14CC-EP504
10/04/2024
Approved By
CAPT Troy Brown, JRM J4 via email
PP-104
UPP-103
UPP-102
UPP-101
UPP-104
UINV-14CC61101A
UPP-105
UPP-110
A. SEE SHEET 14GI-E-001 THROUGH 14GI-E-007 FOR GENERAL NOTES, ABBREVIATIONS, AND
LEGENDS.
B. SEE SHEETS 14CC-EP112 THROUGH 14CC-EP115 FOR LOCATION OF FLOOR BOXES AND WIRING
DEVICES.
C. SEE SHEETS 14CC-T-111 THROUGH 14CC-T-115 FOR ROUTING OF UNDER FLOOR
TELECOMMUNICATIONS PATHWAYS.
D. SEE SHEETS 14CC-EP503 AND 14CC-EP504 FOR APPLICABLE DETAILS AND SCHEDULES.
E. PROVIDE ALL HARDWARE ACCESSORIES, WHICH MAY INCLUDE, BUT ARE NOT LIMITED TO,
FITTINGS, SUPPORTS, DROPOUTS, SPLICE AND END PLATES, ETC. AS REQUIRED FOR A
COMPLETE CABLE TRAY SYSTEM INSTALLATION.
F. PROVIDE FLEXIBLE METAL CONDUIT TO ENCLOSE TC CABLE FOR FINAL CONNECTION TO
FLOOR BOX. FLEXIBLE RACEWAY MUST NOT EXCEED 3 FEET IN LENGTH.
14GI-E-001 14GI-E-007
14CC-EP112 14CC-EP115
14CC-EP503 14CC-EP504
10/04/2024
Approved By
CAPT Troy Brown, JRM J4 via email
UMBC-14CC61102A 400kW
MAINT BYP
UMBC-14CC61101A 1200kW MAINT
BYP UPS-14CC61101A
EUPS-14CC61101
UPS-14CC61102A
DP-14CC61102
UPS-14CC61102B
UPS-14CC61101B
UMBC-14CC61101B 1200kW MAINT
BYP
UMBC-14CC61102B 400kW
MAINT BYP
USWBD-14CC61101B
AB
T-1
4C C6
04 ABT-14CC61108 ABT-14CC61107
SA
BT
-14
CC
RF-14CC61101A
RF-14CC61101B
XFMR-14CC61107
PP-105
XF
MR
-14
CC
2B
XF
MR
-14
CC
XF
MR
-14
CC
2A
UDP-101B
ABT-14CC61101
SABT-14CC61101
ABT-14CC61102
XF
MR
-14
CC
XF
MR
-14
CC
XF
MR
-14
CC
DP-101
UD
P-1
A
PP-14CC61101
LP-14CC61101
UDP-14CC61101
XFMR-14CC61104A
UPP-104A
LC-101
ABT-14CC61103
ELP-101
USWBD-14CC61101A
R14CC-1002A
R14CC-1007B R14CC-1006A
R14CC-1007B
R14CC-1007A
R14CC-1009A
R14CC-1012A
R14CC-1002B
R14CC-1003
R14CC-1011
R14CC-1006
R14CC-1013
R14CC-1020
R14CC-1007
R14CC-4502A
R14CC-4504B R14CC-4504A
R14CC-4522B
R14CC-4523B R14CC-4523A
R14CC-4522A
R14CC-4509
R14CC-4510
R14CC-1004
R14CC-1020B
R14CC-1012
R14CC-1022
R14CC-1008A
R14CC-1003A
R14CC-1029
R14CC-1024
R14CC-4517A
R14CC-4512A
R14CC-4508A
R14CC-4507A
UPP-101B
UPP-101A
R14CC-1015A
R14CC-4526B
LVS-14CC61101B LVS-14CC61101A
R14CC-4528A
R14CC-4534A
R14CC-4534B
R14CC-4530A
R14CC-1006B
R14CC-4517B
R14CC-4602
R14CC-1020A
R14CC-1019B
R14CC-1019A
R14CC-4532B
R14CC-1009B
R14CC-1002
A. SEE SHEET 14GI-E-001 THROUGH 14GI-E-007 FOR GENERAL NOTES, ABBREVIATIONS, AND
LEGENDS.
B. SEE SHEETS 14CC-EP112 THROUGH 14CC-EP115 FOR LOCATION OF FLOOR BOXES AND WIRING
DEVICES.
C. SEE SHEETS 14CC-T-111 THROUGH 14CC-T-115 FOR ROUTING OF UNDER FLOOR
TELECOMMUNICATIONS PATHWAYS.
D. SEE SHEETS 14CC-EP503 AND 14CC-EP504 FOR APPLICABLE DETAILS AND SCHEDULES.
E. PROVIDE ALL HARDWARE ACCESSORIES, WHICH MAY INCLUDE, BUT ARE NOT LIMITED TO,
FITTINGS, SUPPORTS, DROPOUTS, SPLICE AND END PLATES, ETC. AS REQUIRED FOR A
COMPLETE CABLE TRAY SYSTEM INSTALLATION.
F. PROVIDE FLEXIBLE METAL CONDUIT TO ENCLOSE TC CABLE FOR FINAL CONNECTION TO
FLOOR BOX. FLEXIBLE RACEWAY MUST NOT EXCEED 3 FEET IN LENGTH.
14GI-E-001 14GI-E-007
14CC-EP112 14CC-EP115
14CC-EP503 14CC-EP504
10/04/2024
Approved By
CAPT Troy Brown, JRM J4 via email
DP-107B DP-107A
UP
P-1
07 SA
BT
-14
CC
SA
BT
-14
CC
UD
P-1
UP
P-1
UD
P-1
PDU-14CC61103A
PDU-14CC61102A
PDU-14CC61101A
PDU-14CC61103B
PDU-14CC61102B
PDU-14CC61101BSWBD-14CC61103B
SWBD-14CC61103A
DP-14CC61106ADP-14CC61106B
ABT-14CC61105
ABT-14CC61106
INVPP-1101
UINV-14CC61101A
UINV-14CC61101B
XF
MR
-14
CC
XF
MR
-14
CC
XF
MR
-14
CC
XFMR-14CC61112
R14CC-1015B
R14CC-1016B
R14CC-1017B
R14CC-1015A
R14CC-1016AR14CC-1017A
R14CC-1021A
R14CC-1027
R14CC-1028
PP-110
R14CC-4508A R14CC-4512A R14CC-4517A
R14CC-1020B
R14CC-1019A
R14CC-1030
ABT-14CC61109
R14CC-1029
R14CC-4504A
R14CC-4504B R14CC-4534A R14CC-4534B
R1 4C
C-
A
R1 4C
C-
R14CC-4519 R14CC-4519
R14CC-4521
R14CC-4517B
R14CC-4512B
R14CC-4508B
R14CC-4504
R14CC-4518A R14CC-4519A R14CC-4520A R14CC-4521A
R14CC-4518B
R14CC-4510A R14CC-4511A
R14CC-4511B R14CC-4510B
R14CC-4521AR14CC-4520AR14CC-4519A
R14CC-4516A
R14CC-4515AR14CC-4509AR14CC-4513A R14CC-4513B
R14CC-4509B
R14CC-4515B
R14CC-4514A
R14CC-4514B
R14CC-4525
R14CC-1019B
R14CC-1019A
A. SEE SHEET 14GI-E-001 THROUGH 14GI-E-007 FOR GENERAL NOTES, ABBREVIATIONS, AND
LEGENDS.
B. SEE SHEETS 14CC-EP112 THROUGH 14CC-EP115 FOR LOCATION OF FLOOR BOXES AND WIRING
DEVICES.
C. SEE SHEETS 14CC-T-111 THROUGH 14CC-T-115 FOR ROUTING OF UNDER FLOOR
TELECOMMUNICATIONS PATHWAYS.
D. SEE SHEETS 14CC-EP503 AND 14CC-EP504 FOR APPLICABLE DETAILS AND SCHEDULES.
E. PROVIDE ALL HARDWARE ACCESSORIES, WHICH MAY INCLUDE, BUT ARE NOT LIMITED TO,
FITTINGS, SUPPORTS, DROPOUTS, SPLICE AND END PLATES, ETC. AS REQUIRED FOR A
COMPLETE CABLE TRAY SYSTEM INSTALLATION.
F. PROVIDE FLEXIBLE METAL CONDUIT TO ENCLOSE TC CABLE FOR FINAL CONNECTION TO
FLOOR BOX. FLEXIBLE RACEWAY MUST NOT EXCEED 3 FEET IN LENGTH.
14GI-E-001 14GI-E-007
14CC-EP112 14CC-EP115
14CC-EP503 14CC-EP504
10/04/2024
Approved By
CAPT Troy Brown, JRM J4 via email
UPP-110 UPP-105 UPP-103PP-104 UPP-102 UPP-101 UPP-104
UINV-14CC61101A
UINV-14CC61101B
ABT-14CC61109
INVPP-1101
A. SEE SHEET 14GI-E-001 THROUGH 14GI-E-007 FOR GENERAL NOTES, ABBREVIATIONS, AND
LEGENDS.
14GI-E-001 14GI-E-007
10/04/2024
Approved By
CAPT Troy Brown, JRM J4 via email
METERING
AND
RELAYING
52-C1A
ABT-14CC61104
52-C5A
UPS-14CC61101A
(RIDETHROUGH)
52-C9A
ABT-14CC61101
52-C13A
ABT-14CC61103
52-C2A
SPARE
52-C6A
UMBC-14CC61102A
(GRACEFUL)
52-C10A
SPARE
52-C14A
SWBD-14CC61103A
PCMS-14CC69101A
AND
CONTROLS
52-CMA
MAIN
SPD SPACE
52-C3A
UMBC-14CC61101A
(RIDETHROUGH)
52-C7A
UPS-14CC61102A
(GRACEFUL)
52-C4A
UPS-14CC61101A
(RIDETHROUGH)
52-C8A
UPS-14CC61102A
(GRACEFUL)
52-C11A
CH-14CC41101
52-C12A
ABT-14CC61102
52-C15A
SPARE
52-C16A
SPARE SPACE SPACE
52-CTA
TIE
PCMS-14CC69101B
AND
CONTROLS
52-C9B
CH-14CC41102
52-C5B
UPS-14CC61102B
(GRACEFUL)
52-C1B
UMBC-14CC61101B
(RIDETHROUGH)
52-C10B
ABT-14CC61102
52-C2B
UPS-14CC61101B
(RIDETHROUGH)
METERING
AND
RELAYING
52-CTB
TIE
SPACE SPACE
52-C16B
ABT-14CC61104
52-C12B
ABT-14CC61103
52-C7B
ABT-14CC61101
SPACE SPACE
52-CMB
MAIN
52-C13B
SPARE
52-C14B
SWBD-14CC61103B
52-C15B
SPARE
52-C11B
SPARE
52-C6B
UPS-14CC61102B
(GRACEFUL)
52-C3B
UPS-14CC61101B
(RIDETHROUGH)
52-C8B
SPARE
52-C4B
UMBC-14CC61102B
(GRACEFUL)
A. SEE SHEET 14CC-GE001 THROUGH 14GI-E-007 FOR GENERAL NOTES, ABBREVIATIONS, AND
LEGENDS.
14GI-E-007
10/04/2024
Approved By
CAPT Troy Brown, JRM J4 via email
TELECOMMUNICATIONS CABLE TRAY (TYP.)
BUSWAY PLUG-IN CIRCUIT
BREAKER UNIT (TYP.)
TYPE MC CABLE WHIP - SIZED PER REU CABLE
SCHEDULE ON SHEET 14CC-EP507 (TYP.)
BUSWAY (TYP.)
REU A303 (TYP.) - BY OTHERS
REAR OF UNIT
A. SEE SHEET 14GI-E-001 THROUGH 14GI-E-007 FOR GENERAL NOTES, ABBREVIATIONS, AND
LEGENDS.
B. SEE SHEET 14CC-EP404 FOR PLUG-IN CIRCUIT BREAKER UNIT ARRANGEMENT, PLACEMENT,
AND AF/AT VALUES ON THE BUSWAYS IN ROOM 130.
C. SEE SHEET 14CC-EP507 FOR REU TYPE MC CABLE WHIP REQUIREMENTS AT EACH PLUG-IN
UNIT LOCATION.
14GI-E-001 14GI-E-007
14CC-EP404
10/04/2024
Approved By
CAPT Troy Brown, JRM J4 via email
XFMR-14CC61101B XFMR-14CC61101A
6' X 4' X 2' NEMA 4X SS
PULL BOX (TYP).
4-INCH FLEXIBLE LIQUIDTIGHT
HALOGEN FREE ALUMINUM METALLIC
CONDUIT WITH MV FEEDER TO
TRANSFORMER (TYP).
4' WIDE X 6" DEEP ALUMINUM CABLE
TRAY (TYP.)
5" CONDUIT DUCTBANK FROM
MANHOLE (TYP).
4" FLEXIBLE LIQUID-TIGHT HALOGEN
FREE ALUMINUM METALLIC CONDUIT
TO 4" ALUMINUM RIGID CONDUIT
TRANSITION (TYP).
(TYP.)
A. SEE SHEET 14GI-E-001 THROUGH 14GI-E-007 FOR GENERAL NOTES, ABBREVIATIONS, AND
LEGENDS.
01. FLEXIBLE CONDUIT IS NOT LASHED TO THE ALUMINUM CABLE TRAY TO ALLOW MOVEMENT OF CONDUIT DURING SEISMIC EVENTS. FLEXIBLE CONDUIT CAN MOVE 2 FEET IN ALL DIRECTONS.
02. LOOP MV FEEDER CABLE WITHIN NEMA 4X SS PULL BOX AND LASH CONDUCTORS TO LIMIT
MOVEMENT WITHIN PULL BOX.
03. ALUMINUM CABLE TRAY IS MOUNTED TO ALUMINUM CHANNEL STRUT WHICH IS ANCHORED TO
THE SIA CONCRETE FLOOR.
04. PROVIDE PVC COATED RIGID ALUMINUM CONDUIT FOR ALL CONDUITS THAT ARE IN-CONTACT
WITH AND PENETRATING THE CONCRETE FLOOR INTO THE SIA. TRANSITION TO RIGID
ALUMINUM CONDUIT FOR THE REST OF THE CONDUIT INSTALLATION.
14GI-E-001 14GI-E-007
10/04/2024
Approved By
CAPT Troy Brown, JRM J4 via email
XFMR-14CC61101A
4' FLEXIBLE LIQUID-TIGHT HALOGEN FREE
ALUMINUM METALLIC CONDUIT TO 4"
ALUMINUM RIGID CONDUIT TRANSITION (TYP).
4-INCH FLEXIBLE LIQUIDTIGHT HALOGEN-FREE ALUMINUM
METALLIC CONDUIT WITH MV FEEDER TO TRANSFORMER
(TYP).
6' X 4' X 2' NEMA 4X SS
PULL BOX (TYP).
5" CONDUIT DUCTBANK
FROM MANHOLE (TYP)
A. SEE SHEET 14GI-E-001 THROUGH 14GI-E-007 FOR GENERAL NOTES, ABBREVIATIONS, AND
LEGENDS.
01. FLEXIBLE CONDUIT IS NOT LASHED TO THE ALUMINUM CABLE TRAY TO ALLOW MOVEMENT OF CONDUIT DURING SEISMIC EVENTS. FLEXIBLE CONDUIT CAN MOVE 2 FEET IN ALL DIRECTONS.
02. LOOP MV FEEDER CABLE WITHIN NEMA 4X SS PULL BOX AND LASH CONDUCTORS TO LIMIT
MOVEMENT WITHIN PULL BOX.
03. ALUMINUM CABLE TRAY IS MOUNTED TO ALUMINUM CHANNEL STRUT WHICH IS ANCHORED TO
THE SIA CONCRETE FLOOR.
04. PROVIDE PVC COATED RIGID ALUMINUM CONDUIT FOR ALL CONDUITS IN CONTACT WITH AND
PENETRATING THE CONCRETE FLOOR INTO THE SIA. TRANSITION TO RIGID ALUMINUM
CONDUIT FOR THE REST OF THE CONDUIT INSTALLATION.
14GI-E-001 14GI-E-007
10/04/2024
Approved By
CAPT Troy Brown, JRM J4 via email
2" RIGID ALUMINUM
CONDUIT6" X 6" NEMA 4X STAINLESS
STEEL JUNCTION BOX
MOUNTED TO TOWER LEG
6" X 6" NEMA 4X STAINLESS
STEEL JUNCTION BOX
MOUNTED TO TOWER LEG
RF CABLES TO
ANTENNA TOWER
(TYP.)
2" FLEXIBLE LIQUID-TIGHT HALOGEN-FREE ALUMINUM
METALLIC CONDUIT IN RF CABLE TRAY (TYP.)2" RIGID ALUMINUM
CONDUIT
2" FLEXIBLE LIQUID-TIGHT HALOGEN-
FREE ALUMINUM METALLIC CONDUIT
IN RF CABLE TRAY (TYP.)
A. SEE SHEET 14GI-E-001 THROUGH 14GI-E-007 FOR GENERAL NOTES, ABBREVIATIONS, AND
LEGENDS.
01. THREE 2" SCHEDULE 40 PVC CONDUITS FOR POWER REQUIREMENTS AT ANTENNA TOWER.
CONDUITS ARE PART OF THE RF CABLE DUCT BANK TO THE TOWER AND LOCATED ON LEFT
SIDE OF DUCT BANK.
02. PROVIDE TWO SETS OF TWO #8AWG CU XHHW-2 AND #12AWG BARE CU GND IN 2"C FROM
PANEL UDP-14CC61103 (IN ROOM 130) TO RF DUCT BANK LOCATION AT SIA SIDEWALL.
TRANSITION FROM ALUMINUM RIGID CONDUIT TO 2" FLEXIBLE LIQUIDTIGHT HALOGEN-FREE
ALUMINUM METALLIC CONDUIT AND LOOP RACEWAY 10 FOOT AROUND RF CABLE TRAY AT SIA
FLOOR NEAR DUCTBANK. TRANSITION 2' FLEXIBLE CONDUIT TO 2" SCHEDULE 40 PVC CONDUIT
AND CONTINUE CIRCUIT TO ANTENNA TOWER BASE AND TERMINATE IN 6" X 6" NEMA 4X SS
JUNCTION BOX MOUNTED TO TOWER BASE. PROVIDE 12 INCH WHIP OF CONDUCTORS IN
JUNCTION BOX FOR FUTURE CONNECTION BY OTHERS.
03. PROVIDE TWO #10AWG CU XHHW-2 AND #12AWG BARE CU GND IN 2"C FROM PANEL
ELP-14CC61101 (IN ROOM 144) TO RF DUCT BANK LOCATION AT SIA SIDEWALL. TRANSITION
FROM ALUMINUM RIGID CONDUIT TO 2" FLEXIBLE LIQUIDTIGHT HALOGEN-FREE ALUMINUM
METALLIC CONDUIT AND LOOP RACEWAY 10 FOOT AROUND RF CABLE TRAY AT SIA FLOOR
NEAR DUCTBANK. TRANSITION 2' FLEXIBLE CONDUIT TO 2" SCHEDULE 40 PVC CONDUIT AND
CONTINUE CIRCUIT TO ANTENNA TOWER BASE AND TERMINATE IN 6" X 6" NEMA 4X SS
JUNCTION BOX MOUNTED TO TOWER BASE. PROVIDE 12 INCH WHIP OF CONDUCTORS IN
JUNCTION BOX FOR FUTURE CONNECTION.
14GI-E-001 14GI-E-007
10/04/2024
Approved By
CAPT Troy Brown, JRM J4 via email
ANTENNA TOWER
RF CONDUITS
(1)-2" SCHEDULE 40 PVC
ANTENNA TOWER
POWER CONDUIT
(1)-2" SCHEDULE 40 PVC
ANTENNA TOWER
LIGHTING CONDUIT
(1)-2" SCHEDULE 40
PVC CONDUIT - SPARE
A. SEE SHEET 14GI-E-001 THROUGH 14GI-E-007 FOR GENERAL NOTES, ABBREVIATIONS, AND
LEGENDS.
01. PROVIDE TWO SETS OF TWO #8AWG CU XHHW-2 AND #12AWG BARE CU GND IN 2"C FROM
PANEL UDP-14CC61103 (IN ROOM 130) TO RF DUCT BANK LOCATION AT SIA SIDEWALL.
TRANSITION FROM ALUMINUM RIGID CONDUIT TO 2" FLEXIBLE LIQUIDTIGHT HALOGEN-FREE
ALUMINUM METALLIC CONDUIT AND LOOP RACEWAY 10 FOOT AROUND RF CABLE TRAY AT SIA
FLOOR NEAR DUCTBANK. TRANSITION 2' FLEXIBLE CONDUIT TO 2" SCHEDULE 40 PVC CONDUIT
AND CONTINUE CIRCUIT TO ANTENNA TOWER BASE AND TERMINATE IN 6" X 6" NEMA 4X SS
JUNCTION BOX MOUNTED TO TOWER BASE. PROVIDE 12 INCH WHIP OF CONDUCTORS IN
JUNCTION BOX FOR FUTURE CONNECTION BY OTHERS.
02. PROVIDE TWO #10AWG CU XHHW-2 AND #12AWG BARE CU GND IN 2"C FROM PANEL
ELP-14CC61101 (IN ROOM 144) TO RF DUCT BANK LOCATION AT SIA SIDEWALL. TRANSITION
FROM ALUMINUM RIGID CONDUIT TO 2" FLEXIBLE LIQUIDTIGHT HALOGEN-FREE ALUMINUM
METALLIC CONDUIT AND LOOP RACEWAY 10 FOOT AROUND RF CABLE TRAY AT SIA FLOOR
NEAR DUCTBANK. TRANSITION 2' FLEXIBLE CONDUIT TO 2" SCHEDULE 40 PVC CONDUIT AND
CONTINUE CIRCUIT TO ANTENNA TOWER BASE AND TERMINATE IN 6" X 6" NEMA 4X SS
JUNCTION BOX MOUNTED TO TOWER BASE. PROVIDE 12 INCH WHIP OF CONDUCTORS IN
JUNCTION BOX FOR FUTURE CONNECTION.
14GI-E-001 14GI-E-007
10/04/2024
Approved By
CAPT Troy Brown, JRM J4 via email
UPP-111:26
UPP-111:11 UPP-111:28
UPP-111:31 UPP-111:30
UPP-111:25UPP-111:33
UPP-111:29
UPP-106:22
UPP-106:22 UPP-106:22
UPP-106:22
UPP-106:22
UPP-106:23
UPP-106:23UPP-106:23
UPP-106:23
UPP-106:23
UPP-111:20
UPP-111:22
UPP-106:8
UPP-106:8
UPP-106:8UPP-106:8
UPP-111:15 UPP-111:23
UPP-111:14 UPP-111:17
UPP-111:16 UPP-111:8
UPP-111:6
UPP-111:19
UPP-111:21
UPP-111:18 UPP-111:10
UPP-106:21
UPP-106:21
UPP-106:21UPP-106:21
UPP-106:21
UPP-106:8
UPP-106:10 UPP-106:10
UPP-106:10
UPP-106:10 UPP-106:10
UPP-112:14 UPP-112:15 UPP-112:23 UPP-112:10
UPP-112:13
UPP-112:18
UPP-106:9
UPP-106:9
UPP-106:9
UPP-106:6
UPP-106:6 UPP-111:3
UPP-106:13
UPP-106:6
UPP-106:13
UPP-106:13UPP-106:13UPP-106:13
UPP-106:7
UPP-106:6
UPP-106:7
UPP-106:7
UPP-106:7
VAV-14CC41122B
VAV-14CC41122A UPP-112:9UPP-112:17
UPP-106:30,32,34
UPP-101A:9,11,13
UPP-101B:3,5,7
UPP-106:12
UPP-106:12
UPP-106:12
RF-14CC61101B
RF-14CC61101AUPP-106:11
UPP-101B:2
UPP-101A:1
UPP-106:1
UPP-106:11
UPP-14CC61111
UPP-14CC61106
UPP-14CC61101A
UPP-14CC61101B
UPP-111:4 UPP-111:9 UPP-111:5
UPP-106:2
UPP-106:2
UPP-106:2
UPP-106:2UPP-106:2
UPP-106:2
UPP-106:2
UPP-111:2
VAV-14CC41130 VAV-14CC41129
VAV-14CC41118 VAV-14CC41119
VAV-14CC41120 UPP-106:9
UPP-106:2
BCS-14CC65011
UPP-112:4 UPP-112:8
UPP-112:1UPP-112:5
UPP-112:12
VAV-14CC41121
UPP-112:11
VAV-14CC41131
UPP-112:3
A9 A8 A7 A6 A5 A4A10 A3 A2 A1
B9 B8 B7 B6 B5 B4 B3 B2
B1
SABT-14CC61102BUSWAY (TYP.)
BUSWAY A
BUSWAY B
BUSWAY AV
UPP-112:2
UPP-112:6
UPP-111:7
UPP-106:10 UPP-106:7
UPP-106:11
UPP-106:11
UPP-106:12 UPP-106:12
UPP-106:15,17
UPP-111:1
WS-154-01
WS-154-02
WS-154-03
WS-154-08
WS-154-07
WS-154-06
WS-154-05
WS-154-04 WS-154-09
WS-154-10
WS-154-11
WS-154-12
WS-154-13 WS-153-05
WS-153-04
WS-153-03
WS-153-02
WS-153-06
WS-153-07
WS-153-08
WS-153-09
WS-153-10 WS-153-13
WS-153-12
WS-153-11
UPP-106:7
UPP-112:19 UPP-112:20 UPP-112:16 UPP-112:24 UPP-112:29 UPP-112:21 UPP-112:7 UPP-112:25
UPP-14CC61112
UPP-111:12 UPP-111:35 UPP-111:27UPP-111:13
WS-150-01 WS-150-02 WS-150-03
UPP-111:24
WS-153-01
UPP-106:33
UPP-106:25
UPP-106:20 UPP-106:20
UPP-106:25
UPP-106:20
UPP-106:19
UPP-106:19
UPP-106:19
A. SEE SHEET 14GI-E-001 THROUGH 14GI-E-007 FOR GENERAL NOTES, ABBREVIATIONS, AND
LEGENDS.
B. CIRCUITING TAGS SHOWN ON PLANS ARE SHORTENED FOR SPACING AND LEGIBILITY AS
FOLLOWS: (PANEL TYPE)-14CC61(PANEL TAG NUMBER):(CIRCUIT NUMBER) IS SHORTENED TO
(PANEL TYPE)-(PANEL TAG NUMBER):(CIRCUIT NUMBER). EXAMPLE: CIRCUIT TAG
PP-14CC61102:10 IS SHOWN ON PLANS AS PP-102:10.
C. ELECTRICAL DEVICES AND RACEWAY ALONG THE PERIMETER ARE TO BE SURFACE-MOUNTED
FOR INSPECTION PURPOSES AND TO AVOID DAMAGE OF THE RF-SHIELD.
D. UTILITIES SERVICING AREAS OTHER THAN THE SUS SPACE MUST NOT TRANSIT THE SECURE
BOUNDARY 3 SPACE VOLUME UNLESS MITIGATED WITH AO APPROVAL.
E. REFER TO INTERIOR SHEET 14CC-IF108 FOR EXACT WORKSTATION FLOOR BOX LOCATIONS.
F. ELECTRICAL UTILITIES MUST ENTER THE SUS SPACE VOLUME AT A SINGLE POINT.
G. ALL METALLIC CONDUIT PENETRATIONS AT THE SECURE BOUNDARY PERIMETER MUST BE
SEALED WITH AN ACOUSTICAL FOAM OR SEALANT FINISH TO MITIGATE ACOUSTIC EMANATIONS
IN ACCORDANCE WITH ICD-705.
01. REFER TO DETAILS OF SHEET EP502 FOR INTERIOR STC RATED WALL CONDUIT
PENETRATION DETAIL AND WALL MOUNTED RF FILTER DETAILS.
02. INSTALL RECEPTACLES FOR IESS CABINET, COORDINATE FINAL RECEPTACLE LOCATION
WITH CABINET LOCATION. REFER TO SECURITY DRAWINGS FOR ADDITIONAL INFORMATION.
03. MOUNT CONVENIENCE RECEPTACLES AROUND ROOM AT 6 INCHES AFF UNLESS
OTHERWISE NOTED.
14GI-E-001 14GI-E-007
10/04/2024
Approved By
CAPT Troy Brown, JRM J4 via email
VAV-14CC41114E
REU-A205
REU-A201
REU-A202REU-A204
REU-A203
UPP-101:5
UPP-101:5
UPP-101:5UPP-101:5UPP-101:5 UPP-101:3UPP-101:3UPP-101:15UPP-101:15
UPP-101:8 UPP-101:8
UPP-101:9
UPP-101:9
UPP-101:9
UPP-101:9 UPP-101:9 UPP-101:9
UPP-101:9
UPP-101:6
UPP-101:4
UPP-101:2
UPP-101:11
UPP-110:9,11
UPP-110:1,3UPP-110:5,7
UPP-110:6,8 UPP-110:2,4
UPP-101:12
UPP-101:10
UPP-101:7
PP-110:21
UPP-101:13
UPP-101:13
UPP-101:1
UPP-101:1
UPP-101:17UPP-101:17
INVPP-1101:5,7 INVPP-1101:6,8
INVPP-1101:10,12INVPP-1101:9,11
TYP
WS-141-01
WS-141-02
WS-141-03
WS-141-04
WS-141-05
WS-141-06
WS-141-07
WS-141-08
WS-141-09
WS-141-10
WS-141-11
WS-141-12
WS-141-13 WS-141-14
WS-141-15
WS-141-16
WS-141-18
WS-141-19
WS-141-21
WS-141-22
WS-141-23
WS-141-24
WS-141-25
WS-141-26
WS-141-27
WS-141-28
WS-141-29
WS-141-30
WS-141-31
WS-141-32
WS-141-33
WS-141-34
WS-141-35
WS-141-36
WS-141-37
WS-141-38
WS-141-39WS-141-40
WS-140-01 WS-140-02 WS-140-03 WS-140-04 WS-140-05
WS-140-06
WS-140-07
WS-140-08
WS-140-09
WS-140-10
WS-140-11
WS-140-12
WS-140-13
WS-140-14WS-140-15WS-140-16WS-140-17WS-140-18
WS-140-28 WS-140-27 WS-140-26
WS-140-25
WS-140-24
WS-140-23
WS-140-22
WS-140-21WS-140-20WS-140-19
UPP-102:15
UPP-102:16
UPP-102:24
UPP-102:25
UPP-102:27
UPP-102:28UPP-102:17
UPP-102:18
UPP-102:19
UPP-102:20
UPP-102:21
UPP-102:22
UPP-102:29
UPP-102:30
UPP-102:31
UPP-102:32
UPP-104:27 UPP-104:22
UPP-104:25
UPP-104:20
UPP-104:11
UPP-104:6
UPP-104:9
UPP-104:4
UPP-104:7UPP-104:2
UPP-104:23
UPP-104:18
UPP-104:21
UPP-104:16
UPP-104:19
UPP-104:14 UPP-104:8
UPP-104:13
UPP-104:10
UPP-104:15
UPP-104:12
UPP-104:17
UPP-103:18 UPP-103:17 UPP-103:16 UPP-103:15
UPP-101:14 UPP-101:16 UPP-101:18 UPP-101:19 UPP-101:20
UPP-101:21
UPP-101:22
UPP-101:23
UPP-101:24
UPP-101:25
UPP-101:26
UPP-101:27
UPP-103:14
UPP-103:13
UPP-103:12
UPP-103:11UPP-103:10UPP-103:9
UPP-101:28
UPP-101:29UPP-101:30UPP-101:31UPP-101:32UPP-101:33
UPP-101:34
UPP-102:23
WS-141-17
UPP-102:26
WS-141-20
A. SEE SHEET 14GI-E-001 THROUGH 14GI-E-007 FOR GENERAL NOTES, ABBREVIATIONS, AND
LEGENDS.
B. CIRCUITING TAGS SHOWN ON PLANS ARE SHORTENED FOR SPACING AND LEGIBILITY AS
FOLLOWS: (PANEL TYPE)-14CC61(PANEL TAG NUMBER):(CIRCUIT NUMBER) IS SHORTENED TO
(PANEL TYPE)-(PANEL TAG NUMBER):(CIRCUIT NUMBER). EXAMPLE: CIRCUIT TAG
PP-14CC61102:10 IS SHOWN ON PLANS AS PP-102:10.
C. REFER TO AV PLANS FOR AV EQUIPMENT POWER REQUIREMENTS AND RECEPTACLE
MOUNTING HEIGHTS.
D. REFER TO INTERIOR SHEET 14CC-IF108 FOR EXACT WORKSTATION FLOOR BOX LOCATIONS.
01. REFER TO 14CC-EP761 FOR SIZE AND TYPE OF REU CABLE. CABLE LENGTH WILL BE 20 FEET
FOR FURTHER CONNECTION BY OTHERS. CABLE WILL BE COILED AND TIED BELOW RAISED
FLOOR NEAR ASSOCIATED JUNCTION BOX FOR INSTALLATION BY OTHERS.
14GI-E-001 14GI-E-007
14CC-EP761
10/04/2024
Approved By
CAPT Troy Brown, JRM J4 via email
XFMR-14CC61103
XFMR-14CC61104
PP-14CC61111
PP-14CC61102
XFMR-14CC61111
LP-14CC61102
ELP-14CC61102
PP-14CC61103
UPP-14CC61103B
UPP-14CC61103A
VAV-14CC41108
VAV-14CC41107
PP-102:3
PP-102:3
GFCI
GFCI
PP-102:13
PP-102:13
PP-102:13
PP-102:13
PP-102:29
PP-102:29
PP-102:29
UPP-103B:22
PP-102:32
PP-102:32
WH-14CC12104
PP-111:22,24,26
UPP-14CC61102B
UPP-14CC61102A
DP-14CC61108
XFMR-14CC61103B
XFMR-14CC61103A
UPP-103A:1 UPP-103A:8
UPP-103B:13,15
UPP-103B:5
UPP-103A:4,6
UPP-103B:1
UPP-103A:2 UPP-103B:2
LC-14CC61102
UPP-104A:9
UPP-104B:8
DP-108:13,15,17
UPP-103A:3,5 UPP-103B:8,10
UPP-103B:14,16
UPP-103B:3
UPP-103A:7UPP-103B:7,9UPP-103A:13,15
UPP-103A:12,14
PP-111:21,23,25
BCS-14CC65004
PP-102:29 PP-102:29
PP-102:29
PP-102:32PP-102:32
(TYP.)
PP-102:32
A1
A2
A3
A4 B4
B3
B2
B1 L
LL
L
L L
LL
UPP-105:6
PP-102:33
UPP-103A:16,18
UPP-103A:20
UPP-103B:18,20
PP-104:4
PP-104:4
PP-104:13
PP-104:4
PP-104:14
DP-108:8,10,12
GFCI
PP-104:4
PP-104:10
PP-104:17
PP-104:16
PP-104:19
PP-104:1
PP-104:15
DP-108:7,9,11
PP-104:12
PP-104:11
PP-104:2 PP-104:9
PP-104:9
PP-104:9
PP-111:17
PP-104:9
PP-104:9
PP-104:2
VAV-14CC41115B
VAV-14CC41115A
PP-111:1
PP-104:9
GFCI
GFCI
GFCI
GFCI
GFCI
GFCI
PP-104:26
PP-104:27
A. SEE SHEET 14GI-E-001 THROUGH 14GI-E-007 FOR GENERAL NOTES, ABBREVIATIONS, AND
LEGENDS.
B. CIRCUITING TAGS SHOWN ON PLANS ARE SHORTENED FOR SPACING AND LEGIBILITY AS
FOLLOWS: (PANEL TYPE)-14CC61(PANEL TAG NUMBER):(CIRCUIT NUMBER) IS SHORTENED TO
(PANEL TYPE)-(PANEL TAG NUMBER):(CIRCUIT NUMBER). EXAMPLE: CIRCUIT TAG
PP-14CC61102:10 IS SHOWN ON PLANS AS PP-102:10.
C. REFER TO AV PLANS FOR AV EQUIPMENT POWER REQUIREMENTS AND RECEPTACLE
MOUNTING HEIGHTS.
14GI-E-001 14GI-E-007
10/04/2024
Approved By
CAPT Troy Brown, JRM J4 via email
UPP-14CC61102
UPP-14CC61101
PP-14CC61104
UPP-14CC61103
UPP-14CC61110
UPP-14CC61105
UPP-14CC61104
PP-104:8
PP-104:8
PP-104:8
PP-104:8
PP-104:8
PP-104:8
PP-104:8
INVPP-14CC61101
UINV-14CC61101A
UINV-14CC61101B
ABT-14CC61109
UPP-103:1,3
PP-104:8
UPP-103:5,7
UPP-103:2,4
UPP-103:6,8
UPP-104:1,3,5
UPP-105:1,3,5
VAV-14CC41126
DP-14CC61107B
DP-14CC61107A
UPP-14CC61107
XFMR-14CC61108
SABT-14CC61103
SABT-14CC61104
UDP-14CC61102 XFMR-14CC61109
UPP-14CC61109
XFMR-14CC61110
UDP-14CC61103
480V 3PH 100A NEMA 1
DISC. SW.
480V 3PH 100A NEMA 1
DISC. SW.
480V 3PH 600A NEMA 1
DISC. SW.
480V 3PH 600A NEMA 1
DISC. SW.
PP-104:3 PP-104:3
PP-104:3
PP-104:5
PP-104:5
PP-104:5
PP-104:5
PP-104:5
PP-104:5
REU-A210
100AF/50AT 100AF/40AT
200AF/175AT
200AF/175AT 200AF/175AT
100AF/50AT
100AF/50AT
100AF/30AT
100AF/40AT
100AF/30AT 100AF/50AT
100AF/40AT
UDP-102:7,9,11
UPP-109:1,3,5
UPP-109:2,4,6
REU-A301REU-A307
SPARE REU SPARE REU SPARE REU
REU-A306 REU-A212 REU-A211
REU-A215REU-A216REU-A305
REU-A308 REU-A214 REU-A213
REU-A302 REU-A207 REU-A206
REU-A304 REU-A209 REU-A208
REU-A303 REU-L202 REU-L201
100AF/40AT
UDP-102:1,3,5
UDP-102:2,4,6
INVPP-1101:1,3
INVPP-1101:2,4
TYP
UPP-109:7,9,11
UPP-109:8,10,12
100AF/20AT
200AF/175AT
200AF/175AT
200AF/175AT
200AF/175AT
100AF/100AT
200AF/175AT200AF/175AT
100AF/50AT
100AF/30AT
DP-107A:13,15,17
DP-107A:2,4,6
DP-107A:8,10,12
DP-107A:7,9,11
DP-107B:11,13,15
DP-107B:5,7,9
DP-107B:2,4,6
DP-107B:14,16,18
DP-107A:1,3,5
100AF/50AT
PP-111:13
PP-104:5
BUS-14CC61102
DP-107B:8,10,12
UPP-104A:10
UPP-104B:9
BCS-14CC65009
CRAC-14CC41101
CRAC-14CC41102
CRAC-14CC41103
CRAC-14CC41104
EF-14CC41106
100AF/100AT
100AF/20AT
TYP
CRAC-14CC41105
GFDP-14CC61101
1SP-CONV 1SP-RELAY
UPP-107:7,9
UPP-107:2,4
BUS-14CC61101
UPP-105:9
UDP-103:11,13
UPP-105:9
DP-107B
VFD
DP-102:21,23,25
A. SEE SHEET 14GI-E-001 THROUGH 14GI-E-007 FOR GENERAL NOTES, ABBREVIATIONS, AND
LEGENDS.
B. CIRCUITING TAGS SHOWN ON PLANS ARE SHORTENED FOR SPACING AND LEGIBILITY AS
FOLLOWS: (PANEL TYPE)-14CC61(PANEL TAG NUMBER):(CIRCUIT NUMBER) IS SHORTENED TO
(PANEL TYPE)-(PANEL TAG NUMBER):(CIRCUIT NUMBER). EXAMPLE: CIRCUIT TAG
PP-14CC61102:10 IS SHOWN ON PLANS AS PP-102:10.
C. SEE SHEET 14CC-EP761 FOR REU BUSWAY PLUG-IN TYPE MC CABLE SCHEDULE.
D. SEE SHEETS 14CC-EP701 THROUGH 14CC-EP723 FOR PANELBOARD/BUSWAY SCHEDULES.
E. ALL RECEPTACLES ON PRE-CAST WALLS MUST BE SURFACE MOUNTED.
01. FEED AND ROUTE JUNCTION BOX FEEDS TO REU'S OVERHEAD.
02. CAP BUSWAY TEE FOR FUTURE EXPANSION.
03. REFER TO 14CC-EP761 FOR SIZE AND TYPE OF REU CABLE. CABLE LENGTH WILL BE 20
FEET FOR FURTHER CONNECTION BY OTHERS. COIL AND TIE CABLE NEAR CIRCUIT
BREAKER.
14GI-E-001 14GI-E-007
14CC-EP701
14CC-EP761
14CC-EP761
14CC-EP723
10/04/2024
Approved By
CAPT Troy Brown, JRM J4 via email
XFMR-14CC61102B
1200kW BATT JB
400kW BATT JB
UPS-14CC61101B
UMBC-14CC61102B 400kW
MAINT BYP
UPS-14CC61102B
UMBC-14CC61101B 1200kW MAINT
BYP
ABT-14CC61104
EF-14CC41102
EEWS-14CC12102
RAH-14CC41102B
USWBD-14CC61101B
PP-105:5
PP-105:5
PP
-10
5:5
PP-105:5
PP-105:5
PP-105:5
PP-105:3
PP-105:3
PP-105:3PP-105:3
UDP-14CC61101B
NEMA 1 480V 200A DISC
SWITCH
PP-14CC61105
XFMR-14CC61107
PDU-14CC61101A
XFMR-14CC61105
XFMR-14CC61102A
EF-14CC41104
PP-105:1
LVS-14CC61101B
PCMS-14CC69001B
FRCS CABINET B
CC-14CC63001B
BC-14CC61101B
DCP-14CC61101B
BATT-14CC61103B
UPP-104A:7
UPP-104B:7
XFMR-14CC61104B
UPP-14CC61104B
SWBD-14CC61103B:14
SWBD-14CC61103B:15
OPTION ITEM #4
OPTION ITEM #4
BATT-14CC61101B-3
BATT-14CC61101B-2
BATT-14CC61101B-1
BATT-14CC61101B-4
BATT-14CC61101B-5
BATT-14CC61102B-3
BATT-14CC61102B-2
BATT-14CC61102B-1
UPP-104A:12
UPP-104B:11
UPP-104A:17
UPP-104B:16
TP-14CC12103
PP-105:2
TP-14CC12106
PP-105:4
RAH-14CC41101B
UPP-105:13 UPP-105:12
EF-14CC41103
VFD
VFD
VFD
PP-110:13,15
PP-110:16,18
PP-110:17,19
A. SEE SHEET 14GI-E-001 THROUGH 14GI-E-007 FOR GENERAL NOTES, ABBREVIATIONS, AND
LEGENDS.
B. CIRCUITING TAGS SHOWN ON PLANS ARE SHORTENED FOR SPACING AND LEGIBILITY AS
FOLLOWS: (PANEL TYPE)-14CC61(PANEL TAG NUMBER):(CIRCUIT NUMBER) IS SHORTENED TO
(PANEL TYPE)-(PANEL TAG NUMBER):(CIRCUIT NUMBER). EXAMPLE: CIRCUIT TAG
PP-14CC61102:10 IS SHOWN ON PLANS AS PP-102:10.
C. PROVIDE SEISMIC BRACING FOR SWITCHGEAR, SWITCHBOARDS, MAINTENANCE BYPASS
CABINETS, TRANSFORMERS, PANELBOARDS, ABT, SABT, PDU, UPS, BATTERY CABINETS, AND
OTHER ELECTRICAL EQUIPMENT CALLED OUT IN SEISMIC PROTECTION FOR ELECTRICAL
EQUIPMENT SPECIFICATION 26 05 48.00 14.
01. OPTION ITEM #4:
PROVIDE UPS SYSTEMS UPS-14CC61101B AND UPS-14CC61102B INCLUDING RELATED BATTERY
RACKS AND FEEDERS. REFER TO SHEETS 14CC-EP605, 14CC-EP606 AND 14CC-EP607 FOR
ADDITIONAL OPTION ITEM DETAILS.
02. PROVIDE 120V 20A POWER CONNECTION FOR TRAP PRIMER.
03. PROVIDE 120V 1PH POWER CONNECTION FOR SECURITY DIB BOX.
04. PROVIDE EPO BUTTON FOR EACH UPS SYSTEM. REFER TO SPECIFICATION 26 33 53.00 14 FOR
EPO BUTTON DETAILS.
14GI-E-001 14GI-E-007
14CC-EP605 14CC-EP60714CC-EP606
10/04/2024
Approved By
CAPT Troy Brown, JRM J4 via email
XFMR-14CC61102
LP-14CC61101
UMBC-14CC61102A 400kW
MAINT BYP
UMBC-14CC61101A 1200kW MAINT
BYP
400kW BATT JB
1200kW BATT JB
DP-14CC61102
UDP-14CC61101
SABT-14CC61101
ABT-14CC61101
UPS-14CC61101A
BATT-14CC61102A-3
BATT-14CC61102A-2
BATT-14CC61102A-1
DP-14CC61101
EEWS-14CC12101
PP-14CC61101
UPS-14CC61102A
XFMR-14CC61106
RAH-14CC41102A RAH-14CC41101A
ELP-14CC61101
USWBD-14CC61101A
XFMR-14CC61101
EUPS-14CC61101
BATT-14CC61101
ABT-14CC61102
ABT-14CC61103
PP-101:3
PP-101:3
PP-101:3
PP-101:3
PP-101:3
PP-101:5
PP-101:5
PP-101:5
PP-101:5
PP-101:5
PP-101:5
UDP-14CC61101A
LC-14CC61101
PP-101:1
UPP-14CC61104A
XFMR-14CC61104A
PCMS-14CC69001A
BC-14CC61101A
DCP-14CC61101A
BATT-14CC61103A
STCP-14CC61101
UPP-104A:6
UPP-104B:6
LVS-14CC61101A
SWBD-14CC61103A:15SWBD-14CC61103A:14
FAPP-14CC61101
BATT-14CC61101A-1
BATT-14CC61101A-2
BATT-14CC61101A-3
BATT-14CC61101A-4
BATT-14CC61101A-5
FRCS CABINET A
CC-14CC63001A
UPP-104A:11
UPP-104B:10
UPP-104A:16
UPP-104B:15
TP-14CC12107
TP-14CC12104
PP-101:4
PP-101:2
UPP-105:10UPP-105:12
UPP-105:12
UPP-105:10
PP-101:6
FUTURE DATA
ACQUISITION UNIT
FOR SEISMIC
MONITORING SYSTEM
A. SEE SHEET 14GI-E-001 THROUGH 14GI-E-007 FOR GENERAL NOTES, ABBREVIATIONS, AND
LEGENDS.
B. CIRCUITING TAGS SHOWN ON PLANS ARE SHORTENED FOR SPACING AND LEGIBILITY AS
FOLLOWS: (PANEL TYPE)-14CC61(PANEL TAG NUMBER):(CIRCUIT NUMBER) IS SHORTENED TO
(PANEL TYPE)-(PANEL TAG NUMBER):(CIRCUIT NUMBER). EXAMPLE: CIRCUIT TAG
PP-14CC61102:10 IS SHOWN ON PLANS AS PP-102:10.
C. PROVIDE SEISMIC BRACING FOR SWITCHGEAR, SWITCHBOARDS, MAINTENANCE BYPASS
CABINETS, TRANSFORMERS, PANELBOARDS, ABT, SABT, PDU, UPS, BATTERY CABINETS, AND
OTHER ELECTRICAL EQUIPMENT CALLED OUT IN SEISMIC PROTECTION FOR ELECTRICAL
EQUIPMENT SPECIFICATION 26 05 48.00 14.
01. PROVIDE 120V 1PH POWER CONNECTION FOR SECURITY DIB BOX.
02. PROVIDE EPO BUTTON FOR EACH UPS SYSTEM. REFER TO SPECIFICATION 26 33 53.00 14 FOR
EPO BUTTON DETAILS.
03. PROVIDE AND INSTALL (2)-3" PVC COATED RIGID ALUMINUM CONDUITS FOR FUTURE SEISMIC
MONITORING SYSTEM. CONDUITS MUST BE CAPPED AND STUBBED UP MINIMUM 6" ABOVE
FINISHED FLOOR AND MINIMUM 6" INTO SIA AREA. REFER TO STRUCTURAL SHEET 14CC-S-204
FOR ADDITIONAL SEISMIC MONITORING SYSTEM CONDUIT PENETRATIONS.
14GI-E-001 14GI-E-007
10/04/2024
Approved By
CAPT Troy Brown, JRM J4 via email
XFMR-14CC61101B XFMR-14CC61101A
WP/GFCI WP/GFCI
PP-110:3 PP-110:3
LVS-101A:52-C11A
CH-14CC41101
PP-110:3
WP/GFCI
UPP-105:14
TPR-ATPR-B
CH-14CC41102 CH-14CC41103 CH-14CC41104
LVS-101A:52-CB VIA
ABT-104
LVS-14CC61101B:9
LVS-101A:52-C13A VIA
ABT-103
PP-110:3 PP-110:5 PP-110:5
WP/GFCIWP/GFCI WP/GFCI
UPP-105:14
A. SEE SHEET 14GI-E-001 THROUGH 14GI-E-007 FOR GENERAL NOTES, ABBREVIATIONS, AND
LEGENDS.
B. CIRCUITING TAGS SHOWN ON PLANS ARE SHORTENED FOR SPACING AND LEGIBILITY AS
FOLLOWS: (PANEL TYPE)-14CC61(PANEL TAG NUMBER):(CIRCUIT NUMBER) IS SHORTENED TO
(PANEL TYPE)-(PANEL TAG NUMBER):(CIRCUIT NUMBER). EXAMPLE: CIRCUIT TAG
PP-14CC61102:10 IS SHOWN ON PLANS AS PP-102:10.
01. DISCONNECT SWITCHES FOR LOAD BANK. ONE 600A DISCONNECT SWITCH
FOR GRACEFUL SHUTDOWN LOAD BANK, ONE 2000A DISCONNECT SWITCH
FOR RIDE-THROUGH LOAD BANK.
02. PROVIDE 120V 1PH POWER CONNECTION FOR SECURITY DIB BOX.
14GI-E-001 14GI-E-007
10/04/2024
Approved By
CAPT Troy Brown, JRM J4 via email
ABT-14CC61105
ABT-14CC61106
SWBD-14CC61103A
SWBD-14CC61103B
PP-14CC61110
CHWP-14CC41101
CHWP-14CC41102
AHU-14CC41102 AHU-14CC41103
EWU-14CC41101
VAV-14CC41124
XFMR-14CC61112
BP-14CC12101A
BP-14CC12101B
VAV-14CC41128
CAV-14CC41127
CHWP-14CC41103
AHU-14CC41101
PP-110:4
PP-110:4 PP-110:4
PP-110:4
PP-110:6
PP-110:6 PP-110:6PP-110:6
PP-110:6
PP-110:4
CSF-14CC41101 PP-110:8
SWBD-14CC61103A:3
SWBD-14CC61103B:3
SWBD-14CC61103A:5 VIA
ABT-14CC61106
PP-110:11
PP-110:7
VFD VFD VFD
SWBD-103ASWBD-103ASWBD-103A & B VIA
ABT-14CC61106
ABT-14CC61107ABT-14CC61108
BCS-14CC65008
BCS-14CC65004
(CH-14CC41104)
BCS-14CC65003
(CH-14CC41103)
BCS-14CC65002
(CH-14CC41102)
BCS-14CC65001
(CH-14CC41101)
UPP-104B:1
UPP-104B:2
UPP-104B:3
UPP-104B:4
UPP-104A:1
UPP-104A:2
UPP-104A:3
UPP-104A:4
UPP-104A:5
UPP-104B:5
PP-110:2
ET-14CC41102
WS-14CC12101
SWBD-14CC61103A:2
SWBD-14CC61103B:2 SWBD-14CC61103A:2 VIA
ABT-14CC61105
SWBD-14CC61103A:13
SWBD-14CC61103B:13
FAPP-14CC61101:1 FAPP-14CC61101:2
BCS-14CC65005 BCS-14CC65006 BCS-14CC65007
UPP-104A:15
UPP-104B:14
UPP-104A:14
UPP-104B:13
UPP-104A:13
UPP-104B:12
PP-110:20,22,24
CAV-14CC41132
TP-14CC12105
PP-110:25
PP-110:26
UPP-105:8
UPP-105:8
A. SEE SHEET 14GI-E-001 THROUGH 14GI-E-007 FOR GENERAL NOTES, ABBREVIATIONS, AND
LEGENDS.
B. CIRCUITING TAGS SHOWN ON PLANS ARE SHORTENED FOR SPACING AND LEGIBILITY AS
FOLLOWS: (PANEL TYPE)-14CC61(PANEL TAG NUMBER):(CIRCUIT NUMBER) IS SHORTENED TO
(PANEL TYPE)-(PANEL TAG NUMBER):(CIRCUIT NUMBER). EXAMPLE: CIRCUIT TAG
PP-14CC61102:10 IS SHOWN ON PLANS AS PP-102:10.
01. PROVIDE 120V 20A POWER CONNECTION FOR TRAP PRIMER.
02. PROVIDE 120V 1PH POWER CONNECTION FOR SECURITY DIB BOX.
14GI-E-001 14GI-E-007
10/04/2024
Approved By
CAPT Troy Brown, JRM J4 via email
CRAC-14CC41113 CRAC-14CC41112
CRAC-14CC41110
CRAC-14CC41109
CRAC-14CC41108
CRAC-14CC41106 CRAC-14CC41107
PDU-14CC61101B
PDU-14CC61102B
PDU-14CC61103B
DP-14CC61106A
DP-14CC61106B
VAV-14CC41125
CRAC-14CC41111
FUTURE UNIT #2
FUTURE UNIT #1
PP-104:20
PP-104:20
PP-104:21
PP-104:21PP-104:21
PP-104:20
PDU-14CC61101A
PDU-14CC61102A
PDU-14CC61103A
DP-106A:20,22,24 DP-106B:20,22,24 DP-106A:19,21,23 DP-106B:19,21,23 DP-106A:14,16,18 DP-106B:14,16,18
DP-106B:13,15,17
DP-106A:13,15,17
DP-106B:8,10,12
DP-106A:8,10,12
DP-106B:7,9,11
DP-106A:7,9,11
DP-106B:1,3,5DP-106A:1,3,5DP-106B:2,4,6DP-106A:2,4,6
PP-110:23
PP-104:20 PP-104:20
PP-104:21 PP-104:21
PP-104:21
PP-104:20
AA9
AA8
AA7
AA6
AA5
AA4
AA3
AA2
AA1 AB1
AB2
AB3
AB4
AB5
AB6
AB7
AB8
AB9
AB10
AB11 AC9
AC8
AC7
AC6
AC5
AC4
AC3
AC2
AC1 AD1
AD2
AD3
AD4
AD6
AD5
AD8
AD7
AD9
AD11
AD10
AE11
AE10
AE9
AE8
AE7
AE6
AE5
AE4
AE3
AE2
AE1
BA1
BA2
BA3
BA4
BA5
BA6
BA7
BA8
BA9
BA10
BB1
BB2
BB3
BB4
BB5
BB6
BB7
BB8
BB9
BB10
BB11
BB12 BC12
BC11
BC10
BC9
BC8
BC7
BC5
BC6
BC4
BC3
BC2
BC1 BD1
BD2
BD3
BD4
BD5
BD6
BD7
BD8
BD9
BD10
BD11
BD12
BE1
BE2
BE3
BE4
BE5
BE6
BE7
BE8
BE9
BE10
BE11
BE12
TYP.
EF-14CC41105
100AF/40AT
100AF/40AT
100AF/40AT
100AF/40AT
100AF/40AT
100AF/40AT
TYP.
BA11
UPP-105:11 PP-104:24
PP-104:24
PP-104:24
VFD
DP-102:18,20,22
A. SEE SHEET 14GI-E-001 THROUGH 14GI-E-007 FOR GENERAL NOTES, ABBREVIATIONS, AND
LEGENDS.
B. CIRCUITING TAGS SHOWN ON PLANS ARE SHORTENED FOR SPACING AND LEGIBILITY AS
FOLLOWS: (PANEL TYPE)-14CC61(PANEL TAG NUMBER):(CIRCUIT NUMBER) IS SHORTENED TO
(PANEL TYPE)-(PANEL TAG NUMBER):(CIRCUIT NUMBER). EXAMPLE: CIRCUIT TAG
PP-14CC61102:10 IS SHOWN ON PLANS AS PP-102:10.
01. GFGI RACKS.
02. SIX THREE PHASE CIRCUIT BREAKER BUSWAY PLUG-INS FOR DISA RECTIFIER RACK AC1.
EACH PLUG IN MUST HAVE A 20-FOOT 4C #8AWG W/#10 GND CU TYPE MC CABLE WHIP FOR
FUTURE CONNECTION BY OTHERS. COIL WHIP AT EACH PLUG-IN LOCATION.
03. PROVIDE 120V 1PH POWER CONNECTION FOR SECURITY DIB BOX.
14GI-E-001 14GI-E-007
10/04/2024
Approved By
CAPT Troy Brown, JRM J4 via email
VAV-14CC41112
VAV-14CC41113
VAV-14CC41114A
PP-111:11
PP-111:27,29,31
PP-111:2
UPP-102:6 UPP-102:6
UPP-102:6
UPP-102:6
UPP-102:6
UP
P-1
:6
UP
P-1
:7
UPP-102:7
UPP-102:7
UPP-102:7
UPP-102:7
UPP-102:7
REU-A217
C…
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .